0% found this document useful (0 votes)
26 views40 pages

P13055 (39%)

The document is an internship report submitted by Md. Almuiz to the Department of Electrical and Electronic Engineering at Daffodil International University. The report discusses Md. Almuiz's field study of a 500KVA substation and bus-bar trunking system. The report includes sections on the theoretical models of transformers, a literature review of transformer components and specifications, results and discussion of transformer loading and connections, and an overview of bus-bar trunking systems. The report was supervised by Md. Dara Abdus Satter and submitted in partial fulfillment of the requirements for Md. Almuiz's Bachelor of Science degree.

Uploaded by

M. Naziur Sardar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
26 views40 pages

P13055 (39%)

The document is an internship report submitted by Md. Almuiz to the Department of Electrical and Electronic Engineering at Daffodil International University. The report discusses Md. Almuiz's field study of a 500KVA substation and bus-bar trunking system. The report includes sections on the theoretical models of transformers, a literature review of transformer components and specifications, results and discussion of transformer loading and connections, and an overview of bus-bar trunking systems. The report was supervised by Md. Dara Abdus Satter and submitted in partial fulfillment of the requirements for Md. Almuiz's Bachelor of Science degree.

Uploaded by

M. Naziur Sardar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 40

INTERNSHIP REPORT

FIELD STUDY ON SUBSTATION AND BBT


SYSTEM
A field study submitted to the Department of EEE, Faculty of Engineering, DIU in partial
fulfillment of the requirements for the Award of Degree of Bachelor of Science in Electrical and
Electronic Engineering.

Prepared By
Md. Almuiz ID: 153-33-3036

Supervised by

Md. Dara Abdus Satter


Assistant Professor & Associate Head, Department of EEE
Daffodil International University

Department of Electrical and Electronic Engineering


Faculty of Engineering
DAFFODIL INTERNATIONAL UNIVERSITY
January 2019

©Daffodil International University i


APPROVAL
A field study about “500KVA sub-station and BBT” observance conducted by Md.Almuiz, ID:
153-33-3036, 19th Batch, B.sc in EEE program of Daffodil International University, under my
supervision. This work has been carried out by them in the Home in partial fulfillment of the
requirements for the degree of Bachelor of Science in Electrical and Electronic Engineering was
presented to the audience of the Exam Committee on January 2019 and has been accepted as
satisfactory.

Signature of the Candidate

___________________

Name: Md. Almuiz

ID :153-33-3036

Supervised by

_______________________
Md. DaraAbdusSatter
Assistant Professor &
Associate Head
Department of EEE
Faculty of Engineering
Daffodil International University

©Daffodil International University ii


ACKNOWLEDGEMENT
First of all, we give thanks to Allah. We would like to take this opportunity to express my
appreciation and gratitude to project supervisor Md. DaraAbdusSatter, Assistant Professor &
Associate Head, Department of EEE, Faculty of Engineering, Daffodil International University,
for being dedicated in supporting, motivating and guiding me through this internship. This
internship can’t be done without his useful advice and helps. Also thank you very much for
giving us opportunity to field study.
Also I want to convey thankfulness to Mohammad Rafat , Lecturer, Department of Electrical and
Electronic Engineering, Faculty of Engineering, Daffodil International University, for his help,
support and constant encouragement. Apart from that, we would like to thank our entire friends
for sharing knowledge information.
To my beloved family, we want to give them our deepest love and gratitude for being very
supportive and also for their inspiration and encouragement during our studies in this University.

©Daffodil International University iii


CERTIFICATION

This to certify that this internship “500KVA sub-station and BBT system” is done by the
following students under my direct supervision and this work has been carried out by them in the
department of Electrical and Electronic Engineering under the faculty of Engineering of Daffodil
International University in partial fulfillment of the requirements for the degree of bachelor of
science in Electrical and Electronic Engineering. The presentation of the work held on.

