110kv Adyaar Line (Idle) C&R Panel
110kv Adyaar Line (Idle) C&R Panel
A A
SI DG EA
Main Cover Sheet
KPTCL LOI Ref: No. CEE/ T&P/SEE-2/KCO-150/43160/2022-23/7918-31 Dtd.07.07.2022.
Work A:Up-gradation of 2x5MVA, 33/11kV Sub-station at Nehru Maidan to 1x20 MVA, 110/
33kV & 2x 10 MVA, 110/11KV GIS Sub-Station and running of 110kV, 1Cx 630 sq.mm. XLPE UG
cable SC Line for a route length of 3.405 kms from existing 110kV Bejai Sub-Station to the
B proposed 110/33/11kV Nehru Maidan GIS sub-station along with construction of one number of B
110kV Terminal bay at existing 110kV Bejai sub-station in Mangaluru Taluk ,Dakshina kannada
district.
Work B:Construction of 110kV SC line by 630sqmm XLPE single core UG Cable in RCC duct, from
Loc .No.1 of 220kv Varahi-kavoor DC line to the new 110kV Bay inside the premises of 220kV
SRS Kavoor for a route length of 0.40Km in Mangaluru Taluk , Dakshina kannada District.
-On Total Turnkey Basis including Design ,Testing ,Supply of GIS and UG Cable , Supply of all
equipment's/ Materials including Mandatory spares, Erection (including Civil Works ),of all
C materials / equipment's, Testing & commissioning. C
Last Used by: z004mx4y
Time: 2:06:34 PM
Date: 07/07/2023
End Customer
Karnataka Power Transmission
Corporation Ltd
Consultant
-
D EPC/Contractor D
Sharavathy Conductors Pvt Ltd.
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel 114 01
Title
110kV ADYAAR Line (IDLE) C&R Panel
AUX.SUPPLY:220V DC
Drawing No.
(4)G719EA-OG9228-03-114
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Main Cover Sheet Sub-Station at Nehru maidan in Mangaluru 11401
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. For CRP Sh. 01 of 2
3008052247 (4)G719EA-OG9228-03-114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Main Cover Sheet < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1. The revision no. of the drawing is changed whenever changes are asked by client.
A A
The revision no. is continuous from 0, A, B, C….. & so on.
2. The version no. of the drawing is changed whenever the drawing is revised whether due to client’s comments, engineering changes,
factory changes, site comments etc. The version no. is continuous from 0, 1, 2, 3….. & so on.
3. The sheets which are changed can be tracked from the sheet “Summary of Amendments”.
The revision no., version no. and the corresponding reason for amendment is reflected on the “Summary of Amendments” sheet.
B B
C C
Last Used by: z004mx4y
Time: 2:06:48 PM
Date: 12/12/2023
SUMMARY OF AMENDMENTS
04 -- -- -- -- -- --
05 -- -- - -- -- --
06 -- -- -- -- -- --
07 -- -- -- -- -- --
CopyRight (C) Siemens Limited, India All Rights Reserved.
08 -- -- -- -- -- --
09 -- -- - -- -- --
E E
10 -- -- -- -- -- --
11 -- -- - -- -- --
12 -- -- -- -- -- --
13 -- -- -- -- -- --
14 -- -- -- -- -- --
15 -- -- - -- -- --
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Summary of Amendments Sub-Station at Nehru maidan in Mangaluru 11402
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 02 of 2
3008052247 (4)G719EA-OG9228-03-114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Main Cover Sheet <01 ->
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
SI DG EA
Equipment List
B B
C C
Last Used by: z004mx4y
Time: 2:06:59 PM
Date: 06/26/2023
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 01
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd COVER SHEET Sub-Station at Nehru maidan in Mangaluru E11401
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 01 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
295 ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
TC-2 Supervision Relay 1MYN 569 339-A
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
80/86A ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
86A Trip Relay Supvn 1MYN 569 339-A
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
80/86B ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
86B Trip Relay Supvn 1MYN 569 339-A
C C
Last Used by: z004mx4y
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
80/96 ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
Time: 2:07:10 PM
Date: 12/12/2023
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
80A ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
DC-1 Supvn Relay 1MYN 569 339-A
Aux Voltage: 110/220V DC, Contacts: 1NO+2NC, S/R, Flag: Yes (LED)
Relay, Contactor TSR-B
80B ABB, India Case Size: 2U 6C, Dropout Delay ≥ 300ms Boughtout Front Mount 1
DC-2 Supvn Relay 1MYN 569 339-A
Aux Voltage: 48V DC, Contacts: 6NO+2NC, H/R or E/R, Flag: Yes
Relay, Contactor RXMVB2
86A ABB, India Case Size: 2U 12C Boughtout Front Mount 1
Trip Relay 1MYN563035-AH
Use With RXTMA Series Resistor
D D
Aux Voltage: 48V DC, Contacts: 6NO+2NC, H/R or E/R, Flag: Yes
Relay, Contactor RXMVB2
86B ABB, India Case Size: 2U 12C Boughtout Front Mount 1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 02
Contacts: 1NO+1NC
Push Button 3SB5
PB02 Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
Annun.Reset 3SB50 00-0AB01+3SB54 00-0A
Contacts: 1NO+1NC
Push Button 3SB5
PB51 Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
DC-1 FAIL TEST 3SB50 00-0AB01+3SB54 00-0A
Contacts: 1NO+1NC
Push Button 3SB5
PB52 Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
DC-2 FAIL TEST 3SB50 00-0AB01+3SB54 00-0A
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11402
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 02 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <01 03>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Contacts: 1NO+1NC
Push Button 3SB5
PB86A Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
86 Reset 3SB50 00-0AB01+3SB54 00-0A
Contacts: 1NO+1NC
Push Button 3SB5
PB86B Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
86 Reset 3SB50 00-0AB01+3SB54 00-0A
Contacts: 1NO+1NC
Push Button 3SB5
PB96 Siemens, India Actuator Colour: Black, Type: With Plastic Front Ring Boughtout Front Mount 1
96 Reset 3SB50 00-0AB01+3SB54 00-0A
B B
Contacts: 1NO+1NC
Push Button 3SB5
PB01 Siemens, India Actuator Colour: Yellow, Type: With Plastic Front Ring Boughtout Front Mount 1
Annun.Accept 3SB50 00-0AD01+3SB54 00-0A
Contacts: 1NO+1NC
Push Button 3SB5
PB03 Siemens, India Actuator Colour: Green, Type: With Plastic Front Ring Boughtout Front Mount 1
Annun.Test 3SB50 00-0AE01+3SB54 00-0A
3 Positions, 12 Ways, Handle Type: Pistol Grip, Black, Spring Return To Neutral With LMD
Switch BC
CS1 Recom, India Non-Lockable, Postions: Trip (T)-Neutral (N)-Close (C), Rating:25A Boughtout Front Mount 1
CB Control Switch BC251P484SIE1A/244LMR
POS1 (-45°): T-4Ways, POS 2 (0°): N-1Ways, (T-AT-2Ways+C-AC-2Ways), POS3 (+45°): C-3Ways
4 Positions, Angle Interval: 90°, Handle Type: Stayput
Switch PCS
VSS Recom, India Positions: OFF-RY-YB-BR, Frequency: 50Hz, Rating: 25A Boughtout Front Mount 1
Selector Switch PCS25P339VM
D D
2 Positions, 10 Ways, Handle Type: Pistol Grip, Stayput
Switch PDS
PTS-1 Recom, India Non-Lockable, Positions: BUS-1 PT-BUS-2 PT, Rating: 25A Boughtout Front Mount 1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 03
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11403
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 03 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <02 04>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
TC HEALTHY 3SB5235-6HG14
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11404
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 04 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <03 05>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Thermostat TH3090240VAC
3NW 3NW20NNSF+3NWNNSL
E Rating: 10A E
Fuse Holder+Fuse 3NW
FS1 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10
Rating: 10A
Fuse Holder+Fuse 3NW
FS15 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10
Rating: 10A
Fuse Holder+Fuse 3NW
FS16 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10
Rating: 10A
Fuse Holder+Fuse 3NW
FS2 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11405
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 05 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <04 06>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Rating: 10A
Fuse Holder+Fuse 3NW
FS8 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10
Rating: 10A
Fuse Holder+Fuse 3NW
FSC Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS10
Rating: 16A
Fuse Holder+Fuse 3NW
FS101 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16
B B
Rating: 16A
Fuse Holder+Fuse 3NW
FS102 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16
Rating: 16A
Fuse Holder+Fuse 3NW
FS201 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16
Rating: 16A
Fuse Holder+Fuse 3NW
FS202 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16
Rating: 16A
Fuse Holder+Fuse 3NW
FS91 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS16
C C
Last Used by: z004mx4y
Rating: 4A
Fuse Holder+Fuse 3NW
FS13 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
Time: 2:07:48 PM
Date: 12/12/2023
3NW 3NW20NNSF+3NWNS4
Rating: 4A
Fuse Holder+Fuse 3NW
FS14 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS4
Rating: 6A
Fuse Holder+Fuse 3NW
FS10 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
Rating: 6A
Fuse Holder+Fuse 3NW
FS11 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
D D
Rating: 6A
Fuse Holder+Fuse 3NW
FS12 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 06
3NW 3NW20NNSF+3NWNS6
Rating: 6A
Fuse Holder+Fuse 3NW
FS17 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
Rating: 6A
Fuse Holder+Fuse 3NW
FS18 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
CopyRight (C) Siemens Limited, India All Rights Reserved.
