Product data sheet
Specifications
circuit breaker ComPact NSXm
N (50 kA at 415 VAC), 3P 3d, 32
A rating TMD trip unit, EverLink
connectors
LV426402
To be discontinued on: 30 June 2023
To be discontinued
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Important message : This product has been switched to new
ComPacT range and is no longer commercialized. It will continue
to be available in H1 2023 only limited to specific projects.
Main
Range ComPact
Product name ComPact NSXm
Range of product ComPact NSXm
Device short name NSXm 32N
Product or component type Circuit breaker
Device application Protection
Distribution
Number of poles 3P
Protected poles description 3D
[In] rated current 32 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category A
[Icu] rated ultimate short-circuit 90 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 50 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 600...690 V AC 50/60 Hz conforming to IEC 60947-2
Performance level N 50 kA 415 V AC
Trip unit name TM-D
Trip unit technology Thermal-magnetic
Trip unit protection functions LI
Control type Toggle
Circuit breaker mounting mode By screws
Clip-on
Apr 20, 2023 1
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand 8 kV
voltage
[Ics] rated service short-circuit 90 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 50 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
15 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability 20000 cycles
Electrical durability 10000 cycles at 440 V In
20000 cycles at 440 V In/2
5000 cycles at 690 V In
10000 cycles at 690 V In/2
Mounting support Plate
DIN rail
Connection terminals 1 Everlink lug wire size 2.5…95 mm², rigid or stranded aluminium/copper
1 Everlink lug wire size 2.5…70 mm², flexible copper
Connection pitch 35 mm with spreaders
27 mm without spreaders
9 mm pitches 9 module
Protection type L : for overload protection (thermal)
I : for short-circuit protection (magnetic)
Trip unit rating 32 A at 40 °C
Long-time pick-up adjustment Adjustable
type Ir (thermal protection)
[Ir] long-time protection pick-up 0.7...1 x In
adjustment range
Long-time protection delay Fixed
adjustment type tr
[Im] magnetic protection pick- 600 A
up range
Earth-leakage protection Without
Number of slots for electrical 1 slot(s) for auxiliary switch OF
auxiliaries 1 slot(s) for alarm switch SD
1 slot(s) for voltage release MN or MX
Width (W) 81 mm
Height (H) 137 mm
Depth (D) 80 mm
Net weight 1.06 kg
Colour Grey (RAL 7016)
Environment
Standards EN/IEC 60947
Product certifications CCC
EAC
Marine
Pollution degree 3 conforming to IEC 60664-1
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for -25…70 °C
operation
Ambient air temperature for -50…85 °C
storage
2
Apr 20, 2023
Relative humidity 0…95 %
Operating altitude 0...2000 m without derating
2000...5000 m with derating
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 12.5 cm
Package 1 Width 9.0 cm
Package 1 Length 22.0 cm
Package 1 Weight 1.3 kg
Unit Type of Package 2 S03
Number of Units in Package 2 8
Package 2 Height 30.0 cm
Package 2 Width 30.0 cm
Package 2 Length 40.0 cm
Package 2 Weight 12.29 kg
Offer Sustainability
Sustainable offer status Green Premium product
EU RoHS Directive Compliant
EU RoHS Declaration
Mercury free Yes
China RoHS Regulation China RoHS declaration
Product out of China RoHS scope. Substance declaration for your information
RoHS exemption information Yes
Environmental Disclosure Product Environmental Profile
WEEE The product must be disposed on European Union markets following specific waste collection and
never end up in rubbish bins
California proposition 65 WARNING: This product can expose you to chemicals including: DINP, which is known to the State of
California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or
other reproductive harm. For more information go to www.P65Warnings.ca.gov
Recommended replacement(s)
LV426402 is replaced by:
Circuit breaker, ComPacT NSXm 63N, 50kA/415VAC, 3 poles, TMD trip unit 32A,
1x EverLink lugs
C11N3TM032L
Apr 20, 2023 3