Semi Conductor Manufacturing 1
Semi Conductor Manufacturing 1
MANILA CAMPUS
COLLEGE OF ENGINEERING
MECHANICAL ENGINEERING DEPARTMENT
In Partial Fulfillment of the course subject NME 4102: Air-Conditioning and Ventilation
Systems
Submitted by:
Hadap, John Israel F.
Ocampo, John Rey T.
Submitted to:
Engr. Diosdado Doctor
INTRODUCTION
3.8.1
3.8.2
3.9
5.1 Chiller
GLOSSARY OF TERMS
REFERENCES
Introduction
The HVAC's primary purpose is to provide the people their needs towards
thermal comfort and good air quality. The heating and air conditioning function by
moving the warm air, whether inside or outside the establishment to attain the desired
heat intensity while ventilation is responsible for the exchange of air within a space to
provide better air quality indoors. The air quality treatment requires the removal of
elements such as smoke, dust, odor, carbon dioxide, and airborne bacteria.
Building Description
Most of the buildings around the facility also work with electronic components,
Shown on Figure 1.1. A world-class economic processing zone with big factories, one of
those factories is where we will apply our centralized air-conditioning system. Sitting on
a 10.8-hectare lot, lies the semi-conductor manufacturing facility. An approximation of
the lot is shown in Figure 1.2 to better interpret the location of the facility.
Source:
Google Maps 2021
Imagery
Area to be
conditioned
On the first section, a floor plan from the highlighted area from Figure 1.3 is
shown. It is a single-storey building used to manufacture semi-conductors. Having a
total area of 2021.72 m2, the provided floor plan will be the basis of the design of a
centralized air-conditioning system – Shown in Figure 1.4.
Figure 1.4 Semi-Conductor Manufacturing Facility’s Floor Plan
1.3 Zoning
The zoning section provides the zone description together with its area allocation
and orientation. The division of zone is beneficial for the design of air-conditioning and
ventilation system due to the facility’s lack of walls separating each testing procedures,
in which makes the facility wide open. The zoning is also used to produce a more
precise outcome.
Figure 1.5 represents the division of zones of the testing area of a semi-
conductor manufacturing site. It enables separate strategies of air-conditioning and
ventilation system to be applied depending of the zone inclusions.
Zone 5 Zone 3
Zone 4
Zone 2
Zone 1
Zone 1
The first zone is divided into five (5) different segments, all chosen area are not
directly involved on the testing procedure of a semi-conductor. Such areas are the
following; Service lobby, machine room, smock room, maintenance room, and electrical
room. The zone one covers a total floor area of 414.94 m2.
Figure 1.6 Zoning Layout of Zone 1
Zone 2
Zone two consist of three (3) segments, chosen segments are within the range of
loading and unloading location. The area also serves as the main passage for the
workers and materials needed for the testing and packaging of semi-conductor. The
zone covers a total floor area of 618.3 m2.
Zone 3
The zone is particularly focused on the semi-conductor testing, in which involves
the usage of different sets of machineries and manpower. The zone is divided into two
(2) segments, loading and unloading area, and the burn-in testing area. The testing
area can detect early failures in the product and enables the semi-conductor to reduce
the potential defects and conflicts during the usage of the product. The burn-in
procedure typically ranges for a time period of 48 to 168 hours. The zone three covers a
total floor area of 381.84 m2.
Zone four consist of wafer probing equipment used for the process of testing
each die performance and status of a semi-conductor. The portion contains one (1)
handling equipment and four (4) Eagle Test System (ETS-1) which is designed to
perform a high-volume production testing of integrated circuits. The zone four covers a
total floor area of 308.84 m2.
The zone five includes different sets of handling machineries used to produce an
excellent packaging for semi-conductor that passes the testing procedures on zones
four and five. Zone five covers a total floor area of 298.29 m2.
Figure 1.10 Zoning Layout of Zone 5
Table 1.1 Zoning Description
Table 1.1 presents the summary of five (5) different zones with its corresponding
area allocation; it also shows the area dimension together with its orientation for a
specific portion, in a semi-conductor manufacturing facility having a total floor area of
2021.72 m2.