Rating: 6A
Fuse Holder+Fuse 3NW
FS21 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
E Rating: 6A E
Fuse Holder+Fuse 3NW
FS22 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
Rating: 6A
Fuse Holder+Fuse 3NW
FS3 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
Rating: 6A
Fuse Holder+Fuse 3NW
FS4 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
Rating: 6A
Fuse Holder+Fuse 3NW
FS5 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11406
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 06 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <05 07>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Rating: 6A
Fuse Holder+Fuse 3NW
FS9 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
Rating: 6A
Fuse Holder+Fuse 3NW
FS92 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
Rating: 6A
Fuse Holder+Fuse 3NW
FS93 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW20NNSF+3NWNS6
B B
Solid Link With Holder
Link Holder+Link 3NW
ETL1 Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNNSL
3NW 3NW32NNSF+3NWNNSL
Rating: 2A
Fuse Holder+Fuse 3NW
FS19 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
D D
Rating: 2A
Fuse Holder+Fuse 3NW
FS211 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 07
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS212 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS231 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
CopyRight (C) Siemens Limited, India All Rights Reserved.
Rating: 2A
Fuse Holder+Fuse 3NW
FS251 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
E Rating: 2A E
Fuse Holder+Fuse 3NW
FS311 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS331 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS351 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS39 Siemens, India Aux Voltage: 220 V DC Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11407
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 07 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <06 08>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B1C1B Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B1C1R Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B1C1Y Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
B B
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B1C2B Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B1C2R Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B1C2Y Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B2C1B Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
C C
Last Used by: z004mx4y
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B2C1R Siemens, India Boughtout Internal Mount 1
Time: 2:08:07 PM
Date: 12/12/2023
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B2C1Y Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B2C2B Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B2C2R Siemens, India Boughtout Internal Mount 1
3NW 3NW32NNSF+3NWNS2
D D
Rating: 2A
Fuse Holder+Fuse 3NW
FS-B2C2Y Siemens, India Boughtout Internal Mount 1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 08
3NW 3NW32NNSF+3NWNS2
3P4W3E, Accuracy: 0.5, DC O/P: 4-20mA, Dual O/P With Isolation, Frequency: 50Hz
Transducer PD3
MVART AE, India Aux Supply: 220V DC, 4mA/12mA/20mA Corres. To (-80)MVAR/(0)MVAR/(+80)MVAR Boughtout Internal Mount 1
Power Transducer PD3
CTR: 400-200/1A, PTR: 110kV/110V, Range: (-80)-0-(80) MVAR
3P4W3E, Accuracy: 0.5, DC O/P: 4-20mA, Dual O/P With Isolation, Frequency: 50Hz
Transducer PD3
MWT AE, India Aux Supply: 220V DC, 4mA/12mA/20mA Corres. To (-80)MW/(0)MW/(+80)MW Boughtout Internal Mount 1
Power Transducer (MW) PD3
CTR: 400-200/1A, PTR: 110kV/√3/110V/√3 AC, Range: (-80)-0-(80) MW
Aux Voltage: 230V AC
Audible Device ALA
EB Alan, India Electronic Bell, Clamp Mounting Type Boughtout Internal Mount 1
Electronic Bell ALA
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11408
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 08 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <07 09>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
B B
C C
Last Used by: z004mx4y
Time: 2:08:18 PM
Date: 12/12/2023
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 09
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials Sub-Station at Nehru maidan in Mangaluru E11409
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 09 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <08 10>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
NO. OF CROSS
DETAILS MANUFACTURER MODEL DESCRIPTION DIS COLOR LENGTH QTY.
A CORES SECTION A
Patch Cable Non Rugged Multimode FO Patch Cable 1300nm, Core Size 62.5µm, Clad Size 125µm
FO Cable LC-LC
FO Patch Cable 1300nm_LC-LC Preston Type of Material: Glass, Number of Fibers: 2 (Rx) ( Tx), Un-Armored Boughtout OR 3.00 m 1
FO Patch Cable 1300nm_LC-LC
(3 Meters) Both End Connectors: LC-LC, Outer Sheath Colour: Orange, Length: 3 Meters
B B
C C
Last Used by: z004mx4y
Time: 2:08:28 PM
Date: 06/26/2023
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel E114 10
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated E 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Bill of Materials-Cable Sub-Station at Nehru maidan in Mangaluru E11410
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 10 of 10
3008052247 (4)G719EA-OG9228-03-E114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Equipment List <09 ->
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
SI DG EA
General Arrangement
B B
C C
Last Used by: z004mx4y
Time: 2:08:39 PM
Date: 06/26/2023
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel F114 01
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated F 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd COVER SHEET Sub-Station at Nehru maidan in Mangaluru F11401
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 01 of 3
3008052247 (4)G719EA-OG9228-03-F114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: General Arrangement < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
▲2 DESIGN.
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
(Board)
8 SL04 CB SPRING CHARGED 3SB5
A
9 SL05 TC HEALTHY 3SB5
2000 A1 A2 A3 V
10 SL06 ISO 114-89A OPEN 3SB5
PANEL REF : 114CRP 11 SL07 ISO 114-89A CLOSE 3SB5
TVM
2200
86B
80A
195
80/86B
RU-A
RU-B
RU-C
80/96
1000 NOTE:
SIDE VIEW
A A
275
400
80
SLOT FOR BUS WIRING
B B
REAR DOORS
FRONT
Ø14.0 HOLES (4x)
C C
Last Used by: z004mx4y
127
Time: 2:09:19 PM
Date: 06/26/2023
25
2200
2315
519
800
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel F114 03
154
100
CopyRight (C) Siemens Limited, India All Rights Reserved.
25
FRONT
0
100
800
827
A A
SI DG EA
Internal Layout
B B
C C
Last Used by: z004mx4y
Time: 2:09:34 PM
Date: 07/07/2023
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel V114 01
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated V
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd COVER SHEET Sub-Station at Nehru maidan in Mangaluru V11401
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 01 of 2
3008052247 (4)G719EA-OG9228-03-V114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Internal Layout < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
LH1 (D40.00 mmxW60.00 mm) RH1 (D40.00 mmxW60.00 mm) CILS
LH1 CIL RH1
FH1 (D60.00 mmxW60.00 mm)
XB:BVT1(1-10) XB:BVT2(1-10) XB:VT(1-10) FH1 XB:ANN(1-8)
2088 2088 2088
EBZ
XB:ANN
