Machine

The document discusses the supply, installation, testing and commissioning of modular variable refrigerant volume air cooled outdoor units and indoor cassette, ductable, and ceiling mounted units of various capacities. It also includes a central wired remote control system. The outdoor units will have inverter compressors and microprocessor controllers to operate efficiently at temperatures up to 50 degrees Celsius. Indoor units will have features like filters, fans, expansion valves and drain pumps. The system is designed to have a coefficient of performance of at least 3.1 and integrated energy efficiency ratio of at least 6.5.

Uploaded by

sojitramaulik91
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views2 pages

Machine

The document discusses the supply, installation, testing and commissioning of modular variable refrigerant volume air cooled outdoor units and indoor cassette, ductable, and ceiling mounted units of various capacities. It also includes a central wired remote control system. The outdoor units will have inverter compressors and microprocessor controllers to operate efficiently at temperatures up to 50 degrees Celsius. Indoor units will have features like filters, fans, expansion valves and drain pumps. The system is designed to have a coefficient of performance of at least 3.1 and integrated energy efficiency ratio of at least 6.5.

Uploaded by

sojitramaulik91
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLSX, PDF, TXT or read online on Scribd
You are on page 1/ 2

Supply Installation of modular type Variable Refrigerant Volume

air cooled Outdoor units suitable for cooling and heating, having
all hermetically sealed inverter type Scroll Compressor(s),
microprocessor based Controller, top discharge type condensing
unit(s), with R410 A Refrigerant (Or Eco Friendly Green Gas if
any), vibration isolators, with suitable foundation, MS Stand for
Unit with necessary paint etc. complete as required. The unit shall
deliver the rated capacity at AHRI Conditions and work even at
50°C ambient temperature without tripping. The unit shall be
suitable to work on 400V +/- 10%, 3 Phase, 50Hz AC power
supply. The unit shall be filled with first charge of the refrigerant
1 and ready for use as required. The COP at AHRI conditions shall 964 Per Hp
not be less than 3.1 and IEER not less than 6.5. (Design should be
got approval before execution from engineer in charge)

INDOOR UNIT Supply, installation, testing and commissioning of


following minimum capacity 4-way/2 way/radial flow as per
approval VRV Cassette Type Indoor ceiling mounted unit
equipped with synthetic washable media pre-filter, fan section
with low noise fan/dynamically balanced blower, multispeed
motor, coil section with DX Copper coil, electronic expansion
valve, outer cabinet, drain pump, grill, necessary supports,
vibration isolation, cord less remote control etc., suitable for
operation on single phase 230 V ± 10%, 50Hz AC supply, max
noise level 60dB @ 400 cfm per TR(minimum) complete, as
required. The unit shall have automatic force shut down provision
in case of fire on receiving signal from BMS System. The cooling
2 capacity of indoor unit will be at air inlet conditions of 27 Degree 22 Nos.
C DB and 19 Degree C WB temperature fresh air provision
compatible for Remote Operation System 1 TR

3 …do… 1.2 TR 53 Nos.


4 …do… 1.6 TR 204 Nos.

5 …do… 2 TR 115 Nos.


6 …do… 2.4 TR 3 Nos.

7 …do… 2.8 TR 41 Nos.

8 …do… 3.2 TR 8 Nos.


Supply, installation, testing and commissioning of following
minimum capacity and external static pressure VRV ceiling
mounted ductable type Indoor unit equipped with washable
synthetic media pre-filter, fan section with low noise
fan/dynamically balanced blower, multispeed motor, coil section
with DX copper coil, electronic expansion valve, corded remote
control, outer cabinet, vibration isolators, drain pan, other
necessary supports etc., suitable for operation on single phase AC
supply 230 V ± 10%, 50 Hz complete as required. The unit shall
have automatic force shut down provision in case of fire on
9 receiving signal from BMS System. The cooling capacity of indoor 2 Nos.
unit will be at air inlet conditions of 27 Degree C DB and 19
Degree C WB temperature. High Static Ductable units (minimum
110 pascal external static pressure) 5.5 TR

…do… 7.1 TR
10 6 Nos.
…do… 8 TR
11 2 Nos.
…do… 11.0 TR
12 7 Nos.
Central Control System Central wired Remote Control System
13 964 Per HP