TRF It A LV 1ph FLT

This document contains information about fault protection settings for a distribution system. It includes the details of a 58.55kA line-to-ground fault at 0.415kV, and settings for the ground overcurrent protection devices including two circuit breakers and a relay. It also lists the device models, sensor types and pickup thresholds used for the ground fault protection scheme.

Uploaded by

PRADEEP T K
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
22 views1 page

TRF It A LV 1ph FLT

This document contains information about fault protection settings for a distribution system. It includes the details of a 58.55kA line-to-ground fault at 0.415kV, and settings for the ground overcurrent protection devices including two circuit breakers and a relay. It also lists the device models, sensor types and pickup thresholds used for the ground fault protection scheme.

Uploaded by

PRADEEP T K
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

Per Unit

.005 .01 .03 .05 .1 .3 .5 1 3 5 10 30 50 100


1K Normalized (shifted) TCC 1K
Line-to-Ground (Sym) fault: 58.55kA @ 0.415kV
Adj Bus: MDB IT A
500 500
Connector: MDB IT A 0G ACB - Lump4
SQOP File: Untitled
300 Data Rev: Base 300

Configuration: Normal
Date: 10-16-2020

100
MDB IT A IC 100
Square-D MICROLOGIC 6.0
Sensor = 4000
50
Ground Pickup = B (640 Amps) 50
Ground Band = 0.2 (I^x)t = OUT
TFR IT A SBEF RELAY - G
58.55 kA @ 0.415 kV OC1
30 30
t1: 0.14 s, t2: 0.2 s
AREVA
P122
CT Ratio 3000:1
Definite Time
10 Pickup = 0.25 (0.002 - 1 xCT Sec) 10
Time Dial = 0.35
MDB IT A 0G ACB 3x = 0.35 s, 5x = 0.35 s, 8x = 0.35 s
5 Square-D MICROLOGIC 6.0 58.55 kA @ 0.415 kV 5

Seconds
Seconds

Sensor = 3200 t1: 0.35 s


3 Ground Pickup = A (500 Amps) 3
Ground Band = 0.1 (I^x)t = OUT
58.55 kA @ 0.415 kV
t1: 0.08 s, t2: 0.14 s

1 1

.5 .5

.3 .3

.1 .1

MDB IT A TFR
IC IT A SBEF RELAY
R
.05 .05
4000 A
.03 .03

100 kA
MDB IT A 0G ACB

.01 3200 A .01


.005 .01 .03 .05 .1 .3 .5 1 3 5 10 30 50 100
150 kA
Per Unit ETAP Star 18.1.1C

Project: EITC data centre Date: 10-16-2020


Location: SAHAMA SN: POWERSYS_1
Contract: Rev: Base
Engineer: AWAIS Fault: Ground(Normalized)
Filename: C:\ETAP 1811\FRIEBERG\EITC data centre.OTI