Operating Instructions
Micropilot FMR51, FMR52
HART
Free space radar
Order code: XXXXX-XXXXXX
1. Ser. no.: XXXXXXXXXXXX
Ext. ord. cd.: XXX.XXXX.XX
Serial number
2. www.endress.com/deviceviewer Endress+Hauser
Operations App
3.
A0023555
2 Endress+Hauser
Table of contents
Table of contents
Endress+Hauser 3
Table of contents
13 Maintenance . . . . . . . . . . . . . . . . . . . . . . 84
13.1 Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . 84
13.2 Replacing seals . . . . . . . . . . . . . . . . . . . . . . . 84
14 Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
14.1 General information on repairs . . . . . . . . . . . . 85
14.1.1 Repair concept . . . . . . . . . . . . . . . . . 85
4 Endress+Hauser
Micropilot FMR51, FMR52 HART Important document information
1.2 Symbols
Symbol Meaning
DANGER!
DANGER This symbol alerts you to a dangerous situation. Failure to avoid this situation will
result in serious or fatal injury.
WARNING!
WARNING This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in serious or fatal injury.
CAUTION!
CAUTION This symbol alerts you to a dangerous situation. Failure to avoid this situation can
result in minor or medium injury.
NOTE!
NOTICE This symbol contains information on procedures and other facts which do not result in
personal injury.
Symbol Meaning
Direct current
Alternating current
Ground connection
A grounded terminal which, as far as the operator is concerned, is grounded via a
grounding system.
Equipotential connection
A connection that has to be connected to the plant grounding system: This may be a
potential equalization line or a star grounding system depending on national or
company codes of practice.
Endress+Hauser 5
Important document information Micropilot FMR51, FMR52 HART
Symbol Meaning
Torx screwdriver
A0013442
A0011220
Cross-head screwdriver
A0011219
Allen key
A0011221
Hexagon wrench
A0011222
Symbol Meaning
Permitted
Procedures, processes or actions that are permitted.
Preferred
Procedures, processes or actions that are preferred.
Forbidden
Procedures, processes or actions that are forbidden.
Tip
Indicates additional information.
Reference to documentation
A Reference to page
Reference to graphic
1. , 2. , 3. … Series of steps
Result of a step
Visual inspection
Symbol Meaning
1. , 2. , 3. … Series of steps
A, B, C, ... Views
6 Endress+Hauser
Micropilot FMR51, FMR52 HART Important document information
Symbol Meaning
Hazardous area
- Indicates a hazardous area.
Symbol Meaning
Safety instructions
Observe the safety instructions contained in the associated Operating Instructions.
Brief Operating Instructions Guide that takes you quickly to the 1st measured value
KA01100F (FMR51/FMR52, The Brief Operating Instructions contain all the essential information
HART) from incoming acceptance to initial commissioning.
For an overview of the scope of the associated Technical Documentation, refer to the
following:
• The W@M Device Viewer : Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate
or scan the 2-D matrix code (QR code) on the nameplate.
Endress+Hauser 7
Important document information Micropilot FMR51, FMR52 HART
BB ATEX: II 1/2 G Ex ia IIC T6-T1 Ga/Gb • FMR51 XA00677F XA00677F XA00677F XA00685F -
• FMR52
BC ATEX: II 1/2 G Ex d [ia] IIC T6-T1 Ga/Gb • FMR51 XA00680F XA00680F XA00680F XA00688F XA00680F
• FMR52
BD ATEX: II 1/2/3 G Ex ic [ia Ga] IIC T6-T1 • FMR51 XA00678F XA00678F XA00678F XA00686F XA00678F
Ga/Gb/Gc • FMR52
BL ATEX: II 1/2/3 G Ex nA [ia Ga] IIC T6-T1 • FMR51 XA00678F XA00678F XA00678F XA00686F XA00678F
Ga/Gb/Gc • FMR52
B2 ATEX: II 1/2 G Ex ia IIC T6-T1 Ga/Gb • FMR51 XA00683F XA00683F XA00683F XA00691F -
ATEX: II 1/2 D Ex ia IIIC Txx°C Da/Db • FMR52
B3 ATEX: II 1/2 G Ex d [ia] IIC T6-T1 Ga/Gb • FMR51 XA00684F XA00684F XA00684F XA00692F XA00684F
ATEX: II 1/2 D Ex ta IIIC Txx°C Da/Db • FMR52
B4 ATEX:II 1/2 G Ex ia IIC T6-T1 Ga/Gb • FMR51 XA00681F XA00681F XA00681F XA00689F -
ATEX: II 1/2 G Ex d [ia] IIC T6-T1 Ga/Gb • FMR52
CD CSA C/US DIP Cl.II,III Div.1 Gr.E-G FMR51 XA01113F XA01113F XA01113F XA01115F XA01113F
C2 CSA C/US IS Cl.I,II,III Div.1 Gr.A-G, NI Cl.1 Div. • FMR51 XA01112F XA01112F XA01112F XA01114F -
2, Ex ia • FMR52
C3 CSA C/US XP Cl.I,II,III Div.1 Gr.A-G, NI Cl.1 • FMR51 XA01113F XA01113F XA01113F XA01115F XA01113F
Div.2, Ex d • FMR52
FB FM IS Cl.I,II,III Div.1 Gr.A-G, AEx ia, NI Cl.1 • FMR51 XA01116F XA01116F XA01116F XA01118F -
Div.2 • FMR52
FD FM XP Cl.I,II,III Div.1 Gr.A-G, AEx d, NI Cl.1 • FMR51 XA01117F XA01117F XA01117F XA01119F XA01117F
Div.2 • FMR52
FE FM DIP Cl.II,III Div.1 Gr.E-G FMR51 XA01117F XA01117F XA01117F XA01119F XA01117F
IC IECEx: Ex d [ia] IIC T6-T1 Ga/Gb • FMR51 XA00680F XA00680F XA00680F XA00688F XA00680F
• FMR52
ID IECEx: Ex ic [ia Ga] IIC T6-T1 Ga/Gb/Gc • FMR51 XA00678F XA00678F XA00678F XA00686F XA00678F
• FMR52
IL IECEx: Ex nA [ia Ga] IIC T6-T1 Ga/Gb/Gc • FMR51 XA00678F XA00678F XA00678F XA00686F XA00678F
• FMR52
8 Endress+Hauser
Micropilot FMR51, FMR52 HART Important document information
I3 IECEx: Ex d [ia] IIC T6-T1 Ga/Gb • FMR51 XA00684F XA00684F XA00684F XA00692F XA00684F
IEXEx: Ex ta IIIC Txx°C Da/Db • FMR52
MC INMETRO: Ex d[ia] IIC T6 Ga/Gb • FMR51 XA01292F XA01292F XA01293F XA01298F XA01294F
• FMR52
NC NEPSI Ex d[ia] IIC T6 Ga/Gb • FMR51 XA01202F XA01202F XA01202F XA01211F XA01202F
• FMR52
N2 NEPSI Ex ia IIC T6 Ga/Gb, Ex iaD 20/21 T85… • FMR51 XA01205F XA01205F XA01205F XA01214F -
90oC • FMR52
N3 NEPSI Ex d[ia] IIC T6 Ga/Gb, DIP A20/21 • FMR51 XA01206F XA01206F XA01206F XA01215F XA01206F
T85…90oC IP66 • FMR52
8A FM/CSA IS+XP Cl.I,II,III Div.1 Gr.A-G • FMR51 • XA01112F • XA01112F • XA01112F • XA01114F -
• FMR52 • XA01113F • XA01113F • XA01113F • XA01115F
• XA01116F • XA01116F • XA01116F • XA01118F
• XA01117F • XA01117F • XA01117F • XA01119F
For certified devices the relevant Safety Instructions (XA) are indicated on the
nameplate.
Endress+Hauser 9
Important document information Micropilot FMR51, FMR52 HART
If the device is prepared for the remote display FHX50 (product structure: feature 030:
Display, Operation", option L or M), the Ex marking of some certificates changes according
to the following table 1):
N3 L or M NEPSI Ex d [ia] IIC T6-T1 Ga/Gb, DIP A20/21 [ia D] TA, Txx°C
IP6X
1) The marking of certificates not mentioned in this table are not affected by the FHX50.
10 Endress+Hauser
Micropilot FMR51, FMR52 HART Basic safety instructions
Residual risk
The electronics housing and its built-in components such as display module, main
electronics module and I/O electronics module may heat to 80 °C (176 °F) during operation
through heat transfer from the process as well as power dissipation within the electronics.
During operation the sensor may assume a temperature near the temperature of the
measured material.
Endress+Hauser 11
Basic safety instructions Micropilot FMR51, FMR52 HART
2.5.1 CE mark
The measuring system meets the legal requirements of the applicable EC guidelines. These
are listed in the corresponding EC Declaration of Conformity together with the standards
applied.
Endress+Hauser confirms successful testing of the device by affixing to it the CE mark.
12 Endress+Hauser
Micropilot FMR51, FMR52 HART Product description
3 Product description
1 1 1
2 4 5
3 3 3
A0016818
1 1 1
2 3 5
4 4 4
A0016788
Endress+Hauser 13
Product description Micropilot FMR51, FMR52 HART
1 2 3 5
9
6
7
–
Esc
+
8
E
A0012422
14 Endress+Hauser
Micropilot FMR51, FMR52 HART Product description
Endress+Hauser 15
Incoming acceptance and product identification Micropilot FMR51, FMR52 HART
1=2
A0022480
A0016871
A0015502
A0016872
A0022491
A0022494
If one of these conditions is not satisfied, contact your Endress+Hauser Sales Center.
16 Endress+Hauser
Micropilot FMR51, FMR52 HART Incoming acceptance and product identification
For an overview of the scope of the associated Technical Documentation, refer to the
following:
• The W@M Device Viewer: Enter the serial number from the nameplate
(www.endress.com/deviceviewer)
• The Endress+Hauser Operations App: Enter the serial number from the nameplate or
scan the 2-D matrix code (QR code) on the nameplate.
4.2.1 Nameplate
92 (3.62)
2
1
Order code: 3 10
Ser. no.: 4
Ext. ord. cd.: 8
5
26
47 (1.85)
25
Tp max = 24 MWP: 6 9
23 LN = 7
Ta: 22 15
Mat.: 21
20
FW: 18 Dev.Rev.: 16 11
if modification
19 17 13 X = see sep. label
12
Date: 14
mm (in)
A0019444
Only 33 digits of the extended order code can be indicated on the nameplate. If the
extended order code exceeds 33 digits, the rest will not be shown. However, the
complete extended order code can be viewed in the operating menu of the device:
Extended order code 1 to 3 parameter
Endress+Hauser 17
Storage, Transport Micropilot FMR51, FMR52 HART
5 Storage, Transport
A0016875
18 Endress+Hauser
Micropilot FMR51, FMR52 HART Installation
6 Installation
A0016882
Endress+Hauser 19
Installation Micropilot FMR51, FMR52 HART
A0018944
A0016890
20 Endress+Hauser
Micropilot FMR51, FMR52 HART Installation
3
1
A0017123
Endress+Hauser 21
Installation Micropilot FMR51, FMR52 HART
a
W = 2 . D . tan _
2
D
a
A0016891
The beam angle is defined as the angle α where the energy density of the radar waves
reaches half the value of the maximum energy density (3-dB-width). Microwaves are also
emitted outside the signal beam and can be reflected off interfering installations.
