1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

A A
SI DG EA
Main Cover Sheet
KPTCL LOI Ref: No. CEE/ T&P/SEE-2/KCO-150/43160/2022-23/7918-31 Dtd.07.07.2022.

Work A:Up-gradation of 2x5MVA, 33/11kV Sub-station at Nehru Maidan to 1x20 MVA, 110/
33kV & 2x 10 MVA, 110/11KV GIS Sub-Station and running of 110kV, 1Cx 630 sq.mm. XLPE UG
cable SC Line for a route length of 3.405 kms from existing 110kV Bejai Sub-Station to the
B proposed 110/33/11kV Nehru Maidan GIS sub-station along with construction of one number of B
110kV Terminal bay at existing 110kV Bejai sub-station in Mangaluru Taluk ,Dakshina kannada
district.

Work B:Construction of 110kV SC line by 630sqmm XLPE single core UG Cable in RCC duct, from
Loc .No.1 of 220kv Varahi-kavoor DC line to the new 110kV Bay inside the premises of 220kV
SRS Kavoor for a route length of 0.40Km in Mangaluru Taluk , Dakshina kannada District.

-On Total Turnkey Basis including Design ,Testing ,Supply of GIS and UG Cable , Supply of all
equipment's/ Materials including Mandatory spares, Erection (including Civil Works ),of all
C materials / equipment's, Testing & commissioning. C
Last Used by: z004mx4y

Time: 2:06:34 PM
Date: 07/07/2023

End Customer
Karnataka Power Transmission
Corporation Ltd

Consultant
-

D EPC/Contractor D
Sharavathy Conductors Pvt Ltd.
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel 114 01

Project Establishing 110/33/11kV Gas Insulated


Sl. No. Type of Document Document Number Sub-Station at Nehru maidan in Mangaluru
CopyRight (C) Siemens Limited, India All Rights Reserved.

1 Equipment List (4)G719EA-OG9228-03-E114


2 General Arrangement (4)G719EA-OG9228-03-F114
Ref. No.
-
E 3 Internal Layout (4)G719EA-OG9228-03-V114 E
4 Wiring Schematics (4)G719EA-OG9228-03-W114 Substation
220/110kV Substation AT KAVOOR

Title
110kV ADYAAR Line (IDLE) C&R Panel
AUX.SUPPLY:220V DC
Drawing No.
(4)G719EA-OG9228-03-114
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Main Cover Sheet Sub-Station at Nehru maidan in Mangaluru 11401
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. For CRP Sh. 01 of 2
3008052247 (4)G719EA-OG9228-03-114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Main Cover Sheet < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1 Procedure for carrying out Amendments

1. The revision no. of the drawing is changed whenever changes are asked by client.
A A
The revision no. is continuous from 0, A, B, C….. & so on.

2. The version no. of the drawing is changed whenever the drawing is revised whether due to client’s comments, engineering changes,
factory changes, site comments etc. The version no. is continuous from 0, 1, 2, 3….. & so on.

3. The sheets which are changed can be tracked from the sheet “Summary of Amendments”.
The revision no., version no. and the corresponding reason for amendment is reflected on the “Summary of Amendments” sheet.

4. Date format used is MM/DD/YYYY.

B B

C C
Last Used by: z004mx4y

Time: 2:06:48 PM
Date: 12/12/2023

SUMMARY OF AMENDMENTS

Sl. No. Revision Version Remarks Date Drawn By Chkd By

01 0 0 First Submission 05/23/2023 RNG SK

02 A 1 Customer Comments 06/16/2023 RNG SK

D 03 B 2 QT Corrected 12/12/2023 RNG SK D


220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel 114 02

04 -- -- -- -- -- --

05 -- -- - -- -- --

06 -- -- -- -- -- --

07 -- -- -- -- -- --
CopyRight (C) Siemens Limited, India All Rights Reserved.

08 -- -- -- -- -- --

09 -- -- - -- -- --
E E
10 -- -- -- -- -- --

11 -- -- - -- -- --

12 -- -- -- -- -- --

13 -- -- -- -- -- --

14 -- -- -- -- -- --

15 -- -- - -- -- --
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Summary of Amendments Sub-Station at Nehru maidan in Mangaluru 11402
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 02 of 2
3008052247 (4)G719EA-OG9228-03-114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Main Cover Sheet <01 ->
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

A A
SI DG EA
Equipment List

B B

C C
Last Used by: z004mx4y

Time: 2:06:59 PM
Date: 06/26/2023

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 01
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd COVER SHEET Sub-Station at Nehru maidan in Mangaluru E11401
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 01 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
Case Size: 1/1 19”, 4xI, 4xV, 24 BI, 31 BO, 1 Live Status, 14 LED, Flush Mounting
Numerical Relay 7SD52
87L/21 Siemens, India CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 110-250V DC, 115V AC, BI Threshold 88V Boughtout Front Mount 1
Line Differential/Distance Protection 7SD5221-5DB99-9HK4+L0R+M0H+N7H
IEC61850, Electrical EN100, Double, RJ45 Connector
Case Size: 1/3 19”, 4xI, 4xV, 16 BI, 7 BO, 1 Live Status, 7 LED, Flush Mounting
Numerical Relay 7SJ66
67/67N Siemens, India CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 110-250V DC, 115-230V AC, BI Threshold 88V Boughtout Front Mount 1
Backup Protection 7SJ6611-5DB90-1FC0+L0R
IEC 61850, 100 Mbit Ethernet, Electrical, Double, RJ45 Connector
Windows: 28, Window Size: 50x35mm, Configuration: 7Cx4R, Normal Supply: 220V DC
Annunciation MCAN02
FC Bharani, India Trip Facia: Red, Nontrip Facia: Yellow, Seq.: MR-02, With Standby Supply Operation:240V AC Boughtout Front Mount 1
Annunciator MCAN02
DC Fail In Last & AC Fail In Second Last Window
Relay Case With Base, Type: RHGX20
Accessory- Relay, Contactor RHGX
CASE & BASE-1 ABB, India Case Size: 4U 60C Boughtout Front Mount 1
RHGX20-With Case (Flush) 1MYN 560 004-D
B With EPDM Gasket B
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
195 ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
TC-1 Supervision Relay 1MYN 569 339-A

Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
295 ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
TC-2 Supervision Relay 1MYN 569 339-A

Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
80/86A ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
86A Trip Relay Supvn 1MYN 569 339-A

Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
80/86B ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
86B Trip Relay Supvn 1MYN 569 339-A
C C
Last Used by: z004mx4y

Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
80/96 ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
Time: 2:07:10 PM
Date: 12/12/2023

96 Trip Relay Supvn 1MYN 569 339-A

Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
80A ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
DC-1 Supvn Relay 1MYN 569 339-A

Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
80B ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
DC-2 Supvn Relay 1MYN 569 339-A

Aux Voltage: 48V DC, Contacts: 6NO+2NC, H/R or E/R, Flag: Yes
Relay, Contactor RXMVB2
86A ABB, India Case Size: 2U 12C Boughtout Front Mount 1
Trip Relay 1MYN563035-AH
Use With RXTMA Series Resistor
D D
Aux Voltage: 48V DC, Contacts: 6NO+2NC, H/R or E/R, Flag: Yes
Relay, Contactor RXMVB2
86B ABB, India Case Size: 2U 12C Boughtout Front Mount 1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 02

Trip Relay 1MYN563035-AH


Use With RXTMA Series Resistor
Aux Voltage: 48V DC, Contacts: 6NO+2NC, H/R or E/R, Flag: Yes
Relay, Contactor RXMVB2
96 ABB, India Case Size: 2U 12C Boughtout Front Mount 1
LBB Trip Relay 1MYN563035-AH
Use With RXTMA Series Resistor
Aux Voltage: 220-250V DC, Contacts: 6NO, 3NO Per Pole, Flag: No
Relay, Contactor RXMM1
CMRX ABB, India Case Size: 2U 6C Boughtout Front Mount 1
Auxiliary Relay RK 214 003-AS
CopyRight (C) Siemens Limited, India All Rights Reserved.

Aux Voltage: 220-250V DC, Contacts: 2NO+2NC, S/R, Flag: No


Relay, Contactor RXME1
DCCO1 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
DC Changeover Relay RK 221 052-AS

E Aux Voltage: 220-250V DC, Contacts: 2NO+2NC, S/R, Flag: No E


Relay, Contactor RXME1
DCCO2 ABB, India Case Size: 2U 6C Boughtout Front Mount 1
DC Changeover Relay RK 221 052-AS

Contacts: 1NO+1NC
Push Button 3SB5
PB02 Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
Annun.Reset 3SB50 00-0AB01+3SB54 00-0A

Contacts: 1NO+1NC
Push Button 3SB5
PB51 Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
DC-1 FAIL TEST 3SB50 00-0AB01+3SB54 00-0A

Contacts: 1NO+1NC
Push Button 3SB5
PB52 Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
DC-2 FAIL TEST 3SB50 00-0AB01+3SB54 00-0A

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11402
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 02 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <01 03>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
Contacts: 1NO+1NC
Push Button 3SB5
PB53 Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
DC FAIL ACCEPT 3SB50 00-0AB01+3SB54 00-0A

Contacts: 1NO+1NC
Push Button 3SB5
PB86A Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
86 Reset 3SB50 00-0AB01+3SB54 00-0A

Contacts: 1NO+1NC
Push Button 3SB5
PB86B Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
86 Reset 3SB50 00-0AB01+3SB54 00-0A

Contacts: 1NO+1NC
Push Button 3SB5
PB96 Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
96 Reset 3SB50 00-0AB01+3SB54 00-0A
B B
Contacts: 1NO+1NC
Push Button 3SB5
PB01 Siemens, India Actuator Colour: Yellow, Type: With Plastic Front Ring Boughtout Front Mount 1
Annun.Accept 3SB50 00-0AD01+3SB54 00-0A

Contacts: 1NO+1NC
Push Button 3SB5
PB03 Siemens, India Actuator Colour: Green, Type: With Plastic Front Ring Boughtout Front Mount 1
Annun.Test 3SB50 00-0AE01+3SB54 00-0A

Relay Test Block, Type: RTB


Test Block DAV
BLKA Dav, India Boughtout Front Mount 1
Test Block For 87L/21 DAV

Relay Test Block, Type: RTB


Test Block DAV
BLKB Dav, India Boughtout Front Mount 1
Test Block For 87L/21 DAV
C C
Last Used by: z004mx4y

Relay Test Block, Type: RTB


Test Block DAV
BLKC Dav, India Boughtout Front Mount 1
Time: 2:07:20 PM
Date: 12/12/2023

Test Block For 67/67N DAV

Relay Test Block, Type: RTB


Test Block DAV
BLKD Dav, India Boughtout Front Mount 1
Test Block For 67/67N DAV

3 Positions, 12 Ways, Handle Type: Pistol Grip, Black, Spring Return To Neutral With LMD
Switch BC
CS1 Recom, India Non-Lockable, Postions: Trip (T)-Neutral (N)-Close (C), Rating:25A Boughtout Front Mount 1
CB Control Switch BC251P484SIE1A/244LMR
POS1 (-45°): T-4Ways, POS 2 (0°): N-1Ways, (T-AT-2Ways+C-AC-2Ways), POS3 (+45°): C-3Ways
4 Positions, Angle Interval: 90°, Handle Type: Stayput
Switch PCS
VSS Recom, India Positions: OFF-RY-YB-BR, Frequency: 50Hz, Rating: 25A Boughtout Front Mount 1
Selector Switch PCS25P339VM
D D
2 Positions, 10 Ways, Handle Type: Pistol Grip, Stayput
Switch PDS
PTS-1 Recom, India Non-Lockable, Positions: BUS-1 PT-BUS-2 PT, Rating: 25A Boughtout Front Mount 1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 03

Selector Switch PDS25P5104SIE12A/P


POS1 (-450°): BUS-1 PT-5Ways, POS2 (+45°): BUS-2 PT-5Ways
2 Positions, 10 Ways, Handle Type: Pistol Grip, Stayput
Switch PDS
PTS-2 Recom, India Non-Lockable, Positions: BUS-1 PT-BUS-2 PT, Rating: 25A Boughtout Front Mount 1
Selector Switch PDS25P5104SIE12A/P
POS1 (-450°): BUS-1 PT-5Ways, POS2 (+45°): BUS-2 PT-5Ways
2 Positions, 10 Ways, Handle Type: Pistol Grip, Black, Stayput
Switch PDS
LRS Recom, India Lockable, Positions: Local (L)-Remote (R), Rating: 25A Boughtout Front Mount 1
CP/SCADA Selector Switch PDS25P5104SIE37B/L
POS1 (-45°): L-5Ways, POS2 (+45°): R-5Ways
CopyRight (C) Siemens Limited, India All Rights Reserved.

3 Positions, 24 Ways, Handle Type: Pistol Grip, Black, Stayput


Switch PDS
NIT Recom, India Lockable, Positions: Normal (N)-Inter (I)-Transfer (T), Rating: 32A Boughtout Front Mount 1
Selector Switch PDS32P12246SIE43D/L
POS1 (-45°): N-2Ways, POS 2 (0°): I -2Ways (NI-4Ways+IT-14Ways), POS3 (+45°): T-2Ways
E 3P4W, Type: Link, Connection Type: Back E
Test Terminal Block TTB
TTB Dav, India Boughtout Front Mount 1
DAV TTB001

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL02 Siemens, India Compact LED Lamp, Colour: Red Boughtout Front Mount 1
CB CLOSE 3SB5235-6HC14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL07 Siemens, India Compact LED Lamp, Colour: Red Boughtout Front Mount 1
ISO 114-89A CLOSE 3SB5235-6HC14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL09 Siemens, India Compact LED Lamp, Colour: Red Boughtout Front Mount 1
ISO 114-89B CLOSE 3SB5235-6HC14

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11403
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 03 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <02 04>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
Aux Voltage: 42-220V DC, 42-240V AC
Indicating Lamp 3SB5
SL11 Siemens, India Compact LED Lamp, Colour: Red Boughtout Front Mount 1
ISO 114-89D CLOSE 3SB5235-6HC14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL13 Siemens, India Compact LED Lamp, Colour: Red Boughtout Front Mount 1
ESW 114-89DE CLOSE 3SB5235-6HC14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL15 Siemens, India Compact LED Lamp, Colour: Red Boughtout Front Mount 1
ISO 114-89C CLOSE 3SB5235-6HC14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL17 Siemens, India Compact LED Lamp, Colour: Red Boughtout Front Mount 1
ISO 114-89E CLOSE 3SB5235-6HC14
B B
Aux Voltage: 42-220V DC, 42-240V AC
Indicating Lamp 3SB5
SL01 Siemens, India Compact LED Lamp, Colour: Green Boughtout Front Mount 1
CB OPEN 3SB5235-6HE14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL06 Siemens, India Compact LED Lamp, Colour: Green Boughtout Front Mount 1
ISO 114-89A OPEN 3SB5235-6HE14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL08 Siemens, India Compact LED Lamp, Colour: Green Boughtout Front Mount 1
ISO 114-89B OPEN 3SB5235-6HE14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL10 Siemens, India Compact LED Lamp, Colour: Green Boughtout Front Mount 1
ISO 114-89D OPEN 3SB5235-6HE14
C C
Last Used by: z004mx4y

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL12 Siemens, India Compact LED Lamp, Colour: Green Boughtout Front Mount 1
Time: 2:07:29 PM
Date: 12/12/2023

ESW 114-89DE OPEN 3SB5235-6HE14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL14 Siemens, India Compact LED Lamp, Colour: Green Boughtout Front Mount 1
ISO 114-89C OPEN 3SB5235-6HE14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL16 Siemens, India Compact LED Lamp, Colour: Green Boughtout Front Mount 1
ISO 114-89E OPEN 3SB5235-6HE14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL04 Siemens, India Compact LED Lamp, Colour: Blue Boughtout Front Mount 1
CB SPRING CHARGED 3SB5235-6HF14
D D
Aux Voltage: 42-220V DC, 42-240V AC
Indicating Lamp 3SB5
SL05 Siemens, India Compact LED Lamp, Colour: White Boughtout Front Mount 1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 04

TC HEALTHY 3SB5235-6HG14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL52 Siemens, India Compact LED Lamp, Colour: White Boughtout Front Mount 1
DC FAIL INDICATION 3SB5235-6HG14

Aux Voltage: 42-220V DC, 42-240V AC


Indicating Lamp 3SB5
SL03 Siemens, India Compact LED Lamp, Colour: Amber Boughtout Front Mount 1
CB AUTO TRIP 3SB5235-6HL14
CopyRight (C) Siemens Limited, India All Rights Reserved.

