0% found this document useful (0 votes)
39 views32 pages

Catalouge

The document is a product catalogue for Advance Metering Technology Limited (AMTL) that includes information on their three business divisions: power generation, energy meters and devices, and energy consulting services. AMTL generates power through renewable sources like wind, solar, biomass and hydro. They manufacture energy meters and systems and provide energy auditing, consulting and efficiency services. The catalogue describes their product offerings within each division.

Uploaded by

Shokaut
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
39 views32 pages

Catalouge

The document is a product catalogue for Advance Metering Technology Limited (AMTL) that includes information on their three business divisions: power generation, energy meters and devices, and energy consulting services. AMTL generates power through renewable sources like wind, solar, biomass and hydro. They manufacture energy meters and systems and provide energy auditing, consulting and efficiency services. The catalogue describes their product offerings within each division.

Uploaded by

Shokaut
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 32

Product Catalogue

GENERATE, MEASURE & MANAGE ENERGY

driving
innovation
and life
Advance Metering Technology Limited (AMTL) is an energy centric Organization engaged in Power Generation through Renewable
resources, Energy Measurement and Energy Management. AMTL is focused on ensuring a Power Generation from renewable sources,
manufacturing of world class Energy Measurement Devices and Energy Audit Services.
The three business verticals are uniquely poised towards conservation of natural resources, Clean Environmental Practices and reduction of
our dependence on fossil fuels.
Our large team of Engineers and Specialists work relentlessly identify develop and deploy the latest technologies and products and
solutions for our Customers.
AMTL is promoted by the PKR Group, which has been involved in the Electrical and Lighting business for nearly 60 years. The PKR Group is
headed by Mr. P K Ranade , one of the founder promoters of Indo Asian Fusegear Ltd (IAFL), a public limited company and a pioneer in the
Electrical Switchgear Industry.
AMTL was created by de-merger process of IAFL to create a company that is a energy specialist company and it has now multiple business
verticals under its portfolio of products and services.
Power Generation Energy Meters and Devices Energy Consulting Services
Wind Energy Smart Metering Energy Audit
Bio-fuels and Biomass Energy Remote Metering Trainings to Improve Energy Ef ciency
Solar Energy Energy Management Systems Power Analysis
Hydro-Power En M S (ISO 50001)
GENERATION
AMTL has already forayed into the eld of power generation by successfully commissioning 11.7 MW capacity of wind power generation in
the Jaisalmer district of Rajasthan in 2012. AMTL intends to invest strategically in RENEWABLE energy technologies and establish itself as
a signi cant IPP (Independent Power Producer) within the next 4 years.
AMTL has plans to enhance its base of generation to commission 50 MW of power generation capacity in India and overseas in next 4 years.
The focus of Power Division is power production through renewable energy technologies using Wind, Mini-Hydro, Solar & Biomass. The rst
pilot Biomass Power Plant in U.P., India, is planned to be operational in July 2014. A 20 MW Solar Project is also planned in Rajasthan, India
in 2014.
MEASUREMENT
The company manufactures a wide range of energy meters and systems designed for the distribution networks of tomorrow. A dedicated
and experienced R & D team develops and constantly innovates our modern range of meters to exceed our customer needs.
The company has expanded its manufacturing capability in response to the growing demand for Energy meters and metering systems by
substantially expanding the existing facility in Noida. A new modern factory is under construction for new projects using the best global
practices and systems. A focused Sales & Marketing team, at key locations across India, caters to every market and customer segment.
ENERGY AUDIT AND MANAGEMENT
The objective of this division is to provide solutions for the ef cient management of energy for all business enterprises.
Energy Audits form one of the core product offerings for our customers. This involves a detailed inspection and survey of the total energy
consumption in a building, process or system with the end objective of reducing the amount of energy used without impacting existing
performance.
The available consumer base of this division ranges from single residential consumer to the largest industrial establishment or commercial
complex.
However, our customers broadly include the following categories:
Commercial - Malls, Commercial Buildings etc Industrial Energy intensive industrial establishments.
Hospitality Hotel and Resort Complexes.
This division has a large team of Certi ed Energy Auditors with Industry and Consumer speci c expertise in:
 Lighting Control  HVAC Systems  Electrical Distribution  Energy Systems
This team is equipped with a complete range of state of the art Monitoring and Measurement Equipment required to capture and track every
variable involved in the energy audit process.
In addition to the Audit services, AMTL is also equipped to supply all the products and equipment needed to achieve the required saving
potential.
The cost of Energy is increasing substantially and Energy Ef ciency can help curb this expense. The gap of Power supply & demand can be
reduced by demand side power management i.e. Energy Conservation and Energy Ef ciency improvement. The gap can also be reduced by
adopting alternative sources of energy.
The major bene ts of EE enhancement are:
1. Bottom Line Enhancement
Lower energy costs lead to competitive pricing and improved margins.
2. Legislative Compliance
a. Energy Conservation Act 2001 & subsequent amendment 2010.
b. PAT & ECBC enforcement is already in place.
c. Voluntary compliance is easier than mandatory compliance in the future.
3. Global Warming, GHG Emission & Carbon Foot Print Reduction
a. As per Kyoto Protocol, GHG emission is to be brought to the same level that it was in 1990.
b. Reduction of Ecological Damage to our working environment.
4. Corporate Social Responsibility
The organization is recognized as a socially and environmentally responsible Corporate. Industry is the largest end user of commercial
energy in India s economy. The saving potential is generally 15% - 30% depending on the sector. We identify the speci c gaps by performing
Energy Audits and implementing Energy Management Systems.
Contents

REVENUE
METERS
Page No. 3 to 10

PANEL
METERS
Page No. 11 to 22

CURRENT
TRANSFORMERS
Page No. 23 to 27
Notes

eco-smart
REVENUE METERS

Page No. 3 to 10
SEMC / SEML - K Series

SEMLK103C SEMCK103C

eco-smart
1 - Phase, Digital Energy Meters
Salient Features
 Compliance with IS : 13779 & CBIP Report No. 304  State-of-the-art design with class 1.0 accuracy  L i q u i d C r y s t a l
Display / Stepper Motor Counter Display  6 digits including 1 decimal digit (99999.9)  Comprehensive tamper detection
and tamper proofing measures  LED indication (SEML) for calibration, phase indication, earth load tamper and revers
tamper  Display/Record cumulative active energy (kWh)  Compact, sleek and packed in dust, moisture and shock proof
(IP51) polycarbonate enclosure.

