Logamatic 2107
Logamatic 2107
Instructions
AUTOMATIC
11.15am 71°F
T 180 160
AU
140
120
Notice:
2 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Contents
3 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.1 Mounting of the Logamatic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9
3.2 Installation of the Logabracket . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
4 Logamatic 2107 controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
9 Solar data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
9.1 Solar function ON/OFF (with FM 244 only) . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
9.2 Maximum storage tank temperature in solar mode . . . . . . . . . . . . . . . . . . . . . . 45
9.3 Minimum storage tank temperature in solar mode . . . . . . . . . . . . . . . . . . . . . . . 46
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 3
Downloaded from www.Manualslib.com manuals search engine
Contents
12 Heating curve . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
16 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
17 Version number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
18 Sensor curves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
20 Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61
20.1 Troubleshooting "NO HEAT" call . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63
20.2 Troubleshooting „INSUFFICENT HEAT“ call . . . . . . . . . . . . . . . . . . . . . . . . . 66
20.3 Troubleshooting Domestic Hot Water . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
21 Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
4 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Safety instructions and user notes 1
USER NOTE
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 5
Downloaded from www.Manualslib.com manuals search engine
1 Safety instructions and user notes
RISK OF LIFE
SYSTEM DAMAGE
through frost.
CAUTION! z Frost protection is only active if the
controls is switched ON. Switch OFF
the controls and drain the water from
the boiler, the DHW tank and the pipes
of the heating system. The system is
only protected from frost, if it is
completely dry.
RISK TO LIFE
z In an emergency, switch OFF the
emergency shutoff switch outside the
WARNING!
boiler room.
6 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Setting parameters and display data for the Logamatic 2107 2
Press the "Display" key and "Install" key at the same time to call up the service
level (see Chapter "Keys for extended functions", page 14).
Display
AMERICAN Language selection
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 7
Downloaded from www.Manualslib.com manuals search engine
2 Setting parameters and display data for the Logamatic 2107
Display
SOLAR7
RESET Reset
8 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Installation 3
3 Installation
z On the GC124, G124X, GA124, G234X, G244, and G334X boilers remove
the front panel of the boiler.
z Remove rear top panel of the boiler by first unscrewing 2 screws at the rear
edge, then sliding rear panel backward to disengage the hooks.
z Remove the two screws at the top of the Logamatic, and lift up top cover.
z Insert the two front feet of the control into the holes provided on the top of the
boiler. Then, firmly push down on the rear of the control until it snaps into
place.
z Fasten the control to the boiler jacket using the two screws as shown.
z The sensor bundle consists of one thermistor (FK), two capillaries and a
spacer. Mount the sensors per the following boiler specific instructions.
Use the chrome well supplied with the Logamatic.
z G115, G125, GB125, G215, G315: Replace brass well with chrome
Logamatic well. The sensor bundle must be fully inserted into the Logamatic
well.
z GC124, G124X, GA124, GA244, GA334X: Unwrap the sensor bundle.
Remove spacers from the chrome well on the boiler. Remove outer sleeve
from one capillary. Insert both capillaries and thermistor into the chrome well
together with Honeywell capillary.
z G234: The tridicator assembly should be moved to the supply piping and
replaced with the chrome plated Logamatic well. The sensor bundle must be
inserted into this well.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 9
Downloaded from www.Manualslib.com manuals search engine
3 Installation
z Use the white strain relief brackets provided to lock all cables into place on
the back of the control.
z Replace the top housing of the controls and fasten the two screws. The
control is ready to be placed into operation.
10 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Installation 3
The Logabracket is designed to create strain relief for your line voltage and low
voltage wiring for the 2107 Logamatic controls. The bracket is mainly designed
for use with the G115, G125, GB125 and G124X boilers, but with minor
modifications can be used on other boiler models as well.
Line the bracket up with holes, place the Logamatic in place over the holes and
secure with screws provided.
Four conduit connections are provided for line voltage wiring; a slotted opening
is used to run low voltage sensor wiring.
G215
It is necessary to bend down the tabs on the rear jacket panel to prevent
interference between bracket and jacket panel.
G234X, G334X
Simply cut off the tabs of the bracket and mount on the rear panel by drilling an
additional hole for a second mounting screw.