Type: Moving Coil, Accuracy: 1, Scale: 0-240°


Meter SQ
A1 AE, India Range: 0-200A & 0-400A, CTR: 400-200/1A Boughtout Front Mount 1
Analogue Ammeter SQ96
Bezel Size: 96x96mm
E Type: Moving Coil, Accuracy: 1, Scale: 0-240° E
Meter SQ
A2 AE, India Range: 0-200A & 0-400A, CTR: 400-200/1A Boughtout Front Mount 1
Analogue Ammeter SQ96
Bezel Size: 96x96mm
Type: Moving Coil, Accuracy: 1, Scale: 0-240°
Meter SQ
A3 AE, India Range: 0-200A & 0-400A, CTR: 400-200/1A Boughtout Front Mount 1
Analogue Ammeter SQ96
Bezel Size: 96x96mm
Type: Moving Iron, Accuracy: 1, Scale: 240°
Meter SQ
V AE, India Range: 0-125kV, PTR: 110kV/√3/110V/√3 Boughtout Front Mount 1
Analogue Voltmeter SQ96
Bezel Size: 96x96mm
3P4W3E, CTR: Configurable, PTR: Configurable, Accuracy: 0.2S
Multi Function Meter Elite
MFM Secure, India Aux Supply: 80-300V DC/AC Boughtout Front Mount 1
Multi Function Meter Elite 445
Port: RS485 With Modbus Protocol

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11404
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 04 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <03 05>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
3P4W, CTR: 400-200/1A, PTR: 110kV/110V, Class: 0.2S, Adopted CTR: 400/1A , EMF For 200/1A
Energy Meter Premier
TVM Secure, India 4 Quadrant Energy Measurement With ABT, TOD & DLMS Complaint, Import & Export Feature Boughtout Front Mount 1
Meter Premier300
Port: RS485 With Modbus, Surface Mounting
Aux Voltage: 220V DC
Resistor RXTMA1
RU-A ABB, India Case Size: 2U 6C, With 4x820Ω 5W Resistors Boughtout Front Mount 1
Resistor Unit for 86A INRK 711 004-AN
Use With RXMVB2 Relay
Aux Voltage: 220V DC
Resistor RXTMA1
RU-B ABB, India Case Size: 2U 6C, With 4x820Ω 5W Resistors Boughtout Front Mount 1
Resistor Unit for 86B INRK 711 004-AN
Use With RXMVB2 Relay
Aux Voltage: 220V DC
Resistor RXTMA1
RU-C ABB, India Case Size: 2U 6C, With 4x820Ω 5W Resistors Boughtout Front Mount 1
Resistor Unit for 96 INRK 711 004-AN
B Use With RXMVB2 Relay B
Model: 06 Fiber LIU, Ports: Multimode, Cable Entries: 1 Nos, Wall Mounting
LIU
LIU Axis Fully Loaded With Adaptors: 6 LC, Pig Tails: 6 LC Multimode 62.5/125µm, 1300nm Boughtout Internal Mount 1
6 Multimode LC Port
With Complete Accessories
Aux Voltage: 230V AC, Contacts: 2NO+2NC
Contactor 3RH21
80C Siemens, India Boughtout Internal Mount 1
3RH21 3RH2122-1AP00

Aux Voltage: 220V DC, Contacts: 2NO+2NC


Contactor 3RH21
95X Siemens, India Boughtout Internal Mount 1
TC Healthy Multiplication 3RH2122-1BM40

Rating: 20A, 240V AC, Switch With Box


Panel Accessory 39992
HTS Anchor, India Boughtout Internal Mount 1
Heater Switch 39992
C C
Last Used by: z004mx4y

Rating: 30-90°C, 240V AC


Panel Accessory TH3090
TH APT Control, India Boughtout Internal Mount 1
Time: 2:07:38 PM
Date: 12/12/2023

Thermostat TH3090240VAC

Solid Link With Holder


Link Holder+Link 3NW
LK91 Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
LK92 Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
LK93 Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL
D D
Solid Link With Holder
Link Holder+Link 3NW
LK-B1C1N Siemens, India Boughtout Internal Mount 1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 05

3NW 3NW20NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
LK-B1C2N Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
LK-B2C1N Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL
CopyRight (C) Siemens Limited, India All Rights Reserved.

Solid Link With Holder


Link Holder+Link 3NW
LK-B2C2N Siemens, India Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNNSL

E Rating: 10A E
Fuse Holder+Fuse 3NW
FS1 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10

Rating: 10A
Fuse Holder+Fuse 3NW
FS15 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10

Rating: 10A
Fuse Holder+Fuse 3NW
FS16 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10

Rating: 10A
Fuse Holder+Fuse 3NW
FS2 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11405
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 05 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <04 06>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
Rating: 10A
Fuse Holder+Fuse 3NW
FS7 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10

Rating: 10A
Fuse Holder+Fuse 3NW
FS8 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10

Rating: 10A
Fuse Holder+Fuse 3NW
FSC Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10

Rating: 16A
Fuse Holder+Fuse 3NW
FS101 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16
B B
Rating: 16A
Fuse Holder+Fuse 3NW
FS102 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16

Rating: 16A
Fuse Holder+Fuse 3NW
FS201 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16

Rating: 16A
Fuse Holder+Fuse 3NW
FS202 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16

Rating: 16A
Fuse Holder+Fuse 3NW
FS91 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16
C C
Last Used by: z004mx4y

Rating: 4A
Fuse Holder+Fuse 3NW
FS13 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
Time: 2:07:48 PM
Date: 12/12/2023

3NW 3NW20NNSF+3NWNS4

Rating: 4A
Fuse Holder+Fuse 3NW
FS14 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4

Rating: 6A
Fuse Holder+Fuse 3NW
FS10 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6

Rating: 6A
Fuse Holder+Fuse 3NW
FS11 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
D D
Rating: 6A
Fuse Holder+Fuse 3NW
FS12 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 06

3NW 3NW20NNSF+3NWNS6

Rating: 6A
Fuse Holder+Fuse 3NW
FS17 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6

Rating: 6A
Fuse Holder+Fuse 3NW
FS18 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
CopyRight (C) Siemens Limited, India All Rights Reserved.

Rating: 6A
Fuse Holder+Fuse 3NW
FS21 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6

E Rating: 6A E
Fuse Holder+Fuse 3NW
FS22 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6

Rating: 6A
Fuse Holder+Fuse 3NW
FS3 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6

Rating: 6A
Fuse Holder+Fuse 3NW
FS4 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6

Rating: 6A
Fuse Holder+Fuse 3NW
FS5 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11406
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 06 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <05 07>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
Rating: 6A
Fuse Holder+Fuse 3NW
FS6 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6

Rating: 6A
Fuse Holder+Fuse 3NW
FS9 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6

Rating: 6A
Fuse Holder+Fuse 3NW
FS92 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6

Rating: 6A
Fuse Holder+Fuse 3NW
FS93 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
B B
Solid Link With Holder
Link Holder+Link 3NW
ETL1 Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
ETL2 Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
ETL7 Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
LK271 Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNNSL
C C
Last Used by: z004mx4y

Solid Link With Holder


Link Holder+Link 3NW
LK272 Siemens, India Boughtout Internal Mount 1
Time: 2:07:58 PM
Date: 12/12/2023

3NW 3NW32NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
LK371 Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNNSL

Solid Link With Holder


Link Holder+Link 3NW
LK79 Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNNSL

Rating: 2A
Fuse Holder+Fuse 3NW
FS19 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
D D
Rating: 2A
Fuse Holder+Fuse 3NW
FS211 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 07

3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS212 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS231 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
CopyRight (C) Siemens Limited, India All Rights Reserved.

Rating: 2A
Fuse Holder+Fuse 3NW
FS251 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

E Rating: 2A E
Fuse Holder+Fuse 3NW
FS311 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS331 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS351 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS39 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11407
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 07 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <06 08>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
Rating: 2A
Fuse Holder+Fuse 3NW
FS59 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-B1C1B Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-B1C1R Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-B1C1Y Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
B B
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B1C2B Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-B1C2R Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-B1C2Y Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-B2C1B Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
C C
Last Used by: z004mx4y

Rating: 2A
Fuse Holder+Fuse 3NW
FS-B2C1R Siemens, India Boughtout Internal Mount 1
Time: 2:08:07 PM
Date: 12/12/2023

3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-B2C1Y Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-B2C2B Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2

Rating: 2A
Fuse Holder+Fuse 3NW
FS-B2C2R Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
D D
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B2C2Y Siemens, India Boughtout Internal Mount 1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 08

3NW 3NW32NNSF+3NWNS2

Rating: 100W, 240V AC


Panel Accessory SH100
HT APT Control, India Boughtout Internal Mount 1
Space Heater SH100W240

Rating: 14W, 240V AC, Type: LED


Panel Accessory LED
CIL Philips, India Boughtout Internal Mount 1
Cubicle Illumination LED-14W
CopyRight (C) Siemens Limited, India All Rights Reserved.

Rating: 10/20A With Box, 3PIN, 240V AC


Panel Accessory 39996
PS Anchor, India Boughtout Internal Mount 1
Power Socket With Switch 39996

E Diode Unit With Branch Connector E


Diode With Branch Connector Diode
D1 ABB, India (4 Diodes In One Unit) With Branch Connector RTXC1 Boughtout Internal Mount 1
Diode IN5659-3001-A+RK924004-AA

3P4W3E, Accuracy: 0.5, DC O/P: 4-20mA, Dual O/P With Isolation, Frequency: 50Hz
Transducer PD3
MVART AE, India Aux Supply: 220V DC, 4mA/12mA/20mA Corres. To (-80)MVAR/(0)MVAR/(+80)MVAR Boughtout Internal Mount 1
Power Transducer PD3
CTR: 400-200/1A, PTR: 110kV/110V, Range: (-80)-0-(80) MVAR
3P4W3E, Accuracy: 0.5, DC O/P: 4-20mA, Dual O/P With Isolation, Frequency: 50Hz
Transducer PD3
MWT AE, India Aux Supply: 220V DC, 4mA/12mA/20mA Corres. To (-80)MW/(0)MW/(+80)MW Boughtout Internal Mount 1
Power Transducer (MW) PD3
CTR: 400-200/1A, PTR: 110kV/√3/110V/√3 AC, Range: (-80)-0-(80) MW
Aux Voltage: 230V AC
Audible Device ALA
EB Alan, India Electronic Bell, Clamp Mounting Type Boughtout Internal Mount 1
Electronic Bell ALA

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11408
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 08 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <07 09>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

DESIGNATION DETAILS MANUFACTURER MODEL DESCRIPTION DIS MOUNTING QUANTITY


A A
Aux Voltage: 40-300V DC, 90V AC-280V AC
Audible Device BHA
EBZ Bharani, India Electronic Bell, Type-6, Din Rail Mounting Type Boughtout Internal Mount 1
Electronic Bell BHA
Trip, Non Trip Alarm And DC Fail Alarm
Contacts: 1NO+1NC
Panel Accessory 3SE5
CILS Siemens, India Boughtout Internal Mount 1
Limit Switch 3SE5250-0CC05

B B

C C
Last Used by: z004mx4y

Time: 2:08:18 PM
Date: 12/12/2023

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 09
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11409
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 09 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <08 10>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

NO. OF CROSS
DETAILS MANUFACTURER MODEL DESCRIPTION DIS COLOR LENGTH QTY.
A CORES SECTION A
Patch Cable Non Rugged Multimode FO Patch Cable 1300nm, Core Size 62.5µm, Clad Size 125µm
FO Cable LC-LC
FO Patch Cable 1300nm_LC-LC Preston Type of Material: Glass, Number of Fibers: 2 (Rx) ( Tx), Un-Armored Boughtout OR 3.00 m 1
FO Patch Cable 1300nm_LC-LC
(3 Meters) Both End Connectors: LC-LC, Outer Sheath Colour: Orange, Length: 3 Meters

B B

C C
Last Used by: z004mx4y

Time: 2:08:28 PM
Date: 06/26/2023

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 10
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials-Cable Sub-Station at Nehru maidan in Mangaluru E11410
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 10 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <09 ->
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

A A
SI DG EA
General Arrangement

B B

C C
Last Used by: z004mx4y

Time: 2:08:39 PM
Date: 06/26/2023

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel F114 01
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated F 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd COVER SHEET Sub-Station at Nehru maidan in Mangaluru F11401
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 01 of 3
3008052247 (4)G719EA-OG9228-03-F114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: General Arrangement < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
▲2 DESIGN.
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


S. NO. DESCRIPTION TYPE
1 CASE & BASE-1 RHGX20-With Case (Flush) RHGX
2 67/67N Backup Protection 7SJ66
3 87L/21 Line Differential/Distance Protection 7SD52
4 FC Annunciator MCAN02
A 5 SL01 CB OPEN 3SB5 A
NP Type NP.Qty. Name Plate Description
6 SL02 CB CLOSE 3SB5
2100 7 SL03 CB AUTO TRIP 3SB5
110kV ADYAAR LINE (IDLE)