Technical Specifications
Confirms to : IS 13779, IEC 62052/53, CBIP Report No. 304
Accuracy Class : Class 1.0 Connection Diagram
Reference Voltage : 240V AC (-40% to +20%)
Current Rating lb (lm) : 5(20)A, 5(30)A, 10(40)A, 10(60)A
Frequency Range : 50Hz ± 5%
Power Factor Range : 0(lag)-UPF-0(lead)
S1 S2 L2 L1
Starting Current : 0.2% Ib P
N
Meter Constant : 3200 Pulses/kWh
Power Consumption : < 1W/8VA (in voltage circuit); <1VA (in current circuit)
Display : LCD- 5+1 / Stepper Motor Counter Display (99999.9) with rollover

Display/Record Parameters
Indications Tamper Ordering Details
Calibration LED Current reversal, Phase reversal
Reverse Earth loading, DC/AC magnetic influence Rating Voltage Product Code
EMI/EMC interface 5 - 20A 240V AC SEMCK100C/SEMLK100C
5 - 30A 240V AC SEMCK101C/SEMLK101C
10 -40A 240V AC SEMCK102C/SEMLK102C
Communication
No Communication 10 - 60A 240V AC SEMCK103C/SEMLK103C
Type Display
SEMC Stepper Motor Counter
SEML LCD

eco-smart 2013-14
5
SEML - M Series

SEMLM113C

eco-smart
1 - Phase, Multi Function Energy Meter
Salient Features
 Compliance with IS : 13779 & CBIP Report No. 304  State-of-the-art design with class 1.0 accuracy  Blacklit Liquid Crystal
Display-7 segment  7 digits including 1 decimal digit (999999.9)  Comprehensive tamper detection and tamper proofing
measures  LED/LCD indication for calibration, phase indication, earth load tamper and revers tamper  D i s p l a y / R e c o r d
cumulative active energy (kWh)  TOD, MD, Load profile, PF indication  Optical communication port  F o r w a r d e n e r g y
registration in case of all tampers  High resolution energy display mode for dial test  Authenticated Billing code (ABC)
 Compact, sleek and packed in dust, moisture and shock proof (IP51) polycarbonate enclosure.
Technical Specifications
Confirms to : IS 13779, IEC 62052/53, CBIP Report No. 304
Accuracy Class : Class 1.0 (No drift in tolerance of accuracy for 10 years) Connection Diagram
Reference Voltage : 240V AC (-40% to +20%)
Current Rating lb (lm) : 5(20)A, 5(30)A, 10(40)A, 10(60)A
Frequency Range : 50Hz ± 5%
Power Factor Range : 0(lag)-UPF-0(lead)
Starting Current : 0.2% Ib 1 2 3 4 5

Meter Constant : 3200 Pulses/kWh L


Power Consumption : < 1W/8VA (in voltage circuit); <1VA (in current circuit) N
Display : LCD- 6+1

Display/Record Parameters
Auto scroll mode Push button mode Ordering Details
Cumulative active energy (kWh) Real date & time, Instantaneous voltage, Instantaneous
Cumulative MD along with legend current Instantaneous power factor, Instantaneous
Rating Voltage Product Code
load (kW) Supply frequency, MD with date & time, 5 - 20A 240V AC SEMLM110C
Meter serial number 5 - 30A 240V AC SEMLM111C
Tamper Communication 10 -40A 240V AC SEMLM112C
Current reversal, Phase reversal, Optical communication as per IEC 62056-21 10 - 60A 240V AC SEMLM113C
Earth loading, DC/AC magnetic influence Optically isolated RS232/RS485 port for data
EMI/EMC interface, Neutral missing, RCD downloading, GSM/GPRS communication (optional) Type Display
Cover open, Immune and log for abnormal LPR 2.4 GHz (optional), IRDA communication SEML LCD
voltage surge of 35Kv (optional)
* Additional Communication &
Tamper will be available at extra cost.

eco-smart 2013-14
6
SEMC / SEML - D Series

eco-smart
1 - Phase, Dual Source Energy Meter
Salient Features
 Compliance with IS : 13779 & CBIP Report No. 304  State-of-the-art design with class 1.0 accuracy  Liquid Crystal Display-7
segment with Backlit  7 digits including 1 decimal digit (999999.9)  Measure the power consumption on two sources
simultaneously ( DG set & Power grid )  Comprehensive tamper detection and tamper proofing measures  L E D / L C D
indication for calibration, phase indication, earth load tamper and revers tamper  Display/Record cumulative active energy
(kWh)  TOD, MD, Load profile, PF indication Alert on RDU display for low balance and overloads  F o r w a r d e n e r g y
registration in case of all tampers  Inbuilt relays for auto cut-off up to 80Amp.  Authenticated Billing code (ABC)  Compact,
sleek and packed in dust, moisture and shock proof (IP51) polycarbonate enclosure.
Technical Specifications
Confirms to : IS 13779, IEC 62052/53, CBIP Report No. 304
Accuracy Class : Class 1.0
Reference Voltage : 240V AC (-40% to +20%)
Current Rating lb (lm) : 5(20)A, 5(30)A, 10(40)A, 10(60)A
Frequency Range : 50Hz ± 5%
Power Factor Range : 0(lag)-UPF-0(lead) Ordering Details
Starting Current : 0.2% Ib Rating Voltage Product Code
5 - 20A 240V AC SEMLD1B0C
Meter Constant : 3200 Pulses/kWh 5 - 30A 240V AC SEMLD1B1C
Power Consumption : < 1W/8VA (in voltage circuit); <1VA (in current circuit) 10 -40A 240V AC SEMLD1B2C
10 - 60A 240V AC SEMLD1B3C
Display : LCD- 6+1
Type Display
SEML LCD
Display/Record Parameters
Auto scroll mode Push button mode Indications
Cumulative active energy (kWh) for grid LCD check, Meter serial no., History of cumulative Active energy by LED, DG supply indication by
supply, Maximum demand of current month active energy, (kWh) & MD (kW) with date & time LED, Grid supply indication by LED, Overload
(kW) with date & time for grid supply for last six months for grid supply, History of indication (optional)
Real date & time, Cumulative active energy cumulative active energy (kWh) & MD (kW)
Application
(kWh) & MD of current month (kW) with with date & time for last six months for DG supply
Suitable for low cost application, Captivate
date & time for DG supply
generator sets, Individual machine & compressors,
Tamper Communication Lighting loads
Current reversal, Phase reversal, DC/AC Optical communication as per IEC 62056-21, Advantages
magnetic influence, Neutral missing, Cover Optically isolated RS232/RS485 port for data Minimum wiring as same power feeding lines are
open, Immune and log the tamper events for downloading, GSM/GPRS communication utilized for DG Set as well as for mains (Grid) power
abnormal, voltage surge of 35Kv, RCD (optional), LPR 2.4 GHz (optional), IRDA supply, Load control configuration of DG and mains
communication (optional), Downloaded data can be separately, Over and under voltage protection.
used for on the spot billing

