CHP 2
CHP 2
The modeling and analysis of a power system depend upon the “load”. What is load?
The answer to that question depends upon what type of analysis is desired. For exam-
ple, the steady-state analysis (power-flow study) of an interconnected transmission
system will require a different definition of load than that used in the analysis of a
secondary in a distribution feeder. The problem is that the “load” on a power system
is constantly changing. The closer you are to the customer, the more pronounced will
be the ever-changing load. There is no such thing as a “steady-state” load. To come
to grips with load, it is first necessary to look at the “load” of an individual customer.
2.1 DEFINITIONS
The load that an individual customer or a group of customers presents to the distribu-
tion system is constantly changing. Every time a light bulb or an electrical appliance
is switched on or off the load seen by the distribution feeder changes. To describe the
changing load, the following terms are defined:
1. Demand
• Load averaged over a specific period
• Load can be kW, kvar, kVA, A
• Must include the time interval
• Example: The 15-minute kW demand is 100 kW
2. Maximum Demand
• Greatest of all demands which occur over a specific period
• Must include demand interval, period, and units
• Example: The 15-minute maximum kW demand for the week was
150 kW
3. Average Demand
• The average of the demands over a specified period (day, week, month,
etc.)
• Must include demand interval, period, and units
• Example: The 15-minute average kW demand for the month was 350 kW
4. Diversified Demand
• Sum of demands imposed by a group of loads over a particular period
• Must include demand interval, period, and units
• Example: The 15-minute diversified kW demand in the period ending at
9:30 was 200 kW
DOI: 10.1201/9781003261094-2 9
10 Distribution System Modeling and Analysis
2.2.1 Demand
To define the load, the demand curve is broken into equal time intervals. In Figure
2.1, the selected time interval is 15 minutes. In each interval, the average value of the
demand is determined. In Figure 2.1, the straight lines represent the average load in a
time interval. The shorter the time interval, the more accurate will be the value of the
load. This process is very similar to numerical integration. The average value of the
load in an interval is defined as the “15-minute kW demand”.
The 24-hour, 15-minute kW demand curve for a customer is shown in Figure 2.2.
This curve is developed from a spreadsheet that gives the 15-minute kW demand for
a period of 24 hours.
2.2.2 Maximum Demand
The demand curve shown in Figure 2.2 represents a typical residential customer. Each
bar represents the “15-minute kW demand”. Note that during the 24-hour period,
there is a great variation in the demand. This customer has three periods in which
the kW demand exceeds 6.0 kW. The greatest of these is the “15-minute maximum
kW demand”. For this customer, the “15-minute maximum kW demand” occurs at
13:15 and has a value of 6.18 kW.
2.2.3 Average Demand
During the 24-hour period, energy (kWh) will be consumed. The energy in kWh used
during each 15-minute time interval is computed by
1
kWh 15 minute kW demand hour (2.1)
4
The total energy consumed during the day is then the summation of all of the
15-minute interval consumptions. From the spreadsheet, the total energy consumed
12 Distribution System Modeling and Analysis
2.2.4 Load Factor
“Load factor” is a term that is often referred to when describing a load. It is defined
as the ratio of the average demand to the maximum demand. In many ways, load fac-
tor gives an indication of how well the utility’s facilities are being utilized. From the
utility’s standpoint, the optimal load factor would be 1.00 since the system has to be
designed to handle the maximum demand. Sometimes utility companies will encour-
age industrial customers to improve their load factor. One method of encouragement
is to penalize the customer on the electric bill for having a low load factor.
For Customer #1 in Figure 2.2, the load factor is computed to be:
kWaverage 2.46
=
Load Factor = = 0.40 (2.3)
kWmaximum 6.18
TABLE 2.1
Individual Customer Load Characteristics
Cust. #1 Cust. #2 Cust. #3 Cust. #4
These four customers demonstrate that there is great diversity between their loads.