GA124, GA244
These boilers do not require the bracket as strain relief connections are provided
on the rear of the boiler.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 11
Downloaded from www.Manualslib.com manuals search engine
4 Logamatic 2107 controls
9 8
10
AUTOMATIC 7
11.15am 71
6
T 180 160
AU
140
120
T 180 160
AU
140
120
1
3 5
2
4
12 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Logamatic 2107 controls 4
1 2 3 4
Fig. 2 Keypad for basic functions
Item 1: Automatic mode following a program
Item 2: Normal heating mode (day mode)
Item 3: Flue gas test (for measuring flue gases)
Item 4: Setback heating mode (night mode)
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 13
Downloaded from www.Manualslib.com manuals search engine
4 Logamatic 2107 controls
1 2 3 4 5 6
11 10 9
This keypad is used, for example, to enter the day, set the time, select
temperature values, etc.
14 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Checking the manual reset high limit (STB) 5
USER NOTE
Check the STB after the initial installation, and after every service.
RELAY
Hold down the "Display" key and turn the dial, until "BURNER ON" appears in
the display.
ON
z Remove the dial on the boiler water thermostat (Fig. 4).
T 180 16
0
AU
140
120
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 15
Downloaded from www.Manualslib.com manuals search engine
5 Checking the manual reset high limit (STB)
z Push the lever or key (depending on the type of STB) back with a screwdriver
or similar device and hold until the high limit safety cut-out has triggered
1 (Fig. 5).
Press "AUT".
Reattach the dial and turn it to the "AUT" position.
z To reset the manual reset high limit, remove the cover on the STB and press
the reset button located beneath it (Fig. 6).
1...7
Tag Zeit Temp
PROG
Urlaub Auswahl So/Wi
AUT 70
90
60
I 0
50
16 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Using the service level 6
SYSTEM DAMAGE
You will need a pointed object, such as a ball-point pen, to press the "Install"
button.
Press the "Display" key and "Install" key at the same time to call up the service
+ level.
USER NOTE
The unit automatically returns to the standard display if no settings are made
within 5 minutes.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 17
Downloaded from www.Manualslib.com manuals search engine
6 Using the service level
Press the "Display" key and "Install" key at the same time to call up the service
level. Release both keys. Once you have called up the service level, you can
+
access all the setting options it contains.
The service level is broken down into main menus and submenus.
You can scroll through the main menu level by turning the dial.
AMERICAN
BOILER
CIRCUIT 01
CIRCUIT 1
PERIM HTG
REF TEMP
REMOTE
CIRCUIT 1
PERIM HTG
18 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Using the service level 6
When you press the "Display" key in a submenu, the setting parameter to be
changed flashes. Hold down the "Display" key and turn the dial at the same time
+
to change the parameter. The new value will be stored after you release the
"Display" key.
Some parameters are only displayed if the relevant modules are installed
(module FM 241– mixer, FM 242– 2-stage burner, FM 244 – solar module). The
controls detects the modules and enables the parameters.
Press "ENTER".
The unit automatically returns to the standard display if no key is pressed within
5 minutes.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 19
Downloaded from www.Manualslib.com manuals search engine
7 General data
7 General data
USER NOTE
"PUMP KICK"
In all operating modes, all the pumps are switched on and then off again for
10 seconds every Wednesday at 12 noon to prevent pump damage. This is
followed by a brief 5 second pause, then the mixing valves are set to "OPEN"
for 3 minutes. All pumps then return to normal operation.
20 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
General data 7
If the outdoor temperature drops beneath the frost protection limit, the heating
system pump (contacts 61/63) will be started.
The factory default for the frost protection limit is an outdoor temperature of
41°F (5°C).
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
FREEZE TEMP °F
41
Hold down the "Display" key and turn the dial until the desired value appears
+
(in this case "41°F").
43
Press "ENTER" to return to the next higher level.
USER NOTE
The value of the "OASETBACK" setback type is also limited to the freeze
protection limit. The setting applies to all heating circuits.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 21
Downloaded from www.Manualslib.com manuals search engine
7 General data
Time in hours
The building type is used to take into account the heat storage capacity of the
building's mass and the thermal inertia of the building compared to fluctuations
in the outdoor temperature. The lighter the building and the thinner its insulation,
the faster the controls will respond to changes in outdoor temperature (known
as "adjusted outdoor temperature calculation").
