NAVFAC MO-322
Volume II
January1993
SN 0525-LP-542-8700
SNDL DISTRIBUTION
(2 Copies each):
The primary goal of this publication is to provide a system and recommended pro-
cedures to permit cost effective, quality, and responsive real property inspections. Use
of this guidance will assure economical maintenance and maximum reliability of
facilities and equipment.
This publication has been reviewed in accordance with the Secretary of the Navy
Instruction 5600.16A and is certified as an official publication of the Naval Facilities
Engineering Command.
E. R. HAMM
CAPTAIN, CEC, U. S. Navy
Assistant Commander for
Public Works Centers and Departments
i
ABSTRACT
The contents include inspection guides for Structural, Electrical, Mechanical, and
Roofing categories. Each guide is formatted into sections including a definitions sec-
tion, an instructions section and a repair/replacement criteria section. The definitions
section provides a listing of related terms and their meanings and scope with respect to
performance of physical inspection. The instructions section is the basic trade inspec-
tion guide. The repair/replacement criteria section provides guidance to determine the
best course of action to correct reported deficiencies.
iii
CHANGE CONTROL SHEET
Document all changes, page replacements, and pen and ink alterations posted in this manual.
v
Table of Contents
1. INTRODUCTION l-l
2. APPLICATION 2-1
vii
5. STRUCTURAL INSPECTION GUIDE 5-1
viii
5.2.28 Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-54
5.3 REPAIR/REPLACEMENT CRITERIA . . . . . . . . . . . . . . . . . . 5-54
5.3.1 Asbestos . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-54
5.3.2 Ceiling. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-54
5.3.3 Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-54
5.3.4 Door . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-55
5.3.5 Exterior walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-56
5.3.6 Fencing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-56
5.3.7 Floor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-56
5.3.8 Foundation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-56
5.3.9 Interior walls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-56
5.3.10 Painting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-56
5.3.11 Pavement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-57
5.3.12 Stair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-57
5.3.13 Waterfront . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-57
5.3.14 Window . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5-57
ix
6.2.11 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-34
6.2.12 Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-35
6.2.13 Pump (Submersible Sump) . . . . . . . . . . . . . . . . . . . . . . 6-36
6.2.14 Sanitary Sewage Utility System . . . . . . . . . . . . . . . . . . . . 6-36
6.2.15 Steam Utility System . . . . . . . . . . . . . . . . . . . . . . . . . . 6-36
6.2.16 Unfired Pressure Vessels . . . . . . . . . . . . . . . . . . . . . . . 6-37
6.2.17 Water heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-43
6.2.18 Water Utility System . . . . . . . . . . . . . . . . . . . . . . . . . . 6-43
6.3 REPAIR/REPLACEMENT CRITERIA . . . . . . . . . . . . . . . . . . 6-44
6.3.1 Air conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-44
6.3.2 Airhandler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-45
6.3.3 Eye wash/shower . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-45
6.3.4 Exhaust . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-45
6.3.5 Fire protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-46
6.3.6 Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-46
6.3.7 Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-47
6.3.8 Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-48
6.3.9 Plumbing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-49
6.3.10 Water heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6-49
x
7.2.8 Fresh Water Storage (Cathodic Protection System) . . . . . . . . 7-16
7.2.9 Fuses and Small Circuit Breakers (Under 600 Volts and
30 Amperes) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-23
7.2.10 General wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-24
7.2.11 Ground Test (Lightning Protection) . . . . . . . . . . . . . . . . . 7-25
7.2.12 Grounds and Grounding Systems . . . . . . . . . . . . . . . . . . 7-26
7.2.13 Instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-28
7.2.14 Lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-30
7.2.15 Motors and Generators . . . . . . . . . . . . . . . . . . . . . . . . 7-30
7.2.16 Navigation Lights . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-37
7.2.17 Panels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-38
7.2.18 Potheads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-39
7.2.19 Power Plants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-39
7.2.20 Rectifiers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-42
7.2.21 Relays . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-44
7.2.22 Steel Power Poles and Structures . . . . . . . . . . . . . . . . . . 7-45
7.2.23 Switchgear . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-47
7.2.24 Wood Poles and Accessories . . . . . . . . . . . . . . . . . . . . . 7-48
7.3 REPAIR/REPLACEMENT CRITERIA . . . . . . . . . . . . . . . . . . 7-52
7.3.1 Fire Alarm . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-52
7.3.2 General wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-52
7.3.3 Lighting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-53
7.3.4 Panels (Primary, Secondary, and Sub) . . . . . . . . . . . . . . . . 7-53
xi
8.2.5 Trusses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-5
8.2.6 Moisture Survey Instructions for Built-Up Roofs . . . . . . . . . . 8-7
8.3 REPAIR/REPLACEMENT CRITERIA . . . . . . . . . . . . . . . . . . . 8-7
8.3.1 Asphalt strip shingles . . . . . . . . . . . . . . . . . . . . . . . . . . 8-7
8.3.2 Built-up Roof . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-8
8.3.3 Metal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
8.3.4 Slate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
INDEX Index-1
xii
CHAPTER 1. INTRODUCTION
The Shore Facilities Inspection System includes three (3) inspection categories:
Operator Inspection, Preventive Maintenance Inspection (PMI) and Control Inspec-
tion. Specialized Inspection is included within the Control Inspection category. This
manual provides procedural guidance and Inspection Guides needed to perform Con-
trol Inspections.
While this manual does not cover Specialized Inspections performed by Engineering
Field Divisions, Public Works Centers, etc., results of Specialized Inspections should be
integrated with findings of the Control Inspection program to determine overall facility
condition.
1-1
n Identification of existing and potential problems in a facility, for which
cost estimates can be made or, when appropriate, Emergency/Service
calls can be initiated,
n Assessment of facility condition,
n Reassessment of previously identified maintenance and repair work, and
n Information to maintain and update the inventory of facility components.
l-2
CHAPTER 2. APPLICATION
This manual is designed to aid the facilities inspector in preparing and performing
facility inspections and reporting facility deficiencies. A systems approach is used to
facilitate inspections by trade or craft. Generally, inspections are divided into Struc-
tural, Electrical, Mechanical, and Roofing. This manual includes inspection guides for
these categories.
2-1
CHAPTER 3. GENERAL INSPECTION INSTRUCTIONS
3.1 OVERVIEW: Each inspection begins with planning, scheduling, research and folder
preparation. Inspections are performed by inspectors with trade expertise so the best
quality inspection may be made. Each inspector must use their own trade knowledge
when inspecting. The key to good facility maintenance planning is the performance of
complete inspections. Considerations as to repair versus replacement, methods,
materials, conditions, economics, etc. must be considered for each deficiency noted
from the inspection. After inspectors finish facility inspections, they make cost es-
timates for the deficiencies found, prioritize the deficiencies and prepare a facility In-
spection Report.
3.2 SCOPE: A facility inspection includes all systems and components on the facility, in
the facility and within 5 feet of the outside shell of the facility. This includes piping,
wiring, steps, awnings, and sidewalks.
Have a physical - The physical must certify that you are healthy enough to:
n Wear a respirator
n Crawl in attics and crawl spaces
n Endure other daily tasks of inspectors
Have a respirator fitted for you - You must use and take care of the respirator.
Whenever you are in a crawl space, an attic, or other space that might have asbestos, you
must wear a respirator.
Collect other safety equipment - Along with a respirator, the following safety
equipment should be assembled:
Hard hat - to be worn in designated areas
n Safety glasses - to be worn in designated areas
3-1
Safety shoes - to be worn during all inspections
Coveralls - to be worn as necessary
Asbestos coveralls & booties - to be worn in all attics, crawl spaces, and
areas that might have asbestos
Gloves - to be worn as necessary
Ear plugs - to be worn in designated areas
Knee pads - to be worn when crawling
Collect inspection tools - The following items will be useful during inspections:
Group items for all trades:
• Ladders
• Trucks
• Cameras
• Polaroid
• 35 MM
• Sonic tape
• Micro cassette recorder
• Measuring wheel
• Individual items for all trades:
• Employee Identification Card - to be worn or carried during all
inspections
• Note pad
• Inspection Report Forms
• Inspection instructions for your trade
• Flashlight
• Tape measure
• Rule
• Rain suit
• Tool bag
• Clip board
• Screwdrivers
• Phillips
• Straight slot
3-2
Structural:
• Hammer
• Sharp, pointed instrument - knife, etc.
• Adjustable wrench
• Pliers
Mechanical:
• Socket wrench
• Nut driver set
• Allen wrench
• Adjustable wrench
• Amp probe
Electrical:
• Nut driver set
• Amp probe
• Side cutters (9” handle recommended)
• Crescent wrench (6” recommended)
• Slip joint pliers
• Knife
Waterfront:
• Adjustable wrench
• Phillips head screwdriver
• Socket wrench
• Nut driver set
• Boat with life preserver and/or vest
Pavement:
• PAVER book
• Tape measure
• Rule
Utilities:
• Manhole cover puller
• Blower for manholes (if going in)
3-3
Note: It the inspection requires going into the manhole, a gas
free test must be made before entry.
3.5.2 Inspector Scheduling. To begin, the inspector should schedule to meet the
facility point-of-contact to discuss problems about the facility prior to actual inspection.
If the facility has any security restrictions, make arrangements to gain access and follow
procedures as prescribed by local regulations before beginning inspection.
3.5.3 Research and Folder Preparation. Before going to the facility, inspectors
should collect all information available about the area to be inspected. It is important
to determine problems known and previously reported for revision and update in the
scheduled inspection. Sources of this information include previous inspection reports
and cost estimates, currently scheduled or in-process minor and specific (Labor Class
Codes 06-07) jobs, related contract jobs and warranty data, in-process Emergency and
Service jobs, Military Construction (MCON) and Special Projects. ‘Much of this infor-
mation can be obtained in the form of data base reports where automated systems are in
use. Scaled floor plans (one line drawings) should also be obtained for marking
deficiency locations. Inspection Report forms should be obtained and topical informa-
tion completed. All of this information should be organized into a facility inspection
folder for ready use until the job is complete.
3-4
3.7 INSPECTION PROCEDURE:
3-5
3.8 ADDITIONAL INSPECTOR DUTIES:
3.8.1 Emergency/Service Work. For minor deficiencies (where labor is es-
timated to be less than 16 hours), Inspector should submit a Service call. If there could
be loss or damage to government property, essential services have been disrupted or a
personnel hazard exists, Inspector should submit an Emergency call. The Inspection
Report should be annotated accordingly.
3.8.2 Safety Hazards. Where safety hazards are found, Inspector should immedi-
ately notify:
n Activity’s Safety Office
Inspector Supervisor
n Activity’s Staff Civil Engineer or Facilities Management Engineering
Division Director
3.8.3 Use of Repair/Replacement Criteria:
Based on physical inspection, determine the following about the Special Project:
n Is the scope correct?
n Is the cost accurate?
• Has inflation been considered?
• Have parts or labor for the tasks increased faster than inflation?
n Is the proposed method of correction appropriate?
n Does the Project still need to be done?
3-6
n Does the Project have sufficient detail?
Based on the findings above, process Special Project as follows (provide any amend-
ments recommended to special projects):
n Special Project looks correct, no changes are recommended - Don’t do
anything to the Project.
n Incorrect scope or cost - Suggest an amendment to the Project.
n Project unnecessary - Suggest cancellation of the Project.
n Lack of detail - Suggest an amendment to the Project.
3.10 INCORRECT OR CONFLICTING INFORMATION HANDLING:
3-7
CHAPTER 4. INSPECTION GUIDES
This chapter includes Inspection Guides which are trade oriented. Each Guide is
formatted into sections generally including a definitions section, an instructions section
and a repair/replacement criteria section. The definitions section provides a listing of
related terms and their meanings with respect to performance of physical inspection.
The instructions section is the basic trade inspection guide. The repair/replacement
criteria section provides guidance to determine the best course of action to correct
reported deficiencies. Cost estimates should be developed using applicable criteria.
4-1
STRUCTURAL
5.1 DEFINITIONS:
Aircraft Power Check Facility - consists of aircraft securing fittings and mooring eyes
anchored in concrete, tie-down chain assembly with aircraft holdback fitting and blast
deflectors.
Antenna-Supporting Towers and Masts - includes guyed radiators and guys, antenna-
supporting strongbacks, strongback insulation to towers, elevating mechanisms, and
obstruction and navigation lighting, but does not include inspection of antenna.
Bridges and Trestles - includes those constructed of steel, timber, masonry, concrete,
and composite materials. It does not cover concrete boxes with integral floor, which are
classed as culverts regardless of span, and are included in Storm Drainage Systems.
Brows and Gangways - includes brows and gangways constructed of steel, wood, and
aluminum.
Doors and Gates - the door package and the interface with the facility and fence gates
Floor - from top of the foundation to the air in the room, including carpet, tiling, paint-
ing, etc.
Fresh Water Storage - includes ground storage reservoirs and tanks and elevated
5-1
STRUCTURAL
storage tanks in fresh water systems. Included also are the various accessories normally
associated with fresh water tanks.
Grounds - includes lawn and turf areas, areas seeded to rough grasses, agricultural and
grazing lands, woodlands, trees and shrubs, runoff and erosion control works, fill and cut
slopes, gullies, irrigation systems, and weed control.
Pavement - concrete and asphalt roads, parking lots, sidewalks and airfields
Railroad Trackage - includes running tracks, access tracks, classification yards, sidings,
and storage track
Retaining Walls - retaining walls of all kinds, including cribbing and sheet piling when
used as retaining walls.
Stair - stairs go from one level to another with 8 treads or more, steps are less than 8
treads.
Storm Drainage Systems - includes catch-basins, curb inlets, pipelines, headwalls, out-
falls and tide gates, drop structures and spillways, manholes, culverts, subsurface
drainage, gutters, and ditches. A plan of the entire storm drainage system from inlets to
outfall ditches should be used.