(Board)
8 SL04 CB SPRING CHARGED 3SB5

2 CONTROL & RELAY PANEL

A
9 SL05 TC HEALTHY 3SB5
2000 A1 A2 A3 V
10 SL06 ISO 114-89A OPEN 3SB5
PANEL REF : 114CRP 11 SL07 ISO 114-89A CLOSE 3SB5

1900 12 SL08 ISO 114-89B OPEN 3SB5


13 SL09 ISO 114-89B CLOSE 3SB5
FC 14 SL10 ISO 114-89D OPEN 3SB5
1800 15 SL11 ISO 114-89D CLOSE 3SB5
16 SL12 ESW 114-89DE OPEN 3SB5
PB01 PB02 PB03 PB51PB52PB53 SL52
MFM 17 SL13 ESW 114-89DE CLOSE 3SB5
B 1700 B
1 18 SL14 ISO 114-89C OPEN 3SB5
VSS
2
19 SL15 ISO 114-89C CLOSE 3SB5
1600 LRS SL06 SL07 SL08 SL09 PTS-1 20 SL16 ISO 114-89E OPEN 3SB5
21 SL17 ISO 114-89E CLOSE 3SB5
22 SL52 DC FAIL INDICATION 3SB5
1500
23 80/86A 86A Trip Relay Supvn TSR-B
PB86APB86B PB96 SL14 SL15
24 80/86B 86B Trip Relay Supvn TSR-B
PTS-2
1400 25 80/96 96 Trip Relay Supvn TSR-B
SL03 SL01 CS1 SL02 SL04 SL05
26 80A DC-1 Supvn Relay TSR-B
27 80B DC-2 Supvn Relay TSR-B
1300 28 86A Trip Relay RXMVB2
SL10 SL11 SL16 SL17
AUX VOLTAGE:220V DC 29 86B Trip Relay RXMVB2
30 96 LBB Trip Relay RXMVB2
C 1200 C
Last Used by: z004mx4y

TVM

SL12 SL13 31 195 TC-1 Supervision Relay TSR-B


NIT
32 295 TC-2 Supervision Relay TSR-B
Time: 2:09:03 PM
Date: 12/12/2023

2200

1100 33 CMRX Auxiliary Relay RXMM1


34 DCCO1 DC Changeover Relay RXME1
2315

35 DCCO2 DC Changeover Relay RXME1


1000 3
36 A1 Analogue Ammeter SQ
37 A2 Analogue Ammeter SQ
MIMIC NAME PLATE: 38 A3 Analogue Ammeter SQ
900
1. 110kV MAIN BUS-1
67/67N

39 MFM Multi Function Meter Elite


87L/21
2. 110kV MAIN BUS-2 40 TVM Meter Premier
800
3. 110kV ADYAAR LINE (IDLE) 41 V Analogue Voltmeter SQ
42 RU-A Resistor Unit for 86A RXTMA1
43 RU-B Resistor Unit for 86B RXTMA1
D 700 D
44 RU-C Resistor Unit for 96 RXTMA1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel F114 02

45 CS1 CB Control Switch BC


DCCO2 DCCO1
CMRX
86A

86B

80A
195

600 46 LRS CP/SCADA Selector Switch PDS


96

CASE & BASE-1


47 NIT Selector Switch PDS
80/86A

80/86B
RU-A

RU-B

RU-C

80/96

48 PB01 Annun.Accept 3SB5


80B
295

500 49 PB02 Annun.Reset 3SB5


50 PB03 Annun.Test 3SB5
51 PB51 DC-1 FAIL TEST 3SB5
400
52 PB52 DC-2 FAIL TEST 3SB5
15,00mm Anti Vibration Pad
CopyRight (C) Siemens Limited, India All Rights Reserved.

53 PB53 DC FAIL ACCEPT 3SB5


300 TTB BLKD 54 PB86A 86 Reset 3SB5
55 PB86B 86 Reset 3SB5
56 PB96 96 Reset 3SB5
E 200 E
57 PTS-1 Selector Switch PDS
BLKA BLKB BLKC
58 PTS-2 Selector Switch PDS

100 59 VSS Selector Switch PCS


60 BLKA Test Block For 87L/21 DAV
61 BLKB Test Block For 87L/21 DAV
0 0
62 BLKC Test Block For 67/67N DAV
63 BLKD Test Block For 67/67N DAV
100

64 TTB DAV TTB

1000 NOTE:

1.AS PER M/S SHARAVATHY CONFIRMATION WE HAVE PROVIDED PANEL COLOUR,


HEIGHT,DEPTH, MIMIC HEIGHT, MIMIC COLOUR AS PER SIEMENS STANDARD. ALSO
EXISTING DETAILS ARE NOT AVAILABLE.
F 2.BY PASS ISOLATOR PROVISION FOR FUTURE REQUIREMENT. Dimension Unit: mm, All Dimension Tolerance= ±5mm F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated F 114 CRP 1 mm. : 10 mm.
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Front View Sub-Station at Nehru maidan in Mangaluru F11402
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 02 of 3
3008052247 (4)G719EA-OG9228-03-F114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: General Arrangement <01 03>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

SIDE VIEW
A A

275
400

80
SLOT FOR BUS WIRING

B B

REAR DOORS

FRONT
Ø14.0 HOLES (4x)
C C
Last Used by: z004mx4y

127
Time: 2:09:19 PM
Date: 06/26/2023

25
2200
2315

519
800
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel F114 03

154
100
CopyRight (C) Siemens Limited, India All Rights Reserved.

15mm Anti Vibration Pad

25

120 349 349 120


62
1000
E 148
E
12

EARTH BUSBAR SLOT


54
65

FRONT
0
100

800
827

F Dimension Unit: mm, All Dimension Tolerance= ±5mm F


B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated F 114 CRP 1 mm. : 10 mm.
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Side View & Panel Fixing-Top View Sub-Station at Nehru maidan in Mangaluru F11403
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. 1 Cubicle per Bay Sh. 03 of 3
3008052247 (4)G719EA-OG9228-03-F114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: General Arrangement <02 ->
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

A A
SI DG EA
Internal Layout

B B

C C
Last Used by: z004mx4y

Time: 2:09:34 PM
Date: 07/07/2023

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel V114 01
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated V
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd COVER SHEET Sub-Station at Nehru maidan in Mangaluru V11401
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 01 of 2
3008052247 (4)G719EA-OG9228-03-V114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Internal Layout < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


Note: TB Mounting Sequence For Vertical Rail Is Top To Bottom &
For Horizontal Rail Left To Right.

A A
LH1 (D40.00 mmxW60.00 mm) RH1 (D40.00 mmxW60.00 mm) CILS
LH1 CIL RH1
FH1 (D60.00 mmxW60.00 mm)
XB:BVT1(1-10) XB:BVT2(1-10) XB:VT(1-10) FH1 XB:ANN(1-8)
2088 2088 2088

EBZ
XB:ANN
XB:LBB
XB:BVT1

XB:BVT2

XB:AC
XB:VT
XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT

XB:VT
LHMR1 RHMR1

XB:BVT1

XB:BVT1

XB:BVT1

XB:BVT1

XB:BVT1

XB:BVT1

XB:BVT1

XB:BVT1

XB:BVT1

XB:BVT1

XB:BVT2

XB:BVT2

XB:BVT2

XB:BVT2

XB:BVT2

XB:BVT2

XB:BVT2

XB:BVT2

XB:BVT2

XB:BVT2

XB:ANN

XB:ANN

XB:ANN

XB:ANN

XB:ANN

XB:ANN

XB:ANN

XB:ANN
XB:LBB

XB:LBB

XB:LBB

XB:LBB

XB:LBB

XB:LBB

XB:LBB

XB:LBB

XB:LBB

XB:LBB
10

XB:AC

XB:AC

XB:AC
1

9
10

10

10
1

8
2038 2038 XB:AC(1-3)XB:LBB(1-10)
2038
V A3 A2 A1
LH2 (D40.00 mmxW60.00 mm) 1988 1988 RH2 (D40.00 mmxW60.00 mm) 1988
LH2 RH2
1938 FH2 FH2 (D60.00 mmxW25.00 mm) 1938 1938

BUS WIRING SLOT 1888 1888 BUS WIRING SLOT 1888


FC
1838 1838 1838
LH3 LH3 (D60.00 mmxW25.00 mm) RH3 RH3 (D60.00 mmxW25.00 mm)
1788 VSS 1788 1788

MVART

MWT
SL52 PB53PB52PB51 PB03 PB02 PB01

HTS
TH

PS
EB
LHMR2 RHMR2

LIU
1738 MFM 1738 1738
B 1688 1688 1688
B
FH3 (D40.00 mmxW60.00 mm)
LH4 (D40.00 mmxW60.00 mm) 1638 FH3 1638 RH4 RH4 (D60.00 mmxW25.00 mm) 1638
LH4 SL09 SL08 SL07 SL06
PTS-1 LRS

FS-B2C2B
LK-B2C2N
FS-B1C1R

FS-B1C2R

FS-B2C1R

FS-B2C2R
FS-B1C1Y
FS-B1C1B
LK-B1C1N

FS-B1C2Y
FS-B1C2B
LK-B1C2N

FS-B2C1Y
FS-B2C1B
LK-B2C1N

FS-B2C2Y
1588 1588 1588

FS17
FS18

FS91

FS92

FS93
LK91

LK92

LK93
80C

95X
LHMR3

FS21
FS22
1538 1538 RHMR3 1538
FH4 (D40.00 mmxW60.00 mm)
1488 FH4 PB96 PB86BPB86A 1488 1488
LNPL1 SL15 SL14
RNPL1
1438 PTS-2 1438 1438
LH5 (D40.00 mmxW60.00 mm)
LH5 1388 SL05 SL04 SL02 CS1 SL01 SL03 1388 RH5 (D40.00 mmxW60.00 mm) 1388
RH5
1338 1338 1338

FS101
FS102
FS201
FS202

FS13
FS14
FS15
FS16
FS11
FS12

FS10
FS211
FS231
FS251

FS212

FS311
FS331
FS351
LK271

LK272

LK371

FS1
FS2
FS7
FS8
FS5
FS6

FS3
FS4
FS9
ETL1
ETL2
ETL7
FS19
FS39
FS59
LK79

FSC
D1
LHMR4 RHMR4

FV1 (D60.00 mmxW60.00 mm)

FV2 (D60.00 mmxW60.00 mm)


1288 SL17 SL16 SL11 SL10 1288 1288

LNPL2 1238 1238 RNPL2 1238


C C
Last Used by: z004mx4y

TVM
1188 SL13 SL12 1188 1188
LH6 (D60.00 mmxW60.00 mm) NIT RH6 (D60.00 mmxW60.00 mm)
LH6 RH6
Time: 2:42:42 PM
Date: 12/12/2023

1138 1138 1138


2200

X:RS485

X:RS485 (1-4)
X:RS485
1

1088 1088 1088

X:SP (31-125)
X:RS485
2
X:RS485
3
X:RS485
X:SP

X:SP (1-30)
4
X:SP
2315

X:CB (1-51)
X:CB X:SP
X:SP
31
1 X:SP
X:CB
X:SP 32
1
2 X:SP

FH5 (D40.00 mmxW60.00 mm)


X:CB

1038 1038 1038


X:SP 33
2
3 X:SP
X:CB
X:SP 34

X:AI (1-11)
X:AI 3
4 X:SP

FH5
X:CB
X:SP 35
4
5 X:SP
X:AI X:CB
1 X:SP 36
5
6 X:SP
X:AI X:CB
2 X:SP 37
6
7 X:SP
X:AI X:CB

988 988 988


3 X:SP 38
7
8 X:SP
X:AI X:CB
4 X:SP 39
8
9 X:SP
X:AI X:CB
5 X:SP 40
9
10 X:SP
X:AI X:CB
6 X:SP 41
10
11 X:SP
X:AI X:CB
7 X:SP 42
11
12 X:SP
X:AI X:CB
8 X:SP 43
12
13 X:SP
X:AI X:CB

938 938 938


9 X:SP 44
13
14 X:SP
X:AI X:CB
10 X:SP 45
14
15 X:SP
X:AI X:CB
11 X:SP 46
15
16 X:SP
X:CB
X:SP 47
X:VT (1-18)

X:VT 16
X:CB
17
X:SP
X:SP
48
17
18 X:SP

67/67N
X:VT X:CB
X:SP

888 888 888


1 49
18
19 X:SP
X:CB
X:VT X:SP 50
19
2 20 X:SP
X:CB
X:SP 51
20

87L/21
X:VT 21 X:SP
X:CB
3 X:SP 52
22
22 X:SP
X:CB
X:VT X:SP 53
23
4 23 X:SP
X:CB
X:SP 54
24
X:VT 24 X:SP
11 X:CB
X:SP

838 838 838


55
25
25 X:SP
X:VT X:CB
X:SP 56
12 26
26 X:SP
X:CB
X:SP 57
X:VT 27
27 X:SP
13 X:CB
X:SP 58
28
28 X:SP
X:VT X:CB
X:SP 59
14 29
29 X:SP
X:CB
X:SP 60
X:VT 30

788 788 788


30 X:SP
5 X:CB
61
31
X:S

X:S (1-13)
X:VT X:SP
X:CB
6 62
32

RV1 (D40.00 mmxW60.00 mm)


X:SP
X:CB X:S

RV3 (D60.00 mmxW60.00 mm)

RV2 (D40.00 mmxW60.00 mm)


X:VT 63
33 1
LV3 (D40.00 mmxW60.00 mm)

7 X:SP
X:CB X:S
64
34 2
X:VT X:SP
X:CB X:S
8 65
35 3
X:SP
X:CB X:S
X:VT 66
36 4

738 738 738


9 X:SP
X:CB X:S
67
37 5

D D
X:VT X:SP
10 X:CB X:S
68
38 6
X:SP
X:VT X:CB X:S
69
21 7

FH6 (D40.00 mmxW60.00 mm)


15
X:SP
X:CB X:S
70
39 8
X:VT X:SP
16 X:CB X:S

688 688 688


71
40 9

FH6
X:SP
X:VT X:CB X:S
72
17 41 10
X:SP
X:CB X:S
73
X:VT 42 11
X:SP
18 X:CB X:S
74
43 12
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel V114 02

X:SP
X:CB X:S
X:CT (1-31)

X:CT 75

RVMR3

RVMR2
44 13
LVMR3

X:SP
X:CB

X:BVT2 (1-10)
X:CT
45 X:BVT2 76
X:SP

DCCO1 DCCO2
X:CB

638 638 638


1 77
46 X:BVT2

CMRX
X:SP
X:CB 1
X:CT 78
47
2 X:SP

86B

86A
X:CB X:BVT2

80A

195
79
48 2
X:CT X:SP

96
3 X:CB
80
49 X:BVT2
3 X:SP
X:CT X:CB 81
4 50
X:BVT2 X:SP
X:CB 82

588 588 588


4
X:CT 51
X:SP
5

X:ISO (1-28)
X:CT
X:ISO X:BVT2
5
83
X:SP
84
6
X:ISO X:BVT2 X:SP
1 6 85
X:CT
7 CASE & BASE-1 X:ISO
2 X:BVT2
X:SP
86
X:ISO 7 X:SP
X:CT

80/86B

80/86A
3 87
8
X:ISO X:BVT2 X:SP

RU-B

RU-A
RU-C
80/96
4 8 88
X:CT

538 538 X:ISO X:SP

538

80B
9

295
5 X:BVT2 89
X:ISO 9
X:CT X:SP
10 6 90
X:ISO X:BVT2
X:SP
X:CT 7 10
91
11 X:ISO X:SP

X:BVT1 (1-10)
X:CT
8
X:ISO X:BVT1 92
X:SP
12 9 93
X:ISO X:BVT1

488 488 488


X:SP
X:CT 10 1 94
13 X:ISO X:SP
11 X:BVT1 95
X:CT X:ISO 2
X:SP
14 12 96
X:ISO X:BVT1
X:SP
X:CT 13 3
97
15
X:ISO X:SP
14 X:BVT1
98
X:CT 4
X:ISO X:SP
16
15 99
X:BVT1
X:ISO

438 438 438


X:CT 5 X:SP
16 100
17
X:ISO X:SP
X:BVT1
17

FH7 (D40.00 mmxW60.00 mm)


X:CT 6 101
18 X:ISO X:SP
18 102
X:BVT1
X:CT X:ISO 7 X:SP
19 19 103

X:CT
20 FH7 X:ISO
20
X:ISO
X:BVT1
8
X:SP
104
X:SP

X:CT
21

X:CT
388 388 21
X:ISO
22
X:ISO
23
X:BVT1
9

X:BVT1
10
105
X:SP
106
X:SP
107
388
22 X:ISO
CopyRight (C) Siemens Limited, India All Rights Reserved.