eco-smart 2013-14
7
TEMC / TEML - K Series

eco-smart
3 - Phase, Digital Energy Meters
Salient Features
 Compliance with IS : 13779 & CBIP Report No. 304  State-of-the-art design with class 1.0 accuracy  L i q u i d C r y s t a l
Display / Stepper Motor Counter Display  6 digits including 1 decimal digit (99999.9)  Comprehensive tamper detection
and tamper proofing measures  LED indication (TEML) for calibration, phase indication, earth load tamper and revers
tamper  Display/Record cumulative active energy (kWh)  Compact, sleek and packed in dust, moisture and shock proof
(IP51) polycarbonate enclosure.

Technical Specifications
Confirms to : IS 13779, IEC 62052/53, CBIP Report No. 304
Accuracy Class : Class 1.0
Reference Voltage : 3X240V AC (-40% to +20%)
Connection Diagram
Current Rating lb (lm) : 10(40)A, 10(60)A
Frequency Range : 50Hz ± 5%
Power Factor Range : 0(lag)-UPF-0(lead) 1 2 3 4 5 6 7 8 9 10 11

L1
Starting Current : 0.2% Ib L2

L3
Meter Constant : 1600 Pulses/kWh N

Power Consumption : < 1W/8VA (in voltage circuit); <1VA (in current circuit)
Display : LCD- 5+1 / Stepper Motor Counter Display (99999.9) with rollover

Display/Record Parameters
Indications Tamper Ordering Details
Calibration LED, R Phase, Current reversal, Phase reversal
Y Phase, B Phase, Reverse DC/AC magnetic influence Rating Voltage Product Code
10 -40A 240V AC TEMCK405C/TEMLK405C
10 - 60A 240V AC TEMCK406C/TEMLK406C
Type Display
Communication TEMC Stepper Motor Counter
No communication
TEML LCD

eco-smart 2013-14
8
TEML - M Series

eco-smart
3 - Phase, Multi Function Energy Meter
Salient Features
 Compliance with IS : 13779 & CBIP Report No. 304  State-of-the-art design with class 1.0 accuracy  Blacklit Liquid Crystal
Display-7 segment  7 digits including 1 decimal digit (999999.9)  Comprehensive tamper detection and tamper proofing
measures  LED/LCD indication for calibration, phase indication, earth load tamper and revers tamper  D i s p l a y / R e c o r d
cumulative active energy (kWh)  TOD, MD, Load profile, PF indication  Optical communication port  A c c u r a t e e n e r g y
registration in case of all tampers  High resolution energy display mode for dial test  Authenticated Billing code (ABC)
 Compact, sleek and packed in dust, moisture and shock proof (IP51) polycarbonate enclosure.
Technical Specifications
Confirms to : IS 13779, IEC 62052/53, CBIP Report No. 304
Accuracy Class : Class 1.0
Connection Diagram
Reference Voltage : 3X240V AC (-40% to +20%)
Current Rating lb (lm) : 10(40)A, 10(60)A
Frequency Range : 50Hz ± 5% 1 2 3 4 5 6 7 8 9 10 11

Power Factor Range : 0(lag)-UPF-0(lead) L1

L2

Starting Current : 0.2% Ib L3

Meter Constant : 1600 Pulses/kWh


Power Consumption : < 1W/8VA (in voltage circuit); <1VA (in current circuit)
Display : LCD- 6+1

Display/Record Parameters
Auto scroll mode Push button mode Ordering Details
C u m u l a t i v e a c t i v e e n e r g y ( k W h Real date & time, Instantaneous voltage, Instantaneous
Cumulative MD along with legend current Instantaneous power factor, Instantaneous load
Rating Voltage Product Code
(kW) Supply frequency, MD with date & time, Meter serial 10 -40A 240V AC TEMLM412C
Indications number
Calibration LED, R Phase, Y Phase, B Phase, 10 - 60A 240V AC TEMLM413C
Reverse tamper Type Display
Tamper Communication SEML LCD
Current reversal, Phase reversal, Optical communication as per IEC 62056-21
DC/AC magnetic influence, EMI/EMC Optically isolated RS232/RS485 port for data
interface, Neutral missing, RCD downloading, GSM/GPRS communication (optional)
Cover open, Immune and log for abnormal LPR 2.4 GHz (optional), IRDA communication (optional)
voltage surge of 35Kv Downloaded data can be used for on the spot billing.