Swimming Pools - includes swimmi ng pools, wading pools, and accessories, such as
spring boards and diving towers.
5-2
STRUCTURAL
5-3
STRUCTURAL
5-4
STRUCTURAL
5-5
STRUCTURAL
5-6
STRUCTURAL
5-7
STRUCTURAL
Asbestos-Continued
n Friable forms: (dry material which can be crumbled or reduced to powder
by hand pressure.):
• Pipe Lagging
• Sprayed on insulation
• Troweled on insulation
• Tile
• Ceiling
• Acoustic
• Insulating
n Nonfriable forms: (dry material which can be dispersed into atmosphere
by mechanical actions such as sawing.):
• Floor Tile
• Roofing
• Sheathing
• Piping
• Concretes
5.2.5 Bridges and Trestles: Comply with all current safety precautions. Check
for:
n Side Slopes:
• failure to maintain slopes of 1-1/2 to 1 or more
• soil erosion
• inadequately protected with vegetation or mulch
• concrete overlays (if applicable)
• cracking
• spalling
• broken areas
• other damage
• erosion
• settlement
5-8
STRUCTURAL
5-9
STRUCTURAL
5-10
STRUCTURAL
5-11
STRUCTURAL
5-12
STRUCTURAL
5-13
STRUCTURAL
5-14
STRUCTURAL
5-15
STRUCTURAL
5-16
STRUCTURAL
5-17
STRUCTURAL
5-18
STRUCTURAL
5-19
STRUCTURAL
5-20
STRUCTURAL
Exterior wall-Continued
n Wall coverings - Check for:
• Missing sections
• Loose sections
• Damage
• Cracks
• Spalls
• Bulges
n Trim and cornices - Check for:
• Missing Sections
• Loose sections
• Damage
• Rot
Steps, stoops, and porches - Check for:
• Loose sections
• Damage
• Rot
• Bug infestation
• Cracks
• Spalling
• Separation of concrete components
• Settlement
• Missing members
n Water penetration - Look closely at the areas with water damage or water
spots and stains. Check for:
• Openings
• Caulking
• Seals
• Exterior wall surfaces
• Holes
• Cracks
5-21
STRUCTURAL
Exterior wall-Continued
• Mortar joints
• Spalling
• Cracks
• Flashing deficiencies
• Condensation
• Equipment/piping leaks
5.2.12 Fencing: Refer to Doors and Gates above for fence gates. Check for:
n Missing sections and parts:
n Damage:
n Rust:
n Tunneling and erosion:
5.2.13 Floor: Check for:
n Standing Water:
• Grade
• Leaks
• Clogged drains
n Carpet:
• Wear
• Soil
• Damage
n Tile:
• Wear
• Missing and loose tiles
• Damage
n Deflection:
5-22
STRUCTURAL
5.2.14 Foundation:
n Wood - Probe the wood frames with a sharp instrument to check for:
• Rot
• Water damage
• Bug infestation
• Deterioration
• Settling
• Leaks
n Concrete/masonry - Check for:
• Settling
• Deterioration
• Spalling/cracking
• Leaks
5.2.15 Fresh Water Storage: Comply with all current safety precautions. The
health of personnel who enter reservoirs or tanks for inspection must be approved by
the medical officer of the activity. To assure against contamination of potable water,
procedures established by the Public Works Officer must be carried out. Check for:
n Concrete Foundations:
• settlement
• cracks
• spalling
• exposed reinforcing
• insect infestation
• erosion & undermining
n Wood Foundations and Pads:
• checked
• split
• rot
• insect infestation
• direct soil contact of untreated wood
• settlement
5-23
STRUCTURAL
5-24
STRUCTURAL
5-25
STRUCTURAL
5-26
STRUCTURAL
5-27
STRUCTURAL
5-28
STRUCTURAL
Grounds-Continued
• diseases
• insect damage
• erosion
• silt deposits
• waterborne debris
• excessive height
• bruised or damaged ends from dull mower
Trees and Shrubs in Landscaped Areas:
• lack of vigor
• need of trimming
• interference with utilities or buildings
• injury from mowers
• structural weaknesses
• storm, disease or insect damage
Border Strips and Areas Seeded to Rough Grasses for Erosion Control:
• poisonous or noxious weeds
• seedling trees that may hinder future mowing
• erosion and siltation
• lack of vigor
• inadequacy of coverage
• evidence of burning
n Woodlands:
• erosion
• dead, diseased, or damaged trees
• fire-lanes for being impassable
• vegetation growth that may carry ground fires
• hollow trees
5-29
STRUCTURAL
Grounds-Continued
n Earth Dams and Dikes:
• damage from erosion
• burrowing animals
• seepage
• lack of vegetation density or vigor of growth
• drop inlet pipes for stoppage
• logs
• debris
• outlet ends for erosion
• piping damage or failure
n Emergency Spillways of Drop Inlet Dams:
• blockage
• erosion damage
Permanent Check Dams in Water Course:
• overflow at notch section
• bypassing at ends
• erosion on downstream side
• damaged and deteriorated walls and apron
Hillside and Terrace Diversion Embankment, Channels, and Culverts:
• silt
• debris
• rank vegetation
• low and weak sections
• overflow
• erosion
• gullying
• burrowing animals
5-30
STRUCTURAL
Grounds-Continued
n Valley Drainage Channels including Culverts and Lateral Drains and Tile
at Entrance Points:
• overflow
• stoppage
• silt
• debris
• bank vegetation
• erosion
• caving
• sloughing
• scour
n Vegetated Waterways:
• inadequate vegetation fullness and cover in relation to ground
surface area that should be shielded
• erosion of waterway and along sides
• debris
• overflow
n Fill Slopes on Barricades, Highways, Railways, Airfield Runways, Igloos
and other Soil-Covered Buildings:
• erosion
• burning
• steepness
• lack of vigor and insufficient vegetation coverage for protection
against beating rain and direct sunshine
• inadequate fill depth at top of slope wherever buildings and
weather conditions necessitate variations on different slopes
• inadequate surface runoff piping
• insufficient thickness of organic mulch (gravel, slag, etc)
5-31
STRUCTURAL
Grounds-Continued
n Cut Slopes and Diversion Channels:
• erosion
• scour
• burning
• weaknesses from past or possible overflow
• lack of vigor or growth and insufficient vegetation coverage
• inadequate surface runoff piping
n Gulleys including all Surface Water Entrances and Upstream Ends or
Head where Mainstream Enters:
• current rate of erosion
• resulting pollution and sedimentation of downstream lakes
• channels
• damaged lands
• impairment of bridges and other structures
• need of erosion control such as temporary brush and wire dams and
plantings
Sprinkler System Nozzles, Sprays, Hose, Pipe and Valves:
• rust
• corrosion
• clogging
• inadequate width or pressure
• leakage
• defective operation
• evidence of water usage waste indicated by metering records or
computations from nozzle hours per acre per annum
5-32
STRUCTURAL
Grounds-Continued
n Flood Irrigation Systems including Delivery Channels, Gates,
Flow-Control and Water Turnout Works, and Border-Dikes:
• defective operation
• erosion
• silting
• scour
• water loss
• improper application
• failure to supply to all parts of tract
n Windbreaks of Trees:
• breakage
• lack of vigor
• dead or dying trees requiring replacement
• disease and insect damage indicated from condition of leaves
• branches interfering with utility lines
• contour ridges in arid sections inadequate to prevent surface runoff
and retain and cause absorption of storm waters around tree
n Weed Control:
vigor and rapid growths indicating need of reapplying soil sterilents
erosion damage where soil sterilents were used
check for emergence of any and all types of vegetation as an index
of the efficacy of the remaining soil chemicals and a need for
applying additional chemicals to the soil
where selective contact sprays are used, check for percentage of kill
and injury to vegetation that is to be preserved
check vegetation on adjoining lands for damage by spray drift
5.2.17 Imhoff and Septic Tanks: Refer to NAVFAC Technical Publication
DM-5 for standards.
n Visit all septic and Imhoff tanks and manholes to determine proper
operation:
n Note any indication of oil, gasoline, or lubricating grease entering the
system:
5-33
STRUCTURAL
5-34
STRUCTURAL
Railroad Trackage-Continued
n Rails:
• Breaks
• splits
• cracks in head, web or base
• damage from flat wheels
• wear
• head wear
• creeping or shoving, particularly at curves or ends
• batter
• overflow
• chipping
• joints
• loose angle or splice bars
• loose or missing bolts
• inadequate expansion. Ends of 39 ft. rails should butt at
85°F. At lower temperatures, clearance of 1/16 inch for
every 20° difference or part thereof
• loose spikes/fasteners or failure to provide sufficient quantity per tie
• improper tie plate seating
• improper support of rail
• obstructed flangeways of girder-type rails
• obstructed flangeways and tops not flush with pavement or crossing
for standard-type rails
• Road Crossing
• poor condition
• roughness to road traffic
• obstructions
n Ties:
• Decay
• splitting
• general deterioration
5-35
STRUCTURAL
Railroad Trackage-Continued
• rail cutting
• insufficient or improper embedment in ballast to prevent movement
• inadequate drainage
n Ballast:
• Dirt and mud accumulations
• soft or wet spots
• grass or weeds
• washing away and settlement
• inadequate extension beyond ties
• slope to grade steeper than 2 to 1
n Drainage:
• Obstructed drainage ditches and culverts
• erosion of side slopes and shoulders
• actual or potential slides onto or close to track
• washing or erosion at head-walls
• inlets discharge openings
n Turnouts: Refer to NAVFACINST 11230.1(Series) to determine proper
gages, for example, between frogs and flange faces and on tangents and
curves:
• Lack of lubrication
• clogged with debris or dirt
• inadequately spiked
• out-of-gage
• improper operating condition of switch points, switch latches,
targets, and lamps:
• loose/missing rail braces
• worn/damaged switch and frog points
n Tank Car Unloading Tracks:
• Bonding wires across rail joints, between rails and unloading header
pipelines, and connections between rails and ground rods, and
insulated rail joints
5-36
STRUCTURAL
Railroad Trackage-Continued
• loose connections
• corrosion
• frayed or broken strands. (Repair when one strand broken in
7-strand, or more than 3 broken in 19-strand.)
n Protective Devices:
• Warning Signs
• inadequate
• improperly placed
• illegible
• telltales improperly placed and in poor condition
• Warning signals/gates
• inadequate and poor structural stability of bumper blocks and cattle
guards.
• Guard Rails:
• poor structural condition and improper placing at sharp
curves
• steep embankments
• trestles, bridges, or other locations where derailment would
be serious
• Retaining Walls:
• undermining
• misalignment
• weephole obstructions
• other deficiencies that would tend to endanger tracks
n Clearances:
• Clearances at warehouses and structures less than 8’ from center
line of track from rail to 22’ above rail
• Clearances of overhanging shed roof less than 5’6” from centerline
of track and from rail to 15’6” above rail
• Clearances that do not conform to AREA standards and are less
than those required by serving railroad
5-37
STRUCTURAL
Railroad Trackage-Continued
• Presence of weeds or other obstructions blocking view, creating fire
hazard, or reducing clearances
5.2.21 Retaining Walls: Check for:
n Concrete Foundations:
• cracked
• broken
• scoured
• spalling
• exposed reinforcing
• evidence of lateral movement, settlement, undermining and rotation
n Concrete or Masonry Walls:
• cracked
• broken
• spalling
• misplaced sections
• general deterioration
• exposed reinforcing
• eroded and sandy mortar joints
• bulging
• vertical and horizontal misalignment
n Timber Walls and Cribbing:
• cracked
• broken
• loose
• missing
• wearing
• undermining
• rotting
• insect infestation
• bulging
5-38
STRUCTURAL
Retaining Walls-Continued
• vertical and horizontal misalignment
n Sheet Piling and Bulkheads:
• rust
• corrosion
• bulging
• vertical and horizontal misalignment
n Evidence of seepage resulting from obstruction in weepholes or other
drainage outlets:
n Loose or missing premolded expansion joint material allowing washout of
backfill:
n Structural inadequacy and poor physical condition of deadman anchors,
other attachments and fastenings:
n Embankment Slopes and Areas Behind Walls:
• erosion, settlement or slippage resulting from improper drainage
• lack of full sod or vegetation coverage
• damage from burrowing animals
• slopes steeper than angle of repose
5.2.22 Pavement:
n Asphalt - Check for:
• Alligatoring
• Bleeding
• Blade cracking
• Bumps and sags
• Conjugation
• Depression
• Edge cracking
• Joint reflection
• Lane/shoulder
• Longitudinal
• Patching
• Polished
5-39
STRUCTURAL
Pavement-Continued
• Potholes
• Railroad
• Rutting
• Shoving
• Slippage
• Swell
• Weathering
n Concrete - Check for:
• Blow-up buckling
• Comer breaks
• Joint repairs
• Spalling comer or joint
• Pop-outs
• Partial slab replacement
• Full slab replacement
• Partial depth replacement
• Full depth replacement
• Linear cracking
• Shrinking
• Scaling
• Faulting
• Exposed reinforcement
5.2.23 Stair: Exterior stairs, ladders and handrails - Check for:
n Rust:
n Rot:
n Damage:
n Deterioration:
5-40
STRUCTURAL
5.2.24 Storm Drainage System: Comply with all current safety precautions.
Check for:
n Ascertain that invert elevation on nonsedimentation basin and pipe are
same:
n Catch-Basins and Curb Inlets:
• debris
• obstructions
• cracked, broken or improperly seated grating
• settlement
• Top elevation adequate and compatable to prevent ponding
n Pipelines: Inspect pipe smaller than 48” diameter by using a light
between manholes. Crawl through pipe 48” diameter or larger. Tightness
of joints may be checked by blocking off a section between manholes for
24 hours to determine amount of ground water infiltration. Use a
watchman to open line in event of rain:
• Misalignment
• settlement
• cracked
• broken
• open joints
• sediment
• debris
• tree roots
• erosion in concrete pipes
• erosion and corrosion in corrugated metal pipes
n Headwalls:
• cracked
• broken
• spalling
• exposed reinforcing
• settlement
• undermining
• improper condition of pipe joint at headwall
5-41
STRUCTURAL
5-42
STRUCTURAL
5-43
STRUCTURAL
Swimming Pools-Continued
n Tile:
• chipped
• cracked
• loose and missing pieces
• defective mortar joints
n Expansion Joints:
• leakage
n Wall and Floor Finishes:
• roughness
• dirty
n Depth Markers, Safety Markings, and Lane Strips:
• illegible
n Springboards:
• cracks
• breaks
• splintered
• other damage
• loose or missing fastenings
• absence of nonslip coverings
n Ladders:
• rust or corrosion of metal parts
• loose
• missing
• broken
• rot
• other damage to wooden parts
• misalignment of towers
n Other Metal Accessories:
• rust
• corrosion
5-44
STRUCTURAL
Swimming Pools-Continued
• broken or missing parts
• other damage
n Other Wooden Parts:
• cracks
• breaks
• splintered
• loose joints or fastenings
• rot
• insect
• other damage
n Main Drains:
• sediment
• rust.
