Electropneumatics for Engineers
Electropneumatics for Engineers
Compiled by:
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 1
1. Introduction
Pneumatics deals the use of compressed air. Most commonly, compressed air is used to
do mechanical work – that is to produce motion and to generate forces.
Pneumatic drives have the task of converting the energy stored in compressed air into
motion.
Cylinders are most commonly used for pneumatic drives. They are characterized by
robust construction, a large range of types, simple installation and favourable
price/performance. As a result of these benefits, pneumatics is used in a wide range of
applications.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 2
• Packaging
• Filling
• Stamping
In the processing station in Fig. 1.2, the rotary indexing table, feed, clamping and
ejecting devices and the drives for the various tools are pneumatic.
Application example:
Pneumatic drives can only do work usefully if their motions are precise and
carried out at the right time and in the right sequence. Coordinating the
sequence of motion is the task of the controller.
Control engineering deals with the design and structure of controllers. The
following section covers the basic terms used in control engineering.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 3
other variables in the form of output variables by reason of the laws which
characterize the system. The distinguishing feature of open loop controlling is the
open sequence of action via the individual transfer elements or the control chain.
The term open loop control is widely used not only for the process of controlling
but also for the plant as a whole.
Application example
A device closes metal cans with a lid. The closing process is triggered by
operation of a pushbutton at the workplace. When the pushbutton is released,
the piston retracts to the retracted end position.
In this control, the position of the pushbutton (pushed, not pushed) is the input
variable. The position of the pressing cylinder is the output variable. The loop is
open because the output variable (position of the cylinder) has no influence on
the input variable (position of the pushbutton).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 4
Fig. 1.4: Signal and information
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 5
Application example:
In the case of a pressure gauge, each pressure value (information parameter) is
assigned a particular display value (= information). If the signal rises or falls, the
information changes continuously.
Digital signal
A digital signal is a signal with a finite number of value ranges of the information
parameter. Each value range is assigned a specific item of information (DIN
19226, Part 5).
Application example:
A pressure measuring system with a digital display shows the pressure in
increments of 1 bar. There are 8 possible display values (0 to 7 bar) for a pressure
range of 7 bar. That is, there eight possible value ranges for the information
parameter. If the signal rises or falls, the information changes in increments.
Binary signal
A binary signal is a digital signal with only two value ranges for the information
parameter. These are normally designated o and 1 (DIN 19226, Part 5).
Application example:
A control lamp indicates whether a pneumatic system is being correctly supplied
with compressed air. If the supply pressure (= signal) is below 5 bar, the control
lamp is off (0 status). If the pressure is above 5 bar, the control lamp is on (1
status).
Controllers can be divided into different categories according to the type of information
representation, into analogue, digital and binary controllers (DIN 19226, Part 5).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 6
Logic controller
A logic controller generates output signals through logical association of input signals.
Application example:
The assembly device in Fig. 1.3 is extended so that it can be operated from two
positions. The two output signals are linked. The piston rod advances if either
pushbutton 1 or 2 is pressed or if both are pressed.
Sequence controller
A sequence controller is characterized by its step by step operation. The next step can
only be carried out when certain criteria are met.
Application example:
Drilling station. The first step is clamping of the work piece. As soon as the piston rod of
the clamping cylinder has reached the forward end position, this step has been
completed. The second step is to advance the drill. When this motion has been
completed (piston rod of drill feed cylinder in forward end position), the third step is
carried out, etc.
A controller can be divided into the functions signal input, signal processing, signal
output and command execution. The mutual influence of these functions is shown by
the signal flow diagram.
• Signals from the signal input are logically associated (signal processing). Signals for
signal input and signal process are low power signals. Both functions are part of the
signal control section.
• At the signal output stage, signals are amplified from low power to high power. Signal
output forms the link between the signal control section and the power section.
• Command execution takes place at a high power level – that is, in order to reach a
high speed (such as for fast ejection of a work piece from a machine) or to exert a high
force (such as for a press). Command execution belongs to the power section of a
control system.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 7
Fig. 1.6: Signal flow in a control system
The components in the circuit diagram of a purely pneumatic controller are arranged so
that the signal flow is clear. Bottom up: input elements (such as manually operated
valves), logical association elements (such as two-pressure valves), signal output
elements (power valves, such as 5/2-way valves) and finally command execution (such as
cylinders).
The directional control valves form the interface between the signal control
section and the pneumatic power section in both types of controller.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 8
Fig. 1.7: Signal flow and components of a pneumatic control system
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 9
Fig. 1.8: Signal flow and components of an electro-pneumatic control system
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 10
Structure and mode of operation of an electro-pneumatic controller
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 11
2. Fundamentals of electrical technology
Fig. 2.1: Direct current and alternating current plotted against time
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 12
Technical direction of flow
When the control switch is closed, current I flows via the load. The electrons
move from the negative pole to the positive pole of the voltage source. The
direction of flow from quotes "positive" to "negative" was laid down before
electrons were discovered. This definition is still used in practice today. It is
called the technical direction of flow.
Electrical conductors
Electrical current is the flow of charge carriers in one direction. A current can only
flow in a material if a sufficient number of free electrons are available. Materials
that meet this criterion are called electrical conductors. The metals copper,
aluminium and silver are particularly good conductors. Copper is normally used
for conductors in control technology.
Electrical resistance
Every material offers resistance to electrical current. This results when the free
moving electrons collide with the atoms of the conductor material, inhibiting
their motion. Resistance is low in electrical conductors. Materials with particularly
high resistance are called insulators. Rubber- and plastic-based materials are
used for insulation of electrical wires and cables.
Source emf
The negative pole of a voltage source has a surplus of electrons. The positive
pole has a deficit. This difference results in source emf (electromotive force).
Ohm's law
Ohm's law expresses the relationship between voltage, current and resistance. It
states that in a circuit of given resistance, the current is proportional to the
voltage, that is
If the voltage increases, the current increases.
If the voltage decreases, the current decreases.
V=R•I
V = Voltage; Unit: Volt (V)
R = Resistance; Unit: Ohm (Ω)
I = Current; Unit: Ampere (A)
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 13
Electrical power
In mechanics, power can be defined by means of work. The faster work is done,
the greater the power needed. So power is "work divided by time".
The electrical power of a load is also called its electrical power input.
P=V•I
P = Power; Unit: Watt (W)
V = Voltage; Unit: Volt (V)
I = Current; Unit: Ampere (A)
Application example:
Power of a coil
The solenoid coil of a pneumatic 5/2-way valve is supplied with 24 VDC. The
resistance of the coil is 60 Ohm. What is the power?
The current is calculated by means of Ohm's law:
I =RV=60 Ωx24 V = 0.4 A
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 14
Structure of a solenoid
The solenoid has the following structure:
The current-bearing conductor is wound around a coil. The overlapping of
the lines of force of all loops increases the strength of the magnetic field
resulting in a main direction of the field.
An iron core is placed in the centre. When current flows, the iron is also
magnetized. This allows a significantly higher magnetic field to be induced
with the same current (compared to an air-core coil).
These two measures ensure that an solenoid exerts a strong force on ferrous
(=containing iron) materials.
Applications of solenoids
In electro-pneumatic controls, solenoids are primarily used to control the
switching of valves, relays or contactors. This can be demonstrated using the
example of the spring-return directional control valve:
If current flows through the solenoid coil, the piston of the valve is
actuated.
If the current is interrupted, a spring pushes the piston back into its initial
position.
Reactance in AC circuits
If a AC voltage is applied to a coil, an alternating current flows (see Fig. 2.1).This means
that the current and magnetic field are constantly changing. The change in the magnetic
field induces a current in the coil. The induced current opposes the current that induced
the magnetic field. For this reason, a coil offers "resistance" to an alternating current.
This is called reactance.
The reactance increases with the frequency of the voltage and the inductance of the coil.
1 H = 1Vs/A= 1 Ωs
Reactance in DC circuits
In the case of DC circuits, the current, voltage and magnetic field only change when the
current is switched on. For this reason reactance only applies when the circuit is closed
(switching on the current).
In addition to reactance, the coil has ohmic resistance. This resistance applies both to AC
circuits and DC circuits.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 15
2.4. Function of a capacitor
A capacitor consists of two metal plates with an insulating layer (dielectric)
between them. If the capacitor is connected to a DC voltage source (closing the
switch S1 in Fig. 2.4), a charging current flows momentarily. Both plates are
electrically charged by this. If the circuit is then interrupted, the charge remains
stored in the capacitor.
The larger the capacitance of a capacitor, the greater the electrical charge it can
store for a given voltage.
If the charged capacitor is now connected to a load (closing switch S2 in Fig. 2.6),
the capacitor discharges. Current flows through the load until the capacitor is
fully discharged.
If a diode is inserted into an AC circuit, the current can only flow in one direction.
The current is rectified.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 16
Fig. 2.5: Function of a diode
Measurement
Measurement means comparing an unknown variable (such as the length of a
pneumatic cylinder) with a known variable (such as the scale of a measuring
tape). A measuring device (such as a ruler) allows such measurements to be
made. The result – the measured value – consists of a numeric value and a unit
(such as 30.4 cm).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 17
Multi-meters. These devices can be switched between various modes:
DC current and voltage, AC current and voltage.
Current, voltage and resistance
The multi-meter can only measure correctly if the correct mode is set.
Devices for measuring voltage are also called voltmeters. Devices for measuring
current are also called ammeters.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 18
Danger
Before carrying out a measurement, ensure that voltage of the controller on
which you are working does not exceed 24 V!
Measurements on parts of a controller operating at higher voltages (such
as 230 V) may only be carried out by persons with appropriate training or
instruction.
Incorrect measurement methods can result in danger to life.
Please read the safety precautions in Chapters 3 and 7!
Voltage measurement
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 19
Fig. 2.7: Voltage measurement
Current measurement
For current measurement, the measuring device (ammeter) is connected in series to the
load. The entire current flows through the device.
Each ammeter has an internal resistance. In order to minimize the measuring error, the
resistance of the ammeter must be as small as possible.
Resistance measurement
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 20
Indirect measurement measures the current through the load and the voltage
across the load (Fig. 2.9a). The two measurements can either be carried out
simultaneously or one after the other. The resistance is then measured using
Ohm's law.
For direct measurement the load is separated from the rest of the circuit (Fig.
2.9b). The measuring device (ohmmeter) is set to resistance measurement mode
and connected to the terminals of the load. The value of the resistance is
displayed.
If the load is defective (for example, the magnetic coil of a valve is burned out), the
measurement of resistance either results in a value of zero (short-circuit) or an infinitely
high value (open circuit).
Warning!
The direct method must be used for measuring the resistance of a load in AC circuits.
Sources of error
Measuring devices cannot measure voltage, current and resistance to any desired
degree of accuracy. The measuring device itself influences the circuit it is measuring, and
no measuring device can display a value precisely. The permissible display error of a
measuring device is given as a percentage of the upper limit of the effective range. For
example, for a measuring device with an accuracy of 0.5, the display error must not
exceed 0.5 % of the upper limit of the effective range.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 21
Application example:
Display error
A Class 1.5 measuring device is used to measure the voltage of a 9 V battery. The range
is set once to 10 V and once to 100 V. How large is the maximum permissible display
error for the two effective ranges?
The example shows clearly that the permissible error is less for the smaller range. Also,
the device can be read more accurately. For this reason, you should always set the
smallest possible range.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 22
3. Components and assemblies in the electrical signal control section
Fig. 3.1: Component parts of a power supply unit for an electro-pneumatic controller.
Safety precaution!
Because of the high input voltage, power supply units are part of the power
installation (DIN/VDE 100).
Safety regulations for power installations must be observed.
Only authorized personnel may work on power supply units.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 23
3.2. Push button and control switches
Switches are installed in circuits to apply a current to a load or to interrupt the
circuit. These switches are divided into pushbuttons and control switches.
Control switches are mechanically detent in the selected position. The
switch position remains unchanged until a new switch position is selected.
Example: Light switches in the home.
Push button switches only maintain the selected position as long as the
switch is actuated (pressed). Example: Bell push.