eco-smart 2013-14
9
TEMC / TEML - D Series

Dual Source

eco-smart
3 - Phase, Dual Source Energy Meter
Salient Features
 Compliance with IS : 13779 & CBIP Report No. 304  State-of-the-art design with class 1.0 accuracy  Blacklit Liquid Crystal
Display-7 segment  7 digits including 1 decimal digit (999999.9)  Measure the power consumption on two sources
simultaneously ( DG set & Power grid )  Comprehensive tamper detection and tamper proofing measures  L E D / L C D
indication for calibration, phase indication, earth load tamper and revers tamper  Display/Record cumulative active energy
(kWh)  TOD, MD, Load profile, PF indication Alert on RDU display for low balance and overloads  F o r w a r d e n e r g y
registration in case of all tampers  Inbuilt relays for auto cut-off up to 80Amp.  Authenticated Billing code (ABC)  Compact,
sleek and packed in dust, moisture and shock proof (IP51) polycarbonate enclosure.
Technical Specifications
Confirms to : IS 13779, IEC 62052/53, CBIP Report No. 304
Accuracy Class : Class 1.0
Reference Voltage : 3X240V AC (-40% to +20%)
Current Rating lb (lm) : 10(40)A, 10(60)A
Frequency Range : 50Hz ± 5%
Power Factor Range : 0(lag)-UPF-0(lead)
Starting Current : 0.2% Ib
Ordering Details
Meter Constant : 1600 Pulses/kWh Rating Voltage Product Code
Power Consumption : < 1W/8VA (in voltage circuit); <1VA (in current circuit) 10 -40A 240V AC TEMLD4B2C
10 - 60A 240V AC TEMLD4B3C
Display : LCD- 6+1
Type Display
TEML LCD
Display/Record Parameters
Auto scroll mode Push button mode Indications
Cumulative active energy (kWh) for grid LCD check, Meter serial no., History of cumulative Active energy by LED, DG supply indication by
supply, Maximum demand of current month active energy, (kWh) & MD (kW) with date & time LED, Grid supply indication by LED, R Phase
(kW) with date & time for grid supply for last six months for grid supply, History of Y Phase, B Phase, Overload indication (optional)
Real date & time, Cumulative active energy cumulative active energy (kWh) & MD (kW)
Application
(kWh) for DG supply & MD of current with date & time for last six months for DG supply
Suitable for low cost application, Captivate
month (kW) with date & time for DG supply
Communication generator sets, Individual machine & compressors,
Tamper Optical communication as per IEC 62056-21, Lighting loads
Current reversal, Phase reversal, Optically isolated RS232/RS485 port for data Advantages
DC/AC magnetic influence, EMI/EMC downloading, GSM/GPRS communication Minimum wiring as same power feeding lines are
interface, Neutral missing, Cover open, (optional)LPR 2.4 GHz (optional), IRDA utilized for DG Set as well as for mains (Grid) power
Immune and log voltage surge of 35Kv. communication (optional). Downloaded data can be supply, Load control configuration of DG and mains
used for on the spot billing separately, Over and under voltage protection.

eco-smart 2013-14
10
PANEL METERS

Page No. 11 to 22
10
Taskmaster

POWER ANALYZER
96 x 96 mm 96 x 96 mm
(3 Phase)
Main Features
 True RMS Measurement  Upgrade rate of programmable parameter 1 sec to 5 sec
 C lass 1.0 / CBIP 88 (0.5 Optional) (Default 1 sec.)
 Password protection programmable  Auto Scrolling period 1 sec. to 10 sec. (Default 5 sec.)
 Simultaneous sampling of Current & Volts  % of unbalance A & V for all three phases
 Recording of Max./Min. - V, A, Hz, W, VA, PF, VAr value  Pulse output (POP) on time 50-500ms programmable
storage  Front LED pulse 5000 imp/kWH
 Automatic measuring of Kilo, Mega, Giga and decimal  Modbus Communication.
point  Programmable - Energy display counter based on
 RPM display & Neutral current calculation resolution base.
 K-factor V&A (all three phase)  Energy resets at 999999kWH * Multiplication factor
 Clearance and Creepage distance comply to IEC61010  Reverse lock option user programmable for positive
safety standard energy accumulation
 Arithmetic harmonics/Selectable VA measurement  THD for Current and Voltage (upto 31st)
Vector  Ampere hour (Ah) and PF average parameters

Standard Features
 Basic Parameter-VL-L, VL-N, AMP, HZ, Q(Angle V/A)/R, Unbalance (in RYB)  Power Parameter-W, VA, PF, VAR, RYB
VAR (in RYB)  Energy Parameter-WH, VAH, VARh (Ind), VARh(Cap), LH, Old Energy  Other Parameter-THD, KF, H/L

Technical Specifications
Accuracy : Class 1 (As per IEC 62036/53, 61557-12) (Optional Class 0.5)
Sensing/Measurement : True RMS with 1 Sec. update time, 4 Quadrant Power and Energy
Ambient Conditions : Temperature: -5 to +55º C (K55), Humidity : <95% non-condessing
Safety : IP protection: IP51 on front plate, Device safety: As per IEC 61010
Input Voltage : VR, VY, VB, VN inputs - Programmable 110 or 415VLL Nominal (Range 80 to 550V LL), Primary
Programmable up to 999 kV, Burden: <0.2VA
Input Current : AR, AY, AB input current - 50mA-6A (Programmable 1A or 5A), CT Primary Programmable up to 99 kA,
Burden : <0.2 VA
Aux-Supply : 80 - 300V AC/DC, 48V DC Optional, 40-70Hz, Burden : <4VA
Display Type : 7 segment 6 digits LED/ 7 digits graphical LCD display

eco-smart 2013-14
13
Taskmaster
Technical Specifications
Max CT, PT Ratio : 2000 MVA Programmable
Communication : RS485 serial channel connection with Modbus RTU protocol (RS232 optional), Baud rate: 2400 bps to 19200
bps. (Standard 9600 bps)
Mechanical : Enclosure: compact sleek and shock proof engineering plastic, Bezzel Size: 96 x 96 mm
Weight : <300 gms
Recording of Max / Min. value of V, A, Hz, VA, W, Var, PF:
: Protection of 3 phase system against single phasing, min. & max. voltage, over load, highly lagging and
leading Pf, Hz etc. Power Navigator can trap such events for future reference. Identifying & record
unbalance voltage and currents and helps the user to identify the root cause. Unbalance over-burdens the
electrical system and affects in the form of over loading of cables, motors and switchgear.
Harmonics:
: Identify the Total Harmonic Distortion. Presence of THD will urge the user to identify the pollution loads
and take necessary action to mitigate harmonics thru’ an appropriate harmonic filter and save energy and
also to improve plants & equipments efficiency.
Data Logging:
: It is very important information for all types of business to determine performance, quality, efficiency, cost
reduction, fuel consumption monitoring and many other critical factors. This feature provides important
and accurate data for analysis.
1 Minute to 24 hours interval programmable. Data interval and parameter can be selected through RS485
communication.