n Gutter Drains:
• obstructions
n Walls:
• stains from corroded fittings
n Fences, Barricades, Dividing Walls and Footings:
• broken
• loose
• missing
• other damage
n Painted Surfaces:
• blistering
• checking
• cracking
• scaling
• wrinkling
• flaking
• peeling
5-45
STRUCTURAL
Swimming Pools-Continued
• rust
• corrosion
• complete absence of paint
5.2.26 Tunnels and Underground Structures: Comply with all current safety
precautions. Check for:
n Portal Structures:
• drainage defects
• cracks
• breaks
• leaks in face and between face and tunnel lining
• eroded slopes or undermining
n Wing and Face Walls:
• inadequate protection to personnel
• erosion of slopes
• loose rocks
• actual or potential slides
• scouring or undermining of walls
n Door and Gate Operation and Locking Devices:
• rust
• corrosion
• loose, missing or damaged parts
• improper operation
n Concrete Floors:
• cracks
• breaks
• scaling
• other damage surface dusting
• settlement
n Earth and Gravel Floors:
• improper grading and drainage
5-46
STRUCTURAL
5-47
STRUCTURAL
5-48
STRUCTURAL
Topside -
n Concrete or wood structures - Check for:
• Horizontal and vertical alignment
• Missing or broken sections, loose connections, traffic obstructions,
and other hazardous conditions of
• Curbing
• Handrails
• Catwalks
• Wear, breaks, rough or sharp surfaces or edges, and missing bolts of
• Bollards
• Bits
• Cleats
• Capstans
• Loose, missing, or broken screws, and wear on
• Deck drains
• Scuppers
• Rust, corrosion, damage, and bent or worn hinge pins of
• Manhole covers
• Gratings
• Rust, cracking, spalling, and other damage of
• Deck surface
• Curbs
• Cracks, holes, and other damage of asphalt coverings
• Corroded, broken, bent, or missing ladder rungs
5-49
STRUCTURAL
Waterfront-Topside-Continued
• Cracked, rotted, loose, or worn decking of wood structures only
n Synthetic material:
• Structures - Check for
• Cracked, worn, brittle, or deformed plastic
• Railing
• Stanchions
• Gratings
• Lighting devices
• Piping
• Loose or damaged
• Fittings
• Connections
• Exposed fiberglass
• Cracked, worn, or deformed rubber fender components
• Coatings, patches, and jackets - Check for
• Pits, cracks, scars, or abrasions of coatings
• cracked, loose, or dislodged epoxy patches
• Punctures, brittleness, tears, abrasions, seam splitting of
fabric in pile jackets
• Foam filled fenders
• Fender-to-pier connection hardware - Check for
• Condition
• Proper operation
• Corrosion
• Proper horizontal constraint
• Proper vertical and rotational motion allowable
• Chain and tire net - Check for
• Proper operation of end fittings
• Chain symmetry on the fender
• Proper protection of the chains by the tires
5-50
STRUCTURAL
Waterfront-Topside-Continued
• Proper net tension
• End fittings - Check for
• Proper operation
• Corrosion
• Cracking or separation of fender shell around end fit-
tings
Underside -
n Elastomer shell - Note the size and location of the damage on a sketch.
Check for
• Cuts
• Tears
• Punctures
n Concrete:
• Pile caps - Check for
• Damage
• Broken or missing members
• Cracks
• Spalling
• Rust
• Exposed steel reinforcement
• Bearing, batter, and fender piles - Check for
• Damage
• Broken or missing members
• Cracks
• Spalling
• Rust
• Exposed steel reinforcement
5-51
STRUCTURAL
Waterfront-Underside-Continued
• Pilings or structure - check for loose layers of concrete or hollow
spots by sounding with a hammer. A sharp ring noise indicates
sound concrete. A soft surface will be detected, not only by sound
change, but also by a change in the rebound, or feel of the hammer.
A thud or hollow sound indicates a delaminated layer of concrete,
most likely from corrosion of steel reinforcement.
n Wood:
• Stringers and pile caps - Check for
• Damage
• Broken or missing members
• Bearing, batter, and fender piles - Check for
• Damage
5-52
STRUCTURAL
Waterfront-Underside-Continued
n Steel structures - Check for:
• Corrosion - Corrosion may be evident during visual inspection in
the H-piles and sheet piles in two areas, the splash zone and
approximately two feet below mean low water. Inside steel pipe
piling, anaerobic bacterial corrosion caused by sulphate-reducing
bacteria may also be found to exist
• Abrasion - Abrasion of steel structure can generally be recognized
by worn smooth polished areas
• Fatigue distress - Fatigue distress can be recognized by a series of
small hairline fractures perpendicular to the line of stress in the
member. Fatigue cracks are difficult to locate by visual inspection.
This problem is more common in offshore platforms with welded
structural connections than in standard piers and wharves
• Overload damage - Overloading can be recognized by deformation
or distortion of a structural member in the form of a sharp crimp or
compression of a bearing or batter pile, deflection of steel sheet
piling caused by failure of tie-backs or excessive overload of
back-fill or live load
• Loss of foundation material - Erosion may cause loss of foundation
material around the piles supporting the structural element. A loss
of foundation material in front of the sheet pile bulkhead may cause
kick-out of the toe of the wall and result in bulkhead or pile collapse
Underwater -
5-53
STRUCTURAL
5-54
STRUCTURAL
• Steel
• Repair
• General good condition
• Damaged or inoperable hardware
• Superficial damage or deterioration
• Replacement
• General poor condition
• Doors do not operate properly
• Major damage or deterioration to doors or frame
n Interior
• Repair
• General good condition
• Minimum damage
• Replacement hardware easily accessible
5-55
STRUCTURAL
• Replacement
• General poor condition
• Replacement hardware difficult to obtain
5.3.5 Exterior walls: Walls will normally only be repaired. If replacement is
considered, have an engineering study performed.
5.3.6 Fencing:
n Repair:
• Minor, spotty, or no rust (on metal fencing)
• Minor damage or deterioration over small sections of fencing
• General good appearance
n Replacement:
• Severe rusting (on metal fencing)
• Major damage or deterioration over a large part of fencing
• General poor appearance
5.3.7 Floor: (tile, carpet, painted, etc)
5.3.9 Interior walls: Walls will normally only be repaired. If replacement is con-
sidered, have an engineering study performed.
5.3.10 Painting: Painting is cyclic maintenance. Normally every 5 years the inte-
rior and exterior surfaces of a facility should be repainted. Some factors to consider
before specifying a paint job are the:
n Item to be painted:
n Surface type, age, and condition - old and weathered surfaces would
require more frequent applications of paint:
n Time since last painting:
5-56
STRUCTURAL
5.3.11 Pavement : Divide the pavement area into Branches, Sections using MO-
102.5, Pavement Maintenance Management. This will translate inspection results into
types of distress and rate the severity level. Use NAVFAC MO-102.1 (Asphalt Sur-
faced Roads and Parking Lots), NAVFAC MO-102.2 (Jointed Concrete Roads and
Pavement-Continued Parking Lots), NAVFAC MO-102.3 (Asphalt Surfaced Air-
fields), NAVFAC MO-103.4 (Jointed Concrete Airfields). They contain pictures of the
types of distress in asphalt and concrete pavements along with providing the inspector
with a method of determining the severity rating. Record the distress types and their
severity levels. Then calculate the pavement condition index (PCI). The PCI measures
the pavement’s structural integrity and surface operating condition on a scale from 0-
100, where 0 = failed and 100 = excellent condition. Use a PCI chart to rate the pave-
ment condition for repair or replacement.
5.3.12 Stair: Each situation must be assessed by the Inspector before preparing
an estimate. Normally stairs are only repaired.
5.3.14 Window:
n Steel:
• Repair
• General good condition
• Proper operation
• Good fit
• Replacement
• Badly rusted window frame
• Leaks evident
• Single pane
• Many broken, cracked, or deteriorated frames
• Poor frame to wall connection
• Poor operation
• Poor fit
5-57
STRUCTURAL
Window-Continued
n Wood:
• Repair
• General good condition
• Good operation
• Good fit
• Replacement
• Bad rot or deterioration
• Worn tracks (opening and closing difficult)
• Leaks evident
• Single pane
• Many broken, cracked, or deteriorated frames
• Total reglazing of windows required to assure good condition
5-58
MECHANICAL
6.1 DEFINITIONS:
Air handler - devices that move heated, cooled, and untreated air and the associated
ductwork
Emergency eyewash/shower - all eyewashes, showers, and exposed pipe used to wash
eyes or body when contaminated with hazardous materials
Exhaust - devices that cause or allow air to leave a facility (fans, vent, etc.)
Fire protection - everything from the first valve outside of the facility to the discharge
point, includes sprinkler systems and hose outlets, note fire extinguishers
Fuel Facilities -
Distribution - fuel distribution facilities include piping, valves, accessories, signs
and markings, ground connections, pits, tunnels, and ladders
Receiving and Issue - includes platforms and islands, small structures, fuel hose,
hose connections, and adapters, hose racks and reels, grounding connections, portable
ladders and steps, portable gangplanks, signs and markings, general cleanliness, and
painting
Storage - includes surface and subsurface tanks, tank enclosures, and tank fittings
and appurtances
Heating - devices that heat air for a facility, not heat pumps
Incinerators - includes incinerators used for refuse and garbage disposal, including spe-
cial-purpose types
6-1
MECHANICAL
Piping -
Chilled/Hot Water System - from the first valve off the heat exchanger or chiller
to the destination inside the facility
Compressed Air - from the first valve off of the compressor to the destination
inside the facility
Natural Gas - from the first valve on the facility side of the facility water meter to
the destination inside the facility
Sewage - from 5 feet outside the facility to the source inside the facility
Steam - from the first valve on the facility side of the pressure reducing station
closest to the facility, to the destination inside the facility
Water - from the first valve on the facility side of the facility water meter to the
destination inside the facility
Plumbing - all fixtures and exposed pipe related to the distribution and use of water in a
facility
Sanitary Sewage Utility System - the sewage lines from the facilities to the sewage treat-
ment plant
Steam Utility System - the steam distribution system piping from the steam plant to the
point where the steam enters the facility
Unfired Pressure Vessels - includes all closed vessels in which internal pressure is above
atmospheric pressure and the pressure is obtained from an external source except (a)
cylinders for shipment of compressed or liquified gasses; (b) air tanks for brakes on
vehicle; (c) unfired pressure vessels having a volume of 5 cubic feet or less; (d) unfired
pressure vessels designed for a working pressure not exceeding 15 pounds per square
inch gage; (e) unfired pressure vessels containing only water under pressure for domes-
tic supply purposes, including those containing air, the compression of which serves only
as a cushion; (f) unfired pressure vessels used as refrigerant receivers for refrigerating
and air conditioning equipment; (g) expansion or accumulator tanks used in conjunction
with high temperature water installations
Water heaters - devices that heat water for domestic purposes (including converters and
storage tanks when used for domestic hot water)
6-2
MECHANICAL
Water Utility System - the water lines from the base’s source (city line, well, reservoir,
etc.) through any storage tanks to the destination (facility, fire line, etc.)