Signature of the candidate

_____________________
Name: Md. Almuiz
ID :153-33-3036

Supervised by,

_______________________
Md. DaraAbdusSatter
Assistant Professor &
Associate Head
Department of EEE
Faculty of Engineering
Daffodil International University

©Daffodil International University iv


DEDICATED TO

To my Family and my Friends

©Daffodil International University v


ABSTRACT

Soundly, electrical power substations have utilized static and electromechanical gadgets for
power framework insurance, supervisory control and metering. Every gadget freely gains and
procedures the power framework information from relating instrumentation transformers, circuit
breakers, detaches, tap changers, and so on. This methodology has two impediments. First is the
expense related with every gadget getting power framework flags freely that incorporates loads
of copper wire cost and work cost for these wiring. Furthermore, every gadget has just the
neighborhood data from relating associations. Present day microchip based handling innovation
and fiber optic based correspondence innovation has given a chance to gain and process
electrical power framework data in exceptionally viable ways. Along these lines microchip based
innovation has opened up the new time of coordinated substation assurance and control. The
focal points and difficulties of coordinated substation are tended to in this report. Further, the
contextual investigation on Hydro-one encounters with incorporated substation capacities is
likewise portrayed. Progression in current practices for substation assurance and control joining
is clarified. At long last, the highlights of IEC 61850 based substation work combination are
outlined and it has been demonstrated that these highlights upgrade the mix in substation
assurance and control.

©Daffodil International University vi


CONTENTS

TITLE PAGE

APPROVAL i

ACKNOWLEDGEMENT iii

CERTIFICATION iv

DEDICATION v

ABSTRACT vi

CHAPTER 1: INTRODUCTION

1.1 Introduction 1

1.2 Objectives 2

1.3 Destination of Work 2

1.4 Methodology 2

1.5 Field study Outline 3

CHAPER 2: THEORETICAL MODEL

2.1.0 Type of transformers 3


2.1.1 Core type transformer 3
2.1.2 Shell Type Transformer 4
2.1.3 Transformer Construction using Dot Orientation 5
2.1.4 Transformer Primary Tap Changes 5
2.1.5 Transformer Core Losses 5
2.1.6 Hysteresis Losses 6
2.1.7 Eddy Current Losses 6
2.1.8 Copper Losses 6

©Daffodil International University vii


CHAPTER 3: LITERATURE REVEWS

3.1.0 Basic components of a transformer. 7

3.1.1 Technical Specification 7

3.1.2 Transformer cooling systems 9

3.1.3 Tap changer 9

CHAPTER 4: RESULTS AND DISCUSSION

4.1.0 Transformer Loading 10

4.1.1 Transformer loading example 11

4.1.2 Transformer On-load 11

4.1.3 Transformer Ratio 13

4.1.4 Transformer Loading Current: 14

4.1.5 The Autotransformer 15

4.1.6 Disadvantages of an Autotransformer 16

4.1.7 The Current Transformer 17

4.1.8 Current Transformer Example 20

4.1.9 Three Phase Transformers 20

4.2.0 Three Phase Voltages and Currents 21

4.2.1 Three Phase Transformer Connections 21

4.2.2 Transformer Delta and Delta 22

4.2.3 Star-Delta turns ratio 23

4.2.4 Delta-Star Turns Ratio 23

4.2.5 Three Phase Transformer Construction 24

©Daffodil International University viii


CHAPTER 5: BUS-BAR TRANSMISSION

5.1 Bus-bar Trunking System (BBT) 25

5.2 Bus-bar highlights of character 25

5.3 Specifications 25

5.4 Bus-bar Trunking system benefits than Cable 27

CHAPTER 6: CONCLUSION 29

LIST OF FIGURES

2.1 Core type 3

2.2 Shell type 3

2.3 Transformer Construction using Dot Orientation 5

2.4 Transformer Primary Tap Changes 5

2.5 transformer basic circuit diagram 10

4.6 Transformer Loading Current 14

4.7 Auto transformer 16

4.8 construction of Current Transformer 17

4.9 Current Transformer Primary Turns Ratio 20

4.10 Three phase transformer 21

4.11 primary and secondary coil winding 28

REFERENCES 20

©Daffodil International University ix


CHAPTER 1
INTRODUCTION

1.1 Introduction

Electrical transformer is a static electrical machine which changes electrical power starting with
one circuit then onto the next circuit, without changing the recurrence. Transformer can
increment or decline the voltage with relating reduction or increment in current. Electrical
substation for circulation framework is the principle supply to change over the high voltage to
low voltage and where stack are dispersed to the customers. Voltage framework for the electrical
framework to supply for household buyer and mechanical purchaser.Industrial facility which will
provide straightforwardly from Transmission Main Intakes, Main Distribution Sub station.
Substation is where every single electrical hardware, high voltage exchanging, three stage
transformer, high voltage links, low voltage links, low voltage feeder column, battery charging
and so forth which are utilized for electrical providing in power framework and to ensure the
security of the framework by the insurance conspire. Fundamentally, electrical framework have
one or a few approaching and active circuit which are controlled by high voltage exchanging and
meet in at least one in the equivalent of bus-bar framework. By and large, electrical substation is
a point in appropriation framework where: A place where a few electrical types of gear are
introduced and utilized for electrical vitality in power framework. A place where the security of
the framework is gives via naturally protection conspire. A place where one or a few
approaching and active circuit are met at least one bus-bar framework and controlled by high
voltage exchanging hardware which is utilized for exchanging. A place where stack are
circulated, controlled and secured.