VLL
VA
W

Optional Features
 Upto 4 digital output 2 Analogue input TOD Individual Harmonics upto 31st level for V & A  RD (Rising Demand)
 Analogue Input/output  Ethernet Class 0.5 Data logger - 1MB / 8MB optional Demand updation RTC can be
adjusted using external communication upto 60A direct measurements using Hanging CT.

Ordering Details
Rating Size Product Code
Cutout details 3 Phase 96x96 mm TMU0DMC
3 Phase 96x96 mm TMP00DM
92 mm
3 Phase 96x96 mm TM00ALM
m 92 mm
8m
4
3 Phase 96x96 mm TM00BLM
92 mm

m
58m
3 Phase 96x96 mm TMUDMCL
44 mm
96 mm

48 mm

3 Phase 96x96 mm TMP0DML


3 Phase 96x96 mm TM0ALML
3 Phase 96x96 mm TM0BLML

eco-smart 2013-14
14
Series 3

DUAL SOURCE METER


96 x 96 mm
(3 Phase)
Main Features
 2 Line Display  Automatic switching of Display based on input source
 True RMS Measurement  Energy resets at 999999kWH * Multiplication factor
 Password protection programmable  Reverse lock option user programmable for positive
 Simultaneous sampling of Current & Volts energy accumulation
 Automatic measuring of Kilo, Mega, Giga and decimal  Lower CT & PT burden
point  User programmable CT & PT ratio upto 2000 MVA
 Single Energy Meter for EB & DG  User programmable kVAh or kWh for meters with energy
 Single Potential free contact required from AMF panel or
240 Volt

Standard Features
 Power Parameter - W, PF  Energy Parameter-WH, OLD Energy

Technical Specifications
Accuracy : Class 1 (As per IEC 62036/53, 61557-12) (Optional Class 0.5)
Sensing/Measurement : True RMS with 1 Sec. update time
Input voltage : 4 Voltage inputs (VR, VY, VB, VN), Programmable 110 or 415V LL Nominal, (Range 80 to 550V LL), Primary
Programmable up to 999 kV, Burden: 0.2VA Max. per phase.
Input current : Current inputs (AR, AY, AB) 50mA - 6A, (Field configurable 1A or 5A), Primary Programmable up to 99 kA,
Overload: 10A max continuous, 50A max for 3 sec, Burden: 0.2VA Max. per phase.
Aux-Supply : 80 - 300V AC/DC, 48V DC Optional, 40-70Hz, Burden : <4VA
Display Type : 7 segment 6 digits LED display
CT PT Ratio Max : Programmable 2000 MVA
Mechanical : Enclosure: compact sleek and shock proof engineering plastic, Bezzel Size: 96 x 96 mm, 48 x 96 mm
Weight : <300 gms

Optional Features
 Accuracy : Class 0.5 (Optional)  RS485 communication with Modbus RTU protocol (RS232 optional)  U pto Two Digital
output  60 Amp inbuilt CT option

eco-smart 2013-14
15
Series 3

DUAL SOURCE METER


96 x 96 mm
(3 Phase)
Additional Features
 Basic Parameter-VL-L, VL-N, AMP, HZ  Power Parameter-W, PF  Energy Parameter-WH, LH, OLD Energy

Connection Diagram for


Dual Source Energy Meter
R
Y
Main EB Source
R Y B N

B
AMF PANEL
N

Potential
free
contact

R Y B N

METER 1 METER N
DG Source

Cutout details

92 mm
m 92 mm
4 8m
Ordering Details
92 mm

m
58m
44 mm
96 mm

Rating Size Product Code


48 mm

3 Phase 96x96 mm 3M003DS


3 Phase 96x96 mm 3MM03DS

eco-smart 2013-14
16
Series 3

96 x 48 mm

MULTI FUNCTION METER


96 x 96 mm 96 x 96 mm
(3 Phase)
Main Features
 3 Line Display  Programmable - Energy display counter based on
 True RMS Measurement resolution base.
 Password protection programmable  Energy resets at 999999kWH * Multiplication factor
 Simultaneous sampling of Current & Volts  Reverse lock option user programmable for positive
 Automatic measuring of Kilo, Mega, Giga and decimal energy accumulation
point  Lower CT & PT burden
 Auto Scrolling  User programmable CT & PT ratio upto 2000 MVA
 Front LED pulse 2500 imp/kWH  User programmable kVAh or kWh for meters with energy

Standard Features
 Basic Parameter-VL-L, VL-N, AMP, HZ (in RYB)  Power Parameter-W, VA, PF (in RYB)  Energy Parameter-WH, LH

Technical Specifications:
Accuracy : Class 1 (As per IEC 62036/53, 61557-12) (Optional Class 0.5)
Sensing/Measurement : True RMS with 1 Sec. update time
Ambient Conditions : Temperature: 0-55º C, Humidity : <95% non-condessing
Safety : IP protection: IP51 on front plate, Device safety: As per IEC 61010
Input Voltage : VR, VY, VB, VN inputs - Programmable 110 or 415VLL Nominal (Range 80 to 550V LL), Primary
Programmable up to 999 kV, Burden: <0.2VA
Input Current : AR, AY, AB input current - 50mA-6A (Programmable 1A or 5A), CT Primary Programmable up to 99 kA,
Burden : <0.2 VA
Aux-Supply : 80 - 300V AC/DC, 48V DC Optional, 40-70Hz, Burden : <4VA
Display Type : 7 segment 6 digits LED display
CT PT Ratio Max : Programmable 2000 MVA
Communication : RS485 serial channel connection with Modbus RTU protocol (RS232 optional), Baud rate: 2400 bps to
19200 bps. (Preferred 9600 bps)
Mechanical : Enclosure: compact sleek and shock proof engineering plastic, Bezzel Size: 96 x 96 mm, 48 x 96 mm
Weight : <300 gms

eco-smart 2013-14
17
Series 3

96 x 48 mm

MULTI FUNCTION METER


96 x 96 mm 96 x 96 mm
(3 Phase)
Optional Features
 Accuracy : Class 0.5 (Optional)  RS 485 Communication  Upto Two Digital output