Beam diameter W as a function of beam angle α and measuring distance D:
FMR51
3 m (9.8 ft) 1.22 m (4 ft) 0.95 m (3.1 ft) 0.53 m (1.7 ft) 0.42 m (1.4 ft)
6 m (20 ft) 2.44 m (8 ft) 1.9 m (6.2 ft) 1.05 m (3.4 ft) 0.84 m (2.8 ft)
9 m (30 ft) 3.66 m (12 ft) 2.85 m (9.4 ft) 1.58 m (5.2 ft) 1.26 m (4.1 ft)
12 m (39 ft) 4.88 m (16 ft) 3.80 m (12 ft) 2.1 m (6.9 ft) 1.68 m (5.5 ft)
15 m (49 ft) 6.1 m (20 ft) 4.75 m (16 ft) 2.63 m (8.6 ft) 2.10 m (6.9 ft)
20 m (66 ft) 8.14 m (27 ft) 6.34 m (21 ft) 3.50 m (11 ft) 2.80 m (9.2 ft)
25 m (82 ft) 10.17 m (33 ft) 7.92 m (26 ft) 4.37 m (14 ft) 3.50 m (11 ft)
30 m (98 ft) - 9.50 m (31 ft) 5.25 m (17 ft) 4.20 m (14 ft)
35 m (115 ft) - 11.09 m (36 ft) 6.12 m (20 ft) 4.89 m (16 ft)
40 m (131 ft) - 12.67 m (42 ft) 7.00 m (23 ft) 5.59 m (18 ft)
22 Endress+Hauser
Micropilot FMR51, FMR52 HART Installation
FMR52
Endress+Hauser 23
Installation Micropilot FMR51, FMR52 HART
A
100%
H
B
C
0%
øD
A0018872
FMR51 50(1.97)
> 0.2 (0.7) 50 to 250 (1.97 to 9.84) > 0.3 (1.0)
FMR52 200(7.87)
minimum maximum
EN
DN50/PN16 4 45 65
DN80/PN16 8 40 55
DN100/PN16 8 40 60
DN150/PN16 8 75 115
ASME
2"/150lbs 4 40 55
3"/150lbs 4 65 95
4"/150lbs 8 45 70
6"/150lbs 8 85 125
24 Endress+Hauser
Micropilot FMR51, FMR52 HART Installation
minimum maximum
JIS
10K 50A 4 40 60
10K 80A 8 25 35
10K 100A 8 35 55
Alignment
• Align the antenna vertically to the product surface.
The maximum range may be reduced if the horn antenna is not vertically aligned.
• A marking at the flange (somewhere between the flange holes) or the boss enables
alignment of the antenna. This marking must be aligned towards the tank wall as well
as possible.
A B
°
90
°
90
°
90
° °
°
90 90
90
90 90
° °
90 90
° °
A0018974
Depending on the device version the marking may be a circle or two short parallel
lines.
Nozzle mounting
For optimum measurement, the tip of the antenna should extend below the nozzle.
Depending on the antenna size this is achieved by the following maximum nozzle heights:
Endress+Hauser 25
Installation Micropilot FMR51, FMR52 HART
Hmax
A0016820
øD
A0023611
26 Endress+Hauser
Micropilot FMR51, FMR52 HART Installation
If the antenna doesn't extend below the nozzle, observe the following:
• The nozzle end must be smooth and free of burrs. If possible its edge should be
rounded.
• An interference echo suppression must be performed.
• Please contact Endress+Hauser for applications with higher nozzles than those
indicated in the table.
• For mounting in heigh nozzles the device is available in a version with an antenna
extension of up to 1 000 mm (39.4 in) 4)
• The antenna extension may cause interference echoes in the near range. In this
case it may occur that the maximum measurable level is reduced.
Threaded connection
For devices with a threaded connection it may be necessary - depending on the
antenna size - to unmount the horn before fastening the device and to mount it again
afterwards.
• Tighten with the hexagonal nut only.
• Tool : 55 mm hexagonal wrench
• Maximum permissible torque: 60 Nm (44 lbf ft)
Optimum thickness 1) 3.8 mm (0.15 in) 4.0 mm (0.16 in) 3.8 mm (0.15 in) 3.3 mm (0.13 in)
1) Other possible values for the thickness are multiples of the values listed (e.g. for PE: 7,6 mm (0.3 in), 11,4
mm (0.45 in)
Endress+Hauser 27
Installation Micropilot FMR51, FMR52 HART
Alignment
• Align the antenna vertically to the product surface.
The maximum range may be reduced if the horn antenna is not vertically aligned.
• A marking at the flange (somwhere between the flange holes) or the boss enables
alignment of the antenna. This marking must be aligned towards the tank wall as well
as possible.
A B
°
90
°
90
°
90
° °
°
90 90
90
90 90
° °
90 90
° °
A0018974
Depending on the device version the marking may be a circle or two short parallel
lines.
Nozzle mounting
Hmax
A0016819
• For flanges with PTFE cladding: Observe the notes on the mounting of cladded
flanges → 24.
• Usually, the PTFE flange cladding also serves as a seal between the nozzle and the
device flange.
28 Endress+Hauser
Micropilot FMR51, FMR52 HART Installation
°
90
1
A0016841
• For horn antenna: Align the marking towards the slots of the stilling well.
• Measurements can be performed through an open full bore ball valve without any
problems.
• After mounting, the housing can be turned 350° in order to facilitate access to the
display and the terminal compartment → 33.
Endress+Hauser 29
Installation Micropilot FMR51, FMR52 HART
A B A-A
A A 1
1 C
2 3
100%
100%
4
5
(5.91...19.7)
150…500
≤ 1 (0.04)
(5.91...19.7)
150…500
≤ 1 (0.04)
D 6
0%
0%
mm (in)
A0019009
30 Endress+Hauser
Micropilot FMR51, FMR52 HART Installation
°
90
1
°
90
A0019446
9 Installation in bypass
1 Marking for antenna alignment
2 Tank connectors
Endress+Hauser 31
Installation Micropilot FMR51, FMR52 HART
A
A-A
A A
≤ 1 (0.04)
2
C
(7.87) (7.87)
200
100%
200
3
4 B
4
3
(7.87) (7.87)
200
0%
200
mm (in)
A0019010
32 Endress+Hauser
Micropilot FMR51, FMR52 HART Installation
1
2
A0019142
If process temperatures are high, the device must be included in normal tank insulation to
prevent the electronics heating up as a result of heat radiation or convection. The
insulation may not exceed beyond the neck of the housing.
max. 350°
8 mm 8 mm
A0013713
Endress+Hauser 33
Installation Micropilot FMR51, FMR52 HART
–
+
E
3 mm
A0013905
1. If present: Loosen the screw of the securing clamp of the electronics compartment
cover using an Allen key and turn the clamp 90° conterclockwise.
2. Unscrew cover of the electronics compartment from the transmitter housing.
3. Pull out the display module with a gentle rotation movement.
4. Rotate the display module into the desired position: Max. 8 × 45 ° in each direction.
5. Feed the spiral cable into the gap between the housing and main electronics module
and plug the display module into the electronics compartment until it engages.
6. Screw the cover of the electronics compartment firmly back onto the transmitter
housing.
7. Tighten the securing clamp again using the Allen key (Torque: 2.5 Nm).
Are the measuring point identification and labeling correct (visual inspection)?
34 Endress+Hauser
Micropilot FMR51, FMR52 HART Electrical connection
7 Electrical connection
! 2- w
4-2 ire le
0 vel
H A mA
[21 RT
4-2
0m
A ]
ope
A
n Sp
a
711 re pa
HA 20mA
08x rt
xx
RT
4...
+
1 -
1 2 4 5 6
mm
2
10
+ +
–
–
# 4...20 mA
3 B
7 +
1-c 1 -
1 2 4 5 han
nel 4-2 2
ove 0m
[16
] rvo A
ltag
e pro
tec
tion
+ +
–
–
# 4...20 mA
3
A0011294
Endress+Hauser 35
Electrical connection Micropilot FMR51, FMR52 HART
10
9
8
% 2- w
4-2 ire
0
H A mA
[02 RT
PF
S
A /03
] ope
n Sp
a
711 re pa
HA 20 mA
08x rt
3+ ++ xx
31 --
RT
4...
42 +
7
1 -
mm
2 6
4-
10
+ +
–
-
≥250 Ω 4...20 mA
$
1 2 3 4 5 B
3+ 11 +
3 -
4-2 4 +
0m
2-c
A/ 1 -
4-
han
nel 4- 2
[17
ove FIE 20mA
] rvo LD /
ltag
ep
B U
ro S
tec
tion
+ +
–
-
≥250 Ω 4...20 mA
$
1 2 3 4 5
A0013759
36 Endress+Hauser
Micropilot FMR51, FMR52 HART Electrical connection
14
13
12
# 2- w
4-2 ire le
0 v el
H A mA
[04 RT
4-2
0m
A /05
]
A
ope
A
n Sp
20m
a
711 re pa
HA 20mA
08x rt
xx
+
4 ...
3 -
RT
11
4 ...
4 +
1 -
mm
2
+ +
10
1 " –
-
4...20 mA
9 8 4
+ +
2 " –
-
4...20 mA
3 5 6 7 4
B
+ +
1 " –
- +
3 -
4...20 mA 4-2 4 +
10 0m
9 8 4 2-c
A/ 1 -
han
nel 4- 2
[17
ove FIE 20mA
] rvo LD /
ltag
ep
B US
ro tec
tion
+ +
2 " –
-
4...20 mA
3 5 6 7 4
A0013923
This version is also suited for single-channel operation. In this case, current output 1
(terminals 1 and 2) must be used.
Endress+Hauser 37
Electrical connection Micropilot FMR51, FMR52 HART
13
12
11
! 2- w
4-2 ire
0
HA mA
[08 RT
A ]
= V
o pe
48
n Sp
4...
a
711 re pa
HA 20 mA
08x rt
10.
L+ xx
1 L-
RT
4...
2 +
10 9
3 -
mm
4 8
10
7
+ !
-
≥250 Ω 4...20 mA
6
1 2 3 4 5
A0011340
38 Endress+Hauser
Micropilot FMR51, FMR52 HART Electrical connection
13
12
11
! 2- w
4-2 ire
0
H A mA
[09 RT
A ]
~
3V
ope
n
..25
Sp
a
711 re pa
HA 20 mA
9 0.
08x rt
xx
L
1 N
RT
4...
2 +
10 9
3 -
mm
4 8
10
7
+ !
-
≥250 Ω 4...20 mA
6
1 2 3 4 5
A0018965
LCAUTION
To ensure electrical safety:
‣ Do not disconnect the protective connection (6).
‣ Disconnect the supply voltage before disconnecting the protective earth (7).
Connect protective earth to the internal ground terminal (7) before connecting the
supply voltage. If necessary, connect the potential matching line to the external
ground terminal (11).
In order to ensure electromagnetic compatibility (EMC): Do not only ground the device
via the protective earth conductor of the supply cable. Instead, the functional
grounding must also be connected to the process connection (flange or threaded
connection) or to the external ground terminal.