©Daffodil International University 1


1.2 Objectives

The fundamental target of field considers is learn and think about field contemplate with
physically information. This incorporate concentrate the 500KVA sub-station and BBT
framework for used to another task

1. How think about establishment a sub-station.

2. To gauge stack limit and supply.

3. Structure a straightforward circuit and locate reasonable equipment for this part.

1.3 Destination of Work

The fundamental guideline behind working of a transformer is the wonder of shared enlistment
between two windings connected by normal attractive transition. The figure at right demonstrates
the most straightforward type of a transformer. Fundamentally a transformer comprises of two
inductive loops; essential winding and auxiliary winding. The loops are electrically isolated
however attractively connected to one another. At the point when, essential winding is associated
with a wellspring of exchanging voltage, substituting attractive transition is delivered around the
winding. The center gives attractive way to the transition, to get connected with the auxiliary
winding. The majority of the motion gets connected with the optional winding which is called as
'valuable transition' or primary 'motion', and the motion which does not get connected with
auxiliary winding is called as 'spillage motion'. As the transition delivered is substituting (its
bearing is persistently changing), EMF gets prompted in the auxiliary twisting as per Faraday's
law of electromagnetic acceptance. This emf is called 'commonly actuated emf', and the
recurrence of commonly incited emf is same as that of provided emf. On the off chance that the
optional winding is shut circuit, commonly prompted flow courses through it, and subsequently
the electrical vitality is exchanged from one circuit to another circuit.

1.4 Methodology
A probabilistic technique is displayed, considered to help the electric framework arranging
engineers in the determination of the dispersion substation areas, considering the hourly load
©Daffodil International University 2
changes or the everyday stack cycle. The hourly load focuses, for every one of the diverse hourly
load situations, are determined deterministically. These area focuses, appropriately weighted by
their journalist stack greatness, are utilized to figure the best fit likelihood dispersion. This
dispersion is utilized to decide the most extreme probability border of the territory where the
substation ought to ideally be situated by the arranging engineers, considering, for instance, the
accessibility and the expense of the land parcels, which are components of uncommon
significance in urban territories, and different hindrances that might be available in the last
determination of the substation site. Results are introduced and talked about for the use of the
philosophy to a genuine case, accepting three diverse bivariate likelihood circulations: the
Gaussian dispersion, a bivariate form of Freund's exponential dissemination, and the
Weibulllikelihood conveyance.

1.5 Field study Outline

It gives the whole scope of administrations, advances, and parts that are required for the effective
development and activity of a high-voltage substation of any sort. It is dependent upon you to
choose from a far reaching scope of accessible administrations:

• Concept, arranging, designing

• Project execution including venture the board and assembling of every key part

• Commissioning

• Operation

• Maintenance, restorations, overhauls, destroying of old gear

• Financing

©Daffodil International University 3


CHAPTER 2
THEORY
2.1.0 Type of transformers

Transformers generally have one of two types of cores:


• Core type
• Shell type
2.1.1 Core type transformer:

For the most part, the name related with the development of a transformer is dependent upon
how the essential and auxiliary windings are twisted around the focal overlaid steel center. The
two most normal and essential plans of transformer development are the Closed-center
Transformer and the Shell-center Transformer.
In the "shut center" type transformer, the essential and optional windings are twisted outside and
encompass the center ring. In the "shell type “transformer, the essential and auxiliary windings
go inside the steel attractive circuit (center) which frames a shell around the windings as
appeared as follows.

Figure 2.1 core type transformer Figure 2.2: shell type


In the two sorts of transformer center structure, the attractive transition connecting the essential
and auxiliary windings ventures altogether inside the center with no loss of attractive motion
through air. In the center kind transformer development, one portion of each winding is folded
over every leg (or appendage) of the transformers attractive circuit as appeared.

The curls are not masterminded with the essential twisting on one leg and the auxiliary on the
other yet rather 50% of the essential winding and half of the optional winding are put one over
the other concentrically on every leg so as to increment attractive coupling permitting for all
©Daffodil International University 4
intents and purposes the majority of the attractive lines of power experience both the essential
and optional winding in the meantime. Be that as it may, with this sort of transformer
development, a little level of the attractive lines of power stream outside of the center, and this is
designated "spillage transition".