In the case of a normally open contact, the circuit is open if the switch is in its
initial position (not actuated). The circuit is closed by pressing the push button
– current flows to the load. When the plunger is released, the spring returns
the switch to its initial position, interrupting the circuit.
In this case, the circuit is closed when the switch is in its initial position. The
circuit is interrupted by pressing the pushbutton.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 24
Fig. 3.3: Normally open contact (break) – section and symbol
Changeover contact
The changeover contact combines the functions of the normally open and
normally closed contacts in one device. Changeover contacts are used to
close one circuit and open another in one switching operation. The circuits are
momentarily interrupted during changeover.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 25
3.3. Sensors for measuring displacement and pressure
Sensors have the task of measuring information and passing this on to the signal
processing part in a form that can easily be processed. In electro-pneumatic
controllers, sensors are primarily used for the following purposes:
N To detect the advanced and retracted end position of the piston rod in
cylinder drives
To detect the presence and position of work pieces
To measure and monitor pressure
Limit switches
A limit switch is actuated when a machine part or work piece is in a certain position.
Normally, actuation is effected by a cam. Limit switches are normally changeover
contacts. They can then be connected – as required – as a normally open contact,
normally closed contact or changeover contact.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 26
Proximity switches
As a result, proximity switches have a long service life and high switching reliability. The
following types of proximity switch are differentiated:
• Reed switch
Reed switch
Reed switches are magnetically actuated proximity switches. They consist of two contact
reeds in a glass tube filled with inert gas. The field of a magnet causes the two reeds to
close, allowing current to flow. In reed switches that act as normally closed contacts, the
contact reeds are closed by small magnets. This magnetic field is overcome by the
considerably stronger magnetic field of the switching magnets. Reed switches have a
long service life and a very short switching time(approx. 0.2 ms). They are maintenance-
free, but must not be used in environments subject to strong magnetic fields (for
example in the vicinity of resistance welders).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 27
Electronic sensors
Inductive, optical and capacitive proximity switches are electronic sensors. They normally
have three electrical contacts.
In these sensors, no movable contact is switched. Instead, the output is either electrically
connected to the supply voltage or to ground (= output voltage 0 V).
There are two types of electronic sensor with regard to the polarity of the output
voltage.
An inductive proximity sensor consists of an electrical oscillator (1), a flip-flop (2) and an
amplifier (3). When a voltage is applied, the oscillator generates a high frequency
alternating magnetic field that is emitted from the front of the sensor. If an electrical
circuit is introduced into this field, the oscillator is attenuated. The downstream circuitry,
consisting of a flip-flop and an amplifier, evaluates the behaviour of the oscillator and
actuates the output.
Inductive proximity sensors can be used for the detection of all good electrical
conductors (materials). In addition to metals, these include, for example, graphite.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 28
Fig. 3.7: Inductive proximity sensor
Capacitive proximity sensors not only react to highly conductive materials (such as
metals) but also to insulators of high dielectric strength (such as plastics, glass, ceramics,
fluids and wood).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 29
Fig. 3.8: Capacitive proximity sensor
Optical proximity sensors use optical and electronic means for object detection. Red or
infrared light is used. Semiconductor light-emitting diodes (LEDs) are particularly
reliable sources of red or infrared light. They are small and rugged, have a long service
life and can be simply modulated. Photodiodes or phototransistors are used as a
receiver. Red light has the advantage that the light beam can be seen during adjustment
of the optical axes of the proximity switch. Polymer optical fibres can also be used
because of their low attenuation of light of this wavelength.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 30
One-way light barrier
The one-way light barrier has spatially separate transmitter and receiver units. The parts
are mounted in such a way that the transmitter beam is directed at the receiver. The
output is switched if the beam is interrupted.
In the reflective light barrier, the transmitter and receiver are mounted together in one
housing. The reflector is mounted in such a way that the light beam transmitted by the
transmitter is practically completely reflected to the receiver. The output is switched if
the beam is interrupted.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 31
Diffuse reflective optical sensor
In the diffuse reflective optical sensor, the transmitter and receiver are mounted
together in one unit. If the light hits a reflective object, it is redirected to the receiver
and causes the output of the sensor to switch. Because of the functional principle, the
diffuse reflective optical sensor can only be used if the material or machine part to be
detected is highly reflective (for example polished metal surfaces, bright paint).
Pressure sensors
In the mechanically actuated pressure switch, the pressure acts on a cylinder surface. If
the pressure exerted exceeds the spring force of the return spring, the piston moves and
operates the contact set.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 32
Fig. 3.12: Piston-actuated pressure switch
Fig. 3.13a shows the piezo resistive measuring cell of a pressure sensor. Variable resistor
1 changes its value when pressure is applied to the diaphragm. Via the contacts 2, the
resistor is connected to the electronic evaluating device, whichgenerates the output
signal.
Fig. 3.13c illustrates the sensor characteristics, representing the correlation between the
pressure and the electrical output signal. Increasing pressure results in increasing
voltage at the sensor output. A pressure of 1 bar causes a voltage or 1V, a pressure of 2
bar a voltage of 2 V etc.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 33
Fig. 3.13: Construction and characteristic curve of an analogue pressure sensor (Festo
SDE-10-10V/20mA)
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 34
3.4. Relays and contactors
Construction of a relay
A relay is an electromagnetically actuated switch. When a voltage is applied to
the solenoid coil, an electromagnet field results. This causes the armature to be
attracted to the coil core. The armature actuates the relay contacts, either closing
or opening them, depending on the design. A return spring returns the armature
to its initial position when the current to the coil is interrupted.
A relay coil can switch one or more contacts. In addition to the type of relay
described above, there are other types of electromagnetically actuated switch,
such as the retentive relay, the time relay, and the contactor.
Applications of relays
In electro-pneumatic control systems, relays are used for the following functions:
• Signal multiplication
• Delaying and conversion of signals
• Association of information
• Isolation of control circuit from main circuit
In purely electrical controllers, the relay is also used for isolation of DC and AC
circuits.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 35
Retentive relay
The retentive relay responds to current pulses:
• The armature is energised when a positive pulse is applied.
• The armature is de-energised when a negative pulse is applied.
• If no input signal is applied, the previously set switch position is retained
(retention).
The behaviour of a retentive relay is analogous to that of a pneumatic double
pilot valve, which responds to pressure pulses.
Time relay
There are two types of time relay – pull-in delay and drop-out delay. With pull-in
delay, the armature is energised after a set delay; drop-out however, is affected
without delay. The reverse applies in the case of the drop-out delay relay,
whereby the contacts switch accordingly – (see Figs. 3.15, 3.16). The time delay td
can be set.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 36
Fig. 3.15: Relay with pull-in delay
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 37
Functional principle
When switch S1 is actuated, current flows via the variable resistor R1 to capacitor
C1. Diode D1 – connected in parallel – does not allow current to flow in this
direction. Current also flows via discharge resistor R2 (which is initially not of
importance). When capacitor C1 has charged in the switched position of relay K1,
the relay switches.
When S1 is released, the circuit is interrupted and the capacitor discharges
rapidly via diode D1 and the resistor R2. As a result, the relay returns immediately
to its initial position.
Variable resistor R1 allows the charging current to the capacitor to be adjusted –
thus also adjusting the time until the switching voltage for K1 is reached. If a
large resistance is set, a small current flows with the result that the delay is long.
If the resistance is low, a large current flows and the delay is short.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 38
Fig. 3.16: Relay with drop-out delay
Construction of a contactor
Contactors operate in the same way as a relay.
Typical features of a contactor are:
• Double switching (dual contacts)
• Positive-action contacts
• Closed chambers (arc quenching chambers)
These design features allow contactors to switch much higher currents than
relays.
Applications of contactors
Contactors are used for the following applications:
• Currents of 4 to 30 kW are switched via the main contacts of power contactors.
• Control functions and logical associations are switched by auxiliary contacts.
In electro-pneumatic controllers, electrical currents and power are low. For this
reason, they can be implemented with auxiliary contactors. Main or power
contactors are not required.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 40
Fig. 3.19: System components of a PLC
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 41
Fig. 3.20: Signal control section of relay control system (schematic, circuit
diagram not compliant with standard)
The components for signal input (in Fig. 3.20: inductive proximity
switches 1B1 and 1B2 are connected via the controller inputs (I1, I2
etc.) to the relay coils (K1, K2 etc. )
Signal processing is implemented by means of suitable wiring of
several relay coils and contacts.
The components for signal output (in Fig. 3.20: solenoids of directional
control valves 1M1 and 1M2) are connected to the controller outputs
(O1, O2 etc.). They are actuated via the relay contacts.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 42
Fig. 3.21: Signal control section with programmable logic controller (PLC)
Fig. 3.21 shows the signal control section of an electro-pneumatic control system in
which a PLC is used for signal processing.
The components for signal input (in Fig. 3.21: inductive proximity switches 1B1
and 1B2 are connected to the inputs of the PLC (I1, I2).
The programmable microprocessor system of the PLC undertakes all signal
processing tasks.
The components for signal output (in Fig. 3.21: solenoids of directional control
valves 1M1 and 1M2) are connected to the PLC outputs (O1, O2 etc.). They are
actuated by electronic circuits that are part of the microprocessor system.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 43
4. Electrically actuated directional control valves
4.1. Functions
An electro-pneumatic control system works with two forms of energy:
• Electrical energy in the signal control section
• Compressed air in the power section
Electrically actuated directional control valves form the interface between the two
parts of an electro-pneumatic control. They are switched by the output signals of
the signal control section and open or close connections in the power section.
The most important tasks of electrically actuated directional control valves
include:
• Switching supply air on or off
• Extension and retraction of cylinder drives
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 44
Fig. 4.1: Actuation of a pneumatic cylinder
The double-acting cylinder drive in Fig. 4.1b is actuated by a directional control valve
with five ports and two switching positions.
If no current is applied to the solenoid coil, the left cylinder chamber is vented,
the right chamber pressurized. The piston rod is retracted.
If current is applied to the solenoid coil, the directional control valve switches.
The left chamber is pressurized, the right chamber vented. The piston rod
extends.
When the current is interrupted, the valve switches back and the piston rod
retracts.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 45
4.2. Construction and mode of operation
Electrically actuated directional control valves are switched with the aid of
solenoids. They can be divided into two groups:
Spring-return valves only remain in the actuated position as long as
current flows through the solenoid.
Double solenoid valves retain the last switched position even when no
current flows through the solenoid.
Initial position
Port designation
Directional control valves are also differentiated by the number of ports and
the number of switching positions. The valve designation results from the
number of ports and positions, for example:
The following section explains the construction and mode of operation of the
major types of valve.
In its initial position, the working port 2 is linked to the exhaust port 3
by the slot in the armature (see detail) (Fig. 4.2a).
If the solenoid is energised, the magnetic field forces the armature up
against the pressure of the spring (Fig. 4.2b). The lower sealing seat
opens and the path is free for flow from pressure port 1 to working
port 2. The upper sealing seat closes, shutting off the path between
port 1 and port 3.
If the solenoid coil is deenergized, the armature is retracted to its initial
position by the return spring (Fig. 4.2a). The path between port 2 and
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 46
port 3 is opened and the path between port 1 and port 2 closed. The
compressed air is vented via the armature tube at port 3.
Manual override
The manual override A allows the path between port 1 and port 2 to be
opened even if the solenoid is not energized. When the screw is
turned, the eccentric cam actuates the armature. Turning the screw
back returns the armature to its initial position.
Fig. 4.2: 3/2-way solenoid valve with manual override (normally closed)
Fig. 4.3 shows an electrically actuated 3/2-way valve, normally open. Fig. 4.3a shows the
valve in its initial position, Fig. 4.3b actuated. Compared to the initial position of the
closed valve (fig. 4.2) the pressure and exhaust ports are reversed.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 47
Fig. 4.3: 3/2-way valve with manual override (normally open)
In pilot controlled directional control valves, the valve piston is indirectly actuated.
If the coil is de-energized, the armature is pressed against the lower sealing seat
by the spring. The chamber of the upper side of the piston is vented (Fig. 4.4a).