2.3.1 Diversified Demand
It is assumed that the same distribution transformer serves the four customers dis-
cussed previously. The sum of the four 15 kW demands for each time interval is the
“diversified demand” for the group in that time interval, and in this case, the distri-
bution transformer. The 15-minute diversified kW demand of the transformer for the
14 Distribution System Modeling and Analysis
day is shown in Figure 2.6. Note in this figure how the demand curve is beginning
to smooth out. There are not as many significant changes as seen by some of the
individual customer curves.
kWmaximum non coincident demand 6.18 6.82 4.93 7.05 24.98 kW (2.4)
The Nature of Loads 15
2.3.5 Diversity Factor
By definition, diversity factor is the ratio of the maximum non-coincident demand
of a group of customers to the maximum diversified demand of the group. With
reference to the transformer serving four customers, the diversity factor for the four
customers would be
The idea behind the diversity factor is that when the maximum demands of the
customers are known, then the maximum diversified demand of a group of custom-
ers can be computed. There will be a different value of the diversity factor for
different numbers of customers. The previously computed value would apply to
four customers. If there are five customers, then a load survey would have to be set
up to determine the diversity factor for five customers. This process would have to
be repeated for all practical numbers of customers. Table 2.2 is an example of the
diversity factors for the number of customers ranging from one up to 70. The table
was developed from a different database than the four customers that have been
discussed previously.
A graph of the diversity factors is shown in Figure 2.8.
Note in Table 2.2 and Figure 2.8 that the value of the diversity factor has basically
leveled out when the number of customers has reached 70. This is an important
observation because it means, at least for the system from which these diversity fac-
tors were determined, that the diversity factor will remain constant at 3.20 from 70
customers and up. In other words, as viewed from the substation, the maximum
diversified demand of a feeder can be predicted by computing the total non-
coincident maximum demand of all of the customers served by the feeder and divid-
ing by 3.2.
16 Distribution System Modeling and Analysis
TABLE 2.2
Diversity Factors
N DF N DF N DF N DF N DF N DF N DF
2.3.6 Demand Factor
The demand factor can be defined for an individual customer. For example, the
15-minute maximum kW demand of Customer #1 was found to be 6.18 kW. In order
to determine the demand factor, the total connected load of the customer needs to be
known. The total connected load will be the sum of the ratings of all of the electri-
cal devices at the customer’s location. Assume that this total comes to 35 kW, the
demand factor is computed to be
The demand factor gives an indication of the percentage of electrical devices that
are on when the maximum demand occurs. The demand factor can be computed for
an individual customer but not for a distribution transformer or the total feeder.
2.3.7 Utilization Factor
The utilization factor gives an indication of how well the capacity of an electrical
device is being utilized. For example, the transformer serving the four loads is rated
15 kVA. Using the 16.16 kW maximum diversified demand and assuming a power
factor of 0.9, the 15-minute maximum kVA demand on the transformer is computed
by dividing the 16.16 kW maximum kW demand by the power factor and would be
17.96 kVA. The utilization factor is computed to be
2.3.8 Load Diversity
Load diversity is defined as the difference between the non-coincident maximum
demand and the maximum diversified demand. For the transformer in question, the
load diversity is computed to be
2.4 FEEDER LOAD
The load that a feeder serves will display a smoothed-out demand curve as shown in
Figure 2.9.
The feeder demand curve does not display any of the abrupt changes in demand
of an individual customer demand curve or the semi-abrupt changes in the demand
curve of a transformer. The simple explanation for this is that with several hundred
customers served by the feeder, the odds are good that as one customer is turning off
a light bulb another customer will be turning a light bulb on. The feeder load, there-
fore, does not experience a jump as would be seen in the individual customer’s
demand curve.
2.4.1 Load Allocation
In the analysis of a distribution feeder “load,” data will have to be specified. The
data provided will depend upon how detailed the feeder is to be modeled and the
availability of customer load data. The most comprehensive model of a feeder will
represent every distribution transformer. When this is the case, the load allocated to
each transformer needs to be determined.
This maximum diversified demand becomes the allocated “load” for the
transformer.
2.4.1.2 Load Survey
Many times, the maximum demand of individual customers will be known either
from metering or from a knowledge of the energy (kWh) consumed by the customer.
Some utility companies will perform a load survey of similar customers in order to
determine the relationship between the energy consumption in kWh and the maxi-
mum kW demand. Such a load survey requires the installation of a demand meter at
each customer’s location. The meter can be the same type as is used to develop the
demand curves previously discussed, or it can be a simple meter that only records the
maximum demand during the period. At the end of the survey period, the maximum
demand vs. kWh for each customer can be plotted on a common graph. Linear regres-
sion is used to determine the equation of a straight line that gives the kW demand
as a function of kWh. The plot of points for 15 customers, along with the resulting
equation derived from a linear regression algorithm, is shown in Figure 2.10.
