Energies 15 04824
Energies 15 04824
Article
Transient Stability Analysis of a Multi-Machine Power System
Integrated with Renewables
Ajaysekhar Agarala 1 , Sunil S. Bhat 1 , Arghya Mitra 1 , Daria Zychma 2 and Pawel Sowa 2, *
1 Department of Electrical Engineering, Visvesvaraya National Institute of Technology, Nagpur 440010, India;
agaralaajay@students.vnit.ac.in (A.A.); ssbhat@eee.vnit.ac.in (S.S.B.); mitraarghya@eee.vnit.ac.in (A.M.)
2 Department of Power System and Control, Faculty of Electrical Engineering, Silesian University of Technology,
44-100 Gliwice, Poland; daria.zychma@polsl.pl
* Correspondence: pawel.sowa@polsl.pl
Abstract: The impact on the stability of power systems is rising as the penetration level of renewable
energy with sporadic natures rises rapidly on the grid. However, the impact of different types of
renewable energy sources (wind, solar) and their combination on system stability varies even with
the same penetration level. This paper concentrates mainly on the stability analysis of multi-machine
systems connected to various types of renewable energy sources. The study presents a simple
and novel control technique named automatic reactive power support (ARS) for both single and
combinations of renewable sources by injecting the available reactive power into the system during
fault through converters to enhance system stability. The permanent magnet synchronous generator
(PMSG) and doubly fed induction generator (DFIG) are both considered as wind generators in this
paper for comparison. In addition, transient stability enhancement is carried out by improving
critical clearing time of a three-phase fault in the power system. With the creation of a 3-phase fault
at various buses, stability analysis is carried out on the 9-bus WSCC test bus system and also on
the 68-bus IEEE test system. Comparative analysis of six test case conditions is provided and the
Citation: Agarala, A.; Bhat, S.S.;
considered cases are without renewable source, with DFIG as a wind generator, PMSG as a wind
Mitra, A.; Zychma, D.; Sowa, P.
generator, solar PV farm, wind farm with DFIG and solar PV in combination and the combination
Transient Stability Analysis of a
of wind farm with PMSG and solar PV. Moreover, the improvement in critical clearing time of the
Multi-Machine Power System
system is compared using conventional and proposed controls with all the aforementioned renewable
Integrated with Renewables. Energies
2022, 15, 4824. https://doi.org/
sources. Comparative results show that the proposed control technique improves system stability
10.3390/en15134824 and also that the combination of renewable energy sources ought to enhance the critical clearing time
of system.
Academic Editors: Soobae Kim and
Jeonghoon Shin
Keywords: DFIG; PMSG; solar PV; transient stability; multi-machine system and reactive power control
Received: 31 May 2022
Accepted: 24 June 2022
Published: 1 July 2022
1. Introduction
Publisher’s Note: MDPI stays neutral
with regard to jurisdictional claims in The integration of non-conventional energy sources, specifically solar PV power and
published maps and institutional affil- wind power generation sources, with the grid has risen drastically in the past decade [1].
iations. As advanced power electronics develop, solar and wind energy become the most attractive
and promising types of renewable energy sources [2,3]. However, the challenges, such as
the impact of a high penetration level of renewable energy sources (RES), and their possible
solutions are focused and addressed in the literature [4,5].
Copyright: © 2022 by the authors. In [6], studies were conducted to provide electric energy to a local community with
Licensee MDPI, Basel, Switzerland. 100 households and a health center by using a wind–solar hybrid power generation system
This article is an open access article
in Ethiopia. The effect of partial shading in the PV module is investigated in [7–9]. The
distributed under the terms and
benefits and drawbacks of various maximum power point tracking (MPPT) strategies
conditions of the Creative Commons
in solar PVs and their importance is explained in [10–12] to assure maximum power is
Attribution (CC BY) license (https://
delivered to the system. However, the difficulties in the control techniques of MPPT with
creativecommons.org/licenses/by/
proportional-integral-derivative controllers are minimized by using the model predictive
4.0/).
control [13] and the sliding mode control [14]. The workings of wind energy systems
with an implementation of MPPT are investigated in [15–19]. Studies of different types
of wind generators are carried out in [20–23]. The impact of grid-integrated wind farms,
with a DFIG as wind generator, on the transient stability of power systems is investigated
in [24,25]. Stability analysis of grid-integrated solar PV systems is seen in [26–28]. The
decoupled control approach is a well-adapted control method which allows for controlling
real and reactive power independently and is considered in [27]. To enhance stability, the
grid-side converter (GSC) behaves as a STATCOM while the DFIG operates at a constant
speed during the fault. Solar system inverters can be configured to regulate renewable
power generation in response to changes in system frequency and voltage [28].
Recently, studies have been more intense regarding the integration of combinations of
renewable sources which ensure the optimum utilization of resources and hence improve
overall efficiency as compared to single modes of operation. The hybridization of solar and
wind systems exploits the advantages of both while at the same time easing limitations. The
power generated by the hybrid renewables can be extracted more efficiently by implement-
ing new technologies in power electronics. The implementation and working of hybrid
systems of wind and solar energy, their advantages and disadvantages. and different
topologies of hybridization are explained in [29], and the power system equivalents for
dynamic and transient studies are created and analyzed in [30]. The effect on transient
stability with hybrid models of hydro power, solar, and wind power injected to a single
machine connected to an infinite bus system is investigated in [31]. The improvement of
system stability connected to hybrid renewable sources with arbitrary amounts of reactive
power support is mentioned in [32].
The main aim of the proposed research work is introducing a simple, new technique to
improve multi-machine system (MMS) transient stability coupled with both individual and
combinations of renewable sources. The concern about system stability is increasing as the
share of renewable energy injection with variable power natures is expanding. Objectives
of the present work are as follows:
• Modifying the controllers of the converters such that all RES connected to the system
will be injecting the maximum available reactive power into the grid during faults.
Normally, the converters are configured to inject only real power into the grid (with
unity power factor). The injection of reactive power during faults improves the bus
voltage profile and hence enhances the overall stability of system.
• Performing a comparative analysis of critical clearing time for a MMS coupled with
different renewable sources.
The proposed controller’s performance is validated with an individual RES and as
well as hybrid renewables along with different fault locations at different fault instants.
The study is performed on a WSCC 9-bus system and also IEEE 68-bus system.
