Electrical Specs for Architects

The document provides electrical specifications and general notes for a project. It specifies that all electrical work must comply with Philippine electrical codes and laws. The service voltage is 230V, 60Hz single phase. Branch circuits cannot be loaded over 80% capacity. Conduit sizes are based on inside diameter. Spare circuits shall have conduit stubs inside ceilings. Panelboards must be accessible without obstacles. Wire nuts and solderless connectors shall be used for splicing as appropriate to wire gauge. All equipment must be properly grounded with identified ground wires. Mounting heights for devices are specified. Electrical runs shall be concealed as much as possible with proper junction boxes. All electrical work requires supervision of a licensed professional in accordance with laws.

Uploaded by

flor john
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
42 views1 page

Electrical Specs for Architects

The document provides electrical specifications and general notes for a project. It specifies that all electrical work must comply with Philippine electrical codes and laws. The service voltage is 230V, 60Hz single phase. Branch circuits cannot be loaded over 80% capacity. Conduit sizes are based on inside diameter. Spare circuits shall have conduit stubs inside ceilings. Panelboards must be accessible without obstacles. Wire nuts and solderless connectors shall be used for splicing as appropriate to wire gauge. All equipment must be properly grounded with identified ground wires. Mounting heights for devices are specified. Electrical runs shall be concealed as much as possible with proper junction boxes. All electrical work requires supervision of a licensed professional in accordance with laws.

Uploaded by

flor john
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

ELECTRICAL SPECIFICATIONS

GENERAL NOTES

1. ALL ELECTRICAL WORKS HEREIN SHALL BE EXECUTED IN ACCORDANCE WITH THE 2009 EDITION OF
THE PHILIPPINE ELECTRICAL CODE (PEC), THE NEW ELECTRICAL ENGINEERING LAW (RA 7920),
LAWS AND ORDINANCES OF THE LOCAL GOVERNMENT UNIT AND RULES AND REGULATIONS OF THE
LOCAL ELECTRICAL POWER UTILITY COMPANY.
2. SERVICE VOLTAGE SHALL BE 230 V, 60 Hz, 2-WIRE, SINGLE PHASE.
3. NO BRANCH CIRCUIT CONDUCTORS SHALL BE LOADED MORE THAN 80% OF ITS RATED AMPACITY.
4. ALL CONDUIT SIZES ARE BASED ON INSIDE DIAMETERS.
5. PROVIDE 15mmØ STUB-UP WITH CAP INSIDE CEILING FOR ALL 20 AMP. SPARE BRANCH CIRCUIT ON
FLUSH MOUNTED PANEL BOARD.
6. PANELBOARD SHALL BE READILY ACCESSIBLE, THAT NO OBSTACLE SHOULD BLOCK ACESS TO THE
PANEL.
7.

8.
WIRE NUTS SHALL BE USED FOR SPLICING OF WIRE NOT MORE THAN 8.0 sq.mm. FOR LARGER WIRED
SOLDERLESS CONNECTOR SHALL BE USED INSULATED WITH RUBBER AND PLASTIC TAPES.
ALL ELECTRICAL EQUIPMENT TO BE USED HEREIN SHALL BE EQUIPPED WITH PROPER GROUNDING.
ALL GROUND WIRED SHALL BE PROPERLY IDENTIFIED.
A B C A B C
9. UNLESS OTHERWISE SPECIFIED MOUNTING HEIGHTS SHALL BE MEASURED FROM LINE OF
REFERNECE TO CENTER OF DEVICE AS FOLLOWS: 7600
7600
4500 3100
4500 3100

a. LIGHT CONTROL SWITCH -


1.40m ABOVE FLOOR @ CENTER
b. CONVENIENCE OUTLET -
0.30m ABOVE FLOOR @ CENTER FOR
NON-WEATHER PROOF OUTLET
C. SPECIAL PURPOSE OUTLET - 0.20m ABOVE COUNTER @ CENTER FOR
d. WALL TELEPHONE KITCHEN
e. BELL AND BUZZER - 1.40m ABOVE FLOOR LINE FOR
f. PUSH BUTTON BATHROOMS
DN SERVICE AREA / LAUNDRY
g PANELBOARDS, FIRE ALARM, DN SERVICE AREA / LAUNDRY WP WP
- AS REQUIRED BY EQUIPMENT
CONTROL PANEL CABINETS, - 0.30m ABOVE FLOOR @ CENTER
NON-FUSIBLE DISCONNECT

3
- 2.20m ABOVE FLOOR FINISH
SWITCH. -
-
1.40m ABOVE FLOOR FINISH
1.80m ABOVE FLOOR @ CENTER UNLESS
OTHERWISE REQUIRED BY FIELD
CONDITIONS
3 S 5
10. ELECTRICAL RUN SHALL BE DONE ON THE NEARES DISTANCE POSSIBLE WITH ALL WIRING
INSTALLATION CONCEALED FROM VIEW. PROVIDE JUNCTION BOXED OR PULL BOXES OF PROPER