Ordering Details
Cutout details Rating Size Product Code
3 Phase 96x96 mm 3MRM005
92 mm
3 Phase 96x96 mm 3MRM004
mm 92 mm
48
3 Phase 96x96 mm 3MRM003
92 mm

58 mm
44 mm

3 Phase 96x96 mm 3MRM04L


96 mm

48 mm

3 Phase 96x96 mm 3MRM03L


3 Phase 96x48 mm 3MRM04m
3 Phase 96x48 mm 3MRM03m

eco-smart 2013-14
18
Series 2

96 x 48 mm

ENERGY METER
96 x 96 mm
(3 Phase)
Main Features
 1 Line Display  Programmable - Energy display counter based on
 True RMS Measurement resolution base.
 Password protection programmable  Energy resets at 999999kWH * Multiplication factor
 Automatic measuring of Kilo, Mega, Giga and decimal point  Reverse lock option user programmable for positive
 Auto Scrolling energy accumulation
 Lower CT & PT burden
Standard Features  User programmable CT & PT ratio upto 2000 MVA
 Energy Parameter-WH, VA, W, PF (any one programmable )

Technical Specifications
Accuracy : Class 1 (As per IEC 61036, IS 13779, CBIP 88) (Optional Class 0.5)
Sensing/Measurement : True RMS with 1 Sec. update time
Ambient Conditions : Temperature: 0-55º C, Humidity : <95% non-condessing
Safety : IP protection: IP51 on front plate, Device safety: As per IEC 61010
Input Voltage : VR, VY, VB, VN inputs - Programmable 110 or 415VLL Nominal (Range 80 to 550V LL), Primary
Programmable up to 999 kV, Burden: <0.2VA
Input Current : AR, AY, AB input current - 50mA-6A (Programmable 1A or 5A), CT Primary Programmable up to 99 kA,
Burden : <0.2 VA
Aux-Supply : 80 - 300V AC/DC, 48V DC Optional, 40-70Hz, Burden : <4VA
Display Type : 7 segment 6 digits LED display
Mechanical : Enclosure: compact sleek and shock proof engineering plastic, Bezzel Size: 96 x 96 mm, 48 x 96 mm
Weight : <300 gms

Optional Features
 Accuracy : Class 0.5 (Optional)  RS485 communication with Modbus RTU protocol (RS232 optional)

Cutout details

92 mm

mm 92 mm
48
Ordering Details
92 mm

58 mm
44 mm
96 mm

Rating Size Product Code


48 mm

3 Phase 96x96 mm 2MEM001


3 Phase 96x48 mm 2MRM01m

eco-smart 2013-14
19
Series 1

96 x 48 mm

VOLTMETER
96 x 96 mm
(1/3 Phase)
Main Features
 1 Phase/3 Phase voltmeter with inbuilt selector switch  Auto Scrolling
 1 Phase / Star / Delta Wiring type programmable  Voltage primary up to 999k Volt
 Micro controller based operation  Onsite programmable PT primary & PT secondary
 Password protection programmable  Reverse lock option user programmable for positive
 Phase-wise and average information in three phase meters energy accumulation

Standard Features
 Basic Parameter-VL-L, VL-N, Avg & Phase Wise

Technical Specifications
Accuracy : Class 1 (As per IEC 61036, IS 13779, CBIP 88) (Optional Class 0.5)
Sensing/Measurement : True RMS with 1 Sec. update time
Ambient Conditions : Temperature: 0-55º C, Humidity : <95% non-condessing
Safety : IP protection: IP51 on front plate, Device safety: As per IEC 61010
Input Voltage : VR, VY, VB, VN inputs - Programmable 110 or 415VLL Nominal (Range 80 to 550V LL), Primary
Programmable up to 999 kV, Burden: <0.2VA
Aux-Supply : 80 - 300V AC/DC, 48V DC Optional, 40-70Hz, Burden : <4VA
Display Type : 7 segment 4 digits LED display
Mechanical : Enclosure: compact sleek and shock proof engineering plastic, Bezzel Size: 96 x 96 mm, 48 x 96 mm
Weight : <300 gms
Optional Features
 Accuracy : Class 0.5 (Optional)  RS485 communication with Modbus RTU protocol (RS232 optional)
Cutout details

92 mm Ordering Details
m m 92 mm
48 Rating Size Product Code
92 mm

m
58m
1 Phase 96x96 mm 1M0001V
44 mm
96 mm

48 mm

1 Phase 96x48 mm 1M001Vm


3 Phase 96x96 mm 1M0003V
3 Phase 96x48 mm 1M003Vm

eco-smart 2013-14
20
Series 1

96 x 48 mm

AMMETER
96 x 96 mm
(1/3 Phase)
Main Features
 1 Phase/3 Phase ammeter with inbuilt selector switch  Auto Scrolling
 1 Phase / Star / Delta Wiring type programmable  Current primary upto 99 kAmps
 Micro controller based operation  Onsite programmable CT primary & CT secondary
 Password protection programmable  Current secondary 1 Amp to 6 Amp (Default 5 Amp)
 Phase-wise and average information in three phase meters