The straight-line equation derived is
Knowing the maximum demand for each customer is the first step in developing a
table of diversity factors, as shown in Table 2.2. The next step is to perform a load
survey where the maximum diversified demand of groups of customers is metered.
This will involve selecting a series of locations where demand meters can be placed
that will record the maximum demand for groups of customers ranging from at least
two to 70. At each meter location, the maximum demand of all downstream custom-
ers must also be known. With that data, the diversity factor can be computed for the
given number of downstream customers.
The energy in kWh consumed by each customer during a month is known. A load
survey has been conducted for customers in this class, and it has been found that
the customer 15-minute maximum kW demand is given by the equation
The results of this calculation for the remainder of the customers are summarized
next by transformer.
Transformer T1
Customer #1 #2 #3 #4 #5
Transformer T2
Customer #6 #7 #8 #9 #10 #11
Transformer T3
Customer #12 #13 #14 #15 #16 #17 #18
kWmaximum non coincident demand 12.4 13.4 16.1 12.9 11.8 66.6 kW
T1 : kWmaximum non concideent demand
kWmaximum diversified demand 30.3 kW
DF5
kWmaximum non coincident demand 10.1 12.9 13.8 14.2 16.3 14.3
81.6 kW
T2 :
kWmaximum non cooncident demand
kWmaximum diversified demand 35.4 kW
DF6
The Nature of Loads 21
kWmaximum non coincident demand 17.0 15.0 16.7 18.3 17.3 16.1 17.0
117.4 kW
T3 :
kWmaximum non concident demand
kWmaximum diversified demand 48.9 kW
DF7
30.2
=
kVAT1 maximum diversified demand = 33.6 kVA
.9
35.5
= = 39.4 kVA
kVAT 2 maximum diversified demand
.9
48.9
= = 54.4 kVA
kVAT 3 maximum diversified demand
.9
The kVA ratings selected for the three transformers would be 25 kVA, 37.5 kV,
and 50 kVA respectively. With those selections, only Transformer T1 would
experience a significant maximum kVA demand greater than its rating (135%).
2. Determine the 15-minute non-coincident maximum kW demand and
15-minute maximum diversified kW demand for each of the line segments.
265.5
kWmaximum diversified =
demand = 92.8 KW
2.86
Example 2.1 demonstrates that Kirchhoff’s Current Law (KCL) is not obeyed
when the maximum diversified demands are used as the “load” flowing through the
line segments and through the transformers. For example, at node N1, the maximum
diversified demand flowing down the line segment N1–N2 is 92.8 kW and the maxi-
mum diversified demand flowing through Transformer T1 is 30.3 kW. KCL would
then predict that the maximum diversified demand flowing down line segment N2–
N3 would be the difference of these or 62.5 kW. However, the calculations for the
maximum diversified demand in that segment were computed to be 72.6 kW. The
explanation for this is that the maximum diversified demands for the line segments
and transformers don’t necessarily occur at the same time. At the time that the line
segment N2–N3 is experiencing its maximum diversified demand, line segment N1–
N2 and Transformer T1 are not at their maximum values. All that can be said is that
at the time segment N2–N3 is experiencing its maximum diversified demand, the
difference between the actual demand on the line segment N1–N2 and the demand of
Transformer T1 will be 72.6 kW. There will be an infinite number of combinations of
line flow down N1–N2 and through Transformer T1 that will produce the maximum
diversified demand of 72.6 kW on line N2–N3.
minimum give either the total three-phase maximum diversified kW or kVA demand
and/or the maximum current per phase during a month. The kVA ratings of all distri-
bution transformers are always known as feeders. The metered readings can be allo-
cated to each transformer based upon the transformer rating. An “allocation factor”
(AF) can be determined based upon the metered three-phase kW or kVA demand and
the total connected distribution transformer kVA.
where kVAtotal kVA rating = Sum of the kVA ratings of all distribution transformers.
The allocated load per transformer is then determined by
The transformer demand will be either kW or kVA depending upon the metered
quantity.
When the kW or kVA is metered by phase, then the load can be allocated by phase
where it will be necessary to know the phasing of each distribution transformer.
When the maximum current per phase is metered, the load allocated to each dis-
tribution transformer can be done by assuming nominal voltage at the substation and
then computing the resulting kVA. The load allocation will now follow the same
procedure as outlined earlier.
If there is no metered information on the reactive power or power factor of the
feeder, a power factor will have to be assumed for each transformer load.