It is the adjusted outdoor temperature value that is used for the warm weather
shutdown (WWSD) and to calculate the supply temperature using the
characteristic heating curve (Fig. 7).
22 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
General data 7
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
BLDG RESP
2
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case "1").
1
Press "ENTER" to return to the next higher level.
1 (low)
Building response 2 (medium) 2
3 (high)
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 23
Downloaded from www.Manualslib.com manuals search engine
7 General data
The basic 2107 controls single stage burners. To use it with 2-stage or
modulating burners install a FM 242 burner module.
When the FM 242 burner module is installed, the factory default changes from
"1-STAGE" to "2-STAGE".
With 2-stage burners, the operating hours are displayed separately for stage 1
and stage 2.
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
2-STAGE
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case "MODULATE") is displayed.
24 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
General data 7
The modulating output requires the burner module FM 242 and "MODULATE"
burner setting.
The factory default is "30 %", i.e. the burner modulates its set output within an
output range of 30-100 %.
USER NOTE
The data can be found in the technical documentation for the installed burner.
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
MIN MOD
30
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case "40").
40
Press "ENTER" to return to the next higher level.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 25
Downloaded from www.Manualslib.com manuals search engine
7 General data
This feature requires the burner module FM 242 and "MODULATE" burner
setting.
USER NOTE
The data can be found in the technical documentation for the installed burner.
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
MOD TIME
12
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case "15").
15
Press "ENTER" to return to the next higher level.
26 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
General data 7
To protect the boiler against corrosion from condensation inside the combustion
chamber, the boiler pump (while the burner is running) will not start until the
boiler water has reached a certain temperature.
The temperature can be set using the "PUMPLOGIC" parameter.
The factory default is 104°F (40°C), which is recommended for cast iron boilers.
Recommendation:
If a condensing boiler is used, the parameter should be set to 60°F (15°C) in
order to make optimum use of the condensing technology.
NOTE: The GB125BE requires a pumplogic of 104°F (40°C) due to its cast iron
primary heat exchanger.
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
PUMPLOGIC °F
104
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case 122°F (50°C)).
122
Press "ENTER" to return to the next higher level.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 27
Downloaded from www.Manualslib.com manuals search engine
7 General data
The maximum boiler temperature is the highest target temperature the boiler will
reach. The burner should switch off no later than when this temperature is
reached (this applies to heating mode and DHW mode).
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
MAXTEMP 1 °F
176
Hold down "Display" and turn the dial until the required
+
value appears (in this case 167°F (75°C)).
167
Press "ENTER" to return to the next higher level.
USER NOTE
Ensure that the boiler water aquastat dial is set above the maximum boiler
temperature, as it will overwrite the maximum boiler temperature.
28 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
General data 7
Press the "Display" key and "Install" key at the same time to call up the service
level. Release both keys. The selected language, e.g. "AMERICAN", is
displayed in the first main menu. The factory setting for the language is
AMERICAN "AMERICAN". Now hold down the "Display" key and turn the dial to set the
language. Release the "Display" key to store the set language.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 29
Downloaded from www.Manualslib.com manuals search engine
8 Heating circuit data
The controls is designed for 2 heating circuits. The basic 2107 supports 1
heating circuit, which can be upgraded to 2 heating circuits using the
FM241card.
– Circuit 01 = unmixed heating circuit, no heating circuit, perimeter heating
If the right heating system is selected, the other heating circuit parameters are
preset. They must still be verified, however.
30 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Heating circuit data 8
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
CIRCUIT 01
PERIM HTG
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case "NO SYSTEM") is displayed.
NO SYSTEM
USER NOTE
If there is only one heating circuit with mixing valve present (HK2), circuit 1 must
be set to "NO SYSTEM".
If the "NO SYSTEM" setting is used, all of the following settings are hidden for
this circuit.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 31
Downloaded from www.Manualslib.com manuals search engine
8 Heating circuit data
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
CIRCUIT 02
FLOOR HTG
NO SYSTEM
Heating circuit 2 FLOOR HTG
FLOOR HTG
32 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Heating circuit data 8
The reference design temperature helps define the characteristic heating curve
which is the basis for outdoor reset.