An easily accessible power switch must be installed in the proximity of the device. The
power switch must be marked as a disconnector for the device (IEC/EN61010).
Endress+Hauser 39
Electrical connection Micropilot FMR51, FMR52 HART
+
3+ 1
2
+ 3+
-
4-
A0015909
4-
15 Connection of a relay A0015910
HART
• A normal device cable suffices if only the analog signal is used.
• A shielded cable is recommended if using the HART protocol. Observe grounding concept
of the plant.
• For 4-wire devices: Standard device cable is sufficient for the power line.
40 Endress+Hauser
Micropilot FMR51, FMR52 HART Electrical connection
2 not connected
1 2 3 Signal -
A0011175
4 Ground
2 Signal +
2 4 3 Not connected
A0011176
4 Screen
Endress+Hauser 41
Electrical connection Micropilot FMR51, FMR52 HART
"Power Supply, Output" 1) "Approval" 2) Terminal voltage U at the Maximum load R, depending on the supply voltage U0 at the
device supply unit
Ex ia / IS 10.4 to 30 V 3)
0
10 20 30 35 U0 [V]
10.4 21.4
A0017140
4)
• Ex d(ia) / XP 12 to 35 V R [W]
• Ex ic(ia)
• Ex nA(ia) 500
• Ex ta / DIP
Ex ia + Ex d(ia) / IS + XP 12 to 30 V 4)
0
10 20 30 35 U0 [V]
12 23
A0019136
"Power Supply, Output" 1) "Approval" 2) Terminal voltage U Maximum load R, depending on the supply voltage U0 at the
at the device supply unit
• Ex ia / IS 12 to 30 V 3)
0
• Ex ia + Ex d(ia) / IS + XP
10 20 30 35 U0 [V]
12 23
A0019136
42 Endress+Hauser
Micropilot FMR51, FMR52 HART Electrical connection
"Power Supply, Output" 1) "Approval" 2) Terminal voltage U at the Maximum load R, depending on the supply voltage U0 at the
device supply unit
0
10 20 30 U0 [V]
12 23
A0017055
Endress+Hauser 43
Electrical connection Micropilot FMR51, FMR52 HART
Technical data
44 Endress+Hauser
Micropilot FMR51, FMR52 HART Electrical connection
1. 3.
2.
5.
10 (0.4)
4.
5.
10 (0.4)
mm (in)
A0012619
1. Loosen the screw of the securing clamp of the connection compartment cover and
turn the clamp 90° counterclockwise.
2. Unscrew the connection compartment cover.
3. Push the cable through the cable entry. To ensure tight sealing, do not remove the
sealing ring from the cable entry.
4. Strip the cable.
5. Strip the cable ends 10 mm (0.4 in). For stranded cables, also attach wire end
ferrules.
6. Firmly tighten the cable glands.
7.
3
4
1
2
A0013837
Endress+Hauser 45
Electrical connection Micropilot FMR51, FMR52 HART
≤ 3 (0.12)
mm (in)
A0013661
m Are all cable glands installed, firmly tightened and correctly sealed?
m Does the supply voltage match the specifications on the transmitter nameplate?
If supply voltage is present: Is the device ready for operation and do values appear on the display
m
module?
46 Endress+Hauser
Micropilot FMR51, FMR52 HART Operation options
8 Operation options
8.1 Overview
A0032219 A0032221
Format for displaying measured variables and status variables can be individually configured
Permitted ambient temperature for the display: –20 to +70 °C (–4 to +158 °F)
The readability of the display may be impaired at temperatures outside the temperature
range.
Operating local operation with 3 push buttons (, , external operation via touch control; 3 optical
elements ) keys: , ,
Endress+Hauser 47
Operation options Micropilot FMR51, FMR52 HART
1 2 3
A0013137
2 3 6 8
1 4 5 7
A0013764
48 Endress+Hauser
Micropilot FMR51, FMR52 HART Operation options
3 –
+
E
2 1
A0014019
1 Service interface (CDI) of the measuring device (= Endress+Hauser Common Data Interface)
2 Commubox FXA291
3 Computer with "FieldCare" operating tool
Endress+Hauser 49
Operation options Micropilot FMR51, FMR52 HART
The parameter of the Expert menu are Output • Contains all parameters needed to
described in: configure the current output.
GP01014F (HART) • Contains all parameters neeed to
configure the switch output (PFS).
1) In case of operation via operating tools (e.g. FieldCare), the "Language" parameter is located at "Setup →
Advanced setup → Display"
2) only available with local operation
3) only available for operation via DeviceCare or FieldCare
4) On entering the "Expert" menu, an access code is always requested. If a customer specific access code has
not been defined, "0000" has to be entered.
50 Endress+Hauser
Micropilot FMR51, FMR52 HART Operation options
Without access With access code Without access With access code
code code
(from the factory) (from the factory)
Operator --
Maintenance
If an incorrect access code is entered, the user obtains the access rights of the Operator
role.
The user role with which the user is currently logged on is indicated by the Access
status display parameter (for display operation) or Access status tooling parameter
(for tool operation).
Endress+Hauser 51
Operation options Micropilot FMR51, FMR52 HART
52 Endress+Hauser
Micropilot FMR51, FMR52 HART Operation options
The locking of the write access via local operation can be disabled by entering the device-
specific access code.
1. After you press , the input prompt for the access code appears.
2. Enter the access code.
The -symbol in front of the parameters disappears; all previously write-
protected parameters are now re-enabled.
Endress+Hauser 53
Operation options Micropilot FMR51, FMR52 HART
ON
CDI WP
OFF
XXXXXXXXXXXXX
–
+
E
3 mm
A0026157
A0013909
54 Endress+Hauser
Micropilot FMR51, FMR52 HART Operation options
4. Installing the lock switch (WP) on the main electronics module in the ON position
enables the hardware write protection. Installing the lock switch (WP) on the main
electronics module in the OFF position (factory setting) disables the hardware write
protection.
If the hardware write protection is enabled: The Hardware locked option is
displayed in the Locking status parameter. In addition to this, the -symbol
appears in the header of the measured value display and in the navigation view
in front of the parameters.
XXXXXXXXX
20.50
XX XX
A0015870
Endress+Hauser 55
Operation options Micropilot FMR51, FMR52 HART
When attempting to access the operating menu while the keylock is enabled, the
Keylock on message appears.
56 Endress+Hauser
Micropilot FMR51, FMR52 HART Operation options
2
1 2.1
2.3
2.2
1.1 2.6 2.4
1.3 2.5
OPEN
OPEN
1.2 3
ESC
1.4
3.1
E
3.2
5 4
User 20
ABC_
0 1 2 3 4
DEFG HIJK
LMNO PQRS TUVW 5 6 7 8 9
XYZ Aa1
A0012635
Endress+Hauser 57
Operation options Micropilot FMR51, FMR52 HART
Symbol Meaning
Display/operation
Is displayed:
A0011975
• in the main menu next to the selection "Display/operation"
• in the header, if you are in the "Display/operation" menu
Setup
Is displayed:
A0011974
• in the main menu next to the selection "Setup"
• in the header, if you are in the "Setup" menu
Expert
Is displayed:
• in the main menu next to the selection "Expert"
A0011976
• in the header, if you are in the "Expert" menu
Diagnostics
Is displayed:
• in the main menu next to the selection "Diagnostics"
A0011977
• in the header, if you are in the "Diagnostics" menu
Status signals
"Failure"
A device error is present. The measured value is no longer valid.
A0013956
"Function check"
The device is in service mode (e.g. during a simulation).
A0013959
"Out of specification"
The device is operated:
• Outside of its technical specifications (e.g. during startup or a cleaning)
A0013958
• Outside of the configuration carried out by the user (e.g. level outside configured span)
"Maintenance required"
Maintenance is required. The measured value is still valid.
A0013957
Symbol Meaning
Display parameter
Marks display-only parameters which can not be edited.
A0011978
Device locked
• In front of a parameter name: The device is locked via software and/or hardware.
A0011979 • In the header of the measured value screen: The device is locked via hardware.
58 Endress+Hauser
Micropilot FMR51, FMR52 HART Operation options
Symbol Meaning
Measured values
Level
A0011995
Distance
A0011996
Current output
A0011998
Measured current
A0011999
Terminal voltage
A0012106
A0012104
Measuring channels
Measuring channel 1
A0012000
Measuring channel 2
A0012107
Status "Alarm"
The measurment is interrupted. The output assumes the defined alarm value. A diagnostic
message is generated.
A0012102
Status "Warning"
The device continues measuring. A diagnostic message is generated.
A0012103
Endress+Hauser 59
Operation options Micropilot FMR51, FMR52 HART
Key Meaning
Minus key
For menu, submenu
Moves the selection bar upwards in a picklist.
A0013969
For text and numeric editor
In the input mask, moves the selection bar to the left (backwards).
Plus key
For menu, submenu
Moves the selection bar downwards in a picklist.
A0013970
For text and numeric editor
In the input mask, moves the selection bar to the right (forwards).
Enter key
For measured value display
• Pressing the key briefly opens the operating menu.
• Pressing the key for 2 s opens the context menu.
For menu, submenu
• Pressing the key briefly
Opens the selected menu, submenu or parameter.
A0013952
• Pressing the key for 2 s for parameter:
If present, opens the help text for the function of the parameter.
For text and numeric editor
• Pressing the key briefly
– Opens the selected group.
– Carries out the selected action.
• Pressing the key for 2 s confirms the edited parameter value.
A0013955
For measured value display
Enables or disables the keypad lock.
60 Endress+Hauser
Micropilot FMR51, FMR52 HART Operation options
1 1
2 20 2 User
0 1 2 3 4 ABC_ DEFG HIJK
5 6 7 8 9 LMNO PQRS TUVW
3 3
XYZ Aa1
4 4
A0013941 A0013999
1 Editing view
2 Display area of the entered values
3 Input mask
4 Operating elements
Input mask
The following input symbols are available in the input mask of the numeric and text editor:
A0016619
Confirms selection.
A0013985
A0016621
A0013986
A0014040
Toggle
Aa1 • Between upper-case and lower-case letters
• For entering numbers
A0013981
• For entering special characters
Endress+Hauser 61
Operation options Micropilot FMR51, FMR52 HART
Confirms selection.
A0013985
A0013987
A0013986
A0014040
A0013989
A0013991
A0013990
A0013988
62 Endress+Hauser
Micropilot FMR51, FMR52 HART Operation options
XXXXXXXXXX
Setup
20.50
Conf.backup disp
Simulation
kg/h
A0014003-EN
2. Press + simultaneously.
The context menu is closed and the operational display appears.
Endress+Hauser 63
Operation options Micropilot FMR51, FMR52 HART
E (2s)
2x +
E -
+ + -
+
+
E
+ + -
A0014277
64 Endress+Hauser
Micropilot FMR51, FMR52 HART System integration via HART protocol
The allocation of the device variables can be changed in the operating menu:
Expert → Communication → Output
In a HART multidrop loog only one device may use the output current for signal
transmission. For all other devices the follwing must be set:
• Current span (→ 140) = Fixed current
• Fixed current (→ 140) = 4 mA
Endress+Hauser 65
Commissioning via wizard Micropilot FMR51, FMR52 HART
A0027720
If the wizard is cancelled before all necessary parameters have been set, the device
may be in an undefined state. A reset to the default settings is recommended in this
case.