Chapter II
The second chapter involves calculations of the design parameters beneficial for
the application of air-conditioning system strategies that is used for the testing portion of
a semi-conductor manufacturing facility. Such computations are the following;
conduction through external surfaces, transmission load, and others that may affect the
cooling load value. The chapter will also include the tabulated data from the
computation that is used for the evaluation of the air-conditioning design outcome.
Upon the application of air-conditioning and ventilation system for the testing site
of semi-conductor manufacturing facility, factors such as the inside and outside dry bulb
temperatures and humidity ratio should first be considered. It will help on further
computations to evaluate the necessary amount of cooling loads to be applied in the
structure.
Table 2.1 considers the highest temperature recorded during year 2010 to 2020
from the Figure 2.1 as the main basis of the facility’ air-conditioning design.
Temperature
Dry Bulb 39 oC
Relative Humidity 72 %
kg moisture
Humidity Ratio 0.027
kg dry air
Source: Stoecker 1979, Time and Date
With the use of dry bulb and relative humidity provided for year 2010 to 2020 in
the province of Laguna, humidity ratio can now be identified with the use of
psychometric chart at a standard barometric pressure of 101.325 kPa. The gathered
readings are critical for the calculation of design temperature and relative humidity
needed in the semi-conductor manufacturing facility.
kg mo .
≈ 0.032
kg d . air
By using the data from the Table 2.1, the outside relative humidity can now be
calculated with the use of equation pertaining to humidity ratio (W).
ps
W =0.622 ( Stoecker , 1979)
pt − ps
Where:
kg mo .
W =Humidity Ratio; W =0.032
kg d .air
pt =atmospheric pressure ; pt =101.325 kPa
0.032
kg moisture
kg dry air
=0.622
( ps
101.325 kpa−p s )
ps =4.96 kPa
The saturation pressure ( p sat ) of the pure water at the same temperature can be
found in the book of Stoecker 2nd edition, Table A-1 using interpolation.
ps
RH = (Stoecker , 1979)
p sat
4.22 kPa
RH = × 100 %
7 kPa
RH =60.29 %
The 2007 ASHRAE handbook – HVAC application was used in determining the
standard temperature range for a semi-conductor manufacturing facility. The handbook
provided the dry bulb and relative humidity value necessary for a good air-conditioning
design.
Source: ASHRAE, 2007
Overall, the summary of design temperature and relative humidity are presented
at the Table 2.2 for evaluation. The mean of relative humidity range provided by 2007
ASHRAE handbook was used for the inside desired value.
The thermal resistance of air or air film is small relative to the thermal resistance
of most wall assemblies. But is still considered on solving the over-all resistance of the
design. Air Film, is an imaginary film on the surface on a building, either exterior or
interior. On the interior wall surface, the thermal resistance of air is shown in Table 2.3
as still air. It is dependent of the position of the surface and the direction of heat
transfer. On the exterior wall surface, air is moved by wind, hence the thermal
resistance is also dependent with windspeed. Table 2.3 shows the standardized value
of surface resistance on the interior and exterior wall. (ASHRAE, 2009)
Thermal
Heat Transfer
Resistance, R
Direction
( hr ∙ f t 2 ∙ ℉ /BTU )
Vertical Still Air Horizontal 0.68
7.5 mph Wind Any 0.25
Source: ASHRAE, 2009 – Surface Resistance
Heat gain by a direct contact from sunrays affects the inside temperature of the
establishment the most. Whereas, all surfaces of the manufacturing facility having an
open contact to the sun will be considered throughout the computation to determine the
required amount of cooling load in order to attain the desired inside temperature. Such
surfaces involved are the external walls, roof and windows. The equation provided
below will be used as the main basis to compute the thermal conduction through
exterior structures.
Zon Thermal
Type Description Quantity
e Conductivity
6mm Acrylic/ Polycarb (Swinging
3 Single Glazing – Insulated Fiberglass/ Vinyl 1 4.18 W/(m K)
Frame)
3.2 mm glass (Sliding –
5 Single Glazing 2 5.20 W/(m K)
Wood/Vinyl Frame)
Source: 2017 ASHRAE Handbook – Fundamentals and Stoecker 1979
Figure 2.2 shows the type of window being considered for each zone. However,
the portion of the semiconductor manufacturing facility whereas the design will be
applied only consist a total of three (3) windows based on the floorplan layout presented
in chapter one.