If the coil is energized, the solenoid pulls the armature down. The chamber on
the upper side of the piston is pressurized (Fig. 4.4b).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 48
Fig. 4.4: Pilot controlled directional control valve
Fig. 4.5 shows two cross-sections of an electrically actuated pilot controlled 3/2-way
valve.
In its initial position, the piston surface is only subject to atmospheric pressure, so
the return spring pushes the piston up (Fig. 4.5a). Ports 2 and 3 are connected.
If the solenoid coil is energized, the chamber below the valve piston is connected
to pressure port 1 (Fig. 4.5b). The force on the upper surface of the valve piston
increases, pressing the piston down. The connection between ports 2 and 3 is
closed, the connection between ports 1 and 2 opened. The valve remains in this
position as long as the solenoid coil is energized.
If the solenoid coil is de-energized, the valve switches back to its initial position.
A minimum supply pressure (control pressure) is required to actuate the pilot controlled
valve against the spring pressure. This pressure is given in the valve specifications and
lies – depending on type – in the range of about 2 to 3 bar.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 49
Fig. 4.5: Pilot controlled 3/2-way solenoid valve (normally closed, with manual override)
The greater the flow rate of a directional control valve, the higher the flow.
In the case of a directly actuated valve, flow to the consuming device is released by the
armature (see Fig. 4.2). In order to ensure a sufficiently large opening and sufficient flow
rate, a relatively large armature is required. This in turn requires a large return spring –
against which the solenoid must exert a large force. This results in relatively large
component size and high power consumption.
In a pilot controlled valve, flow to the consuming device is switched by the main stage
(Fig. 4.5). The valve piston is pressurized via the air duct. A relatively small airflow is
sufficient, so the armature can be comparatively small with low actuation force. The
solenoid can also be smaller than for a directly actuated valve. Power consumption and
heat dissipation are lower.
The advantages with regard to power consumption, size of solenoids and heat
dissipation have led to almost exclusive use being made of pilot controlled directional
control valves in electro-pneumatic control systems.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 50
Pilot controlled 5/2-way valve
Fig. 4.6 shows the two switching positions of an electrically actuated pilot controlled
5/2-way valve.
In its initial position, the piston is at the left stop (Fig. 4.6a). Ports 1 and 2 and
ports 4 and 5 are connected.
If the solenoid coil is energized, the valve spool moves to the right stop (Fig.
4.6b). In this position, ports 1 and 4 and 2 and 3 are connected.
If the solenoid is de-energized, the return spring returns the valve spool to its
initial position.
Pilot air is supplied via port 84.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 51
Pilot controlled 5/2-way double solenoid valve
Fig. 4.7 shows two cross-sections of a pilot controlled 5/2-way double solenoid valve.
If the piston is at the left stop, ports 1 and 2 and 4 and 5 are connected (Fig.
4.7a).
If the left solenoid coil is energized, the piston moves to the right stop and
ports 1 and 4 and 2 and 3 are connected (Fig. 4.7b).
If the valve is to be retracted to its initial position, it is not sufficient to de-
energized the left solenoid coil. Rather, the right solenoid coil must be
energized.
If neither solenoid coil is energized, friction holds the piston in the last position
selected. This also applies if both solenoids coils are energized simultaneously, as
they oppose each other with equal force.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 52
5/3-way valve with exhausted initial position
Fig. 4.8 shows the three switching positions of an electrically actuated, pilot
controlled 5/3-way valve.
In its initial position, the solenoid coils are de-energized and the piston spool
is held in the mid-position by the two springs (Fig. 4.8a). Ports 2 and 3 and 4
and 5 are connected. Port 1 is closed.
If the left solenoid coil is energized, the piston moves to its right stop (Fig.
4.8b). Ports 1 and 4 and 2 and 3 are connected.
If the right solenoid coil is energized, the piston moves to its left stop (Fig.
4.8c). In this position, ports 1 and 2 and 4 and 5 are connected.
Each position is held as long as the appropriate coil is energized. If neither coil
is energized, the valve returns to the initial mid-position.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 53
Fig. 4.8: Pilot-actuated 5/3-way double solenoid valve (mid-position exhausted)
Influence of mid-position
Directional control valves with two positions (such as 3/2-way or 5/2-way valves) allow
the extension or retraction of a cylinder. Directional control valves with three positions
(such as 5/3-way valves) have a mid-position offering additional options for cylinder
actuation. This can be demonstrated using the example of three 5/3-way valves with
different mid-positions. We will look at the behaviour of the cylinder drive when the
directional control valve is in mid-position.
If a 5/3-way valve is used in which the working ports are exhausted, the piston of
the cylinder drive does not exert any force on the piston rod. The piston rod can
be moved freely (Fig. 4.9a).
If a 5/3-way valve is used in which the all ports are closed, the piston of the
cylinder drive is held in position. This also applies ifthe piston rod is not at a stop
(Fig. 4.9b)
If a 5/3-way valve is used in which the working ports are pressurized, the piston
rod extends with reduced force (Fig. 4.9c).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 54
Fig. 4.9: Influence of mid-position of 5/3-way double solenoid valves
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 55
4.3. Types and pneumatic performance data
Electrically actuated directional control valves are manufactured in a wide range
of variants and sizes to meet different requirements in industrial practice.
A step by step approach is useful when selecting a suitable valve:
First establish the required valve type based on the task, required
behaviour in the event of power failure (for example, spring-return 5/2 way
valve).
In a second step, the manufacturer's catalogue is used to establish which
valve meets the required performance at the lowest cost. Here, not only
the cost of the valve, but also for installation, maintenance, spare parts
inventory etc. must be taken into account.
Tables 4.1 and 4.2 summarize the most commonly used valve types with their
symbols and applications.
Table 4.1: Applications and symbols for spring-return electrically actuated directional
control valves
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 56
If no valve with all required properties is available, often a valve with a different number
of ports can be used.
4/2-way valves and 5/2-way valves fulfil the same function. They are
exchangeable.
To implement the function of a 3/2-way double-solenoid valve, the working port
of a 4/2-way or 5/2-way double solenoid valve is fitted with a plug.
An electro-pneumatic control system should be designed in such a way that work pieces
are not damaged by uncontrolled motion in the event of a power failure or cable break.
The behaviour of the pneumatic cylinder under such circumstances can be determined
by the choice of directional control valve:
A spring-return 3/2-way or 5/2-way valve switches to its initial position and the
piston rod of the cylinder returns to its initial position.
A spring-centered 5/3-way valve also switches to its initial position. If the working
ports are exhausted in the initial position, the cylinder is not subject to force. If
the ports are pressurized, the piston rod extends at reduced force. If the ports are
closed, the motion of the piston rod is interrupted.
A double-solenoid valve retains its current position. The piston rod completes
the current motion.
Electrically actuated directional control valves are of modular design. The following
components are required for their operation:
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 57
A 3/2-way valve is shown in Fig. 4.10 as an example of this design principle.
Fig. 4.10: Modular design of an electrically actuated directional control valve (Festo)
On an in-line valve all pneumatic ports are threaded so that the tubes and
silencers can be fitted directly on the valve. Valves can be mounted individually,
but several valves can also be mounted together in a single manifold.
On a sub-base valve all valve ports are brought out to one side, and the holes for
the ports in the valve housing are unthreaded. Sub-base valves are mounted
individually or in groups on sub-bases or manifolds.
Application example:
Fig. 4.12 shows a valve manifold block with assembled sub-base valves. A double
solenoid valve is shown in the foreground, behind which are two spring-return
directional control valves with just one solenoid for valve actuation. The spare valve
position in the foreground is sealed with a blanking plate. The ports for the consuming
devices are visible in the foreground at the lower right.
The supply air and exhaust ports are located on the end plate facing the rear right (not
visible in the photograph).
Fig. 4.12: Mounting of electrically actuated directional control valves on a valve manifold
block (Festo)
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 59
ISO valves
Certain sub-base valves are standardized in accordance with ISO. They have
standardized dimensions, thus enabling valves from different manufacturers to be
mounted on an ISO sub-base.
The pneumatic performance data and operating conditions of three 5/2-way valves are
summarized in Table 4.3.
Table 4.3: Pneumatic performance data of electrically actuated directional control valves
(Festo)
Whether a directional control valve with a high or low flow rate should be used is
dependent on the cylinder being actuated.
A cylinder with a large piston surface or a high speed of motion calls for the use of a
valve with a high flow rate. A cylinder with a small piston surface or a low speed of
motion can be actuated by a valve with a low flow rate. The nominal size and nominal
flow rate are measures of the valve's flow characteristics.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 60
To determine the nominal size of the valve, the narrowest valve cross section through
which air flows must be found. The corresponding cross-sectional area is converted into
a circular area. The diameter of this area is the valve's nominal size.
A large nominal size results in a high flow rate, and a small nominal size in a low flow
rate.
The nominal flow rate of a valve is measured under specified conditions. A pressure of 6
bar is maintained upstream of the valve for the measurement, and a pressure of 5 bar
downstream of the valve.
On account of their flow rates, the valves described in Table 4.3 with a nominal size of 4
mm are mostly used for cylinders with a piston diameter of up to 50 mm. The valve with
a nominal size of 14 mm, on the other hand, is suitable for cylinders with a large piston
diameter where the piston rod is expected to reach high advance and retract speeds.
Pressure range
The pressure range is the range of supply pressure at which the valve can be operated.
The upper limit of the pressure is determined by the strength of the housing, the lower
limit by the pilot control stage (see Section 4.2).
If the valve actuates a drive that only operates at low pressure (such as a vacuum suction
cup), the pressure is not sufficient to actuate the pilot control stage. A valve with
separate pilot pressure supply is therefore necessary.
Response times
The response times indicate the length of time that elapses between actuation of the
contact and the valve switching over.
In spring-return valves, the response time for switching from the initial position to the
actuated position is usually shorter than for the switching operation in the opposite
direction.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 61
4.4. Performance data of solenoid coils
If the signal control section operates with AC voltage and therefore AC solenoid
coils are used, the frequency of the AC voltage must be within a specified range.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 62
For the AC coils described in the table, frequencies up to 5 % above or below 50
Hz are permissible; in other words the permitted frequency range is between 47.5
and 52.5 Hz.
Temperature data
Reliable operation of the solenoid coil can only be guaranteed if the ambient
temperature and the medium temperature, i.e. the temperature of the
compressed air, are within the specified limits.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 63
The longer the pickup time of a solenoid coil, the greater the response time of
the actuated directional control valve.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 64
Fig. 4.13: Protective circuit of a solenoid coil
Auxiliary functions
In addition to the protective circuit required for operation of the valve, further
auxiliary functions can be integrated in the cable connection, for example:
• Indicator lamp (lights up when the solenoid is actuated)
• Switching delay (to allow delayed actuation)
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 65
Fig. 4.14: Solenoid coil, adapter and socket
Class of protection
Plugs, sockets and adapters are sealed in order to prevent either dust or moisture
from entering the plug connection. If the adapter, solenoid coil and valve have
different classes of protection, the lowest of the three classes of protection
applies to the assembled valve, coil and cable conduit.
Explosion protection
If it is intended to use electrically actuated directional control valves in an
environment subject to explosion hazards, special solenoid coils approved for
such applications are required; these have moulded cables.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 66
5. Developing an electro-pneumatic control system
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 67
Fig. 5.1: Procedure for development and implementation of an electro-pneumatic
control system
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 68
5.2. Project design procedure
Project design for an electropneumatic control system involves the following (see
Fig. 5.1):
Formulation of the control task and stipulation of the requirements to be
met by the control system
Conceptual design of the control system and selection of the necessary
components
Graphical representation of the control task
Planning of the control system and preparation of diagrams and parts lists.