66 Endress+Hauser
Micropilot FMR51, FMR52 HART Commissioning via operating menu
XXXXXXXXX
20.50
XX XX
Main menu 0104-1
Language
English
Operation
Setup
Language 0104-1
à English
Deutsch
Español
Français
Language 0104-1
à English
Deutsch
Español
Français
Hauptmenü 0104-1
Sprache
Deutsch
Betrieb
Setup
A0013996
Endress+Hauser 67
Commissioning via operating menu Micropilot FMR51, FMR52 HART
100%
E
F
L 0%
A0016933
5) If, for example, the measuring range covers only an upper part of the tank (E << tank height), it is mandatory to enter the acutal tank height into
the "Setup → Advanced Setup → Level → Tank/silo height" parameter.
68 Endress+Hauser
Micropilot FMR51, FMR52 HART Commissioning via operating menu
The response time of the device is preset by the Tank type parameter (→ 107).
More detailed settings are possible in the Advanced setup submenu.
Endress+Hauser 69
Commissioning via operating menu Micropilot FMR51, FMR52 HART
70 Endress+Hauser
Micropilot FMR51, FMR52 HART Commissioning via operating menu
Endress+Hauser 71
Commissioning via operating menu Micropilot FMR51, FMR52 HART
72 Endress+Hauser
Micropilot FMR51, FMR52 HART Commissioning via operating menu
Endress+Hauser 73
Diagnostics and troubleshooting Micropilot FMR51, FMR52 HART
Device does not respond. Supply voltage does not match the Connect the correct voltage.
value indicated on the nameplate.
The cables do not contact the Ensure electrical contact between the
terminals properly. cable and the terminal.
Values on the display Contrast setting is too weak or too • Increase contrast by pressing and
invisible strong. simultaneously.
• Decrease contrast by pressing and
simultaneously.
The plug of the display cable is not Connect the plug correctly.
connected correctly.
Output current < 3.6 mA Signal cable connection incorrect. Check connection.
HART communication does Communication resistor missing or Install the communication resistor (
not function. incorrectly installed. 250 Ω) correctly → 35.
CDI communication does not Wrong setting of the COM port on Check the setting of the COM port on
work. the computer. the computer and change it if necessary.
74 Endress+Hauser
Micropilot FMR51, FMR52 HART Diagnostics and troubleshooting
No change of measured value Interference echo from installations, • Carry out tank mapping (Confirm
on filling / emptying nozzle or build-up on the antenna. distance parameter (→ 111)).
• If necessary, clean antenna
• If necessary, selet better mopunting
position
If the surface is not calm (e.g. Signal is weakened by the rough • Carry out tank mapping (Confirm
filling, emptying, agitator surface - the interference echoes are distance parameter (→ 111)).
running), the measured value sometimes stronger. • Select Tank type (→ 107) =
jumps sporadically to a Process vessel with agitator.
higher level • Increase integration time (Expert
→ Sensor → Distance → Integration
time)
• Optimize orientation of the antenna
• If necessary, select a better mounting
position and/or larger antenna.
Error message F941 or S941 Level echo is too weak. • Check Medium group parameter
"Echo lost" (→ 108).
• If necessary, select a more detailed
setting in Medium property
parameter (→ 119).
• Optimize alignment of antenna
• If necessary, select a better
installation position and/or larger
antenna.
Device displays a level when Interference echo Carry out mapping over entire
the tank is empty. measuring range when the tank is
empty (Confirm distance parameter
(→ 111)).
Wrong slope of the level in Wrong tank type selected. Set Tank type parameter (→ 107)
the entire measuring range correctly.
Endress+Hauser 75
Diagnostics and troubleshooting Micropilot FMR51, FMR52 HART
2 1
XXXXXXXXX S XXXXXXXXX S
20.50 S801
Supply voltage
3
4
X XX i Menu
5
A0013939-EN
1 Status signal
2 Status symbol (symbol for event level)
3 Status symbol with diagnostics event
4 Event text
5 Operating elements
Status signals
"Failure"
A device error is present. The measured value is no longer valid.
A0013956
"Function check"
The device is in service mode (e.g. during a simulation).
A0013959
"Out of specification"
The device is operated:
• Outside of its technical specifications (e.g. during startup or a cleaning)
A0013958
• Outside of the configuration carried out by the user (e.g. level outside configured span)
"Maintenance required"
Maintenance is required. The measured value is still valid.
A0013957
"Alarm" status
The measurement is interrupted. The signal outputs take on the defined alarm condition.
A0013961 A diagnostic message is generated.
"Warning" status
The device continues to measure. A diagnostic message is generated.
A0013962
76 Endress+Hauser
Micropilot FMR51, FMR52 HART Diagnostics and troubleshooting
Diagnostics event
↓ ↓ ↓
3-digit number
If two or more diagnostic messages are pending simultaneously, only the message with the
highest priority is shown. Additional pending diagnostic messages can be shown in
Diagnostic list submenu (→ 162).
Past diagnostic messages that are no longer pending are shown as follows:
• On the local display:
in Event logbook submenu (→ 163)
• In FieldCare:
via the "Event List /HistoROM" function.
Operating elements
Plus key
Opens the message about the remedial measures.
A0013970
Enter key
Opens the operating menu.
A0013952
Endress+Hauser 77
Diagnostics and troubleshooting Micropilot FMR51, FMR52 HART
XXXXXXXXX S XXXXXXXXX S
20.50 S801
Supply voltage
X XX i Menu
Diagnostic list S
Diagnostics 1
1 S801 Supply voltage
Diagnostics 2
Diagnostics 3
A0013940-EN
The user is in the Diagnostics menu at an entry for a diagnostics event, e.g. in Diagnostic
list submenu or in Previous diagnostics.
1. Press .
The message for the remedial measures for the selected diagnostic event opens.
2. Press + simultaneously.
The message for the remedial measures closes.
78 Endress+Hauser
Micropilot FMR51, FMR52 HART Diagnostics and troubleshooting
Endress+Hauser 79
Diagnostics and troubleshooting Micropilot FMR51, FMR52 HART
Diagnostic of electronic
Diagnostic of configuration
80 Endress+Hauser
Micropilot FMR51, FMR52 HART Diagnostics and troubleshooting
Diagnostic of process
6) This submenu is only available for operation via local display. In the case of operation via FieldCare, the event list can be displayed with the "Event
List / HistoROM" functionality of FieldCare.
Endress+Hauser 81
Diagnostics and troubleshooting Micropilot FMR51, FMR52 HART
In addition to the operation time of its occurrence, each event is also assigned a symbol
that indicates whether the event has occurred or is ended:
• Diagnostic event
– : Event has occurred
– : Event has ended
• Information event
: Event has occurred
I1089 Power on
82 Endress+Hauser
Micropilot FMR51, FMR52 HART Diagnostics and troubleshooting
1) contains information on the Heartbeat wizards which are available in the latest DTM version for DeviceCare and FieldCare.
The firmware version can explicitly be ordered via the product structure. In this way it
is possible to ensure compatibility of the firmware version with an existing or planned
system integration.
Endress+Hauser 83
Maintenance Micropilot FMR51, FMR52 HART
13 Maintenance
The measuring device requires no special maintenance.
84 Endress+Hauser
Micropilot FMR51, FMR52 HART Repairs
14 Repairs
Endress+Hauser 85
Repairs Micropilot FMR51, FMR52 HART
002847-A
6 3
4 1 5
Additional information: www.endress.com/deviceviewer
A0014979
14.3 Return
The measuring device must be returned if it is need of repair or a factory calibration, or if
the wrong measuring device has been delivered or ordered. Legal specifications require
Endress+Hauser, as an ISO-certified company, to follow certain procedures when handling
products that are in contact with the medium.
To ensure safe, swift and professional device returns, please refer to the procedure and
conditions for returning devices provided on the Endress+Hauser website at
http://www.endress.com/support/return-material
14.4 Disposal
Observe the following notes during disposal:
• Observe valid federal/national regulations.
• Ensure proper separation and reuse of the device components.
86 Endress+Hauser
Micropilot FMR51, FMR52 HART Accessories
15 Accessories
Accessory Description
222 (8.74)
A0015466
4)
65°
35°
(6.1
156
A0015472
Enclosed",
The weather protection cover can be ordered together with the device (product structure, feature 620 "Accessory
option PB "Weather Protection Cover").
Alternatively, it can be separately ordered as an accessory; order code 71162242.
Endress+Hauser 87
Accessories Micropilot FMR51, FMR52 HART
Accessories Description
2.
1.
4.
3.
A0019128
• Material:
– Plastic PBT
– 316L/1.4404
• Degree of protection: IP68 / NEMA 6P and IP66 / NEMA 4x
• Suitable for display modules:
– SD02 (push buttons)
– SD03 (touch control)
• Connecting cable:
– Cable supplied with device up to 30 m (98 ft)
– Standard cable supplied by customer up to 60 m (196 ft)
• Ambient temperature range: –40 to 80 °C (–40 to 176 °F)
• Ambient temperature range (option): –50 to 80 °C (–58 to 176 °F) 1)
• IfL ortheM).remote display should be used, order the device version "Prepared for display FHX50" (feature 030, version
For the FHX50, you must select option A: "Prepared for display FHX50" under feature 050 "Measuring
device version".
• If the device version "Prepared for display FHX50" was not originally ordered and a FHX50 display is to be
retrofitted, you must select version B "Not prepared for display FHX50" under feature 050: "Measuring device
version" when ordering the FHX50. In this case, a retrofit kit for the device is supplied with the FHX50. The kit
can be used to prepare the device so that the FHX50 can be used.
Use of the FHX50 may be restricted for transmitters with an approval. A device can only be retrofitted with the
FHX50 if the option L or M ("Prepared for FHX50") is listed under Basic specifications, item 4 "Display, operation" in
the Safety Instructions (XA) for the device.
Also pay attention to the Safety Instructions (XA) of the FHX50.
88 Endress+Hauser
Micropilot FMR51, FMR52 HART Accessories
Accessory Description
Hornschutz für
Hornantenne
80 mm (3 in) oder
100 mm (4 in) A
L
ød
øD
A0019143
A Horn antenna of the Micropilot (not supplied with the horn protection)
B Horn protection
⌀d Diameter of horn protection (see table below)
⌀D Minimum nozzle diameter (see table below)
L Length of antenna with horn protection (see table below)
Danger of explosion
Avoid electrostatic charging of the horn protection.
BC: Horn 80mm/3" 71105890 238 mm (9.4 in) 96 mm (3.78 in) ≥ DN100
BD: Horn 100mm/4" 71105889 302 mm (11.9 in) 116 mm (4.57 in) ≥ DN150
The horn protection can also be ordered together with the device. Product structure:
Feature 610 "Accessory Mounted", option OW "Horn protection, PTFE".
Endress+Hauser 89
Accessories Micropilot FMR51, FMR52 HART
Accessory Description
B
L
ød
øD
A0027190
BD: Horn 100mm/4" 71105889 267 mm (10.5 in) 116 mm (4.57 in) ≥ DN150
90 Endress+Hauser
Micropilot FMR51, FMR52 HART Accessories
Accessory Description
A0021734
Technical data
• Resistance per channel: 2 * 0.5 Ωmax
• Threshold DC voltage: 400 to 700 V
• Threshold impulse voltage: < 800 V
• Capacitance at 1 MHz: < 1.5 pF
• Nominal arrest impulse voltage (8/20 μs): 10 kA
• Suited for wire cross-sections: 0.2 to 2.5 mm2 (24 to 14 AWG)
Accessory Description
Gas-tight feedthrough Chemically inert glass feedthrough; prevents migration of gases into the electronics housing.
