SINAMICS G115D Technical Specs

This document provides data and specifications for a SINAMICS G115D drive unit, including its technical ratings, ambient operating conditions, control features, and communication protocols. It lists detailed information on the drive's inputs, outputs, connections, compliance with standards, and dimensions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views4 pages

SINAMICS G115D Technical Specs

This document provides data and specifications for a SINAMICS G115D drive unit, including its technical ratings, ambient operating conditions, control features, and communication protocols. It lists detailed information on the drive's inputs, outputs, connections, compliance with standards, and dimensions.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Data sheet for SINAMICS G115D

Article No. : 6SL3520-3XL01-5AF0

Client order no. : Item no. : Figure similar


Order no. : Consignment no. :
Offer no. : Project : G115D
Remarks :

Rated data General tech. specifications


Input Power factor λ 0.00 ... 0.89

Number of phases 3 AC Offset factor cos φ 0.99

Line voltage 380 ... 480 V +10 % -10 % Efficiency η 0.97

Line frequency 45 ... 66 Hz Power loss 0.067 kW

Rated current 3.48 A Filter class (integrated) RFI suppression filter for Category C2

Output Brake voltage 180V DC (default)

Number of phases 3 AC Integrated braking resistor (continuous


braking power P_DB / peak power 10W / 100W
Rated voltage 400 V P_max)

Rated power IEC 400V (HO) 1.50 kW


Ambient conditions
Rated power NEC 480V (HO) 2.00 hp
Cooling Natural convection cooling
Rated current (HO) 4.10 A
Installation altitude 1,000 m (3,280.84 ft)
Max. output current 8.20 A
Ambient temperature
Pulse frequency 4 kHz
Operation -30 ... 55 °C (-22 ... 131 °F)
Output frequency for vector control 0 ... 240 Hz
Transport -40 ... 70 °C (-40 ... 158 °F)
Output frequency for V/f control 0 ... 550 Hz
Storage -40 ... 70 °C (-40 ... 158 °F)
Overload capability
Relative humidity
High Overload (HO)
95 % At 40 °C (104 °F), condensation
Max. operation
200% × base load current IH for 3 s, followed by 150% for 57 s within a cycle and icing not permissible
time of 300s
Mechanical data
Inputs / outputs
Degree of protection IP65/66 / UL type 4X
Standard digital inputs
Frame size FSA
Number 1) 4
Net weight 6.71 kg (14.76 lb)
Switching level: 0 → 1 11 V
Dimensions
Switching level: 1 → 0 5V
Width 380 mm (14.96 in)
Max. inrush current 15 mA
Height 216 mm (8.50 in)
Fail-safe digital inputs
Depth 129 mm (5.08 in)
Number 1

Digital inputs / outputs parameterizable Closed-loop control techniques


V/f linear / square-law / parameterizable Yes
Number 2
V/f with flux current control (FCC) Yes
PTC/ KTY interface
V/f ECO linear / square-law Yes
1 motor temperature sensor input, possible sensor PTC, KTY, PT1000, thermo
click, accuracy ±5 °C Sensorless vector control Yes

Vector control, with sensor No

Encoderless torque control Yes

Torque control, with encoder No

Communication
Communication PROFINET, EtherNet/IP

Version M12

Control option
Control option Repair switch and local remote control

Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 1 of 2 Generated Tue Feb 13 09:40:53 CET 2024
Data sheet for SINAMICS G115D

Article No. : 6SL3520-3XL01-5AF0

Connections Standards
Connection type CE, C-Tick (RCM), EAC, KCC, SEMI F47,
Compliance with standards
REACH
Version Connector without daisy chain
EMC Directive 2014/30/EC, Low-Voltage
CE marking
3AC 400V supply Directive 2014/35/EC

Version 1x Quickon
1)
4 inputs PNP, not isolated, additional 2x switcheable DI/DO
24 V DC power supply

Variant integrated

Version integrated

Digital I/O

Version M12

Motor

Version Q8/0

External brake resistor

Version Cable gland (Standard)

PE connection

Version On housing with M5 screw

Max. motor cable length

Shielded 15 m (49.21 ft)

Converter losses to IEC61800-9-2*


Efficiency class IE2

Comparison with the reference


28.14 %
converter (90% / 100%)

I 59.6 W (2.1 %) 62.4 W (2.2 %) 66.7 W (2.3 %)


100%

46.9 W (1.7 %) 48.1 W (1.7 %) 49.8 W (1.8 %)


50%

41.7 W (1.5 %) 42.3 W (1.5 %)


25%

50% 90% f

The percentage values show the losses in relation to the rated apparent power of
the converter.

The diagram shows the losses for the points (as per standard IEC61800-9-2) of
the relative torque generating current (I) over the relative motor stator frequency
(f). The values are valid for the basic version of the converter without
options/components.

*calculated values

Technical data are subject to change! There may be discrepancies between calculated and rating plate values. Page 2 of 2 Generated Tue Feb 13 09:40:53 CET 2024
Filename: 6SL3520-3XL01-5AF0_3D_5c57d92a010e6217c99c9d07b7b4a71a.pdf