Liebert EXS 10-60 kVA
Liebert EXS 10-60 kVA
10-60 kVA
Different Types of UPS Systems
Choose a single-phase or three-phase UPS system depends on several factors, such as the power
requirements of the critical loads, the available space, budget, and future growth plans
• Typically used for small to • Typically used for medium to large-sized loads
medium-sized loads (up to (above 10kVA)
20kVA) • Provides backup power to three-phase equipment
• Provides backup power to • Offers higher efficiency, reliability, and
single-phase equipment redundancy compared to single-phase UPS
• Usually has a lower initial • Can handle higher loads and provide scalability
cost than three-phase UPS for future growth
• Easy to install and maintain • Provides flexibility in terms of installation and
• Provides adequate maintenance
protection for critical loads • Can be more expensive upfront, but can offer
that require only single- cost savings over time due to improved efficiency
phase power and reduced downtime
Cost savings
Three-phase power brings greater efficiency which ensures remarkable
operational cost savings and Total Cost of Ownership (TCO) and
environmental impact reduction
For detailed product configuration please check the pricelist or reach out
to Vertiv
4
Liebert EXS 10-60 kVA Features
Flexible and Optimized One of the most compact footprint on the market
Optimizes the performances
Parallel system up to 4 units
Design through leading technology Battery charger up to 13A (10-40kVA) and 25A (60kVA)
Flexible Monitoring and Monitoring adds flexibility SNMP, MODBUS, environmental sensors
Management Options Programmable dry contacts
to each installation
Vertiv LIFE Services compatible
5
Key Benefits
6
Designed Applications
IT environment
Retail and wholesale
Transportation
Emergency lighting
Healthcare
Government
Manufacturing
Energy and utilities
Financial services
Media and entertainment
Transportation and logistics
7
Appendix
8
Liebert EXS Integrated runtime and dimensions
Standard version Extended version
up to 2x32x9 Ah up to 4x32x9 Ah
1300 1300
mm mm 200 1600 1600
200 200 200
mm mm mm
mm mm mm
95.00%
95.00% 95.00%
94.50% 94.50%
94.00% 94.00%
20% 30% 40% 50% 60% 70% 80% 90% 100% 20% 30% 40% 50% 60% 70% 80% 90% 100%
11
Vision Lithium-Ion battery: Liebert EXS portfolio (50 Ah cell)
Norminal Nominal Battery Cutoff V Battery Charge Cell Cabinet C rate C rate
Modules Cabinet Code Pack Type Cell Type
System Energy [kWh] (2,8V/cell) (3,5V/cell) series Dimension (discharge) (charge)
TP80 LIBTP80S 409.6V50Ah 20,48 358,4 448 51.2V50Ah 3.2V50Ah 128 600*1000*2000
Cabinet 8
modules
TP160 LIBTP160S 409.6V100Ah 40,96 358,4 448 51.2V100Ah 3.2V50Ah 128 600*1000*2000
TP100 LIBTP100S 512V50Ah 25,6 448 560 51.2V50Ah 3.2V50Ah 160 600*1000*2000
Cabinet 10
modules
5 1
TP200 LIBTP200S 512V100Ah 51,2 448 560 51.2V100Ah 3.2V50Ah 160 600*1000*2000
TP120 LIBTP120S 614.4V50Ah 30,72 537,6 672 51.2V50Ah 3.2V50Ah 192 600*1000*2000
Cabinet 12
modules
TP240 LIBTP240S 614.4V100Ah 61,44 537,6 672 51.2V100Ah 3.2V50Ah 192 600*1000*2300
EXS 30÷80
TP80 ✓
TP160 ✓
TP100 ✓
TP200 ✓
TP120 Not available
13
Liebert EXS 10-20 kVA
Product description
Standard version Extended version
Feature Liebert® EXS up to 2x32x9 Ah up to 4x32x9 Ah
Rating 10 – 15 – 20 kVA
Double-Conversion T-free
Technology
(3/3 or 3/1)
Input Power Factor 0.99
Load Power Factor Up to 1 1300 mm 1300 mm
14
Liebert EXS 10-20 kVA
Efficiency
97.00%
96.50% 96.18%
95.83%
96.00%
95.67%
95.37%
95.50%
95.00%
94.50%
94.00%
20% 30% 40% 50% 60% 70% 80% 90% 100%
15
Liebert EXS 10-20 kVA
Integrated runtime
Battery Standard version Extended version
Configuration
10 kVA 15 kVA 20 kVA up to 2x32x9 Ah up to 4x32x9 Ah
1x32x9 Ah 7 5 -
100% Load
2x32x9 Ah 21 13 7
1.0 PF
3x32x9 Ah 36 21 15
[min]
4x32x9 Ah 53 30 21
1300 mm 1300 mm
1x32x9 Ah 8 6 -
100% Load 200 200
2x32x9 Ah 24 15 8 mm mm
0.9 PF
3x32x9 Ah 42 24 17
[min]