X:SP

X:BC (1-10)
X:CT
24
X:ISO X:BC 108
X:SP
23 25 109
X:BC
X:ISO X:SP
X:CT 1
26 110
24 X:BC
X:ISO X:SP

338 338 338


2
27 111
X:CT X:BC
X:ISO X:SP
25 3
28 112
X:BC
X:CT 4 X:SP
X:DC2

X:DC2 (1-3)
113

BLKD
26 X:BC

TTB 5 X:SP
X:CT 114
X:DC2 X:BC
27 6 X:SP
1
115
X:BC
X:CT 7 X:SP
X:DC2

288 288 288


28 116
2 X:BC
8 X:SP
X:CT 117
X:DC2 X:BC
29 X:SP
3 9
118
X:BC
X:CT X:SP
30 X:DC1 10
119
X:SP

X:DC1 (1-3)
X:CT 120
31 X:DC1
1 X:SP
121

FH8 (D25.00 mmxW60.00 mm)


X:SP

238 238 238


X:DC1
2 122

E E
X:SP
X:DC1 123

FH8
3 X:SP
124
X:SP
X:AC 125

X:AC (1-3)
X:AC
1

188 188 188


FV1

FV2
X:AC
2

X:AC

BLKC BLKB BLKA


3

RV1
RV3

RV2
LV3

138 138 138

88 E-BB 88 88
HT

0
0 0 0
100

15.00
1000
Cable Duct for External Wire/Cable

Name Plate Rail

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated V 114 CRP 1 mm. : 10 mm.
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Internal Layout Sub-Station at Nehru maidan in Mangaluru V11402
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 02 of 2
3008052247 (4)G719EA-OG9228-03-V114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Internal Layout <01 ->
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

A A
SI DG EA
Wiring Schematics

B B

C C
Last Used by: z004mx4y

Time: 2:10:35 PM
Date: 07/07/2023

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 01
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd COVER SHEET Sub-Station at Nehru maidan in Mangaluru W11401
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 01 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

PANEL PANEL
SHEET NO. DESCRIPTION DRAWING NUMBER SHEET NO. DESCRIPTION DRAWING NUMBER
A REFERENCE REFERENCE A
COVER SHEET 67/67N Relay BO Circuit
01 (4)G719EA-OG9228-03-W114 114 CRP 19 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
List of Documents 86A Master Trip Relay Circuit
02 (4)G719EA-OG9228-03-W114 114 CRP 20 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
List Of Reference Documents 86B Master Trip Relay Circuit
03 (4)G719EA-OG9228-03-W114 114 CRP 21 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
Legend 96 LBB Trip Relay Circuit
04 (4)G719EA-OG9228-03-W114 114 CRP 22 (4)G719EA-OG9228-03-W114 114 CRP
B Wiring Schematics Wiring Schematics B
Single Line Diagram CB TC-1 Circuit
05 (4)G719EA-OG9228-03-W114 114 CRP 23 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
Trip Logic Diagram CB TC-2 Circuit
06 (4)G719EA-OG9228-03-W114 114 CRP 24 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
AC Distribution TC1 & TC2 Circuit of Buscoupler
07 (4)G719EA-OG9228-03-W114 114 CRP 24A (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
DC Distribution Indication Circuit
08 (4)G719EA-OG9228-03-W114 114 CRP 25 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
C C
Last Used by: z004mx4y

Bus VT Supply Distribution Indication Circuit


08A (4)G719EA-OG9228-03-W114 114 CRP 25A (4)G719EA-OG9228-03-W114 114 CRP
Time: 2:10:48 PM
Date: 07/07/2023

Wiring Schematics Wiring Schematics


Voltage Selection Circuit Annuciation Circuit
08B (4)G719EA-OG9228-03-W114 114 CRP 26 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
Meetering Circuit Annunciation Circuit
09 (4)G719EA-OG9228-03-W114 114 CRP 27 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
Metering Circuit Spare Contact Distribution
10 (4)G719EA-OG9228-03-W114 114 CRP 28 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
D D
87L/21 Relay CT VT Circuit Test Block & switch Distribution Circuit
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 02

11 (4)G719EA-OG9228-03-W114 114 CRP 29 (4)G719EA-OG9228-03-W114 114 CRP


Wiring Schematics Wiring Schematics
87L/21 Relay BI Circuit Connection Diagram For 67/67N
12 (4)G719EA-OG9228-03-W114 114 CRP 30 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
87L/21 Relay BI Circuit Connection Diagram For 87L/21
13 (4)G719EA-OG9228-03-W114 114 CRP 31 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
CopyRight (C) Siemens Limited, India All Rights Reserved.

87L/21 Relay BO Circuit Connection Diagram For 87L/21


14 (4)G719EA-OG9228-03-W114 114 CRP 32 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
E 87L/21 Relay BO Circuit BI/BO Table E
15 (4)G719EA-OG9228-03-W114 114 CRP 33 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
BI/BO Table
16 (4)G719EA-OG9228-03-W114 114 CRP 34 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
67/67N Relay CT Circuit
17 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics
67/67N Relay BI Circuit
18 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd List of Documents Sub-Station at Nehru maidan in Mangaluru W11402
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 02 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <01 03>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

A A

B B

LIST OF REFERENCE DRAWINGS


DESCRIPTION DRAWING NO MAKE OF THE EQUIPMENTS
SLD - SHARAVATHY CONDUCTORS PVT LTD.
CURRENT TRANSFORMER - -
VOLTAGE TRANSFORMER - -
C CB DRAWING (4)G71AHS-EA401-W1240- SIEMENS LTD,AURANGABAD C
Last Used by: z004mx4y

ISOL& EARTH SWITCH - -


Time: 2:10:57 PM
Date: 07/07/2023

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 03
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd List Of Reference Documents Sub-Station at Nehru maidan in Mangaluru W11403
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 03 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <02 04>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1 SYMBOL & DESCRIPTION SYMBOL & DESCRIPTION SYMBOL & DESCRIPTION

A A
L+ L-
HOOTER

CAPACITIVE VOLTAGE TRANSFORMER

POWER SUPPLY
BELL
CIRCUIT BREAKER Designation Comment

-S
X:AC Incoming AC Ckt

X:AI Transducer Ckt


ISOLATOR
X:BC
PUSH BUTTON
X:BVT1 BUS-1 VT SUPPLY
B X:BVT2 BUS-2 VT SUPPLY
B
X:CB CB Ckt
CURRENT TRANSFORMER
X:CT CT Ckt
STABLIZING RESISTOR X:DC1 Incoming DC-1 Ckt

X:DC2 Incoming DC-2 Ckt


SURGE ARRESTER
X:ISO Isolator Ckt
U
X:RS485 RS485 Communication

VARIASTOR X:S Scada Ckt


EARTH BAR
X:SP Spare Ckt

X:SP Spare Ckt

X:VT PT Ckt

XB:AC Incoming AC Ckt


C C
Last Used by: z004mx4y

SWITCH CONTACT
WAVE TRAP XB:ANN Annunciation Ckt

XB:BVT1 BUS-1 VT SUPPLY BUS WIRING


Time: 2:11:10 PM
Date: 07/07/2023

XB:BVT2 BUS-2 VT SUPPLY BUS WIRING

XB:LBB LBB Circuit


SOCKET
FUSE XB:VT PT Ckt

1S2

1S2

1S2
I II III
LINK

1S2

1S2

1S2
CURRENT TRANSFORMER SECONDARY

DISCONNECTING TERMINAL
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 04

NON-DISCONNECTING TERMINAL OPERATING COIL

RELAY TEST BLOCK


CopyRight (C) Siemens Limited, India All Rights Reserved.

CURRENT COIL

OPEARTING/REST COIL

E LATCHED CONTACT-NO E

I> I>
LATCHED CONTACT-NC

MCB

SPACE HEATER

FLOURCENT LAMP BINARY INPUT


F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Legend Sub-Station at Nehru maidan in Mangaluru W11404
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 04 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <03 05>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1 110kV ADYAAR LINE


(IDLE)

A A

LA

114-89DE

B B

114-89D

114-52

P1

C C
Last Used by: z004mx4y

CT
114-89E CORE-3 7SJ66 67/67N
RATIO: 400-200/1A Backup Protection
Time: 2:11:25 PM
Date: 07/07/2023

CLASS: 5P20
Burden: 30VA
From Bus VT

CT
CORE-2 PD3 MWT PD3 MVART SQ Premier TVM Elite MFM
RATIO: 400-200/1A Power Transducer (MW) Power Transducer Analogue Ammeter Meter Multi Function Meter
CLASS: 0.2
Burden: 10VA
From BUS VT

CT
CORE-1 7SD52 87L/21
RATIO: 400-200/1A Line Differential/Distance Protection
D CLASS: PS, Vk=800V @400/1 ,Rct=<4ohm @400/1 D
Im @Vk/2=20mA
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 05

From Sel Bus VT


P2

114-89C
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

114-89A 114-89B

NOTE: (114-89E ) BY PASS ISOLATOR PROVISION MADE FOR FUTURE REQUIREMENT.

110kV BUS-2

110kV BUS-1

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Single Line Diagram Sub-Station at Nehru maidan in Mangaluru W11405
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 05 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <04 06>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

A A

TELE PROTECTION SIGNALS


CB TC-1 R, Y, B-PHASE
86A 3-PH TRIP RELAY
86B 3-PH TRIP RELAY

CB TC-2 R,Y,B-PHASE
96 LBB TRIP RELAY
B DEVICE B

LBB INITIATION
FUNCTION DESCRIPTION TYPE
DESIGNATION

DR TRIGGER
CLOSE CB
87L/21 LINE DIFF.PROTN 7SD522 X X X X @
87L/21 DISTANCE PROTN-Z2/3/4 7SD522 X X X X @
87L/21 O/V STAGE-1 (INBUILT OF 87L/21) - 59 7SD522 X X X @
C C
Last Used by: z004mx4y

87L/21 O/V STAGE-2 (INBUILT OF 87L/21) - 59 7SD522 X X X @


87L/21 SOTF PROTECTION (INBUILT OF 87L/21) 7SD522 X X @
Time: 2:11:36 PM
Date: 07/07/2023

87L/21 LBB PROTN-50Z 7SD522 # X @


67/67N DIR. O/C PROTN. - 67 7SJ66 X X @
67/67N DIR. IDMTL E/F PROTN. - 67N 7SJ66 X X X @
67/67N LBB PROTN-50Z 7SJ66 X X @
86A 3Ph TRIP RELAY RXMVB2 X X X
86B 3Ph TRIP RELAY RXMVB2 X X X
96 LBB TRIP RELAY RXMVB2 X X
D CS52 CB MANUAL CLOSE X D
CS52 CB MANUAL TRIP X X
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 06

X INITIATION CONTACT (HARD WIRED)


@ SOFT SIGNALS
$ RELAY INTERNAL FUNCTION
# WILL BE UTILIZE IF REQUIRED AT SITE
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Trip Logic Diagram Sub-Station at Nehru maidan in Mangaluru W11406
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 06 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <05 07>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

X:AC 1 H1

A A
2 H2

ADJ PANEL

XB:AC 1

B ADJ PANEL
B
FS93
H1 2 1 H21
6A
LK93
H2 2 1 H22

EB
16A

6A
2

2
2

2
80A 80C
LK91

LK92
FS91

FS92
26 27 H23 21 22 H24

L
N
/08.3 /07.7
1

1
1

1
80B
C 26 27 C
Last Used by: z004mx4y

/08.3 SL52
X1 X2
Time: 2:11:52 PM
Date: 07/07/2023

H4 DC FAIL INDICATION

80C
13 14 H27
H3

/07.7

3RH21

H31

H32
80C
CILS CIL PB53
21 22 H5 1 2 1-3 1-4 A1 A2
/29.3 /29.4

/27.5

/27.5
DC FAIL ACCEPT
13 14
/07.6 To DC Fail Scheme
TO ANNUN 21 22
/07.6 To DC Fail Scheme
CKT 31 32
D D
43 44
HTS TH
1 HT 2
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 07

1 2 H7 1 2 H8

PS
1 PSS 2

E
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

NOTE: TB NUMBER AND FERRULE NUMBERS MAY CHANGE DURING MANUFACTURING

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd AC Distribution Sub-Station at Nehru maidan in Mangaluru W11407
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 07 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <06 08>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


DCDB 114 CRP

DC Changeover Relay
DCCO1
11 21
A A
14 15
/08.5
24 25
/08.5
16 17
/08.6
26 27
X:DC1 FS101 /08.6 DCCO1
+VE J11 2 1 J13 14 15 J1
220V DC -1 16A /08.3
1 FS102
SUPPLY DCCO1
J12 2 1 J14 24 25 J2
-VE 16A /08.3
2