The rest of the article is organised as follows. Section 2 presents the mathematical mod-
elling of a complete power system including the RES. Both the existing control techniques
and the proposed control techniques used in the RES are explained in Section 3. Section 4 is
carried out with analysis of system results followed by the conclusion in Section 5.
n machine systems with i = 1 through n) including a static exciter with one time constant
and one gain can be summarized as [24,34]
dδi
= ωs ∆ωi (1)
dt
d∆ωi
2Hi = Pmi − Pei − K Di ∆ωi (2)
dt
dE0 qi
0 xdi 0 xdi
T doi = − 0 E qi + − 1 Vi cos(δi − θi ) + E f di (3)
dt x di x 0 di
dE f di
TAi = − E f di + Vre f i − Vi K Ai (4)
dt
where δ represents the rotor angle, ω s and ∆ω i are the synchronous speed and deviation in
rotor speed (per unit), respectively, KD is damping coefficient, H represents the inertia con-
stant, Pe and Pm are the output electrical power and input mechanical power, respectively,
the q-axis and d-axis components of synchronous reactance are represented by xq and xd ,
respectively, x0 q and x0 d are the q-axis and d-axis components of transient reactance, E0 qi is
the q-axis component of voltages behind the transient reactance of the ith generator, T0 doi
is the d-axis open circuit time constant, TA and KA are the time constant and gain of the
exciter, Efd represents the exciter voltage, V is the per unit terminal voltage of the machine,
and angle is represented by θ.
where IL and ID are photocurrent and reverse saturation current of diode, respectively. K
denotes Boltzmann’s constant, T is the temperature, ‘α’ is the diode ideality factor, and
‘q’ represents charge of electron. RSH and RS represent the equivalent shunt and series
resistance of the PV cell. A connection diagram of a solar PV farm to the grid is shown
in Figure 1. The power generated by the solar PV is injected to the grid through a4boost
Energies 2022, 15, x FOR PEER REVIEW of 19
converter, voltage source converter (VSC) filter, and transformer. Equations of solar PVs
are modelled assuming that power generated is always maximum.
Figure
Figure 1.
1. Connection
Connection diagram
diagram of
of aa solar
solar PV
PV farm
farm to the system.
dωr 1
= [k θtw + Csh ωbase (ωt − ωr ) − Te ], (6)
dt 2Hg sh
dθtw
= ωbase (ωt − ωr ), (7)
dt
dωt 1
= [ Tm − k sh θtw − Csh ωbase (ωt − ωr )]. (8)
dt 2Ht
Here, ω t and ω r are the mechanical speed of the turbine and rotor, respectively, Hg
and Ht are the generator and the turbine inertia, respectively, θ tw represents the torsional
angle of shaft, and Csh and ksh are the damping coefficient and shaft stiffness, respectively.
Tm and Te are the mechanical and electrical torque, respectively.
where t
X = ids , iqs , e0 d , e0 q
t
U = vds , vqs , vdr , vqr
R L2 L2m
−ωeB Lrr ωeB Lrr ωeB ω R Lrr −ωeB Rr
L L − L 2 Rs + Lr 2 m L
Lss Lrr − L2m ss
− Lrr Lss Lrr − L2m Lss Lrr − L2m
ss rr m rr
L2 Rr L2m
ωeB Lrr −ωeB Lrr −ωeB Rr ωeB ω R Lrr
L L − L2 Lss − Lrrm R +
2
Lss Lrr − Lm s 2 Lss Lrr − L2m Lss Lrr − L2m
2 Lrr
A = ss rr m
−ωeB Rr
0 −ωeB ωs RLr L2 m ω s ( ω s − ωr )
rr Lrr
2
−ωeB Rr
−ωeB ωs RLr L2 m 0 ω s ( ω s − ωr ) Lrr
rr
Lm
−1 0 Lrr 0
0 −1 Lm
0 Lrr
B =
− ωs Lm
0 0 0 Lrr
− ωs Lm
0 0 Lrr 0
where ‘v’ and ‘i’ are voltage and current of the machine, respectively. The suffixes ‘qs’, ‘qr’,
‘ds’, and ‘dr’ are q-axis and d-axis components of stator and rotor quantities, respectively.
‘ω eB ’ is base electrical speed and ‘ω s ’ is the synchronous speed. ‘L’ and ‘R’ are the inductance
and resistance of the machine, respectively. The suffixes ‘ss’, ‘rr’, and ‘m’ are self and mutual
components, respectively. In addition, the equivalent q-axis and d-axis source voltages
behind transient reactance “e’ q ” and “e’ d ” are as follows
ωs Lm
e0 q = − ( Lrr idr + Lm ids )
Lrr
‘ωeB’ is base electrical speed and ‘ωs’ is the synchronous speed. ‘L’ and ‘R’ are the induct-
ance and resistance of the machine, respectively. The suffixes ‘ss’, ‘rr’, and ‘m’ are self and
mutual components, respectively. In addition, the equivalent q-axis and d-axis source volt-
ages behind transient reactance “e’q” and “e’d” are as follows
ωe's L=mω s m ( L i + L i )
L
0
e d = d LrrLrr iqrrr qr+ Lmm iqsqs
Lrr
Figure2.2.Connection
Figure Connectiondiagram
diagramofofaawind
windfarm
farmwith
witha aDFIG
DFIGtotothe
thesystem.
system.
The
Theelectromagnetic
electromagnetictorque
torqueisisasasfollows
follows
Te T= = 1eq0ie
1 h ' + e0 i ' .
i
q iqs +d edsd ids .
qs (10)
(10)
e ωs
ωs
2.5.
Energies 2022, 15, x FOR PEER REVIEW Modelling of the PMSG 6 of 19
Figure3.3.Connection
Figure Connectiondiagram
diagramofofaawind
windfarm
farmwith
withaaPMSG
PMSGtotothe
thesystem.
system.
2.6.
2.6.Integration
IntegrationofofRESRESwith
withthe
theGrid
Grid
Integration
Integrationof ofrenewable
renewableenergy
energysources
sourcesto tothe
thegrid
gridisisaagreat
greattask
taskwith
withan
anincreased
increased
penetration level. The integration of hybrid renewables to the existing power
penetration level. The integration of hybrid renewables to the existing power system system creates
cre-
technical
ates technical challenges including harmonic distortion, flicker, voltage regulation,The
challenges including harmonic distortion, flicker, voltage regulation, etc. etc.
challenges
The challengesinvolved in thein
involved integration of RESofwith
the integration RESthe
withgrid
theand theand
grid advanced techniques
the advanced tech-
to overcome
niques those challenges
to overcome are presented
those challenges in [38,39].
are presented The power
in [38,39]. generated
The power by theby
generated RES
the
isRES
intermittent in nature
is intermittent and can
in nature andcause stability
can cause issues
stability grid-side.
issues TheThe
grid-side. synchronization
synchronization of
of voltage magnitude and the frequency of RES with the grid is the most important aspect
in integrating RES to the grid. The injection of power must also occur with less harmonics.
voltage magnitude and the frequency of RES with the grid is the most important aspect in
integrating RES to the grid. The injection of power must also occur with less harmonics.