XB:LBB
XB:BVT1
XB:BVT2
XB:AC
XB:VT
XB:VT
XB:VT
XB:VT
XB:VT
XB:VT
XB:VT
XB:VT
XB:VT
XB:VT
XB:VT
LHMR1 RHMR1
XB:BVT1
XB:BVT1
XB:BVT1
XB:BVT1
XB:BVT1
XB:BVT1
XB:BVT1
XB:BVT1
XB:BVT1
XB:BVT1
XB:BVT2
XB:BVT2
XB:BVT2
XB:BVT2
XB:BVT2
XB:BVT2
XB:BVT2
XB:BVT2
XB:BVT2
XB:BVT2
XB:ANN
XB:ANN
XB:ANN
XB:ANN
XB:ANN
XB:ANN
XB:ANN
XB:ANN
XB:LBB
XB:LBB
XB:LBB
XB:LBB
XB:LBB
XB:LBB
XB:LBB
XB:LBB
XB:LBB
XB:LBB
10
XB:AC
XB:AC
XB:AC
1
9
10
10
10
1
8
2038 2038 XB:AC(1-3)XB:LBB(1-10)
2038
V A3 A2 A1
LH2 (D40.00 mmxW60.00 mm) 1988 1988 RH2 (D40.00 mmxW60.00 mm) 1988
LH2 RH2
1938 FH2 FH2 (D60.00 mmxW25.00 mm) 1938 1938
MVART
MWT
SL52 PB53PB52PB51 PB03 PB02 PB01
HTS
TH
PS
EB
LHMR2 RHMR2
LIU
1738 MFM 1738 1738
B 1688 1688 1688
B
FH3 (D40.00 mmxW60.00 mm)
LH4 (D40.00 mmxW60.00 mm) 1638 FH3 1638 RH4 RH4 (D60.00 mmxW25.00 mm) 1638
LH4 SL09 SL08 SL07 SL06
PTS-1 LRS
FS-B2C2B
LK-B2C2N
FS-B1C1R
FS-B1C2R
FS-B2C1R
FS-B2C2R
FS-B1C1Y
FS-B1C1B
LK-B1C1N
FS-B1C2Y
FS-B1C2B
LK-B1C2N
FS-B2C1Y
FS-B2C1B
LK-B2C1N
FS-B2C2Y
1588 1588 1588
FS17
FS18
FS91
FS92
FS93
LK91
LK92
LK93
80C
95X
LHMR3
FS21
FS22
1538 1538 RHMR3 1538
FH4 (D40.00 mmxW60.00 mm)
1488 FH4 PB96 PB86BPB86A 1488 1488
LNPL1 SL15 SL14
RNPL1
1438 PTS-2 1438 1438
LH5 (D40.00 mmxW60.00 mm)
LH5 1388 SL05 SL04 SL02 CS1 SL01 SL03 1388 RH5 (D40.00 mmxW60.00 mm) 1388
RH5
1338 1338 1338
FS101
FS102
FS201
FS202
FS13
FS14
FS15
FS16
FS11
FS12
FS10
FS211
FS231
FS251
FS212
FS311
FS331
FS351
LK271
LK272
LK371
FS1
FS2
FS7
FS8
FS5
FS6
FS3
FS4
FS9
ETL1
ETL2
ETL7
FS19
FS39
FS59
LK79
FSC
D1
LHMR4 RHMR4
TVM
1188 SL13 SL12 1188 1188
LH6 (D60.00 mmxW60.00 mm) NIT RH6 (D60.00 mmxW60.00 mm)
LH6 RH6
Time: 2:42:42 PM
Date: 12/12/2023
X:RS485
X:RS485 (1-4)
X:RS485
1
X:SP (31-125)
X:RS485
2
X:RS485
3
X:RS485
X:SP
X:SP (1-30)
4
X:SP
2315
X:CB (1-51)
X:CB X:SP
X:SP
31
1 X:SP
X:CB
X:SP 32
1
2 X:SP
X:AI (1-11)
X:AI 3
4 X:SP
FH5
X:CB
X:SP 35
4
5 X:SP
X:AI X:CB
1 X:SP 36
5
6 X:SP
X:AI X:CB
2 X:SP 37
6
7 X:SP
X:AI X:CB
X:VT 16
X:CB
17
X:SP
X:SP
48
17
18 X:SP
67/67N
X:VT X:CB
X:SP
87L/21
X:VT 21 X:SP
X:CB
3 X:SP 52
22
22 X:SP
X:CB
X:VT X:SP 53
23
4 23 X:SP
X:CB
X:SP 54
24
X:VT 24 X:SP
11 X:CB
X:SP
X:S (1-13)
X:VT X:SP
X:CB
6 62
32
7 X:SP
X:CB X:S
64
34 2
X:VT X:SP
X:CB X:S
8 65
35 3
X:SP
X:CB X:S
X:VT 66
36 4
D D
X:VT X:SP
10 X:CB X:S
68
38 6
X:SP
X:VT X:CB X:S
69
21 7
FH6
X:SP
X:VT X:CB X:S
72
17 41 10
X:SP
X:CB X:S
73
X:VT 42 11
X:SP
18 X:CB X:S
74
43 12
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel V114 02
X:SP
X:CB X:S
X:CT (1-31)
X:CT 75
RVMR3
RVMR2
44 13
LVMR3
X:SP
X:CB
X:BVT2 (1-10)
X:CT
45 X:BVT2 76
X:SP
DCCO1 DCCO2
X:CB
CMRX
X:SP
X:CB 1
X:CT 78
47
2 X:SP
86B
86A
X:CB X:BVT2
80A
195
79
48 2
X:CT X:SP
96
3 X:CB
80
49 X:BVT2
3 X:SP
X:CT X:CB 81
4 50
X:BVT2 X:SP
X:CB 82
X:ISO (1-28)
X:CT
X:ISO X:BVT2
5
83
X:SP
84
6
X:ISO X:BVT2 X:SP
1 6 85
X:CT
7 CASE & BASE-1 X:ISO
2 X:BVT2
X:SP
86
X:ISO 7 X:SP
X:CT
80/86B
80/86A
3 87
8
X:ISO X:BVT2 X:SP
RU-B
RU-A
RU-C
80/96
4 8 88
X:CT
538
80B
9
295
5 X:BVT2 89
X:ISO 9
X:CT X:SP
10 6 90
X:ISO X:BVT2
X:SP
X:CT 7 10
91
11 X:ISO X:SP
X:BVT1 (1-10)
X:CT
8
X:ISO X:BVT1 92
X:SP
12 9 93
X:ISO X:BVT1
X:CT
20 FH7 X:ISO
20
X:ISO
X:BVT1
8
X:SP
104
X:SP
X:CT
21
X:CT
388 388 21
X:ISO
22
X:ISO
23
X:BVT1
9
X:BVT1
10
105
X:SP
106
X:SP
107
388
22 X:ISO
CopyRight (C) Siemens Limited, India All Rights Reserved.
X:SP
X:BC (1-10)
X:CT
24
X:ISO X:BC 108
X:SP
23 25 109
X:BC
X:ISO X:SP
X:CT 1
26 110
24 X:BC
X:ISO X:SP
X:DC2 (1-3)
113
BLKD
26 X:BC
TTB 5 X:SP
X:CT 114
X:DC2 X:BC
27 6 X:SP
1
115
X:BC
X:CT 7 X:SP
X:DC2
X:DC1 (1-3)
X:CT 120
31 X:DC1
1 X:SP
121
E E
X:SP
X:DC1 123
FH8
3 X:SP
124
X:SP
X:AC 125
X:AC (1-3)
X:AC
1
FV2
X:AC
2
X:AC
RV1
RV3
RV2
LV3
88 E-BB 88 88
HT
0
0 0 0
100
15.00
1000
Cable Duct for External Wire/Cable
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated V 114 CRP 1 mm. : 10 mm.
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Internal Layout Sub-Station at Nehru maidan in Mangaluru V11402
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 02 of 2
3008052247 (4)G719EA-OG9228-03-V114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Internal Layout <01 ->
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
SI DG EA
Wiring Schematics
B B
C C
Last Used by: z004mx4y
Time: 2:10:35 PM
Date: 07/07/2023
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 01
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd COVER SHEET Sub-Station at Nehru maidan in Mangaluru W11401
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 01 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics < 02>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
PANEL PANEL
SHEET NO. DESCRIPTION DRAWING NUMBER SHEET NO. DESCRIPTION DRAWING NUMBER
A REFERENCE REFERENCE A
COVER SHEET 67/67N Relay BO Circuit
01 (4)G719EA-OG9228-03-W114 114 CRP 19 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
List of Documents 86A Master Trip Relay Circuit
02 (4)G719EA-OG9228-03-W114 114 CRP 20 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
List Of Reference Documents 86B Master Trip Relay Circuit
03 (4)G719EA-OG9228-03-W114 114 CRP 21 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
Legend 96 LBB Trip Relay Circuit
04 (4)G719EA-OG9228-03-W114 114 CRP 22 (4)G719EA-OG9228-03-W114 114 CRP
B Wiring Schematics Wiring Schematics B
Single Line Diagram CB TC-1 Circuit
05 (4)G719EA-OG9228-03-W114 114 CRP 23 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
Trip Logic Diagram CB TC-2 Circuit
06 (4)G719EA-OG9228-03-W114 114 CRP 24 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
AC Distribution TC1 & TC2 Circuit of Buscoupler
07 (4)G719EA-OG9228-03-W114 114 CRP 24A (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
DC Distribution Indication Circuit
08 (4)G719EA-OG9228-03-W114 114 CRP 25 (4)G719EA-OG9228-03-W114 114 CRP
Wiring Schematics Wiring Schematics
C C
Last Used by: z004mx4y
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd List of Documents Sub-Station at Nehru maidan in Mangaluru W11402
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 02 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <01 03>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
B B
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 03
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd List Of Reference Documents Sub-Station at Nehru maidan in Mangaluru W11403
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 03 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <02 04>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
Sheet Version: V 1.1 SYMBOL & DESCRIPTION SYMBOL & DESCRIPTION SYMBOL & DESCRIPTION
A A
L+ L-
HOOTER
POWER SUPPLY
BELL
CIRCUIT BREAKER Designation Comment
-S
X:AC Incoming AC Ckt
X:VT PT Ckt
SWITCH CONTACT
WAVE TRAP XB:ANN Annunciation Ckt
1S2
1S2
1S2
I II III
LINK
1S2
1S2
1S2
CURRENT TRANSFORMER SECONDARY
DISCONNECTING TERMINAL
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 04
CURRENT COIL
OPEARTING/REST COIL
E LATCHED CONTACT-NO E
I> I>
LATCHED CONTACT-NC
MCB
SPACE HEATER
A A
LA
114-89DE
B B
114-89D
114-52
P1
C C
Last Used by: z004mx4y
CT
114-89E CORE-3 7SJ66 67/67N
RATIO: 400-200/1A Backup Protection
Time: 2:11:25 PM
Date: 07/07/2023
CLASS: 5P20
Burden: 30VA
From Bus VT
CT
CORE-2 PD3 MWT PD3 MVART SQ Premier TVM Elite MFM
RATIO: 400-200/1A Power Transducer (MW) Power Transducer Analogue Ammeter Meter Multi Function Meter