10A

10A

10A

10A
2-2

6A

6A

6A

6A

4A

4A
2

2
FS13

FS14

FS15

FS16
B B

FS1

FS2

FS3

FS4

FS5

FS6
/29.4

1
PB51
2-1
DC-1 Supvn Relay

17

27

17

27

L101

L102
80A

/08.3

/08.3

/08.3

/08.3
K1

K2

L1

L2
12 21

J13A

K901

K902

K101

K102

DCCO1

DCCO1

DCCO2

DCCO2
/23.1

/23.1

/09.6

/09.6

/27.4

/27.4
11 13

/12.3

/12.6

/20.3

/20.8

16

26

16

26
28 18 INDICATION TO ANNUN
/28.2 Spare
16 17 CIRCUIT BREAKER TRIP RELAY METERING
/26.2 TO ANN TO 87L/21 RELAY
CLOSING & 86A CKT
C CIRCUIT C
Last Used by: z004mx4y

26 27
/07.5 To AC Distribution Ckt TRIPCOIL-1
Time: 2:12:14 PM
Date: 07/07/2023

DC Changeover Relay
DCCO2
11 21

14 15
/08.5
24 25
/08.5
16 17
D /08.7 D
26 27
X:DC2 FS201 /08.7 DCCO2
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 08

+VE J21 2 1 J23 14 15 J3


220V DC -2 16A /08.3
1 FS202
SUPPLY DCCO2
J22 2 1 J24 24 25 J4
-VE 16A /08.3
2
2-2

6A

6A

6A

6A
2

2
10A

10A

FS17

FS18

FS21

FS22
6A

6A

6A

6A
/29.5

2
CopyRight (C) Siemens Limited, India All Rights Reserved.

FS10

FS11

FS12
FS7

FS8

FS9

1
1

1
PB52

E E
2-1

U1

U2
DC-2 Supvn Relay
80B
12 21
J23A

K201

K202

P101

P102
K51

K52

K401

K402

11 13 X:SP 1 2
/24.3

/24.3

/21.3

/21.8

/22.3

/22.8
/18.3

/18.6

28 18
/28.4 Spare
16 17 TRIP RELAY TO 96 RELAY
/26.2 TO ANN CIRCUIT BREAKER SPARE
86B CKT CIRCUIT
26 27 TRIP COIL-2 TO 67/67N RELAY
/07.5 To AC Distribution Ckt
CIRCUIT

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd DC Distribution Sub-Station at Nehru maidan in Mangaluru W11408
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 08 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <07 08A>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


ADJ PANEL 114 CRP ADJ PANEL 114 CRP

A FS-B1C1R FS-B2C1R A
BUS-1 VT PROTECTION CORE-1

BUS-2 VT PROTECTION CORE-1


XB:BVT1 1 1E111 2 1 1E113 XB:BVT2 1 2E111 2 1 2E113
/08B.2 /08B.2
2A 2A

FS-B1C1Y FS-B2C1Y
2 1E131 2 1 1E133 2 2E131 2 1 2E133
/08B.2 /08B.2
2A 2A

FS-B1C1B FS-B2C1B
3 1E151 2 1 1E153 3 2E151 2 1 2E153
/08B.2 /08B.2
2A 2A

LK-B1C1N LK-B2C1N
4 1E171 2 1 1E173 4 2E171 2 1 2E173
/08B.2 /08B.2

B ADJ PANEL ADJ PANEL B


X:BVT1 1 X:BVT2 1

2 2

3 3

4 4

C C
Last Used by: z004mx4y

Time: 2:12:41 PM
Date: 07/07/2023

ADJ PANEL ADJ PANEL

FS-B1C2R FS-B2C2R
XB:BVT1 5 1E211 2 1 1E213 XB:BVT2 5 2E211 2 1 2E213
BUS-1 VT METERING CORE-2

/08B.5 /08B.5

BUS-2 VT METERING CORE-2


2A 2A

FS-B1C2Y FS-B2C2Y
6 1E231 2 1 1E233 6 2E231 2 1 2E233
/08B.5 /08B.5
2A 2A
D D
FS-B1C2B FS-B2C2B
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 08A

7 1E251 2 1 1E253 7 2E251 2 1 2E253


/08B.5 /08B.5
2A 2A

LK-B1C2N LK-B2C2N
8 1E271 2 1 1E273 8 2E271 2 1 2E273
/08B.5 /08B.5

ADJ PANEL ADJ PANEL


X:BVT1 5
CopyRight (C) Siemens Limited, India All Rights Reserved.

X:BVT2 5
6
6
E 7 E
7
8
8

F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F


B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bus VT Supply Distribution Sub-Station at Nehru maidan in Mangaluru W11408A
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 08A of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <08 08B>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1 114 CRP

A A

PTS-1 PTS-2
B BUS-1 PT BUS-2 PT BUS-1 PT BUS-2 PT B
1E113 1 2 E115 1E213 1 2 E11
/08A.4 /11.3 /08A.4 /09.3
/29.6 /29.7

1E133 3 4 E135 1E233 3 4 E31


/08A.4 /11.3 /08A.4 /09.3
/29.6 /29.7
TO 87L/21 TO TVM
1E153 5 6 E155 1E253 5 6 E51
/08A.4 /11.3 /08A.4 /09.3
/29.6 /29.7

1E173 7 8 E175 1E273 7 8 E71


/08A.4 /11.3 /08A.4 /09.3
/29.6 /29.7

C C
Last Used by: z004mx4y

Time: 2:13:01 PM
Date: 07/07/2023

2E113 11 12 2E213 11 12
/08A.8 /08A.8
/29.6 /29.7

2E133 13 14 2E233 13 14
/08A.8 /08A.8
/29.6 /29.7

2E153 15 16 2E253 15 16
/08A.8 /08A.8
/29.6 /29.7
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 08B

2E173 17 18 2E273 17 18
/08A.8 /08A.8
/29.6 /29.7
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F


B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Voltage Selection Circuit Sub-Station at Nehru maidan in Mangaluru W11408B
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 08B of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <08A 09>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1 114 CRP

A A

110kV BUS SIDE TTB Power Transducer (MW)


CT JB R1 VR R2 E15 MWT
D13

OUTPUT-1
1 1 1 17 S101 X:AI 1
+
X:CT 1 D11 2 2 3 18 S102 2
-
2 3 3 D71 D15 D15
/10.2

OUTPUT-2
VY 4 19 3

CT INPUT
Y1 Y2 E35 S103 X:AI
+
B 3 4 4 D33 6 20 S104 4 B
-
4 D31 5 5
6 6 D71 7 D35 D35
/10.2
5 B1 VB B2 E55 9
6 7 7 D53
P2

P2

P2

CT D51
CORE-2 2S3 2S3 2S3 8 8 2
R-PH 9 9 5 D55 D55

VT INPUT
D71
/10.2
RATIO: 400-200/1A

D71S
2S1 2S1 2S1 N1 VN N2 E75 8
CLASS: 0.2
11
P1

P1

P1

/08.7
/08.7

AUX SUPPLY
13
~/+
7 D71 14
~/-

L1
L2
C 8 C
Last Used by: z004mx4y

Time: 2:13:31 PM
Date: 07/07/2023

ETL1
D73S 2 1E

LINE SIDE

L1
L2
/10.3
/10.3
D71 D71
/10.1

E15 E15
D /10.1 D
FS311
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 09

E11 X:VT 1 E11A 2 1 E13 E35 E35


/08B.7 /10.1
2A
FS331
E31 2 E31A 2 1 E33 E55 E55
/08B.7 /10.1
2A
FS351
E51 3 E51A 2 1 E53 E75 E75
/08B.7 /10.1
2A
LK371
E71 4 E71A 2 1 E73
/08B.7
CopyRight (C) Siemens Limited, India All Rights Reserved.

ADJ PANEL
XB:VT 1
E E
XB:VT 2

XB:VT 3

XB:VT 4

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Meetering Circuit Sub-Station at Nehru maidan in Mangaluru W11409
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 09 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <08B 10>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

D21

D41
A A
D61

Power Transducer
MVART

OUTPUT-1
D15 1 17 S105 X:AI 5
/09.8 +
3 18 S106 6 Meter Multi Function Meter
-
A1 TVM R MFM V1
1 2

OUTPUT-2
4 19 7 1S I1S1

CT INPUT
D35 S107 X:AI D23 D25
/09.8 + A
6 20 S108 8
- R
1L I1S2
D55 7 A2 Y V2
/09.8
B 9 1 2 D43 2S D45 I2S1 B
A
Y
2 2L I2S2
5 A3 B V3

VT INPUT

RS485 PORT
8 1 2 D63 3S D65 I3S1 +
A
11 -
B
3L I3S2 SG

AUX SUPPLY
13 N VN

/09.6
/09.6
~/+
14
~/- AUX SUPPLY
+/P -/N

L1
L2
C C
Last Used by: z004mx4y

TVM
Time: 2:13:49 PM
Date: 07/07/2023

RS485

COM
L1
L2

Rx
Tx
/25.3
/25.6

Screened
D71 cable
/09.8

X:RS485 1 2 3
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 10

E15 E15 VSS V


/09.8
R V1 E115B 1 2
V
E35 E35 Y
/09.8
B V2 E117A
E55 E55
/09.8
CopyRight (C) Siemens Limited, India All Rights Reserved.

E75 E75
/09.8

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Metering Circuit Sub-Station at Nehru maidan in Mangaluru W11410
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 10 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <09 11>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

87L/21 (7SD522)
110kV BUS SIDE 87L/21
A -11.1
A
CT JB

BLKA IL1 Run


X:CT 11 A11 S3 R3 A13 Q1 * Q2
12 /29.3 /30.1
Error
BLKA IL2
13 A31 S4 R4 A33 Q3 * Q4
LED 1 R-PHASE TRIP
14 /29.3 /30.1

BLKA IL3 LED 2 Y-PHASE TRIP


15 A51 S5 R5 A53 Q5 * Q6
16 /29.3 /30.1
P2

P2

P2
CT LED 3 B-PHASE TRIP
1S3 1S3 1S3

A71S
CORE-1
R-PH
BLKA LED 4 ZONE-1 OPTD
B RATIO: 400-200/1A 1S1 1S1 1S1 17 A71 S6 R6 A73 B
CLASS: PS,
18 /29.3
Vk=800V @400/1 , LED 5 Z2/Z3/Z4 OPTD
P1

P1

P1

Rct=<4ohm @400/1

A73S
Im @Vk/2=20mA
ETL2 LED 6 VT FUSE FAIL
2 1 EW

LED 7 SOTF OPTD

LINE SIDE 87L/21


FS211 BLKB UL1 -11.2
E115 X:VT 11 E115A 2 1 E117 S3 R3 E119 R15 *
/08B.3
2A /29.4 /30.1
LED 1 OCR OPTD
C C
Last Used by: z004mx4y

Selected Bus VT supply

FS231 BLKB UL2


E135 12 E135A 2 1 E137 S4 R4 E139 R17 *
/08B.3 LED 2 EFR OPTD
2A
Time: 2:14:13 PM

/29.4 /30.1
Date: 07/07/2023

FS251 BLKB UL3 LED 3 LBB OPTD


E155 13 E155A 2 1 E157 S5 R5 E159 R18 * R16
/08B.3
2A /29.4 /30.1
LED 4 LINE .DIFF OPTD
LK271 BLKB
E175 14 E175A 2 1 E177 S6 R6 E179
/08B.3 LED 5 DIST.OPTD
/29.4
E115
/17.3 FS212 BLKB U4 LED 6 SPARE
X:VT 5 E311 2 1 E313 S7 R7 E315 R13 * R14
TO 67/67N

E135 2A /29.4 /30.1


/17.3 LED 7 SPARE
D LK272 BLKB D
E155 6 E371 2 1 E373 S9 R9 E375
/17.3
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 11

/29.4
E175
/17.3
CopyRight (C) Siemens Limited, India All Rights Reserved.

REMOTE END
LOCAL END
(ADYAAR LINE
E (KAVOOR SS)
(IDLE)) E
LINE LENGTH XX KM

Tx Rx
@@1300nm MONOMODE LC CONNECTOR FO CABLE LC LC
LC LC LC
LINE LC LINE
NOTE: DIFFERENTIAL DIFFERENTIAL
LIU Rx Tx LIU$$
RELAY RELAY
1.LIU $$ TO BE MOUNTED IN REMOTE END CRP PANEL.SAME WILL BE SUPPLIED IN THE (7SD522) LC LC @@1300nm MONOMODE LC CONNECTOR FO CABLE LC LC (7SD522)$$
LC LC
REMOTE END PANEL AND NOT IN SIEMENS SCOPE.
2.$$ - REMOTE END RELAY WILL BE SUPPLIED IN THE REMOTE END PANEL AND NOT IN
SIEMENS SCOPE.
3.@@ THUS MARKED CABLES ARE NOT IN SIEMENS SCOPE OF SUPPLY
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 87L/21 Relay CT VT Circuit Sub-Station at Nehru maidan in Mangaluru W11411
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 11 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <10 12>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

/08.4

/08.4
A 87L/21
A

K901

K902
114-52 Power Supply
BLKA
S2 R2 K903 K1 K2
NIT + -
/29.3
NIT /30.1
X:CB 19 K901A 1 2
/29.7
NIT
NIT BI1
X1 X1 X:CB 20 K905A K905 K17 K18
3 4 MAIN/BC CB OPEN
45 46 /29.7 /30.1
CB OPEN
CS1
T AT N AC C BI2
13 14 K907 J1 J2
CB CLOSE COMMAND
B /29.2 /30.1 B

X:S 5 X:S 6

CB HEALTHY CB CLOSE FROM SCADA BI3


XX XX X:CB 21 K909 J3
CB HEALTHY
XX XX /30.1

DWG.NO: (4)G71AHS-EA401-W1240-
SH.NO:02

B/C NIT
NIT
X:CB 40 K901C 45 46
C /29.7 C
Last Used by: z004mx4y

NIT
XX XX NIT
Time: 2:14:34 PM
Date: 12/12/2023

X:CB 41 K905B 47 48
XX CB OPEN XX X:ISO 23 /29.7

BI4
X:ISO 24 K911 J4
114-89D/DE 89D ISOL.OPEN
/30.1
BI5
X:ISO 25 K913 J6 J5
89D ISOL.CLOSE
/30.1

BI6
X:ISO 26 K915 J7 J8
89DE ISOL.OPEN
XX XX /30.1

XX XX BI7
D 89D ISOL.OPEN D
X:ISO 27 K917 J9 J10
89DE ISOL.CLOSE
XX XX /30.1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 12

86A BI8
XX XX 117 118 K921 J11 J12
86A OPTD
89D ISOL.CLOSE /20.6 /30.1
XX XX
86B BI9
XX XX 117 118 K923 P17 P18
86B OPTD
89DE ISOL.OPEN /21.6 /30.1
XX XX
96 BI10
XX XX 117 118 K925 N1 N2
96 OPTD
CopyRight (C) Siemens Limited, India All Rights Reserved.