Figure 2.5 presents the glass specification used for zones 3 and 5 for the
establishment. It also demonstrates a decrease in temperature as the heat passes
through the glass. However, there will be no considered solar heat gain through
transparent surfaces in the facility due to the lack of external windows on the floorplan
layout that has a direct contact to the sun, since the windows are only located in
between zones as shown in the zoning description on chapter one. Yet, the glass and
other transparent surfaces specification that can be found within the site are still
gathered for the computation of the transmission load.
T outside
T inside
The external wall design specifications are shown in the Figure 2.6 to better
visualize the wall composition. The type of material, thermal resistance and wall
thickness are also included to be used in cooling load computation. However, the
cooling load required for the conduction through facility’s ceiling will be disregarded on
the computation, since the facility is a two-storey building and the main facility to be
airconditioned is located on the ground level.
Figure 2.6 Exterior Wall Composition
CEMENT PLASTER
LIGHTWEIGHT AGGREGATE
The external wall composition is used as the main basis in the computation for
the conduction through external wall surfaces that passes through the establishment.
Table 2.5 presents the material resistance data of the wall whereas all necessary data
such as the thermal conductivity, thickness and thermal resistance of the wall material
are indicated. Those value will set the limit of the heat that passes through the walls
from the outside environment into a lower temperature.
Thermal Thermal
Thickness (x)
Surface Type Conductivity (k) Resistance (R)
(mm) 2
W /(m∙ K ) (m ∙ k )/W
Outside Air film - - - 0.029
Gypsum
Exterior Material 10 0.16 -
wallboard
Lightweight
Concrete 127 0.20 -
aggregate
Insulating Mineral wool
25 0.04 1.940
Material fiber
Cement
Interior Material 15 0.72 -
plaster
Inside Air film - - - 0.120
Source: 2017 ASHRAE Handbook – Fundamentals and Stoecker 1979
x
R=
k
R=
10 mm ( 10001 mmm ) =0.014 m ∙ k
2
W W
0.72
m∙ k
By following the same solving procedure for the remaining wall thermal
resistance value:
2
m ∙k
Rtotal= ( 0.029+0.014+ 0.635+0.02+0.120 )
W
2
m ∙k
Rtotal=0.818
W
While, for the computation of the wall overall heat transfer coefficient that will be
used in the computation of thermal transmission load.
1
U= 2
m ∙k
0.818
W
W
U =1.22 2
m K
The surface area that will undergo thermal transmission process is provided in
Table 2.8. One example computation for wall area is also given below for clarification.
For Hallway :W A =4 m× 48 m
2
W A =192 m
By following the same solving procedure for the remaining wall area:
Wall Wall
Zone Wall Area
Segment Orientation Height Lengt
No. (m2)
(m) h (m)
Hallway West 4 48 192
Service Lobby South 4 7.5 30
Machine Room South 4 4.3 17
1
Smock Room South 4 9 36
South 12 48
Electrical Room 4
East 10.2 40
BIB Cart Parking Area East 4 2.85 11
2
Handler Parking Area South 4 6.3 25
Burn-In Loading &
East 4 7 28
Unloading Area
3
North 11.5 46
Burn-In Testing Area 4
East 27.6 110
4 Water Probing Area North 4 18 72
Semi-Conductor
5 North 4 14.8 59
Handling Area
Source: Pita, 2002
Q=U × A ×CLT D c
W
Q=1.22 2
( 240 m2 ) ( 14 ) K
m K
Q=3279.14 W
Similar process for the remaining values will be used for further computation.
Hence, the computed data is listed on the Table 2.7 excluding the overall heat transfer
coefficient (U) due to the similar wall configuration value.