CLASS: 0.2
Burden: 10VA
From BUS VT
CT
CORE-1 7SD52 87L/21
RATIO: 400-200/1A Line Differential/Distance Protection
D CLASS: PS, Vk=800V @400/1 ,Rct=<4ohm @400/1 D
Im @Vk/2=20mA
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 05
114-89C
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
114-89A 114-89B
110kV BUS-2
110kV BUS-1
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Single Line Diagram Sub-Station at Nehru maidan in Mangaluru W11405
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 05 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <04 06>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
CB TC-2 R,Y,B-PHASE
96 LBB TRIP RELAY
B DEVICE B
LBB INITIATION
FUNCTION DESCRIPTION TYPE
DESIGNATION
DR TRIGGER
CLOSE CB
87L/21 LINE DIFF.PROTN 7SD522 X X X X @
87L/21 DISTANCE PROTN-Z2/3/4 7SD522 X X X X @
87L/21 O/V STAGE-1 (INBUILT OF 87L/21) - 59 7SD522 X X X @
C C
Last Used by: z004mx4y
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Trip Logic Diagram Sub-Station at Nehru maidan in Mangaluru W11406
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 06 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <05 07>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
X:AC 1 H1
A A
2 H2
ADJ PANEL
XB:AC 1
B ADJ PANEL
B
FS93
H1 2 1 H21
6A
LK93
H2 2 1 H22
EB
16A
6A
2
2
2
2
80A 80C
LK91
LK92
FS91
FS92
26 27 H23 21 22 H24
L
N
/08.3 /07.7
1
1
1
1
80B
C 26 27 C
Last Used by: z004mx4y
/08.3 SL52
X1 X2
Time: 2:11:52 PM
Date: 07/07/2023
H4 DC FAIL INDICATION
80C
13 14 H27
H3
/07.7
3RH21
H31
H32
80C
CILS CIL PB53
21 22 H5 1 2 1-3 1-4 A1 A2
/29.3 /29.4
/27.5
/27.5
DC FAIL ACCEPT
13 14
/07.6 To DC Fail Scheme
TO ANNUN 21 22
/07.6 To DC Fail Scheme
CKT 31 32
D D
43 44
HTS TH
1 HT 2
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 07
1 2 H7 1 2 H8
PS
1 PSS 2
E
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd AC Distribution Sub-Station at Nehru maidan in Mangaluru W11407
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 07 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <06 08>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
DC Changeover Relay
DCCO1
11 21
A A
14 15
/08.5
24 25
/08.5
16 17
/08.6
26 27
X:DC1 FS101 /08.6 DCCO1
+VE J11 2 1 J13 14 15 J1
220V DC -1 16A /08.3
1 FS102
SUPPLY DCCO1
J12 2 1 J14 24 25 J2
-VE 16A /08.3
2
10A
10A
10A
10A
2-2
6A
6A
6A
6A
4A
4A
2
2
FS13
FS14
FS15
FS16
B B
FS1
FS2
FS3
FS4
FS5
FS6
/29.4
1
PB51
2-1
DC-1 Supvn Relay
17
27
17
27
L101
L102
80A
/08.3
/08.3
/08.3
/08.3
K1
K2
L1
L2
12 21
J13A
K901
K902
K101
K102
DCCO1
DCCO1
DCCO2
DCCO2
/23.1
/23.1
/09.6
/09.6
/27.4
/27.4
11 13
/12.3
/12.6
/20.3
/20.8
16
26
16
26
28 18 INDICATION TO ANNUN
/28.2 Spare
16 17 CIRCUIT BREAKER TRIP RELAY METERING
/26.2 TO ANN TO 87L/21 RELAY
CLOSING & 86A CKT
C CIRCUIT C
Last Used by: z004mx4y
26 27
/07.5 To AC Distribution Ckt TRIPCOIL-1
Time: 2:12:14 PM
Date: 07/07/2023
DC Changeover Relay
DCCO2
11 21
14 15
/08.5
24 25
/08.5
16 17
D /08.7 D
26 27
X:DC2 FS201 /08.7 DCCO2
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 08
6A
6A
6A
6A
2
2
10A
10A
FS17
FS18
FS21
FS22
6A
6A
6A
6A
/29.5
2
CopyRight (C) Siemens Limited, India All Rights Reserved.
FS10
FS11
FS12
FS7
FS8
FS9
1
1
1
PB52
E E
2-1
U1
U2
DC-2 Supvn Relay
80B
12 21
J23A
K201
K202
P101
P102
K51
K52
K401
K402
11 13 X:SP 1 2
/24.3
/24.3
/21.3
/21.8
/22.3
/22.8
/18.3
/18.6
28 18
/28.4 Spare
16 17 TRIP RELAY TO 96 RELAY
/26.2 TO ANN CIRCUIT BREAKER SPARE
86B CKT CIRCUIT
26 27 TRIP COIL-2 TO 67/67N RELAY
/07.5 To AC Distribution Ckt
CIRCUIT
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd DC Distribution Sub-Station at Nehru maidan in Mangaluru W11408
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 08 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <07 08A>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A FS-B1C1R FS-B2C1R A
BUS-1 VT PROTECTION CORE-1
FS-B1C1Y FS-B2C1Y
2 1E131 2 1 1E133 2 2E131 2 1 2E133
/08B.2 /08B.2
2A 2A
FS-B1C1B FS-B2C1B
3 1E151 2 1 1E153 3 2E151 2 1 2E153
/08B.2 /08B.2
2A 2A
LK-B1C1N LK-B2C1N
4 1E171 2 1 1E173 4 2E171 2 1 2E173
/08B.2 /08B.2
2 2
3 3
4 4
C C
Last Used by: z004mx4y
Time: 2:12:41 PM
Date: 07/07/2023
FS-B1C2R FS-B2C2R
XB:BVT1 5 1E211 2 1 1E213 XB:BVT2 5 2E211 2 1 2E213
BUS-1 VT METERING CORE-2
/08B.5 /08B.5
FS-B1C2Y FS-B2C2Y
6 1E231 2 1 1E233 6 2E231 2 1 2E233
/08B.5 /08B.5
2A 2A
D D
FS-B1C2B FS-B2C2B
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 08A
LK-B1C2N LK-B2C2N
8 1E271 2 1 1E273 8 2E271 2 1 2E273
/08B.5 /08B.5
X:BVT2 5
6
6
E 7 E
7
8
8
A A
PTS-1 PTS-2
B BUS-1 PT BUS-2 PT BUS-1 PT BUS-2 PT B
1E113 1 2 E115 1E213 1 2 E11
/08A.4 /11.3 /08A.4 /09.3
/29.6 /29.7
C C
Last Used by: z004mx4y
Time: 2:13:01 PM
Date: 07/07/2023
2E113 11 12 2E213 11 12
/08A.8 /08A.8
/29.6 /29.7
2E133 13 14 2E233 13 14
/08A.8 /08A.8
/29.6 /29.7
2E153 15 16 2E253 15 16
/08A.8 /08A.8
/29.6 /29.7
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 08B
2E173 17 18 2E273 17 18
/08A.8 /08A.8
/29.6 /29.7
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
A A
OUTPUT-1
1 1 1 17 S101 X:AI 1
+
X:CT 1 D11 2 2 3 18 S102 2
-
2 3 3 D71 D15 D15
/10.2
OUTPUT-2
VY 4 19 3
CT INPUT
Y1 Y2 E35 S103 X:AI
+
B 3 4 4 D33 6 20 S104 4 B
-
4 D31 5 5
6 6 D71 7 D35 D35
/10.2
5 B1 VB B2 E55 9
6 7 7 D53
P2
P2
P2
CT D51
CORE-2 2S3 2S3 2S3 8 8 2
R-PH 9 9 5 D55 D55
VT INPUT
D71
/10.2
RATIO: 400-200/1A
D71S
2S1 2S1 2S1 N1 VN N2 E75 8
CLASS: 0.2
11
P1
P1
P1
/08.7
/08.7
AUX SUPPLY
13
~/+
7 D71 14
~/-
L1
L2
C 8 C
Last Used by: z004mx4y
Time: 2:13:31 PM
Date: 07/07/2023
ETL1
D73S 2 1E
LINE SIDE
L1
L2
/10.3
/10.3
D71 D71
/10.1
E15 E15
D /10.1 D
FS311
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 09
ADJ PANEL
XB:VT 1
E E
XB:VT 2
XB:VT 3
XB:VT 4
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Meetering Circuit Sub-Station at Nehru maidan in Mangaluru W11409
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 09 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <08B 10>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
D21
D41
A A
D61
Power Transducer
MVART
OUTPUT-1
D15 1 17 S105 X:AI 5
/09.8 +
3 18 S106 6 Meter Multi Function Meter
-
A1 TVM R MFM V1
1 2
OUTPUT-2
4 19 7 1S I1S1
CT INPUT
D35 S107 X:AI D23 D25
/09.8 + A
6 20 S108 8
- R
1L I1S2
D55 7 A2 Y V2
/09.8
B 9 1 2 D43 2S D45 I2S1 B
A
Y
2 2L I2S2
5 A3 B V3
VT INPUT
RS485 PORT
8 1 2 D63 3S D65 I3S1 +
A
11 -
B
3L I3S2 SG
AUX SUPPLY
13 N VN
/09.6
/09.6
~/+
14
~/- AUX SUPPLY
+/P -/N
L1
L2
C C
Last Used by: z004mx4y
TVM
Time: 2:13:49 PM
Date: 07/07/2023
RS485
COM
L1
L2
Rx
Tx
/25.3
/25.6
Screened
D71 cable
/09.8
X:RS485 1 2 3
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 10
E75 E75
/09.8
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Metering Circuit Sub-Station at Nehru maidan in Mangaluru W11410
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 10 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <09 11>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
87L/21 (7SD522)
110kV BUS SIDE 87L/21
A -11.1
A
CT JB
P2
P2
CT LED 3 B-PHASE TRIP
1S3 1S3 1S3
A71S
CORE-1
R-PH
BLKA LED 4 ZONE-1 OPTD
B RATIO: 400-200/1A 1S1 1S1 1S1 17 A71 S6 R6 A73 B
CLASS: PS,
18 /29.3
Vk=800V @400/1 , LED 5 Z2/Z3/Z4 OPTD
P1
P1
P1
Rct=<4ohm @400/1
A73S
Im @Vk/2=20mA
ETL2 LED 6 VT FUSE FAIL
2 1 EW
/29.4 /30.1
Date: 07/07/2023
/29.4
E175
/17.3
CopyRight (C) Siemens Limited, India All Rights Reserved.
