Air Dryer Manual - 2
Air Dryer Manual - 2
Air Dryers
operation instruction
One
CONTENTS
Introduction …………………………………………………………2
Two
1. Introduction
The main purpose of this manual is teaching user how to make our equipment to be treated
in exact use and maintenance. This procedure can prolong equipment's used-life and reduce
trouble for assuring the quality of air dryer. This manual also offers the related data in
equipment for reference & inspection. It's important to be familiar with this manual prior to
starting this equipment; moreover, subject to the instruction in operation and maintenance for
avoiding caused trouble of equipment.
2. Function Introductions
The main function of refrigerated type compressed air dryers is to remove the moisture in
compressed air, lowering the compressed air temperature to 1.6oC at dew point temperature
by air-to-refrigerant heat exchanger (refrigeration evaporator), and then, most of the water
vapor condenses into liquid droplets which are separated out of the air stream by a separator
and condensed liquid is discharged to out of the unit by auto drain, then finishing the whole
drying process. If all conditions are normal, it just has about 0.59 g/m3 water vapor in dry
compressed air, and its percentage of water removed can reach 93%.
Three
■ 3-2Refrigeration system flow
Refrigerant turns into air refrigerant of high pressure and high temperature by refrigeration
compressor (1). Moreover, lowering the temperature of air refrigerant-by-refrigerant heat
exchanger (2) first, then enters into liquid refrigeration after heat dissipation by condenser (3).
The main function of drier (4) is to dry and filter out water and impurity from refrigeration pipe.
After high-pressure liquid refrigerant is expansion through capillary tube (5), then forming air
and absorbing heat from compressed air in evaporator lowering air temperature, water vapor
condenses into liquid droplets. Refrigerant flow returning to compressor side of inlet by
through pipe, then continues use it after compressed it, then forming return route. (See
Diagram 1)
Four
26. Air-outlet Pressure Meter
27. Refrigeration Low-pressure Meter
28. Refrigeration High-pressure Meter DIAGRAM 1
Five
2) Usage of work station:
Environment Temperature: ≤42℃ (Water cooler model not limited)
Inlet Temperature : XS- A≤45℃ XS- AH ≤80℃
Inlet Pressure: 0.2Mpa-1.0Mpa (Over than 1.0Mpa may to order the goods)
Quantity of Cooler Water: Account on 0.18 t/h with every dealing 1Nm3/min
Cooler Water Temperature: Inlet water temperature≤35℃
Cooler Water pressure: 0.2-0.4Mpa
Six
D. Install a set of electric element beside of the power, for example the setup switch and
the air switch and the fuse and so on.
E. To touch the ground rightly.
Seven
8. Adjust of the Air Dryer
Our entire machine pass adjusts before out of the factory. And In generate, the user of below
12A(W) can use the machine install and operation illustration directly to open the machine.
Over 15A(W) model machine should let our technical worker to adjust the machine for you.
The operation people should take in our operation train first. During the using, if the machine
having abnormal phenomena, should relate with our company. And under leading of our
technical worker adjust some valve. Forbid to operate blindness and cause to attain machine
and the element.
9. General Maintenance Information
1) Clean the Air-cooling condenser usually to avoid the bott effect on the heating efficiency.
Clean way like following diagram
2) Check the automatic drain is needed to prevent sludge and contamination everyday. If clog,
please clean them by according to dissolve diagram
3) Clean the Water-cooling with the clean water and note to clean the filter to avoid the pipe
jam and can't expedite. The clean way like diagram 4. (If there is no water filter, should add
a filter net on the inlet of the pipe. If the auto drain doesn't work, can use the drain by hand
but it must exhaust the water in time to avoid the water inlet the air.
4) Note the three phases electric run with no phase.
5) Note to listen the compressor run in clam and no noise or not.
6) Note to touch the air inlet and outlet temperature with different temperature. (Normal
condition is near 10-17℃)..