6-3
MECHANICAL
Air conditioning-Continued
• Insulation damage and type
• Diffuser operation
• Return air grills operation and condition
• Compressors - Check for
• Excessive noise
• Oil on deck
• Leaks at connections to compressors
• Pumps - Check for
• Leaking at packing glands
• Excessive noise
• Leaking at connections
• Electric and pneumatic controls - check for proper operation
• Check water treatment chemicals and system
• Water cooling towers, casings, baffles, fans and tower water
distribution system including piping and insulation, sump heaters
(steam and electric) - check condition and operation
• Absorption chillers (centrifugal and reciprocating) - check for
proper operation and condition
• Expansion tanks - check for condition and proper operation
• Vacuum pumps - check for condition and proper operation
6.2.2 Air handlers:
Check for:
• Condition and operation of
• Fan motors
• Squirrel cages
• Fan belts
• Condition of flexible connection between duct and air handler
• Proper lubrication
6.2.3 Boilers: Comply with all applicable safety precautions. This procedure
does not include all requirements and specifications to perform this inspection. Refer
to NAVFAC MO-324, Inspection and Certification of Boilers and Unfired Pressure
6-4
MECHANICAL
Boilers-Continued
Vessels for more information. Inspectors must obtain and possess a valid NAV-
FACENGCOM Certificate of Competency and a current license issued by the
geographic Engineering Field Division/Engineering Field Activity (EFD)/(EFA). Con-
tracted inspectors must possess a state certificate and a current license issued by the
EFD/EFA. Before entering the shell or drums of the boiler, make sure that they have
been properly ventilated; that there is no inflammable gas present; that the blow-off and
surface blow-off valve, the main and auxiliary steam valves, feed-water valves, and all
other valves on connecting pipes are closed; and that a reliable method is used to
safeguard these valves while anyone is inside the boiler. When electric cords are used
inside a boiler they should be in good condition, well insulated, designed to withstand
mechanical injury and provided with a suitable guard. Naked lights are prohibited. On
this inspection report, indicate decrease in pressure-carrying capacity and recommenda-
tions not completed or scheduled for completion from previous inspection reports and
log sheets. Check for:
EXTERNAL INSPECTION
n Safety and Relief Valves:
• accumulated rust, scale or debris
• obstructed drain
• hazardous conditions created by discharge
• try lever not free
• gags removed
• stems not bent
n Automatic Low-Water (Level or Flow) Fuel Cut-Off and/or Water
Feeding Device:
• rust
• corrosion
• deteriorated or defective parts
• improper function
n Gages:
• cracked, broken, missing or dirty glass
• illegible markings
• bent pointer
6-5
MECHANICAL
Boilers-Continued
• leaking connections
• improper function of cock between gage and boiler
n Water Columns and Gage Glasses:
• excessive corrosion
• cracked or dirty glasses
• leakage
• improper drainage
n Material Storage: lumber or other material on boiler or setting:
n Lagging:
• loose or missing material
• cracks
• open seams
• evidence of vapor or water leaks
n Casing:
• distortion
• slippage of bricks
• open seams, cracks
• looseness
• sheared bolts
n Shell:
• corrosion
• cracks
• leaking roofs, valves, pipes
• rust streaks on covering
n Boiler Doors:
• sagging
• warping
• cracking
• chipped or broken edges
• worn hinges
6-6
MECHANICAL
Boilers-Continued
• defective locks or latches
• improper operation
• deteriorated or damaged blast deflectors
• condition of gasket
n Breechings:
• excessive corrosion
• cracked welds
• loose or broken connections
• separated sections
n Overhead Machinery: loose parts or material that may drop on or strike
boiler:
n Foundation: settlement, improper level:
n Piping:
• leakage
• strain or torsion
• excessive corrosion
• improper drainage
• misalignment
• lack of support
• inadequate provision for expansion or contraction
• excessive vibration
• water pockets at valves and connections
• loose, deteriorated, strained, inadequate connections
• settlement
• improper tension or alignment in supports
n Stop and Check Valves:
• loose, missing, broken parts
• excessive wear or corrosion
• leakage
• obstructed drain openings
6-7
MECHANICAL
Boilers-Continued
n Pressure Reducing Valves:
• loose, missing, broken parts
• rust, scale, other substance preventing proper operation
n Blow-Off Tanks:
• excessive corrosion
• cracks
• distortion, other weakness
• leaks, water pockets
• improperly placed valves
n Ladders and Runways:
• broken, cracked, split, badly worn members
• excessive corrosion
• loose or missing bolts or other connections
• broken welds
• abnormal deflection
• loose or warped sections
• slippery surfaces
• inadequate anchorage
n Electric Steam Generators: Refer to Chapter 7, Electrical Inspections
Guide, Motors and Generators. Check for:
• burnt, corroded, frayed, or broken strands in grounding cable
• loose connections
• broken or deteriorated screens and guards
• missing, illegible, or improperly posted warning signs
INTERNAL INSPECTION
n Contamination:
• connection of potable water to sewer system
• absence of air gap between potable water and waste pipe
n Preparation for Inspection:
• inadequate
6-8
MECHANICAL
Boilers-Continued
• incomplete
• untimely
n Steam Gage: improperly calibrated. Recalibrate:
n Boilers Secured or Stored:
• Wet Lay-up
• incompletely filled
• improper pH and sulfite concentration
• Dry Layup
• not completely dry
• inadequate supply of desiccant
• improper or inadequate placement of desiccant
n Waterside Metal Surfaces:
• evidence of oil. Report presence of oil
• indications of scale. Report location, amount, density, degree of
hardness, and age of scale
n Plates:
• cracks
• defective joints
• distortion
• erosion
• excessive corrosion
• grooving
• lap seam cracks
• cracked or severely corroded rivets
• cracked welds
• Determine minimum thickness and calculate new maximum
allowable working pressure
n Stays and Braces:
• cracks
• bends
• looseness
6-9
MECHANICAL
Boilers-Continued
• uneven tension
• excessive corrosion or erosion
• loose, cracked, broken connections
n Reinforcing Plates:
• excessive corrosion
• worn
• cracked
• deformed
• insecurely fastened
• openings obstructed
n Openings and Connections for Piping and External Attachments:
• obstructed
• inadequate
• excessive corrosion
n Internal Piping and Fittings:
• loose connections
• breaks
• cracks excessive corrosion
• clogging
n Protection for Blow-Off Connection:
• spalling
• cracking
• looseness
• missing or worn parts
n Manholes and Handholes:
• corrosion
• leakage
• distorted
• elongated
• excessively corroded holding clamps
6-10
MECHANICAL
Boilers-Continued
n Tubes:
• deterioration
• excessive reduction in thickness
• bulges
• cracks
• defective welds
• erosion
• corrosion
• waste pockets
• scale
• distortion
n Ligaments: broken, cracked, leaks:
n Drumheads: cracks, deformation, excessive corrosion:
n Flanging: grooving:
n Soot Blowers:
• worn, loose, or inadequate bearings and parts
• incorrect alignment of nozzles
• excessive scouring of refractory baffles
• incorrect blowing ranges
• inadequate traps
• condition of packing
• signs of direct impingement of steam on tubes
n Fireside Surfaces or Gas Passages:
• steam pockets
• corrosion
• bulging
• blistering
• distortion
• deformation
• excessive burning action
6-11
MECHANICAL
Boilers-Continued
• fly ash deposits
• flame leakage
• localization of heat
• deteriorated or loose tie rods and buck stays
n Fusible Plugs:
• poor condition
• unsound metal
• in service more than one year
• exposed to steam temperature in excess of 425°F
n Setting:
• improper level
• tendency to settlement
• inadequate provision for expansion and contraction
• excessive corrosion
• holes
• cracks
• slippage
• distortion
• binding
• loose bricks
• improper air space
• poor insulation of steel supporting members
• excessive vibration
n Furnaces and Baffles:
• spalling
• cracking
• settlement
• distortion
• abnormal cracks and seams
• excessive burning and corrosion
6-12
MECHANICAL
Boilers-Continued
• fly ash deposits
• inadequate expansion joints
• improper protection of mud drums
• loose, missing, deteriorated, improperly placed baffling
n Firing Equipment and Dampers:
• Burners
• loose, broken, or missing parts
• excessive wear or corrosion
• Grates, Stokers and Feeders
• loose, broken or missing parts
• excessive wear or corrosion
• Dampers
• loose, broken, missing, bent, warped, or binding parts
• excessive wear or corrosion
• improper operating condition
n Low-Water Fuel Cut-Off and/or Water Feeding Device:
• scale or dirt deposits
• restricted moving parts
• excessive wear
• loose, broken, or missing parts
• improper function
HYDROSTATIC TEST
n Preparation: inadequate, incomplete:
n Inspection:
• leakage
• loose parts
• distortion
• deformations
• Report row and number of tubes requiring rolling or replacement
6-13
MECHANICAL
Boilers-Continued
n Maximum allowable Working Pressure: Recalculate:
INSPECTION OF OPERATION
n Firing Equipment: improper or inefficient operation:
n Controls:
• inability to maintain proper steam pressure or water temperature
and air-fuel ratio throughout capacity range of boiler with load
swings of the rapidity encountered in operation
• improper programming sequence and timing
• improper cutoff of fuel supply; inability to maintain proper water
level or to operate cutoff devices
• Test flue gas for CO
• Check air-fuel ratio with CO2 and O2 measuring devices
n Steam and Water Piping:
• leakage
• excessive vibration
• water-hammer
• tendency to crystallize
n Water Columns and Gage Glasses: restricted connections:
n Steam Gages:
• stuck pointer
• restricted movement of pointer
• obstructed connections
n Temperature Indicating Devices: excessive temperatures indicated,
particularly during and immediately after high load demands:
n Blow-Off Valves:
• restricted openings
• excessively worn or otherwise defective
n Stop and Check Valves:
• excessive vibration
• ineffective or defective operation
6-14
MECHANICAL
Boilers-Continued
n Pressure Reducing Valves: defective, inadequate, improper operation:
n Metering and Recording Devices: improper operation:
n Boiler Auxiliaries:
• steam leakage
• wastage to atmosphere
• unnecessary use
• inadequate or improper functioning
n Boiler Safety and Water-Pressure Relief Valves:
• improper operation
• obstructed discharge
• does not release at required pressure
• have qualified personnel adjust to proper setting requirements (See
MO-324 for appropriate organizations/personnel authorized to
perform this function)
n Feedwater Treatment:
• Equipment: ineffective, inadequate, improper operation
• Materials: incorrect, insufficient
n Feedwater Quality:
• proper analyses
• allowable ranges
• periodic checks
n Fuel Handling Practices:
• multiple handling
• use of duplex equipment for small loads
• unnecessary heating
• improperly maintained equipment
• insufficient operation
n Partial Loading: unnecessary use of similar equipment at part load when
one unit could carry load:
6-15
MECHANICAL
6-16
MECHANICAL
Distribution -
n Above-Ground Piping:
• leakage
• loose connections
• damaged or missing hangers and supports
• misalignment causing undue stresses at pipe joints or failure to
allow freedom of movement at expansion joints
• defective gland nuts and bolts at expansion joints and clamp-type
couplings
• deteriorated or damaged paint or protective coverings. Stop leaks
by takeup within limits of packing gland adjustments
• defective packing
• defective hangers and supports
• defective gland nuts and bolts
6-17
MECHANICAL
Fuel Facilities-Distribution-Continued
• defective anchorage
n Underground Piping: Location of underground leaks may be determined
by sectioning the pipelines and performing hydrostatic tests. See Military
Fuel Operations Handbook, Office of the Assistant Secretary of Defense
(Supply and Logistics):
• leakage indicated by earth discoloration
• dead vegetation
• presence of odors
• review periodic oil sampling records to determine if there is
entrainment of ground water
• review and compare fuel and replenishment records to determine if
there is a loss of fuel
n Valves:
• leaks
• corrosion
• visible defects in stem, operating handwheel or lever, body packing,
gland, flanges, and gaskets
• inadequate lubrication, wear, mechanical damage
• damage to protective coatings
• difficult operation
• Where operational functions of the system will permit and where
precautions are feasible against contamination of the fuel, the
following inspections should be performed
• Operate gate and plug-type valves to fully closed and open
position, to ascertain condition of valve seats and stem
threads and to test limit cutout of remote-controlled valves
• Inspect plug valves for incorrect adjustment
• Remove inspection covers of check valves and inspect such
parts as valve seats, gates, and hinges, for wear and damage
• Lift pressure vacuum relief valves by hand to assure against
sticking; if setting is questionable, check and reset as
specified by the manufacturer’s instructions
6-18
MECHANICAL
Fuel Facilities-Distribution-Continued
• Check for
• loose flanges at leaking gaskets
• defective gaskets
• leaking stems, within the limit of packing gland adjust-
ment
• defective packing
• defective or missing bolts and nuts, handwheels, and
operating levers
n Meters and Pressure Gages:
• significant drop in pressure after 15 minutes
• leakage
• cracked dial cover glasses
• defective gaskets
• moisture behind glasses
• mechanical damage
• inaccuracy of indicating and recording mechanisms
n Thermometers:
• inaccuracy
• mechanical damage
• loss of indicating fluid
n Strainers: Remove obstructions. Remove and examine for wear, damage,
obstructions, and replace defective screens:
• leaks
• defective operation
n Shock Absorbers:
• leaks and mechanical damage
• liquid in U-bend of liquid-cushion type not at proper level
• tube pressure at which pneumatic-tube type operates is below
normal pressure plus the amount specified by manufacturer
• low pressure
6-19
MECHANICAL
Fuel Facilities-Distribution-Continued
• hammering sound in pipelines of bellows-type after previous
satisfactory operation indicates probable damage and must
be repaired or replaced
• liquid in air-chamber type
n Vents:
• damaged screens
• dirt or other obstructions blocking discharge to atmosphere
• restricted by paint or corrosion
n Grounding Connections:
• loose
• missing
• mechanical or corrosive damage
• failure to maintain electrical continuity