The various steps in project design are explained in the following, illustrated with
the aid of an example.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 69
Table 5.1: List for specifying requirements to be met by an electro-pneumatic
control system
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 70
Conceptual design of an electro-pneumatic control system
Electro-pneumatic control systems can be designed according to widely differing
concepts. Examples include:
With a PLC or with relays for signal processing
With separately installed directional control valves or with directional
control valves mounted in a valve terminal
With standard cylinders or with cylinders featuring auxiliary functions (such
as linear guides, end position cushioning, slots for attachment)
The conceptual design of the control system has a decisive influence on the
expense of further development, i.e. the cost of planning, setting up and
commissioning the control system. Measures to reduce expenditure include:
Modular control system design (use of identical circuit and program
modules for different control configurations)
Using state-of-the-art components and assemblies (such as bus systems
and valve terminals; see Chapter 9)
Selection of components
Once the overall concept of the control system is in place, the necessary
components can be chosen. These include:
Before work is started on drawing up the circuit diagrams, certain points have to
be clarified:
Clarification and illustration of the sequence is most easily done using graphical
methods, for example with a displacement-step diagram, a displacement-time
diagram, a function diagram or a function chart. The various methods are
explained in Sections 6.1 and 6.2.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 71
Control system planning, diagrams and parts list
The last stage of project engineering involves compiling all documents that are
necessary for setting up the control system. These include:
Parts list
Pneumatic circuit diagram
Electrical circuit diagram
Terminal diagram
The presentation of circuit and terminal diagrams in accordance with the relevant
standards is explained in Sections 6.3 to 6.7. Chapter 8 deals with the design of
circuit diagrams for relay control systems.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 72
Note:
The movement cycle of the lifting device is described in Table 5.2 (see positional
sketch, Fig. 5.2). It comprises four steps.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 73
Operator control
The control system of the lifting device must enable the device to be run in a
continuous cycle (continuous operation). A single cycle operating mode is also
necessary in which the sequence is processed precisely once.
The operator control equipment for the system must conform to the relevant
standards (see Section 7.4). The control panel for the lifting device is shown in
Fig. 5.3.
The following operating functions are specified in more detail in relation to the
lifting device:
"EMERGENCY STOP": When this is actuated, not only the electrical power
supply, also the pneumatic power supply must be shut down.
"Reset": This returns the system to the initial position, i.e. the piston rods
of cylinders 1A and 2A retract, the piston rod of cylinder 3A extends.
"Continuous cycle OFF": This stops the continuous cycle process. If there is
already a work piece in the device, it is transferred to the upper roller
conveyor.
The piston rods of cylinders 1A and 2A retract. The device is subsequently in its
initial position.
Fig. 5.3: Control panel of the control system for the lifting device
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 74
Ambient conditions
The electrical components of the signal control section are installed in a control
cabinet and must conform to the relevant safety regulations (see Chapter 7).
Power supply
The electrical signal control section and the main circuit are to be operated with
24 VDC. A power supply unit therefore needs to be provided to supply this
voltage.
As the linear guides of the lifting platform and of the pushing device are already
part of the station, cylinders without integrated guides are used. Double-acting
cylinders are used for drives 1A and 2A. Drive 3A takes the form of a single-acting
stopper cylinder.
Selection of cylinders
The cylinders are chosen on the basis of the requirements in terms of force and
stroke, using catalogues obtained from pneumatics manufacturers.
On account of the required drive force, cylinder 1A must have a piston diameter
of at least 40 mm, and cylinder 2A a piston diameter of at least 32 mm.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 75
• Cylinder 1A: Festo DNGUL-40-500-PPV-A
A stopper cylinder is used for drive 3A; it is extended if the compressed air supply
fails. This requirement is met by a Festo STA-32-20-P-A type cylinder, for example
In order to obtain the required behaviour for drives 1A and 2A in the event of a
power failure, the valves used are spring-centered 5/3-way valves with a closed
mid-position.
As the movements of the piston rods are relatively slow, valves of a comparatively
small nominal size are adequate. Valves with 1/8-inch ports are used to match
the smaller of the two cylinders. Directional control valves of the Festo
The supply of compressed air for all three control chains must be shut off as soon
as the electrical power supply fails or an EMERGENCY STOP is triggered. An
additional, electrically actuated, spring-return 3/2-way valve is therefore
necessary which enables the supply of compressed air only when the electrical
power supply is functioning properly and no EMERGENCY STOP device has been
actuated. In order to ensure that there is adequate flow, a Festo CPE14-M1H-
3GL-1/8 type valve is used.
Speed regulation
The advance and retract speeds of drives 1A and 2A are regulated by means of
exhaust air flow control. Function connectors reduce tubing work, because they
are screwed directly into the cylinder bore. The type of connectors required are
those with a one-way flow control function, for example Festo GRLA-1/4 (cylinder
1A) or GFLA-1/8 (cylinder 2A).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 76
Selection of proximity switches
The proximity switches are selected to match the cylinders. It makes sense to use
positive-switching sensors. For example, inductive sensors of type SMTO-1-PS-
KLED- 24 are suitable for cylinders 1A and 2A, and type SMT-8-PS-KL-LED-24 for
cylinder 3A.
For controlling the device (see movement sequence) two proximity switches are
needed for each of cylinders 1A and 2A in order to detect the forward and
retracted end positions. In the case of cylinder 3A it is sufficient to have one
sensor to detect the forward end position.
The subsequent steps of the project design process are made easier by listing the
cylinders, solenoids, sensors, control elements and indicators (Table 5.3).
Components belonging to an individual control chain are shown on the same line
of the table.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 77
Displacement-step diagram for the lifting device
The displacement-step diagram for the lifting device is shown in Fig. 5.4. It
illustrates the steps in which the piston rods of the three cylinders advance and
retract, and when the proximity switches respond.
The electrical and pneumatic circuit diagrams for the lifting device are shown in
Figs. 5.5 and 5.6. Each drive is actuated by a directional control valve. The
additional directional control valve, actuated by coil 0Y1, switches on the
compressed air.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 78
Fig. 5.5: Pneumatic circuit diagram of the lifting device
The procedure for drawing up the electrical circuit diagram for the control system of the
lifting device is explained in Section 8.8. The electrical circuit diagram is shown in Figs.
8.22, 8.25 to 8.27, 8.29 and 8.30.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 79
Fig. 5.6a: Electrical circuit diagram of the lifting device – control elements
Fig. 5.6b: Electrical circuit diagram of the lifting device – sensor evaluation
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 80
Fig. 5.6c: Electrical circuit diagram of the lifting device – switching of sequence steps
Fig. 5.6d: Electrical circuit diagram of the lifting device – circuitry of solenoid coils
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 81
5.4. Procedure for implementing the control system
Implementation of an electro-pneumatic control system entails:
• Procuring all necessary components
• Installing the control system
• Programming (if a PLC is being used)
• Commissioning the control system
Programming a PLC
If a programmable logic controller (PLC) is used, the motion sequence of the
pneumatic drives is determined by the program. The basis for developing the PLC
program is provided by either a function diagram or a function chart. Program
development can be carried out concurrently with setting up the control system.
Either a personal computer or a programming unit can be used as the tool for
program development. The procedure comprises the following steps (Fig. 5.7):
• Design the program
• Enter the program in the personal computer or the programming unit
• Translate the program
• Test the program (initially in simulation, as far as possible, i.e. on the personal
computer or with the programming unit)
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 82
Fig. 5.7: Development of a PLC program
The final functional test for the program cannot be carried out until the
Electro-pneumatic control system as a whole is commissioned. When installation
of the control system and program development is completed, the program is
loaded into the main memory of the PLC. The electro-pneumatic control system
is then prepared for commissioning.
Commissioning
Commissioning has three main purposes:
Testing operation of the control system under all conditions occurring in
practice
Carrying out the necessary settings on the control system (adjustment of
proximity switches, setting of throttles etc.)
Correcting errors in the control system
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 83
The pneumatic power section should initially be operated with reduced supply
pressure. This reduces the risk of personnel coming to harm and/or the
installation being damaged (for example if two piston rods collide) if there are
faults in the control system.
Once the control system is working faultlessly and the operator of the control system is
convinced that it is functioning properly, development is completed.
Handover of the control system from the developer to the operator involves the
following:
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 84
Maintenance, service and repair
Malfunctions and failures in a control system prove very expensive because
production or parts of production are at a standstill for the duration of the failure.
In order to avert failure, maintenance and service work is carried out at specified
intervals. Components susceptible to wear are replaced as a preventive measure.
If faults occur despite this action, the failed components have to be repaired or
replaced. Maintenance, service, troubleshooting and repair are made easier if all
components of the control system are arranged in a clear, easily accessible
layout.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 85
6. Documentation for an electro-pneumatic control system
It is essential for the circuit diagrams and terminal diagram to be available to the
maintenance staff so that malfunctions and faults can be quickly located and
corrected. In many cases troubleshooting is made easier if a function diagram or
function chart, positional sketch and parts lists are available. These records should
therefore be included with the documentation of each control system.
All documentation must be drawn up in accordance with the relevant guidelines and
standards. This is the only way of ensuring that all documents are clear,
unambiguous and easily readable.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 86
6.1. Function diagram
The sequence of motions of an electro-pneumatic control system is illustrated in
graphical form by means of a Function diagram.
Application example:
A sheet-metal bending device (positional sketch: Fig. 6.1) has two double-acting
pneumatic cylinder drives that are actuated with spring-return 5/2-way valves.
Cylinder 1A is used to clamp the work piece. Proximity switches 1B2
(forward end position) and 1B1 (retracted end position) and a 5/2-way
valve with solenoid coil 1M1 are assigned to this cylinder.
Cylinder 2A (forward end position: proximity switch 2B2, rear end position:
proximity switch 2B1, 5/2-way valve with solenoid coil 2M1) executes the
bending process.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 87
Displacement-step diagram
The movements of the piston rods are shown in the displacement-step diagram. The
individual movement steps are numbered consecutively from left to right. If there is
more than one power component, the movements of the piston rods are plotted one
below the other (Fig. 6.2). This diagram illustrates how the various movements follow on
from each other.
Note:
VDI standard 3260 "Function diagrams of driven machines and production facilities" has
been withdrawn. In this book it is still used to illustrate control sequences.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 88
Displacement-time diagram
Logical associations and mutual influencing of the various control chains can be
represented by signal lines in the function diagram. For the application examined here it
is more appropriate to represent only the drive movements in a displacement-step or
displacement-time diagram. The sequence and signal logic are better documented by
other means, for example a function chart (Section 6.2).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 89
6.2. Function chart
A function chart in accordance with DIN/EN 40719/6 can be used for graphical
representation of a control system irrespective of the technology used. Function
charts are used in many fields of automation for planning and documenting
sequence controls, for example in power stations, industrial process engineering
facilities or material flow systems.
Step field
Each step field is numbered in accordance with the sequence. The initial state of
the sequence (basic setting of the control system) is identified by a step field with
a double frame.
Command field
Each command field identifies an operation that is executed in a particular step,
and is sub-divided into three parts. (Fig. 6.5):
The nature of the command is shown in the left-hand part. Non-storing
(N), for example, means that the output is actuated for this step only.
Table 6.1 gives an overview of the possible types of commands.
The effect of the command, for example to advance a cylinder drive, is
shown in the central part.
The feedback signal acknowledging execution of the command is entered
in the right-hand part (for example in the form of a number or by
specifying the corresponding sensor).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 90
If more than one operation is executed in one step, there will be more than
one command field associated with the step.
Transition conditions
Transition from one step to the next does not take place until the associated
transition condition has been satisfied. In order to improve the overall clarity
of the function chart, the transition conditions are numbered. The numbering
refers to the step and the command whose acknowledgement is evaluated
(Fig. 6.6).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 91
Logical association of transition conditions
Parallel branching and parallel union are used in function charts when more
than two or more part sequences have to be executed in parallel. Fig. 6.8
shows a branch with two parallel sequences. When transition condition 1 is
met, both part sequences are started simultaneously. The step after the
reunion is only activated when both part sequences have been completed and
when transition condition 2 is met.
Application example:
Fig. 6.10 shows the function chart for the sheet-metal bending device (positional sketch:
Fig. 6.1). Four sequence steps are executed during one movement cycle (see Section 6.1,
Function diagram Fig. 6.2).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 93
Fig. 6.10: Function chart for the bending device
As an aid to planning and troubleshooting, the function chart has the following
advantages:
The mode of operation of the signal control section can be documented down to
the last detail.