It follows the idea that the colder the weather, the greater the heat loss of a
structure, and the higher a boiler supply temperature needed to compensate for
the resulting losses.
REF TEMP °F
167
The factory default setting results in a characteristic heating curve as shown
2 (Fig. 8, Item 1).
Boiler supply temperature [°F(°C)]
194 (90)
176 (80) The reference design temperature (Fig. 8, Item 2) is used to adjust the heating
167 (75)
curve. Depending on the measured outdoor temperature, the boiler supply
158 (70) 1
140 (60)
temperature is changed in order to keep the room temperature stable and save
as much on fuel as possible (Fig. 8).
122 (50)
104 (40) When changing the reference design temperature, the gradient of the heating
86 (30)
curve is adjusted.
68 (20)
68 60 50 41 32 23 14 +5
(+20) (+15) (+10) (+5) (±0) (-5) (-10) (-15)
194 (90)
Design temperature 140°F (60 °C) for +5°F (-15 °C) outdoor temperature.
176 (80)
167 (75) A boiler temperature of 140°F (60°C) is achieved by setting the reference design
158 (70)
temperature to 133°F (56°C) (at an outdoor temperature of 14°F (-10°C)),
140 (60)
122 (50) The reference design temperature can be set from 86 to 194°F (30 to +90°C).
104 (40)
86 (30)
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 33
Downloaded from www.Manualslib.com manuals search engine
8 Heating circuit data
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
REF TEMP °F
167
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case 133°F (56°C)).
133
Press "ENTER" to return to the next higher level.
34 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Heating circuit data 8
For the heating circuit 02 with mixing valve (if installed), you can set the DHW
priority or DHW heating in parallel to the heating mode.
Please note that if you select DHW heating in parallel to heating mode, it will take
longer to recharge the tank.
USER NOTE
For heating circuit 01 the DHW priority is always ON and cannot be disabled.
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
DHW PRIOR
ON
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case "OFF").
OFF
Press "ENTER" to return to the next higher level.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 35
Downloaded from www.Manualslib.com manuals search engine
8 Heating circuit data
The maximum heating circuit temperature is a target temperature that should not
be exceeded in the heating circuit.
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
MAX TEMP °F
194
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case 140°F).
140
Press "ENTER" to return to the next higher level.
*) This function does not replace the safety thermostat for switching of the pump
for radiant heating circuit.
36 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Heating circuit data 8
A BFU (accessory) remote control allows to easily control a heating system from
the living space.
If the controller is equipped with a BFU remote control, the remote control must
be activated and assigned to the appropriate heating circuit.
Instructions for assigning the remote control to the required heating circuit
(HK1 or HK2) can be found in the remote control operating instructions.
USER NOTE
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
Turn the dial until "HEAT CIRC 1" or "HEAT CIRC 2" is displayed.
Turn the dial until "REMOTE 1" for heating circuit 1 or "REMOTE 2" for heating
circuit 2 is displayed.
REMOTE 1
OFF
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case "ON").
ON
Press "ENTER" to return to the next higher level.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 37
Downloaded from www.Manualslib.com manuals search engine
8 Heating circuit data
If the remote control is active, the desired room temperature for day and night
mode must be entered on the remote control, rather than via the controls.
The "AUT", "Day mode" and "Night mode" keys on the controls also are disabled
for this heating circuit with remote control.
If you press the "Temp", "AUT", "Day mode" or "Night mode" key, "REMOTE"
appears on the display if the remote control is active.
All settings can then only be made via the remote control.
38 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Heating circuit data 8
USER NOTE
The maximum room temperature hook-up determines the range within which
deviations from the room setpoint value may be corrected. Influencing factors
such as open windows or additional heat sources, e.g. wood burning stove,
open fireplace, are thus eliminated in the area where the remote control is
installed. If other rooms are supplied with heat via this heating circuit, then the
aforementioned influencing factors can cause these near-by rooms to be
supplied with insufficient heat. The function should be set to "OFF" to eliminate
the chance of insufficient supply.
The maximum differential temperature can only be entered if the remote control
has been activated. The influence of the room temperature on the DHW
temperature (heating curve) is thus limited.
