Per Unit
.005     .01             .03   .05     .1           .3      .5       1            3        5        10          30      50       100
          1K                                                          Normalized (shifted) TCC                                                    1K
                                                                      Line-to-Ground (Sym) fault:   58.55kA @ 0.415kV
                                                                      Adj Bus:                      MDB IT A
          500                                                                                                                                     500
                                                                      Connector:                    MDB IT A 0G ACB - Lump4
                                                                      SQOP File:                    Untitled
          300                                                         Data Rev:                     Base                                          300
                                                                      Configuration:                Normal
                                                                      Date:                         10-16-2020
          100
                                            MDB IT A IC                                                                                           100
                                            Square-D MICROLOGIC 6.0
                                            Sensor = 4000
          50
                                            Ground Pickup = B (640 Amps)                                                                          50
                                            Ground Band = 0.2 (I^x)t = OUT
                                                                                            TFR IT A SBEF RELAY - G
                                            58.55 kA @ 0.415 kV                             OC1
          30                                                                                                                                      30
                                            t1: 0.14 s, t2: 0.2 s
                                                                                            AREVA
                                                                                            P122
                                                                                            CT Ratio 3000:1
                                                                                            Definite Time
          10                                                                                Pickup = 0.25 (0.002 - 1 xCT Sec)                     10
                                                                                            Time Dial = 0.35
                                     MDB IT A 0G ACB                                        3x = 0.35 s, 5x = 0.35 s, 8x = 0.35 s
           5                         Square-D MICROLOGIC 6.0                                58.55 kA @ 0.415 kV                                   5
                                                                                                                                                        Seconds
Seconds
                                     Sensor = 3200                                          t1: 0.35 s
           3                         Ground Pickup = A (500 Amps)                                                                                 3
                                     Ground Band = 0.1 (I^x)t = OUT
                                     58.55 kA @ 0.415 kV
                                     t1: 0.08 s, t2: 0.14 s
           1                                                                                                                                      1
           .5                                                                                                                                     .5
           .3                                                                                                                                     .3
           .1                                                                                                                                     .1
                                  MDB IT A TFR
                                           IC IT A SBEF RELAY
                                 R
          .05                                                                                                                                     .05
                                  4000 A
          .03                                                                                                                                     .03
                     100 kA
                         MDB IT A 0G ACB
          .01               3200 A                                                                                                              .01
            .005     .01             .03   .05     .1           .3      .5       1            3        5        10          30      50       100
                            150 kA
                                                                         Per Unit                                             ETAP Star 18.1.1C
                Project:    EITC data centre                                                        Date:    10-16-2020
                Location:   SAHAMA                                                                  SN:      POWERSYS_1
                Contract:                                                                           Rev:     Base
                Engineer:   AWAIS                                                                   Fault:   Ground(Normalized)
                Filename:   C:\ETAP 1811\FRIEBERG\EITC data centre.OTI