Thermal
Zone Wall Area CLTDc
Segment Orientation Conduction
No. (m2) (K )
(W)
Hallway West 192 14 2268
Service Lobby South 30 19 480.94
Machine Room South 17 19 275.74
1 Smock Room South 36 19 577.13
Maintenance Room - - - -
South 48 19 769.5
Electrical Room
East 40 19 769.5
BIB Cart Parking
East 11 19 654.075
Area
Handler Parking
2 South 25 19 182.76
Area
Loading &
- - - -
Unloading Area
3 Burn-In Loading &
East 28 19 -
Unloading Area
Burn-In Testing North 46 19 448.88
North 46 19 1769.85
Area
East 110 19
4 Water Probing Area North 72 19 737.44
Semi-Conductor
5 North 59 19 1154.25
Handling Area
Total 10088
Source: Pita, 2002
Thermal
Zone Wall Area CLTDc
Segment Orientation Conduction
No. (m2) (K )
(W)
Hallway West 192 14 3279.36
Service Lobby South 30 19 695.4
Machine Room South 17 19 394.06
1 Smock Room South 36 19 834.48
Maintenance Room - - - -
South 48 19 1112.64
Electrical Room
East 40 19 927.2
BIB Cart Parking
East 11 19 254.98
Area
Handler Parking
2 South 25 19 579.5
Area
Loading &
- - - -
Unloading Area
Burn-In Loading &
East 28 19 649.04
Unloading Area
3
Burn-In Testing North 46 19 1066.28
Area East 110 19 2549.8
4 Water Probing Area North 72 19 1668.96
Semi-Conductor
5 North 59 19 1367.62
Handling Area
Total 15379.32
Source: Pita, 2002
Thermal transmission load section discusses the sensible heat load that affects
the cooling load in different ways. That includes the gain or loss of heat passing through
each facilities section. It includes the doors, walls, transparent surfaces, and others
where temperature difference occurs. However, the transmission load on the ceiling of
semiconductor manufacturing facility is not considered due to the 2 nd floor level of the
establishment where room temperature is also based from 20 oC.
The primary equations that will be involved in the thermal transmission load:
1 x
U= ¿ ; R= (Stoecker, 1979)
R total
k
Where:
QTT = Amount of thermal transmission load , ( W )
( )
2
¿ m ∙k
Rtotal=Total thermal resistance ,
W
x=thickness of wall(m)
Overall
Heat Surface
Wall Transmission
Transfer Temperature
Zone Segment Orientation Area Load
Coefficient Difference -
(m2) (W)
W ¿−t i (K )
( 2
¿
m ∙K
Hallway West 0.693 192 25-20 665.28
Service
South 0.693 30 25-20 103.95
Lobby
Machine
South 0.693 17.2 25-20 59.59
1 Room
Smock
South 0.693 36 25-20 124.74
Room
Electrical South 0.693 48 25-20 166.32
Room East 0.693 40.8 25-20 141.37
Loading &
2 Unloading East 0.693 61.6 213.44
Area
Burn-In North 0.693 28 25-20 97.02
3
Testing Area East 0.693 110 25-20 381.15
5 Semi- North 0.693 76 25-20 263.34
Conductor
Handling
Area
Total 2216.21
Source: 2017 ASHRAE Handbook – Fundamentals and Stoecker 1979
The thermal transmission load on the transparent surfaces only involves two (2)
sets of windows that can be located in between zones. These two (2) windows will be
used for the computation of the amount of heat transfer from a zone to another. The
windows are located in zones 3 and 5 as shown in the floorplan layout (Chapter 1).
Table 2.9 shows the transmission load through the establishment windows.