Shell type transformer centers beat this spillage transition as both the essential and auxiliary
windings are twisted on a similar focus leg or appendage which has double the cross-sectional
territory of the two external appendages. The preferred standpoint here is that the attractive
motion has two shut attractive ways to stream around outside to the loops on both left and right
hand sides before returning back to the focal curls.

This implies the attractive motion coursing around the external appendages of this kind of
transformer development is equivalent to Φ/2. As the attractive motion has a shut way around the
curls, this has the upside of diminishing center misfortunes and expanding by and large
proficiency.

2.1.2 Shell Type Transformer


The coils are former wound and mounted in layers stacked with insulation between them. A shell
type transformer may have simple rectangular form (as shown in above fig), or it may have a
pose:

i) Step up transformer: Voltage increases (with subsequent decrease in current) at


secondary.
ii) Step down transformer: Voltage decreases (with subsequent increase in current) at
secondary.

A) On the basis type of supply:

i) Single phase transformer


ii) Three phase transformer

B) On the basis of their use:

i) Power transformer: Used in transmission network, high rating


ii) Distribution transformer: Used in distribution network, comparatively lower rating
than that of power transformers.

C) Instrument transformer:
Used in relay and protection purpose in different instruments in industries
• Current transformer (CT)
• Potential transformer (PT)

©Daffodil International University 5


D) On the basis of cooling employed

• Oil-filled self cooled type


• Oil-filled water cooled type
• Air blast type (air cooled)

2.1.3 Transformer Construction using Dot Orientation

2.1.4 Transformer Primary Tap Changes

Fig 2.4: tap change

In this basic precedent, the essential tap changes are determined for a supply voltage change of ±5%,
however any esteem can be picked. A few transformers may have at least two essential or at least two
auxiliary windings for use in various applications giving diverse voltages from a solitary center.

2.1.5 Transformer Core Losses


The capacity of iron or steel to convey attractive motion is a lot more noteworthy than it is in air, and this
capacity to enable attractive motion to stream is called porous. This implies a steel covered center can
convey an attractive motion multiple times superior to that of air. In any case, when an attractive motion
streams in a transformers steel center, two sorts of misfortunes happen in the steel. One named "vortex
current misfortunes" and the other named "hysteresis misfortunes”.

©Daffodil International University 6


2.1.6 Hysteresis Losses
Transformer Hysteresis Losses are caused in light of the erosion of the atoms against the stream of the
attractive lines of power required to polarize the center, which are always altering in esteem and course
first one way and after that the other because of the impact of the sinusoidal supply voltage.
Additionally, transformers are intended to work at a specific supply recurrence. Bringing down the
recurrence of the supply will result in expanded hysteresis and higher temperature in the iron center. So
diminishing the supply recurrence from 60 Hertz to 50 Hertz will raise the measure of hysteresis present,
diminished the VA limit of the transformer.

2.1.7 Eddy Current Losses


Transformer Eddy Current Losses then again are caused by the stream of circling ebbs and flows
prompted into the steel caused by the stream of the attractive transition around the center. These coursing
flows are created in light of the fact that to the attractive transition the center is acting like a solitary circle
of wire. Since the iron center is a decent conductor, the swirl flows instigated by a strong iron center will
be expansive.
2.1.8 Copper Losses

In any case, there is likewise another kind of vitality misfortune related with transformers called
"copper misfortunes". Transformer Copper Losses are for the most part because of the electrical
opposition of the essential and optional windings. Most transformer loops are produced using
copper wire which has opposition in Ohms. This opposition restricts the charging flows coursing
through them.

At the point when a heap is associated with the transformers optional twisting, extensive
electrical flows stream in both the essential and the auxiliary windings, electrical vitality and
power misfortunes happen as warmth. For the most part copper misfortunes fluctuate with the
heap current, being just about zero at no-heap, and at a greatest at full-stack when current stream
is at most extreme.

A transformers VA rating can be expanded by better plan and transformer development to lessen
these center and copper misfortunes. Transformers with high voltage and current evaluations
need conveyors of substantial cross-segment to support limit their copper misfortunes.
Expanding the rate of warmth dissemination (better cooling) by constrained air or oil, or by
enhancing the transformers protection so it will withstand higher temperatures can likewise build
a transformers VA rating.