Standard Features
 Basic Parameter-AMP-AVg, AR, AY, AB

Technical Specifications
Accuracy : Class 1 (As per IEC 61036, IS 13779, CBIP 88) (Optional Class 0.5)
Sensing/Measurement : True RMS with 1 Sec. update time
Ambient Conditions : Temperature: 0-55º C, Humidity : <95% non-condessing
Safety : IP protection: IP51 on front plate, Device safety: As per IEC 61010
Input Current : AR, AY, AB input current - 50mA-6A (Programmable 1A or 5A), CT Primary Programmable up to 99 kA,
Burden : <0.2 VA
Aux-Supply : 80 - 300V AC/DC, 48V DC Optional, 40-70Hz, Burden : <4VA
Display Type : 7 segment 4 digits LED display
Mechanical : Enclosure: compact sleek and shock proof engineering plastic, Bezzel Size: 96 x 96 mm, 48 x 96 mm
Weight : <300 gms
Optional Features
 Accuracy : Class 0.5 (Optional)  RS485 communication with Modbus RTU protocol (RS232 optional)
Cutout details

92 mm Ordering Details
m m 92 mm
48 Rating Size Product Code
92 mm

m
58m
1 Phase 96x96 mm 1M0001A
44 mm
96 mm

48 mm

1 Phase 96x48 mm 1M001Am


3 Phase 96x96 mm 1M0003A
3 Phase 96x48 mm 1M003Am

eco-smart 2013-14
21
Series 1

96 x 48 mm

FREQUENCY METER
96 x 96 mm
(1 Phase)
Main Features
 Wider range of display 35 Hz to 70 Hz
 Micro controller based operation
 Password protection programmable
 Available in 96 x 96 mm & 96 x 48 mm

Standard Features
 Basic Parameter- Hz

Technical Specifications:
Accuracy : Class 0.2(As per IEC 61036, IS 13779, CBIP 88)
Sensing/Measurement : True RMS with 1 Sec. update time
Ambient Conditions : Temperature: 0-55º C, Humidity : <95% non-condessing
Safety : IP protection: IP51 on front plate, Device safety: As per IEC 61010
Aux-Supply : 80 - 300V AC 50/60Hz Option, Burden : <4VA
Display Type : 7 segment 4 digits LED display
Mechanical : Enclosure: compact sleek and shock proof engineering plastic, Bezzel Size: 96 x 96 mm, 48 x 96 mm
Weight : <300 gms

Cutout details

92 mm

m m 92 mm
48
92 mm

m
58m Ordering Details
44 mm
96 mm

48 mm

Rating Size Product Code


1 Phase 96x96 mm 1M001HZ
1 Phase 96x48 mm 1M01HZm

eco-smart 2013-14
22
CURRENT TRANSFORMERS

Page No. 23 to 27
Current Transformers

49 62 60 62
.0 .0
.0 10.5

26.5
7.9 0
73.5

7.90
80
31

AM 301
32

AM 3301
36

AM 301E AM 401
32

AM 4401
36
MOULDED
Standard Features
 Flame retardant and self extinguishing  Finger touch proof terminals as per IEC 185
 Accommodate wide range of busbar size  Insulation Class E
 Easy to mount, compact in size  M5 Screw clamps on secondary terminals
 Ultrasonically welded and non-breakable

Technical Specifications
Accuracy : Class 0.5, Class 1, Class 3 depending upon variants.
Ambient Conditions : -20º C to +70ºC, Humidity <95% RH ( non condensing)
Safety : Flame retardant glass filled ABS, VE 404 and IEC 185 compliance
Saturation Coefficient : < 5
Primary Rating : From 5Amp. to 4000 Amp.
Secondary Output : 5 Amp. ( 1Amp. optional)
Max System Volt : 720 V
Max Test Volt : 3 KV for 1 minute
Overload : 1.2 times rated current continuously
Mounting Hardware : Feet and busbar screw
Rated Dynamic Current : 7.5 kA for 1 sec.

Rated AM 301 AM 3301 Rated AM 301E AM 401 AM 4401


Ratio Accuracy Class Accuracy Class Ratio Accuracy Class Accuracy Class Accuracy Class
0.5 1 3 0.5 1 3 0.5 1 3 0.5 1 3 0.5 1 3
50/5A 1.25 VA 60/5A 1 VA
60/5A 1 VA 1.25 VA 75/5A 1 VA
75/5A 1 VA 1.25 VA 80/5A 1 VA
80/5A 1 VA 1.25 VA 100/5A 1 VA
100/5A 1 VA 5 VA 125/5A 1 VA
125/5A 1 VA 5 VA 150/5A 1 VA 2.5 VA 2.5 VA 2.5 VA
150/5A 1 VA 2.5 VA 5 VA 200/5A 2.5 VA 2.5 VA 5 VA
200/5A 2.5 VA 5 VA 250/5A 2.5 VA 2.5 VA 5 VA
250/5A 2.5 VA 5 VA 300/5A 2.5 VA 5 VA 2.5 VA 5 VA 5 VA
300/5A 2.5 VA 5 VA 5 VA 400/5A 5 VA 5 VA 7.5 VA 5 VA 7.5 VA
400/5A 5 VA 5 VA 500/5A 5 VA 5 VA 7.5 VA 7.5 VA
500/5A 5 VA 5 VA 600/5A 5 VA 5 VA 7.5 VA 7.5 VA
600/5A 5 VA 5 VA 750/5A 5 VA 7.5 VA 7.5 VA
750/5A 5 VA 800/5A 5 VA 7.5 VA 7.5 VA

eco-smart 2013-14
25
Current Transformers

85 10 43
0 25

40
162
110

197

163
K

103.5
124

1P

13 23.5

MOULDED
32 3
40 5 33 16
40 93

AM 601 AM 801 AM 1001 AM 1020 AM 1201

Standard Features
 Flame retardant and self extinguishing  Finger touch proof terminals as per IEC 185
 Accommodate wide range of busbar size  Insulation Class E
 Easy to mount, compact in size  M5 Screw clamps on secondary terminals
 Ultrasonically welded and non-breakable

Technical Specifications
Accuracy : Class 0.5, Class 1, Class 3 depending upon variants.
Ambient Conditions : -20º C to +70ºC, Humidity <95% RH ( non condensing)
Safety : Flame retardant glass filled ABS, VE 404 and IEC 185 compliance
Saturation Coefficient : < 5
Primary Rating : From 5Amp. to 4000 Amp.
Secondary Output : 5 Amp. ( 1Amp. optional)
Max System Volt : 720 V
Max Test Volt : 3 KV for 1 minute
Overload : 1.2 times rated current continuously
Mounting Hardware : Feet and busbar screw
Rated Dynamic Current : 7.5 kA for 1 sec.