4x32x9 Ah 58 35 24 650 mm
650 mm
1x32x9 Ah 11 6 5 335 mm 577 mm
100% Load
2x32x9 Ah 28 17 11
0.8 PF
3x32x9 Ah 50 28 19
[min]
4x32x9 Ah 64 42 28
1x32x9 Ah 15 7 6
75% Load
2x32x9 Ah 35 20 15
0.9 PF
3x32x9 Ah 58 35 24
[min]
4x32x9 Ah 75 52 35
Note: The battery runtime is indicative and is meant for new and fully-charged batteries
16
Liebert EXS 10-20 kVA standard cabinet
Front and rear view
Power module ventilation holes Customer cables
USB port
LED indicators Functional keys Vertiv™ IntelliSlot™ port
Maintenance bypass
Display breaker
panel Dry contacts
Output,
input and
static bypass Multi-functional
breakers port
Battery
ventilation
holes Parallel ports
Ventilation holes
Casters
17
Liebert EXS 10-20 kVA extended cabinet
Front and rear view
Ventilation holes Customer cables
USB port
LED indicators Functional keys Vertiv™ IntelliSlot™ port
Battery
ventilation
holes
Maintenance
Display bypass
panel breaker Dry
contacts
Output,
input and
static bypass
Multi-
breakers
functional
port
Battery
ventilation
holes Parallel ports
Ventilation holes
Casters
18
Liebert EXS 10-20 kVA
Breakers
Output breaker
(50 A)
Input breaker
(50 A)
19
Liebert EXS 10-20 kVA
Communication interface
Liebert® IntelliSlot® port
Intellislot extender option for
simultaneous use of unity and
relay card
USB port
Programmable
dry contacts:
2 input
2 output (fixed to backfeed)
UPS 2
UPS 3
Capacity Redundancy
Redundant UPS
21
Liebert EXS 10-20 kVA
Serviceability
22
Liebert EXS 10-15-20 kVA pricelist explained
Available on the UPS pricelist:
Empty UPS
UPS with internal batteries: 1 up to 4* 32*9Ah, 5y or 10y, by CSB HR/HRL 1234W
Dual intellislot → standard unit has one intellislot only
Made in China or Made in Europe
Internal transformer
Internal backfeed shunts
Internal fuses for 30kA withstand
IP31
23
Liebert EXS
30-40 kVA
24
Liebert EXS 30-40 kVA
Product description
25
Liebert EXS 30-40kVA
Efficiency
97.00%
96.50%
96.10%
95.98%
96.00%
95.55%
95.50%
95.00%
95.00%
94.50%
94.00%
20% 30% 40% 50% 60% 70% 80% 90% 100%
26
Liebert EXS 30-40 kVA
Integrated runtime
Battery Configuration 30 kVA 40 kVA
2x32x9 Ah 5 -
100% Load 3x32x9 Ah 7 5 Liebert EXS 30-40kVA
1.0 PF 4x32x9 Ah 12 7 up to 4x40x9 Ah
[min] 1x32x34Ah 13 8
4x40x9 Ah 16 11
2x32x9 Ah 6 -
100% Load 3x32x9 Ah 8 6
0.9 PF 4x32x9 Ah 14 8
[min] 1x32x34Ah 15 10
4x40x9 Ah 18 13
2x32x9 Ah 6 4
100% Load 1x32x23 Ah 10 6,5
3x32x9 Ah 11 7 1600 mm
0.8 PF
4x32x9 Ah 17 11
[min] 1x32x34Ah 18 12 200 mm
4x40x9 Ah 21 15
2x32x9 Ah 7 6
1x32x23 Ah 9,5 6 750 mm
75% Load 440 mm
3x32x9 Ah 14 8
0.9 PF
4x32x9 Ah 20 14
[min] 1x32x34Ah 23 15
4x40x9 Ah 28 21 27
Note: The battery runtime is indicative and is meant for new and fully-charged batteries
Liebert EXS 30-40 kVA
Front and rear view
Display panel Customer cables
Power module
ventilation holes
USB port
Cold start
Vertiv™ IntelliSlot™ button
ports
Maintenance
Bypass breaker
Ventilation holes
Input breaker
(100 A)
30
Liebert EXS 30-40 kVA
Parallel system
Capacity Redundancy
31
Liebert EXS 30-40 kVA
Serviceability
32
Liebert EXS 30-40 kVA pricelist explained
Available on the UPS pricelist:
Empty UPS → can connect to external battery cabinets
UPS with internal batteries: 1 up to 4* 32*9Ah, 4*40*9Ah, 5y or 10y, by CSB HR/HRL 1234W or 1*32*34Ah, 10y, by Leoch XP12-150
→ Standard unit cannot connect to external battery cabinets
Made in China or Made in Europe
Internal transformer
CSI for parallel
Internal backfeed shunts
Internal fuses for 30kA withstand
Possibility to connect internal and external batteries together
IP31
Available in the options list:
BCB Box 160 A → includes the board for the battery disconnection in case of ground fault, arc fault, EPO, EOD, UPS shutdown
Empty battery cabinet A3 (w*d*h 600*825*1600mm)
Battery cabinets A3 with 4*32*9Ah, 5y or 10y, by CSB or 1*32*34Ah 1*40*34Ah, 10y by Leoch, 1*32*23Ah 10y by Yuasa SWL750 FR
Parallel or Dual bus cables 5m, 10m or 15m