Heat Surface
Transfer Area temperature Transmission
Zone Type Description 2
Coefficient (m ) difference - Load (W)
2
(W /m ∙ K ) ¿−t i (K )
6mm Acrylic/
Polycarb
Single (Swinging –
3 4.18 3 20-20 0
Glazing Insulated
Fiberglass/
Vinyl Frame)
3.2 mm
glass
Single
5 (Sliding – 5.20 3 25-20 78 x 2
Glazing
Wood/Vinyl
Frame)
Total 156
Source: 2017 ASHRAE Handbook – Fundamentals and Stoecker 1979
Door Thermal Transmission Load
Heat Transfer
Transmission
Zone Segment Type Quantity Coefficient
2
Load (W)
(W /m ∙ K )
Hallway - - - -
Single
Service Lobby 1 0.44 13.31
Door
Single
Machine Room 1 0.44 13.31
Door
1
Double
Smock Room 4 0.44 106.44
Door
Single
Maintenance Room 2 0.44 53.22
Door
Electrical Room - - - -
Double
BIB Cart Parking Area 1 0.44 13.31
Door
2 Handler Parking Area - - - -
Loading & Unloading
- - - -
Area
Burn-In Loading & Double
1 0.44 13.31
Unloading Area Door
3
Double
Burn-In Testing Area 2 0.44 53.22
Door
4 Water Probing Area - - - -
Semi-Conductor Handling
5 - - - -
Area
Total 266.12
Note: The dash (-) in the Table 2.10 means that the segment is an open area
Source: 2017 ASHRAE Handbook – Fundamentals and Stoecker 1979
and does not require any use of doors.
Table 2.11 Summary for Transmission Load
T. L. T. L.
T. L.
through through
Zone Segment Orientation through Total (W)
windows doors
walls (W)
(W) (W)
Hallway West 2430 - - 665.28
Service Lobby South 379.69 - 13.31 117.26
Machine Room South 217.69 - 13.31 72.9
Smock Room South 455.63 - 106.44 231.18
1
Maintenance
- - - 53.22 53.22
Room
South 607.5 - - 166.32
Electrical Room
East 607.5 - - 141.37
BIB Cart Parking
East - - 13.31 13.31
Area
Handler Parking
2 South - - - 0
Area
Loading &
- - - - 213.44
Unloading Area
Burn-In Loading
& Unloading East - - 13.31 13.31
3 Area
Burn-In Testing North 354.375 - 53.22 150.24
Area East 1397.25 - - 381.15
Water Probing
4 North - - - 0
Area
Semi-Conductor
5 North - 156 - 419.34
Handling Area
Total 2638.32
Table 2.11 present the total transmission load passing through establishment’s
internal surfaces. The table also indicated each load for heat that passes through
internal walls, windows, and doors having a total of 2638.32 watts.
Another factor affecting the amount of cooling load required is the lighting load,
whereas it emits heat and produces light simultaneously. The lighting load computation
will include the calculation of the required number of lumens per square area in order to
determine the power rating necessary for the computation of lighting load. It will also
help to determine the number of required lightbulbs involving the calculation of required
number of lumens per area. The design for the number of lumens per square area will
be set as 350 as the standard value. Figure 2.9 presents the type of light bulb to be
used on the whole testing portion of semiconductor manufacturing facility.
Table 2.12 presents the calculated value for the required lumens per light bulb
using the standard lumens per square area of 200. The equation used on the table is
presented below:
No . of lumens
No . of Light Bulb=
Lumens per bulb
For the sample computation of the minimum number of light bulbs required for
hallway:
34650 cd
No . of Light Bulb=
cd
2150
bulb
Standard
Wall Floor Lumens Required No. of
Zone
Segment Area Area per Area Lumens Light
No.
( )
(m2) (m2) cd (cd ) Bulb
2
m
Hallway 240 68 180 12240 6
Service Lobby 37.5 28 180 5040 2
Machine Room 21.5 15 180 2700 1
1 Smock Room 45 27 180 4860 2
Maintenance
- 7.2 180 1296 1
Room
Electrical Room 60 75 180 13500 6
BIB Cart Parking
51 34.16 180 6148.8 3
Area
Handler Parking
2 14.25 42 180 7560 4
Area
Loading &
237.5 480 180 86400 40
Unloading Area
Burn-In Loading
3 & Unloading 195.5 330 180 59400 28
Area
Water Probing
4 57.5 255 180 45900 21
Area
Semi-Conductor
5 90 275.5 180 49590 23
Handling Area
Source: Philips
The equation for determining cooling load due to heat gain from lighting is:
Where:
W =Lighting Capacity
B=Ballast Factor
Figure 2.10 shows the table used for identifying the amount of CLF needed for
semiconductor manufacturing operation which it involves 16 full hours of operation.