Lm
Te = − λqs idr , (13)
Lss
λqs Vds
Lm Vds
Qs = iqr − . (14)
Lss Lss
The reference values of both q-axis and d-axis components of rotor currents are calcu-
lated by re-arranging (13) and (14) as follows
Lss
idrre f = − Tere f , (15)
Lm λqs
Lss λqs
iqrre f =− Qsre f + . (16)
Lm Vds Lm
for the grid voltage become zero (i.e., Vq = 0). Thus, the expression for active and reactive
power of Equations (17) and (18) can be modified as follows:
3
P= V I , (19)
2 d d
3
Q= V Iq . (20)
2 d
From (19) and (20) we can control P and Q independently by d-axis and q-axis compo-
nents of current (Id and Iq ), respectively. The reference for the q-axis component of current
is chosen to be zero (i.e., Iqpref = 0) in order to maintain unity power factor for the power
injected into the grid. Voltage equations between the grid and inverter are as follows [24]
d
Vd = R g Id + L g I − ωs L g Iq + Vds , (21)
Energies 2022, 15, x FOR PEER REVIEW dt d 8 of 19
d
Vq = R g Iq + L g Iq + ωs L g Id . (22)
dt
Here, Rg and Lg are the resistance and inductance of line, respectively. The conven-
Here, R and Lg are the resistance and inductance of line, respectively. The conven-
tional controlgblock of the GSC is shown in Figure 4.
tional control block of the GSC is shown in Figure 4.
(a)
(b)
Figure
Figure4.4.(a)
(a)q-axis
q-axiscontrol
controlblock;
block;(b)
(b)d-axis
d-axiscontrol
control block
block of
of GSC.
GSC.
3.2.
3.2.Conventional
ConventionalControllers
Controllersin
inthe
thePMSG
PMSG
Wind farms
Wind farms with
with aa PMSG
PMSG also
also have
have two
two converters.
converters. One
Oneisisaamachine
machineside
sideconverter
converter
(MSC),and
(MSC), andthe
the other
other is
is aa grid-side
grid-side converter
converter(GSC).
(GSC).The
Theconventional
conventionalcontrollers
controllersused
usedin
in
thesetwo
these twoconverters
convertersare
are presented
presented here.
here.
3.2.1.Controllers
3.2.1. Controllersininthe
theMachine
MachineSide
SideConverter
Converter (MSC)
(MSC)
Extraction of
Extraction of maximum
maximum powerpowerisis the
the aimaim of
of the
the MSC
MSC controller
controller for
for the
the PMSG
PMSG byby
controlling the speed of the PMSG rotor. The MPPT controller starts to
controlling the speed of the PMSG rotor. The MPPT controller starts to operate when theoperate when the
speedof
speed ofthe
thewind
windisis greater
greaterthan
thanthe
the cut
cut in in speed,
speed, and
and itit will
will stop
stop when
when the
the wind
wind speed
speed
surpasses the rated value. The torque (T e ) equation of the permanent magnet
surpasses the rated value. The torque (Te) equation of the permanent magnet synchronous synchronous
generatorisisgiven
generator given by
by [37]
[37]
p
T = −1.5 p λ i + L − L i i ,
Tee = −1.5 2 λMMqiq + ( Ldd − Lqq )didqiq ,
(23)
(23)
2
where p is the number of pole pairs, λM is the magnetic flux produced by the permanent
where
magnetsp isinthe
thenumber
PMSGof poleand
rotor, pairs, λM is the quantities
remaining magnetic flux
holdproduced
the sameby the permanent
definition except
magnets
that these quantities belong to the PMSG. The electromagnetic torque Te can beexcept
in the PMSG rotor, and remaining quantities hold the same definition that
controlled
these quantities belong to the PMSG. The electromagnetic torque Te can be controlled in-
dependently by q-axis current iq alone by assuming that the d-axis current id is equal to
zero. Thus, the torque expression will be simplified to
p
Te = −1.5 λM iq .
2
(24)
Energies 2022, 15, 4824 8 of 18
independently by q-axis current iq alone by assuming that the d-axis current id is equal to
zero. Thus, the torque expression will be simplified to
p
Te = −1.5 λ M iq . (24)
2
It is clear from (24) that torque can be controlled solely by iq . The control structure
of the MSC is derived from the voltage–current equation and torque equation as shown
in Figure 5. Reference torque is calculated from optimal speed of rotation. Iqref can be
calculated from reference torque which is kept to an optimum value. The error signals
Energies 2022, 15, x FOR PEER REVIEW
are
9 of 19
generated by comparing actual currents with the reference values. Error signal through PI
of the controller gives d-axis and q-axis reference rotor voltages (Vdref and Vqref ). Reference
phase voltages in the abc frame will be obtained by converting dq0 voltages. With the use of
these signals in the abc frame and PWM, switching pulses of the MSC are then generated.
Teref = Koptωr 2 ; if ωr < ωr rated , (25)
Extraction of optimal wind power delivers the needed torque or power reference, which is
given by
where
Tere f = Kopt ωr 2 ; if ωr < ωr rated , (25)
0.5 ρπ R 5CPmaxωtB2
where K opt =
0.5ρπRλ5 C
3 2
opt S B
Pmax ωtB
Kopt =
λ3opt SB
(a)
(b)
Figure
Figure5.5.(a)
(a)q-axis
q-axiscontrol
controlblock;
block;(b)
(b)d-axis
d-axiscontrol
controlblock
blockof
ofMSC.
MSC.
Here,ωωtBtBand
Here, andSSB Bare
arethe
thebase
basespeed
speedand andthe thebase basepower
powerofofthe
thewind
windturbine,
turbine,respec-
respec-
tively. CCPmax
tively. Pmaxisis the
the maximum
maximum value
value ofofCC
P,P , the
the wind
wind turbine’s
turbine’s coefficient
coefficient of
of performance,
performance,
whichisisobtained
which obtained when
when pitch
pitch angle
angle (β) 0◦ ;λλoptoptisisthe
(β)==0°; thetip
tipspeed
speedratio whenCC
ratiowhen P =
PC CPmax
=Pmax . .
