6es7 134-6gf00-0aa1

The document provides information on the SIMATIC ET 200SP analog input module AI 8xI 2-/4-wire BA. Key details include that it is a 16-bit module suitable for basic analog input on currents between -20mA to +20mA. It has 8 analog inputs, supports 1ms sampling on each channel, and includes diagnostics features to monitor things like the supply voltage and detect wire breaks.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
349 views4 pages

6es7 134-6gf00-0aa1

The document provides information on the SIMATIC ET 200SP analog input module AI 8xI 2-/4-wire BA. Key details include that it is a 16-bit module suitable for basic analog input on currents between -20mA to +20mA. It has 8 analog inputs, supports 1ms sampling on each channel, and includes diagnostics features to monitor things like the supply voltage and detect wire breaks.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Data sheet 6ES7134-6GF00-0AA1

SIMATIC ET 200SP, Analog input module, AI 8XI 2-/4-wire Basic,


suitable for BU type A0, A1, Color code CC01, Module diagnostics,
16 bit

General information
Product type designation AI 8xI 2-/4-wire BA
HW functional status from FS04
Firmware version
● FW update possible Yes
usable BaseUnits BU type A0, A1
Color code for module-specific color identification CC01
plate
Product function
● I&M data Yes; I&M0 to I&M3
● Isochronous mode No
● Measuring range scalable No
Engineering with
● STEP 7 TIA Portal configurable/integrated as of V13 SP1
version
● STEP 7 configurable/integrated as of version V5.5 SP3 / -
● PROFIBUS as of GSD version/GSD revision GSD Revision 5
● PROFINET as of GSD version/GSD revision GSDML V2.3
Operating mode

6ES7134-6GF00-0AA1 Subject to change without notice


Page 1/4 05/21/2020 © Copyright Siemens
● Oversampling No
● MSI No

CiR – Configuration in RUN


Reparameterization possible in RUN Yes
Calibration possible in RUN No

Supply voltage
Rated value (DC) 24 V
permissible range, lower limit (DC) 19.2 V
permissible range, upper limit (DC) 28.8 V
Reverse polarity protection Yes

Input current
Current consumption, max. 25 mA; without sensor supply

Encoder supply
24 V encoder supply
● 24 V Yes
● Short-circuit protection Yes
● Output current, max. 0.7 A; total current of all encoders/channels

Power loss
Power loss, typ. 0.7 W; Without encoder supply voltage

Address area
Address space per module
● Address space per module, max. 16 byte

Hardware configuration
Automatic encoding
● Mechanical coding element Yes
Selection of BaseUnit for connection variants
● 1-wire connection BU type A0, A1
● 2-wire connection BU type A0, A1
● 4-wire connection BU type A0, A1 + potential distributor module

Analog inputs
Number of analog inputs 8; Single-ended
● For current measurement 8
permissible input current for current input (destruction 50 mA
limit), max.
Cycle time (all channels), min. 1 ms; per channel
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 100 Ω; 15 bit
● -20 mA to +20 mA Yes

6ES7134-6GF00-0AA1 Subject to change without notice


Page 2/4 05/21/2020 © Copyright Siemens
— Input resistance (-20 mA to +20 mA) 100 Ω; 16 bit incl. sign
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 100 Ω; 15 bit
Cable length
● shielded, max. 200 m

Analog value generation for the inputs


Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), 16 bit
max.
● Integration time, parameterizable Yes
● Interference voltage suppression for 16.67 / 50 / 60 / 4 800 (16.67 / 50 / 60)
interference frequency f1 in Hz
● Conversion time (per channel) 180 / 60 / 50 / 0.625 (67.5 / 22.5 / 18.75) ms
Smoothing of measured values
● Number of smoothing levels 4; None; 4/8/16 times
● parameterizable Yes

Encoder
Connection of signal encoders
● for voltage measurement No
● for current measurement as 2-wire transducer Yes
— Burden of 2-wire transmitter, max. 650 Ω
● for current measurement as 4-wire transducer Yes

Errors/accuracies
Linearity error (relative to input range), (+/-) 0.01 %
Temperature error (relative to input range), (+/-) 0.005 %/K
Crosstalk between the inputs, min. 50 dB
Repeat accuracy in steady state at 25 °C (relative to 0.05 %
input range), (+/-)
Operational error limit in overall temperature range
● Current, relative to input range, (+/-) 0.5 %
Basic error limit (operational limit at 25 °C)
● Current, relative to input range, (+/-) 0.3 %
Interference voltage suppression for f = n x (f1 +/- 1 %), f1 = interference frequency
● Series mode interference (peak value of 70 dB; With conversion time 67.5 / 22.5 / 18.75 ms: 40 dB
interference < rated value of input range), min.

Interrupts/diagnostics/status information
Diagnostics function Yes
Alarms
● Diagnostic alarm Yes
● Limit value alarm No
Diagnostic messages

6ES7134-6GF00-0AA1 Subject to change without notice


Page 3/4 05/21/2020 © Copyright Siemens
● Monitoring the supply voltage Yes
● Wire-break Yes; at 4 to 20 mA
● Short-circuit Yes; Sensor supply to M; module by module
● Group error Yes
● Overflow/underflow Yes
Diagnostics indication LED
● Monitoring of the supply voltage (PWR-LED) Yes; green LED
● Channel status display Yes; green LED
● for channel diagnostics No
● for module diagnostics Yes; green/red DIAG LED

Potential separation
Potential separation channels
● between the channels No
● between the channels and backplane bus Yes
● between the channels and the power supply of No
the electronics

Isolation
Isolation tested with 707 V DC (type test)

Ambient conditions
Ambient temperature during operation
● horizontal installation, min. -30 °C
● horizontal installation, max. 60 °C
● vertical installation, min. -30 °C
● vertical installation, max. 50 °C
Altitude during operation relating to sea level
● Installation altitude above sea level, max. 5 000 m; Restrictions for installation altitudes > 2 000 m, see
manual

Dimensions
Width 15 mm
Height 73 mm
Depth 58 mm

Weights
Weight, approx. 31 g

last modified: 05/09/2020

6ES7134-6GF00-0AA1 Subject to change without notice


Page 4/4 05/21/2020 © Copyright Siemens