USER NOTE
If you entered "OFF", the room temperature no longer has any influence on the
supply temperature (heating curve).
This setting is generally recommended for FLOOR HTG systems.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 39
Downloaded from www.Manualslib.com manuals search engine
8 Heating circuit data
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
ROOM COMP °F
6
Hold down the "Display" key and turn the dial until the desired value appears (in
+
this case "OFF").
OFF
Press "ENTER" to return to the next higher level.
40 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Heating circuit data 8
The Logamatic 2107 control contains night setback capability and allows you to
select from 4 different types or modes of night setback for customized operation.
These setback modes differ in their operation.
In this mode the heating system shuts down completely during the night time as
BLR OFF long as the outdoor temperature exceeds the "FREEZTEMP" setting. Below the
"FREEZTEMP" value, the circulators run in freeze protection mode. The boiler
only fires if the water temperature drops below 41°F (5°C). No room sensors are
used in this setback mode.
SETBACK The heating circulators continue operation in the "SETBACK" mode; the boiler
operates on a lower heating curve and fires the burner as needed. This mode is
generally used when no room sensors are present and individual zones are
controlled by conventional thermostats.
This setback mode should only be selected when a room sensor is installed and
RMSETBACK activated. The system operates to maintain the desired night time temperature
as specified on the room sensor. The circulators will operate continuously when
the outdoor temperature is below the "FREEZTEMP" setting; the circulators shut
down when the outdoor temperature is above the "FREEZTEMP" setting and the
actual room temperature exceeds the night time setting.
The heating system (burner and heating circulators) shuts down in night mode
OASETBACK if the outdoor temperature exceeds the "FREEZTEMP"; if the outdoor
temperature drops below the "FREEZTEMP", the heating system operates on a
setback curve. This mode should only be used on buildings not occupied in the
night mode; i.e. commercial and daytime use only buildings. A room sensor is
generally not used in this application.
Recommended setting
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 41
Downloaded from www.Manualslib.com manuals search engine
8 Heating circuit data
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
OASETBACK
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case "OASETBACK").
42 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Heating circuit data 8
for
. example: Displayed room temperature 72°F (22°C)
Measured room temperature 75°F (24°C)
Offset -3°F (-2°C)
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
OFFSET °F
0
Hold down the "Display" key and turn the dial until the required value appears
+ (in this case "-3°F").
-3
Press "ENTER" to return to the next higher level.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 43
Downloaded from www.Manualslib.com manuals search engine
9 Solar data
9 Solar data
The Solar function menu option is used to optimize the solar gain and minimize
the use of fossil fuel.
To achieve this, the controllers for the solar heating system and the conventional
heating boiler are combined in a single unit. The controls monitors the current
solar gain and the stored heat in the DHW tank, and reduces the setpoint
temperature in the standby part of the DHW tank to prevent it being reheated
unnecessarily.
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
SLRFN ON
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case "SLRFN OFF").
44 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Solar data 9
The solar heating system will collect all solar heat that can be harvested. It will
only stop when there is not sufficient insolation or to protect the tank from
overheating. When "MAX SOL T" is reached at the top tank sensor FB, the solar
pump is switched off.
RISK OF SCALDING
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
MAX-SL SR °F
167
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case "194°F").
194
Press "ENTER" to return to the next higher level.
USER NOTE
Take the lime content of the local drinking water into consideration when
determining the "MAX-SL SR" setting in order to prevent the tank scaling up.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 45
Downloaded from www.Manualslib.com manuals search engine
9 Solar data
The DHW temperature to be generated by the boiler for a given solar gain
(DHW setpoint, see operating instructions for the settings) may be automatically
reduced so that the tank can be charged the solar heating system. The
"MIN SOL T" parameter contains the lower limit to which the temperature may
fall. If the temperature of the DHW in the tank (FB sensor) falls below the value
set here, then it is recharged by the boiler. The DHW setpoint temperature to be
generated by the boiler is lowered no further than "MIN SL SR".
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
MIN SL SR °F
100
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case "130°F").
130
Press "ENTER" to return to the next higher level.
46 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
DHW production ON/OFF 10
If the heating system is equipped with a DHW tank, DHW heating must be
activated. The factory setting is "ON".