REMOTE END
LOCAL END
(ADYAAR LINE
E (KAVOOR SS)
(IDLE)) E
LINE LENGTH XX KM
Tx Rx
@@1300nm MONOMODE LC CONNECTOR FO CABLE LC LC
LC LC LC
LINE LC LINE
NOTE: DIFFERENTIAL DIFFERENTIAL
LIU Rx Tx LIU$$
RELAY RELAY
1.LIU $$ TO BE MOUNTED IN REMOTE END CRP PANEL.SAME WILL BE SUPPLIED IN THE (7SD522) LC LC @@1300nm MONOMODE LC CONNECTOR FO CABLE LC LC (7SD522)$$
LC LC
REMOTE END PANEL AND NOT IN SIEMENS SCOPE.
2.$$ - REMOTE END RELAY WILL BE SUPPLIED IN THE REMOTE END PANEL AND NOT IN
SIEMENS SCOPE.
3.@@ THUS MARKED CABLES ARE NOT IN SIEMENS SCOPE OF SUPPLY
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 87L/21 Relay CT VT Circuit Sub-Station at Nehru maidan in Mangaluru W11411
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 11 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <10 12>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
/08.4
/08.4
A 87L/21
A
K901
K902
114-52 Power Supply
BLKA
S2 R2 K903 K1 K2
NIT + -
/29.3
NIT /30.1
X:CB 19 K901A 1 2
/29.7
NIT
NIT BI1
X1 X1 X:CB 20 K905A K905 K17 K18
3 4 MAIN/BC CB OPEN
45 46 /29.7 /30.1
CB OPEN
CS1
T AT N AC C BI2
13 14 K907 J1 J2
CB CLOSE COMMAND
B /29.2 /30.1 B
X:S 5 X:S 6
DWG.NO: (4)G71AHS-EA401-W1240-
SH.NO:02
B/C NIT
NIT
X:CB 40 K901C 45 46
C /29.7 C
Last Used by: z004mx4y
NIT
XX XX NIT
Time: 2:14:34 PM
Date: 12/12/2023
X:CB 41 K905B 47 48
XX CB OPEN XX X:ISO 23 /29.7
BI4
X:ISO 24 K911 J4
114-89D/DE 89D ISOL.OPEN
/30.1
BI5
X:ISO 25 K913 J6 J5
89D ISOL.CLOSE
/30.1
BI6
X:ISO 26 K915 J7 J8
89DE ISOL.OPEN
XX XX /30.1
XX XX BI7
D 89D ISOL.OPEN D
X:ISO 27 K917 J9 J10
89DE ISOL.CLOSE
XX XX /30.1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 12
86A BI8
XX XX 117 118 K921 J11 J12
86A OPTD
89D ISOL.CLOSE /20.6 /30.1
XX XX
86B BI9
XX XX 117 118 K923 P17 P18
86B OPTD
89DE ISOL.OPEN /21.6 /30.1
XX XX
96 BI10
XX XX 117 118 K925 N1 N2
96 OPTD
CopyRight (C) Siemens Limited, India All Rights Reserved.
BI11
X:SP 4 X:SP 6 K927 N3
Spare
E /30.1 E
BI12
X:SP 7 K929 N4
Spare
/30.1
BI13
X:SP 8 K931 N6 N5
Spare
/30.1
E-BB PE
K901
K902
PE EW
PE
/13.3
/13.6
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 87L/21 Relay BI Circuit Sub-Station at Nehru maidan in Mangaluru W11412
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 12 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <11 13>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
/12.6
/12.3
A 87L/21
A
K902
K901
BI14
X:SP 9 X:SP 13 K933 N7 N8
Spare
/30.1
BI15
X:SP 14 K935 N9 N10
Spare
B X:SP 10 /30.1 B
BI16
X:SP 15 K937 N11 N12
Spare
/30.1
BI17
X:SP 16 K939 H17 H18
Spare
/30.1
BI18
X:SP 17 K941 G1 G2
Spare
/30.1
C C
Last Used by: z004mx4y
Time: 2:14:51 PM
Date: 07/07/2023
BI19
X:SP 11 X:SP 18 K943 G3
Spare
/30.1
BI20
X:SP 19 K945 G4
Spare
X:SP 12 /30.1
BI21
X:SP 20 K947 G6 G5
Spare
/30.1
BI22
X:SP 21 K949 G7 G8
D Spare D
/30.1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 13
BI23
X:SP 22 K951 G9 G10
Spare
/30.1
BI24
X:SP 23 K953 G11 G12
Spare
/30.1
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
K902
K901
/14.3
/14.4
A A
87L/21
BO1
K6 L103
/26.2 DIST Z1 OPTD TO ANNUN
/30.1
BO2
K7 L105
/26.2 DIST Z2/3/4 OPTD TO ANNUN
/30.1
BO3
L101 K5 K8 U113 X:SP 113
/26.2 SPARE
/30.1
B B
BO4
K10 K9 U114 X:SP 114
SPARE
/30.1
BO5
K12 K11 L111
/26.2 VT FUSE FAIL TO ANNUN
/30.1
BO6
CMRX .A K901 K14 K13 K901D
/13.3 /14.2 TO CMRX.A
K901D 11 12 K902 /30.1
/14.6 /13.6
13 14
/23.5 TO CB CLOSING BO7
C 108 K16 K15 110 C
Last Used by: z004mx4y
R1
Date: 07/07/2023
U26 X:SP 26
/30.1 SPARE
BO9
R2 U27 X:SP 27
/30.1 SPARE
BO10
R3 L141
/26.6 OCR OPTD TO ANNUN
/30.1
BO11
R4 L143
/26.6 EFR OPTD TO ANNUN
/30.1
BO12
L101 R5 R6 L145
D /26.5 /26.6 BRC/PSB TO ANNUN D
/30.1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 14
BLKA BO13
K101 S1 R1 K103 R8 R7 K105
/20.4 /20.5 DISTANCE RELAY OPTD-86A
/29.3 /30.1
BLKB BO14
K201 S1 R1 K201A R10 R9 K205
/21.4 /21.5 DISTANCE RELAY OPTD-86B
/29.4 /30.1
CopyRight (C) Siemens Limited, India All Rights Reserved.