©Daffodil International University 7


CHAPTER 3: LITERATURE REVEWS
3.1.0 These are the basic components of a transformer.

• Laminated core.
• Windings.
• Insulating materials.
• Transformer oil.
• Tap changer.
• Oil Conservator.
• Breather.
• Cooling tubes
kVA stands for Kilovolt-Ampere and is the rating normally used to rate a
transformer. The size of a transformer is determined by the kVA of the load. ...
The Current that passes through transformer windings will determine the Copper
Losses, whereas Iron Losses, Core Losses or Insulation Losses depends on voltage.
Copper losses (I²R) depends on current which passing
through transformer winding while Iron losses or core losses or Insulation losses
depends on Voltage. That's why the transformer rating may be expressed in VA
or kVA, not in W or kW.

What is a three phase transformer?


Three Phase Transformer Star and Delta Configurations. But what do we mean
by “star” (also known as Wye) and “delta” (also known as Mesh) when dealing
with three-phase transformer connections. A three phase
transformer has three sets of primary and secondary windings.

3.1.1 Technical Specification of 11/0.415 KV ,500 KVA Distribution


Transformer

Serial Technical Specification Requirement of Technical Data


BTCL
1 Rated Capacity (KVA) 500 500
2 Rated Frequency (Hz) 50 50
3 Rated Voltage (Primary), V 11000 11000

©Daffodil International University 8


4 Rated Voltage (Secondary), 415 415
V
5 Core Japan South Korea
6 Insulation Materials South Korea South Korea
7 Manufactured by RPTL RPTL
8 Accessories Silica gel Breather Silica gel Breather
Thermometer Thermometer
Buchloz Relay Buchloz Relay
9 Winding Super enameled Super enameled
copper wire copper wire
10 No. of Phase three three
11 Cooling System Oil Naturally Air ONAN
Cooled
12 No. of HT Bushing Three Nos. Three Nos.
13 No. of LT Bushing Four Nos. Four Nos.
14 Bushing Position Tank Top Tank Top
15 Accessories Conservation oil Conservation oil
level indicator drain level indicator
and filling valves drain and filling
lifting lungs bi- valves lifting lungs
directional rollers bi-directional
with first fitting of rollers with first
oil in Transformer fitting of oil in
Transformer

There are different ways of cooling transformer in order to protect from thermal
degradation.
1) ONAN-Oil natural air natural
2) ONAF- Oil natural air forces
3) OFWF- Oil forced water forced
4) ODAF-Oil directed air forced
5) ODWF- Oil directed water forced

©Daffodil International University 9


3.1.2 Cooling System of Transformer
This is the simplest transformer cooling system. The full form of ONAN is "Oil
Natural Air Natural". Here natural convectional flow of hot oil is utilized for
cooling. In convectional circulation of oil. This hot oil which comes to upper side,
will dissipate heat in the atmosphere by natural conduction, convection & radiation
in air and will become cold. In this way the oil in the transformer tank continually
circulate when the transformer put into load. As the rate of dissipation of heat in air
depends upon dissipating surface of the oil tank, it is essential to increase the
effective surface area of the tank. So additional dissipating surface in the form of
tubes or radiators connected to the transformer tank. This is known a s radiator of
transformer or radiator bank of transformer.

ONAF- Oil natural air forces

The full form of ONAF is "Oil Natural Air Forced". As the heat dissipation rate is faster and
more in ONAF transformer cooling method than ONAN cooling system, electrical
power transformer can be put into more load without crossing the permissible temperature limits

OFWF- Oil forced water forced


In this method, the oil is cooled in the cooling plant using air blast produced by the fans. These
fans need not be used all the time. During low loads, fans are turned off. Hence the system will
be similar to that of Oil Natural Air natural (ONAN). At higher loads, the pumps and fans are
switched on, and the system changes to Oil Forced Air Forced (OFAF). This method increases
the system efficiency. This is a flexible method of cooling in which up to 50% of rating ONAN
can be used, and OFAF can be used for higher loads. This method is used in transformers having
ratings above 30MVA.
ODAF-Oil directed air forced

ODAF or Oil Directed Air Forced Cooling of Transformer can be considered as the improved
version of OFAF. Here forced circulation of oil directed to flow through predetermined paths in
transformer winding. pre-decided oil flowing paths between insulated conductor are provided for
ensuring faster rate of heat transfer.