89DE ISOL.CLOSE /22.7 /30.1

BI11
X:SP 4 X:SP 6 K927 N3
Spare
E /30.1 E
BI12
X:SP 7 K929 N4
Spare
/30.1

BI13
X:SP 8 K931 N6 N5
Spare
/30.1

E-BB PE
K901

K902
PE EW
PE
/13.3

/13.6
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 87L/21 Relay BI Circuit Sub-Station at Nehru maidan in Mangaluru W11412
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 12 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <11 13>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

/12.6
/12.3
A 87L/21
A

K902
K901
BI14
X:SP 9 X:SP 13 K933 N7 N8
Spare
/30.1

BI15
X:SP 14 K935 N9 N10
Spare
B X:SP 10 /30.1 B
BI16
X:SP 15 K937 N11 N12
Spare
/30.1

BI17
X:SP 16 K939 H17 H18
Spare
/30.1

BI18
X:SP 17 K941 G1 G2
Spare
/30.1

C C
Last Used by: z004mx4y

Time: 2:14:51 PM
Date: 07/07/2023

BI19
X:SP 11 X:SP 18 K943 G3
Spare
/30.1

BI20
X:SP 19 K945 G4
Spare
X:SP 12 /30.1

BI21
X:SP 20 K947 G6 G5
Spare
/30.1

BI22
X:SP 21 K949 G7 G8
D Spare D
/30.1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 13

BI23
X:SP 22 K951 G9 G10
Spare
/30.1

BI24
X:SP 23 K953 G11 G12
Spare
/30.1
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

K902
K901

/14.3
/14.4

F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F


B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 87L/21 Relay BI Circuit Sub-Station at Nehru maidan in Mangaluru W11413
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 13 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <12 14>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

A A
87L/21

BO1
K6 L103
/26.2 DIST Z1 OPTD TO ANNUN
/30.1

BO2
K7 L105
/26.2 DIST Z2/3/4 OPTD TO ANNUN
/30.1

BO3
L101 K5 K8 U113 X:SP 113
/26.2 SPARE
/30.1
B B
BO4
K10 K9 U114 X:SP 114
SPARE
/30.1

BO5
K12 K11 L111
/26.2 VT FUSE FAIL TO ANNUN
/30.1

BO6
CMRX .A K901 K14 K13 K901D
/13.3 /14.2 TO CMRX.A
K901D 11 12 K902 /30.1
/14.6 /13.6

13 14
/23.5 TO CB CLOSING BO7
C 108 K16 K15 110 C
Last Used by: z004mx4y

15 16 X:SP U108 U110 X:SP


SPARE
17 18 /30.1
BO8
Time: 2:15:11 PM

R1
Date: 07/07/2023

U26 X:SP 26
/30.1 SPARE
BO9
R2 U27 X:SP 27
/30.1 SPARE
BO10
R3 L141
/26.6 OCR OPTD TO ANNUN
/30.1

BO11
R4 L143
/26.6 EFR OPTD TO ANNUN
/30.1

BO12
L101 R5 R6 L145
D /26.5 /26.6 BRC/PSB TO ANNUN D
/30.1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 14

BLKA BO13
K101 S1 R1 K103 R8 R7 K105
/20.4 /20.5 DISTANCE RELAY OPTD-86A
/29.3 /30.1

BLKB BO14
K201 S1 R1 K201A R10 R9 K205
/21.4 /21.5 DISTANCE RELAY OPTD-86B
/29.4 /30.1
CopyRight (C) Siemens Limited, India All Rights Reserved.

BO15
X:SP 24 U69 R12 R11 U70 X:SP 25
SPARE
/30.1
E E

F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F


B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 87L/21 Relay BO Circuit Sub-Station at Nehru maidan in Mangaluru W11414
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 14 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <13 15>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

A 87L/21
A

BLKA BO16
P101 S8 R8 P101B P4 P3 P103
/22.4 /22.4 LBB Protn optd
/29.3 /31.1

BO17
P6 U28 X:SP 28
/31.1 SPARE
BO18
P7 U29 X:SP 29
B /31.1 SPARE B
BLKA BO19
KT301A S9 R9 KT301B P5 P8 KT303A
/24A.3 /24A.4 TO BC 86.1
/29.3 /31.1

BLKA BO20
KT401A S10 R10 KT401B P10 P9 KT403A
/24A.3 /24A.4 TO BC 86.2
/29.3 /31.1

BO21
K1 P12 P11 K17
/23.4 /23.5 TO TC-1
/31.1

BO22
K51 P14 P13 K61
/24.4 /24.5 TO TC-2
/31.1
C C
Last Used by: z004mx4y

Time: 2:41:29 PM
Date: 12/12/2023

BO23
L101 P16 P15 L129
/26.2 /26.3 LINE DIFF.OPTD TO ANNUN
/31.1

BO24
X:SP 32 U32 H4 H3 U33 X:SP 33
SPARE
/31.1

BO25
H6 X:SP 34
/31.1 SPARE
BO26
H7 X:SP 35
/31.1 SPARE
D D
BLKB BO27
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 15

KT1A S8 R8 KT1B H5 H8 KT3A


/24A.3 /24A.4 TO BC TC-1
/29.4 /31.1

BLKB BO28
KT51A S10 R10 KT51B H10 H9 KT53A
/24A.3 /24A.4 TO BC TC-2
/29.4 /31.1

BO29
X:SP 40 U40 H12 H11 U41 X:SP 41
SPARE
/31.1
CopyRight (C) Siemens Limited, India All Rights Reserved.

BO30
X:SP 42 U42 H14 H13 U43 X:SP 43
SPARE
/31.1
E E
BO31
X:SP 44 U44 H16 H15 U45 X:SP 45
SPARE
/31.1

LC Life Status Contact


L101 K4 K3 L151
/26.6 /26.7
/30.1

F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F


B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 87L/21 Relay BO Circuit Sub-Station at Nehru maidan in Mangaluru W11415
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 15 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <14 16>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

A A

B B

C
Blank sheet C
Last Used by: z004mx4y

Time: 2:15:43 PM
Date: 07/07/2023

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 16
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Sub-Station at Nehru maidan in Mangaluru W11416
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 16 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <15 17>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

110kV BUS SIDE 67/67N


CT JB 67/67N
A LED Configuration
A
X:CT BLKC IA
21 C11 S3 R3 C13 Q1 • Q2
LED-1 OCR TRIP R-PHASE
22 /29.5 /32.1

C75
BLKC IB LED-2 OCR TRIP Y-PHASE
23 C31 S4 R4 C33 Q3 • Q4
24 /29.5 /32.1
LED-3 OCR TRIP B-PHASE
BLKC IC
25 C51 S5 R5 C53 Q5 • Q6
LED-4 EFR OPTD
26 /29.5 /32.1
P2

P2

P2
CT
3S3 3S3 3S3

C71S
CORE-3 LED-5 VT FUSE FAIL
R-PH
RATIO: 400-200/1A BLKC IN/INs
3S1 3S1 3S1 27 C71 S6 R6 C73 Q7 • Q8
CLASS: 5P20, 30VA LED-6 LBB OPTD
B 28 /29.5 /32.1 B
P1

P1

P1

ETL7 LED-7 HISET


C73S 2 1 EW

LINE SIDE

FS19 BLKC VA
E115 X:VT 7 E213 2 1 E215 S7 R7 E217 R1 •
/11.3
C 2A /29.5 /32.1 C
Last Used by: z004mx4y

FS39 BLKC VB
Time: 2:16:11 PM

2 1 S8 R8 •
Date: 07/07/2023

E135 8 E233 E235 E237 R2


BUS PT SUPPLY

/11.3
2A /32.1
SELECTED

/29.5

FS59 BLKC VC
E155 9 E253 2 1 E255 S9 R9 E257 R3 • R4
/11.3
2A /29.5 /32.1

LK79 BLKC
E175 10 E273 2 1 E275 S10 R10 E277 E277
/11.3
/29.5

VL4
R5 • R6
ADJ PANEL /32.1
D D
XB:VT 5
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 17

XB:VT 6

XB:VT 7

XB:VT 8
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 67/67N Relay CT Circuit Sub-Station at Nehru maidan in Mangaluru W11417
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 17 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <16 18>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

67/67N

/08.4

/08.4
A A

K401

K402
BLKC
S2 R2 K403 P1 P2
+ - Power Supply
/29.5
/32.1

86A BI1
123 124 K405 F1 F2 86A TRIP RELAY OPTD
/20.6 /32.1 (LBB INITIATION)

86B BI2
123 124 K407 F3 F4 86B TRIP RELAY OPTD
/21.6 /32.1 (LBB INITIATION)
B B
96 BI3
114-52 123 124 K409 F6 F5
96 TRIP RELAY OPTD
/22.7 /32.1

X:CB 38

BI4
X1 X1 X:CB 39 K411 F7
CB CLOSE STATUS
37 38 /32.1
CB CLOSE

DWG.NO: (4)G71AHS-EA401-W1240- BI5


SH.NO:02 X:SP 46 X:SP 47 K413 F8 F9
Spare
/32.1

BI6
C 48 F11 C
Last Used by: z004mx4y

X:SP K415
Spare
/32.1
Time: 2:16:32 PM
Date: 07/07/2023

BI7
X:SP 49 K417 F12 F10
Spare
/32.1

BI8
X:SP 50 X:SP 51 K419 K1
Spare
/32.1

BI9
X:SP 52 K421 K2
Spare
/32.1

BI10
X:SP 53 K423 K3
D Spare D
/32.1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 18

BI11
X:SP 54 X:SP 55 K425 K4
Spare
/32.1

BI12
X:SP 56 K427 K5
Spare
/32.1

BI13
X:SP 57 K429 K6
Spare
CopyRight (C) Siemens Limited, India All Rights Reserved.

/32.1

BI14
X:SP 58 X:SP 59 K431 K7
Spare
E /32.1 E
BI15
X:SP 60 K433 K8
Spare
/32.1

BI16
X:SP 61 K435 K9 K10
Spare
/32.1
K401

K402
EW
/19.4

/19.3

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 67/67N Relay BI Circuit Sub-Station at Nehru maidan in Mangaluru W11418
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 18 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <17 19>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

67/67N

A A
BLKD BO1
K201 S1 R1 K201B P4 P3 K205
/21.4 /21.5 O/C Protn Optd
/29.5 /32.1

BLKC BO2
K101 S1 R1 K107 P6 P5 K105
/20.4 /20.5 BACKUP O/C & E/F RELAY OPTD
/29.5 /32.1

BO3
P7 U62 X:SP 62
/32.1 Spare

B B
BO4
K401 P9 P8 K401A
/18.3 /19.2 TO CMRX.B
/32.1

CMRX .B
K401A 21 22 K402
/19.6 /18.6
BO6
23 24 L101 P10 P12 L125 DIR O/C PROTN OPTD
/24A.3 TO BC 86.1 /26.2 /26.3 TO ANNUN
25 26 /32.1
/24A.3 TO BC 86.2
27 28
BO5
P11 L127 DIR E/F RELAY OPTD
/26.3
/32.1 TO ANNUN

C C
Last Used by: z004mx4y

BLKD BO7
Time: 2:40:01 PM

S3 R3 P101A K13 K11


Date: 12/12/2023

P101 P103A
/22.4 /22.4 LBB Protn optd
/29.5 /32.1 K12

Live Live Status


L101 K16 K15 L151
/26.6 /26.7
/32.1

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 19
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F


B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 67/67N Relay BO Circuit Sub-Station at Nehru maidan in Mangaluru W11419
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 19 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <18 20>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

A A

/08.5

/08.5
K101

K102
87L/21 Trip Relay
86A
From 87L/21 Relay
K101 K105 K105 212 211 K102A
/14.4 /14.6 O
B 221 B

11
12
13
14
67/67N RU-A
122 121 4X820Ω/5W
From 67/67N Relay R
K101 K105

21
22
23
24
/19.4 /19.6
113 114
/23.4 TO 110kV CB TC-1 CKT
115 116
/24.4 TO 110kV CB TC-2 CKT
117 118
/12.4 TO 87L/21 BI CKT
123 124
/18.4 TO 67/67N BI CKT
213 214
/26.6 TO ANNUN
227 228
/28.2 SPARE

K109
225 226
/23.3 TO 110kV CB CLSG I/L CKT
X:SP 65 X:SP 66 223 224

K105A
FUTURE USE /28.4 SPARE
C C
Last Used by: z004mx4y

Time: 2:17:02 PM
Date: 07/07/2023

PB86A
1-3 1-4
/29.3

86A Trip Relay Supvn


80/86A
12 21

11 13
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 20

28 18
16 17
/26.6 TO ANN
26 27
/28.2 SPARE
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 86A Master Trip Relay Circuit Sub-Station at Nehru maidan in Mangaluru W11420
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 20 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <19 21>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

A A

/08.5

/08.5
K201

K202
87L/21 Trip Relay
86B
From 87L/21 Relay
K201 K205 K205 212 211 K202A
/14.4 /14.6 O
B 221 B

11
12
13
14
67/67N RU-B
K207 122 121 4X820Ω/5W
From 67/67N Relay R
K201 K205

21
22
23
24
/19.4 /19.6
113 114
/23.4 TO 110kV CB TC-1 CKT
115 116
/24.4 TO 110kV CB TC-2 CKT
117 118
/12.4 TO 87L/21 BI CKT
X:SP 67 X:SP 68 123 124
FUTURE USE /18.4 TO 67/67N BI CKT
213 214
/26.6 TO ANNUN

K205A
227 228
/28.2 SPARE
225 226
/23.3 TO 110kV CB CLSG I/L CKT
223 224
/28.4 SPARE
C C
Last Used by: z004mx4y

PB86B
1-3 1-4
/29.4
Time: 2:17:17 PM
Date: 07/07/2023

86B Trip Relay Supvn


80/86B
12 21

11 13

28 18
16 17
/26.6 TO ANN
26 27
/28.2 SPARE
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 21
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 86B Master Trip Relay Circuit Sub-Station at Nehru maidan in Mangaluru W11421
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 21 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <20 22>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ADJ PANEL ADJ PANEL
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

P101

P102

P103

P104

P101

P102

P103

P104
A A

114 CRP

XB:LBB 1

/08.8

/08.8
LBB TRIP BUS-1
B B

LBB TRIP BUS-2


P101

P102
-VE
+VE
P102

From 67/67N Relay D1 LBB Trip Relay


67/67N 96
P101 P103A P103A 1 2 P105 212 211 P102A
/19.4 /19.6 O
LBB OPERATED 221

11
12
13
14
P104
RU-C
87L/21 P107 122 121 4X820Ω/5W
R
69 P101 P103 70

21
22
23
24
X:SP X:SP Resistor Unit for 96
/15.4 /15.6
C C
Last Used by: z004mx4y

113 114
/23.4 TO 110kV CB TC-1 CKT
115 116
89A /24.4 TO 110kV CB TC-2 CKT
Time: 2:38:02 PM
Date: 12/12/2023