Therefore, by following the same solving procedure, the value for total occupants’
load during the working hours in Semi-Conductor Manufacturing Site within the testing
facility is shown in Table 2.13 below
Lighting
Ballast
Zone Segment Type Quantity CLF Load (W)
Factor
The heat gain from people is composed of two parts, sensible heat and the latent
heat resulting from perspiration. Some of the sensible heat may be absorbed by the
heat storage effect, but not the latent heat. The equations for cooling loads from
sensible and latent heat gains from people are:
Where:
The number of people displayed in the site floorplan is used for the calculation of
the number of occupants. However, 50% of the total occupants displayed in the floor
plan will be added for allowance, this will help the cooling load calculation to be
consistent on the actual load of people during the working hours.
Figure 2.11 presents the sensible and latent heat gain within the manufacturing
facility during working hours. The values provided will be used as a variable in
calculating total occupant’s load.
On the other hand, the CLF for people is shown in Figure 2.12 in which a total of
10 hours in space and time after entry will be used, having an overall cooling load factor
of 0.89 for people within the facility. Meanwhile, below also shows the sample
computation on hallway for the values presented in the Table 2.14.
Qs =978.11Watts
Ql=2549.7 Watts
Qt =3527.81Watts
Therefore, by following the same solving procedure, the value for total occupants’
load during the working hours in Semi-Conductor Manufacturing Site within the testing
facility is shown in Table 2.13 below.
Total
No. of Sensible Latent
Zone Segment CLF Occupants
Occupants Heat (W) Heat (W)
Load (W)
Hallway 10 0.89 978.11 1831.70 2809.81
The heat output from motors and the equipment driven by them results from the
conversion of the electrical energy to heat. The proportion of heat generated that is
gained by the air-conditioned space depends on whether the motor and driven load are
both in the space or only one of them is (PITA, 2002). Below is the equipment load
equation provided by the handbook.
N=No . of equipment
Equipment
Equipment
Equipment Description Quantity Power
Load
Rating
Zone 1
PC System 2 60 120
Zone 2
RASCO JAGUAR Handler 4 1500 6000
SYNAX SX1101 Handler 3 1500 4500
MCT 5100 DUAL Probing Machine 9 2250 20250
MCT 5100 ePRO Handler 3 1500 4500
PC System 8 60 480
EPSON
Tester 2 1500 3000
NS800 Series
EPSON
Photo Printer 1 500 500
ASL3000
SRM MAV-068 Handler 1 1150 1150
EPSON
Handler 11 1200 13200
NS6040
Zone 3
DCW-336F-MP550 Burn-In Oven 7 1500 10500
DCA-336F-MP Burn-In Oven 7 1500 10500
MP-1406F Burn-In Oven 5 800 4000
MP-206F-WAS Burn-In Oven 9 1500 13500
MP-336F Burn-In Oven 2 1000 2000
DC 136 Burn-In Oven 1 3500 3500
DC-1506-WAS Burn-In Oven 1 3220 3220
AEHR MAX2B Burn-In Oven 3 500 1500
AEHR ATS-12100 Burn-in Oven 13 900 11700
PC SYSTEM 2 60 120
Zone 4
MCT 5100 DUAL Probing Machine 1 800 800
Wafer Inspection
MTT ETS-1 4 1200 4800
Equipment
PC System 4 60 240
Zone 5
MCT 3608 E Handler 2 500 1000
RASCO MAV-0 Handler 1 1500 1500
RASCO MAV-044 Handler 1 1500 1500
RASCO ePRO Handler 3 580 1740
AETRIUM 5050
Handler 1 2000 2000
MAV -040
SMR MAV-02. Handler 3 950 2850
MCT AETRIUM
Handler 9 800 7200
EPRO
MCT 3608 ePRO Handler 17 500 8500
ASECO (S2-006
Handler 2 1500 3000
SENTRY 20)
MCT 5100 ePRO Handler 4 400 1600
PC System 10 60 600
Total 151570
Table 2.14 presents the total equipment load for the testing and packaging sector
of a semiconductor manufacturing facility. Some of the equivalent value shown for each
equipment rating are derived from the machine’s manual and manufacturer. However,
some equipment that shows no power rating information from the said sources are
obtained from alternative machines that has similar equipment configuration. For
instance, due to lack of information regarding to the power rating of Rasco MAV-0 on its
equipment manual and different HVAC handbooks, the power rating being considered is
from MCT SO 2800 that has the same function and technical configuration but different
brand and model.
