TYCO Fire Protection Products Technical Support
October 15, 2016
Software Release
Product: 4100ES, 4010ES
Programmer: ESProgrammer_3.05.exe
Executive: ES_3.05.bin
Slaves included: 4010idnetplus_3.12.10
(new files in bold) Amp_20203 (cards 566-205, -206, -208 use with > 28 speakers/circuit)
Amp_2.03.03 (cards 566-205, -206, -208 use with up to 28 speakers/circuit)
Amp2_3.02.05 (cards 566-521, -523, -524)
AudAna_20101
AudDig_10502 (card 566-033)
AudDig2_20102 (card 566-409)
BMUX_10102
BNIC_1.01.02
CPUBoot_2.02.02
EBOOT_1.01.03
EOS_1.01.02
EPS_1.05.02
ESS_1.05.02
FUI_1.05
FUIBoot_104
idnet_3.12.10
idnet1plus_3.12.10
idnet2_1.03
idnetplus_3.12.10
LMC_3.01.01
MSS_31208
mssi_3.12.10
mxdloop_2.01.03
Phone_1.04.01
RPS_31208
SPS_204 (for Rev E and earlier boards)
sps_3.12.10
TFXLoop_10103
TIC_3.01.01
TIC2_1.01.01
TPS_1.05.05
XALIC_10105
XBC_10604
XPS_31208
XSIG_101
Compatibility See SB11002 (in C:\4100ESINFO)
After downloading:
Find the Programmer installation file in C:\4100ESProg
Find the BIN files in C:\4100ubin\Rev3-05
Find the documentation in C:\4100ESinfo
To Install the Programmer go to C:\4100ESProg and double click on ESProgrammer_3.05.exe
ES Programmer 3.05
DBF Revision = 174
Functional Changes:
This release is synchronized with the release of the AutoPulse Programmer (version 3.05).
Fixed Defects:
755204 4100ESI NDU jobs are missing the Network Interface and Repeater Cards as
selectable cards
Other Changes:
None
4100/4010ES Executive 3.05
Functional Changes
Add support for panel branding (no branding available for 4100ES)
Fixed Defects
None
Other Changes
None
Usage Notes
Requires revision 2.02.02 or greater of CPU Bootloader.
Revision 3.04.03 of the ESSupport tools should be used with this release.
Requires EPS revision 1.05.02 or later
Requires InfoAlarm revision 1.04 and InfoAlarm Bootloader revision 1.04.
FUI_1.05.bin
Functional Changes
Added support for NXNA Symbolic Name (SIGx-y) direct point call up.
Fixed Defects
None
Other Changes
None
TIC2_1.01.01.bin
Functional Changes
None
Fixed Defects
747704 TIC2 does not generate broadcast alarm message in local mode.
Other Changes
None