DATA SHEET               SPEC. No.
Ds 4019
                      OFFSHORE                                                 FOR
                                                                   GENERATOR RELAY,                  Rev. No.       0
                      DESIGN SECTION
                                                                CONTROL, SYNCHONISING &              Discipline     Elect
                      Engineering Services                       LOADSHEDDING PANELS
                      ISO 9001 : 2000                                  (T.G. SET)                    Page 1 of 6
                                                            DATA SHEET
       GENERATOR RELAY, CONTROL, SYNCHONISING & LOADSHEDDING PANELS
                               (T.G. SET)
1.0        SITE CONDITIONS
 1.1         Location                           :                              As per scope of work
1.2         Application                         :                                do
1.3         Area Classification                 :                               Safe
1.4    Presence of H2S in                       :                               No
   atmosphere
1.5         Installation                        :                              --------
 1.6         Design Ambient Temperature:                                       As mentioned in bid package
 1.7         Relative Humidity                      :                            do
 1.8         Elevation                              :                            MSL (approx)
1.9        Other site conditions                :                              Refer Spec. No 5006
2.0          SCOPE
2.1          Synchronising Panel                        :              Required
2.2          Load Shedding Panel                        :              Required
2.3          Relay & Control Panel                      :              1 no. for per set.
 3.0           UTILITIES
 3.1 Control Supply for Relays/                             :      110 VDC, * Watts
     Control Element
3.2 Control Supply for annunciator :       110 V DC, * Watts
    except for DC fail annunciator At one point
       FORMAT No.          Ref. PROCEDURE No.                   ISSUE No.                 REV. No.           REV. DATE:
       ODS/SOF/004A        ODS/SOP/008 TO 015                      02                       01                01/08/2006
                                                                          DATA SHEET           SPEC. No.      Ds 4019
                          OFFSHORE                                           FOR
                                                                GENERATOR RELAY,               Rev. No.       0
                          DESIGN SECTION
                                                             CONTROL, SYNCHONISING &           Discipline     Elect
                          Engineering Services                LOADSHEDDING PANELS
                          ISO 9001 : 2000                           (T.G. SET)                 Page 2 of 6
 3.3 Aux. & Space Heater supply                        :          240 V AC * KVA
                                                                   1phase 50 Hz
4.0          PANEL DETAILS
 4.1 Make                                          :
4.2          Type                                  :                          Simplex
4.3          Colour shade                              :
4.4          Dimensions ( LxWxH ) & Weight
           • Relay and Control Panel               :
           • Synchronising Panel                   :
           • Load Shedding Panel                   :
5.0          COMPONENT DETAILS
5.1          RELAY & CONTROL PANEL
5.1.1 RELAYS (Minimum)                                      NEMA NO.            QTY          MAKE      TYPE
      i.       Voltage Restrained O/C Relay (51V)
  ii.          Overload Relay               (49)
 iii.          IDMTL Eartnfault Relay                  (51G)
  iv.          Undervoltage Relay                      (27)
  v.           Overvoltage Relay                       (59)
  vi.          Negative Phase Sequence Relay (46)
 vii.          Underfrequency Relay                    (81)
viii.          Differential Protection Relay               (87)
           FORMAT No.        Ref. PROCEDURE No.               ISSUE No.           REV. No.             REV. DATE:
           ODS/SOF/004A      ODS/SOP/008 TO 015                  02                 01                  01/08/2006
                                                              DATA SHEET         SPEC. No.      Ds 4019
                       OFFSHORE                                  FOR
                                                    GENERATOR RELAY,             Rev. No.       0
                       DESIGN SECTION
                                                 CONTROL, SYNCHONISING &         Discipline     Elect
                       Engineering Services       LOADSHEDDING PANELS
                       ISO 9001 : 2000                  (T.G. SET)               Page 3 of 6
  ix.       Gen. Field failure relay           (40)
  x.        Reverse power relay                (32)
  xi.       P.T Secondary monitor relay        (60)
 xii.       Exciter Field O/C relay            (76)
xiii.       DC Cont. Supply Monitor relay (80)
xiv.        AC Cont. Supply Monitor relay (27)
 xv.        Trip Ckt. Supervision Relay        (95)
xvi.        Auxiliary Relays
        •   Lock out relay ( Generator )       (86G)
        •   Lock out relay ( Turbine )         (86T)
xvii.        Timers
5.1.2 METERS/INDICATORS/RECORDERS
   i. Generator Phase Ammeter
  ii. Generator Line Voltmeter
  iii. Power Factor Meter
  iv. KW/MW Meter with M.D.I
  v. KVAR/MVAR Meter
  vi. KVA/MVA Meter
 vii. KWH/MWH Meter
viii. Frequency Meter
  ix. Field Ammeter
        FORMAT No.        Ref. PROCEDURE No.      ISSUE No.           REV. No.           REV. DATE:
        ODS/SOF/004A      ODS/SOP/008 TO 015         02                 01                01/08/2006
                                                       DATA SHEET         SPEC. No.      Ds 4019
                   OFFSHORE                               FOR
                                              GENERATOR RELAY,            Rev. No.       0
                   DESIGN SECTION
                                           CONTROL, SYNCHONISING &        Discipline     Elect
                   Engineering Services     LOADSHEDDING PANELS
                   ISO 9001 : 2000                (T.G. SET)              Page 4 of 6
 x. Recorders
           •     Load (MW)
           •     Frequency
           •     Voltage (3 Phase)
           •     Current (3 Phase)
           •     Clock ( Quartz )
           •     Hour run meter
5.1.2 CONTROL SWITCH/PUSH/BUTTONS
    i. Breaker Control Switch
    ii. Ammeter Selector Switch
   iii. Voltmeter Selector Switch
   iv. Control Supply M.C.B. (A.C./D.C)
    v. Space heater Supply M.C.B.