If no DHW heating is installed, it should be disabled to avoid the DHW SENSR
ERR error message.
The controls starts the burner if necessary in order to heat the DWH. The DHW
tank charging pump runs. Once the burner has been switched off, the controls
uses the residual heat in the boiler to heat the DHW.
Once the set DHW temperature is reached, the DHW tank charging pump is
switched off. Normal heating mode is resumed at the end of the DHW heating
cycle.
A recirculation pump (if installed) may be controlled if the DHW heating is
activated.
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
DHW PROD
ON
Hold down the "Display" key and turn the dial until the required value appears
+
(in this case "OFF").
OFF
Press "ENTER" to return to the next higher level.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 47
Downloaded from www.Manualslib.com manuals search engine
11 DHW recirculation pump
The DHW recirculation pump ensures a constant supply of hot water to the taps.
It is automatically activated with DHW heating and the pump runs in intermittent
or continuous mode if at least one heating circuit is in normal heating mode (day
mode), or if DHW heating is in day mode.
The DHW recirculation pump runs continuously in the "ON" position.
The factory default is "2", i.e. 2 pump runs per hour, running for 3 minutes each
time (Fig. 10).
3 minutes 3
ON
OFF
1 hour
Fig. 10 Illustration of the DHW recirculation pump running time with factory setting 2
The intermittent mode may be set to 1 to 6 pump starts per hour in order to
minimize the operating costs of the recirculation pump. This setting saves
energy while ensuring comfort.
48 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
DHW recirculation pump 11
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
Turn the dial until the "RECIRCPUMP 2" main menu is displayed.
RECIRCPUMP
2
Hold down the "Display" key and turn the dial anti-clockwise until the required
+
value appears (in this case "4").
4
Press "ENTER" to return to the next higher level.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 49
Downloaded from www.Manualslib.com manuals search engine
12 Heating curve
12 Heating curve
The heating curve test is used to display the DHW temperature for the current
operating status at external temperatures 50°F (+10°C), 32°F (±0°C) and 14°F
(-10°C).
The heating curve displayed here (Fig. 11) is calculated by the controls on the
basis of the values set for design temperature, offset and setpoint room
DHW temperature in °F (°C)
Heating curve temperature, and corresponds to the currently active characteristic. To ensure
that there is no shift during commissioning, ensure during commissioning that:
167 (75)
the heating circuit is in "day mode"
144 (62)
(press the "Day" key),
113 (45)
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
Turn the dial until "HTG CURVE 01" for heating circuit 1 or "HTG CURVE 2" for
heating circuit 2 (mixed circuit) is displayed.
HTG CURVE
01
Hold down "Display" and turn the dial. The first display contains the DHW
+ temperature at 50°F (+10°C), the second at 32°F (±0°C) and the third
at 14°F (-10°C).
HTG CURVE °F
113 50
HTG CURVE °F
144 32
HTG CURVE °F Release the "Display" key to return to the next higher level.
167 14
50 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Running the relay test 13
The relay test is used to check that the switching relays in the controls are
working correctly.
SYSTEM DAMAGE
due to controller functions being deactivated for the duration of the relay test.
CAUTION!
The heat supply to the system is not guaranteed, so it is essential to press the
"ENTER" key at the end of the relay test to exit the relay test function and thus
avoid damaging the system.
The displays differ according to which modules are installed in the controls. The
following relays can be called up:
z Burner 1st stage / 2nd stage
z Modulation open/closed OFF
z Boiler system pump HK1
z Heating circuit pump HK 2
z Mix valve open/closed/OFF
z Tank DHW pump
z DHW recirculation pump
z Solar pump
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 51
Downloaded from www.Manualslib.com manuals search engine
13 Running the relay test
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
RELAY
Hold down the "Display" key and turn the dial, until "BURNER ON" appears in
+ the display.
BURNER If the burner is working correctly and the operating hours signal has been
returned by the burner, an "h" appears in the display.
h ON Turn the dial to display all the relay functions in succession.
The relay switching states are represented by symbols, e.g. for the recirculation
pump (left, 1st symbol) or for DHW tank filling pump / solar pump
(right, 2nd symbol).