3.2.2.Controllers
3.2.2. Controllersininthe
theGSC
GSC
The GSC
The GSC of
of the
the wind
windfarm
farmwith
withthe PMSG
the PMSG is the same
is the as the
same as wind farmfarm
the wind with with
the DFIG.
the
The control strategy, as illustrated in Figure 4, and the equations to model the controller
DFIG. The control strategy, as illustrated in Figure 4, and the equations to model the con- are
also the
troller aresame.
also the same.
3.2.3. Pitch Angle Control
3.2.3. Pitch Angle Control
If the speed of the wind exceeds its rated value, a mechanical method is used to protect
If the speed of the wind exceeds its rated value, a mechanical method is used to pro-
the blade from being damaged by controlling blade angle. For wind speed below the
tect the blade from being damaged by controlling blade angle. For wind speed below the
rated value, the maximum power point tracking technique is implemented such that the
rated value, the maximum power point tracking technique is implemented such that the
maximum amount of power can be extracted from wind velocity. If the wind speed is very
maximum amount of power can be extracted from wind velocity. If the wind speed is very
high (more than the rated velocity), the power extraction is limited by pitch angle control.
high (more than the rated velocity), the power extraction is limited by pitch angle control.
This is achieved by turning the blades away from the wind.
This is achieved by turning the blades away from the wind.
3.3.2. A
Controllers in thenext
VSC is present VSCto the DC–DC chopper circuit which converts DC voltage to 3-
phase AC. VSC
A VSC controllers
is present next toaim thetoDC–DC
maintain DC-link
chopper voltage
circuit which as aconverts
constantDC value and to
voltage to
3-phase
regulateAC. theVSC flowcontrollers
of reactiveaim andto active
maintain DC-link
power voltage
between theasgrida constant value and
and inverters to
inde-
regulate
pendently. the Theflowsame
of reactive
control and active power
strategy as in Figurebetween
4 is the grid and inverters
implemented independently.
for the GSC. The equa-
The
tionssame control
to model thestrategy
controller as inareFigure 4 is implemented
also identical to (19)–(22). forKeeping
the GSC.the The equations
reactive to
power
model
reference the tocontroller are also
zero is also identical
followed heretosuch
(19)–(22). Keeping
that the powerthe reactive
injected power
into reference
the grid to
is main-
zero
tained is also followed
at unity power here such that the power injected into the grid is maintained at unity
factor.
power factor.
3.4. Proposed Controllers
3.4. Proposed Controllers
The integration of hybrid renewable energy sources to the grid is increasing in ca-
The
pacity and integration of hybrid
also affects renewable
the stability of theenergy sources
system. to the grid
However, is increasing
if the in capacity
injected power (both
and
active also
andaffects the stability
reactive) of the tactically
is controlled system. However,
during a if the injected
small durationpower of time(both active and
of disturbance
reactive)
(such as is controlled
a fault), system tactically
stability during
can bea enhanced.
small duration of timemagnitude
Bus voltage of disturbance will (such
decreaseas
a fault), system stability can be enhanced. Bus voltage magnitude will decrease during a
during a fault. Injection of reactive power helps to improve the voltage profile and hence
fault. Injection of reactive power helps to improve the voltage profile and hence improves
improves system stability.
system stability.
Here, the controllers of the VSC in solar PVs and the GSC in both the DFIG and the
Here, the controllers of the VSC in solar PVs and the GSC in both the DFIG and the
PMSG are adjusted in a way so that both the RES inject maximum available reactive power
PMSG are adjusted in a way so that both the RES inject maximum available reactive power
throughout fault duration to achieve the enhancement in stability. This automated control
throughout fault duration to achieve the enhancement in stability. This automated control
of converters is termed as Automatic Reactive-power Support (ARS) in this paper. The
of converters is termed as Automatic Reactive-power Support (ARS) in this paper. The
procedure of ARS is the same for the VSC of solar PVs and the GSC of both DFIGs and
procedure of ARS is the same for the VSC of solar PVs and the GSC of both DFIGs and
PMSGs. Reactive power injected into the grid will be zero when there is no disturbance in
PMSGs. Reactive power injected into the grid will be zero when there is no disturbance in
the system. In contrast, during fault periods maximum available reactive power is injected
the system. In contrast, during fault periods maximum available reactive power is injected
to grid. This is achieved by changing the reference value of q-axis current to the maximum
to grid. This is achieved by changing the reference value of q-axis current to the maximum
available current
available current (i.e.,
(i.e., IIqref ==Idrated) and
Idrated ) andIdref I= 0. =
This
0. modification
This modification in the incontroller is shown
the controller is
qref dref
in Figure 6. The first block in Figure 6 is the switch, which
shown in Figure 6. The first block in Figure 6 is the switch, which has three inputs andhas three inputs and one output.
Theoutput.
one detection The ofdetection
faults is carried
of faults outis by comparing
carried out by the RMS voltage
comparing the RMS of the bus (in
voltage ofpu)
the with
bus
0.6pu. If V rms ≤ 0.6, then the switch gives Iqref = Idrated as output, otherwise the switch gives
(in pu) with 0.6pu. If Vrms ≤ 0.6, then the switch gives Iqref = Idrated as output, otherwise
Iqref switch
the = 0 as output.
gives IqrefThe= combined
0 as output. effect
Theimproves
combinedterminal voltage and
effect improves hencevoltage
terminal ensuresand sta-
bility enhancement. The real power injected will be zero
hence ensures stability enhancement. The real power injected will be zero in the case ofin the case of solar systems and
PMSG-based
solar systems and windPMSG-based
farms since wind these farms
systems arethese
since connected
systems to the grid through
are connected back-to-
to the grid
back converters,
through back-to-back whereas in thewhereas
converters, DFIG-based in thewind farm the
DFIG-based wind realfarm
power transferred
the real power
through thethrough
transferred back-to-back converter only
the back-to-back kept toonly
converter zero kept
to achieve
to zero thetoproposed
achieve themodification
proposed
in the controller.
modification in the controller.
Figure6.6.Proposed
Figure Proposedcontroller
controller(ARS)
(ARS)for theq-axis
forthe q-axiscontrol
controlblock.
block.