2.7 Infiltration
Infiltration is defined as the flow of outside air into the building in either through
cracks around windows, other unintentional openings, or through the normal use of
exterior doors. (ASHRAE, 2009). It has a significant influence on the cooling load for it
produces both sensible and latent heat gain to the rooms (Pita, 2002).
The amount of sensible heat gain can be calculated using the sensible heat
equation:
Qs =M C p ΔT (Pita , 2002)
Where:
Qs =The heat required ¿ cool outdoor ( warm ) air ¿ room temperature , BTU /hr
BTU
C p=Specific heat of air , ∙F
lb
The equation above from Pita, gives us a value of (m) measured in lb/hr.
However, flow rates in HVAC are usually measured in ft 3/min (CFM). Hence, converting
the lb/hr value of (m) to ft3/min gives us the equation:
Where:
3
CFM =Air infiltration flow rate , f t /min
Outdoor air, infiltrating the building, is often less humid than the inside air. At
some point, the air humidity ratio in the building may fall to an unacceptable level for
comfort. To maintain comfortable air humidity ratio, water vapor must be added. The
addition of this moisture requires latent heat vaporization of water (Pita, 2002). The
equation for the latent heat is expressed in the equation:
Where:
3
CFM =Air infiltration Rate , f t /min
' '
W i∧W o=Indoor∧outdoor humidity ratio , grains water /lb dry air
In solving the CFM, doors and windows are both considered and calculated by
using “crack method”. Pita describes the crack method as the accurate estimate of the
rate of infiltration per foot of crack opening established by using data from various
energy standards. Figure 2.13 presents the typical allowable design air infiltration rates
through exterior doors and windows.
CFM =I ∙ L
Where:
3
CFM =Air infiltration flow rate , f t /min
CFM
I =Infiltration rate through cracks ,
ft
There are a total of 3 windows in the semi-conductor facility. Table 2.15 presents
a data table for these windows in which the CFM from the crack openings are
calculated. In addition, the design of the windows is a standard double-hung type 3 ft W
x 4 ft H window. Where the length of crack is:
L=3 ( 3 ) +2 ( 4 )=17 ft
Zone Type Infiltration Rate Quantity Length of crack, ft CFM, ft3/min
The calculation of CFM from doors also came from the Infiltration rates of Pita,
shown on Figure 2.14.
For a sample computation, the calculation for the infiltration load on zone 3 is
presented below whereas,
QT =Qs +Ql
Qs =1.1 x CFM x Δ T
( )
3
ft
Qs =1.1 6.29 ( 77−68 ) ℉
min
( )
BTU 1 Watts
Qs =62.271 =18.26 Watts
hr BTU
3.41
hr
For the latent heat:
( )
3
ft grains water
Ql=0.68 6.29 ( 0.032−0.027 )
min lb dry air
( )
BTU 1 Watts
Q l=0.0214 =0.0063 Watts
hr BTU
3.41
hr
QT =18.26+0.0063
QT =18.27 Watts
2.8 Ventilation
The ventilation helps to improve indoor air quality by removing moisture, smoke,
smells, heat, dust, airborne bacteria, carbon dioxide, and other pollutants, as well as
controlling temperature and replenishing oxygen. The sensible and latent heat of
outside air is usually greater that that of the room air, so it becomes part of the cooling
load (Pita 2002). By the using the provided equation for both latent and sensible heat to
determine the amount of ventilation load necessary to attain the design indoor
temperature of the building.
Where:
BTU
Q s =Sensible cooling loads ¿ ventilation air ,
hr
3
CFM =air ventilation rate , f t /min
Where:
BTU
Ql=Latent cooling loads ¿ ventilation air ,
hr
' '
W o −W i =Outdoor ∧inside humidity ratio , grains water /lb dry air
The value used for the ACH required for the CFM computation are collected from
“Americraft Manufacturing Co. INC.” Table 2.17 presents the data for ACH whereas the
all values are extracted. ACH depends on the purpose or usage of the room, whereas
some rooms on the semiconductor manufacturing facility will require higher air change
per hour than the others. For instance, the zone 3 burn in testing air requires higher air
change compared on the zone 2 which does not govern any operating equipment.
