VALVE-REGULATED LEAD ACID BATTERIES: INDIVIDUAL DATA SHEET
LC-RD1217P For main and standby power supplies. Expected trickle life: Approx
3-5 years at 25°C, Approx. 5 years at 20°C.
Dimensions (mm)
Terminal type: LC-RD1217P: M5 bolt and nut
2.992±0.079 (76±2)
0.492 (12.5)
0.217 (5.5)
7.126±0.079 (181±2) 0.886 (22)
0.040 (1)
0.197 (5) 4.429 (112.5) 0.197 (5) 0.443 (11)
6.575±0.079 (167±2)
6.043 (153.5)
Photo/Label for reference only.
7.067 (179.5) 2.933 (74.5)
Specifications
Battery case resin: Standard (UL94HB) Color is black.
Nominal Voltage 12V
Rated Capacity (20 hour rate) 17Ah
Length 7.126 inches (181.0 mm) Discharge characteristics 77°F (25°C) (Note)
Width 2.992 inches (76.0 mm) 14.4
Dimensions 13.8
Terminal voltage (V)
Height 6.575 inches (167.0 mm) 13.2
12.6
Total Height 6.575 inches (167.0 mm) 12.0
Approx. mass 14.34 lbs. (6.5 kg) 11.4
10.8
Standard Terminals
LC-RD1217P 10.2 1.7A 0.85A
and Resin
UL94HB M5 Bolt and Nut 9.6
4.25A
17A
9.0 34A
8.4 51A
7.8
Characteristics 0 1 2 4 6 8 10 20 40 60 2 4 6 8 10 20 40
(Minute) (Hour)
20 hour rate (850mA) 17Ah Duration of discharge
10 hour rate (1500mA) 15Ah
(note)
Capacity 5 hour rate (2600mA) 13Ah (Note)
77˚F (25˚C) 1 hour rate (10000mA) 10Ah Duration of discharge vs. Discharge current
1.5 hour rate discharge
7A 30
Cut-off voltage 10.5 V
Fully charged battery Approx. 12mΩ
20
Internal resistance
77˚F (25˚C) 15
Temperature 104˚F (40˚C) 102% 10
dependency 77˚F (25˚C) 100%
(Hour)
of capacity 32˚F (0˚C) 85%
(20 hour rate) 65% 5
5˚F (-15˚C)
4
Residual capacity 91%
Duration of discharge
3
after standing 3 months
Self discharge Residual capacity 2
77˚F (25˚C) 82%
after standing 6 months 1.5 104˚F (40˚C)
Residual capacity 64% 1 77˚F (25˚C)
after standing 12 months 50
40
Cycle use Initial current 6.8 A or smaller 30
Charge (Repeating
use) 14.5V to 14.9V 20 32˚F (0˚C)
Method
(Minute)
Control voltage
(per 12V cell 25˚C)
(Constant 5˚F (-15˚C)
Voltage) Initial current 2.55 A or smaller 10
Trickle use 13.6V to 13.8V
Control voltage
(per 12V cell 25˚C) 5
(Note) The above characteristics data are average values obtained
3
within three charge/discharge. Cycles not the minimum values. 300 500 1 3 5 10 30 50 100
(Note) For cycle use of the battery, please contact us in advance. (mA) (A)
Discharge current
VRLA BATTERIES AUGUST 2005
This information is generally descriptive only and is not intended to make or imply any representation, guarantee or warranty with respect to any cells and batteries. Cell and battery designs/specifications are subject to
modification without notice. Contact Panasonic for the latest information.
Mouser Electronics
Authorized Distributor
Click to View Pricing, Inventory, Delivery & Lifecycle Information:
Panasonic:
LC-RD1217P