USER NOTE
The pump symbol lights up continuously if the DHW tank filling pump is running.
If the solar pump and DHW tank filling pump are running, then the solar pump
symbol flashes.
Safety instructions
All available relays can be manually activated and deactivated in the relay test.
With the solar pump it should be noted that a safety override may prevent
activation if there is a risk of damage to the system (collector, DHW tank).
Specifically this means that it will not be switched on if:
z the solar module is defective
z a defective collector (FSK) or DHW heating sensor (FB) was detected
z the collector temperature has reached the maximum permitted temperature
z the tank temperature has reached the maximum permitted temperature
52 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Performing an LCD test 14
The LCD test is used to check whether all the figures and symbols are displayed
in full.
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
LCD TEST
Hold down "Display" and turn the dial. All the numbers and symbols must appear
+
on the display.
°F°C
1 2
Release the "Display" key.
1234567
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 53
Downloaded from www.Manualslib.com manuals search engine
15 Time, correcting the accuracy
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
TIME
0
Hold down "Display" and turn the dial until the identified deviation appears in the
+
display, e.g.: if it is 10 s/day fast, then set to -10 s/day.
-10
Press the "Display" key to return to the next higher level.
54 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Reset 16
16 Reset
"RESET" is used to return all the controls settings to their factory settings. Any
previously programmed heating times as well as burner and solar hours remain
unchanged, however.
Reset steps
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
RESET
8888 888
Hold down the "Display" key until all the numbers in the display have
disappeared.
No "RESET" is carried out if you release the "Display" key before all the numbers
have disappeared.
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 55
Downloaded from www.Manualslib.com manuals search engine
17 Version number
17 Version number
Press the "Display" key and "Install" key at the same time to call up the service
+ level. "AMERICAN" appears as the first main menu.
VERSION
3.24
56 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Sensor curves 18
18 Sensor curves
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 57
Downloaded from www.Manualslib.com manuals search engine
18 Sensor curves
Boiler water (FK), supply (FV), DHW (FB) and solar water tank (FSS) temperature sensors
Resistance [k:]
68 (20) 86 (30) 104 (40) 122 (50) 140 (60) 158 (70) 176 (80) 194 (90)
Water temperature [°F (°C)]
.
-58 (-50) 32 (0) 122 (50) 212 (100) 302 (150) 392 (200) 482 (250)
Collector temperature [°F (°C)]
58 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Operating values at the service level/setup report 19
Type of construction 1, 2, 3 2
Outdoor setback
Room setback
Setback type for heating circuit 1 Outdoor setback
Setback
Switch-off
Outdoor setback
Room setback
Setback type for heating circuit 2 Outdoor setback
Setback
Switch-off
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 59
Downloaded from www.Manualslib.com manuals search engine
19 Operating values at the service level/setup report
60 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting 20
20 Troubleshooting
Effects on control
Fault Possible cause of the fault Remedy
characteristics
Sensor defective.
Check the sensor
Connecting cable
Collector sensor error connection.
interrupted Solar pump is switched off
SL SENSOR ERROR Replace the sensor
Solar module (FM 244)
Replace the module
defective
Sensor defective.
Check the sensor
Connecting cable
Solar hot water sensor error connection.
interrupted Solar pump is switched off
DHW-SL ERROR Replace the sensor
Solar module (FM 244)
Replace the module
defective
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 61
Downloaded from www.Manualslib.com manuals search engine
20 Troubleshooting
Effects on control
Fault Possible cause of the fault Remedy
characteristics
62 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting 20
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 63
Downloaded from www.Manualslib.com manuals search engine
20 Troubleshooting
Oil burners – factory jumper between terminals 12 & 10, Gas burners – remove factory installed jumper between
brings 120V from 12 to 10. When contacts close terminals 10 & 12. The contacts between terminals 10 &
between terminals 10 & 11, 120V power is sent from 11 are now “dry” (no voltage present) and switching to
terminal 11 to Hot on the burner (terminal 4 is the the burner is now low voltage between terminals 10 & 11
neutral). on the R2107 and TT (or RW) on the boiler aquastat.
64 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting 20
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 65
Downloaded from www.Manualslib.com manuals search engine
20 Troubleshooting
66 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Troubleshooting 20
A “DHW PROD ERR” message will appear on the LCD screen of the R2107 control with regard to domestic hot water
production.
