Ordering Easergy P3 Standard
Easergy P3U30 configuration
U30 Application
U30 Feeder & Motor, 4xI, 4xU. 2DI, 5DO
X1 Phase currents & voltage input, X1
5 1A / 5A & 1U (100 / 110V), pluggable clamp connector X5 = B
6 1A / 5A & 1U (100 / 110V), pluggable ring lug connector X5 = B
7 3 LPCT & 4 LPVT, Io clamp connector X5 = C
8 3 LPCT & 4 LPVT, Io ring-lug connector X5 = C
X1 Earth-fault current input, X1
A 1A / 5A
B 0,2A / 1A
C 2A / 20A CSH
X2 Nominal Supply Voltage [V], X2
(1 Always check the power supply range from the relay’s serial A Power A 48 - 230V (range: 40 ... 265 Vac / dc)
number sticker
B Power B 24 - 48V (range: 18 ... 57 Vdc) (1
A Future option
A None
Nominal Digital Input voltage (voltage withstand)
1 24 Vac / dc (255 Vac / dc)
2 110 Vac / dc (255 Vac / dc)
3 220 Vac / dc (255 Vac / dc)
4 24 Vac / dc for DI -DI2, 110 Vac / dc for DI3-DI16 (255 Vac / dc)
5 24 Vac / dc for DI1-DI2, 220 Vac / dc for DI3-DI16 (255 Vac / dc)
X5 Voltage measurements + I/O, X5
B 3U (100 / 110V) + 6DI + 3DO X1 = 5 or 6
C 6 DI + 3 DO X1 = 7 or 8
X4 I/O with comms, X4
B RS-485 + 8DI
C 2 x RJ-45 + 8DI
D 2 x LC + 8DI
E RJ + 232 + 8DI with IRIG-B
F LC + 232 + 8DI with IRIG-B
G RS-485 + 6DI + 3DO X1 = 5 or 6
H 2 x RJ-45 + 6DI + 3DO X1 = 5 or 6
I 2 x LC + 6DI + 3DO X1 = 5 or 6
Product version
A Version 2.1, newest FW
Region
A English, IEC
1. Choose your option B English, ANSI Slot X1 = 6
C Chinese
2. Mark your choice in the box below
R Russian
3. Check your order code:
Easergy P3 U30 A
Slot numbers X1 X1 X2 X5 X4
www.se.com Easergy P3 Catalog | 119