n Grading at Pits and Tunnels: Adjacent earth surface improperly sloped
and does not divert surface water away from pits and areas above tunnels:
n Pits for Valves, Meters, and Pumps:
• defective cover gaskets, hinges, locks
• dry hinges
• trash and debris
• cracked, spalled, or broken concrete areas
• rotted, splintered, broken, and other damage to wooden parts
• rust, corrosion, and cracks in metal covers and frames
• defective gaskets, hinges, locks
• unlubricated hinges
• trash and debris in pits
• other deficiencies
n Underground Tunnels:
• deteriorated protective coatings
• rust
• corrosion
• decay
6-20
MECHANICAL
6-21
MECHANICAL
6-22
MECHANICAL
• binding
n Hardware:
• defective hinges
• locks
• broken glass
n Hose Racks and Reels:
• corrosion of metal
6-23
MECHANICAL
6-24
MECHANICAL
Fuel Facilities-Storage -
n Foundations:
• settling movement
• upheaving
• inadequate soil coverage
n Exterior Concrete Surfaces:
• spalling
• cracking
• exposed reinforcing
• leakage
n Exterior Steel Surfaces:
• rust
• corrosion
• distortion or other structural failure
• leakage
• deteriorated paint
n Roof Surfaces:
• defects in waterproofing
• heat-reflecting coatings, coverings
n Floating and Expansion-Type Roofs, Seals, Supports, and Support Guides:
• rust
• corrosion
• improper sealing
• deteriorated paint
• structural or mechanical damage caused by freezing weather
conditions
n Structural Supports and Connections:
• rust
• corrosion
• rot
6-25
MECHANICAL
Fuel Facilities-Storage-Continued
• broken
• cracked
• distorted
• loose
• missing
• deteriorated paint
n Tank Linings:
• loss of elasticity
• granulation
• discoloration
• cracks
• peeling
• sloughing off
n Tank Interior:
• rust
• corrosion
• scale
• deteriorated protective coatings
n Frames and Covers on Manholes and Hatches:
• rust
• corrosion
• cracks
• breaks
• missing or damaged bolts
• worn defective hinges and gaskets
n Vents:
• rust
• corrosion
• dirty screens
6-26
MECHANICAL
Fuel Facilities-Storage-Continued
n Pressure and Vacuum Relief Valves:
• defective operation
• leakage
• improper adjustment
n Manometers and Thermometers:
• inaccuracy
• mechanical damage
• loss of fluid
n Float Gages:
• wear
• binding
• apparent inaccuracy
n Cables, Sheaves, and Winch of Swing Lines:
• wear
• mechanical damage
• stuffing boxes and liquid seals
• deterioration
• improper operation
n Stairs, Ladders, Platforms, and Walkways:
• rust
• corrosion
• rot
• broken
• cracked
• loose
• missing
• members or connections
• deteriorated paint
6-27
MECHANICAL
Fuel Facilities-Storage-Continued
n Roof Drains and Screens:
• missing
• rust
• clogging
n Ground Connections:
• loose
• missing
• mechanical damage
• corrosion interfering with electrical continuity
n Interior Heating, Inlet and Outlet Pipes, Nozzles, Supports, Sumps, and
Sump Drains:
• rust
• corrosion
• wear
• loose or missing parts
• obstructions
• other defects
n Dikes:
• cracks
• breaks
• spalling
• rust
• corrosion
• settlement
• heaving
• soil erosion
• water seepage
• inadequate sod cover on outer face where earth-filled
• inadequate treatment of inner face to prevent vegetation growth
• access steps for settlement
6-28
MECHANICAL
Fuel Facilities-Storage-Continued
• breaks
• other damage
n Drainage Ditches, Sumps and Earth Surfaces between Ditch and
Foundation:
• improper slope to divert surface water away from foundation and
berm
• trash and debris
• erosion
n Leakage: Locate leaks by filling completely with water and applying
hydrostatic pressure of 4 ft. of water for not less than 4 hours:
• review records to determine indication of fuel losses
• review oil sample records to determine if water infiltration
6.2.9 Heating:
n Thermostats - Check for:
• Proper operation (if possible)
• Vacuum or air leaks
• Proper location
n Coils - Check for:
• Leaks
• Proper vacuum breaker on condensate return for steam coils
n Zone pumps - check for proper operation:
n Radiators - Check for:
• Radiator valves and traps condition
• Leaks at push nipples
• Operation of automatic air vents on hot water systems
n Baseboard radiators - Check for:
• Leaks in fin tubes
• Damaged cover and mounting frame
• Leaks of radiator valves and traps on steam units
• Leaks of automatic air vents on hot water units
6-29
MECHANICAL
Heating-Continued
n Fan coil units - Check for:
• Proper operation
• Damaged cabinet
• Proper drainage of drain pan
• Leaks
• Proper mounting
n Duct system and components - Check for:
• Cleanliness
• Proper operation of dampers
• Insulation damage and type
• condition and operation of diffusers
n Control valves - Check for:
• Vacuum or air leaks at connections
• Proper operation
n Heat exchangers - Check for:
• Casing leaks
• Condition and proper operation of traps
• Proper operation of associated valves and pumps
• Proper operation and condition of vacuum breaker on condensate
return
n Expansion tanks - Check for:
• Leaks
• Deterioration
• Proper operation
n Boilers: Perform general inspection of boilers and unfired pressure
vessels. Use ASHRAE guidelines for life expectancy. Refer to Boilers
and Unfired Pressure Vessels sections in this chapter:
• Stack - Check for:
• Deteriorated metal
• Proper stack cap and tension cables
6-30
MECHANICAL
Heating-Continued
• Check certification to ensure it is current
• Casings - Check for
• Deterioration
• Insulation deterioration and type
6.2.10 Incinerators: Comply with all current safety precautions. Before inspec-
tion, operating personnel should thoroughly clean inside of furnace. Check for:
n Refractory Linings at Throats, Roof Arches, Door Arches and Jambs,
Target Wall, Charging Hole Covers, Guillotine Doors, and Combustion
Chambers:
• spalling
• loosening
• deterioration of areas or individual units
n Combustion Chambers:
• deformations
• breaks
• wear
• corrosion
• soot deposits
• clinkers
• ashes
• excessive slag formations indicating excessive lining deterioration
• depositing of an excessive amount of noncombustibles
n Drying Hearths and Grates:
• warped sections
• burned-out areas
n Exterior Settings:
• settlement
• cracks
• broken areas
• eroded and sandy mortar joints
6-31
MECHANICAL
Incinerators-Continued
• failure to provide adequate expansion and contraction between
furnace setting and building and between flue and chimney
n If leakage is suspected, make open flame test and draft gage, arch, door
frames, and wall surfaces:
n Failure of furnace steel framing supports are indicated by damage to
arches and roof areas, door casings, and walls:
n Cables and Rigging of Adjustable Dampers and Counterweighted Doors:
• rust
• corrosion
• inadequate lubrication
• damaged or frayed strands
• improper operation through defective pulleys, wheels, or other parts
n Doors:
• rust
• corrosion
• warped
• loose fit
• damaged or missing parts of latches and hinges
n Tuyeres and Tuyere Plates:
• warped
• burned-out areas
n Charging Chute Frames and Covers:
• rust
• corrosion
• broken
• loose
• missing parts
n Inadequate ash-handling and ash-removal facilities:
n Portable-Type Pyrometers and Recording or Indicating Types fitted with
High and Low Temperature Warning Lights:
6-32
MECHANICAL
Incinerators-Continued
• inadequate
• inaccurate
n Combustion Chamber Draft Gage:
• improper operating condition
• inaccuracy
n Need of supplementary fuel:
n Burner Assemblies:
• improper fuel-air mixtures
• leakage
• clogged jets, orifices, petcocks, valves
• improper positioning of pilot light
• nonuniform flame spread
• dirty filters
n Wiring and Controls:
• loose connections
• damaged insulation
• evidence of short circuits
• loose or weak contact springs
• worn or pitted contacts
n Examine motor windings and brush rigging:
n Operate control mechanisms through complete cycle of operation:
n Nonavailability and poor condition of operating tools:
n All-Metal Trash Burners and Incinerators:
• rust
• corrosion
• burned-through areas
• warped and buckled surfaces
6-33
MECHANICAL
Incinerators-Continued
n Can-Washer Equipment:
• vacuum breakers not installed in water lines
• improper operating conditions
• improper drainage for cleaning areas
n Painted Surfaces:
• rust
• corrosion
• cracking
• scaling
• peeling
• wrinkling
• alligatoring
• chalking
• fading
• complete loss of paint
6.2.11 Piping:
n Drain vent and waste - Check for:
• Hanger system condition
• Proper grading
• Weeping or leaking joints
• Deteriorated piping
n Steam and water distribution - Check for:
• Pipe type
• Hanger system condition
• Deteriorated piping
• Leaking, and weeping joints
• Insulation condition and type - if asbestos, determine if it needs to
be encapsulated or removed
• Proper grade on condensate return
• Type of pipe on condensate return (when applicable)
6-34
MECHANICAL
Piping-Continued
• Proper operation of steam traps
• Proper drainage, cracking, and proper venting of cooling wells
• Valves - Check for
• Leaking flanges
• Packing condition
• Test operation where practical
• Expansion joints - Check for
• Leaks at packing glands
• Anchor points and slip guides
• Pressure reducing valves and components - Check for
• Chattering
• Leaking packing glands
• (Water distribution only) Check water for rust and color of water
(Cold water rust may require filter where water enters building or
shows signs of rusting. Hot water rust only may require hot water
tank to be flushed or replaced.)
6.2.12 Plumbing:
n Sinks/tubs - Check for:
• Cracks and wear of porcelain or other surface
• Inoperative or leaking mixing valves
• Pop-up waste (drain plug) operation
• Proper installation
• Proper drainage
n Showers - Check for:
• Proper drainage
• Leaking valves
• Leaks through floor
n Water closet - Check for:
• Proper flush cycles
• Cracked bowls or tanks
• Proper securing of flanges
6-35
MECHANICAL
Plumbing-Continued
• Leaks around flushometer connections
n Urinals - Check for:
Proper flush cycles
Cracks
Proper securing of flanges
Deteriorated “P’ traps
Deteriorated wall connections
6.2.13 Pump (Submersible Sump): Check for water and debris in pits and drain
if necessary. Check pump for proper operation.
6.2.14 Sanitary Sewage Utility System: Start the inspections at the facilities and
follow the lines until they reach the water treatment facility. Obtain sanitary sewage
utility system drawings before inspections. Nothing should be turned on or off and noth-
ing should be opened or closed unless special arrangements have been made with the ac-
tivity. Notify the local utility department before starting the inspections. Check for:
n Proper operation of lift stations:
n Proper inflow of the sewage into the treatment plant (check with the plant
operator about problems):
n Proper flow through manholes:
6.2.15 Steam Utility System: Start the inspection from the steam generating
plant and follow the lines until they reach a facility or other destination. Obtain steam
utility system drawings before inspections. Nothing should be turned on or off and noth-
ing should be opened or closed unless special arrangements have been made with the ac-
tivity. Coordinate any inspection with the station utility department before starting the
inspections. Have operating personnel available during the inspection to provide infor-
mation on conditions and to provide access to pits, mechanical rooms, and fenced
enclosures. Check through a visual inspection for:
n Leaks:
n Proper insulation. (The insulation should meet current criteria and be
serviceable:)
n Condition of all components, including:
• Pipe
• Valves
• Flanges
6-36
MECHANICAL
EXTERNAL INSPECTION
n Safety and Relief Valves:
• accumulated rust, scale or other debris
• obstructed drain
• hazardous conditions created by discharge
• levers do not operate freely
6-37
MECHANICAL
• bent pointer
• leaking connections
• inoperative
n Lagging:
• loose or missing material
• cracks
• open seams
• evidence of vapor or water leaks
n Shell:
• corrosion
• leakage
• cracks
• distortion
• cracked or broken welds
• loose or cracked rivets
• loose or missing caulking
n Supports:
• settlement
• deterioration
• lack of rigidity
6-38
MECHANICAL
6-39
MECHANICAL
INTERNAL INSPECTION
n Preparation for Inspection:
• inadequate
• incomplete
• untimely
n Pressure Gage:
• improperly calibrated. Recalibrate
n Vessels Secured or Stored:
• not completely dry
• inadequate supply of desiccant
• improper or inadequate placement of desiccant
n Corrosion Resistant Lining:
• cracks
• corrosion behind lining
• corrosion behind deposits on lining
n Minimum Thickness (Surfaces exposed to Corrosion from Vessels’
Contents):
• determine
n Maximum Corrosion Rate:
• determine
n Shell Plates:
• cracks
• defective joints
• distortion
• erosion
6-40
MECHANICAL
6-41
MECHANICAL
INSPECTION OF OPERATION
n Controls:
• inability to maintain proper pressures
• improper adjustment for cut-out and cut-in devices
n Piping:
• leakage
• excessive vibration
• tendency to crystallize
n Pressure Indicating Gages:
• stuck pointer
• restricted movement of pointer
• obstructed connections
n Temperature Indicating Devices:
• excessive temperatures indicated
• particularly during and immediately after high load demands
n Stop and Check Valves:
6-42
MECHANICAL
6-43
MECHANICAL
6-44
MECHANICAL
Air Conditioning-Continued
• Repair
• Only minor adjustments required
• Repair is cost effective
• Replacement
• Old, broken, damaged, or inoperative thermostats, valves,
and/or other major components
• Uncontrollable temperature variations throughout facility
6.3.2 Air handler -
n Repair:
• General good condition
• Only specific parts require replacement or repair
• Parts are easy to procure
• Replacing or repairing parts is cost effective
n Replacement:
• Over 12 years old
• Badly corroded or otherwise deteriorated
• Fan motors inoperative
• Coil stopped up
• Fins fall off when touched
• Parts difficult or impossible to procure
• Replacing or repairing parts is not cost effective
6.3.3 Eye wash/shower -
n Repair - Minor problems:
n Replacement:
• Cracked fixtures
• Not conforming with applicable codes
6.3.4 Exhaust -
n Repair:
• General good condition
• Parts are easy to procure
6-45
MECHANICAL
Exhaust -Continued
• Replacing or repairing parts is cost effective
• Minor parts required to make operable
n Replacement:
• Over 15 years old
• Badly corroded or rusted
• Undersized
• Inoperable
• Parts difficult or impossible to procure
• Replacing or repairing parts is not cost effective
6.3.5 Fire protection : Any type of fire suppression or detection system that has
not been actually tested for a long period of time should be tested by the
EFD/EFA/PWC fire protection engineer. Consult with them for testing frequency of
fire protection systems. Also see NAVFAC MO-117, Maintenance of Fire Protection
Systems.