3.1.3 Tap changer


Above demonstrates a normal focus tap transformer. The tapping point is in the correct focus of
the optional winding giving a typical association with two equivalent however inverse auxiliary
voltages. With the inside tap grounded, the yield VA will be sure in nature regarding the ground,
while the voltage at the other auxiliary, VB will be negative and inverse in nature, that is they are
180o electrical degrees out-of-stage with one another

©Daffodil International University 10


CHAPTER 4: RESULTS AND DISCUSSION

4.1.0 Loading Transformer

Transformer provide a voltage on secondary winding to transfer power between their I/O they
require to load.

Fig 2.5: transformer basic circuit diagram


In the past transformer instructional exercises, I expected this transformer is perfect, that is one
in which are no center misfortunes in the transformer winding. In genuine transformers there will
be misfortunes related with the transformers stacking "on-stack". Well initially how about we see
the end result for a transformer when it is in this "no-heap" condition, that is with no electrical
load associated its secondary winding no optional flow streaming.

When its auxiliary side winding is open circuited, at the end of the day, nothing is joined and the
transformer stacking is zero. At the point when an AC sinusoidal supply is associated with the
essential twisting of a transformer, a little current, IOPEN will move through the essential curl
twisting because of the nearness of the essential supply voltage.

With the auxiliary circuit open, not all that much, back emf alongside essential winding
opposition to restrain stream of this essential power. The ammeter above will show a little current
coursing through the essential twisting despite the fact that the optional circuit is open circuited. This no-
heap essential current is comprised of the accompanying two parts:

• An in-stage current, IE which supplies the center misfortunes (vortex current and hysteresis).

• A little current, IM at 90o to the voltage which sets up the attractive transition.

©Daffodil International University 11


Figure: vector diagram

Note this no-heap essential current, Io is little contrasted with the transformers ordinary full-stack current.
Additionally because of the iron misfortunes present in the center and a little measure of copper
misfortunes in the essential winding, Io does not fall behind the supply voltage, Vp by precisely 90o, (
cosφ = 0 ), there will be some little stage edge distinction.
4.1.1 Transformer loading example :
A solitary stage transformer has a vitality part, IE 2 Ampere and a polarizing segment, IM of 5 Ampere.
Ascertain no-heap current and coming about power factor.

4.1.2 Transformer “On-load”


At the point electrical load is associated with the optional twisting of a transformer stacking is
along these lines more noteworthy than zero of a flow streams in the auxiliary twisting to the
heap. This optional current is because of the actuated auxiliary voltage, set up by the attractive
motion made in the center from the essential power.

©Daffodil International University 12


This joined attractive field diminishes EMF essential winding. Essential power keeps on
expanding the centers attractive at its unique quality a transformer to work accurately. And
reasonable condition should dependably exist between the require and extra attractive fields.
Consider the circuit underneath.

We realize that the turns proportion of a transformer expresses that the aggregate prompted voltage in
each winding is relative to the quantity of turns in that winding and furthermore that the power yield and
power contribution of a transformer is equivalent to the volts times amperes, ( V x I ). In this manner

Be that as it may, we likewise know already that the voltage proportion of a transformer is equivalent to
the turns proportion of a transformer as: "voltage proportion = turns proportion". At that point the
connection between the voltage, current and number of turns in a transformer can be connected together
and is in this way given as:

©Daffodil International University 13


4.1.3 Transformer Ratio:

• Where:

• NP/NS = VP/VS - represents the voltage ratio

• NP/NS = IS/IP - represents the current ratio

The current oppositely relating to voltage and unit of turns. Infers with a transformer stacking on the
discretionary turning in order to keep up a good power level over transformers windings, if the voltage is
wandered up, the current must be wandered down and the a different way. Figuratively speaking, "higher
voltage-cut down current

As a transformers extent is the associations between the amount of turns in the fundamental and
discretionary, the voltage over each winding, and the current through the windings, we can enhance the
above transformer extent condition to find the estimation.

The total current drawn from the supply by the basic winding is the vector aggregate of the no-
store current, Io and the additional supply current, I1 in view of the helper transformer stacking
and which waits behind the supply voltage by an edge. We can exhibit this relationship as a
phasor graph.

he mean current drawn from the supply by the basic winding is the vector total of the no-pile
current, Io and the additional supply current I1 as a result of the helper transformer stacking and
which waits behind the supply voltage by an edge of Φ.

©Daffodil International University 14


4.1.4 Transformer Loading Current:

Fig 4.6: Transformers Loading Current

If we given currents IS & Io we calculate the primary current IP by this methods.