Modern substations will have microprocessor-based metering that will provide
kW, kvar, kVA, power factor, and current per phase. With this data, the reactive power
can also be allocated. Since the metered data at the substation will include losses, an
iterative process will have to be followed so that the allocated load plus losses will
equal the metered readings.
92.9
=
AF = 0.8258
112.5
Which method to use depends upon the purpose of the analysis. If the purpose of the
analysis is to determine as closely as possible the maximum demand on a distribu-
tion transformer, then either the diversity factor or the transformer load manage-
ment method can be used. Neither of these methods should be employed when the
analysis of the total feeder is to be performed. The problem is that using either of
those methods will result in a much larger maximum diversified demand at the sub-
station than actually exists. When the total feeder is to be analyzed, the only method
that gives good results is that of allocating load based upon the kVA ratings of the
transformers.
Example 2.3: For the system of Example 2.1, assume the voltage
at N1 is 2,400 volts; compute the secondary voltages on the three
transformers using the diversity factors.
The system of Example 2.1, including segment distances, is shown in Figure 2.12.
5000
N1 – N2: Z12 0.3 j 0.6 0.2841 j 0.5682
5280
500
N2 – N3: Z23 0.3 j 0.6 0.0284 j 0.0568
5280
750
N3 – N4: Z34 0.3 j 0.6 0.0426 j 0.0852
5280
kW jkvar 92.9 j 45.0
I12 43.0 / 25.84 A
kV 2.4 / 0
V2 V1 Z12·I12
kW jkvar 30.3 j14.7
IT1 14.16 / 26.84 A
kV 2.378 / 0.4
VT1 V2 ZT1·IT1
2321.5 / 0.8
VlowT1 232.15 / 0.8 V
10
kW jkvar 72.6 j 35.2
I23 33.9 / 25.24 A
kV 2.378 / 0.4
V3 V2 Z23·I23
kW jkvar 35.5 j17.2
IT 2 16.58 / 26.27 A
kV 2.3767 / 0.4
VT 2 V3 ZT 2·IT 2
2331.1 / 0.8
VlowT 2 233.1 / 0.8 V
10
kW jkvar 49.0 j 23.7
I34 22.9 / 25.27 A
kV 2.3767 / 0.4
V4 V3 Z34 I34
The current flowing into T3 is the same as the current from N3 to N4.
28 Distribution System Modeling and Analysis
kW jkvar 51.0 j 24.7
IT 3 23.91 / 26.30 A
kV 2.375.0 / 0.5
VT 3 V4 ZT 3 IT 3
2326.1 / 1.0
VlowT 3 232.6 / 1.0 V
10
Calculate the percent voltage drop to the secondary of Transformer T3. Use the
secondary voltage referred to the high side.
V1 | VT 3 | 2400 2326.1
Vdrop 100 100 3.0789%
| V1 | 2400
Example 2.4: For the system of Example 2.1, assume the voltage
at N1 is 2,400 volts, compute the secondary voltages on the three
transformers allocating the loads based upon the transformer ratings.
Assume that the metered kW demand at N1 is 92.9 kW.
The impedances of the line segments and transformers are the same as in Example
2.3.
Assume the load power factor is 0.9 lagging and compute the kVA demand at
N1 from the metered demand.
92.9
S12 / cos1 0.9 92.9 j 45.0 103.2 / 25.84 kVA
0 .9
103.2 / 25.84
AF 0.9175 / 25.84
25 37.5 50
Using these values of line flows and flows into transformers, the procedure for
computing the transformer secondary voltages is exactly the same as in Example
2.3. When this procedure is followed, the node and secondary transformer volt-
ages are as follows:
V1 | VT 3 | 2400 2334.8
Vdrop 100 100 2.7179%
|V1 | 2400
was severely reduced with the addition of the EV charger from 0.4 to 0.18. Lastly, the
loading on the distribution transformer is a concern. It was previously calculated that
the maximum diversified demand for Customers #1 through #4 was 16.16 kW, and
those four customers were connected to a 15 kVA transformer. During the period of
maximum diversified demand, the kVA load on the transformer was calculated to be
The Nature of Loads 31
17.96, which produced a transformer utilization factor of 1.197. This is slightly over-
loaded but tolerable for short periods of time. EV chargers that use smart charging
assume a power factor of 0.95 lagging, so the total kVA load on the transformer for
the new maximum diversified demand is
16.16 9.6
kVAmaximum demand 28.06 kVA.