BO15
X:SP 24 U69 R12 R11 U70 X:SP 25
SPARE
/30.1
E E
A 87L/21
A
BLKA BO16
P101 S8 R8 P101B P4 P3 P103
/22.4 /22.4 LBB Protn optd
/29.3 /31.1
BO17
P6 U28 X:SP 28
/31.1 SPARE
BO18
P7 U29 X:SP 29
B /31.1 SPARE B
BLKA BO19
KT301A S9 R9 KT301B P5 P8 KT303A
/24A.3 /24A.4 TO BC 86.1
/29.3 /31.1
BLKA BO20
KT401A S10 R10 KT401B P10 P9 KT403A
/24A.3 /24A.4 TO BC 86.2
/29.3 /31.1
BO21
K1 P12 P11 K17
/23.4 /23.5 TO TC-1
/31.1
BO22
K51 P14 P13 K61
/24.4 /24.5 TO TC-2
/31.1
C C
Last Used by: z004mx4y
Time: 2:41:29 PM
Date: 12/12/2023
BO23
L101 P16 P15 L129
/26.2 /26.3 LINE DIFF.OPTD TO ANNUN
/31.1
BO24
X:SP 32 U32 H4 H3 U33 X:SP 33
SPARE
/31.1
BO25
H6 X:SP 34
/31.1 SPARE
BO26
H7 X:SP 35
/31.1 SPARE
D D
BLKB BO27
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 15
BLKB BO28
KT51A S10 R10 KT51B H10 H9 KT53A
/24A.3 /24A.4 TO BC TC-2
/29.4 /31.1
BO29
X:SP 40 U40 H12 H11 U41 X:SP 41
SPARE
/31.1
CopyRight (C) Siemens Limited, India All Rights Reserved.
BO30
X:SP 42 U42 H14 H13 U43 X:SP 43
SPARE
/31.1
E E
BO31
X:SP 44 U44 H16 H15 U45 X:SP 45
SPARE
/31.1
A A
B B
C
Blank sheet C
Last Used by: z004mx4y
Time: 2:15:43 PM
Date: 07/07/2023
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 16
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Sub-Station at Nehru maidan in Mangaluru W11416
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 16 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <15 17>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
C75
BLKC IB LED-2 OCR TRIP Y-PHASE
23 C31 S4 R4 C33 Q3 • Q4
24 /29.5 /32.1
LED-3 OCR TRIP B-PHASE
BLKC IC
25 C51 S5 R5 C53 Q5 • Q6
LED-4 EFR OPTD
26 /29.5 /32.1
P2
P2
P2
CT
3S3 3S3 3S3
C71S
CORE-3 LED-5 VT FUSE FAIL
R-PH
RATIO: 400-200/1A BLKC IN/INs
3S1 3S1 3S1 27 C71 S6 R6 C73 Q7 • Q8
CLASS: 5P20, 30VA LED-6 LBB OPTD
B 28 /29.5 /32.1 B
P1
P1
P1
LINE SIDE
FS19 BLKC VA
E115 X:VT 7 E213 2 1 E215 S7 R7 E217 R1 •
/11.3
C 2A /29.5 /32.1 C
Last Used by: z004mx4y
FS39 BLKC VB
Time: 2:16:11 PM
2 1 S8 R8 •
Date: 07/07/2023
/11.3
2A /32.1
SELECTED
/29.5
FS59 BLKC VC
E155 9 E253 2 1 E255 S9 R9 E257 R3 • R4
/11.3
2A /29.5 /32.1
LK79 BLKC
E175 10 E273 2 1 E275 S10 R10 E277 E277
/11.3
/29.5
VL4
R5 • R6
ADJ PANEL /32.1
D D
XB:VT 5
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 17
XB:VT 6
XB:VT 7
XB:VT 8
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 67/67N Relay CT Circuit Sub-Station at Nehru maidan in Mangaluru W11417
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 17 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <16 18>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
67/67N
/08.4
/08.4
A A
K401
K402
BLKC
S2 R2 K403 P1 P2
+ - Power Supply
/29.5
/32.1
86A BI1
123 124 K405 F1 F2 86A TRIP RELAY OPTD
/20.6 /32.1 (LBB INITIATION)
86B BI2
123 124 K407 F3 F4 86B TRIP RELAY OPTD
/21.6 /32.1 (LBB INITIATION)
B B
96 BI3
114-52 123 124 K409 F6 F5
96 TRIP RELAY OPTD
/22.7 /32.1
X:CB 38
BI4
X1 X1 X:CB 39 K411 F7
CB CLOSE STATUS
37 38 /32.1
CB CLOSE
BI6
C 48 F11 C
Last Used by: z004mx4y
X:SP K415
Spare
/32.1
Time: 2:16:32 PM
Date: 07/07/2023
BI7
X:SP 49 K417 F12 F10
Spare
/32.1
BI8
X:SP 50 X:SP 51 K419 K1
Spare
/32.1
BI9
X:SP 52 K421 K2
Spare
/32.1
BI10
X:SP 53 K423 K3
D Spare D
/32.1
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 18
BI11
X:SP 54 X:SP 55 K425 K4
Spare
/32.1
BI12
X:SP 56 K427 K5
Spare
/32.1
BI13
X:SP 57 K429 K6
Spare
CopyRight (C) Siemens Limited, India All Rights Reserved.
/32.1
BI14
X:SP 58 X:SP 59 K431 K7
Spare
E /32.1 E
BI15
X:SP 60 K433 K8
Spare
/32.1
BI16
X:SP 61 K435 K9 K10
Spare
/32.1
K401
K402
EW
/19.4
/19.3
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 67/67N Relay BI Circuit Sub-Station at Nehru maidan in Mangaluru W11418
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 18 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <17 19>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
67/67N
A A
BLKD BO1
K201 S1 R1 K201B P4 P3 K205
/21.4 /21.5 O/C Protn Optd
/29.5 /32.1
BLKC BO2
K101 S1 R1 K107 P6 P5 K105
/20.4 /20.5 BACKUP O/C & E/F RELAY OPTD
/29.5 /32.1
BO3
P7 U62 X:SP 62
/32.1 Spare
B B
BO4
K401 P9 P8 K401A
/18.3 /19.2 TO CMRX.B
/32.1
CMRX .B
K401A 21 22 K402
/19.6 /18.6
BO6
23 24 L101 P10 P12 L125 DIR O/C PROTN OPTD
/24A.3 TO BC 86.1 /26.2 /26.3 TO ANNUN
25 26 /32.1
/24A.3 TO BC 86.2
27 28
BO5
P11 L127 DIR E/F RELAY OPTD
/26.3
/32.1 TO ANNUN
C C
Last Used by: z004mx4y
BLKD BO7
Time: 2:40:01 PM
P101 P103A
/22.4 /22.4 LBB Protn optd
/29.5 /32.1 K12
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 19
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
A A
/08.5
/08.5
K101
K102
87L/21 Trip Relay
86A
From 87L/21 Relay
K101 K105 K105 212 211 K102A
/14.4 /14.6 O
B 221 B
11
12
13
14
67/67N RU-A
122 121 4X820Ω/5W
From 67/67N Relay R
K101 K105
21
22
23
24
/19.4 /19.6
113 114
/23.4 TO 110kV CB TC-1 CKT
115 116
/24.4 TO 110kV CB TC-2 CKT
117 118
/12.4 TO 87L/21 BI CKT
123 124
/18.4 TO 67/67N BI CKT
213 214
/26.6 TO ANNUN
227 228
/28.2 SPARE
K109
225 226
/23.3 TO 110kV CB CLSG I/L CKT
X:SP 65 X:SP 66 223 224
K105A
FUTURE USE /28.4 SPARE
C C
Last Used by: z004mx4y
Time: 2:17:02 PM
Date: 07/07/2023
PB86A
1-3 1-4
/29.3
11 13
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 20
28 18
16 17
/26.6 TO ANN
26 27
/28.2 SPARE
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 86A Master Trip Relay Circuit Sub-Station at Nehru maidan in Mangaluru W11420
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 20 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <19 21>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
/08.5
/08.5
K201
K202
87L/21 Trip Relay
86B
From 87L/21 Relay
K201 K205 K205 212 211 K202A
/14.4 /14.6 O
B 221 B
11
12
13
14
67/67N RU-B
K207 122 121 4X820Ω/5W
From 67/67N Relay R
K201 K205
21
22
23
24
/19.4 /19.6
113 114
/23.4 TO 110kV CB TC-1 CKT
115 116
/24.4 TO 110kV CB TC-2 CKT
117 118
/12.4 TO 87L/21 BI CKT
X:SP 67 X:SP 68 123 124
FUTURE USE /18.4 TO 67/67N BI CKT
213 214
/26.6 TO ANNUN
K205A
227 228
/28.2 SPARE
225 226
/23.3 TO 110kV CB CLSG I/L CKT
223 224
/28.4 SPARE
C C
Last Used by: z004mx4y
PB86B
1-3 1-4
/29.4
Time: 2:17:17 PM
Date: 07/07/2023
11 13
28 18
16 17
/26.6 TO ANN
26 27
/28.2 SPARE
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 21
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 86B Master Trip Relay Circuit Sub-Station at Nehru maidan in Mangaluru W11421
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 21 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <20 22>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
ADJ PANEL ADJ PANEL
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
P101
P102
P103
P104
P101
P102
P103
P104
A A
114 CRP
XB:LBB 1
/08.8
/08.8
LBB TRIP BUS-1
B B
P102
-VE
+VE
P102
11
12
13
14
P104
RU-C
87L/21 P107 122 121 4X820Ω/5W
R
69 P101 P103 70
21
22
23
24
X:SP X:SP Resistor Unit for 96
/15.4 /15.6
C C
Last Used by: z004mx4y
113 114
/23.4 TO 110kV CB TC-1 CKT
115 116
89A /24.4 TO 110kV CB TC-2 CKT
Time: 2:38:02 PM
Date: 12/12/2023
PB96
1-3 1-4
/29.3
D 96 Trip Relay Supvn D
80/96
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 22
12 21
P103
P109
P101 11 13
28 18
16 17
/26.6 TO ANN
26 27
/28.2 SPARE
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
5
8
XB:LBB
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd 96 LBB Trip Relay Circuit Sub-Station at Nehru maidan in Mangaluru W11422
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 22 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <21 23>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
114 CRP
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
K1 X:CB 5
B B
LRS CS1
L R T AT N AC C X1
3 4 K13 1 2 K11 X:CB 6
REMOTE TRIP-1
/29.6 /29.2 7
LRS
L R
K1 15 16 K15 X:S 7 SCADA TRIP X:S 8
/29.6 COMMAND K1 X:CB 7
86A X1
113 114 K17 X:CB 8
/20.6 PROTN TRIP
6
86B
113 114
/21.6 X1
C C
Last Used by: z004mx4y
96 POST CLOSE
113 114 8
/22.7
Time: 2:17:57 PM
Date: 07/07/2023
87L/21
From 87L/21 Relay
K1 K17
/15.4 /15.6
X:SP 71 X:SP 73
FUTURE USE
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 23
X1
11 13 K21 X:CB 10
PRE CLOSE
9
28 18
/25A.4 To Indication Circuit
16 17
CopyRight (C) Siemens Limited, India All Rights Reserved.