The key characteristics of a control system can be visualized in graphical form
(important especially when planning and documenting large control systems).
The sequence-oriented structure makes it easy to determine when which step
enabling conditions are necessary and when which output signals are set.
The finalized control system can be implemented at relatively low cost on the
basis of a detailed function chart.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 94
6.3. Pneumatic circuit diagram
The pneumatic circuit diagram of a control system shows how the various
pneumatic components are connected to each other and how they interact. The
graphical symbols representing the components are arranged so as to obtain a
clear circuit diagram in which there is as little crossing of lines as possible. A
pneumatic circuit diagram therefore does not reveal the actual spatial
arrangement of the components.
In a pneumatic circuit diagram the components are represented by graphical
(circuit) symbols, which are standardized according to DIN/ISO 1219-1. It must be
possible to recognize the following characteristics from a graphical symbol:
• Type of actuation
• Number of ports and their designations
• Number of switching positions
The symbols shown on the following pages are only those for components which
are used frequently in electro-pneumatic control systems.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 95
Fig. 6.11: Graphical symbols for the power supply section
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 96
Graphical symbols for valves
The symbols for pneumatic valves are composed of one or more squares (Fig.
6.12).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 97
Types of directional control valve actuation
The following information is required in order to fully represent a directional
control valve in a pneumatic circuit diagram:
• Basic type of valve actuation
• Reset method
• Pilot control (if applicable)
• Additional forms of actuation (such as manual override, if available)
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 98
Table 6.2: Designation of working lines and pilot lines on directional control
valves
Graphical symbols for non-return valves, flow control valves and quick
exhaust valves
Non-return valves determine the direction of flow, and flow control valves
determine the flow rate in a pneumatic control circuit. With quick exhaust valves
it is possible to achieve particularly high motion speeds with pneumatic drives
because the compressed air can escape virtually un-throttled. The associated
graphical symbols are shown in Fig. 6.15.
Fig. 6.15: Graphical symbols for non-return valves, flow control valves and quick
exhaust valve
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 99
Graphical symbols for pressure control valves
Pressure control valves are used for the following functions:
• Maintaining a constant pressure (pressure regulating valve)
• Pressure-dependent changeover (pressure sequence valve)
The graphical symbols for pressure control valves are shown in Fig. 6.16.
As an alternative to a pressure control valve in an electro-pneumatic control
system it is also possible to use a directional control valve that is actuated by a
signal from a pressure switch or pressure sensor.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 100
Fig. 6.17: Graphical symbols for proportional valves
The graphical symbols for pneumatic power components are shown in Fig. 6.18.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 101
Fig. 6.18: Graphical symbols for pneumatic power components
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 102
Fig. 6.19: Other graphical symbols for pneumatic and electro-pneumatic
components
For control systems with several power components, the symbols for the various
drive units are drawn alongside each other. The symbols for the associated valves
are arranged beneath each drive symbol (Fig. 6.20).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 103
Positions of cylinders and directional control valves
All components in a pneumatic circuit diagram are represented as if the electrical
signal control section is in the de-energized condition. This means:
• The solenoid coils of the directional control valves are not actuated.
• The cylinder drives are in the initial position.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 104
Identification code for components
Every component (apart from connection lines and connecting tubes) is identified
in accordance with Fig. 6.21. The identification code contains the following
information:
• Unit number (digit; may be omitted if the entire circuit consists of one unit)
• Circuit number (digit, mandatory)
• Component identification (letter, mandatory)
• Component number (digit, mandatory)
Unit number
If there are several units and electro-pneumatic control systems in a particular
plant, the unit number helps to clarify the assignment between circuit diagrams
and control systems. All pneumatic components of a control system (unit) are
identified by the same unit number. In the example circuit diagram (Fig. 6.20) the
unit number is not shown in the identification code.
Circuit number
Preferably all components belonging to the power supply should be identified by
circuit number 0. The other circuit numbers are then assigned to the various
control chains (= circuits). The following assignments apply to the control system
shown in Fig. 6.20.
• Power supply and main switch: number 0
• Control chain "Insertion/clamping": circuit number 1
• Control chain "Drilling": circuit number 2
• Control chain "Sliding table": circuit number
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 105
Component identification and number
Every component in an electro-pneumatic control system is assigned a
component identification (identification codes: Table 6.3) and a component
number in the circuit diagram. Within each circuit, components with the same
component identification are numbered consecutively from the bottom to the
top and from left to right. The valves in the "Insertion/clamping" control chain
(circuit 1 in the circuit diagram in Fig. 6.26) are therefore identified as follows:
Directional control valve: 1V1 (circuit number 1, component identification
V, component number 1)
One-way flow control valve: 1V2 (circuit number 1, component
identification V, component number 2)
Technical information
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 106
6.4. Electrical circuit diagram
The electrical circuit diagram of a control system shows how the electrical control
components are interconnected and how they interact. Depending on the task
definition, the following types of circuit diagram are used in compliance with
DIN/EN 61082-2:
• Overview diagram
• Function diagram
• Circuit diagram
Overview diagram
An overview diagram provides an overview of the electrical apparatus of a
relatively large system, for example a packing machine or an assembly unit. It
shows only the most important interdependencies. The various subsystems are
shown in greater detail in other diagrams.
Function diagram
A function diagram illustrates the individual functions of a system. No account is
taken of how these functions are executed.
Circuit diagram
A Circuit diagram shows the details of the design of systems, installations,
apparatus etc. It contains:
• Graphical symbols for the items of equipment
• Connections between these items
• Equipment identifiers
• Terminal identifiers
• Other details necessary for tracing the paths (signal identifiers, notes on the
representation location
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 107
Electrical circuit diagram of an electro-pneumatic control system
A circuit diagram with distributed representation is used to represent the signal
control section in electro-pneumatics. It is only if control systems are very large
that an overview diagram or function diagram is prepared in addition.
Electrical symbols
In a circuit diagram the components are represented by graphical symbols that
are standardized according to DIN 40900. Symbols used to represent electrical
components that are frequently found in electro-pneumatic control systems are
shown in Figs. 6.22 to 6.27.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 108
Fig. 6.23: Graphical symbols for contacts: basic functions and delayed actuation
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 109
Fig. 6.25: Graphical symbols for electromechanical drive
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 111
Current paths
The individual current paths of an electro-pneumatic control system are drawn
alongside each other in the circuit diagram and numbered consecutively. The
circuit diagram of an electro-pneumatic control system shown in Fig. 6.28 has 10
current paths. Current paths 1 to 8 belong to the control circuit, current paths 9
and 10 to the main circuit.
Identification of components
The components in the circuit diagram of a control system are identified by a
letter in accordance with Table 6.4. Components with identical identifying letters
are assigned consecutive numbers (for example 1S1, 1S2 etc.).
Sensors and valve coils must be represented both in the pneumatic circuit
diagram and the electrical circuit diagram. In order to ensure that there is no
ambiguity and that the diagrams are easy to read, the symbols in both types of
diagram should be identified and numbered in the same way. For example, if a
certain limit switch is designated 1S1 in the pneumatic circuit diagram, the same
identification should also be used in the electrical circuit diagram.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 112
Table 6.4: Designation of components in an electrical circuit diagram (DIN 40719, Part 2)
Fig. 6.30 shows a sectional view of a relay with its associated terminal designations. The
terminals of a relay coil are designated A1 and A2.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 113
Table 6.5: Function numbers for contacts
Fig. 6.29: Contact designation by means of function numbers and sequence numbers
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 114
Example of terminal designations for a relay
In the circuit diagram in Fig. 6.28, the terminals of relay K1 are identified as follows:
All contacts actuated by a relay coil or contactor coil are listed in a contact element
table. The contact element table is placed beneath the current path containing the relay
coil. Contact element tables may be shown in either simplified or detailed form (Fig.
6.31).
Fig. 6.31: Contact element table for a relay in simplified and detailed form
There are a total of 4 contact element tables in the circuit diagram in Fig. 6.28:
The electrical circuit diagram is shown in the de-energized state (electric power supply
switched off). If limit switches are actuated in this position, they are identified by an
arrow (Fig. 6.32). The associated contacts are also shown in the actuated position.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 115
Fig. 6.32: Representation of actuated contacts in a circuit diagram
The large number of components and the distances between them make wiring a
significant cost factor in an electro-pneumatic control system.
Wiring requirements
The wiring of an electro-pneumatic control system must satisfy the following
requirements:
Cost-effective design (use of components which allow speedy wiring while
maintaining a good price/performance ratio, optimization of the circuit
diagram in terms of wiring expense, use of components with reduced
number of terminals)
Simple troubleshooting (clear wiring which is accurately documented and
is easy to follow)
Swift repair (simple replacement of components by means of terminal or
plug-in connections, no soldered-on components.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 116
Fieldbus systems
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 117
Wiring with terminal strips
A terminal has two receptacles for electrical lines; these are arranged one
beneath the other and have an electrically conductive connection (Fig. 6.34).
All terminals are attached to a strip, alongside each other. Electrically
conductive connections between adjacent terminals can be established with
straps or jumpers.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 118
Terminal allocation
In the circuit diagram, each terminal is represented by a circle (Fig. 6.37). The terminals
are identified by the letter X, and are numbered consecutively in sequence within the
terminal strip (terminal designation X1, X2 etc. for example). If there is more than one
terminal strip, each strip is also assigned a sequence number (terminal designation X2.6,
for example, for the 6th terminal of terminal strip 2).
The terminal allocation list itemizes the allocations of all terminals of one strip in order.
If the control system has more than one terminal strip, a separate list is produced for
each strip. Terminal allocation lists are used as aids for control system installation,
troubleshooting (measuring signals at the terminals) and repair.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 119
Preparation of a terminal connection diagram
The basis on which to produce the terminal connection diagram is the circuit diagram
with no terminal allocations shown. The terminal connection diagram is drawn up in two
stages:
1. Allocation of terminal numbers and drawing the terminals in the circuit diagram.
Application example:
The circuit diagram of a control system without the terminal markings (Fig. 6.35)
A printed form for a terminal allocation list (Fig. 6.36)
Fig. 6.35: Pneumatic circuit diagram and electrical circuit diagram of an electro-
pneumatic control system
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 120
Fig. 6.36: Printed form for a terminal allocation list
In the circuit diagram in Fig. 6.37, the components are allocated to terminals X1-9 to X1-17.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 121
Fig. 6.37: Circuit diagram with terminals entered
Entries are made in the terminal allocation list in the following steps:
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 122
Fig. 6.38: Terminal allocation list for the example control system
The structure of a terminal allocation list is based on the design of the terminal strip.
Accordingly, an electro-pneumatic control system can largely be wired up on the
basis of the terminal allocation list (Fig. 6.38):
All lines running to components outside the control cabinet are connected in
accordance with the list on the left-hand side of the terminal strip.
All lines running to components inside the control cabinet are connected in
accordance with the list on the right-hand side of the terminal strip.
Adjacent terminals on which a bridge has been drawn in the terminal
allocation list are connected to each other.
Lines linking two components inside the control cabinet are not routed via the
terminal strip. They are therefore not included in the terminal allocation list and have
to be wired up according to the circuit diagram.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 123
7. Safety measures for electro-pneumatic control systems
Fig. 7.1: Moving parts of machines and equipment: sources of danger and protective
measures
Electric current is another source of danger. The dangers and protective measures
relating to electric current are summarized in Fig. 7.2.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 124
Safety rules!