DHW ERR - when the tank temperature drops to the low limit (9°F below the set point), the R2107 goes into DHW
priority mode.
During DHW priority, the R2107 raises the boiler water temperature to it’s high limit, interrupts power to the space
heating circuit {terminals 61(N) & 63 (H)} and energizes the DHW pump circuit {terminals 24 (N) & 25 (H)}. The pump
circuit symbol is displayed on the LCD screen.
In DHW priority, if the R2107 does not sense a rise in DHW temperature in 30 minutes, it will display a DHW PROD
ERR message.
At this point, the control will go back to space heating mode and lock out the DHW to avoid freezing the building. This
message is general in nature and the R2107 control is essentially telling you, “I tried to make domestic hot water but
nothing happened”.
IN MOST CASES THE PROBLEM IS NOT WITH THE R2107 CONTROL. To rule out the R2107, turn power off to the
R2107 to reset.
The R2107 will again try to make DHW. Check terminals 24 & 25 for 120V. If power is present and boiler fires the R2107
is o.k.
1 - bad circulator
4 - closed valve
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 67
Downloaded from www.Manualslib.com manuals search engine
21 Index
21 Index
B
Boiler water temperature sensor . . . . . . . . . . 58
Burner system . . . . . . . . . . . . . . . . . . . 24
C
Collector sensor . . . . . . . . . . . . . . . . . . 58
Controls on the 2107 . . . . . . . . . . . . . . . . 12
D
Design temperature . . . . . . . . . . . . . . . . 33
DHW priority . . . . . . . . . . . . . . . . . . . . 35
DHW recirculation pump . . . . . . . . . . . . . . 48
E
Emergency shutoff switch – heating system . . . . 6
F
Frost protection . . . . . . . . . . . . . . . . . . . 6
H
Heat storage capacity . . . . . . . . . . . . . . . 22
Heating circuit temperature . . . . . . . . . . . . . 36
Heating curve . . . . . . . . . . . . . . . . . . . . 50
Heating system . . . . . . . . . . . . . . . . . . . 30
L
Language selection . . . . . . . . . . . . . . . . . 29
LCD test . . . . . . . . . . . . . . . . . . . . . . 53
M
Manual reset high limit (STB) . . . . . . . . . . . . 17
Maximum room temperature hook-up . . . . . . . 39
Menu . . . . . . . . . . . . . . . . . . . . . . . . 18
Modulating output . . . . . . . . . . . . . . . . . 25
O
OFF temperature . . . . . . . . . . . . . . . . . . 28
ON temperature . . . . . . . . . . . . . . . . . . 27
Operating time of the burner actuator . . . . . . . 26
Outdoor temperature sensor . . . . . . . . . . . . 57
P
Password . . . . . . . . . . . . . . . . . . . . . . 17
Pump kick . . . . . . . . . . . . . . . . . . . . . 20
Pump logic . . . . . . . . . . . . . . . . . . . . . 27
R
Relay test . . . . . . . . . . . . . . . . . . . . . . 51
Remote control . . . . . . . . . . . . . . . . . . . 37
Reset . . . . . . . . . . . . . . . . . . . . . . . . 55
Room temperature offset . . . . . . . . . . . . . . 43
S
Safety instructions . . . . . . . . . . . . . . . . . 5
Sensor curves . . . . . . . . . . . . . . . . . . . 57
Service level . . . . . . . . . . . . . . . . . . . . 17
Setting parameters . . . . . . . . . . . . . . . . . 19
Setup report . . . . . . . . . . . . . . . . . .59, 61
Solar function . . . . . . . . . . . . . . . . . . . . 44
System frost protection, frost protection . . . . . . 21
T
Type of construction . . . . . . . . . . . . . . . . 22
Type of setback . . . . . . . . . . . . . . . . . . . 41
V
Version number . . . . . . . . . . . . . . . . . . . 56
68 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.
Downloaded from www.Manualslib.com manuals search engine
Notes
Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications. 69
Downloaded from www.Manualslib.com manuals search engine
Notes
70 Logamatic 2107 controls - We reserve the right to make any changes due to technical modifications.