/26.2 TO ANN
26 27
/28.2 SPARE
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd CB TC-1 Circuit Sub-Station at Nehru maidan in Mangaluru W11423
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 23 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <22 24>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
K51 X:CB 13
LRS CS1
L R T AT N AC C X1
K51 5 6 K57 3 4 K55 X:CB 14
REMOTE TRIP-2
LRS /29.6 /29.2 12
L R
19 20 K59 X:S 9 SCADA TRIP X:S 10
/29.6 COMMAND
K51 X:CB 15
B B
86A X1
115 116 K61 X:CB 16
/20.6 PROTN TRIP
11
86B
115 116
/21.6 X1
96 POST CLOSE
115 116 13
/22.7
87L/21
From 87L/21 Relay
K51 K61
/15.4 /15.6
X:SP 75 X:SP 76
FUTURE USE
C C
Last Used by: z004mx4y
12 21
PRE CLOSE
X1
11 13 K63 X:CB 18
14
28 18
/25A.4 To Indication Circuit
16 17
/26.2 TO ANN
26 27
/28.2 SPARE
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 24
CopyRight (C) Siemens Limited, India All Rights Reserved.
DWG.NO: (4)G71AHS-EA401-W1240-
SH.NO:01
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd CB TC-2 Circuit Sub-Station at Nehru maidan in Mangaluru W11424
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 24 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <23 24A>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
NIT
A NIT A
KT1A 27 28 KT1 X:BC 1 XX XX
/29.7
87L/21
NIT
NIT TO BC TC-1
KT1A KT3A 29 30 KT3 2 XX
/15.4 /15.6
/29.7
From 87L/21 Relay
NIT
NIT
KT51A 31 32 KT51 X:BC 3 XX XX
/29.7
87L/21
NIT TO BC TC-2
B NIT B
KT51A KT53A 33 34 KT53 4 XX
/15.4 /15.6
/29.7
From 87L/21 Relay
NIT
NIT
KT301A 17 18 K301BC X:BC 5 XX XX
/29.7
87L/21
NIT TO BC 86.1
NIT
KT301A KT303A 19 20 K305BC 6 XX
/15.4 /15.6
/29.7
From 87L/21 Relay
C C
Last Used by: z004mx4y
CMRX
Time: 2:18:31 PM
Date: 07/07/2023
.B
23 24
/19.2
NIT
NIT
KT401A 23 24 K401BC X:BC 7 XX XX
/29.7
87L/21
NIT TO BC 86.2
NIT
KT401A KT403A 25 26 K405BC 8 XX
/15.4 /15.6
/29.7
From 87L/21 Relay
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 24A
CMRX
.B
25 26
/19.2
NOTE:
XX TB’S IDENTIFIED AT THE SITE
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
/10.3
/10.3
114-52
A A
L1
L2
X:CB 22
SL01
X:CB 23 L9 X1 X2
CB OPEN
SL02
X:CB 24 L13 X1 X2
CB CLOSE
CS1 CS1
T AT N AC C T AT N AC C SL03
X:CB 25 L19 9 10 L19A 21 22 L21 X1 X2
B /29.2 /29.2 CB AUTO TRIP
B
SL04
X:CB 26 L23 X1 X2
CB SPRING CHARGED
114-89A
X:ISO 1
SL06
X:ISO 2 L3 X1 X2
ISO 114-89A OPEN
SL07
X:ISO 3 L5 X1 X2
C C
Last Used by: z004mx4y
X:ISO 4
SL08
X:ISO 5 L39 X1 X2
ISO 114-89B OPEN
SL09
X:ISO 6 L41 X1 X2
ISO 114-89B CLOSE
114-89D
X:ISO 7
D SL10 D
X:ISO 8 L31 X1 X2
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 25
SL11
X:ISO 9 L33 X1 X2
ISO 114-89D CLOSE
114-89DE
X:ISO 10
SL12
X:ISO 11 L35 X1 X2
CopyRight (C) Siemens Limited, India All Rights Reserved.
SL13
X:ISO 12 L37 X1 X2
E ESW 114-89DE CLOSE E
L1
L2
/25A.4
/25A.6
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Indication Circuit Sub-Station at Nehru maidan in Mangaluru W11425
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 25 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <24A 25A>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
114 CRP
/25.3
/25.6
A A
L1
L2
114-89C
X:ISO 13
SL14
X:ISO 14 L43 X1 X2
ISO 114-89C OPEN
SL15
X:ISO 15 L45 X1 X2
ISO 114-89C CLOSE
B 114-89E B
X:ISO 20
SL16
X:ISO 21 L47 X1 X2
ISO 114-89E OPEN
SL17
X:ISO 22 L49 X1 X2
ISO 114-89E CLOSE
195 SL05
28 18 L11 L11 X1 X2
/23.4
TC HEALTHY
C C
Last Used by: z004mx4y
28 18 95X
Date: 07/07/2023
/24.5 A1 A2
13 14
/23.1 TO CB Closing Ckt
21 22
31 32
43 44
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 25A
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
FC FC
L101 Common L101 Common
A A
C
114-52
87L/21
L103 L103 DIST Z1 OPTD X:CB 34 CB SF6 X:CB 35 L135 CB SF6 LOCKOUT
17
/14.6
1
T
T
LOCKOUT
NT
18
/14.6
2
T
80/96
X:SP 111 L107 SPARE 16 17 L139 TRIP RELAY 96 DC FAIL
NT
19
3
T
87L/21 /22.4
L101
/14.4
L141 L141 DIST OCR OPTD
20
/14.6
T
B X:SP 112 L109 SPARE B
4
T
From 87L/ 21 Relay
L101
/14.4
L111 L111 VT FUSE FAIL L143 L143 DIST EFR OPTD
NT
21
/14.6 /14.6
T
195
16 17 L113 CB TC1 FAULTY
NT
6
/23.4 L145 L145 BRC/PSB
22
/14.6
T
295
16 17 L115 CB TC2 FAULTY
NT
7
/24.5
80/86A
16 17 L147 TRIP RELAY 86A DC FAIL
NT
23
LRS /20.5
C C
Last Used by: z004mx4y
L R
13 14 L117 SWITCH IN SCADA POS
NT
8
80/86B
Time: 2:19:42 PM
L149
NT
24
/21.5
TRIPPED THRU
X:S 3 SCADA X:S 4 L119 TRIPPED THROUGH SCADA L101 Common
C
9
T
87L/21
80B
16 17
From 87L/21 Relay
/08.3 L101 L151 L151 NUMERICAL RELAY FAULTY
NT
25
80A /15.4 /15.6
16 17 L121 MAIN DC FAIL
NT
10
/08.3
114-52
67/67N
D D
X:CB 27 CB CTD OPTD X:CB 28 L123 CB CTD OPTD L101 L151
NT
11
/19.4 /19.6
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 26
67/67N
L101 L125 DIR O/C PROTN OPTD
12
/19.4 /19.6
T
26
T
L127 DIR E/F RELAY OPTD /20.6 (86A,86B& 96)
13
/19.6
T
CopyRight (C) Siemens Limited, India All Rights Reserved.