To be ordered with the device: product structure, feature 610 "Accessory Mounted", option NC "Gas-tight feedthrough"
Endress+Hauser 91
Accessories Micropilot FMR51, FMR52 HART
Commubox FXA195 For intrinsically safe HART communication with FieldCare via the USB interface.
HART
For details refer to Technical Information TI00404F
Accessory Description
Commubox FXA291 Connects Endress+Hauser field devices with CDI interface (= Endress+Hauser
Common Data Interface) to the USB interface of a computer.
Order code: 51516983
Accessory Description
HART Loop Converter Evaluates the dynamic HART variables and converts them to analog current signals
HMX50 or limit values.
Order code: 71063562
Accessory Description
Accessory Description
Fieldgate FXA320 Gateway for remote monitoring of connected 4-20mA measuring devices via web
browser.
Accessory Description
Fieldgate FXA520 Gateway for remote diagnosis and parametrization of connected HART measuring
devices via web browser.
Accessory Description
Field Xpert SFX350 Field Xpert SFX350 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
fieldbus devices in the non-Ex area.
92 Endress+Hauser
Micropilot FMR51, FMR52 HART Accessories
Accessory Description
Field Xpert SFX370 Field Xpert SFX370 is a mobile computer for commissioning and maintenance. It
enables efficient device configuration and diagnostics for HART and FOUNDATION
fieldbus devices in the non-Ex area and the Ex area.
Graphic Data Manager The graphic data manager Memograph M provides information on all the relevant
Memograph M process variables. Measured values are recorded correctly, limit values are
monitored and measuring points analyzed. The data are stored in the 256 MB
internal memory and also on an SD card or USB stick.
RN221N Active barrier with power supply for safe separation of 4 to 20 mA current circuits.
Provides bi-directional HART transmission.
RNS221 Transmitter supply for 2-wire sensors or transmitters exclusively for non-Ex areas.
Provides bi-directional communication using the HART communication sockets.
Endress+Hauser 93
Operating menu Micropilot FMR51, FMR52 HART
16 Operating menu
Language → 148
Setup → 107
Level → 110
Distance → 110
‣ Mapping → 115
Distance → 115
94 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
‣ Level → 119
‣ Linearization → 125
Diameter → 130
‣ Edit table
Level → 132
Endress+Hauser 95
Operating menu Micropilot FMR51, FMR52 HART
96 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
‣ Display → 148
Language → 148
Header → 151
Separator → 152
Backlight → 153
Endress+Hauser 97
Operating menu Micropilot FMR51, FMR52 HART
‣ Administration → 157
Diagnostics → 160
Diagnostics 1 to 5 → 162
98 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Device ID → 165
Manufacturer ID → 166
Distance → 110
‣ Simulation → 173
Endress+Hauser 99
Operating menu Micropilot FMR51, FMR52 HART
100 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Setup → 107
Level → 110
Distance → 110
‣ Level → 119
Endress+Hauser 101
Operating menu Micropilot FMR51, FMR52 HART
‣ Linearization → 125
Diameter → 130
Level → 132
Level → 133
102 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Endress+Hauser 103
Operating menu Micropilot FMR51, FMR52 HART
‣ Display → 148
Language → 148
Header → 151
Separator → 152
Backlight → 153
‣ Administration → 157
Diagnostics → 160
104 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Timestamp → 160
Timestamp → 161
Diagnostics 1 to 5 → 162
Timestamp 1 to 5 → 162
Device ID → 165
Manufacturer ID → 166
Distance → 110
Endress+Hauser 105
Operating menu Micropilot FMR51, FMR52 HART
‣ Simulation → 173
‣ Heartbeat → 179
106 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Navigation Setup
Device tag
Description Enter a unique name for the measuring point to identify the device quickly within the
plant.
Distance unit
Factory setting m
Tank type
Endress+Hauser 107
Operating menu Micropilot FMR51, FMR52 HART
Additional information Depending on the antenna some of the options mentioned above may not be available or
there may be additional options.
Tube diameter
Factory setting 0m
Medium group
Selection • Others
• Water based (DC >= 4)
Additional information This parameter roughly specifies the dielectric constant (DC) of the medium. For a more
detailed definition of the DC use the Medium property parameter (→ 119).
The Medium group parameter presets the Medium property parameter (→ 119) as
follows:
Others Unknown
The Medium property parameter can be changed at a later point of time. However,
when doing so, the Medium group parameter retains its value. Only the Medium
property parameter is relevant for the signal evaluation.
The measuring range may be reduced for small dielectric constants. For details refer
to the Technical Information (TI) of the respective device.
108 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Empty calibration
Description Specify the distance E between the process connection and the minimum level (0%). This
defines the starting point of the measuring range.
Additional information
0%
A0019486
The measuring range starts at the point at which the radar beam hits the tank or silo
bottom. In the case of dished boiler ends or conical outlets levels below this point can
not be measured.
Full calibration
Description Specify the distance F between the minimum level (0%) and the maximum level (100%).
Endress+Hauser 109
Operating menu Micropilot FMR51, FMR52 HART
Additional information
100%
0%
A0019487
Level
Additional information
0%
A0019482
Distance
Description Displays the measured distance D between the reference point (lower edge of the flange or
threaded connection) and the level.
110 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Additional information
A0019483
Signal quality
Confirm distance
Description Specify, whether the measured distance matches the real distance.
Depending on the selection the device automatically sets the range of mapping.
Endress+Hauser 111
Operating menu Micropilot FMR51, FMR52 HART
112 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Present mapping
Additional information This parameter defines up to which distance the new mapping is to be recorded. The
distance is measured from the reference point, i.e. from the lower edge of the mounting
flange or the threaded connection.
For reference purposes the Present mapping parameter (→ 113) is displayed
together with this parameter. It indicates up to which distance a mapping has already
been recorded.
Record map
Selection • No
• Record map
• Overlay map
• Factory map
• Delete partial map
Factory setting No
Endress+Hauser 113
Operating menu Micropilot FMR51, FMR52 HART
114 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Confirm distance
Description → 111
Description → 113
Record map
Description → 113
Distance
Description → 110
Endress+Hauser 115
Operating menu Micropilot FMR51, FMR52 HART
116 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Locking status
Description Indicates the write protection with the highest priority that is currently active.
Description Indicates access authorization to parameters via operating tool (e.g. FieldCare).
Additional information The access authorization can be changed via the Enter access code parameter
(→ 118).
If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the Locking status
parameter (→ 117).
Endress+Hauser 117
Operating menu Micropilot FMR51, FMR52 HART
Additional information If a symbol appears in front of a parameter, the parameter cannot be changed via
the local display with the current access authorization.
The access authorization can be changed via the Enter access code parameter
(→ 118).
If additional write protection is active, this restricts the current access authorization
even further. The write protection status can be viewed via the Locking status
parameter (→ 117).
Additional information • For local operation, the customer-specific access code, which has been defined in the
Define access code parameter (→ 157), has to be entered.
• If an incorrect access code is entered, the user retains his current access authorization.
• The write protection affects all parameters marked with the -symbol in this document.
On the local display, the -symbol in front of a parameter indicates that the parameter
is write-protected.
• If no key is pressed for 10 min, or the user switches from the navigation and editing
mode back to the measured value display mode, the device automatically locks the write-
protected parameters after another 60 s.
Please contact your Endress+Hauser Sales Center if you lose your access code.
118 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
"Level" submenu
Medium type
Additional information This parameter determines the value of several other parameters and strongly
influences the complete signal evaluation. Therefore, it is strongly recommended not
to change the factory setting.
Medium property
Selection • Unknown
• DC 1.4 ... 1.6
• DC 1.6 ... 1.9
• DC 1.9 ... 2.5
• DC 2.5 ... 4
• DC 4 ... 7
• DC 7 ... 15
• DC > 15
Factory setting Dependent on Medium type (→ 119) and Medium group (→ 108).
Solid Unknown
Others Unknown
For dielectric constants (DC values) of many media commonly used in various
industries refer to:
• the Endress+Hauser DC manual (CP01076F)
• the Endress+Hauser "DC Values App" (available for Android and iOS)
Endress+Hauser 119
Operating menu Micropilot FMR51, FMR52 HART
Additional information Max. filling speed liquid is preset by Tank type (→ 107). It can, however, be adjusted
to the process in the vessel at any time. If Tank type (→ 107) is changed again at a
later point of time, it may be necessary to repeat the fine adjustment.
Additional information Max. draining speed liquid (→ 120) is preset by Tank type (→ 107). It can,
however, be adjusted to the process in the vessel at any time. If Tank type (→ 107) is
changed again at a later point of time, it may be necessary to repeat the fine adjustment.
120 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Level unit
Factory setting %
Additional information The level unit may differ from the distance unit defined in the Distance unit parameter
(→ 107):
• The unit defined in the Distance unit parameter is used for the basic calibration (Empty
calibration (→ 109) and Full calibration (→ 109)).
• The unit defined in the Level unit parameter is used to display the (unlinearized) level.
Endress+Hauser 121
Operating menu Micropilot FMR51, FMR52 HART
Blocking distance
Additional information Signals in the blocking distance are only evaluated if they have been outside the blocking
distance when the device was switched on and move into the blocking distance due to a
level change during operation. Signals which are already in the blocking distance when the
device is switched on, are ignored.
This behavior is only valid if the following two conditions are met:
• Expert → Sensor → Echo tracking → Evaluation mode = Short time history or Long
time history)
• Expert → Sensor → Gas phase comp. → GPC mode= On, Without correction or
External correction
If one of these conditions is not met, signals in the blocking distance will always be
ignored.
If required, a different behavior for signals in the blocking distance can be defined by
the Endress+Hauser service.
BD
A0019492
Level correction
122 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Additional information The value specified in this parameter is added to the measured level (before linearization).
Tank/silo height
Description Specify total height of the tank or silo as measured from the process connection.
Additional information If the parametrized measuring range (Empty calibration (→ 109)) differs significantly
from the tank or silo height, it is recommended to enter the tank or silo height. Example:
Continuous level monitoring in the upper third of a tank or silo.
E
0%
1
A0019867
For tanks with conical outlet, Tank/silo height should not be changed as in this type
of applications Empty calibration (→ 109) is usually not << the tank or silo
height.
Endress+Hauser 123
Operating menu Micropilot FMR51, FMR52 HART
"Linearization" submenu
2
A
L
100%
L 1 B L‘
0%
M L‘
L
100%
C L2
L1
0% L‘1L‘2 L‘
L
100%
H
D
0% M L‘
L
100%
h
E
0% M L‘
L
100%
F
h 0% M L‘
L
100%
G d
0%
M L‘
L
100%
H d
0%
M L‘
A0019648
32 Linearization: Transformation of the level and (if relevant) the interface height into a volume or weight;
the transformation is dependent on the shape of the vessel.