X:ISO 16 X:X XX X:X XX X:ISO 17 117 118


/12.4 TO 87L/21 BI CKT
123 124
89A CLOSE /18.4 TO 67/67N BI CKT
213 214
/26.6 TO ANNUN
227 228
/28.4 SPARE
89B
225 226
/23.2 TO 110kV CB CLSG I/L CKT
X:ISO 18 X:X XX X:X XX X:ISO 19 223 224
/28.4 SPARE
89B CLOSE

PB96
1-3 1-4
/29.3
D 96 Trip Relay Supvn D
80/96
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 22

12 21
P103

P109

P101 11 13

28 18
16 17
/26.6 TO ANN
26 27
/28.2 SPARE
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E
5

8
XB:LBB

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 96 LBB Trip Relay Circuit Sub-Station at Nehru maidan in Mangaluru W11422
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 22 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <21 23>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
114 CRP
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114-52
X1
K1 K1 X:CB 1
/08.4 +VE
1
X1
K2 K2 X:CB 2
A /08.4 -VE A
2
NIT CMRX
95X 96 86B 86A NIT .A FSC
13 14 K9D 225 226 K9B 225 226 K9C 225 226 K5B 9 10 K5C X:SP 72 X:SP 74 K7 13 14 K5 2 1 X:CB 3
/25A.6 /22.7 /21.6 /20.6 /29.7 /14.2 10A
FUTURE I/L
REMOTE E/SW OPEN
LRS CS1
L R T AT N AC C REMOTE CLOSE
K41 K9A X:CB 4 X1
1 2 11 12
/29.6 /29.2 16
LRS
L R
K9 11 12 K5A X:S 1 SCADA CLOSE X:S 2
/29.6 COMMAND

K1 X:CB 5
B B
LRS CS1
L R T AT N AC C X1
3 4 K13 1 2 K11 X:CB 6
REMOTE TRIP-1
/29.6 /29.2 7
LRS
L R
K1 15 16 K15 X:S 7 SCADA TRIP X:S 8
/29.6 COMMAND K1 X:CB 7

86A X1
113 114 K17 X:CB 8
/20.6 PROTN TRIP
6
86B
113 114
/21.6 X1
C C
Last Used by: z004mx4y

96 POST CLOSE
113 114 8
/22.7
Time: 2:17:57 PM
Date: 07/07/2023

87L/21
From 87L/21 Relay
K1 K17
/15.4 /15.6

X:SP 71 X:SP 73
FUTURE USE

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 23

TC-1 Supervision Relay


195
12 21

X1
11 13 K21 X:CB 10
PRE CLOSE
9
28 18
/25A.4 To Indication Circuit
16 17
CopyRight (C) Siemens Limited, India All Rights Reserved.

/26.2 TO ANN
26 27
/28.2 SPARE

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd CB TC-1 Circuit Sub-Station at Nehru maidan in Mangaluru W11423
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 23 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <22 24>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP 114-52
CIRCUIT BREAKER 52 (TC-2)
X1
K51 K51 X:CB 11
/08.4 +VE
A 1 A
K52 K52 X:CB 12 -VE
/08.4
2

K51 X:CB 13

LRS CS1
L R T AT N AC C X1
K51 5 6 K57 3 4 K55 X:CB 14
REMOTE TRIP-2
LRS /29.6 /29.2 12
L R
19 20 K59 X:S 9 SCADA TRIP X:S 10
/29.6 COMMAND

K51 X:CB 15

B B
86A X1
115 116 K61 X:CB 16
/20.6 PROTN TRIP
11
86B
115 116
/21.6 X1
96 POST CLOSE
115 116 13
/22.7
87L/21
From 87L/21 Relay
K51 K61
/15.4 /15.6

X:SP 75 X:SP 76
FUTURE USE

C C
Last Used by: z004mx4y

TC-2 Supervision Relay


295
Time: 2:18:14 PM
Date: 07/07/2023

12 21
PRE CLOSE
X1
11 13 K63 X:CB 18
14
28 18
/25A.4 To Indication Circuit
16 17
/26.2 TO ANN
26 27
/28.2 SPARE

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 24
CopyRight (C) Siemens Limited, India All Rights Reserved.

DWG.NO: (4)G71AHS-EA401-W1240-
SH.NO:01

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd CB TC-2 Circuit Sub-Station at Nehru maidan in Mangaluru W11424
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 24 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <23 24A>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1 114 CRP B/C

NIT
A NIT A
KT1A 27 28 KT1 X:BC 1 XX XX
/29.7
87L/21
NIT
NIT TO BC TC-1
KT1A KT3A 29 30 KT3 2 XX
/15.4 /15.6
/29.7
From 87L/21 Relay

NIT
NIT
KT51A 31 32 KT51 X:BC 3 XX XX
/29.7
87L/21
NIT TO BC TC-2
B NIT B
KT51A KT53A 33 34 KT53 4 XX
/15.4 /15.6
/29.7
From 87L/21 Relay

NIT
NIT
KT301A 17 18 K301BC X:BC 5 XX XX
/29.7
87L/21
NIT TO BC 86.1
NIT
KT301A KT303A 19 20 K305BC 6 XX
/15.4 /15.6
/29.7
From 87L/21 Relay

C C
Last Used by: z004mx4y

CMRX
Time: 2:18:31 PM
Date: 07/07/2023

.B
23 24
/19.2

NIT
NIT
KT401A 23 24 K401BC X:BC 7 XX XX
/29.7
87L/21
NIT TO BC 86.2
NIT
KT401A KT403A 25 26 K405BC 8 XX
/15.4 /15.6
/29.7
From 87L/21 Relay
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 24A

CMRX
.B
25 26
/19.2
NOTE:
XX TB’S IDENTIFIED AT THE SITE
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F


B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd TC1 & TC2 Circuit of Buscoupler Sub-Station at Nehru maidan in Mangaluru W11424A
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 24A of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <24 25>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

/10.3

/10.3
114-52
A A

L1

L2
X:CB 22

SL01
X:CB 23 L9 X1 X2
CB OPEN

SL02
X:CB 24 L13 X1 X2
CB CLOSE

CS1 CS1
T AT N AC C T AT N AC C SL03
X:CB 25 L19 9 10 L19A 21 22 L21 X1 X2
B /29.2 /29.2 CB AUTO TRIP
B
SL04
X:CB 26 L23 X1 X2
CB SPRING CHARGED

114-89A
X:ISO 1

SL06
X:ISO 2 L3 X1 X2
ISO 114-89A OPEN

SL07
X:ISO 3 L5 X1 X2
C C
Last Used by: z004mx4y

ISO 114-89A CLOSE


114-89B
Time: 2:18:58 PM
Date: 07/07/2023

X:ISO 4

SL08
X:ISO 5 L39 X1 X2
ISO 114-89B OPEN

SL09
X:ISO 6 L41 X1 X2
ISO 114-89B CLOSE

114-89D
X:ISO 7

D SL10 D
X:ISO 8 L31 X1 X2
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 25

ISO 114-89D OPEN

SL11
X:ISO 9 L33 X1 X2
ISO 114-89D CLOSE
114-89DE
X:ISO 10

SL12
X:ISO 11 L35 X1 X2
CopyRight (C) Siemens Limited, India All Rights Reserved.

ESW 114-89DE OPEN

SL13
X:ISO 12 L37 X1 X2
E ESW 114-89DE CLOSE E
L1

L2
/25A.4

/25A.6
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Indication Circuit Sub-Station at Nehru maidan in Mangaluru W11425
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 25 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <24A 25A>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1

114 CRP

/25.3

/25.6
A A

L1

L2
114-89C
X:ISO 13

SL14
X:ISO 14 L43 X1 X2
ISO 114-89C OPEN

SL15
X:ISO 15 L45 X1 X2
ISO 114-89C CLOSE

B 114-89E B
X:ISO 20

SL16
X:ISO 21 L47 X1 X2
ISO 114-89E OPEN

SL17
X:ISO 22 L49 X1 X2
ISO 114-89E CLOSE

195 SL05
28 18 L11 L11 X1 X2
/23.4
TC HEALTHY
C C
Last Used by: z004mx4y

295 TC Healthy Multiplication


Time: 2:19:18 PM

28 18 95X
Date: 07/07/2023

/24.5 A1 A2

13 14
/23.1 TO CB Closing Ckt
21 22
31 32
43 44

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 25A
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F


B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Indication Circuit Sub-Station at Nehru maidan in Mangaluru W11425A
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 25A of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <25 26>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

FC FC
L101 Common L101 Common
A A

C
114-52
87L/21
L103 L103 DIST Z1 OPTD X:CB 34 CB SF6 X:CB 35 L135 CB SF6 LOCKOUT

17
/14.6

1
T

T
LOCKOUT

From 87L/21 Relay CB SF6 GAS PRE


L105 L105 DIST Z2/3/4 OPTD X:CB 36 LOW ALARM X:CB 37 L137 CB SF6 GAS PRE LOW ALARM

NT
18
/14.6

2
T
80/96
X:SP 111 L107 SPARE 16 17 L139 TRIP RELAY 96 DC FAIL

NT
19
3
T
87L/21 /22.4
L101
/14.4
L141 L141 DIST OCR OPTD

20
/14.6

T
B X:SP 112 L109 SPARE B

4
T
From 87L/ 21 Relay
L101
/14.4
L111 L111 VT FUSE FAIL L143 L143 DIST EFR OPTD

NT

21
/14.6 /14.6

T
195
16 17 L113 CB TC1 FAULTY

NT
6
/23.4 L145 L145 BRC/PSB

22
/14.6

T
295
16 17 L115 CB TC2 FAULTY

NT
7
/24.5
80/86A
16 17 L147 TRIP RELAY 86A DC FAIL

NT
23
LRS /20.5
C C
Last Used by: z004mx4y

L R
13 14 L117 SWITCH IN SCADA POS

NT
8
80/86B
Time: 2:19:42 PM

/29.6 16 17 TRIP RELAY 86B DC FAIL


Date: 07/07/2023

L149

NT
24
/21.5

TRIPPED THRU
X:S 3 SCADA X:S 4 L119 TRIPPED THROUGH SCADA L101 Common

C
9
T
87L/21
80B
16 17
From 87L/21 Relay
/08.3 L101 L151 L151 NUMERICAL RELAY FAULTY

NT
25
80A /15.4 /15.6
16 17 L121 MAIN DC FAIL
NT
10

/08.3
114-52
67/67N
D D
X:CB 27 CB CTD OPTD X:CB 28 L123 CB CTD OPTD L101 L151
NT
11

/19.4 /19.6
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 26

From 67/67N Relay

67/67N
L101 L125 DIR O/C PROTN OPTD
12

/19.4 /19.6
T

From 67/67N Relay 86A


213 214 L153 TRIP RELAY OPTD

26
T
L127 DIR E/F RELAY OPTD /20.6 (86A,86B& 96)
13

/19.6
T
CopyRight (C) Siemens Limited, India All Rights Reserved.

86B
87L/21 213 214
/21.6 AC FAIL

NT
27
L101 L129 LINE DIFF.OPTD
14

/15.4 /15.6 96
T

E 213 214 E
114-52 /22.7 DC FAIL

NT
28
X:CB 30 X:CB 31 L131 CB AC FAIL
NT
15

CB AC FAIL
L101 Common

C
X:CB 32 CB DC FAIL X:CB 33 L133 CB DC FAIL
NT
16

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Annuciation Circuit Sub-Station at Nehru maidan in Mangaluru W11426
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 26 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <25A 27>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


ADJ PANEL ADJ PANEL 114 CRP

A A

/08.8

/08.8

/07.4

/07.4
EBZ

FC

L101

L102

H32

H31
+

Ph
Ne
-(T1)
-(T2)
H31 230V AC PH

PH
PH
H32 230V NEU

NU
NU
H31
H31 XB:ANN 1 DF1

DF1
C
B H33 B
H33 XB:ANN 2 H33 DF2

DF2
C
L101 220V DC (-Ve)

-VE
-VE
L102 220V DC (+Ve)

+VE
+VE
L157
L157 XB:ANN 3 L157 Bell

T1
T1
L102A Trip Alarm

L102A XB:ANN 4 L102 Bell

T2
T2
L159 Trip Alarm

L159 XB:ANN 5 L159 Hooter

NTI
NTI
Non Trip Alarm
C L102B C
Last Used by: z004mx4y

L102B XB:ANN 6 L102 Hooter

NT2
NT2
Non Trip Alarm
Time: 2:19:59 PM
Date: 07/07/2023

L161 Common

C
PB01
1-4 1-3 L163 Accept

A
/29.4
PB02
1-4 1-3 L165 Reset

R
/29.4
PB03
1-4 1-3 L167 Lamp Test

LT
/29.4

EW

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 27
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Annunciation Circuit Sub-Station at Nehru maidan in Mangaluru W11427
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 27 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <26 28>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

A A

U77 X:SP 77 U93 X:SP 93

86B 86A
227 228 U78 X:SP 78 223 224 U94 X:SP 94
/21.6 /20.6

U79 X:SP 79 U95 X:SP 95


B B
80/96 96
26 27 U80 X:SP 80 227 228 U96 X:SP 96
/22.4 /22.7
SPARE

U81 X:SP 81 U97 X:SP 97

86A 96
227 228 U82 X:SP 82 223 224 U98 X:SP 98
/20.6 /22.7

U83 X:SP 83
U99 X:SP 99
80/86A
C 26 27 U84 84 C
Last Used by: z004mx4y

X:SP
/20.5 86B
SPARE 223 224 U100 X:SP 100
/21.6
Time: 2:20:20 PM
Date: 07/07/2023

U85 X:SP 85

80/86B
26 27 U86 X:SP 86
/21.5 U103 X:SP 103
SPARE

80B
U87 X:SP 87 28 18 U104 X:SP 104
/08.3
80A
28 18 U88 X:SP 88
/08.3
Spare
D D
U89 X:SP 89
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 28

195
26 27 U90 X:SP 90
/23.4
SPARE

U91 X:SP 91

295
26 27 U92 X:SP 92
/24.5
SPARE
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Spare Contact Distribution Sub-Station at Nehru maidan in Mangaluru W11428
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 28 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <27 29>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