LBS extender kits 50m or 150m
Shelves kit for internal batteries
• 10B14842GPK1 for 1 up to 4* 32*9Ah → shorter shelves, is suitable for the customization of int+ext batteries
• 10B14842GPK2 for 4*40*9Ah or 1*32*34Ah → longer shelves, is not suitable for the customization of int+ext batteries
Battery temperature compensation kit
33
Internal and external batteries connection for EXS 30-40kVA
Fuses (and related cables) added between the power terminal block and the internal
batteries,
to protect the internal batteries from eventual short-circuit on the terminal path
34
Extended battery configurations
Standard Battery
Load = 40kVA Internal Battery External Batteries Extended
autonomy cabinet
PF = 0,8 Configuration Configuration autonomy [min]
[min] type
- - 1x40x34Ah A3 17
- - 1x40x54Ah A3 22
4x32x9 Ah 10 4x32x9Ah A3 25
Internal +
external 1x32x34Ah 12,5 1x32x34Ah A3 31,5
batteries - - 1x40x75Ah N 38,5
[min]
- - 1x40x100Ah N 60,5
- - 2x40x100Ah N 140
36
Liebert EXS 60 kVA
Product description
Feature Liebert® EXS Weight [kg]
Rating 60 kVA Empty 215
Technology Double-Conversion T-free
1x32x34Ah 655
Input Power Factor 0.99
Load Power Factor Up to 1 1x40x34Ah 855
Input THDi ≤ 3%
Nominal Input Voltage 380 – 400 – 415 V
Nominal Input Frequency 50/60 Hz 1600 mm
37
Liebert EXS 60kVA
Efficiency
97.00%
96.50%
96.10%
95.98%
96.00%
95.55%
95.50%
95.00%
95.00%
94.50%
94.00%
20% 30% 40% 50% 60% 70% 80% 90% 100%
38
Liebert EXS 60 kVA
Integrated runtime
Liebert EXS 60kVA
up to 1x40x34 Ah
39
Liebert EXS 60 kVA
Front and rear view
Display panel Power module Customer cables
ventilation holes
Cold start
button
Dry contacts
USB port
Ventilation
holes Parallel and LBS
ports
Vertiv™ IntelliSlot™
ports Output, input and
Maintenance
static bypass
Bypass breaker
breakers Battery
Casters
ventilation holes 40
Liebert EXS 60 kVA
Breakers
Static bypass breaker
(125 A) Input breaker
Output breaker (125 A)
(100 A)
42
Liebert EXS 60 kVA
Parallel system
Capacity Redundancy
43
Liebert EXS 60 kVA
Serviceability
45
Liebert EXS
Options
46
BCB options for Liebert EXS
Liebert EXS 30-40kVA Liebert EXS 60kVA
BCB rating: 160 A BCB rating: 225 A
BCB WxDxH: 450x252x636 mm BCB WxDxH: 450x252x636 mm
47
Battery cabinet options for Liebert EXS
Battery cabinet type A3
WxDxH: 600x825x1600 mm
Weight (empty frame): 115 kg
Weight (4x32x9Ah): 480 kg
Weight (32x34Ah): 515 kg
Weight (40x34Ah): 605 kg
Weight (40x54Ah): 855 kg
Battery Battery brand Battery type
5y: 9Ah CSB HR 1234W
10y: 9Ah CSB HRL 1234W
10y: 34Ah LEOCH XP12-150
10y: 54Ah CSB GPL 12520
48
Battery cabinet options for Liebert EXS
49
Back-feed protection option
Maintenance bypass switch Q3
UPS
UUU
Shorting copper Bypass input switch Q2
bar of common
input configuration
Automatic
Rectifier DC inverter switch
Inverter UPS output
UUU
bus
Rectifier input Output switch Q5
Mains input switch Q1
Charger
Battery
Shunt-trip coil (and related cables) added to the mains input and static bypass input breakers to
open in case of back-feed,
so to stop the flowing of current back to the mains or generator
50
Withstand short-circuit current 30kA option
Automatic
Rectifier DC inverter switch
Inverter UPS output
bus
Rectifier input Output switch Q5
Mains input switch Q1
Charger
Battery
Fuses (and related cables) added to the static bypass to enhance the
short-circuit withstand current up to 30 kA
51
IP31 option
IP Protection:
Protection against the contact of solid bodies to 2.5mm
and vertical fall of water drops
Confidential. Property of Vertiv. 52
Liebert EXS 10-80 kVA
Monitoring
53
Liebert EXS 10-60 kVA
Vertiv LIFE Services compatibility
Remote diagnostic and preventive monitoring service
54
Liebert EXS 10-60 kVA
Vertiv LIFE Services compatibility
• HTTP Client
OVER IP • Reduced communication cost
• Non-intrusive approach
GSM • Solution when landline is unavailable
55
Liebert EXS 10-60 kVA
Optimized and integrated solution