4.1.WSCC
4.1. WSCC9-Bus 9-BusTest
TestSystem
System
Thesystem
The system under
under study,
study,WSCC
WSCC9-bus,9-bus,isisshown
shownin inFigure
Figure77withwithrenewable
renewableenergyenergy
sources (RES). An additional load is also connected at bus 8. Additional
sources (RES). An additional load is also connected at bus 8. Additional load is used to load is used to
nullify effects
nullify effects on the initial
initial state
stateofofthe
thesystem.
system.The The total power
total power from
from RES injected
RES injectedintointo
the
system
the systemis 80 MW.
is 80 MW. However,
However,for forboth
boththe
thecombinations
combinationsof of RES,
RES, itit is considered
considered thatthat the
the
powerinjected
power injected through
through thethe wind
wind farm
farm isis 60
60MW,
MW,and and20 20MW
MWpowerpowerisisinjected
injectedthrough
through
the
thesolar
solar PV
PV farm so that the the total
totalinjected
injectedpower
powerintointothe
thesystem
systemwould wouldremain
remain 8080 MWMW to
to make
make theresults
the resultscomparable.
comparable.AA3-phase3-phasefaultfaultisiscreated
createdatat bus
bus 55 and the rotor
rotor angle
angle of of
both
bothgenerators
generatorsisisobserved.
observed. Study
Study of the system
of the waswas
system carried out inout
carried twoinsteps
two and
stepsinvolved
and in-
constant power injection
volved constant with the with
power injection assumption that windthat
the assumption speed
wind and solarand
speed irradiation were
solar irradia-
constant
tion were with time, and
constant withthe injection
time, and theof varying
injectionpower whilepower
of varying considering
while that wind speed
considering that
and
wind solar
speedirradiation
and solarchanges withchanges
irradiation time. with time.
Figure7.7.WSCC
Figure WSCC3-machine
3-machine9-bus
9-bussystem
systemconnected
connectedwith
withRES
RESatatbus
bus8.8.
4.1.1.
4.2. 9-Bus
9-Bus Test Test System
System withwith Constant
Constant PowerPower Injection
Injection
Initially, the
Initially, the wind
wind speed
speed isisconsidered
consideredasas13.95 m/s
13.95 m/sandandthe the
solar irradiation
solar as 1000
irradiation as
W/m 2
2. A 3-phase fault is created at 0.2 s and cleared after 431 ms.
1000 W/m . A 3-phase fault is created at 0.2 s and cleared after 431 ms. Rotor angle of Rotor angle of generator-
2 is shown here
generator-2 in Figure
is shown here8a inwith and8awithout
Figure with and different
without RES. FigureRES.
different 8a shows
Figurethat
8astability
shows
is improved
that stability iswith the power
improved withinjection
the power of injection
RES withofconventional control when
RES with conventional compared
control when
to the system
compared to thewithout
systemRES. RotorRES.
without angle variations
Rotor of generator-2
angle variations with ARSwith
of generator-2 are shown
ARS arein
Figure in
shown 8bFigure
when the fault isthe
8b when created at created
fault is 0.2 s andatcleared
0.2 s andafter 484 ms,
cleared since
after 484the
ms,lowest
sinceCCT
the
of generator-2
lowest is 483 ms (when
CCT of generator-2 is 483connected
ms (when with a DFIG
connected wind
with farm wind
a DFIG becausefarmof because
low powerof
rating
low powerof back-to-back converters).converters).
rating of back-to-back The system The voltage profile
system at busprofile
voltage 8 when at connected
bus 8 when to
connected to different
different types of RES types of RESinis Figure
is shown shown 9inforFigure
both9 conventional
for both conventional and proposed
and proposed control
control
techniquestechniques
with the with
faultthe fault duration
duration of 440
of 440 ms. It isms. It is
clear clear
from from 9a–e
Figure Figure 9a–e
that thethat the
voltage
profile is improved with the proposed control technique. The improvement in the voltage
profile caused by the fault is because of the reactive power supply during the time period
of the fault and hence improves the CCT of the system.
Energies 2022, 15, 4824 11 of 18
Energies 2022,
2022, 15,
15, xx FOR
FOR PEER
voltage profile is improved with the proposed control technique. The improvement12inofthe
PEER REVIEW
REVIEW 19
Energies voltage 12 of
profile caused by the fault is because of the reactive power supply during the 19
time
period of the fault and hence improves the CCT of the system.
(a)
(a) (b)
(b)
Figure 8. Variations in
Variations in rotor
in rotor angle
rotor angle (δ
angle (δ 21) with: (a) conventional control and (b) proposed control (ARS)
(δ21
Figure 8.
Figure 8.Variations 21))with:
with:(a)
(a)conventional
conventionalcontrol
controland
and(b)
(b)proposed
proposedcontrol
control(ARS)
(ARS)
when
when the fault is at bus 5.
when the fault is at bus 5.
(a)
(a) (b)
(b)
(c)
(c)
(d)
(d) (e)
(e)
Figure 9.
Figure 9. Variations
Variations in
in system
system voltage
voltage at
at bus
bus 88 when
when connected
connected to:
to: (a)
(a) aa wind
wind farm
farm with
with aa DFIG;
DFIG; (b)
(b)
Figure
a wind 9. Variations
farm with a in system
PMSG; (c) voltage
a solar at bus
PV 8 when
farm; (d) a connected to:
combination (a)a awind
of windfarm
farmwith
withaaDFIG
DFIG;and
(b) aa
a wind farm with a PMSG; (c) a solar PV farm; (d) a combination of a wind farm with a DFIG and a
windPV
solar farm with
farm; a PMSG;
and (c) a solar PV
(e) aa combination
combination of aafarm;
wind(d) a combination
farm DFIGofand
with aa DFIG a wind
and farm
PVwith
farm.a DFIG and a
solar PV farm; and (e) of wind farm with aa solar
solar PV farm.
solar PV farm; and (e) a combination of a wind farm with a DFIG and a solar PV farm.
The reactive
The reactive power
power support
support given
given byby the
the DFIG
DFIG wind
wind farm
farm during
during the
the fault
fault period
period is
is
less compared to the PMSG wind farm with proposed control because of the low
less compared to the PMSG wind farm with proposed control because of the low rating of rating of
the DFIG
the DFIG grid-side
grid-side converter
converter which
which is
is shown
shown inin Figure
Figure 10.