86B
87L/21 213 214
/21.6 AC FAIL
NT
27
L101 L129 LINE DIFF.OPTD
14
/15.4 /15.6 96
T
E 213 214 E
114-52 /22.7 DC FAIL
NT
28
X:CB 30 X:CB 31 L131 CB AC FAIL
NT
15
CB AC FAIL
L101 Common
C
X:CB 32 CB DC FAIL X:CB 33 L133 CB DC FAIL
NT
16
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Annuciation Circuit Sub-Station at Nehru maidan in Mangaluru W11426
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 26 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <25A 27>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
/08.8
/08.8
/07.4
/07.4
EBZ
FC
L101
L102
H32
H31
+
Ph
Ne
-(T1)
-(T2)
H31 230V AC PH
PH
PH
H32 230V NEU
NU
NU
H31
H31 XB:ANN 1 DF1
DF1
C
B H33 B
H33 XB:ANN 2 H33 DF2
DF2
C
L101 220V DC (-Ve)
-VE
-VE
L102 220V DC (+Ve)
+VE
+VE
L157
L157 XB:ANN 3 L157 Bell
T1
T1
L102A Trip Alarm
T2
T2
L159 Trip Alarm
NTI
NTI
Non Trip Alarm
C L102B C
Last Used by: z004mx4y
NT2
NT2
Non Trip Alarm
Time: 2:19:59 PM
Date: 07/07/2023
L161 Common
C
PB01
1-4 1-3 L163 Accept
A
/29.4
PB02
1-4 1-3 L165 Reset
R
/29.4
PB03
1-4 1-3 L167 Lamp Test
LT
/29.4
EW
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 27
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Annunciation Circuit Sub-Station at Nehru maidan in Mangaluru W11427
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 27 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <26 28>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
A A
86B 86A
227 228 U78 X:SP 78 223 224 U94 X:SP 94
/21.6 /20.6
86A 96
227 228 U82 X:SP 82 223 224 U98 X:SP 98
/20.6 /22.7
U83 X:SP 83
U99 X:SP 99
80/86A
C 26 27 U84 84 C
Last Used by: z004mx4y
X:SP
/20.5 86B
SPARE 223 224 U100 X:SP 100
/21.6
Time: 2:20:20 PM
Date: 07/07/2023
U85 X:SP 85
80/86B
26 27 U86 X:SP 86
/21.5 U103 X:SP 103
SPARE
80B
U87 X:SP 87 28 18 U104 X:SP 104
/08.3
80A
28 18 U88 X:SP 88
/08.3
Spare
D D
U89 X:SP 89
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 28
195
26 27 U90 X:SP 90
/23.4
SPARE
U91 X:SP 91
295
26 27 U92 X:SP 92
/24.5
SPARE
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Spare Contact Distribution Sub-Station at Nehru maidan in Mangaluru W11428
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 28 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <27 29>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
/08B.2 8 /08B.6 8
47 48
17 18 17 18 /12.4 24
/08B.2 9 /08B.6 9
19 20 19 20
10 10
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Test Block & switch Distribution Circuit Sub-Station at Nehru maidan in Mangaluru W11429
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 29 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <28 30>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
: Case Size: 1/1 19”, 4xI, 4xV, 24 BI, 31 BO, 1 Live Status, 14 LED, Flush Mounting
DB Version: SL-V 1.1-08/01/2019
E-Base Version: 7.1.0.1305
Power Supply
-
B B
D
A
F
PE
K1
K2
/12.6 /12.6
Current Inputs
*
*
Q1
Q2
Q3
Q4
Q5
Q6
Q7
Q8
C C
Last Used by: z004mx4y
Voltage Inputs
*
*
R15
R17
R18
R16
R13
87L/21 /11.6 /11.6 /11.6 /11.6R14
BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 30
Input 1-16
L+
L+
L+
L+
L+
L+
L+
L+
L+
L+
L+
L+
L+
L+
L+
L+
N10
N11
N12
K17
K18
P17
P18
J10
J11
J12
N1
N2
N3
N4
N6
N5
N7
N8
N9
J1
J2
J3
J4
J6
J5
J7
J8
J9
87L/21 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /12.6 /13.5 /13.5 /13.5
Input 17-24
L+
L+
L+
L+
L+
L+
L+
L+
E G10 E
G11
G12
H17
H18
G1
G2
G3
G4
G6
G5
G7
G8
G9
LC BO1 BO2 BO3 BO4 BO5 BO6 BO7 BO8 BO9 BO10 BO11 BO12 BO13 BO14 BO15
2 3
2 3
1
X40
X41
Life Status Contact
2
2
2
Output (20x BO, 12x Fast)
R10
R11
R12
K10
K11
K12
K13
K14
K15
K16
R1
R2
R3
R4
R6
R5
R7
R8
R9
K3
K4
K6
K7
K8
K5
K9
F 87L/21 /15.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 /14.5 F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Connection Diagram For 67/67N Sub-Station at Nehru maidan in Mangaluru W11430
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 30 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <29 31>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
1
Output (20x BO, 12x Fast)
2
2
2
A A
H10
H11
H12
H13
H14
H15
H16
P10
P11
P12
P13
P14
P15
P16
H3
H4
H6
H7
H8
H5
H9
P3
P4
P6
P7
P8
P5
P9
87L/21 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5 /15.5
B B
C C
Last Used by: z004mx4y
Time: 2:21:33 PM
Date: 07/07/2023
D D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 31
CopyRight (C) Siemens Limited, India All Rights Reserved.
E E
Time Synchronization
Live
System Interface
3
1
B B
FP
K15
K16
PE
FP
P1
P2
B
/18.5 /19.5
IA IB IC IN/INs
Current Inputs
•
•
C C
Last Used by: z004mx4y
Q1
Q2
Q3
Q4
Q5
Q6
Q7
Q8
Time: 2:21:54 PM
VA VB VC VL4
Voltage Inputs
•
•
R1
R2
R3
R4
R5
R6
67/67N /17.6 /17.6 /17.6 /17.6
D BI1 BI2 BI3 BI4 BI5 BI6 BI7 BI8 BI9 BI10 BI11 BI12 BI13 BI14 BI15 BI16 D
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 32
Input 1-16
K10
F11
F12
F10
K1
K2
K3
K4
K5
K6
K7
K8
K9
F1
F2
F3
F4
F6
F5
F7
F8
F9
67/67N /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5 /18.5
CopyRight (C) Siemens Limited, India All Rights Reserved.
Output 1-7
E E
P11
P12
P10
K12
K11
K13
P3
P4
P5
P6
P7
P8
P9
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd Connection Diagram For 87L/21 Sub-Station at Nehru maidan in Mangaluru W11432
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 32 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <31 33>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
CB CLOSE STATUS
67/67N BI4 /W114/18.5
B B
Spare
67/67N BI5 /W114/18.5
Spare
67/67N BI6 /W114/18.5
Spare
67/67N BI7 /W114/18.5
Spare
67/67N BI8 /W114/18.5
C C
Last Used by: z004mx4y
Spare
67/67N BI9 /W114/18.5
Time: 2:22:07 PM
Date: 12/12/2023
Spare
67/67N BI10 /W114/18.5
Spare
67/67N BI11 /W114/18.5
Spare
67/67N BI12 /W114/18.5
D D
Spare
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 33
Spare
67/67N BI14 /W114/18.5
Spare
67/67N BI15 /W114/18.5
CopyRight (C) Siemens Limited, India All Rights Reserved.
Spare
67/67N BI16 /W114/18.5
E E
O/C Protn Optd
67/67N BO1 /W114/19.5
Spare
67/67N BO3 /W114/19.5
TO CMRX.B
67/67N BO4 /W114/19.5
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd BI/BO Table Sub-Station at Nehru maidan in Mangaluru W11433
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 33 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <32 34>
1 2 3 4 5 6 7 8
1 2 3 4 5 6 7 8
D D
Spare SPARE SPARE
220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel W114 34
E E
Spare DISTANCE RELAY OPTD-86A
87L/21 BI17 /W114/13.5 87L/21 BO13 /W114/14.5
Spare SPARE
87L/21 BI19 /W114/13.5 87L/21 BO15 /W114/14.5
F F
B QT Corrected 12/12/2023 RNG Version 2 220/110kV Substation AT KAVOOR 110kV ADYAAR Line (IDLE) C&R Panel Establishing 110/33/11kV Gas Insulated W 114 CRP
A Customer Cmnts 06/16/2023 RNG Drawn By RNG Karnataka Power Transmission Corporation Ltd BI/BO Table Sub-Station at Nehru maidan in Mangaluru W11434
0 First Submission 05/23/2023 RNG Chkd By SK Sharavathy Conductors Pvt Ltd. Sh. 34 of 38
3008052247 (4)G719EA-OG9228-03-W114
Revision Remarks Date Name Appr By MS Orig.: Replaces: Replaced by: Wiring Schematics <33 ->
1 2 3 4 5 6 7 8