6.3.6 Heating :
n Radiators/convectors (steam or hot water):
• Repair
• General good condition
• Only specific parts require replacement or repair
• Parts are easy to procure
• Replacing or repairing parts is cost effective
• Replacement
• Over 15 years old
• Unit doesn’t work
• Badly corroded
• Fins fall off when touched
• Parts difficult or impossible to procure
• Replacing or repairing parts is not cost effective
6-46
MECHANICAL
Heating -Continued
n Boilers and related piping:
• Repair
• Less than 20 years old
• Adequate output
• Parts are easy to procure
• Replacing or repairing parts is cost effective
• Records show few repairs
• Replacement
• Over 20 years old
• Records show many repairs
• Related piping badly deteriorated
• Inadequate output
• Parts difficult or impossible to procure
• Replacing or repairing parts is not cost effective
n Controls (electric/pneumatic):
• Repair
• Only minor adjustments required
• Repair is cost effective
• Replacement
• Old, broken, damaged, or inoperative thermostats, valves,
and/or other major components
• Uncontrollable temperature variations throughout facility
6.3.7 Insulation: - (Fiberglass, Armaflex)
n Repair:
• Only small areas tom or damaged
• Repair would be cost effective
n Replacement:
• Over 50% tom or damaged
• Repair not cost effective
6-47
MECHANICAL
6.3.8 Piping -
n Pipe oil and lubricants (POL): Making repair/replacement
recommendations for above ground POL lines is very difficult because of
the many factors to consider. POL lines located near the waterfront
deteriorate about 50% faster than those away from the water. This
deterioration is due to the constant exposure to salt, water, and air if
above ground):
• Waterfront
• Repair
• Less than 10 years old
• Random or spot corrosion or rust
• General good condition
• Replacement
• Over 10 years old
• Wall thickness reduced 50% (NDT check)
• Evidence of numerous repairs
• Evidence of line stress (possibly due to hangar failure)
• Many and major leaks
• Large areas of deterioration or rust
• Above ground, away from waterfront
• Repair
• Less than 20 years old
• Little or no loss in wall thickness (NDT check)
• Little or no rust or deterioration
• Replacement
• Over 20 years old
• Wall thickness reduced 50% (NDT check)
• Evidence of numerous repairs
• Evidence of line stress (possibly due to hanger failure)
• Many and major leaks
• Large areas of deterioration or rust
6-48
MECHANICAL
Piping-Continued
n All but pipe oil and lubricants (POL):
• Repair
• Less than 20 years old
• Minor, isolated leaks
• Little or no corrosion
• General good condition
• Replacement
• Over 20 years old
• Frequent, bad leaks (joints, other places)
• Bad corrosion
• Frequent repairs (check with activity records)
• Evidence of blockages in pipe due to corrosion
6.3.9 Plumbing:
n Repair - Minor problems:
n Replacement:
• Cracked fixtures
• Not conforming with applicable codes
6.3.10 Water heaters:
n Repair - Minor rusting:
n Replacement:
• Leaking water jackets
• Leaking steam bundle
• Replace water heater converters when over 20% of the tubes are
plugged
6-49
ELECTRICAL
7.1 DEFINITIONS:
Cathodic Protection Systems - includes wood poles used to support overhead electric
distribution systems and/or telephone open wire or serial cable systems and such acces-
sories and related items as crossarms, insulators, pins, tiewires, hardware, line wires
near the pole, guywires, and groundwires
Distribution Transformer -
Electrical Utility System - the overhead and underground power transmission and dis-
tribution lines from the source (base power plant, local utility feed, etc.) to the facility
or other final destination
Fire Alarm - the electronic warning system for fire. From the panel to the activating
device to the alarm
Fuses and Small Circuit Breakers (Under 600 Volts and 30 Amperes) -Visual inspec-
tion only of fuses and small circuit breakers and their enclosures in electrical circuits
operating at 600 volts or below and rated at 30 amperes and below
General wiring - all wiring throughout a facility including attic and crawl space wiring
Grounds and Grounding Systems - includes electrical grounds and grounding systems
for all electrical equipment, apparatus, machinery, metallic conduit, and all accessories
that are a part of the outdoor electrical power distribution system. It also includes
grounds of structural supports, frames, towers, safety fencing, hardware, equipment
enclosures, system neutrals, and buried ground cable networks and counter-poises used
in substation and similar areas. In such places, good engineering practice, Bureau
7-1
ELECTRICAL
specifications, and other controlling rules and regulations such as National Electric
Code, National Electrical Safety Code, and United States Navy Safety Precautions for
Shore Activities, NAVSO P-2455, require grounding for operational and personnel
safety. Proper operation of grounding systems for Ordinance Storage Facilities is espe-
cially important
Lighting - all the devices that produce light in or around the facility, going from the
panel to the light
Panels - breaker boxes that have one power input and usually many distribution output
lines. Panel types are:
Primary - the main power coming into a facility going into the primary panel
Secondary - the second source of power coming into a facility. This will be rated
equal to or less than that of the primary panel
Sub - panels off the primary or secondary panel. Note in the comment area if these
panels serve other panels
Power Plants - includes electrical equipment and apparatus in electric power generating
plants of the station type
Relays - Protective relays located in electrical power circuits only. It does not include
relays used to protect or control utilization equipment. Inspection is limited to those
aspects that relate to care rather than to the operating characteristics of relays
Steel Power Poles and Structures - Steel power poles and towers, metallic street light-
ing standards, A-frames, and all other steel structures used to support electric power
lines or equipment, including those used for transmission lines, distribution systems, sub-
stations, and switching stations
7-2
ELECTRICAL
Wood Poles and Accessories - Wood poles used to support overhead electric distribu-
tion systems and/or telephone open wire or aerial cable systems. Included are such ac-
cessories and related items as crossarms, insulators, pins, tiewires, hardware, line wires
near the pole, guywires, and ground-wires. Inspection of equipment such as trans-
formers, cutouts, lightning arresters, or terminal boxes that are mounted on wood poles
is covered elsewhere
7-3
ELECTRICAL
7-4
ELECTRICAL
7-5
ELECTRICAL
7.2.2 Chimneys and Stacks (Electrical): Comply with all current safety precau-
tions. Also refer to Chimneys and Stacks (Structural). Check for:
n Lightning Rods, Terminals, Cables, and Ground Connections: Test for
electrical continuity from aerial terminals through ground connections:
• corrosion
• loose
• burned
• missing
• other damaged parts and connections
n Lights, Hoods, Reflectors, Shields, and Receptacle Fittings:
• failure to operate
• missing, loose, or damaged parts
• moisture
• need of relamping
n Conduit:
• breaks and other damage
• remove conduit inspection plates and examine internal connections
• for lack of tightness and inadequacy
• relays for defective operation
• for loose or weak contact springs
• worn or pitted contacts
• moisture
7.2.3 Disconnecting Switches: Comply with all current safety precautions. DO
NOT operate until tests show circuit is dead and grounding harnesses have been at-
tached. DO NOT operate without prior clearance from operating forces. Inspection of
pole-mounted switches requires an assistant to operate the switch from the ground.
Determine if the preventive maintenance inspections are adequate. Check for:
n Group-Operated Switches:
• rust
• corrosion
• loose brackets and holding bolts
• nonrigid bearings and supports
7-6
ELECTRICAL
7-7
ELECTRICAL
7-8
ELECTRICAL
7-9
ELECTRICAL
Distribution Transformer-Continued
• broken cable insulation
• corrosion indicated by blue, green, white, or brown corrosion
products on metallic portions of all main and ground terminals,
including terminal board and grounding connections inside
transformer case
n Enclosure and Cases:
• signs of moisture if case is opened
• plugged breathers
• inactive desiccant
• enclosure leakage
• weathertightness
• rust or corrosion on inside cover
n Coils and Cores: If feasible, probe down side with glass rod, and if dirt
and sludge exceed approximately 1/2 inch, arrange to change or filter
insulating oil, and have coils and cores cleaned. Use low-pressure air, if
available, to blow out dust from air-cooled transformers, or pull out dust
with vacuum equipment:
• interior deficiencies
• dirt
• sludge
n Gages and Alarms: ENGINEERING TESTS should be performed under
supervision of qualified electrical engineer before, during, or after
inspection as applicable. Assistance of inspectors and craft personnel is
required, and arrangements should be made with proper authority to
assure coordinated effort by everyone taking part:
• liquid Level Gage and Alarm System
• dirty
• not readable
• improper frequency of calibration
• test grounding system
• test dielectric strength of insulating liquid. Refer to NAVFAC
MO-200
7-10
ELECTRICAL
Distribution Transformer-Continued
• test insulation resistance. Refer to NAVFAC MO-200
• measure load current with recording meter over period of time
when load is likely to be at its peak
• measure peakload voltage
• make regulation tests and tests of operating temperature during
peak-load-current tests
• test and calibrate thermometers or other temperature alarm systems
7-11
ELECTRICAL
Distribution Transformer-Continued
n Hangers, Brackets, Braces and Connections:
• rust
• corrosion
• bent
• distorted
• loose
• missing
• broken
• split
• other damage
• burning or charring at wood contact points resulting from grounding
deficiency
n Enclosures, Cases and Attached Appurtenances:
• collections of dirt and other debris close to enclosure that may
interfere with radiation of heat from transformer or flashover
• dirt, particularly around insulators, bushings, or cable entrance
boxes
• leaks of liquid-filled transformers
• deteriorated paint
• scaling
• rust
• corrosion, particularly at all attached appurtenances, such as lifting
lugs, bracket connections, and metallic parts in contact with each
other
n Nameplates and Warning Signs:
• dirty
• chipped
• worn
• corroded
• illegible
7-12
ELECTRICAL
Distribution Transformer-Continued
• improperly placed
n Grounding:
• loose, missing, broken connections
• signs of burning or overheating
• corrosion
• rust
• frayed cable strands
• more than 1 strand broken in 7-strand cable
• more than 3 strands broken in 19-strand cable
n Bushings and Insulators:
• cracked, chipped, or broken porcelain
• indication of carbon deposits
• streaks from flashovers
• dirt, dust, grease, soot, or other foreign material on porcelain parts
• signs of oil or moisture at point of insulator entrance
n Grounding and Phase Terminals:
• overheating evidenced by excessive discolorations of copper
• loose connection bolts
• defective cable insulation
• no mechanical tension apparent as a result of temperature changes
• leads appear improper and create danger of flashovers from unsafe
phase-to-phase or phase-to-ground clearances caused by
deterioration of leads or expansions during temperature changes.
n Lightning Arresters:
• where attached to or mounted on, refer to Ground Test (Lightning
Protection) (Electrical)
n Breathers:
• holes plugged with debris
• desiccant-type breathers need servicing or replacement
7-13
ELECTRICAL
Distribution Transformer-Continued
n Grills and Louvers for Ventilation of Air-Cooled Transformers:
Openings located near floor or ground line can be inspected with small
nonmetallic framed mirror having long insulated handle, used in
conjunction with light from hand flashlamp having insulated casing.
Throw light beam onto mirror and reflect upward into openings:
• plugged with debris or foreign matter, interfering with free passage
of air.
7.2.5 Electrical Utility System: Start the inspections from the source (power
plant, local power company feed, or where the power lines come up from the ground.)
Obtain electrical utility system drawings before inspections. Nothing should be turned
on or off and nothing should be opened or closed unless special arrangements have
been made with the activity. Notify the local utility department before starting the in-
spections.
n Overhead - Check for:
• Condition of all components, especially
• Rusting of metal parts
• Rotting of pole (knock the base of the pole with a hammer
and listen to sound)
• Broken insulators
• Proper sag of conductors
• Proper installation of components
• Leaking transformers
n Underground:
7-14
ELECTRICAL
7-15
ELECTRICAL
7-16
ELECTRICAL
7-17
ELECTRICAL
7-18
ELECTRICAL
7-19
ELECTRICAL
7-20
ELECTRICAL
7-21
ELECTRICAL
7-42
ELECTRICAL
7-23
ELECTRICAL
Fuses and Small Circuit Breakers (Under 600 Volts and 30 Amperes)-Continued
n Enclosures:
• deterioration of enclosures or connecting conduit or cable due to
rust or corrosion
• loose, corroded, or missing covers
n Connections (if visible without removing covers):
• loose
• corroded
• inadequate
• deteriorated insulation
n Capacity:
• Check size of existing fuses or circuit breakers against system
engineering drawings. Report oversized fuses and circuit breakers
n Fuses:
• overheating indicated by discoloration of brass or copper at contact
points
• distortion
• charring
• deterioration of fiber cases of cartridge type cases
n Circuit Breakers:
• distortion
• charring
• deterioration of molded portions of case
n Grounding:
• loose corroded connections
• deteriorated or abraded insulation
• frayed or broken cables
7.2.10 General wiring: Check for:
n Broken conduit:
n Exposed wiring:
n Missing box and conduit covers missing:
7-24
ELECTRICAL
General Wiring-Continued
n Deterioration of conductor insulation:
n Sagging or improperly supported conduit:
n Condition of electrical devices, receptacles, switches, electrical
equipment, motors, etc.:
n Romex wiring exposed to physical damage:
7.2.11 Ground Test (Lightning Protection):
n Lightning Protection System Requirements:
The resistance of the primary and secondary system shall not exceed 10 ohms. When
the primary system is installed in wet ground, its resistance shall not exceed 3 ohms. To
obtain continuous and reliable protection, the systems shall be maintained to function
efficiently. A higher resistance caused by any parts of the system being corroded,
broken, or poorly installed may cause lightning discharged or current to take a less resis-
tant path through the building and its contents thereby causing fires and explosions.
Deterioration is most active at the places where the conductors enter the ground.
n Semiannual Inspection:
Ensure that the primary and secondary systems are visually inspected semiannually for
evidence of corrosion and broken connections. Repairs for all discrepancies found
during these inspections shall be made immediately.
n Annual Test:
Ensure that the lightning protection system is tested electrically annually. The results of
these tests, together with the description of the defects noted and repairs made, shall be
submitted to the person responsible for the efficient operation of the lightning protec-
tion systems and entered in the station records.
n Equipment Used:
Electrical tests consist of measuring the ohms resistance of the system to ground and the
ohms resistance of any grounding system or individual ground connection. An instru-
ment such as an ohmmeter or a megger should be used to measure the resistance. The
procedures outlined below are based on the use of a testing instrument which is
equipped with a test ground. If an instrument such as a megger is used, two instrument
grounds are needed. The manufacturer’s instructions for using the instrument should
be followed carefully to avoid damage to the instrument and to insure valid results.