   vi. Parallel/Independent Selector Switch
   vii. Voltage Raise / Lower P.B
  viii. Speed Raise / Lower P.B
   ix. Auto/ manual Selector Switch
    x. Lamp test P.B
   xi. Test/Accept/reset P.B for annunciator
   xii. MCBs for miscellaneous use
  xiii. Emergency Trip Push Button
  FORMAT No.          Ref. PROCEDURE No.   ISSUE No.           REV. No.           REV. DATE:
  ODS/SOF/004A        ODS/SOP/008 TO 015      02                 01                01/08/2006
                                                              DATA SHEET         SPEC. No.      Ds 4019
                  OFFSHORE                                       FOR
                                                     GENERATOR RELAY,            Rev. No.       0
                  DESIGN SECTION
                                                  CONTROL, SYNCHONISING &        Discipline     Elect
                  Engineering Services             LOADSHEDDING PANELS
                  ISO 9001 : 2000                        (T.G. SET)              Page 5 of 6
5.1.4 MISCELLANEOUS ITEMS
     i. Annunciator Points
     ii. Space heater
    iii. Test Plugs
    iv. Cubicle Illumination Lamp
     v. 5A Socket with Switch
    vi. Hooters (AC & DC)
      vii.MimicDiagram
5.2 SYNCHRONISING PANEL                      ( COMMON FOR ALL GENERATORS )
  i. Check Synchronising Relay             (25)
 ii. Synchroscope
 iii. Synchronisation mode selector switch
 iv. Synchroscope cut off switch
 v. Double Frequency Meter
 vi. Double Voltmeter
vii. Auto synchronising Relay with Accessories
viii. Synchronising lamps
 ix. Breaker Control Switch
 x. Voltage Raise/Lower P.B
 xi. Speed Raise/Lower P.B
xii. PT Selector Switch
   FORMAT No.         Ref. PROCEDURE No.          ISSUE No.           REV. No.           REV. DATE:
   ODS/SOF/004A       ODS/SOP/008 TO 015             02                 01                01/08/2006
                                                     DATA SHEET         SPEC. No.      Ds 4019
                 OFFSHORE                               FOR
                                            GENERATOR RELAY,            Rev. No.       0
                 DESIGN SECTION
                                         CONTROL, SYNCHONISING &        Discipline     Elect
                 Engineering Services     LOADSHEDDING PANELS
                 ISO 9001 : 2000                (T.G. SET)              Page 6 of 6
5.3 LOAD SHEDDING PANEL
   As described in clause 5.9.10 of the Functional specification no. FS 4019 (the functional
   specification for control, relay, synchronizing and load shedding panel.)
 NOTE
  • All blank columns and Data marked with asterisk (*) shall be filled up by Vendor.
  • The relays shall be of multi protection and multi metering electronic intelligent type (
    microprocessor based numerical programmable logic relay ).
  • This Data Sheet for TG incomer has not been provided and shall be developed by contractor
    for purchase requisition based on requirement given in FS4040 and shall be submitted to
    company for approval.
  • At MNW, Alstom make load shedding panel is provided which is interfaced with HV drives
    and generator cubicle of MNW but same is not working and needs to be disconnected.
    After disconnection of interfacing of HV drives and generator cubicles of MNW, the same
    shall be extended to MNP load shedding panel by providing and executing suitable
    interface equipment and multi core cable.
  • In addition to the generator annunciation points, contractor shall decide additional
    annunciation points as per requirements mentioned elsewhere in bid package        during
    detailed engineering and provide the same in the generator control panel.
  FORMAT No.        Ref. PROCEDURE No.   ISSUE No.           REV. No.           REV. DATE:
  ODS/SOF/004A      ODS/SOP/008 TO 015      02                 01                01/08/2006