10. Figure
Figure 10
10 clarifies
clarifies that
that the
the re-
re-
active power supplied to the system during fault is larger when the combination
active power supplied to the system during fault is larger when the combination of the of the
Energies 2022, 15, 4824 12 of 18
Energies 2022, 15, x FOR PEER REVIEW The reactive power support given by the DFIG wind farm during the fault period is
13 of 19
less compared to the PMSG wind farm with proposed control because of the low rating
of the DFIG grid-side converter which is shown in Figure 10. Figure 10 clarifies that the
reactive power supplied to the system during fault is larger when the combination of the
PMSG
PMSG wind
wind farm
farm and
and solar
solar PVs
PVs is connected to
is connected to the system since
the system since the rating of
the rating of converters
converters
connected
connected to
to the
the RES
RES are the same
are the same as
as the
the rating
rating of
of the
the RES.
RES.
CCT of of generator-2
generator-2(δ(δ2121))with
withno
norenewable
renewable source is 430
source ms.ms.
is 430 CCT values
CCT of generator-2
values of genera-
for different
tor-2 renewable
for different sources
renewable withwith
sources conventional
conventionaland and
proposed
proposedcontrol techniques
control techniquesare
tabulated
are in Table
tabulated 1. Hybrid
in Table renewable
1. Hybrid sources
renewable (the combination
sources (the combinationof theofDFIG wind wind
the DFIG farm
and solar
farm and PVs)
solargive
PVs)a give
CCT aofCCT465 ms
of with thewith
465 ms conventional control which
the conventional is an
control improvement
which is an im-
of 35 ms, whereas the hybrid renewable source (PMSG wind
provement of 35 ms, whereas the hybrid renewable source (PMSG wind farm and farm and solar PV) gives
solara
CCT of 551 ms with the proposed control, an improvement of 121
PV) gives a CCT of 551 ms with the proposed control, an improvement of 121 ms com-ms compared to when
no renewable
pared to whensource (No RES)
no renewable is connected.
source (No RES)Itisisconnected.
clear fromItTable 1 that
is clear fromtheTable
improvement
1 that the
in CCT is better when the combination of PMSG wind farm
improvement in CCT is better when the combination of PMSG wind farm and and solar PVs is connected
solar PVsto
the
is system with
connected proposed
to the control
system with ARS when
proposed compared
control ARS when to remaining
comparedcases.
to remaining cases.
1. CCT
Table 1.
Table CCTofofgenerator-2
generator-2with
withconventional and
conventional proposed
and control
proposed when
control connected
when to different
connected RES.
to different
RES.
CCT of δ21 in ms
Type of RES Connected
Conventional ControlCCT of δ21 in Control
Proposed ms Improvement
Type of RES Connected
No RES 1 Conventional Control Proposed
430 Control Improvement
No RES 1 430
DFIG 463 483 20
DFIG 463 483 20
PMSG 453 533 80
PMSG 453 533 80
Solar PV 458 544 86
Solar PV 458 544 86
DFIGand
DFIG and Solar
Solar PV
PV 465
465 500
500 35
35
PMSG and Solar PV
PMSG and Solar PV 452
452 551
551 99
99
11 No RESrepresents
No RES representsthethe system
system without
without any renewable
any renewable energy energy
source. source.
4.3. 9-Bus
4.1.2. 9-Bus Test System
Test Systemwith Variable
with Power
Variable Injection
Power Injection
The profiles
The profiles of
of both
both wind
wind speed
speed and
and solar
solar irradiation
irradiation areare shown
shown in in Figure
Figure 11. Four
11. Four
different instances
different instances ofof time,
time, namely
namely A–D,
A–D, are
are considered
considered here here toto support
support different
different combi-
combi-
nations of
nations of variations
variations inin both
both wind
wind speed
speed and
and solar
solar irradiation
irradiation suchsuch that
that one
one profile
profile isis in
in aa
positive slope and the other is in a negative slope, or vice versa, or one
positive slope and the other is in a negative slope, or vice versa, or one profile is in local profile is in local
minimum and
minimum and the other is
the other is with
with some
some slope.
slope. The
The fault
fault instants
instants (time
(time instants)
instants) are
are simulated
simulated
by creating the fault at that particular time instant, and these fault instants
by creating the fault at that particular time instant, and these fault instants represent time represent time
along the profiles of wind speed and solar irradiation at which the fault
along the profiles of wind speed and solar irradiation at which the fault was created in the was created in
the system
system for for study.
study. ForForthethe case
case of of fault
fault instant
instant ‘C’,‘C’,the
thefault
faultisiscreated
createdatat4040 ss with
with wind
wind
speed 15.8 m/s and solar irradiation 800 W/m 2 , which can also be seen in Figure 11. CCT
speed 15.8 m/s and solar irradiation 800 W/m , which can also be seen in Figure 11. CCT
2
values of generator-2 for different RES and with variable power injection into the system
for both conventional and proposed control techniques are tabulated in Table 2 with faults
Energies 2022, 15, 4824 13 of 18
Moreover, Table 1 specifically shows the CCT of generator-2 when the system is
connected to RES and the power injected by the RES is maintained at a constant throughout
4.2.
the IEEE
study. 68-Bus
Table Test
2 shows theSystem
same CCT with power injected into the system varying with
respect to time. Therefore, the CCT values of particular renewable energy sources are
The
different system
in Tables under
1 and 2. study, IEE 16-machine 68-bus, is shown in Figure 12. A
source is connected at different buses considering five different zones [24
4.4. IEEE 68-Bus Test System
power from RES injected into the system is 400 MW. However, for both com
The system under study, IEE 16-machine 68-bus, is shown in Figure 12. A renewable
RES, it is considered as 300 MW through the wind farm and 100MW throu
source is connected at different buses considering five different zones [24]. The total power
farm
from RESininjected
order into
to make the isresults
the system 400 MW.comparable. Thecombinations
However, for both buses in the different
of RES, it is zone
lows: as 300 MW through the wind farm and 100MW through the solar farm in order
considered
to make the results comparable. The buses in the different zones are as follows:
Zone-I: {4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 54, 55}.
Zone-I: {4, 5, 6, 7, 8, 9, 10, 11, 12, 13, 14, 54, 55}.
Zone-II:Zone-II:
{1, 2, 3, 17,{1,
18,2,25,
3,26,
17,27,18,
28,25, 26,60,
29, 53, 27,61}.
28,
29, 53, 60, 61}.
Figure
Figure 12. 12. Single
Single line diagram
line diagram of IEEE 16-machine
of IEEE 16-machine 68-bus system68-bus
[24]. system [24].
better in the combination of wind farm with PMSG and solar PV when compared to other
RES, due to the low power rating of back-to-back converters in the wind farm with a16DFIG.