1 Selection of linearization type and unit
2 Configuration of the linearization
A Linearization type (→ 127) = None
B Linearization type (→ 127) = Linear
C Linearization type (→ 127) = Table
D Linearization type (→ 127) = Pyramid bottom
E Linearization type (→ 127) = Conical bottom
F Linearization type (→ 127) = Angled bottom
G Linearization type (→ 127) = Horizontal cylinder
H Linearization type (→ 127) = Sphere
L Level before linearization (measured in distance units)
L' Level linearized (→ 129) (corresponds to volume or weight)
M Maximum value (→ 130)
d Diameter (→ 130)
h Intermediate height (→ 130)
124 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
‣ Linearization
Diameter → 130
‣ Edit table
Level → 132
Endress+Hauser 125
Operating menu Micropilot FMR51, FMR52 HART
‣ Linearization
Diameter → 130
Level → 132
Level → 133
126 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Description of parameters
Linearization type
Selection • None
• Linear
• Table
• Pyramid bottom
• Conical bottom
• Angled bottom
• Horizontal cylinder
• Sphere
Additional information
A B
100%
100%
0% 0%
C/D E
100% 100%
0% 0%
F/G
100%
0%
A0021476
33 Linearization types
A None
B Table
C Pyramid bottom
D Conical bottom
E Angled bottom
F Sphere
G Horizontal cylinder
Endress+Hauser 127
Operating menu Micropilot FMR51, FMR52 HART
128 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Custom-specific units
Free text
Factory setting %
Additional information The selected unit is only used to be indicated on the display. The measured value is not
transformed according to the selected unit.
It is also possible to configure a distance-to-distance linearization, i.e. a
transformation from the level unit to a different distance unit. To do so, select the
Linear linearization mode. In order to define the new level unit, select the Free text
option in the Unit after linearization parameter and enter the required unit into the
Free text parameter (→ 129).
Free text
Level linearized
Additional information The unit is defined by the Unit after linearization parameter → 128.
Endress+Hauser 129
Operating menu Micropilot FMR51, FMR52 HART
Maximum value
Description Specify the maximum content of the vessel (100%) measured in the units after
linearization.
Diameter
Factory setting 2m
Additional information The unit is defined in the Distance unit parameter (→ 107).
Intermediate height
Factory setting 0m
130 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Additional information
H
0%
A0013264
H Intermediate height
Table mode
Selection • Manual
• Semiautomatic
• Clear table
• Sort table
Before entering a linearization table, the values for Empty calibration (→ 109)
and Full calibration (→ 109) must be set correctly.
If values of the table need to be changed after the full or empty calibration have been
changed, a correct evaluation is only ensured if the existing table is deleted and the
complete table is entered again. To do so delete the existing table (Table mode
(→ 131) = Clear table). Then enter a new table.
Endress+Hauser 131
Operating menu Micropilot FMR51, FMR52 HART
The factory setting for the level unit is "%". If you want to enter the linearization table
in physical units, you must select the appropriate unit in the Level unit parameter
(→ 121) beforehand.
If a decreasing table is entered, the values for 20 mA and 4 mA of the current output
are interchanged. That means: 20 mA refers to the lowest level, whereas 4 mA refers
to the highest level. If required, the current output can be inverted in the Measuring
mode parameter.
Table number
User entry 1 to 32
Factory setting 1
Level (Manual)
Description Enter level value of the table point (value before linearization).
Factory setting 0%
132 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Level (Semiautomatic)
Description Displays measured level (value before linearization). This value is transmitted to the table.
Customer value
Factory setting 0%
Activate table
Selection • Disable
• Enable
Endress+Hauser 133
Operating menu Micropilot FMR51, FMR52 HART
Description Define the behavior of the output signal in case of a lost echo.
Additional information Use the unit which has been defined for the measured value output:
• without linearization: Level unit (→ 121)
• with linearization: Unit after linearization (→ 128)
134 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Description Define the slope of the ramp in the case of a lost echo.
Additional information
100%
B
A
C
0%
t
min
A0013269
• The unit for the slope of the ramp is "percentage of the measuring range per minute" (%/
min).
• For a negative slope of the ramp: The measured value is continuously decreased until it
reaches 0%.
• For a positive slope of the ramp: The measured value is continuosly increased until it
reaches 100%.
Blocking distance
Additional information Signals in the blocking distance are only evaluated if they have been outside the blocking
distance when the device was switched on and move into the blocking distance due to a
Endress+Hauser 135
Operating menu Micropilot FMR51, FMR52 HART
level change during operation. Signals which are already in the blocking distance when the
device is switched on, are ignored.
This behavior is only valid if the following two conditions are met:
• Expert → Sensor → Echo tracking → Evaluation mode = Short time history or Long
time history)
• Expert → Sensor → Gas phase comp. → GPC mode= On, Without correction or
External correction
If one of these conditions is not met, signals in the blocking distance will always be
ignored.
If required, a different behavior for signals in the blocking distance can be defined by
the Endress+Hauser service.
BD
A0019492
136 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Endress+Hauser 137
Operating menu Micropilot FMR51, FMR52 HART
Factory setting 0
Code incorrect
Description Indicates that a wrong unlocking code has been entered. Select procedure.
138 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Additional information Definition of the current range for the process variables
Process variable 4 mA value 20 mA value
1)
Level linearized 0 % or the associated 100 % 2) or the associated linearized value
linearized value
Distance 0 (i.e. level is at the reference Empty calibration (→ 109) (i.e. level is at
point) 0 %)
It may be necessary to adjust the 4mA and 20mA values to the application (especially
in the case of the Analog output adv. diagnostics 1/2 and Area of incoupling
options).
This can be done by the following parameters:
• Expert → Output → Curr.output 1 to 2 → Turn down
• Expert → Output → Curr.output 1 to 2 → 4 mA value
• Expert → Output → Curr.output 1 to 2 → 20 mA value
Endress+Hauser 139
Operating menu Micropilot FMR51, FMR52 HART
Current span
Description Select current range for process variable and alarm signal.
Selection • 4...20 mA
• 4...20 mA NAMUR
• 4...20 mA US
• Fixed current
Fixed current Constant current, defined in the Fixed current parameter (→ 140).
• In the case of an error, the output current assumes the value defined in the Failure
mode parameter (→ 141).
• If the meausred value is out of the measuring range, diagnostic message Current
output is issued.
In a HART multidrop loop only one device can use the analog current to transmit a
signal. For all other devices one must set:
• Current span = Fixed current
• Fixed current (→ 140) = 4 mA
Fixed current
Factory setting 4 mA
140 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Damping output
Description Define time constant τ for the damping of the output current.
Additional information Fluctuations of the measured value affect the output current with an exponential delay,
the time constant τ of which is defined in this parameter. With a small time constant the
output reacts immediately to changes of the measrued value. With a big time constant the
reaction of the output is more delayed. For τ = 0 (factory setting) there is no damping.
Failure mode
Selection • Min.
• Max.
• Last valid value
• Actual value
• Defined value
Endress+Hauser 141
Operating menu Micropilot FMR51, FMR52 HART
Failure current
Output current 1 to 2
142 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Selection • Off
• On
• Diagnostic behavior
• Limit
• Digital Output
Assign status
Selection • Off
• Digital output AD 1
• Digital output AD 2
Endress+Hauser 143
Operating menu Micropilot FMR51, FMR52 HART
Additional information The Digital output AD 1 and Digital output AD 2 options refer to the Advanced
Diagnostic Blocks. A switch signal generated in these blocks can be transmitted via the
switch output.
Assign limit
Selection • Off
• Level linearized
• Distance
• Terminal voltage
• Electronic temperature
• Relative echo amplitude
• Area of incoupling
Selection • Alarm
• Alarm or warning
• Warning
Switch-on value
144 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Factory setting 0
Additional information The switching behavior depends on the relative position of the Switch-on value and
Switch-off value parameters:
Switch-on value > Switch-off value
– The output is closed if the measured value is larger than Switch-on value.
– The output is opened if the measured value is smaller than Switch-off value.
B
t
D
t
A0015585
A Switch-on value
B Switch-off value
C Output closed (conductive)
D Output opened (non-conductive)
A
t
D
t
A0015586
A Switch-on value
B Switch-off value
C Output closed (conductive)
D Output opened (non-conductive)
Endress+Hauser 145
Operating menu Micropilot FMR51, FMR52 HART
Switch-on delay
Switch-off value
Factory setting 0
Additional information The switching behavior depends on the relative position of the Switch-on value and
Switch-off value parameters; description: see the Switch-on value parameter
(→ 144).
Switch-off delay
146 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Failure mode
Switch status
Selection • No
• Yes
Factory setting No
Endress+Hauser 147
Operating menu Micropilot FMR51, FMR52 HART
"Display" submenu
The Display submenu is only visible if a display module is connected to the device.
Language
Selection • English
• Deutsch *
• Français *
• Español *
• Italiano *
• Nederlands *
• Portuguesa *
• Polski *
• русский язык (Russian) *
• Svenska *
• Türkçe *
• 中文 (Chinese) *
• 日本語 (Japanese) *
• 한국어 (Korean) *
• Bahasa Indonesia *
• tiếng Việt (Vietnamese) *
• čeština (Czech) *
Factory setting The language selected in feature 500 of the product structure.
If no language has been selected: English
Format display
148 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Additional information
4841.000
1 Â mm
A0019963
1 Â
93.5 %
1 Â 159.0
mm
A0019964
1 Â 93.5
%
1 Â 159.0
mm
A0019965
1 Â 159.0 mm
V 1 Â 23.5 V
1 Â 93.5
%
A0019966
1 Â 93.5 %
1 Â 159.0 mm
V 1 Â 93.5 V
1 Â 26.3 °C
A0019968
• The Value 1 to 4 display → 150 parameters specify which measured values are
shown on the display and in which order.
• If more measured values are specified than the current display mode permits, the
values alternate on the device display. The display time until the next change is
configured in the Display interval parameter (→ 150).
Endress+Hauser 149
Operating menu Micropilot FMR51, FMR52 HART
Value 1 to 4 display
Description Select the measured value that is shown on the local display.
Selection • None 9)
• Level linearized
• Distance
• Current output 1 10)
• Measured current
• Current output 2
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
• Area of incoupling
Decimal places 1 to 4
Description Select the number of decimal places for the display value.
Selection •x
• x.x
• x.xx
• x.xxx
• x.xxxx
Additional information The setting does not affect the measuring or computational accuracy of the device.
Display interval
Description Set time measured values are shown on display if display alternates between values.
150 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
User entry 1 to 10 s
Factory setting 5s
Additional information This parameter is only relevant if the number of selected measuring values exceeds the
number of values the selected display format can display simultaneously.
Display damping
Header
Additional information
1 XXXXXXXXX
A0013375
Endress+Hauser 151
Operating menu Micropilot FMR51, FMR52 HART
Header text
Additional information The number of characters which can be displayed depends on the characters used.
Separator
Selection •.
•,
Factory setting .
Number format
Selection • Decimal
• ft-in-1/16''
Additional information The ft-in-1/16'' option is only valid for distance units.
Description Select number of decimal places for the representation of numbers within the operating
menu.
152 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Selection •x
• x.x
• x.xx
• x.xxx
• x.xxxx
Additional information • Is only valid for numbers in the operating menu (e.g. Empty calibration, Full
calibration), but not for the measured value display. The number of decimal places for
the measured value display is defined in the Decimal places 1 to 4 → 150
parameters.
