Series 2, 3, 4, & 5 Aluminum - Straight Sections
Series 2, 3, 4, & 5 Aluminum
Eaton I-1 B-Line series Cable Tray Systems
Series 2, 3, 4, & 5 Aluminum - Straight Sections
3" NEMA VE 1 Loading Depth
4" Side Rail Height
Straight Section Part Numbering
Prefix
Example: 24 A 09 - 24 - 144
Series Material *Type *Width Length
A = Aluminum Ladder- 06 = 6" ¨ 144 = 12 ft.
¡
24 24
06 = 6" rung spacing 09 = 9" 120 = 10 ft.
09 = 9" rung spacing 12 = 12" ¨ 240 = 20 ft.
¡
H24 H24
12 = 12" rung spacing 18 = 18" 144 = 12 ft.
24 = 24" ¨ 240 = 20 ft.
¡
34 34
30 = 30" 144 = 12 ft.
36 = 36"
¨Primary
Trough-
Length.
¡Secondary
6" thru 36" wide
Length.
VT = Ventilated Trough
Rung ST = Non-Ventilated Trough See page C-23 for
Spacing
explanation of lengths.
Width
(Inside)
For side
Overall Width rail data, see
(Width + 11/2") charts on pages
APP-6 & APP-7
See page APP-1 for additional rung options. *Special sizes available.
Series 2, 3, 4, & 5 Aluminum
Ladder Type Ventilated Trough Non-Ventilated Trough
(Specify Rung Spacing)
Green = Fastest shipped items Black = Normal lead-time items Red = Normally long lead-time items
All dimensions in parentheses are millimeters unless otherwise specified.
Eaton I-3 B-Line series Cable Tray Systems
Series 2, 3, 4, & 5 Aluminum - Straight Sections
3" NEMA VE 1 Loading Depth
4" Side Rail Height
Values are based on simple beam tests per NEMA VE 1 on 36" wide cable tray with rungs spaced on 12" centers. Cable trays will
support without collapse a 200 lb. (90.7 kg) concentrated load over and above published loads. Published load safety factor is 1.5.
To convert 1.5 safety factor to 2.0, multiply the published load by 0.75. To obtain mid-span deflection, multiply a load by the deflection
multiplier. Cable tray must be supported on spans shorter than or equal to the length of the cable tray being installed.
Individual rungs will support without collapse a 200 lb. (90.7 kg) concentrated load applied at the mid-span of the rung, over and above
the NEMA rated cable load with a 1.5 safety factor for highlighted NEMA spans and loads.
B-Line Side Rail NEMA, CSA & UL Span Load Deflection Design Factors Span Load Deflection Design Factors
Series Dimensions Classifications ft lbs/ft Multiplier for Two Rails meters kg/m Multiplier for Two Rails
1.75 NEMA: 16A, 12C 6 487* 0.001 1.8 725* 0.017
CSA: 277 kg/m 3.0m 8 284 0.003 Area = 1.05 in2 2.4 422 0.055 Area = 6.77 cm2
24 3.05
D-3m 10 181 0.008 Sx = 1.34 in3 3.0 270 0.136 Sx = 21.96 cm3
4.12
UL Cross-Sectional 12 126 0.016 Ix = 2.85 in4 3.7 187 0.279 Ix = 118.63 cm4
Area: 1.00 in2 14 93 0.030 4.3 138 0.618
16 71 0.052 4.9 105 0.883
When trays are used in continuous spans, the deflection of the tray is reduced by as much as 50%. Design factors: Ix = Moment
of Inertia, Sx = Section Modulus.
* When using 18" rung spacing, load capacity is limited to 394 lbs/ft (586.27 kg/m) for 30" tray width and 325 lbs/ft (483.6 kg/m) for
36" tray width.
B-Line Side Rail NEMA, CSA & UL Span Load Deflection Design Factors Span Load Deflection Design Factors
Series Dimensions Classifications ft lbs/ft Multiplier for Two Rails meters kg/m Multiplier for Two Rails
1.75 NEMA: 20A 10 225 0.006 3.0 330 0.106
CSA: 84 kg/m 6.1m 12 156 0.013 Area = 1.32 in2 3.7 226 0.222 Area = 8.52 cm2
H24 2.98
D-6m 14 115 0.023 Sx = 1.57 in3 4.3 171 0.400 Sx = 25.73 cm3
4.19
UL Cross-Sectional 16 88 0.040 Ix = 3.69 in4 4.9 129 0.693 Ix = 153.59 cm4
Area: 1.00 in2 18 70 0.064 5.5 103 1.093
20 56 0.098 6.1 83 1.682
When trays are used in continuous spans, the deflection of the tray is reduced by as much as 50%. Design factors: Ix = Moment
of Inertia, Sx = Section Modulus.
B-Line Side Rail NEMA, CSA & UL Span Load Deflection Design Factors Span Load Deflection Design Factors
Series Dimensions Classifications ft lbs/ft Multiplier for Two Rails meters kg/m Multiplier for Two Rails
Series 2, 3, 4, & 5 Aluminum
1.75 NEMA: 20B, 16C 10 320 0.005 3.0 476 0.077
CSA: 112 kg/m 6.0m 12 222 0.009 Area = 1.82 in2 3.7 331 0.160 Area = 11.74 cm2
34 3.08
E-6m 14 163 0.017 Sx = 2.10 in3 4.3 243 0.296 Sx = 34.41 cm3
4.20
UL Cross-Sectional 16 125 0.030 Ix = 4.98 in4 4.9 186 0.505 Ix = 207.28 cm4
Area: 1.50 in2 18 99 0.047 5.5 147 0.810
20 80 0.072 6.1 119 1.234
When trays are used in continuous spans, the deflection of the tray is reduced by as much as 50%. Design factors: Ix = Moment
of Inertia, Sx = Section Modulus.
All dimensions in parentheses are millimeters unless otherwise specified.
B-Line series Cable Tray Systems I-4 Eaton