Energies 2022, 15, x FOR PEER REVIEW of 19
Thus, the reactive power support given by the wind farm with a DFIG is low during fault
periods when compared to either the wind farm with a PMSG or the solar PV farm.
(a) (b)
Figure 13.
Figure 13. Variations
Variations in
in rotor
rotorangle
anglewhen
whenthe
thefault
faultisisatatbus
bus5353
with: (a)(a)
with: conventional control
conventional andand
control (b)
proposed control (ARS).
(b) proposed control (ARS).
Table3.
Table 3. CCT
CCT with
with conventional
conventionaland
andproposed
proposedcontrol
controlwhen
whenconnected
connectedto
todifferent
differentRES.
RES.
5. Conclusions
The analysis of the transient stability of a MMS with different types of renewable
energy sources is presented here with a simple control technique to enhance system stability
with and without considering the presence of various RES and the combination of those
sources. Both the doubly fed induction generator (DFIG) and the permanent magnet syn-
chronous generator (PMSG) are considered as wind generators. Enhancement of transient
stability is carried out by improving critical clearing time of faults in the system. Using a
simple control of reactive and active powers during faults improved system stability as
well as voltage profile. This study is carried out on both a 9-bus WSCC test system and a
68-bus IEEE test system by creating a 3-phase fault at different buses as well as different
time instants. Results are compared for several cases which includes the system with a
DFIG as a wind generator, a PMSG as a wind generator, a solar PV farm, the combination
of a DFIG as a wind generator and solar PVs, and the combination of a PMSG as a wind
generator and solar PVs as well as the system without any renewable source. Additionally,
results are compared for all these combinations with conventional control and proposed
control ARS. It is observed from the findings discussed in the paper that the combination of
wind power with a PMSG and solar PVs connected to the system improves system stability
with the proposed control technique when compared to a system connected to the other
types of RES and also to the conventional control. It is also observed from the results that
the improvement in system stability is better in regards to variable power injection when
the combination of wind power with a PMSG and solar PVs is connected to the system.
Author Contributions: Conceptualization, A.A. and A.M.; methodology and validation, A.A., A.M.
and S.S.B.; writing—original draft preparation, A.A.; writing—review and editing, A.M., S.S.B., D.Z.
and P.S.; supervision, S.S.B., A.M. and P.S. All authors have read and agreed to the published version
of the manuscript.
Funding: This research received no external funding.
Institutional Review Board Statement: Not applicable.
Informed Consent Statement: Not applicable.
Data Availability Statement: Not applicable.
Conflicts of Interest: The authors declare no conflict of interest.
Energies 2022, 15, 4824 17 of 18
References
1. Kroposki, B.; Johnson, B.; Zhang, Y.; Gevorgian, V.; Denholm, P.; Hodge, B.-M.; Hannegan, B. Achieving a 100% renewable grid:
Operating electric power systems with extremely high levels of variable renewable energy. IEEE Power Energy Mag. 2017, 15,
61–73. [CrossRef]
2. Hansen, L.H.; Helle, L.; Blaabjerg, F.; Ritchie, E.; Munk-Nielsen, S.; Bindner, H.; Soerensen, P.; Bak-Jensen, B. Conceptual Survey of
Generators and Power Electronics for Wind Turbines; Risø-R-1205; Risø National Laboratory: Roskilde, Denmark, 2001.
3. Chakraborty, S.; Kramer, B.; Kroposki, B. A review of power electronics interfaces for distributed energy systems towards
achieving low-cost modular design. Renew. Sustain. Energy Rev. 2009, 13, 2323–2335. [CrossRef]
4. Du, E.; Zhang, N.; Kang, C.; Xia, Q. A High-efficiency network-constrained clustered unit commitment model for power system
planning studies. IEEE Trans. Power Syst. 2019, 34, 2498–2508. [CrossRef]
5. Hou, Q.; Du, E.; Zhang, N.; Kang, C. Impact of high renewable penetration on the power system operation mode: A data-driven
approach. IEEE Trans. Power Syst. 2020, 35, 731–741. [CrossRef]
6. Bekele, G.; Boneya, G. Design of a Photovoltaic-Wind Hybrid Power Generation System for Ethiopian Remote Area. Ph.D. Thesis,
Addis Ababa University, Addis Ababa, Ethiopia, 2011.
7. Patel, H.; Agarwal, V. Matlab based modeling to study the effect of partial shading on PV array characteristics. IEEE Trans. Energy
Convers. 2008, 23, 302–310. [CrossRef]
8. Abdulazeez, M.; Iskender, I. Simulation and Experimental Study of Shading Effect on Series and Parallel Connected PV Modules. In
Proceedings of the 2011 7th International Conference on Electrical and Electronics Engineering, Bursa, Turkey, 1–4 December 2011.
9. SiyuGuo, T.M.W.; Walsh, T.M. Analyzing Partial Shading of PV Module by Circuit Modeling. In Proceedings of the 2012 38th
IEEE Photovoltaic Specialists Conference, Austin, TX, USA, 3–8 June 2012.
10. Xuesong, Z.; Daichun, S.; Youjie, M.; Deshu, C. The Simulation and Design for MPPT of PV System Based on Incremental
Conductance Method. In Proceedings of the 2010 WASE International Conference on Information Engineering, Beidai, China,
14–15 August 2010.
11. Safari, A.; Mekhilef, S. Simulation and hardware implementation of incremental conductance MPPT with direct control method
using cuk converter. IEEE Trans. Ind. Electron. 2011, 58, 1154–1161. [CrossRef]
12. Rosu-Hamzescu, M.; Oprea, S. Practical Guide to Implementing Solar Panel MPPT Algorithm; Microchip Technology Inc.: Chandler,
AZ, USA, 2013.
13. Palmieri, A.; Rosini, A.; Procopio, R.; Bonfiglio, A. An MPC-sliding mode cascaded control architecture for PV grid-feeding
inverters. Energies 2020, 13, 2326. [CrossRef]
14. Feshara, H.F.; Ibrahim, A.M.; El-Amary, N.H.; Sharaf, S.M. Performance evaluation of variable structure controller based on
sliding mode technique for a grid-connected solar network. IEEE Access 2019, 7, 84349–84359. [CrossRef]
15. Taftichat, T.; Agbossou, K. Output power Maximization of a Permanent Magnet Synchronous Generator Based Stand-Alone Wind
Turbine System. In Proceedings of the 2006 IEEE International Symposium on Industrial Electronics, Montreal, QC, Canada, 9–13
July 2006.