7-25
ELECTRICAL
A copper-clad steel rod from 3/8 inch to 1 inch in diameter and long enough to be
driven into the ground so it makes good contact with permanently moist soil should be
used for the test ground. The diameter of the rod has little effect on the magnitude of
the electrical resistance to ground.
n Method of Test:
Primary System:
One lead of the test instrument should be connected to the test ground and
the second lead in turn to each of the air terminals. The resistance to ground for each
air terminal shall be recorded.
Secondary System:
The resistance to ground and the electrical continuity of all grounded doors,
windows, gutters, downspouts, shutters, trusses, columns, girders, reinforcing rods, and
other metal objects in buildings and magazines should be tested by securing one lead of
the test instrument to the part being tested and the other lead to the test ground.
n Electrical Connections:
In order to assure low contact resistance, the metallic surfaces forming each electrical
contact must be carefully scraped until they are bright and shiny to remove any paint
and oxide film. The teeth of terminal clips should similarly contact a bright and shiny
metallic surface. If the surface film is not removed, sufficient pressure must be applied
to terminal clips to cause their teeth to break through to the basic metal conductor un-
derneath.
7.2.12 Grounds and Grounding Systems: Comply with all current safety
precautions. The condition of the grounding system is important both for proper opera-
tion of the distribution system to obtain indications of improper or unsafe conditions af-
fecting operation of the system and to protect personnel from electric shock that might
result in injury or death. Grounds and grounding systems require maintenance at
much higher levels of perfection than most other facilities, to assure the required de-
gree of safety to personnel. Because a current as low as 5 milliamperes is considered
7-26
ELECTRICAL
dangerously high and current as low as 10 milliamperes may be fatal, extreme care must
be exercised in inspecting and testing ground and grounding systems to minimize danger
of electric shock and possible resulting injury or death. In general, NEVER open a
grounding circuit connection when the equipment it is intended to protect is energized.
This applies equally to grounds on structural or supporting members, to grounds on
equipment enclosures, and to grounds on either primary or secondary system neutrals.
The life and safety of everyone approaching, or coming in contact with, electrical
facilities depends on how carefully and completely inspections of grounds and ground-
ing systems are performed. When equipment is energized, DO NOT make inspection
at bases of electrical equipment, regardless of circuit voltage. Determine if preventive
maintenance inspections are adequate. Check for:
n Visual Connections:
• loose, missing, broken connections
• signs of burning or overheating
• corrosion
• rust
• frayed cable strands, more than one strand broken in 7-strand cable,
more than 3 strands broken in 19-strand cable
n Underground Connections:
• unsatisfactory condition or defects uncovered when 4 or 5
connections are exposed to view by digging
7-27
ELECTRICAL
7-28
ELECTRICAL
Instruments-Continued
• improperly marked and identified
• incorrect type and range for application
• no manufacturers’ instructions for servicing
• poor physical condition of instrument cases, portable cases, handles
nameplate, leads, calibrated leads, shunts, multipliers
• loose electrical connections
• dirty or corroded contact surfaces
• inadequate, poorly arranged, improperly insulated wire, cable, and
leads
• broken glass
• pointer friction
• warped or dirty scale
• bent pointers
• missing parts
• moving elements not locked when instruments provided with
locking devices are not in use
• inkwell not clean and dry when portable type recording instruments
are in storage
n Calibration:
• Not serviced, calibrated, or tested at appropriate intervals to
accepted standards of accuracy for particular instrument
• records of tests not available
n Watt-Hour Meters:
• nonoperative voltage (power-on) indicating lamps
• Outdoor Service Meters
• poor physical condition
• loose weather seals
• moisture or dirt in enclosure
• corrosion
• loose connections
• missing parts
7-29
ELECTRICAL
Instruments-Continued
n DC Ammeters:
• improperly connected in grounded leg of grounded DC circuits
n Instrument Transformers:
• poor physical condition
• dirty
• inadequate connections
• visual evidence of overloading or overheating
7.2.14 Lighting: Check condition and operation of:
n Diffusers, lens, globes:
n Broken or aging fixture:
n Proper wiring and mounting of fixtures:
n Proper operation of all emergency lighting fixtures:
n Assure that emergency lights are wired into dedicated circuits:
7.2.15 Motors and Generators: Comply with all current safety precautions.
Determine if preventive maintenance inspection is adequate. When practicable, start,
run, and cycle motor and generator equipment through load range. Take care in start-
ing motors and generators. On standby or infrequently operated equipment, check
rotor freedom and lubrication. At humid locations check records for evidence of
regular exercise; if not found arrange for drying out windings; megger windings before
starting motor. Check for:
7-30
ELECTRICAL
7-31
ELECTRICAL
7-32
ELECTRICAL
7-33
ELECTRICAL
7-34
ELECTRICAL
7-35
ELECTRICAL
INSULATION-RESISTANCE VALUES
7-36
ELECTRICAL
OVERHEATING:
Overload
Field or armature short circuit
Poor ventilation
Rotor off center
Unbalanced phase currents
Excessive field current
Line voltage too low
Bearing friction
HUNTING ACTION:
Load variation
Variation in voltage frequency (unstable speed of prime mover)
7-37
ELECTRICAL
Navigation Lights-Continued
• defective insulators, cleats, and cable supports
• broken or missing parts
• exposed live parts
• evidence of overheating
• grounds and short circuits
• overheated splices
• damaged or defective insulation
• need for painting of noncurrent-carrying parts subject to corrosion
• defective operation (try manually and electrically when practicable)
n Battery:
• Connections
• loose
• corroded
• dirty
• inadequate
• proper output voltage
7.2.17 Panels: (primary, secondary, and sub)
Check for:
n Ground wire and buss:
n Proper wire connections:
n Correct circuit breaker size (Ampere):
n Deterioration of conductor insulation:
n Unprotected or tapped circuits:
n Excessive heat:
n Proper feeder and branch circuit conductors:
n Proper load amps and feeder conductor size:
n Unbalanced load:
n Circuit capacity (to see if circuits could be added):
n Age of panel (economical availability of replacement parts):
7-38
ELECTRICAL
7.2.18 Potheads: Comply with all current safety precautions. DO NOT TOUCH
when energized. Determine if preventive maintenance inspections are adequate. Check
for:
n Porcelain:
• cracks
• breaks
• chips
• checking of porcelain glaze
• streaks of carbon deposits indicating flashovers and possible damage
• dirt, dust, grease or other deposits
• cracks, breaks, or deterioration of cement sealing compound
• leakage
• signs of moisture
n Cable Clamps:
• corrosion
• loose bolts, solder or GROUND CONNECTION
• poor mechanical connections. (Corrosion of lead cables and
connections at potheads indicated by presence of a white, brownish,
or reddish product.)
n Terminal Studs and Bolting Pads:
• corrosion
• loose connections
• poor contacts evidenced by discolorations from heating.
n Mountings:
• corrosion
• other weakness
7.2.19 Power Plants: Comply with all current safety precautions. Check for:
n General:
• Housekeeping: lack of cleanliness or orderliness
• Safety Signs and Posted Instructions
• inadequate
• illegible
7-39
ELECTRICAL
Power Plants-Continued
• improper location
• Operating Log, Plant Log, and Maintenance Records
• failure to record pertinent readings
• other information necessary to locate and evaluate trouble
areas and trends
• Evidence of need to follow up deficiencies that may lead to
breakdown
n Generator Loading Operating Log:
• review for duration and amount of overload, ambient temperature,
temperature rise. Note when rated temperature is approached or
exceeded
n Insulation:
• Make insulating test measurements of generator field, armature
windings, and cable from main breaker terminals. Note evidence of
electrical weakness to extent that normal operating voltage or
surges may result in failure
n Generator Excitation Systems:
• inadequate
• not serviceable
• unreliable
• poor physical condition of emergency exciters and associated
equipment, including rheostats, pilot exciters, voltage regulators,
motor drives
• inadequate ground indicating system in ungrounded exciter circuits
n Plant Battery:
• Battery Room or Enclosure:
• lack of cleanliness
• unacceptable temperature
• inadequate ventilation
• unsatisfactory condition of floor
• fire hazard from lighting and power fixtures, fittings, and
cable
7-40
ELECTRICAL
Power Plants-Continued
• Operating and Maintenance Records:
• review for deficiencies in specific gravity levels
• cell temperature
• makeup water history
• equalizing charge practices
• sustained overcharges and discharges
• Connections:
• loose
• corroded
• dirty
• inadequate
• Cells:
• oversulphated plates
• physical erosion
• internal shorts
• buckled plates
• cracked grids
• dirty electrolyte
• improper electrolyte level
• excessive sedimentation
• Chargers and Controls: poor physical condition
• Instruments: inaccurate, (check frequency of calibration)
n Buses:
• poor condition
• dirty
• structural distortion
• loose joints and connections
• evidence of overheating
7-41
ELECTRICAL
Power Plants-Continued
n Control Switchboards:
• poor physical condition
• dirty
• Wiring and Connections
• lack of neatness
• looseness
• Fuses in Control Wiring System: improper size
• Indicating Lamps: not operating
• Mimic Buses
• illegible
• inaccurate
7.2.20 Rectifiers: Comply with all current safety precautions. Rectifier cabinets
and enclosures contain energized electrical equipment. DO NOT tighten wires, make
adjustments, or disturb any valve, control, or other adjustment device. Check for:
ENCLOSURES
n General Area Housekeeping:
• dust
• dirt
• trash
• debris
n Exterior:
• mechanical damage
• excessive corrosion (more than two rust spots 1/2 inch diameter)
• corroded, binding or unlubricated hinges and latches
n Interior:
• rust
• corrosion
• moisture condensation
• indications of excessive heating
7-42
ELECTRICAL
Rectifiers-Continued
n Wiring:
• broken
• damaged
• deteriorated
• missing insulation or clamps
• corroded or mechanically damaged conduit
• cracked or broken sleeves on floor or wall bushings
METALLICRECTIFIERS
n Electric Meters:
• Record readings from all AC and DC ammeters and voltmeters.
Report if supply voltage is more than 5% below or above nameplate
rating. Report defective meters
n Temperature:
• Record readings of water temperature indicators, if provided. On
indoor installations record ambient temperature at apparent hottest
point five feet from units. Report if temperature of cooling water is
more than 10% above that recommended by manufacturer
n Fan:
• dirt
• excessive vibration
• loose hold-down bolts
• loose or worn bearings
• inadequate or improper lubrication
MERCURY-ARC RECTIFIERS
n Meters and Gages:
• illegible
• inadequate lighting
• cracked, broken, dirty or badly stained viewport glasses
7-43
ELECTRICAL
Rectifiers-Continued
n Water Cooling Systems:
• leaks
• rust
• corrosion
• mechanical damage
• excessive vibration
n Pumps, Fans, and Motors:
• leaks
• excessive vibration
• loose or missing hold-down bolts
• deteriorated mounting pads or shock pads
• inadequate or improper lubrication
7.2.21 Relays: Comply with all current safety precautions. Determine if preven-
tive maintenance inspections are adequate. Check for:
n Relays (General):
• dirty
• evidence of moisture
• high temperature
• other adverse conditions
• visible corrosion
• deterioration or pitting of contacts, pivots, and coils
• broken or loose parts and connections
n Temperature and Pressure Relay:
• settings at improper temperature and pressure limits
• evidence of damaging temperature or pressure conditions
7-44
ELECTRICAL
7.2.22 Steel Power Poles and Structures: Comply with all current safety precau-
tions. Remember these structures are part of an Electrical system and may be conduct-
ing current. Avoid contact with line poles and structures until they have been grounded
and/or deenergized. Check for:
n Ground Area:
• trash, debris, weeds or brush one foot in height within 3 feet of pole
or structure
n Concrete Bases, Pads and Anchor Bolts:
• cracks, including surface cracks wider than 1/16 inch
• breaks
• chipped areas deeper than 1/2 inch
• settlement
• movement
• defective paint/galvanizing
• visible rust or corrosion to depths exceeding 1/16 inch
• loose or missing nuts/bolts
• where visible, inspect all metal where it enters concrete
n Street Light Standard Handholes and Bell Interiors: Visual Inspection
Only, If Energized:
• rust
• corrosion
• installed transformers
• loose wires
• excessive discolorations from heating and sparking
• signs of insulating compound or other leakage
• charred, burned, or missing insulation
n Poles, Structures, Crossarms and Beams: Inspection from Ground, Use
Field Glasses:
• defective paint/galvanizing
• visible rust or corrosion, especially pitting where visible
• inspect all metal in contact with, or entering concrete
• loose bolts and pins
7-45
ELECTRICAL
7-46
ELECTRICAL
7.2.23 Switchgear: Comply with all current safety precautions. Check for:
n Asbestos: Inspect ARC chutes and flash pads for friable asbestos.