4.1.5 Transformers Voltage Regulation

The voltage control of a transformer is described as the modification in assistant terminal voltage when
the transformer stacking is at its most prominent, i.e. full-stack associated while the basic supply voltage

©Daffodil International University 15


is held consistent. Course chooses the voltage drop that occurs inside the transformer as the pile voltage
ends up being unnecessarily low a result of the transformers stacking being to high which therefore
impacts its execution and viability.
Voltage control is conveyed as a rate of the no-stack voltage. That point if E addresses the no-store helper
voltage and V addresses the full-stack discretionary voltage, the rate bearing of a transformer is given as

So for example a transformer passes on 100 volts at no-store and the voltage drops to 95 volts at full load,
the control would be 5%. The estimation of E-V will depend on the internal impedance of the winding
which joins its resistance is R and even more basically its AC reactance X of the current and the stage
edge.
In like manner voltage bearing generally increases as the power factor of the pile ends up being all the all
the more slacking. Voltage bearing concerning the transformer stacking can be either positive or negative
in regard, that is with the no-load voltage as reference, the change down in charge as the store is
associated, or with the full-stack as reference and the switch up in heading as the pile is diminished or
ousted.
In the accompanying instructional exercise about Transformers we will look at the Multiple Winding
Transformer which has more than one basic winding or more than one assistant winding and see how we
can interface no less than two discretionary windings together in order to supply more voltage or
progressively current to the related load
4.1.5 The Auto transformer
Primary and secondary windings of an Auto transformer are conducted electrically and magnetically reducing the costs

Fig 4.7: Auto transformer

Not at all like the past voltage had transformer which has two electrically segregated windings called: the
essential and the optional an Auto transformer has just a single voltage winding which is basic to the two
sides. This single winding is tapped at different indicates along its length give a level of the essential
voltage supply over its optional load. At that point the autotransformer has the typical attractive center
however just makes them wind, which is normal to both the essential and auxiliary circuits.

The area of twisting assigned as the essential piece of the winding is associated with the AC control
source with the auxiliary being a piece of this essential winding. An autotransformer can likewise be
utilized to step the supply voltage up or somewhere around switching the associations. In the event that
the essential is the aggregate winding and is associated with a supply, and the auxiliary circuit is
associated crosswise over just a segment of the twisting then the optional voltage is ventured down.

©Daffodil International University 16


4.1.6 Dis-advantages of an Autotransformer

• Principle damage of an autotransformer is that it does not have the essential to optional twisting
isolation of a regular twofold twisted transformer. At that point an autotransformer can not be
securely utilized for presume down higher voltages to much lower voltages appropriate for littler
burdens.

• If the auxiliary side winding ends up open-circuited, stack current quits moving through
the essential winding halting the transformer activity bringing about the full essential voltage
being connected to the optional terminals.

• the optional circuit endures short out condition of the subsequent essential power would be a
lot bigger of a comparable twofold twisted transformer because of the expanded motion linkage
harming the auto transformer.

• From the nonpartisan association is regular to both essential and optional windings and
earthing of the auxiliary twisting consequently earthing the essential as there no disconnection
between two windings. Twofold twisted transformer at times used to disengage gear from world.

Autotransformer has numerous utilizations and optimize including the beginning acceptance
engines control of transmission lines can utilize to shift voltage when it required elective
proportion near solidarity.

4.1.7 Current Transformer

The Current Transformer is a sort of "instrument transformer" is intended to create a substituting current
in optional winding which is it corresponding to current being estimated in its requirement.

©Daffodil International University 17


Fig 4.8: construction of Current Transformer

Flow transformer diminish high voltage flows to a much lower esteem and give an advantageous
optimizing the genuine electrical flow streaming an AC transmission line utilizing a idle ammeter. The
essential of activity of a fundamental current transformer is marginally not quite the same as that of a
conventional voltage transformer.

Different voltage or power transformer took a gander at already, the present transformer comprises of just
a single or not very many turns as its essential winding. This essential winding can be of either a solitary
level turn, a curl of substantial wire folded over the center or only a conduit or transport bar set through a
focal gap as appeared.

Because of this sort of game plan, the present transformer is frequently alluded too as an "arrangement
transformer" as the essential winding, which never has in excess of a not very many turns, is in
arrangement with the current conveying conductor providing a heap.

The auxiliary twisting in any case, may have countless turns twisted on a covered center of low-
misfortune attractive material. This center has an extensive cross-sectional region with the goal that the
attractive transition thickness made is low utilizing a lot littler cross-sectional zone wire, contingent on
how much the current must be ventured down as it endeavors to yield a steady current, free of the
associated load.