Source: https://americraftmfg.com/general-ventilation-requirements/
Hence for the sample computation of CFM on zone 2 using the ACH value
presented above:
( ( ) )
3
3.28 ft
556.16 m3
m f t3
CFM =10 = 3270.92
60 min
2 10 556.16 3270.92
3 12 330 2328.98
4 12 255 1799.65
5 10 180 1058.63
Note: Zone 1 is not included in the table since ventilation is not necessary.
Now, for the sample computation of sensible and latent cooling loads for zone 2:
QT =Qs +Ql
Qs =1.1 ( CFM ) TC
( )
3
ft
Qs =1.1 3270.92 ( 77−68 ) ℉
min
( )
BTU 1 Watts
Q s =32382.11 =9496.22 Watts
hr BTU
3.41
hr
( )
3
ft grains water
Ql=0.68 3270.92 ( 0.032−0.027 )
min lb dry air
( )
BTU 1 Watts
Ql=11.12 =3.26 Watts
hr BTU
3.41
hr
QT =9496.22+3.26
QT =9499.48 Watts
Conduction TOTAL
Transmissio Lighting Occupancy Equipment Infiltration Ventilation
Description through External (10% FS) TOR
n Load (W) Load (W) Load (W) Load (W) Load (W) Load (W)
Surfaces (W) WATTS
Zone 1
Hallway 3279.36 665.28 435.744 2809.81 0 0 0 7909.21 2.25
Maintenance
- 53.22 72.624 1218.76 120 0 0 1611.06 0.46
Room
Electrical Room 1112.64 307.69 435.744 1793.76 0 0 0 4014.82 1.14
Total Cooling Load in Zone 1 19628.3 5.58
Zone 2
BIB Cart Parking
927.2 13.31 217.872 415.42 0 0 0 1731.18 0.49
Area
Handler Parking
254.98 0 290.496 642.52 0 0 0 1306.80 0.37
Area
Loading &
579.5 213.44 2904.96 7034.58 53580 0 9499.48 81193.16 23.07
Unloading Area
Total Cooling Load in Zone 2 84231.1 23.93
Zone 3
Burn-In Loading
& Unloading - 13.31 2033.472 3165.56 60540 0 0 72327.58 20.55
Area
Burn-In Testing
649.04 531.39 1525.104 2843.77 - 18.27 6763.88 13564.60 3.85
Area
Zone 4
Zone 5
Semi-Conductor
2549.8 419.34 435.744 6726.59 31490 36.53 3074.50 49205.75 13.98
Handling Area
11% 7%
4%
13%
SOLAR AND TRANSMISSION
LOAD
LIGHTING LOAD
OCCUPANTS LOAD
EQUIPMENT LOAD
INFILTRATION AND VENTI-
LATION LOAD
65%
For observation purposes on which factor affects the cooling load of the semiconductor manufacturing facility the
most is provided above through a pie chart in Figure 2.15. The graph displays the equivalent required cooling load in
terms of wattage for factors within the facility adding heat to the system. Therefore, as a conclusion, in order to reach the
design inside temperature of 20 oC having 39 oC on the outside of the facility, a total of 72.68 ton of refrigeration must be
supplied on the testing portion of the semiconductor manufacturing facility to attain the desired temperature.
0%
21%
35%
4%
Zone 1
Zone 2
Zone 3
Zone 4
Zone 5
40%
Figure 2.16 presents the equipment cooling load for each zone to determine which area requires higher cooling
load due to higher quantity of equipment. Based on the figure presented above, it can be seen that zone 3 has the highest
required cooling load in terms of equipment due to the use of burn in ovens for the testing of semiconductor wafer under
extreme temperature level. On the other hand, it can also be observed that zones 1 and 4 has the lowest required cooling
load due to the small quantity of equipment required.