0.9 0.95
which is an unacceptable kVA load on the transformer, even for short periods of time.
This would require the distribution engineer to intervene by replacing this trans-
former. In addition, it will be shown in Chapter 9 that the high current drawn by these
EV chargers has a significant impact on the customer’s service voltage, which also
must be considered.
The impact that EV chargers have on the grid is significant; however, the cost of
an “electrical gallon” or an eGallon as defined by the Department of Energy, is still
much cheaper than a gallon of petroleum-based gasoline [1]. Due to the differential
in cost of petroleum-based energy and electrical energy, and the continued electrifi-
cation of traditionally non-electrified devices, the trend of EVs is likely to continue
to grow. This will have to be addressed by distribution engineers to keep the grid
stable and reliable and to keep voltages within limits.
2.6 SUMMARY
This chapter has demonstrated the nature of the loads on a distribution feeder. There
is a great diversity between individual customer demands, but as the demand is moni-
tored on line segments working back toward the substation, the effect of the diver-
sity between demands becomes very slight. It was shown that the effect of diversity
between customer demands must be taken into account when the demand on a dis-
tribution transformer is computed. The effect of diversity for short laterals can be
taken into account in determining the maximum flow on the lateral. For the diversity
factors of Table 2.2, it was shown that when the number of customers exceeds 70, the
effect of diversity has pretty much disappeared. This is evidenced by the fact that the
diversity factor has become almost constant as the number of customers approached
70. It must be understood that the number 70 will apply only to the diversity factors
of Table 2.2. If a utility is going to use diversity factors, then that utility must perform
a comprehensive load survey to develop the table of diversity factors that apply to
that particular system.
Examples 2.3 and 2.4 show that the final node and transformer voltages are
approximately the same. There is very little difference between the voltages when the
32 Distribution System Modeling and Analysis
loads were allocated using the diversity factors and when the loads were allocated
based upon the transformer kVA ratings.
Section 2.5 showed that EV chargers add a significant load to the grid. The load
due to just one EV charger is substantial enough to cause overloading of transform-
ers, which could require replacement of the device.
PROBLEMS
2.1 The following are the 15-minute kW demands for four customers
between the hours of 17:00 and 21:00. A 25 kVA single-phase trans-
former serves the four customers.
Time #1 #2 #3 #4 #5 #6 #7 #8
3:00–3:30 10 0 10 5 15 10 50 30
3:30–4:00 20 25 15 20 25 20 30 40
4:00–4:30 5 30 30 15 10 30 10 10
4:30–5:00 0 10 20 10 13 40 25 50
5:00–5:30 15 5 5 25 30 30 15 5
5:30–6:00 15 15 10 10 5 20 30 25
6:00–6:30 5 25 25 15 10 10 30 25
6:30–7:00 10 50 15 30 15 5 10 30
Time #1 #2 #3 #4 #5
KW KW KW KW kW
05:00 2.13 0.19 4.11 8.68 0.39
05:15 2.09 0.52 4.11 9.26 0.36
05:30 2.15 0.24 4.24 8.55 0.43
05:45 2.52 1.80 4.04 9.09 0.33
06:00 3.25 0.69 4.22 9.34 0.46
06:15 3.26 0.24 4.27 8.22 0.34
06:30 3.22 0.54 4.29 9.57 0.44
06:45 2.27 5.34 4.93 8.45 0.36
07:00 2.24 5.81 3.72 10.29 0.38
07:15 2.20 5.22 3.64 11.26 0.39
07:30 2.08 2.12 3.35 9.25 5.66
07:45 2.13 0.86 2.89 10.21 6.37
08:00 2.12 0.39 2.55 10.41 4.17
08:15 2.08 0.29 3.00 8.31 0.85
08:30 2.10 2.57 2.76 9.09 1.67
08:45 3.81 0.37 2.53 9.58 1.30
09:00 2.04 0.21 2.40 7.88 2.70
The Nature of Loads 35
T1 and T2: 37.5 kVA, 2,400–240 volts, Z = 0.01 + j0.03 per unit
T3 and T4: 50 kVA, 2,400–240 volts, Z = 0.015 + j0.035 per unit
36 Distribution System Modeling and Analysis
Use the diversity factors found in Table 2.2 to complete the following:
REFERENCES
1. “eGallon”. Accessed on Dec. 8, 2021. [Online]. Available: https://www.energy.gov/
maps/egallon.