In order to provide the best possible safeguards for operating personnel, various
safety rules and standards must be observed when designing electro-pneumatic
control systems. The key standards dealing with protection against the dangers
of electric current are listed below:
Protective Measures for Electrical Power Installations up to 1000 V (DIN
VDE 0100)
Specifications for Electrical Equipment and Safety of Machines (DIN/EN
60204)
Degrees of Protection of Electrical Equipment (DIN-VDE 470-1)
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 125
RM = RU1 + RI + RU2
The contact resistances RU1 and RU2 vary greatly depending on the contact
surface and the moistness and thickness of the skin. This affects the total
resistance RM. It may range between the following extremes:
Less than 1000 ohms (large contact surfaces, wet, sweaty skin)
Several million ohms (point contact, very dry, thick skin)
The current I through the human body is dependent on the source voltage V,
the resistance RL of the electric line, the resistance RM of the person and the
resistance RE of the ground (Fig. 7.3d). It is calculated as follows:
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 126
When touching a conductor at a low contact resistance RU and
consequently low resistance RM (such as with large contact surfaces,
sweaty skin, wet clothing)
There are a wide variety of protective measures which prevent the operator of an
electro-pneumatic control system from being put at risk from electric current.
Grounding
Components which are liable to be touched by anyone must be grounded. If a
grounded housing becomes live, the result is a short circuit and the overcurrent
protective devices are tripped, interrupting the voltage supply. Various devices
are used for overcurrent protection:
• Fuses
• Power circuit-breakers
• Fault-current-operated circuit-breakers
• Fault-voltage-operated circuit-breakers
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 127
Safety extra-low voltage
There is no risk to life when touching an electric conductor carrying a voltage of
less than approximately 30 V because only a small current flows through the
body.
For this reason, electro-pneumatic control systems are not normally operated at
the voltage of the electrical supply network (such as 230 V AC) but at 24 V DC.
The supply voltage is reduced by a power supply unit with an isolating
transformer (see Section 3.1).
Despite this precaution, the electrical wiring at the inputs to the power supply
unit carry high voltage.
Main switch
Every machine and installation must have a main switch. This switch is used to
switch off the supply of electric power for the duration of cleaning, maintenance
or repair work and for lengthy shut down periods. The main switch must be
manually operated and must have only two switch positions: "0" (Off) and "1"
(On). The Off position must be lockable in order to prevent manual starting or
remote starting. If there is more than one incoming supply, the main switches
must be interlocked such that no danger can arise for the maintenance
personnel.
EMERGENCY STOP
The EMERGENCY STOP control switch is actuated by the operator in dangerous
situations.
Once the EMERGENCY STOP device has been actuated the drives must be shut
down as quickly as possible and the control system should be isolated from the
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 128
electrical and pneumatic power supplies where feasible. The following limitations
have to be observed, however:
If illumination is necessary, this must not be switched off.
Auxiliary units and brake devices provided to aid rapid shutdown must not
be rendered ineffective.
Clamped work pieces must not be released.
Retraction movements must be initiated by actuation of the EMERGENCY
STOP device where necessary. Such movements may however only be
initiated if this can be done without danger
An electro-pneumatic control system has other control elements in addition to the main
and EMERGENCY STOP switch. An example of a control panel is shown in Fig. 7.5.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 129
A distinction is drawn between two different types of operation for electro-pneumatic
control systems:
Manual operation
Automatic, i.e. program-controlled operation
Manual operation
Automatic operation
Pressing the "Continuous cycle OFF" pushbutton (or a "Stop" button) interrupts the
sequence. The interruption occurs either after the next step or after completion of the
entire sequence.
The main switch and EMERGENCY STOP switch are effective in all operating modes. They
must be available on every electro-pneumatic control system together with control
elements for "Manual" and "Automatic", "Start", "Stop" and "Reset".
Table 7.1 provides an overview of the colours of control elements and what these
colours mean, in line with EN 60204.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 130
Table 7.1: Colour coding of control elements of machine control systems
To enable operating staff to immediately identify the operating status of a system, especially
malfunctions and dangerous situations, indicator lamps are colour-coded in accordance with EN
60204. The meanings of the various colours are shown in Table 7.2.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 131
7.5. Protecting electrical equipment against environmental influences
Electrical equipment such as sensors or programmable logic controllers may be
exposed to a variety of environmental influences. The factors which may impair
operation of such equipment include dust, moisture and foreign matter.
Depending on the circumstances of installation and the environmental
conditions, electrical equipment may be protected by housings and seals. Such
measures also prevent danger to personnel handling the equipment.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 132
Table 7.4: Protection against moisture and water
Example 1: PLC
A programmable logic controller is accommodated in a metal housing which has
slits for cooling. IP 20 is specified as the degree of protection. This means:
First digit 2: protection against the ingress of foreign bodies with a
diameter greater than 12 mm, live parts protected against touching with
fingers
Second digit 0: no protection against the ingress of water or moisture
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 133
8. Relay control systems
The principal advantages of relay control systems are the clarity of their design
and the ease of understanding their mode of operation.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 134
The more complex indirect type of control is used whenever the following
conditions apply:
The control circuit and main circuit operate with different voltages (such as
24 V and 230 V).
The current through the coil of the directional control valve exceeds the
permissible current for the pushbutton (such as current through the coil:
0.5 A; permissible current through the pushbutton: 0.1 A).
Several valves are operated with one pushbutton or one control switch.
Complex links are necessary between the signals of the various
pushbuttons.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 135
Control of a double-acting cylinder
The electrical signal control section is unchanged from the control system for a single-acting
cylinder. As there are two cylinder chambers which have to be vented or pressurized, either a
4/2 or 5/2-way valve is used (Fig. 8.2a and 8.2b respectively).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 136
8.3. Logic operations
In order to produce the required movements by pneumatic cylinders, it is often
necessary to combine signals from several control elements through logic
operations.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 137
Series connection (AND circuit)
In this case the piston rod of a cylinder is to be advanced only if both pushbuttons, S1 and S2,
are pressed. The contacts of the two pushbuttons are arranged in series in the circuit diagram
(Figs. 8.4c and 8.4d).
As long as neither or only one of the two pushbuttons is pressed, the directional control
valve remains in the normal position. The piston rod is retracted.
If both pushbuttons are pressed at the same time, the directional control valve switches.
The piston rod advances.
When at least one of the two pushbuttons is released, the valve switches to the normal
position. The piston rod is retracted.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 138
Representation of logic operations in tabular form
The OR and AND operations are shown in summarized form in Tables 8.1. and 8.2.
The following values are assigned to the signals in the three right-hand columns:
In practice it is usually necessary for the piston rod to be fully advanced even if
the pushbutton is pressed only briefly. To achieve this, the directional control
valve must remain in the actuated position when the pushbutton is released; in
other words, actuation of the pushbutton must be stored.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 139
Signal storage with double solenoid valve
A double solenoid valve maintains its switching position even when the
associated solenoid coil is no longer energized. It is used as a storage element.
Manual forward and return stroke control with double solenoid valve.
Manual forward and return stroke control with double solenoid valve
The piston rod of a cylinder is to be controlled by brief actuation of two
pushbuttons (S1: advance, S2: retract).
Fig. 8.5: Manual forward and return stroke control with signal storage by double solenoid
valve
The two pushbuttons act directly and indirectly on the coils of a double solenoid
valve (Figs. 8.5c and 8.5d).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 140
When pushbutton S1 is pressed, solenoid coil 1M1 is energized. The double
solenoid valve switches and the piston rod advances. If the pushbutton is
released during the advancing movement, the piston rod continues extending to
the forward end position because the valve retains its switching position.
Fig. 8.6: Automatic return stroke control with signal storage by double solenoid valve
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 141
The circuit diagram for return stroke control is shown in Figs. 8.6b and 8.6c. When
pushbutton S1 is pressed, the piston rod advances (see previous example). When
the piston rod reaches the forward end position, current is applied to solenoid
coil 1M2 via limit switch 1S2, and the piston rod retracts.
The prerequisite for the return movement is that pushbutton S1 must first have
been released.
Fig. 8.7: Automatic forward and return stroke control with signal storage by double
solenoid valve
Initially the control system is in the normal position. The piston rod is in the
retracted position and limit switch S1 is actuated (Figs. 8.7b and 8.7c). When
contact S1 is closed, the piston rod advances. When the forward end position is
reached, limit switch 1S2 is actuated and the piston rod is retracted. Provided the
contact of S1 remains closed, another movement cycle begins when the piston
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 142
rod reaches the retracted end position. If the contact of S1 has been opened in
the meantime, the piston rod remains at the retracted end position.
When the "OFF" pushbutton is pressed the flow of current is interrupted and the
relay becomes de-energised. If the "ON" and "OFF" pushbuttons are both
pressed at the same time, the relay coil is energized. This circuit is referred to as a
dominant ON latching circuit.
The circuit in Fig. 8.8b exhibits the same behaviour as the circuit in Fig. 8.8a
provided that either only the "ON" pushbutton or only the "OFF" pushbutton is
pressed. The behaviour is different when both pushbuttons are pressed: The relay
coil is not energized. This circuit is referred to as a dominant OFF latching circuit.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 143
Manual forward and return stroke control via relay with latching function
In this case the piston rod of a cylinder is to advance when pushbutton S1 is
pressed and retract when pushbutton S2 is pressed. A relay with latching function
is to be used for signal storage.
Fig. 8.9: Manual forward and return stroke control with signal storage by latching relay
When pushbutton S1 is pressed, the relay is latched (Fig. 8.9c). The directional
control valve is actuated via another relay contact. When the latching is released
by actuation of pushbutton S2, the piston rod retracts.
As this is a dominant OFF relay circuit, actuation of both pushbuttons together
results in the piston rod being retracted or in it remaining in the retracted end
position.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 144
Comparison of signal storage by double solenoid valve and latching relay
Signal storage can be affected in the power section by means of a double
solenoid valve, or alternatively in the signal control section by means of a relay
with latching function. The various circuits behave differently in response to the
simultaneous presence of a setting and resetting signal, and in the event of
failure of the electrical power supply or a wire break (Table 8.3; see Section 4.3).
Table 8.3: Comparison of signal storage by latching circuit and double solenoid valve
8.5. Delay
Time relays with delayed switch-on or switch-off are used for tasks such as these.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 145
Fig. 8.10: Delayed return (delayed switch-on relay, storage by double solenoid valve)
Fig. 8.10b shows the electrical circuit diagram for delayed retraction. When
pushbutton S1 is actuated, the piston rod advances. When it reaches the forward
end position, limit switch 1S2 closes. Current flows through coil K2. Contact K2
remains open until the variable time delay (in this case: 10 seconds) has elapsed.
The contact is then closed, and the piston rod retracts.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 146
Application example:
Feeding device
The positional sketch of a feeding device is shown in Fig. 8.11. The end positions
of the two cylinder drives 1A and 2A are detected by the positive switching
inductive proximity switches 1B1 and 2B2.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 147
Fig. 8.12: Displacement-step diagram for the feeding device
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 148
Fig. 8.14: Procedure for designing the relay circuit diagram for the feeding device
Sensor evaluation
In a relay circuit the signals are combined with each other by the contacts of
control switches, pushbuttons and relays. The electronic proximity switches used
here do not have contacts; instead they generate an output signal by means of
an electronic circuit. Each sensor output signal therefore acts on the coil of a
relay, which in turn switches the necessary contact or contacts (Fig. 8.15). If
proximity switch 1B1 is tripped, for example, current flows through the coil of
relay K1. The related contacts switch to the actuated position.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 149
First sequence step
The following preconditions must be satisfied before the sequence is started:
Piston rod of cylinder 1A in retracted end position (proximity switch 1B1
and relay K1 actuated)
Piston rod of cylinder 2A in retracted end position (proximity switch 2B1
and relay K3 actuated)
START pushbutton (S5) actuated
If all of these conditions are met, relay coil K6 is energised. Solenoid coil 1M1 is
actuated, and the piston rod of cylinder 1A advances.
Fig. 8.16: Electrical circuit diagram with sensor evaluation and first sequence step
Fig. 8.17: Electrical circuit diagram with sensor evaluation and first and second steps of
the sequence
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 150
Third sequence step
When the piston rod of cylinder 2A reaches the forward end position, sensor 2B2
responds. The third step of the sequence is activated. Solenoid coil 1M2 is
actuated, and the piston rod of drive 1A retracts.