• The setting does not affect the accuracy of the measurement or the calculations.
Backlight
Prerequisite The device has the SD03 local display (with optical keys).
Selection • Disable
• Enable
Contrast display
Description Adjust local display contrast setting to ambient conditions (e.g. lighting or reading angle).
User entry 20 to 80 %
Endress+Hauser 153
Operating menu Micropilot FMR51, FMR52 HART
The configuration of the device can be saved to the display module at a certain point of
time (backup). The saved configurateion can be restored to the device if required, e.g. in
order to bring the device back into a defined state. The configuration can also be
transferred to a different device of the same type using the display module.
Operating time
User interface Days (d), hours (h), minutes (m), seconds (s)
Last backup
Description Indicates when the last data backup was saved to the display module.
User interface Days (d), hours (h), minutes (m), seconds (s)
Configuration management
Description Select action for managing the device data in the display module.
Selection • Cancel
• Execute backup
• Restore
• Duplicate
• Compare
• Clear backup data
154 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Backup state
Comparison result
Description Displays the comparison result between the device and the display.
Endress+Hauser 155
Operating menu Micropilot FMR51, FMR52 HART
156 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
"Administration" submenu
Factory setting 0
Additional information If the factory setting is not changed or 0 is defined as the access code, the parameters
are not write-protected and the configuration data of the device can then always be
modified. The user is logged on in the Maintenance role.
The write protection affects all parameters marked with the symbol in this
document. On the local display, the symbol in front of a parameter indicates that
the parameter is write-protected.
Once the access code has been defined, write-protected parameters can only be
modified if the access code is entered in the Enter access code parameter
(→ 118).
Please contact your Endress+Hauser Sales Center if you lose your access code.
For display operation: The new access code is only valid after it has been confirmed in
the Confirm access code parameter (→ 159).
Device reset
Selection • Cancel
• To factory defaults
• To delivery settings
• Of customer settings
• To transducer defaults
• Restart device
Endress+Hauser 157
Operating menu Micropilot FMR51, FMR52 HART
158 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Navigation Setup → Advanced setup → Administration → Def. access code → Def. access code
Description → 157
Navigation Setup → Advanced setup → Administration → Def. access code → Confirm code
Factory setting 0
Endress+Hauser 159
Operating menu Micropilot FMR51, FMR52 HART
Actual diagnostics
Timestamp
User interface Days (d), hours (h), minutes (m), seconds (s)
Previous diagnostics
Description Displays the last diagnostic message which has been active before the current message.
160 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Timestamp
User interface Days (d), hours (h), minutes (m), seconds (s)
Description Displays the time the device has been in operation since the last device restart.
User interface Days (d), hours (h), minutes (m), seconds (s)
Operating time
User interface Days (d), hours (h), minutes (m), seconds (s)
Endress+Hauser 161
Operating menu Micropilot FMR51, FMR52 HART
Diagnostics 1 to 5
Description Display the current diagnostics messages with the highest to fifth-highest priority.
Timestamp 1 to 5
User interface Days (d), hours (h), minutes (m), seconds (s)
162 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Filter options
Description Select category (status signal) whose event messages are displayed in the events list.
Selection • All
• Failure (F)
• Function check (C)
• Out of specification (S)
• Maintenance required (M)
• Information (I)
Additional information • This parameter is only used for operation via the local display.
• The status signals are categorized according to NAMUR NE 107.
Endress+Hauser 163
Operating menu Micropilot FMR51, FMR52 HART
Device tag
Serial number
Firmware version
Additional information For firmware versions differing only in the last two digits ("zz") there is no difference
concerning functionality or operation.
Device name
164 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Order code
Additional information The order code is generated from the extended roder code, which defines all device
features of the product structure. In contrast, the device features can not be read directly
from the order code.
Additional information The extended order code indicates the version of all the features of the product structure
and thus uniquely identifies the device.
Device revision
Description Displays the device revision registered for this device at the HART Communication
Foundation.
Additional information The device revision is used to allocate the correct Device Description file (DD) to the device.
Device ID
Additional information In addition to the Device type and Manufacturer ID, the Device ID is part of the unique
device identification (Unique ID) which characterizes each HART device unambiguously.
Endress+Hauser 165
Operating menu Micropilot FMR51, FMR52 HART
Device type
Description Displays the device type with which the device is registered with the the HART
Communication Foundation.
Additional information The device type is needed to allocate the correct Device Description file (DD) to the device.
Manufacturer ID
Description Displays the manufactured ID with which the device is registered with the HART
Communication Foundation.
166 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Distance
Description Displays the measured distance D between the reference point (lower edge of the flange or
threaded connection) and the level.
Additional information
A0019483
Level linearized
Additional information The unit is defined by the Unit after linearization parameter → 128.
Output current 1 to 2
Endress+Hauser 167
Operating menu Micropilot FMR51, FMR52 HART
Measured current 1
Terminal voltage 1
Electronic temperature
168 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Assign channel 1 to 4
Selection • Off
• Level linearized
• Distance
• Current output 1
• Measured current
• Current output 2 *
• Terminal voltage
• Electronic temperature
• Absolute echo amplitude
• Relative echo amplitude
• Area of incoupling
• Analog output adv. diagnostics 1
• Analog output adv. diagnostics 2
Additional information A total of 1000 measured values can be logged. This means:
• 1000 data points if 1 logging channel is used
• 500 data points if 2 logging channels are used
• 333 data points if 3 logging channels are used
• 250 data points if 4 logging channels are used
If the maximum number of data points is reached, the oldest data points in the data log
are cyclically overwritten in such a way that the last 1000, 500, 333 or 250 measured
values are always in the log (ring memory principle).
The logged data are deleted if a new option is selected in this parameter.
Logging interval
Endress+Hauser 169
Operating menu Micropilot FMR51, FMR52 HART
Additional information This parameter defines the interval between the individual data points in the data log, and
thus the maximum loggable process time T log :
• If 1 logging channel is used: T log = 1000 ⋅ t log
• If 2 logging channels are used: T log = 500 ⋅ t log
• If 3 logging channels are used: T log = 333 ⋅ t log
• If 4 logging channels are used: T log = 250 ⋅ t log
Once this time elapses, the oldest data points in the data log are cyclically overwritten such
that a time of T log always remains in the memory (ring memory principle).
The logged data are deleted if this parameter is changed.
Example
When using 1 logging channel
• Tlog = 1000 ⋅ 1 s = 1 000 s ≈ 16.5 min
• Tlog = 1000 ⋅ 10 s = 1 000 s ≈ 2.75 h
• Tlog = 1000 ⋅ 80 s = 80 000 s ≈ 22 h
• Tlog = 1000 ⋅ 3 600 s = 3 600 000 s ≈ 41 d
Selection • Cancel
• Clear data
170 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
• x-axis: depending on the number of selected channels, 250 to 1000 measured values of
a process variable are displayed.
• y-axis: covers the approximate measured value span and constantly adapts this to the
measurement.
To return to the operating menu, press and simultaneaously.
Endress+Hauser 171
Operating menu Micropilot FMR51, FMR52 HART
172 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
‣ Simulation
Endress+Hauser 173
Operating menu Micropilot FMR51, FMR52 HART
Description of parameters
Selection • Off
• Level
• Level linearized
Additional information • The value of the variable to be simulated is defined in the Process variable value
parameter (→ 174).
• If Assign measurement variable ≠ Off, a simulation is active. This is indicated by a
diagnotic message of the Function check (C) category.
Factory setting 0
Additional information Downstream measured value processing and the signal output use this simulation value. In
this way, users can verify whether the measuring device has been configured correctly.
Selection • Off
• On
174 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Additional information An active simulation is indicated by a diagnostic message of the Function check (C)
category.
Additional information The current output assumes the value specified in this parameter. In this way, users can
verify the correct adjustment of the current output and the correct function of connected
control units.
Selection • Off
• On
Switch status
Selection • Open
• Closed
Additional information The switch status assumes the value defined in this parameter. This helps to check correct
operation of connected control units.
Endress+Hauser 175
Operating menu Micropilot FMR51, FMR52 HART
Selection • Off
• On
Additional information When selecting the On option, the device generates an alarm. This helps to check the
correct output behavior of the device in the case of an alarm.
An active simulation is indicated by the diagnostic message C484 Failure mode
simulation.
176 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Selection • No
• Yes
Factory setting No
Additional information In the case of a lost echo a device check can not be performed.
Description Displays the operating time at which the last device check has been performed.
Endress+Hauser 177
Operating menu Micropilot FMR51, FMR52 HART
Level signal
Description Displays result of the device check for the level signal.
Additional information For Level signal = Check not OK: Check the mounting position of the device and the
dielectric constant of the medium.