7) The environment temperature of the Air Dryer does not fit below to 10℃, to avoid attaining
the compressor because of lacking the oil.
8) Clean the dust on the outside box usually.
Eight
10. Trouble Shooting
Nine
Air flow is higher than compressor's Replace compressor with larger
Air flow exceed rated air discharge capacity and the air discharge capacity
rated value pressure drops automatically
Reduce air flow
Ten
C) Can't operation
Symptom Possible Cause Corrective Action
Check the condition of earth
connection, check if the fuse
The power supply Fuse has broken
has broken or there is short
can't supple voltage
circuit.
Wire has broken Find the broken point and repair
Make the input voltage on the
Voltage is abnormal range shown on
nameplate
Switch has faulty Replace
Connector has faulty Replace
The power supply
Over Current Relay has faulty Replace
works normally but
High-low voltage switch has faulty Replace
can't startup machine
Startup Breaker has faulty Replace
Capacitor has faulty Replace
Temperature Switch, Flow Switch has
Replace
faulty
Compressor has faulty Replace
High-low voltage switch or over-current Find the reason for jumping off,
Switches are all relay hasn'treset after jumping off. then reset the switch or relay
normal, but still can't Compressor has faulty Replace
startup machine Find the loosen place and
Wire has loosen
fasten
D) Running is not good after startup
Eleven
startup Overload switch jump off Check
Condenser is too dirty Clean
Capacitor has faulty Replace
Voltage switch or temperature switch
Replace
has faulty to cause fan stop working
Hydraulic switch has faulty Replace
The interval between two startup
Continuous startup for several times
should be 3 minutes
Over Current Replay
Compressor has overloaded Reduce air flow
jumps off
Circumstance temperature or air dryer's Improve ventilation or add
inlet temperature cooling device
Fuse has broken Replace
Contactor has faulty Replace
Cooling water hasn't recycled Check cooling water
Twelve
Condenser fins clogged Clean
Drain valves are breakdown or not fully
Renew or open valves
opened
Back to normal pressure 2-25
Incorrect working pressure
kg/cm2
Incorrect auto-drain Auto drain declined Lay flate & reset
system Clean (refer to maintenance
Strainer is clogged
items)
Drain lines clogged Clean
Drain lines are higher than auto drain's Reset the drain lines
Trouble of drain float Replace
Thirteen
CT8893D User Guide Version: h160826
1 Technique Index
Temperature display range: -20~100℃(The resolution is 0.1℃)
Power supply: 220V ± 10% ( Product supply voltage to the product label shall
prevail)
Temperature sensor: NTC R25=5kΩ,B(25/50)=3470K
2 Operating Guide
2.1 Meaning of the index lights on the panel
Index
Name Light Flash
light
Ready to refrigerate, in the state of
Refrigeration Refrigerating
compressor start delay pro
Fan Fanning -
Defrost Defrosting -
Alarm - Alarm state
2.2 Meaning of the LED display
Alarm signal will alternate display temperature and warning code. (A xx)
To cancel the alarm need recharge the controller. Display code as follow:
Code Meaning Explain
Alarm from external alarm signal, refer to the internal
A11 External alarm
parameter code “F50”
The dew-point The dew-point sensor broken-line or short circuit(The
A21
sensor fault dew-point temperature display “OPE” or “SHr”)
Condensation The condensation broken-line or short circuit(Press “” will
A22
sensor fault display “SHr” or “OPE”)
The dew-point If alarm occurred in the dew-point temperature higher than the
A31
temperature fault set value, can choose whether closing down or not (F51).
Fourteen
The dew-point temperature alarm will not occurred when
compressor starts in five minutes.
Condensation If alarm occurred in the condensation temperature higher than
A32
temperature fault the set value, can choose whether closing down or not.(F52)
2.3 Temperature display
After power on self-test, the LED display the dew-point temperature value. When press
on“”, it will display the temperature of condenser. Reverse will back to display the dew-point
temperature.
