Chofu Commissioning Guide 1
Chofu Commissioning Guide 1
Commissioning Guide
03/22-V4
Contents
Pre-Commissioning
Pre-Commissioning Checks ........................................................................................................................................................................................ 4
Filling the System with Water ..................................................................................................................................................................................... 4
Heat Pump Controller .................................................................................................................................................................................................... 5
Resetting Errors
Resetting Errors...............................................................................................................................................................................................................19
Additional Information
Additional Information................................................................................................................................................................................................19
03/22-V4
Page: 3 of 19
Pre-Commissioning
Pre-Commissioning Checks
Prior to Filling with water
A: Ensure the heat pump is installed in accordance with the installation manual.
B: Ensure the power is isolated to the unit.
C: Remove the side cover of the unit to expose the water pump, compressor and electrical enclosure.
D: Check the pre-charge of the expansion vessel is set to 1 bar.
03/22-V4
03/22-V4
Page: 5 of 19
Room Thermostat
Connection (remote contact)
Connect room thermostat wiring to terminals #20, #21 via the normally open contacts of the room thermostat.
The thermostat requires volt free contacts to open/close terminals #20, #21. If the thermostat features a switched
live output for on/off, an external relay with volt free contacts will need to be used. Open contacts = Off;
Closed contacts = On. These terminals are enabled when changing parameter 5120. See system configuration
for more details.
Low voltage, not polarity sensitive.
DO NOT APPLY 230V TO THESE TERMINALS.
03/22-V4
1. Enter the password to access the SERVICE level, specify parameter number “9999” and enter password
“738”, and press the Set button to confirm entry of the password.
1. “SErv” (means SERVICE) will be displayed in the position of room temperature display. In SERVICE level,
all parameters can be accessed. The procedures of setting parameters are same as INSTALLER level.
Value
Parameter Description
Default Set To
03/22-V4
Value
Parameter Description
Default Set To
0 = DHW is unavailable
3101 0 1
1 = DHW is available, and priority DHW over space heating
03/22-V4
Page: 9 of 19
Selecting The Correct
Cooling Option
The following system configurations are for systems that provide both heating and cooling. Depending on the
type of cooling system or part of the country the home is in, the cooling settings need to be selected to ensure
they are suitable.
The following system types are 3-A & 3-B for heating and cooling without domestic hot water heating & 4-A & 4-B
for heating and cooling with domestic hot water heating. The A & B of these systems are the different cooling
set points which are explained further below.
Note: For radiant cooling systems the CHNZ SmartOne thermostat must be used with the
dew point check function enabled. The floor probe must be installed in conduit in the floor
slab for an underfloor heating system or securely attached and insulated to a return pipe on
a Variocomp/Modulepanel system.
03/22-V4
Value
Parameter Description
Default Set To
03/22-V4
Page: 11 of 19
System 3-B: Heat Pump Switched On/Off by Room
Thermostat(s) Heating & Type B Cooling
Value
Parameter Description
Default Set To
03/22-V4
Value
Parameter Description
Default Set To
Note: While setting up this system and the thermostat, the 0-10V output from the thermostat will
drop on and off causing an L5 error on the heat pump. While this may not clear immediately, after
a few minutes the fault can be reset and heat pump operation will resume.
03/22-V4
Page: 13 of 19
System 4-A: Heat Pump Switched On/Off by Room
Thermostat(s) Heating & Type A Cooling + DHW
Value
Parameter Description
Default Set To
0 = DHW is available
3101 0 1
1 = DHW is available, and priority DHW over space heating
03/22-V4
Value
Parameter Description
Default Set To
03/22-V4
Page: 15 of 19
System 4-B: Heat Pump Switched On/Off by Room
Thermostat(s) Heating & Type B Cooling + DHW
Value
Parameter Description
Default Set To
0 = DHW is available
3101 0 1
1 = DHW is available, and priority DHW over space heating
03/22-V4
Value
Parameter Description
Default Set To
Enable DHW sensor: Terminal 7-8
5107 0 = Disable 0 1
1 = Enable
Terminal 17-18: Humidity sensor
5117 0 = Disable 0 1
1 = Enable
Terminal 20-21: On/Off remote contact or EHS Alarm input
0 = Disable (Remote controller only)
5120 0 1
1 = On/Off remote contact
2 = EHS Alarm input
Note: While setting up this system and the thermostat, the 0-10V output from the thermostat will
drop on and off causing an L5 error on the heat pump. While this may not clear immediately, after
a few minutes the fault can be reset and heat pump operation will resume.
03/22-V4
Page: 17 of 19
System Operational Checks
Once the heat pump is set up, it is a very good idea to check that everything works as intended and that
the heat pump starts and stops when it should in response to the controls used, and there is a good flow rate
at the manifolds and radiators get hot.
Alternatively these can be viewed from the outdoor units terminal PCB.
03/22-V4
If an excessive flow rate occurs due to low pressure loss of the circulating loop, adjust the Main water pump
speed so that the flow rate is reduced.
Using the Dip switches on the PCB (Terminal) – as noted on the above diagram, 3-Pump speeds are available.
Be aware that an excessively low flow rate may cause problems including diminished capacity, poor circulation, or
system errors.
At the factory shipment, both SW5 and SW6 are Off, which means the pump will operate at maximum.
Resetting Errors
The procedure to reset the error display differs between error codes and there are 3 ways to reset: Auto, Power Off,
and Manual. See “List of Errors codes” in the Chofu installation manual for the procedure to reset each error code.
Auto: Automatically. Once it returns to normal condition, the error will be reset. When the unit stops, it may
not be possible to reset automatically. Then, it needs to be reset manually.
Power Off: Manually. If Heat pump unit returns to normal condition, turn Off the power supply once and turn On
again, then the error will be reset.
Manual: Manually. To reset the error, press – and + button of the Master Remote controller at the same time for
3 seconds, or press Reset SW on the PCB (Terminal).
If the error persists please contact our technical aftersales team for assistance with the fault:
aftersalestechnical@centralheating.co.nz or call 0800 357 1233
03/22-V4
Page: 19 of 19
New Zealand’s
Experts
The combination of our skills, products,
experience and people, make us New Zealand’s
experts in the central heating industry. We take
pride in supplying the right heating system or
products for our customers’ specific functionality
and budget requirements so that at the end
of every project, both our customers and their
clients are delighted—and warm.