114 CRP

BLKA BLKB BLKD


A BLKC A
CS1 S1 R1 S1 R1 S1 R1 S1 R1
/14.4 /14.4 /19.4 /19.4
T AT N AC C S2 R2 S2 R2 S2 R2 S2 R2
/12.4 /18.4
1 2 S3 R3 S3 R3 S3 R3 S3 R3 NIT
/23.5 1 /11.5 /11.5 /17.5 /19.4
S4 R4 S4 R4 S4 R4 S4 R4 NIT
3 4 /11.5 /11.5 /17.5
/24.5 2 S5 R5 S5 R5 S5 R5 S5 R5 1 2
/11.5 /11.5 /17.5 LRS /12.3 1
5 6 S6 R6 S6 R6 S6 R6 S6 R6 L R
3 /11.5 /11.5 /17.5 3 4
S7 R7 S7 R7 S7 R7 S7 R7 1 2 /12.4 2
7 8 /11.5 /17.5 /23.3 1
4 S8 R8 S8 R8 S8 R8 S8 R8 5 6
/15.4 /15.4 /17.5 3 4 3
9 10 S9 R9 S9 R9 S9 R9 S9 R9 /23.3 2
/25.4 5 /15.4 /11.5 /17.5 7 8
S10 R10 S10 R10 S10 R10 S10 R10 5 6 4
11 12 /15.4 /15.4 /17.5 /24.3 3
/23.5 6 9 10
7 8 /23.4 5
13 14 4
/12.4 7 11 12
B 9 10 6 B
15 16 5
8 13 14
11 12 7
17 18 /23.3 6
9 15 16
13 14 8
19 20 /26.2 7
10 17 18
15 16 /24A.5 9
21 22 /23.3 8
/25.5 11 19 20
17 18 /24A.5 10
23 24 9
12 21 22
19 20 11
PB86A PB01 PB86B PB52 /24.3 10
23 24
1-3 1-4 1-3 1-4 1-3 1-4 1-3 1-4 /24A.5 12
/20.4 /27.4 /21.4
2-1 2-2 2-1 2-2 2-1 2-2 2-1 2-2 25 26
/08.2 /24A.5 13
27 28
C /24A.5 14 C
Last Used by: z004mx4y

PB96 PB02 PB53 PTS-1 PTS-2 29 30


/24A.5 15
Time: 2:20:50 PM

BUS-1 PT BUS-2 PT BUS-1 PT BUS-2 PT


Date: 07/07/2023

1-3 1-4 1-3 1-4 1-3 1-4


/22.4 /27.4 /07.6 DC FAIL ACCEPT 31 32
2-1 2-2 2-1 2-2 2-1 2-2 1 2 1 2 /24A.5 16
/08B.2 1 /08B.6 1
33 34
3 4 3 4 /24A.5 17
CILS /08B.2 2 /08B.6 2
35 36
13 14 PB03 PB51 5 6 5 6 18
/08B.2 3 /08B.6 3
21 22 1-3 1-4 1-3 1-4 37 38
/07.3 /27.4 7 8 7 8 19
2-1 2-2 2-1 2-2 /08B.2 4 /08B.6 4
/08.3 39 40
9 10 9 10 20
5 5
41 42
11 12 11 12 21
/08B.2 6 /08B.6 6
43 44
13 14 13 14 22
D /08B.2 7 /08B.6 7 D
45 46
15 16 15 16 /12.3 23
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 29

/08B.2 8 /08B.6 8
47 48
17 18 17 18 /12.4 24
/08B.2 9 /08B.6 9
19 20 19 20
10 10
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Test Block & switch Distribution Circuit Sub-Station at Nehru maidan in Mangaluru W11429
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 29 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <28 30>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
: Case Size: 1/1 19”, 4xI, 4xV, 24 BI, 31 BO, 1 Live Status, 14 LED, Flush Mounting
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


Designation Technical Specifications:
Type : 7SD52 Region World, 50/60 Hz, IEC/ANSI, Language English (UK) (Language Can Be Changed)
Port B: IEC61850, Electrical EN100, Double, RJ45 Connector
Manufacturer : Siemens FO18, Optical 1300 nm, Duplex LC Connector, For Distances Up To 60km, Via Monomode FO Cable for Direct FO Connection
Single-/Three-Pole Tripping, With Automatic Reclosure, With Synchro-Check
Order No. : 7SD5221-5DB99-9HK4+L0R+M0H+N7H Overcurrent Time Protection / Circuit Breaker Failure Protection (CBF), +With Earth Fault Protection, +Pickup Z<, Polygon, With Power Swing Option, With Parallel Line Compensation
Product Code : 7SD5221-5DB99-9HK4+L0R+M0H+N7H 4 Remote Commands / 24 Remote Indications, +Fault Locator - 1 Side, +Voltage and Frequency Protection
Capacitive Current Load Compensation
Current : Iph = 1A, Ie = 1A
A Voltage : DC 110-250V, AC 115V, Binary Input Threshold 88V A
Add. Info. 1 : CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 110-250V DC, 115V AC, BI Threshold 88V
Add. Info. 2 : IEC61850, Electrical EN100, Double, RJ45 Connector

Comment Remarks Location Equipment Function


Line Differential/Distance Protection 250 87L/21

Power Supply

-
B B

D
A

F
PE
K1

K2
/12.6 /12.6

IL1 IL2 IL3 I4

Current Inputs
*

*
Q1
Q2

Q3
Q4

Q5
Q6

Q7
Q8
C C
Last Used by: z004mx4y

87L/21 /11.6 /11.6 /11.6


Time: 2:21:17 PM
Date: 07/07/2023

UL1 UL2 UL3 U4

Voltage Inputs
*

*
R15

R17

R18
R16

R13
87L/21 /11.6 /11.6 /11.6 /11.6R14

BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 30

Input 1-16
L+

L+

L+

L+

L+

L+

L+

L+

L+

L+

L+

L+

L+

L+

L+

L+
N10

N11
N12
K17
K18

P17
P18
J10

J11
J12

N1
N2

N3

N4

N6
N5

N7
N8

N9
J1
J2

J3

J4

J6
J5

J7
J8

J9
87L/21 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /13.5 /13.5 /13.5

BI17 BI18 BI19 BI20 BI21 BI22 BI23 BI24


CopyRight (C) Siemens Limited, India All Rights Reserved.

Input 17-24
L+

L+

L+

L+

L+

L+

L+

L+
E G10 E

G11
G12
H17
H18

G1
G2

G3

G4

G6
G5

G7
G8

G9

87L/21 /13.5 /13.5 /13.5 /13.5 /13.5 /13.5 /13.5 /13.5

LC BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 BO15
2 3

2 3

1
X40

X41
Life Status Contact

2
2

2
Output (20x BO, 12x Fast)

R10

R11
R12
K10

K11
K12

K13
K14

K15
K16

R1

R2

R3

R4

R6
R5

R7
R8

R9
K3
K4

K6

K7

K8
K5

K9

F 87L/21 /15.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Connection Diagram For 67/67N Sub-Station at Nehru maidan in Mangaluru W11430
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 30 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <29 31>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


BO16 BO17 BO18 BO19 BO20 BO21 BO22 BO23 BO24 BO25 BO26 BO27 BO28 BO29 BO30 BO31

1
Output (20x BO, 12x Fast)

2
2

2
A A

H10

H11
H12

H13
H14

H15
H16
P10

P11
P12

P13
P14

P15
P16

H3
H4

H6

H7

H8
H5

H9
P3
P4

P6

P7

P8
P5

P9
87L/21 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5

B B

C C
Last Used by: z004mx4y

Time: 2:21:33 PM
Date: 07/07/2023

D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 31
CopyRight (C) Siemens Limited, India All Rights Reserved.

E E

F Unless otherwise specified, wires are PVC, 1.5mm Sq, GY F


B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Connection Diagram For 87L/21 Sub-Station at Nehru maidan in Mangaluru W11431
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 31 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <30 32>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1


Designation : Case Size: 1/3 19”, 4xI, 4xV, 16 BI, 7 BO, 1 Live Status, 7 LED, Flush Mounting Technical Specifications:
Type : 7SJ66
Manufacturer : Siemens
Order No. : 7SJ6611-5DB90-1FC0+L0R
Product Code :
A Current :
A
Voltage :
Add. Info. 1 : CT Sec: 1A, PT Sec: 110V AC, Aux Supply: 110-250V DC, 115-230V AC, BI Threshold 88V
Add. Info. 2 : IEC 61850, 100 Mbit Ethernet, Electrical, Double, RJ45 Connector

Comment Remarks Location Equipment Function


Backup Protection 250 67/67N

Time Synchronization
Live

System Interface
3

1
B B

FP
K15
K16
PE

FP
P1

P2

B
/18.5 /19.5

IA IB IC IN/INs

Current Inputs


C C
Last Used by: z004mx4y

Q1
Q2

Q3
Q4

Q5
Q6

Q7
Q8
Time: 2:21:54 PM

67/67N /17.6 /17.6 /17.6 /17.6


Date: 07/07/2023

VA VB VC VL4

Voltage Inputs


R1

R2

R3
R4

R5
R6
67/67N /17.6 /17.6 /17.6 /17.6

D BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16 D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 32

Input 1-16

K10
F11

F12
F10

K1

K2

K3

K4

K5

K6

K7

K8

K9
F1
F2

F3
F4

F6
F5

F7

F8
F9

67/67N /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5
CopyRight (C) Siemens Limited, India All Rights Reserved.

BO1 BO2 BO3 BO4 BO5 BO6 BO7

Output 1-7
E E
P11

P12
P10

K12
K11
K13
P3
P4

P5
P6

P7

P8
P9

67/67N /19.5 /19.5 /19.5 /19.5 /19.5 /19.5 /19.5

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Connection Diagram For 87L/21 Sub-Station at Nehru maidan in Mangaluru W11432
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 32 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <31 33>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1 BI/BO Table


Design. BI/BO Comments Sheet Ref. Design. BI/BO Comments Sheet Ref. Design. BI/BO Comments Sheet Ref.
A A

86A TRIP RELAY OPTD DIR E/F RELAY OPTD


67/67N BI1 /W114/18.5 67/67N BO5 /W114/19.5
(LBB INITIATION) TO ANNUN

86B TRIP RELAY OPTD DIR O/C PROTN OPTD


67/67N BI2 /W114/18.5 67/67N BO6 /W114/19.5
(LBB INITIATION) TO ANNUN

96 TRIP RELAY OPTD LBB Protn optd


67/67N BI3 /W114/18.5 67/67N BO7 /W114/19.5

CB CLOSE STATUS
67/67N BI4 /W114/18.5
B B
Spare
67/67N BI5 /W114/18.5

Spare
67/67N BI6 /W114/18.5

Spare
67/67N BI7 /W114/18.5

Spare
67/67N BI8 /W114/18.5
C C
Last Used by: z004mx4y

Spare
67/67N BI9 /W114/18.5
Time: 2:22:07 PM
Date: 12/12/2023

Spare
67/67N BI10 /W114/18.5

Spare
67/67N BI11 /W114/18.5

Spare
67/67N BI12 /W114/18.5

D D
Spare
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 33

67/67N BI13 /W114/18.5

Spare
67/67N BI14 /W114/18.5

Spare
67/67N BI15 /W114/18.5
CopyRight (C) Siemens Limited, India All Rights Reserved.

Spare
67/67N BI16 /W114/18.5

E E
O/C Protn Optd
67/67N BO1 /W114/19.5

BACKUP O/C & E/F RELAY OPTD


67/67N BO2 /W114/19.5

Spare
67/67N BO3 /W114/19.5

TO CMRX.B
67/67N BO4 /W114/19.5

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd BI/BO Table Sub-Station at Nehru maidan in Mangaluru W11433
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 33 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <32 34>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8

DB Version: SL-V 1.1-08/01/2019


E-Base Version: 7.1.0.1305

Sheet Version: V 1.1 BI/BO Table


Design. BI/BO Comments Sheet Ref. Design. BI/BO Comments Sheet Ref. Design. BI/BO Comments Sheet Ref.
A A

MAIN/BC CB OPEN Spare SPARE


87L/21 BI1 /W114/12.6 87L/21 BI21 /W114/13.5 87L/21 BO17 /W114/15.5

CB CLOSE COMMAND Spare SPARE


87L/21 BI2 /W114/12.6 87L/21 BI22 /W114/13.5 87L/21 BO18 /W114/15.5

CB HEALTHY Spare TO BC 86.1


87L/21 BI3 /W114/12.6 87L/21 BI23 /W114/13.5 87L/21 BO19 /W114/15.5

89D ISOL.OPEN Spare TO BC 86.2


87L/21 BI4 /W114/12.6 87L/21 BI24 /W114/13.5 87L/21 BO20 /W114/15.5
B B
89D ISOL.CLOSE DIST Z1 OPTD TO ANNUN TO TC-1
87L/21 BI5 /W114/12.6 87L/21 BO1 /W114/14.5 87L/21 BO21 /W114/15.5

89DE ISOL.OPEN DIST Z2/3/4 OPTD TO ANNUN TO TC-2


87L/21 BI6 /W114/12.6 87L/21 BO2 /W114/14.5 87L/21 BO22 /W114/15.5

89DE ISOL.CLOSE SPARE LINE DIFF.OPTD TO ANNUN


87L/21 BI7 /W114/12.6 87L/21 BO3 /W114/14.5 87L/21 BO23 /W114/15.5

86A OPTD SPARE SPARE


87L/21 BI8 /W114/12.6 87L/21 BO4 /W114/14.5 87L/21 BO24 /W114/15.5
C C
Last Used by: z004mx4y

86B OPTD VT FUSE FAIL TO ANNUN SPARE


87L/21 BI9 /W114/12.6 87L/21 BO5 /W114/14.5 87L/21 BO25 /W114/15.5
Time: 2:22:17 PM
Date: 12/12/2023

96 OPTD TO CMRX.A SPARE


87L/21 BI10 /W114/12.6 87L/21 BO6 /W114/14.5 87L/21 BO26 /W114/15.5

Spare SPARE TO BC TC-1


87L/21 BI11 /W114/12.6 87L/21 BO7 /W114/14.5 87L/21 BO27 /W114/15.5

Spare SPARE TO BC TC-2


87L/21 BI12 /W114/12.6 87L/21 BO8 /W114/14.5 87L/21 BO28 /W114/15.5

D D
Spare SPARE SPARE
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 34

87L/21 BI13 /W114/12.6 87L/21 BO9 /W114/14.5 87L/21 BO29 /W114/15.5

Spare OCR OPTD TO ANNUN SPARE


87L/21 BI14 /W114/13.5 87L/21 BO10 /W114/14.5 87L/21 BO30 /W114/15.5

Spare EFR OPTD TO ANNUN SPARE


87L/21 BI15 /W114/13.5 87L/21 BO11 /W114/14.5 87L/21 BO31 /W114/15.5
CopyRight (C) Siemens Limited, India All Rights Reserved.

Spare BRC/PSB TO ANNUN


87L/21 BI16 /W114/13.5 87L/21 BO12 /W114/14.5

E E
Spare DISTANCE RELAY OPTD-86A
87L/21 BI17 /W114/13.5 87L/21 BO13 /W114/14.5

Spare DISTANCE RELAY OPTD-86B


87L/21 BI18 /W114/13.5 87L/21 BO14 /W114/14.5

Spare SPARE
87L/21 BI19 /W114/13.5 87L/21 BO15 /W114/14.5

Spare LBB Protn optd


87L/21 BI20 /W114/13.5 87L/21 BO16 /W114/15.5

F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd BI/BO Table Sub-Station at Nehru maidan in Mangaluru W11434
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 34 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <33 ->