2.4 Cumulative working hours display
Pressing on the“ ”at the same time, will display the compressor accumulated
operational time. Unit: hours
2.5 Higher level operation
Long press “M” 5 seconds to enter parameter setting condition. If have set the command,
will display word “PAS” to hint import the command. Using press“ ”to import the
command. If the code is right, it will display parameter code. Parameter code as followed table:
Setting Factory
Category Code Parameter name Unit Remark
range setting
The way of
dealing with 0 : Only alarm, not
F51 dew-point 0-1 1 - close.
temperature 1: Alarm and close.
alarm.
The way of
dealing with 0 : Only alarm, not
F52 condensation 0-1 1 - close.
temperature 1: Alarm and close.
alarm.
Fifteen
OFF means no
OFF
password
F80 Password 0001 -- OFF -
0000 System means
9999
clearing password
Switch machine
F83 YES - NO YES -
state memory
System means Display the
compressor Hou
F85 - -
accumulated r
operational time
Reset compressor
NO:not reset
F86 accumulated NO - YES NO -
YES:reset
operational time.
F88 Reserved
F98 Reserved
Testing This function can attract all relays in turn, and
F99 Test-self
please don’t use it when the controller is running!
End Exit
Sixteen
When external alarm occurs, stop the compressor and fan. External alarm signal has 5
modes (F50): 0: without external alarm, 1: always open, unlocked, 2: always
open, locked; 3: always closed, unlocked; 4: always closed, locked. “Always
open” means in normal state, external alarm signal is open, if closed, the
controller is alarm; “Always closed” is on the contrary. “Locked” means that
when external alarm signal becomes normal, the controller is still in the alarm
state, and it needs to press any key to resume.
3.4 Command
In order to prevent irrespective persons from changing the
parameters, you can set a password (F80), and if you have set a
password, the controller will hint you to enter the password after
you press the key “M” for 5 seconds, you must enter the correct
Setting Factory
Category Code Parameter name Unit Remark
range setting
dew-point
F11 temperature 10 - 45 20 ℃ It will warning when
warning point the temperature
Condensation higher than the set
F12 temperature 42 - 70 65 ℃ value.
Temperature warning point
Dew-point sensor -20.0 – Amend dew-point
F18 0.0 ℃
amendment 20.0 sensor error
Condensation
-20.0 – Amend condensation
F19 sensor 0.0 ℃
20.0 sensor error
amendment
Min
Compressor F21 Sensor delay time 0.0 – 10.0 1.0
ute
Seventeen
It will start when
Start antifreezing
-5.0 – dew-point
F31 demand 2.0 ℃
10.0 temperature lower
temperature
than the set value.
It will stop when
Antifreezing dew-point
F32 1-5 2.0 ℃
return difference temperature higher
than F31+F32.
OFF: close fan
1. The fan under the
control of
condensation
Fan/
The second way OFF temperature.
Antifreezing F41 1 -
the output mode. 1-3 2. Fan worked at the
same time with
compressor.
3. Antifreezing outpu
mode.
Fan start It will start when
F42 32 - 55 42 ℃
temperature condensation
temperature higher
Fan close than the set value. It
F43 temperature return 0.5 – 10.0 2.0 ℃ will close when lower
difference. than set return
difference.
Eighteen
0: without external
alarm
1 : always open,
unlocked
External alarm 2 : always open,
Alarm F50 0-4 0 -
mode locked
3: always closed,
unlocked
4: always closed,
locked
password, and then you can set the parameters. If you don’t need the password,
you can set F80 to “0000”. Notice that you must remember the password, and if
you forget the password, you can not enter the set state.
4 Wiring Diagram
Nineteen
5 Notes
Please use the temperature sensor allocated by our company.
If compressor power is less than 1.5HP, can direct control by internal relay. Otherwise
need to connect ac contactor.
Fan loaded with no more than 200w.
We have installed a 460V transformer to 220V, and the customer is connected to the
460V/60hz power supply, which can be directly used
Twenty