Rated AM 601 AM 801 AM 1001 Rated AM 1020 AM 3301


Ratio Accuracy Class Accuracy Class Accuracy Class Ratio Accuracy Class Accuracy Class
0.5 1 3 0.5 1 3 0.5 1 3 0.5 1 3 0.5 1 3
400/5A 10 VA 5 VA 7.5 VA 5 VA 400/5A 5 VA
500/5A 10 VA 5 VA 7.5 VA 5 VA 10 VA 500/5A 5 VA 10 VA
600/5A 10 VA 15 VA 5 VA 7.5 VA 5 VA 10 VA 600/5A 5 VA 10 VA
750/5A 10 VA 15 VA 10 VA 15 VA 10 VA 15 VA 750/5A 10 VA 15 VA 10 VA 15 VA
800/5A 10 VA 15 VA 10 VA 15 VA 10 VA 15 VA 800/5A 10 VA 15 VA 10 VA 15 VA
1000/5A 10 VA 15 VA 10 VA 15 VA 15 VA 1000/5A 15 VA 15 VA
1200/5A 15 VA 10 VA 15 VA 15 VA 1200/5A 15 VA 15 VA
1250/5A 15 VA 10 VA 15 VA 15 VA 1250/5A 15 VA 15 VA
1500/5A 15 VA 10 VA 15 VA 15 VA 1500/5A 15 VA 15 VA
1600/5A 15 VA 10 VA 15 VA 15 VA 1600/5A 15 VA 15 VA
2000/5A 10 VA 15 VA 15 VA 30 VA 2000/5A 15 VA 30 VA 15 VA 30 VA
2500/5A 15 VA 30 VA 2500/5A 15 VA 30 VA 15 VA 30 VA
3000/5A 30 VA 3000/5A 30 VA 30 VA
4000/5A 30 VA 4000/5A 30 VA

eco-smart 2013-14
26
Current Transformers

RESIN CAST
AM 801 AT 201 &
TAPE WOUND
Standard Features
 Flame retardant and self extinguishing  Ultrasonically welded and non-breakable
 Accommodate wide range of busbar size  Finger touch proof terminals as per IEC 185
 Easy to mount, compact in size  Insulation Class E
Technical Specifications  M5 Screw clamps on secondary terminals

Accuracy : Class 0.5, Class 1, Class 3 depending upon variants.


Ambient Conditions : -20º C to +70ºC, Humidity <95% RH ( non condensing)
Safety : Flame retardant glass filled ABS, VE 404 and IEC 185 compliance
Saturation Coefficient : < 5
Primary Rating : From 50Amp. to 3000 Amp.
Secondary Output : 5 Amp. ( 1Amp. optional)
Max System Volt : 720 V
Max Test Volt : 3 KV for 1 minute
Overload : 1.2 times rated current continuously
Mounting Hardware : Feet and busbar screw
Rated Dynamic Current : 7.5 kA for 1 sec.
Rated AR 501(Bar Primary) AR 501(Wound Primary) Rated Ratio VA Class ID (mm) OD (mm) Width (mm)
Ratio Accuracy Class Primary Accuracy Class 50/5A 5 3 30 85 50
1 3 1 3 60/5A 5 3 30 85 50
50/5A 5 VA 1-50 5 - 7.5 - 10 VA 75/5A 5 3 30 85 50
60/5A 5 VA 1-50 2.5 - 7.5 - 10 VA 100/5A 2.5 - 5 1-3 30 85 50
75/5A 5 VA 1-50 15 VA 150/5A 7.5 - 10 1-3 30 85 50
100/5A 7.5 VA 51-100 5 - 7.5 - 10 VA 200/5A 10 - 15 1-3 52 95 45
150/5A 10 VA 51-100 2.5 - 7.5 - 10 VA 250/5A 10 - 15 1-3 52 95 45
200/5A 10 VA 51-100 15 VA 300/5A 10 - 15 1-3 52 95 45
250/5A 15 VA 400/5A 15 - 30 1-3 60 100 40
300/5A 15 VA 500/5A 15 - 30 1-3 60 100 40
400/5A 15 VA
600/5A 15 - 30 1-3 60 100 40
500/5A 15 VA
800/5A 15 - 30 1-3 80 130 40
600/5A 15 VA
1000/5A 15 - 30 1-3 80 130 40
800/5A 15 VA
1200/5A 15 - 30 0.5 - 3 125 175 40
1000/5A 15 VA
1600/5A 15 - 30 0.5 - 1 125 175 40
1200/5A 15 VA
2000/5A 15 - 30 0.5 - 1 125 175 40
1600/5A 15 VA
2000/5A 15 VA 2500/5A 15 - 30 0.5 - 1 125 175 40
2500/5A 15 VA 3000/5A 15 - 30 0.5 - 1 125 175 40
3000/5A 15 VA

eco-smart 2013-14
27
Notes

right to discontinue or change specification of any product without any notification to the user.
Due to continuous technology up gradation and design requirements, the company reserves the

Corporate Office: Tel: + 91 120 4531 400 / 4531 401


B 189, Phase II, Noida Fax:+ 91 120 4531 402
Gautam Budh Nagar Email: sales@pkrgroup.in
Uttar Pradesh, INDIA Web: www.pkrgroup.in
ADVANCE METERING TECHNOLOGY LTD
An ISO 9001 : 2008 company Customer Care : +91 120 4531 400 28
B 189, Phase II,
Noida 201 305
Gautam Budh Nagar
Uttar Pradesh, India
Tel: + 91 120 4531 400 / 4531 401
Fax: + 91 120 4531 402
E mail: corporate@pkrgroup.in