Fig. 8.18: Electrical circuit diagram with sensor evaluation and first, second and third
steps of the sequence
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 151
8.7. Circuit for evaluating control elements
The electro-pneumatic control systems explained in Sections 8.2 to 8.6
accomplish the functions they are required to perform. Important control
elements such as a main switch and EMERGENCY STOP switch are missing (see
Section 7.4).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 152
Fig. 8.20: Design of a relay control system with selection operating modes by pushbutton
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 153
Main switch
When the main switch is closed, relay K1 is energised. Voltage is supplied to the signal
control section and the entire system via contact K1.
EMERGENCY STOP
If the EMERGENCY STOP switch is actuated, relay K2 is de-energised and the associated
contacts switch to the normal position.
The EMERGENCY STOP line is connected to the supply voltage via the normally
closed contact of K2. Warning lamps can be actuated via this line, for example.
The "EMERGENCY STOP released" line is de-energized, causing the voltage
supply to the signal control section to be interrupted. As long as EMERGENCY
STOP applies, all control elements except the main switch are rendered
inoperative.
Manual operation
When the "Manual" pushbutton is actuated, relay K4 picks up and latches. The line
marked "Manual" in the circuit diagram is connected to the supply voltage. If relay K3 is
latched, the latching is released. The line marked "Automatic" is disconnected from the
supply voltage.
These functions can only be executed in manual mode. Power is therefore supplied to
the associated contacts and relays via the line marked "Manual".
Automatic operation
When the "Automatic" pushbutton is actuated, relay K3 is energised and latches. The
line marked "Automatic" in the circuit diagram is connected to the supply voltage. If
relay K4 is latched, the latching is released, and the line marked "Manual" is
disconnected from the supply voltage.
These functions are only possible in automatic mode. Electrical power is therefore
supplied to the associated contacts and relays via the line marked "Automatic".
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 154
If "Automatic" mode is selected (relay K3 latched) and "Continuous cycle ON" is active
(relay K5 latched), the control system runs in continuous operation. This means that
when one movement cycle is completed, the next one follows automatically.
Actuating the "Continuous cycle OFF" pushbutton releases the latching of relay K5. The
program-controlled sequence stops as soon as the last step in the sequence is
completed.
When the "Single cycle Start" pushbutton is actuated, the sequence (movement cycle) is
executed once only.
This section explains the design of a relay control system with clearly defined
requirements as to operator control, operational performance and behaviour in
the event of a fault. The control system for a lifting device is used as an example.
All requirements to be met by this control system are described in Section 5.3.
The relay control system is designed in the following order:
• Power supply
• Sensor evaluation
• Operator control
• Program-controlled sequence
• Wiring of solenoids
The flow chart (Fig. 8.21) illustrates the various steps involved in designing the
circuit diagram.
Because of the large size of the circuit, it is shown in a total of 6 partial circuit
diagrams (Figs. 8.22, 8.25 to 8.27, 8.29 and 8.30).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 155
Fig. 8.21: Procedure for designing the relay circuit diagram for a lifting device
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 156
Main switch (S1) and EMERGENCY STOP (S2) control elements
In comparison with the standard circuit in Fig. 8.20, evaluation of the main switch
and EMERGENCY STOP control elements can be simplified because the
EMERGENCY STOP signal is required in inverted form only. The associated circuit
diagram is shown in Fig. 8.22.
Fig. 8.22: Relay circuit for the main switch and EMERGENCY STOP control elements
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 157
Fig. 8.24: Pneumatic circuit diagram of the lifting device
Sensor evaluation
Electrical power is supplied to the sensors as long as the EMERGENCY STOP device is
not actuated. Relays K6 to K11 are assigned to sensors 1B1 to 3B1 and B5 (Fig. 8.25).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 158
Manual (S3) and Reset (S5) control elements
The circuit diagram for evaluation of the Manual and Reset control elements is shown in
Fig. 8.26. Evaluation of the "Manual" pushbutton is carried out in accordance with the
standard circuit (Fig. 8.20). When pushbutton S3 is pressed, relay K4 is latched (Fig. 8.26).
When the EMERGENCY STOP pushbutton is pressed, the piston rods of cylinders 1A and
2A remain at whatever intermediate position they happen to be in. In order to restore
the control system to a known status, the drives have to be returned to their initial
positions. This is the purpose of the reset process.
If "Manual" mode is selected (relay K4 latched) and the "Reset" pushbutton (S5) is
pressed, relay K12 is then latched. The reset process is ended when the piston rods of
the cylinders assume the following positions:
Cylinder 1A: retracted end position (sensor 1B1 responds, relay K6 actuated)
Cylinder 2A: retracted end position (sensor 2B1 responds, relay K8 actuated)
Cylinder 3A: forward end position (sensor 3B1 responds, relay K11 actuated)
When all three of these conditions are met, the latching of relay K12 is released via
normally closed contacts K6, K8 and K11.
Fig. 8.26: Relay circuit diagram for the "Manual" and "Reset" control elements
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 159
Automatic (S4), Continuous cycle ON (S6) and Continuous cycle OFF (S8) control
elements
Evaluation of the "Automatic", "Continuous cycle ON" and "Continuous cycle OFF"
pushbuttons is carried out in accordance with the standard circuit (Fig. 8.20).
"Continuous cycle ON" is stored by latching of relay K5 (Fig. 8.27)
Fig. 8.27: Relay circuit diagram for the "Automatic", "Continuous cycle ON" and "Continuous
cycle OFF" control elements
There are different ways of implementing a stepped sequence with a relay control
system. In this case a reset sequencer is used.
The movement process is made up of four steps (see Table 8.4). Relays K13 (step 1) to
K16 (step 4) are assigned to these four steps.
The schematic design of the reset sequencer with signal storage by latching relays is
shown in Fig. 8.28.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 160
Table 8.4: Movement process for the lifting device
Interlocking of steps
The way in which the reset sequencer works can be explained using the example of the
second step in the sequence.
If the preceding step is set (in this case: step 1, normally open contact of relay K13
closed) and the other setting conditions for step 2 are satisfied, relay K14 switches to the
latched position. The latching of relay K13 is released via the normally closed contact of
relay K14. The second step in the sequence is now set, and the first step deactivated.
To enable the sequence to be started, the fourth step of the sequence (relay K16) must
be activated. When the system is switched to automatic mode, therefore, relay coil K16
is actuated via the "Automatic" line and normally closed contact K17. Relay K16 is
latched. Current flows through the coil of relay K17 via a normally open contact of K16,
and relay K17 is also latched. No more current flows through the normally closed
contact of K17.
Note: Relays K1 to K12 are already used for the control elements and sensor evaluation.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 161
Fig. 8.28: Schematic design of a reset sequencer for the lifting device
The step enabling conditions for all 4 sequence steps are shown in table 8.5. In order to
ensure that the required sequence is obtained, none of the steps can be set unless the
relay in the preceding step has been actuated.
Table 8.5: Step enabling conditions for the four sequence steps
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 162
Relay circuit diagram for the program-controlled sequence
The relay circuit for implementing the four steps of the sequence (Fig. 8.29) is obtained
by transferring the step enabling conditions to the reset sequencer (Fig. 8.28). The way
in which this relay circuit works is explained in the following.
Fig. 8.29: Relay circuit diagram for the four sequence steps
To allow the first movement step to be activated, the following conditions must be
satisfied:
If all of these conditions are satisfied, relay K13 is latched and the first step is active.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 163
Progression from first to second step
If optical sensor B5 responds while the first step is active, the setting condition for the
second step is satisfied. The step is activated by actuation of relay K14. Relay K14 is
latched, and the latching of relay K13 is released by the normally closed contact K14.
If proximity switch 1B2 responds while the second step is active, relay K15 is latched. The
latching of relay K14 is released.
If proximity switch 2B2 responds while the third step is active, relay K16 is latched. The
latching of relay K15 is released.
The same conditions apply to progression from the fourth to the first step as to starting
of the first step.
Main circuits
The solenoid coils of the directional control valves are actuated with the main circuits.
There are 6 coils altogether. To allow power to be supplied to the coils, the main switch
must be in position 1 and the EMERGENCY STOP device must not have been actuated.
The other conditions for actuation of the solenoid coils are summarized in table 8.6.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 164
The compressed air is connected via relay K18 in order to prevent the pneumatic drives
from moving before the relays have assumed a defined position.
List of relays
All of the relays used for controlling the lifting device are listed in table 8.7, with their
associated functions.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 165
Table 8.7: Functions of the relays
All switches and pushbuttons used for controlling the lifting device are listed in Table 8.8.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 166
The complete electrical circuit diagram for the lifting device is shown in Figs. 8.31a to
8.31d.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 167
Fig. 8.31c: Electrical circuit diagram of lifting device – switching of sequence steps
Fig. 8.31d: Electrical circuit diagram of lifting device – circuitry of solenoid coils
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 168
Measures to reduce costs of equipment and installation
There are various measures which can be taken to reduce the number of relays and
contacts in comparison with the above example (Table 8.9). This reduces investment
costs and the cost of installation. Undesirable consequences do occur, however,
particularly with regard to behaviour in the event of a fault. It is greatly dependent on
the individual application whether measures to reduce the number of relays are
advisable, and if so, which ones.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 169
9. Design of Modern Electro-pneumatic Control Systems
Cost reduction
The overall costs of an electro-pneumatic control system are affected by many
factors. Accordingly, the opportunities for reducing cost are also highly diverse
(Fig. 9.1). The design of present-day electro-pneumatic control systems is
primarily aimed at reducing the cost of project planning, installation,
commissioning and maintenance.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 170
Improving performance data
Examples of how the performance data of pneumatic components can be
improved include:
• Reducing cycle times by increasing motion speeds
• Reducing mounting space and weight
• Integration of additional functions, such as linear guides
Multi-position cylinders
Multi-position cylinders are used for applications in which more than two
positions are needed. Fig. 9.2 illustrates the mode of operation of a double-
acting multi-position cylinder. One piston rod is attached to the frame, the other
is connected to the load. Four different positions can be approached precisely to
a stop.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 171
Fig. 9.2: Multi-position cylinder with four different positions
Robotics
For handling and assembly operations it is often necessary to use components
which are capable of executing movements in two or three different directions.
This field used to be dominated by special-purpose designs. Nowadays
increasing use is being made of standard, commercially available handling
modules which can be combined to suit the application. The modular approach
has the following advantages:
• Simple assembly
• Matching drive units and mechanical guides
• Integrated power supply line, such as for grippers or suction cups
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 172
Rotary/linear drive
The rotary/linear drive (Fig. 9.3a) can be used to reposition work pieces, for
example (Fig. 9.3b). The bearing assembly of the piston rod is designed to cope
with high transverse loads. The drive can be mounted in different ways, for
example with a flange on the end face or with slot nuts which are inserted into
the linear profile. If necessary, the power for the gripper or suction cup can be
supplied through the hollow piston rod.
Pneumatic grippers
Pneumatically driven grippers are used for manipulating work pieces. Various
types of gripper are shown in Fig. 9.4.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 173
Fig. 9.4: Pneumatic grippers
Fig. 9.5a shows a section through the angular gripper shown in Fig. 9.4b. It is
driven by a double-acting cylinder. Fig. 9.5b illustrates how gripper jaws (in this
case: for cylindrical work pieces) and proximity switches are attached to the
gripper.
The choice of gripper type, size and jaws is dependent on the shape and weight
of the work pieces.
Fig. 9.5: Angular gripper: drive principle, gripper jaws and proximity switch
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 174
Vacuum suction cup
Vacuum suction cups are used for handling large work pieces (such as packages),
flexible parts (such as foils) or parts with sensitive surfaces (such as optical
lenses).
Fig. 9.6a illustrates the principle of vacuum generation using an ejector. The
compressed air flows through a jet nozzle, in which it is accelerated to high
speed.
Downstream of the jet nozzle the pressure is lower than the ambient pressure. As
a result, air is sucked in from connection U, causing a partial vacuum here also.
The vacuum suction cup is attached at connection U.