178 Endress+Hauser
Micropilot FMR51, FMR52 HART Operating menu
Endress+Hauser 179
Index
Index
A Declaration of Conformity . . . . . . . . . . . . . . . . . . . . . 12
Access authorization to parameters Define access code . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Read access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Define access code (Parameter) . . . . . . . . . . . . 157, 159
Write access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Define access code (Wizard) . . . . . . . . . . . . . . . . . . 159
Access code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Incorrect input . . . . . . . . . . . . . . . . . . . . . . . . . . . 51 Device alarm simulation (Parameter) . . . . . . . . . . . . 176
Access status display (Parameter) . . . . . . . . . . . . . . 118 Device check (Submenu) . . . . . . . . . . . . . . . . . . . . . 177
Access status tooling (Parameter) . . . . . . . . . . . . . . 117 Device Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Accessories Device ID (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 165
Communication specific . . . . . . . . . . . . . . . . . . . . 92 Device information (Submenu) . . . . . . . . . . . . . . . . 164
Device specific . . . . . . . . . . . . . . . . . . . . . . . . . . . 87 Device name (Parameter) . . . . . . . . . . . . . . . . . . . . 164
Service specific . . . . . . . . . . . . . . . . . . . . . . . . . . . 93 Device replacement . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Activate table (Parameter) . . . . . . . . . . . . . . . . . . . . 133 Device reset (Parameter) . . . . . . . . . . . . . . . . . . . . . 157
Actual diagnostics (Parameter) . . . . . . . . . . . . . . . . 160 Device revision (Parameter) . . . . . . . . . . . . . . . . . . . 165
Administration (Submenu) . . . . . . . . . . . . . . . . . . . 157 Device tag (Parameter) . . . . . . . . . . . . . . . . . . 107, 164
Advanced process conditions (Parameter) . . . . . . . . 120 Device type (Parameter) . . . . . . . . . . . . . . . . . . . . . 166
Advanced setup (Submenu) . . . . . . . . . . . . . . . . . . . 117 Diagnostic event
Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 In the operating tool . . . . . . . . . . . . . . . . . . . . . . . 79
Residual risk . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Diagnostic events . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Assign channel 1 to 4 (Parameter) . . . . . . . . . . . . . . 169 Diagnostic list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Assign current output (Parameter) . . . . . . . . . . . . . . 139 Diagnostic list (Submenu) . . . . . . . . . . . . . . . . . . . . 162
Assign diagnostic behavior (Parameter) . . . . . . . . . . 144 Diagnostic message . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Assign limit (Parameter) . . . . . . . . . . . . . . . . . . . . . 144 Diagnostics
Assign measurement variable (Parameter) . . . . . . . . 174 Symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Assign status (Parameter) . . . . . . . . . . . . . . . . . . . . 143 Diagnostics (Menu) . . . . . . . . . . . . . . . . . . . . . . . . . 160
Diagnostics 1 to 5 (Parameter) . . . . . . . . . . . . . . . . . 162
B Diagnostics event . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Backlight (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 153 Diameter (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 130
Backup state (Parameter) . . . . . . . . . . . . . . . . . . . . 155 DIP switch
Blocking distance (Parameter) . . . . . . . . . . . . . 122, 135 see Write protection switch
Display (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . . 148
C Display and operating module FHX50 . . . . . . . . . . . . 48
CE mark . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 Display channel 1 to 4 (Submenu) . . . . . . . . . . . . . . 171
Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84 Display damping (Parameter) . . . . . . . . . . . . . . . . . 151
Clear logging data (Parameter) . . . . . . . . . . . . . . . . 170 Display interval (Parameter) . . . . . . . . . . . . . . . . . . 150
Code incorrect (Parameter) . . . . . . . . . . . . . . . . . . . 138 Display module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Comparison result (Parameter) . . . . . . . . . . . . . . . . 155 Display symbols for submenus . . . . . . . . . . . . . . . . . . 58
Configuration backup display (Submenu) . . . . . . . . . 154 Display symbols for the locking state . . . . . . . . . . . . . 58
Configuration management (Parameter) . . . . . . . . . 154 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Configuration of a level measurement . . . . . . . . . . . . 68 Distance (Parameter) . . . . . . . . . . . . . . . . 110, 115, 167
Confirm access code (Parameter) . . . . . . . . . . . . . . . 159 Distance unit (Parameter) . . . . . . . . . . . . . . . . . . . . 107
Confirm distance (Parameter) . . . . . . . . . . . . . 111, 115 Document
Context menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63 Function . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Contrast display (Parameter) . . . . . . . . . . . . . . . . . . 153 Document function . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Current output 1 to 2 (Submenu) . . . . . . . . . . . . . . . 139
Current output 1 to 2 simulation (Parameter) . . . . . . 174 E
Current span (Parameter) . . . . . . . . . . . . . . . . . . . . 140 Electrical connection
Customer value (Parameter) . . . . . . . . . . . . . . . . . . 133 Commubox FXA291 . . . . . . . . . . . . . . . . . . . . . . . 49
Operating tools
D Via service interface (CDI) . . . . . . . . . . . . . . . . 49
Damping output (Parameter) . . . . . . . . . . . . . . . . . . 141 Electronic temperature (Parameter) . . . . . . . . . . . . . 168
Data logging (Submenu) . . . . . . . . . . . . . . . . . . . . . 169 Electronics housing
DD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Deactivate SIL/WHG (Wizard) . . . . . . . . . . . . . . . . . 138 Turning
Decimal places 1 (Parameter) . . . . . . . . . . . . . . . . . 150 see Turning the transmitter housing
Decimal places menu (Parameter) . . . . . . . . . . . . . . 152 Empty calibration (Parameter) . . . . . . . . . . . . . . . . . 109
180 Endress+Hauser
Index
H N
Hardware write protection . . . . . . . . . . . . . . . . . . . . . 54 Number format (Parameter) . . . . . . . . . . . . . . . . . . 152
HART device variables . . . . . . . . . . . . . . . . . . . . . . . . 65
HART integration . . . . . . . . . . . . . . . . . . . . . . . . . . . 65 O
HART protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48 Operating elements
Header (Parameter) . . . . . . . . . . . . . . . . . . . . . . . . 151 Diagnostics message . . . . . . . . . . . . . . . . . . . . . . . 77
Header text (Parameter) . . . . . . . . . . . . . . . . . . . . . 152 Operating module . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Heartbeat (Submenu) . . . . . . . . . . . . . . . . . . . . . . . 179 Operating time (Parameter) . . . . . . . . . . . . . . . 154, 161
Housing Operating time from restart (Parameter) . . . . . . . . . 161
Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Order code (Parameter) . . . . . . . . . . . . . . . . . . . . . . 165
I Output current 1 to 2 (Parameter) . . . . . . . . . . 142, 167
Input mask . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61 Output echo lost (Parameter) . . . . . . . . . . . . . . . . . . 134
Intermediate height (Parameter) . . . . . . . . . . . . . . . 130 Overvoltage protection
Invert output signal (Parameter) . . . . . . . . . . . . . . . 147 General information . . . . . . . . . . . . . . . . . . . . . . . 44
K P
Keypad lock Prepare recording map (Parameter) . . . . . . . . . . . . . 115
Disabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Present mapping (Parameter) . . . . . . . . . . . . . . . . . 113
Switch-on . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56 Previous diagnostics (Parameter) . . . . . . . . . . . . . . . 160
Process variable value (Parameter) . . . . . . . . . . . . . . 174
L Product safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Language (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 148 PV (HART device variable) . . . . . . . . . . . . . . . . . . . . . 65
Last backup (Parameter) . . . . . . . . . . . . . . . . . . . . . 154
Last check time (Parameter) . . . . . . . . . . . . . . . . . . 177 R
Level (Parameter) . . . . . . . . . . . . . . . . . . 110, 132, 133 Ramp at echo lost (Parameter) . . . . . . . . . . . . . . . . . 135
Level (Submenu) . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 Read access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Level correction (Parameter) . . . . . . . . . . . . . . . . . . 122 Record map (Parameter) . . . . . . . . . . . . . . . . . 113, 115
Level linearized (Parameter) . . . . . . . . . . . . . . 129, 167 Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . 15
Level measurement configuration . . . . . . . . . . . . . . . 68 Remedial measures
Level signal (Parameter) . . . . . . . . . . . . . . . . . . . . . 178 Calling up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Level unit (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 121 Closing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Linearization (Submenu) . . . . . . . . . . . . . 125, 126, 127 Remote operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Linearization type (Parameter) . . . . . . . . . . . . . . . . 127 Repair concept . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Endress+Hauser 181
Index
Replacing a device . . . . . . . . . . . . . . . . . . . . . . . . . . . 85 T
Requirements for personnel . . . . . . . . . . . . . . . . . . . . 11 Table mode (Parameter) . . . . . . . . . . . . . . . . . . . . . 131
Reset write protection (Parameter) . . . . . . . . . . . . . 138 Table number (Parameter) . . . . . . . . . . . . . . . . . . . . 132
Result device check (Parameter) . . . . . . . . . . . . . . . . 177 Tank type (Parameter) . . . . . . . . . . . . . . . . . . . . . . 107
Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Tank/silo height (Parameter) . . . . . . . . . . . . . . . . . 123
Terminal voltage 1 (Parameter) . . . . . . . . . . . . . . . . 168
S Timestamp (Parameter) . . . . . . . . . . . . . . 160, 161, 162
Safety instructions Transmitter
Basic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Turning the display module . . . . . . . . . . . . . . . . . 34
Safety Instructions (XA) . . . . . . . . . . . . . . . . . . . . . . . . 8 Turning the housing . . . . . . . . . . . . . . . . . . . . . . . 33
Safety settings (Submenu) . . . . . . . . . . . . . . . . . . . . 134 Transmitter housing
Separator (Parameter) . . . . . . . . . . . . . . . . . . . . . . . 152 Turning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Serial number (Parameter) . . . . . . . . . . . . . . . . . . . 164 Trouble shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Setting the operating language . . . . . . . . . . . . . . . . . 67 Tube diameter (Parameter) . . . . . . . . . . . . . . . . . . . 108
Settings Turning the display module . . . . . . . . . . . . . . . . . . . . 34
Manage device configuration . . . . . . . . . . . . . . . . 72 TV (HART device variable) . . . . . . . . . . . . . . . . . . . . . 65
Operating language . . . . . . . . . . . . . . . . . . . . . . . 67
Setup (Menu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107 U
Signal quality (Parameter) . . . . . . . . . . . . . . . . . . . . 111 Unit after linearization (Parameter) . . . . . . . . . . . . . 128
SIL/WHG confirmation (Wizard) . . . . . . . . . . . . . . . 137
Simulation (Submenu) . . . . . . . . . . . . . . . . . . . 173, 174 V
Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Value 1 display (Parameter) . . . . . . . . . . . . . . . . . . 150
Nameplate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86 Value current output 1 to 2 (Parameter) . . . . . . . . . . 175
Start device check (Parameter) . . . . . . . . . . . . . . . . . 177 Value echo lost (Parameter) . . . . . . . . . . . . . . . . . . . 134
Status signals . . . . . . . . . . . . . . . . . . . . . . . . . . . 58, 76
Submenu W
Administration . . . . . . . . . . . . . . . . . . . . . . . . . . 157 W@M Device Viewer . . . . . . . . . . . . . . . . . . . . . . . . . 86
Advanced setup . . . . . . . . . . . . . . . . . . . . . . . . . 117 Wizard
Configuration backup display . . . . . . . . . . . . . . . 154 Deactivate SIL/WHG . . . . . . . . . . . . . . . . . . . . . . 138
Current output 1 to 2 . . . . . . . . . . . . . . . . . . . . . 139 Define access code . . . . . . . . . . . . . . . . . . . . . . . 159
Data logging . . . . . . . . . . . . . . . . . . . . . . . . . . . 169 Mapping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Device check . . . . . . . . . . . . . . . . . . . . . . . . . . . 177 SIL/WHG confirmation . . . . . . . . . . . . . . . . . . . . 137
Device information . . . . . . . . . . . . . . . . . . . . . . . 164 Workplace safety . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Diagnostic list . . . . . . . . . . . . . . . . . . . . . . . . . . 162 Write access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 148 Write protection
Display channel 1 to 4 . . . . . . . . . . . . . . . . . . . . 171 Via access code . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Event list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 163 Via write protection switch . . . . . . . . . . . . . . . . . . 54
Event logbook . . . . . . . . . . . . . . . . . . . . . . . . . . 163 Write protection switch . . . . . . . . . . . . . . . . . . . . . . . 54
Events list . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Heartbeat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119
Linearization . . . . . . . . . . . . . . . . . . . 125, 126, 127
Measured values . . . . . . . . . . . . . . . . . . . . . . . . 167
Safety settings . . . . . . . . . . . . . . . . . . . . . . . . . . 134
Simulation . . . . . . . . . . . . . . . . . . . . . . . . . 173, 174
Switch output . . . . . . . . . . . . . . . . . . . . . . . . . . . 143
SV (HART device variable) . . . . . . . . . . . . . . . . . . . . . 65
Switch output (Submenu) . . . . . . . . . . . . . . . . . . . . 143
Switch output function (Parameter) . . . . . . . . . . . . . 143
Switch output simulation (Parameter) . . . . . . . . . . . 175
Switch status (Parameter) . . . . . . . . . . . . . . . . 147, 175
Switch-off delay (Parameter) . . . . . . . . . . . . . . . . . . 146
Switch-off value (Parameter) . . . . . . . . . . . . . . . . . . 146
Switch-on delay (Parameter) . . . . . . . . . . . . . . . . . . 146
Switch-on value (Parameter) . . . . . . . . . . . . . . . . . . 144