Vacuum to eliminate safety and health hazard using high efficiency
particulate air vacuum (HEPA VAC) Do not use compressed air. Avoid
dispersing asbestos. Then encapsulate and seal with insulating paint such
as “Gyptal” or equivalent from any manufacturer. Use protective clothing
and respirator as required. Empty HEPA VAC into plastic bag for
disposal at approved asbestos disposal facility:
n Are preventive maintenance inspections adequate?
n Housekeeping:
•
dampness
•
dirty
•inaccessibility
•
detrimental conditions such as ambient temperatures in excess of
100°F
• humidity causing sweating of metal enclosures
• rodents or insect infestations
• stored combustibles
• trash, dirt or dust accumulations
• poor location
• poor ventilation
• gas, steam or water leakage
n Exterior Housing and Enclosure Ground:
rust
corrosion
need for painting
signs of abuse
unauthorized or improper signs
storage materials or dust accumulating on top of enclosures
missing parts or other items
poor condition or inadequacy of enclosure ground
7-47
ELECTRICAL
Switchgear-Continued
n Interior of Compartments, Cubicles and Drawers:
• dirty
• condensation
• symptoms of overheating
• burns from ground and short circuits
• defective insulation
• defective operation of locks, doors, and drawers
n Air and Oil Circuit Breakers, Oilless-Type Air Blast Breakers
(Deenergized/50 Amperes and above):
• incorrect wipe of main and arcing contacts on opening and closing
• overheating
• lack of continuity
• looseness of connections on all mechanisms
• incorrectly placed pins and cotter pins
• improper functioning of rods and moving parts and binding occurs
when breaker is operated
n Tests:
• Measure operating voltage on electrically-operated breakers
• Measure operating voltages in switchgear control circuits
• Make liquid dielectric strength tests. Liquid should be changed if
tests under 18,000 volts
• Measure insulation resistance and evaluate
• minimum value or low limit recommended is 2 megohms
total (after one minute at approximately 25 degrees C.) for
safe operation or before making high-potential tests
• make high-potential tests at 65 percent of initial installed
value, or in accordance with manufacturer’s recommendation
7.2.24 Wood Poles and Accessories: Comply with all current safety precautions.
Because overhead electric distribution systems are energized almost continuous-ly, in-
spection of such items as poles, hardware, and associated accessories should be made
from the ground using field glasses except during those periods when placed outages of
the various systems will permit a climbing inspection. Ordinarily such climbing inspec-
tions will occur very infrequently and should be performed only when it is certain
7-48
ELECTRICAL
that all line wires attached to the pole are deenergized and provided with safety ground-
ing. Poles supporting only telephone open wires or telephone aerial cables should not
be climbed unless an obvious defect indicates the necessity of climbing to permit a
closer inspection. It is essential that questionable poles be tested and supported before
the pole is subjected to the unbalanced load caused by climbing for closer inspection.
Particular attention shall be given to weather conditions, power hazards, traffic warning
procedures, and tree and brush cuttings. Check for:
n Ground Area:
• water ponding at base
• debris, trash, or weeds within 3 feet in any direction
n Poles: Visual Inspection, Except as Indicated:
• sound-test with unpointed hammer for hollowness caused by
termites, carpenter ants, and/or decay fungi. Sounding should be
from groundline to the highest point reached from standing
position; actual condition of questionable poles should be
confirmed by drilling a 3/8” hole(s) with a wood bit to center of pole
in the area under suspect. Test holes must be plugged with a 7/16”
perservative treated wood dowel. Check for external decay most
prevalent in the vicinity of the ground-line area, knotholes, large
splits and checks, and in and around woodpecker holes
• splits
• lightning, bird, insect, vehicle, or other damage
• make shallow excavation around pole and take increment boring if
a faulty condition below ground is suspected. (Upon completion of
boring treat hole with wood preservative, drive treated plug into
hole, sterilize soil, backfill and tamp excavation.)
• ground-line treatment of untreated poles required in addition to all
poles in-service at least ten (10) years. Pole ground-line
re-treatments should be conducted on a ten year cycle. Preparers of
pole maintenance contracts should refer to NAVFAC Specification
TS-20212 for guidance.
• failure of originally installed protective treatment of pole
7-49
ELECTRICAL
Note: Pole plant inspectors should become familiar with NAVFAC MO-312.3,
Inspection, Maintenance and Procurement Procedures for Wood Poles. This hand-
book provides detailed guidance on inspection and maintenance procedures for wood
pole plants.
n Crossarms and Buckarms: Use Field Glasses:
• splits
• bum
• decay
• twists
• weathering damage
• other defects
n Insulators and Pins: Use Field Glasses:
• cracks
• breaks
• chips
• dirty or missing insulators
• cracked, broken or missing pins
• rust
• corrosion
• looseness of insulator bolted connections and fastenings to
crossarms resulting in strains on line wires or movement of wires on
insulators
7-50
ELECTRICAL
7-51
ELECTRICAL
7-52
ELECTRICAL
7.3.3 Lighting:
n Repair:
• Less than 20 years old
• Replacement parts available
• Replacing/repairing parts is cost effective
• General good condition and appearance
n Replacement:
• Over 20 years old
• Badly damaged or deteriorated beyond repair
• Parts difficult or impossible to procure
• Replacing or repairing parts is not cost effective
• Lighting replacement should be considered when a new suspended
ceiling is to be installed.
7.3.4 Panels: (Primary, Secondary, and Sub)
n Repair:
• General good condition
• No overloading
• No evidence of burning or arcing (fire or shock hazard)
n Replacement:
• Over 20 years old
• Badly damaged or deteriorated
• Panel overloaded
• Panel displays evidence of burning or arcing (fire or shock hazard)
7-53
ROOFING
8.1 DEFINITIONS:
Test Cuts - destructive tests used to determine primarily the composition of the roofing
system, conformance with specification, i.e., bitumen weights, and condition. Normally
test cuts are limited in number and therefore are not a complete indication of the condi-
tion of a roof structure.
Trusses - includes all types of building trusses that are normally designed for the express
purpose of supporting roof loads as well as ceilings where applicable. All lateral and
vertical bracing and ties between trusses are included
l Rust
l Damage
n Valleys:
• Punctures
• Weathering
• Deterioration
8-l
ROOFING
8-2
ROOFING
Built-up roof-Continued
• Bituminous
• Splits
• Tears
• Punctures
• Absence of protective coatings
• Separation from vertical surfaces
n Bare spots - Bare spots expose the plies directly to the elements which
can accelerate deterioration. Check for:
• Cracking
• Alligatoring
• Deteriorated felt
n Blisters - Blisters are an indication of moisture or gas between roof plies.
Do not apply enough pressure to rupture blisters as this will allow water
intrusion. Blisters do not necessarily indicate roof system failure. Check
for:
• Punctures
• Splits
• Water - by gently touching to see if water will come out of blister
n Pitch pockets
• Cracking
• Shrinkage
• Absence of bitumen
• Deterioration of perimeter metal
n Ponding water - Ponding around roof penetrations will result in leaks.
Ponding of a large area could indicate a possible structural defect.
Stopped up roof drain will cause ponding. Check for:
• Location
• Percentage of roof surface which displays ponding
n Penetrations - The majority of roof failures begin in areas near
penetrations. Check for:
• Proper flashings
• Ponding of water near penetration
8-3
ROOFING
Built-up roof-Continued
n General surface appearance:
• Displacement of aggregate
• Weathering
• Debris
8.2.3 Metal roof: Check for:
n Surface:
• Rust
• Punctures
• Tears
• Wind damage
n Fasteners:
• Loose fasteners
• Missing fasteners
• Deterioration
n Seams:
• Looseness
• Rust
n Penetrations:
• Deterioration
• Deterioration of surrounding flashing
8.2.4 Slate roof: (Do not walk on slate roof if possible.) Check for:
n Flashings:
• Missing sections
• Punctures
• Rust
• Separation of strip flashing from vertical surfaces
• Reglet seals
n Valleys - Check flashing:
n Penetrations - Check flashing:
8-4
ROOFING
Slate Roof-Continued
n Missing slate percentage - If twenty five percent (25%) or more of the
slate is missing, consider roof replacement. If this much slate is missing,
the fasteners have probably failed. Reuse some of the slate if possible
during roof replacement:
8.2.5 Trusses: Comply with all current safety precautions. To identify truss mem-
bers for the report, use a sketch of the truss and label the panel points either numerical-
ly or alphabetically. The deficient member may then be identified by indicating the
panel points between which it lies. Check for:
n Truss Sag: Examine trusses for sagging by stretching piano wire between
supports and measuring vertical defections at panel points or use a
surveying instrument:
n Painted Surfaces:
• blistering
• checking
• cracking
• scaling
• wrinkling
• flaking
• mildew
• bleeding
• rust
• corrosion
• complete absence of paint, particularly at end of members
• record film thickness and condition on metal surfaces
TIMBER
n From Ground: Use field glasses:
• twisted and bowed members
• excessive number and size of knots
• slope of grain over one inch in ten
• checks and splits in ends of web members
• separation or slippage at joints
8-5
ROOFING
Trusses-Continued
• sag
• overloading
n From Truss:
• loose bolts
• split rings
• shear plates
• fastening devices
• checks and splits in bracing, chord members, splice plates (scabs),
web members and filler blocks
• missing filler blocks
• improper end and edge distances
• looseness of tie rods. (Bolts may be considered loose if after
striking head of bolt a sharp blow with a hammer, the nuts can be
taken up two full turns or more.)
n Steel Splice Plates:
• rupture
• shearing
• crushing
• rust
n Wooden Parts:
• dry rot
• dampness and surface moisture of long duration
• termite and other insect, and fungus infestation. Termite and fungus
infestations are often detected prior to actual visual damage by
probing with a sharp-pointed instrument those areas where
prolonged dampness is not directly associated with rainfall or damp
climate
n Wooden Supports near or at Ground Level:
• termite tubes or tunnels
• dirt piled up to wood level
8-6
ROOFING
Trusses-Continued
• need of protective treatment. If removal of dirt piles is
impracticable, wood in direct contact with, or less than 8 inches
from ground level should be given protective treatment
STEEL
n From Ground:
• twisted
• bowed
• deformed
• broken members
n From Truss:
• loose bolts
• rivets
• defective welds
n From Truss: rupture, shearing, or crushing of steel plates, members,
bolts, and rivets:
8.2.6 Moisture Survey Instructions for Built-Up Roofs: Partial or total built-up
roof replacement recommendations can be made using moisture survey results. NAV-
FAC prefers a moisture survey to be completed before any built-up roof is replaced.
n Mark out a grid on the roof:
n Using the nuclear moisture detector test and record the moisture level at
each marked point:
n Map out the grid and test results:
n Draw conclusions and make recommendations from the test results:
n Prepare cost estimates based on your recommendations:
8.3 REPAIR/REPLACEMENT CRITERIA:
8.3.1 Asphalt strip shingles:
n Repair:
• Uniform and flat shingles
• Ample minerals
• Pliable
8-7
ROOFING
8-8
ROOFING
8.3.3 Metal:
n Repair:
• Repair should always be first consideration for metal roofing as it is
often impractical to replace metal roofs.
• General good appearance
• No deep rust, only surface rust if there is any
• No major deterioration
n Replacement:
• Last resort, if repairs are not possible
• Many repairs evident
• Frequent leaks -check activity’s records
• Leaks interfering with mission
• Deep rust
• Deterioration on underside of roof
• General poor appearance
8.3.4 Slate:
n Repair:
• Few if any leaks
• Few broken, missing, or deteriorated slates
• Good appearance
n Replacement:
• Many and frequent leaks
• Many repairs evident
• Leaks interfering with the mission
• Missing 25% or more of slate
• Large number of deteriorated or broken slate
8-9
INDEX
Index-l
F I
Index-2
0 Metallic Rectifiers, 7-43
Mercury-Arc Rectifiers, 7-43
Omissions, 3-7,4-1 Relays, 7-2,7-44
Operator Records, 7-30 Repair/Replacement Criteria, S-54,
Overview, 3-l 6-44,7-52,8-7
Respirator, 3-l
P Responsibilities, 3-4
Retaining Walls, 5-1,5-38
Paint, 5-1,5-4,5-6,5-15,5-34,5-56 Roof, 5-4,6-25,8-l
Painters Trolley, 5-19 Moisture Survey, 8-7
Panels, 7-2,7-38,7-53 Roofing System, 8-l
Primary, 7-2
Secondary, 7-2 S
Sub, 7-2
Pavement, 5-1,5-39,5-57 Sacrificial Anode Systems, 7-3,7-16
Physical, 3-1 Safety Equipment, 3-l
Piers, 5-10 Safety Hazards, 3-6
Piping, 6-2,6-34,6-48 Sanitary Sewage Utility System, 6-2,6-36
Chilled/Hot Water System, 6-2 Scheduling, 3-4
Compressed Air, 6-2 Scope, 3-l
Natural Gas, 6-2 Septic Tanks, 5-33
Sewage, 6-2 Service Work, 3-6
Steam, 6-2 Sewage, 6-2
Water, 6-2 Slate Roof, 8-4,8-9
Pitch Pockets, 8-3 Sodded Areas, 5-5
Plumbing, 6-2,6-35,6-49 Special Projects, 3-6
Potheads, 7-2,7-39 Specialized Inspections, l-l
Power Plants, 7-2,7-39 Spillways, 5-30
Preventive Maintenance Inspection Sprinkler System, 5-32
Oversight, 3-4 Stacks, 7-6
Protective Devices, 5-37 stair, 5-1,5-40,5-57
Pump, 6-36 Steam, 6-2,6-5,6-8,6-9,6-11,6-14,
6-15,6-33,6-34
Q Steam Utility System, 6-2,6-36
Steel Framing, 5-11
Quality Assurance, 3-7 Steel Power Poles and Structures, 7-2,
7-45
R Steel Tanks, 5-24
Storm Drainage System, 5-1,5-41
Radiators, 6-29 Superstructures, 5-12
Railroad Trackage, 5-1,5-34 Swimming Pools, 5-1,5-43
Rectifier-Powered Systems, 7-4,7-17 Switchgear, 7-3,7-47
Rectifiers, 7-42
Enclosures, 7-4,7-42
Index-3
T Water Utility System, 6-3,6-43
Waterfront, 3-3,5-2,5-49,5-57
Tanks, Topside, 5-2
Concrete, S-24,7-19 Underside , 5-2
Interior, 6-26 Underwater, 5-2
Linings, 6-26 Weed Control, 5-33
Steel, 5-24,7-19 Window, 5-2,5-54,5-57
Wood, 5-24,7-19 Wood Flooring, 5-12,5-16
Test Cuts, 8-l Woodlands, 5-29
Ties, 5-35 Wood Poles and Accessories, 7-3,7-48
Timber, 8-5 Workload Planning, 3-l
Timber Framing, 5-11
Timber Towers, 5-6,5-25 Z
Tools, 3-2
Towers, 5-25,7-20 Zone Pumps, 6-29
Trees, 5-29
Trusses, 8-1,8-5
Timber, 8-5
Steel, 8-7
Tunnels and Underground Structures,
5-1,5-46,6-20
Ventilation,
Motors & Generators, 7-31
Ventilators,
Ammunition Storage, 5-5
Index-4