Vacuum generator
The mode of operation of a vacuum generator based on the ejector principle is
illustrated in Figs. 9.6b and 9.6c. Fig. 9.6b shows the "Suction" mode. The
electrically operated 2/2-way valve 1 is open. Compressed air flows from
connection 1 through the jet nozzle to the silencer 3. As a result, a partial vacuum
is generated at the suction cup 2 and the work piece is taken up.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 175
Fig. 9.6c shows the "Release" mode. The directional control valve 2 is open, and
the compressed air is fed directly to the suction cup. The parts picked up by the
unit are rapidly ejected from the suction cup via a pressure surge from
connection 1 via valve 2.
9.3. Sensors
Increasing use is now being made of electronically operating binary sensors in
electro-pneumatics. Such sensors include:
• Inductive proximity sensors instead of reed switches
• Pneumatic-electronic converters instead of pressure switches
The absence of moving parts means that these sensors offer a longer service life
and greater reliability. Moreover, the switching point can often be set more
precisely and easily.
Position detection
Table 9.1 provides an overview of binary sensors that are used to detect
positions.
Limit valves are still widely used on account of their rugged design.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 176
Advantages of programmable logic controllers
Compared to a relay control system, a programmable logic controller offers a
whole series of inherent advantages:
Greater reliability and longer service life because it operates without
moving contacts
Less project planning work as tested programs and subprograms can be
used for a number of different control setups, whereas each relay control
circuit has to be wired and tested from scratch
Faster control development because programming and wiring can be
carried out in parallel
Simpler monitoring of stations by a higher-level host computer because a
programmable logic controller can easily exchange data with the host
computer.
If one considers not merely the hardware costs but also the expenditure on
project planning, setting up, commissioning and maintenance, a PLC is nowadays
usually the most cost-effective solution for implementation of a signal processing
system.
Today's electro-pneumatic control systems are therefore almost always equipped
with a PLC.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 177
In order to achieve a high flow rate, the interior of the housing is
redesigned to improve flow.
The wall thickness of the housing is reduced as much as possible in order
to minimize size and weight.
The valve blocks of modular design shown in Figs. 9.7b and 9.7c feature
particularly low-loss air ducting, very compact dimensions and good price-
performance. A block may consist of the following:
Fig. 9.7a shows a directional control valve module optimized for block
mounting.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 178
Fig. 9.7: Modular design of a valve block
The electrical contacts of the valve blocks in Fig. 9.7 are brought out at the
top. This allows the solenoid coils to be wired differently by using the
relevant electrical connection modules (Fig. 9.7):
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 179
a) Individual connection with separate connector for each solenoid coil
b) Multi-pin plug connection
c) Fieldbus connection
d) Actuator-sensor interface
Valve terminals
Valve blocks in which the electrical supply lines are also brought together (by multi-pin
plug, fieldbus or AS i connection) are referred to as valve terminals.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 180
sensors are connected to the input module via plugs; the input module may be
set up separately or integrated in a valve terminal. The advantages are as follows:
No need for terminal boxes and associated terminals strips (Figs. 9.15b
and 9.15c).
Faulty directional control valves and sensors can be replaced without
having to be disconnected from and reconnected to terminals.
Wiring effort is reduced.
Fig. 9.9a shows a valve terminal and an input module to which the sensors are
connected via plugs. The two components are connected to each other via a
fieldbus line.
Fig. 9.9b shows a valve terminal on which valves, sensor connections and a PLC
are combined.
Valve/sensor terminal
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 181
a. Valve terminal and separate sensor connection unit
b. Valve terminal with integrated sensor connection unit and integrated PLC
On a valve terminal with multiple connections, all electrical connections are consolidated
within the terminal on a multi-pin plug (Fig. 9.8b). A mating socket is used to connect
the cable that runs to the terminal strip in the control cabinet (Fig. 9.15b). Several valve
terminals with multi-pin connections can be connected to the terminal strip in the
control cabinet (Fig. 9.15b).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 182
Layout of a fieldbus system
The programmable logic controller and the valve terminals each have an interface
by means of which they are connected to the fieldbus. Each interface consists of a
transmitter circuit and a receiver circuit.
The fieldbus transfers information between the PLC and the valve terminals.
The power for operating the valves and sensor is transmitted via the same cable
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 183
Mode of operation of a fieldbus system
The exchange of information between the PLC and the valve terminal proceeds as
follows:
If the solenoid coil of a valve is to be actuated, for example, the PLC sends a
sequence of binary signals over the fieldbus. From this signal sequence the valve
terminal detects which solenoid coil is to be actuated and executes the
command.
If the signal status of a proximity switch changes, the valve terminal or the sensor
connection module sends a signal sequence to the programmable logic
controller. The PLC recognizes the change and takes account of it when
processing the program.
Apart from the input/output statuses, other information is exchanged over the
fieldbus, for example preventing the PLC and a valve terminal or two valve
terminals from transmitting at the same time.
Types of fieldbus
There are numerous types of fieldbus. They differ in terms of the following features:
• Electrical connection
• Transmission rate
Fieldbus systems can be divided into company-specific (proprietary) bus systems and
open bus systems which are used by various PLC manufacturers (for example Profibus).
Valve terminals and sensor connection modules are available for a great many fieldbus
systems. Only controllers and valve terminals that are designed for the same fieldbus
may be combined with each other.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 184
Wiring of a fieldbus system
When using a fieldbus, there is no need for a terminal box or any terminal strips (see Fig.
9.15c).
Fig. 9.11 shows a directional control valve that is connected to the AS interface via a
combi-socket. The two solenoid coils of the valve are actuated via the interface. In
addition, two binary sensors can be supplied with power and evaluated via the same
interface.
A continuous two-wire cable (yellow, i.e. light-coloured flat cable in Fig. 9.11)
connects the PLC to all sensors and valves. This two-wire cable supplies power to
the stations on the bus and at the same time serves to transmit signals.
The stations are clamped directly to the two-wire cable; no connectors are
needed (Fig. 9.11).
If the stations on the bus still need to be supplied with electrical power after an
EMERGENCY STOP has been triggered or if valves with a high electrical power
consumption are connected to the bus, an additional power supply is required. This is
provided via the black flat cable shown in Fig. 9.11. The power supply carried on the
yellow cable is disconnected in the event of an EMERGENCY STOP.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 185
Fig. 9.11: Directional control valve with AS interface
The AS interface is designed to allow only small units to be connected. There can be up
to four input or output signals per AS-i connection. Various types of valve terminals,
combi-sockets and input/output modules with AS-i connections are listed in Table 9.2.
Table 9.2: Examples of valve terminals, combi-sockets and input/output modules with AS-i
connections
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 186
Advantages of the actuator sensor interface
The AS interface has a number of advantages over other fieldbus systems, namely:
Information can be transmitted very quickly, such that the bus is not overloaded
even when there are a large number of stations on the bus.
The electronics for signal conversion, the bus cable and the connection between
the bus cable and the connected components are overall more cost-effective.
Thanks to extensive development work in the field of valve terminals and bus systems
there are numerous different ways of arranging and connecting the components of an
electro-pneumatic control system. A summary of the options is shown in Fig. 9.12.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 187
Selection of components and installation concept
Fig. 9.13: Factors influencing the cost of equipment, installation and maintenance of an electro-
pneumatic control system
Fig. 9.14: Decision-making criteria for determining optimum component arrangement, tube
connection and wiring
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 188
Control example
Table 9.4 indicates how many components are saved in the example control
system by using block-type valve assembly.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 189
Table 9.4: Reducing tubing effort in the example control system by using block-type
valve assembly
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 190
a) Valve blocks with conventional wiring (wiring concept 1)
b) Valve terminal with multi-pin plug connection (wiring concept 2)
c) Valve terminal with fieldbus connection (wiring concept 3)
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 191
Table 9.5: Amount of wiring needed for the example control system (conventional wiring)
The amount of wiring needed for the 5 different concepts is shown in Table 9.6.
Table 9.6: Comparison of amount of wiring needed for the example control system
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 192
Wiring concept 2: Multi-pin plug connection
All valves and sensor connections in the control system are arranged on one
valve terminal. If the valve terminal is connected via a multi-pin connector, the
equipment not needed in comparison with the conventional wiring concept is the
terminal box, terminal strip 2 and the cables to the solenoid coils (Table 9.6).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 193
Table 9.7: Characteristics and main areas of application of various wiring concepts
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 194
Fig. 9.16: Design of an electro-pneumatic control system using the AS-interface
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 195
Function of a proportional pressure regulating valve
A proportional pressure valve converts a voltage, its input signal, into a pressure, its
output signal. The pressure at the output to a consuming device can be adjusted
continuously from 0 bar to a maximum of, for example, 6 bar.
Fig. 9.18a shows proportional pressure regulating valves of various nominal sizes.
Fig. 9.17a is an illustration of a device for testing office chairs. In order to test the long-
term durability of the backrest spring, a periodically changing force is applied to the
chair. The maximum force and the characteristics of the force as a function of time can
be varied in such a way as to run different test cycles. Two possible characteristics of
force as a function of time are shown in Fig. 9.17b.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 196
Control of the test apparatus
The electro-pneumatic control system for the test apparatus operates according to the
following principle:
When the voltage at the output of the PLC is increased, the proportional valve raises
the pressure in the cylinder chamber. The piston force increases. When the voltage at
the output of the PLC is decreased, the proportional valve lowers the pressure in the
cylinder chamber. The piston force decreases.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 197
Equivalent circuit diagram of a proportional pressure regulating valve
Fig. 9.18b shows the equivalent circuit diagram of a proportional pressure regulating
valve. The valve has a compressed air supply port, a consumer port and an exhaust
port. The two electrical connections have the following functions:
The signal input on the valve is connected to the analogue output of the
electrical control system.
On the signal output of the valve, the pressure prevailing at the consuming
device output can be tapped in the form of an analogue electrical signal.
Connection of this output is not essential for operation of the valve.
The pressure at the consumer port is measured with a pressure sensor. The measured
value is compared to the pressure set point.
If the pressure set point is higher than the actual pressure value, switching valve
A is opened (Fig. 9.18b). The pressure on the upper side of the pressure balance
increases. As a result, the consumer port is connected to the supply port.
Compressed air flows to the consumer port. The pressure at the consumer port
increases. The pressure on both surfaces of the pressure balance is matched, and
the balance moves back to its initial position. When the required pressure is
reached, the valve closes.
If the pressure set point is lower than the actual pressure value, switching valve B
is opened. The pressure on the upper side of the pressure balance decays. The
consumer port is connected to the exhaust side. The pressure at the consumer
port falls, and the pressure balance moves to its initial position.
Fig. 9.18c shows the pressure characteristic at the consumer port for three different but
constant input voltages. The pressure is kept constant over large ranges, irrespective of
the flow rate through the valve. It is only at a very high flow rate that the pressure falls.
The connections between the valve ports can be opened and shut off. The flow rate can
be varied between zero and the maximum value.
Fig. 9.19a shows proportional directional control valves of various nominal sizes.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 198
Application of a proportional directional control valve
A proportional directional control valve allows continuous adjustment of the valve flow
rate and therefore the speed of travel of the piston rod of a pneumatic cylinder.
This means that the speed characteristic can be optimized, enabling high speeds to be
achieved with gentle acceleration and braking (Fig. 9.19d). Applications are found in
conveying sensitive goods (for example in the food industry).
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 199
Equivalent circuit diagram of a proportional directional control valve
Fig. 9.19b shows the equivalent circuit diagram of a 5/3-way proportional valve. The
valve adopts different switching positions according to the analogue electrical input
signal (= manipulated variable):
Input signal below 5 V: ports 1 and 2 are connected, and ports 4 and 5
Input signal 5 V: valve closed (mid-position)
Input signal above 5 V: ports 1 and 4 are connected, and ports 2 and 3
The valve opening is also adjusted as a function of the manipulated variable. The
relationship between the manipulated variable and the flow rate is described by the
flow/signal function (Fig. 9.19c):
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 200
Application example for a pneumatic positioning drive
Pneumatic positioning drives are used in handling, for example, or for palletizing or
assembly. Fig. 9.20 shows a facility in which drink cartons are sorted into packaging with
the aid of a pneumatic positioning drive.
MCE14-ME Elective 1
EROSJ -SLSU-CEN-ME Page 201