3000
SIZE ALTHOUGH NOT INDICATED IN THE PLANS.

3000
11. ALL ELECTRICAL WORK SHALL BE DONE UNDER THE IMMEDIATE SUPERVISION OF A DULY LICENSED REF
ELECTRICAL ENGINEER/ PRACTITIONER IN CONFORMANCE WITH RA 7920.
S
S2 S3w
2

6000
2

6000
MATERIAL SPECIFICATIONS
c 1 CABLE
S
S2 S3(abc)

3000
3000
1. ALL WIRING SHALL BE IN RIGID STEEL CODUIT (R.S.C.) FOR SERVICE LINES AND UNPLASTICIZED
POLYVYNIL CHLORIDE, RIGID UP.V.C.).
2. MINIMUM SIZE OF CONDUIT SHALL BE 15mmØ FOR RIGID STEEL CONDUIT (R.S.C) AND 15mmØ FOR
S3w TV
4

UNPLASTICIZED POLYVYNIL CHLORIDE, RIGID (UP.V.C.). c CANOPY

3. UNLESS OTHERWISE SPECIFIED, BRANCH CIRCUIT CONDUCTORS SHALL BE COPPER TYPE THHN,

1
CANOPY
90°C, 600 VOLT INSULATION. 2
h 3
4. THE MINIMUM SIZE OF WIRE SHALL BE 3.5sq.mm. (#12 AWG) FOR POWER AND 2.0sq.mm. (#14 AWG)
FOR LIGHTING.
5. CIRCUIT BREAKERS SHALL BE U.S. MADE "G.E." OR "WESTINGHOUSE" OR JAPAN MADE "FUJI"
BRAND, BUT ONLY ONE BRAND THRU-OUT.
1 OVERHANG CANOPY
a a CANOPY
b b
OVERHANG CANOPY CANOPY
WP
6. ALL CIRCUIT BREAKER FOR LIGHTING AND CONVENIENCE OUTLETS SHALL BE COMMERCIAL UP
UP
BOLT-ON TYPE, 10KAIC FOR BRANCHES AND INDUSTRIAL TYPE 18KAIC FOR MAIN AND MOTORS.
7. GENERAL USE RECEPTACLE SHALL BE RATED 20A, 220 VOLT GROUNDING TYPE PARALLEL SLOTS.
RECEPTACLE USED BY WATER HEATER, ACU & RANGE MUST HAVE GROUND FAULT CIRCUIT
INTERRUPTOR (GFCI).
8. ALL UTILITY, JUNCTION BOZES AND PULL BOXES SHALL BE PVC WITH REQUIRED THICKNESS IN
CONFORMANCE WITH THE LATEST EDITION OF P.E.C.
UP
9. PANELBOARDS AND OVERCURRENT PROTECTION ENCLOSURES SHALL BE NEMA-1 FOR INDOOR UP
USE, UNLESS OTHERWISE SPECIFIED ON PLANS.
10. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND OF APPROVED TYPE FOR THE PURPOSE
AND LOCATION WITH PROPER FITTINGS AND SUPPORT.

LEGEND
ACU LIGHTING LAYOUT POWER LAYOUT
T.V. SCALE: 1:15
SCALE: 1:15
TEL

S1 PP
S2 LP
S3
M

WP

ACU G

R.A. 9266
SECTION 20
Drawings and specifications duly signed, stamped or
saArkitekto TE
D ARCHIT
C
PREPARED: PROJECT TITLE AND LOCATION: APPROVED: SHEET NO.:
E
I
UN

UNITED ARCHITECTS OF THE PHILIPPNES


TS

The Integrated and Accredited Professional Organization of Architects


5
197
OF

sealed, as instruments of service, are the intellectual .


UAP Hotline:+632 888 966 Website:https://www.united-architects.org E PHILIPPINES
TH

CODI A+ESPELETA properties and documents of the architect, whether the


PROPOSED ONE-STOREY
Lot 28, Blk. 6, Imperial Southplains Subd., Layon Ligao City
object for which they are made is executed or not. It shall
FOR YOUR PLANS AND DESIGNS
FRELAN S. BRIMBUELA 8
be unlawful for any person, without the consent of the
PROFESSIONAL ELECTRICAL ENGINEER RESIDENTIAL BUILDING MR. AH VINCENT S. ALLORDE
kray.espeleta@gmail.com 09491153649
arch.janlove@gmail.com 09202987949
architect or author of said documents, to duplicate or to
make copies of said documents for use in the repetition
of and for other projects or buildings, whether partly or
in whole.
GETANARCHITECT PRC NO.:
VALIDITY:
3401
June 30, 2022
PTR NO.: 3478746DATE:
PLACE ISSUED: LIGAOTIN:
Jan. 2, 2020
183-274-752
LOT 02, TUBURAN, LIGAO CITY, ALBAY OWNER E1 9