16. Gules, R.; Pacheco, J.D.P.; Hey, H.L.; Imhoff, J. Maximum power point tracking system with Parallel connection for PV stand-alone
application. IEEE Trans. Ind. Electron. 2008, 55, 2674–2683. [CrossRef]
17. Rahmani, S.; Hamadi, A.; Ndtoungou, A.; Al-Haddad, K.; Kanaan, H.Y. Performance Evaluation of a PMSG-Based Variable Speed
Wind Generation System Using Maximum Power Point Tracking. In Proceedings of the 2012 IEEE Electrical Power and Energy
Conference, London, ON, Canada, 10–12 October 2012.
18. Jamil, M.; Gupta, R.; Singh, M. A Review of Power Converter Topology Used with PMSG Based Wind Power Generation. In
Proceedings of the 2012 IEEE 5th Power India Conference, Murthal, India, 19–22 December 2012.
19. Koutroulis, E.; Kalaitzakis, K. Design of a maximum power tracking system for wind-energy conversion application. IEEE Trans.
Ind. Electron. 2006, 53, 486–494. [CrossRef]
20. Ahuja, H.; Bhuvaneswari, G.; Balasubramanian, R. Performance Comparison of DFIG and PMSG Based WECS. In Proceedings of
the IET Conference on Renewable Power Generation (RPG 2011), Edinburgh, UK, 6–8 September 2011; pp. 1–6.
21. Fandi, G.; Igbinovia, F.O.; Ahmad, I.; Svec, J.; Muller, Z. Modeling and Simulation of a Gearless Variable Speed Wind Turbine
System With PMSG. In Proceedings of the 2017 IEEE PES PowerAfrica, Accra, Ghana, 27–30 June 2017; pp. 59–64.
22. Wang, L.; Truong, D.-N. Stability enhancement of a power system with a PMSG-based and a DFIG-based offshore wind farm
using a SVC with an adaptive-network-based fuzzy inference system. IEEE Trans. Ind. Electron. 2013, 60, 2799–2807. [CrossRef]
23. Ngom, I.; Mboup, A.B.; Thiaw, L.; Mustapha, S.S.; Slama-Belkhodja, I. Improved Control for DC-Link Fluctuation during Voltage
Dip Based on DFIG. In Proceedings of the 2018 9th International Renewable Energy Congress (IREC), Hammamet, Tunisia, 20–22
March 2018; pp. 1–6.
24. Mitra, A.; Chatterjee, D. Active power control of DFIG-based wind farm for improvement of transient stability of power systems.
IEEE Trans. Power Syst. 2016, 31, 82–93. [CrossRef]
25. Mitra, A.; Chatterjee, D. A sensitivity-based approach to assess the impacts of integration of variable speed wind farms on the
transient stability of power systems. Renew. Energy 2013, 60, 662–671. [CrossRef]
26. Zhou, T.; Francois, B. Energy management and power control of a hybrid active wind generator for distributed power generation
and grid integration. IEEE Trans. Ind. Electron. 2011, 58, 95–104. [CrossRef]
Energies 2022, 15, 4824 18 of 18
27. Ropp, M.; Gonzalez, S. Development of a MATLAB/simulink model of a single-phase grid-connected photovoltaic system. IEEE
Trans. Energy Convers. 2009, 24, 195–202. [CrossRef]
28. Ku, T.-T.; Lin, C.-H.; Hsu, C.-T.; Chen, C.-S.; Liao, Z.-Y.; Wang, S.-D.; Chen, F.-F. Enhancement of power system operation by
renewable ancillary service. IEEE Trans. Ind. Appl. 2020, 56, 6150–6157. [CrossRef]
29. Hirose, T.; Matsuo, H. Standalone hybrid wind-solar power generation system applying dump power control without dump load.
IEEE Trans. Ind. Electron. 2012, 59, 988–997. [CrossRef]
30. Sowa, P.; Zychma, D. Dynamic equivalents in power system studies: A review. Energies 2022, 15, 1396. [CrossRef]
31. Olulope, P.K.; Folly, K.A.; Venayagamoorthy, G.K. Modeling and Simulation of Hybrid Distributed Generation and Its Impact on
Transient Stability of Power System. In Proceedings of the 2013 IEEE International Conference on Industrial Technology (ICIT),
Cape Town, South Africa, 25–28 February 2013; pp. 1757–1762.
32. Ghanasyam, P.; Verma, A.; Mitra, A. Impact of Hybrid Renewable Sources on the Transient Stability of Multi-Machine Power
System. In Proceedings of the IEEE International Conference on Power Electronics, Drives and Energy Systems (PEDES), Chennai,
India, 18–21 December 2018; pp. 1–5. [CrossRef]
33. Machowski, J.; Lubosny, Z.; Bialek, J.W.; Bumby, J.R. Power System Dynamics: Stability and Control; John Wiley & Sons: New York,
NY, USA, 2020.
34. Kundur, P. Power System Stability and Control; McGraw-Hill: New York, NY, USA, 1994.
35. Pal, B.; Mei, F. Modelling adequacy of the doubly fed induction generator for small-signal stability studies in power systems.
IET Renew. Power Gener. 2008, 2, 181–190. [CrossRef]
36. Yang, S.; Zhang, L. Modeling and Control of the PMSG Wind Generation System with a Novel Controller. In Proceedings of
the 2013 Third International Conference on Intelligent System Design and Engineering Applications, Hong Kong, China, 16–18
January 2013; pp. 946–949.
37. Kurian, S.; Sindhu, T.K.; Cheriyan, E.P. Modelling and Simulation of Direct Driven Wind Electric Generator for Grid Integration.
In Proceedings of the 2012 Annual IEEE India Conference (INDICON), Kochi, India, 7–9 December 2012; pp. 171–174.
38. Mai, T.; Hand, M.M.; Baldwin, S.F.; Wiser, R.H.; Brinkman, G.L.; Denholm, P.; Arent, D.J.; Porro, G.; Sandor, D.; Hostick, D.J.; et al.
Renewable electricity futures for the United States. IEEE Trans. Sustain. Energy 2014, 5, 372–378. [CrossRef]
39. Hashimoto, J.; Ustun, T.S.; Suzuki, M.; Sugahara, S.; Hasegawa, M.; Otani, K. Advanced grid integration test platform for
increased distributed renewable energy penetration in smart grids. IEEE Access 2021, 9, 34040–34053. [CrossRef]