The optional winding will supply a current into either a short out an ammeter or resistive load until the
point that the voltages actuated in secondary at sufficiently enormous soak center.

As opposed to a voltage transformer, the fundamental current of a present transformer isn't dependent of
the discretionary load current yet rather is controlled by an external load. The helper current is typically
assessed at a standard 1 Ampere or 5 Amperes for greater basic current evaluations.

There are three fundamental sorts of current transformers: wound, toroidal and bar.

©Daffodil International University 18


• Wound Current Transformer – The transformers fundamental winding is physically related in course of
action with the conductor that passes on the conscious current gushing in the circuit. The extent of the
helper current is liable to the turns extent of the transformer.

• Toroidal Current Transformer – These don't contain a fundamental winding. Or maybe, the line that
passes on the present spilling in the framework is hung through a window or hole in the toroidal
transformer. Some present transformers have a "split focus" which empowers it to be opened, presented,
and close, without separating the circuit to which they are joined.

• Bar type Current Transformer – This sort of current transformer uses the genuine connection or
transport bar of the crucial circuit as the fundamental winding, which is similar to a singular turn. They
are totally shielded from the high working voltage of the system and are ordinarily dashed to the present
passing on device.

Current transformers can decrease current measurements from countless down to a standard yield of an
acknowledged extent to either 5 Ampere for common errand. Thusly little and exact instruments and
control devices can be used with CT's since they are shielded a long way from any high-voltage electrical
links. There are a collection of metering applications and uses for current transformers for instance with
Wattmeter's control factor meters watt-hour meters guarded exchanges.

By extending the amount of discretionary windings Ns the helper current can be made significantly tinier
than the current in the basic circuit being assessed in light of the way that as Ns increases Is goes some
place close to a relating total. Accordingly, the amount of turns and the current in the basic and assistant
windings are associated by a retrogressive degree.

from which we get:

©Daffodil International University 19


Fig 4.9: Current Transformer Primary Turns Ratio

4.1.8 Current Transformer Example


A bar-type current transformer which has 1 turn on its fundamental and 160 turns on its helper is to be
used with a standard extent of ammeters that have an internal hindrance of 0.2ω. The ammeter is required
to give a full scale redirection when the fundamental current is 800 Amps. Figure the most extraordinary
helper present and discretionary voltage over the ammeter
Secondary Current:

Voltage across Ammeter:

We can see over that since the optional of the present transformer is associated over the ammeter, which
has a little obstruction, the voltage drop over the auxiliary winding is just 1.0 volts at full essential
current.
High voltage grounds that the voltages per turn proportion relatively steady in essential and optional
windings.
Therefore:

©Daffodil International University 20


Present transformer commitment worked no-heap included when the rule major current is going
through it likewise as a voltage transformer ought to never work into a short out. On the off
chance that the ammeter is to be cleared a short out ought to be put over the optional terminals
first to go out on a limb of stun. This high voltage is in light of the fact that when the assistant is
open-circuited the iron focus of the transformer works at an abnormal state of inundation and
with nothing to stop it, it makes an oddly far reaching discretionary voltage, and in our
fundamental model over this was resolved.

4.1.9 3 Phase Transformers

3-p Transformers is mother of power distribution where Delta or Star connections

Fig
4.10: three phase transformer

©Daffodil International University 21


4.2.0 Three Phase Voltage and Current

Where: VL is line-to-line voltage, and VP is stage to-unbiased voltage.


A transformer cannot go about as a stage changing gadget and change single-stage into three-
stage or three-stage into single stage. To make the transformer associations good with three-stage
supplies we have to interface them together with a specific goal in mind to shape a Three Phase
Transformer Configuration.
A three stage transformer can be built in interfacing together three single-stage transformers, in
this manner framing an alleged three stage transformer bank pre-collected and adjusted three
stage transformer which comprises of three sets of single stage windings mounted onto one
single overlaid center.
4.2.1 Three Phase Transformer Connections

The essential and optional windings of a transformer can be associated in various set up as
appeared meet for all intents and purposes any necessity. On account of three stages transformer
windings three types of association are conceivable star delta and interconnected-star.
©Daffodil International University 22
4.2.2 Transformer Delta and Delta Connections
In a delta associated gathering of transformers, the line voltage, VL is equivalent to the supply voltage,
VL = VS. Be that as it may, the current in each stage winding is given as: 1/√3 × IL of the line current,
where IL is the line current.

One disservice of delta associated three stage transformers is that every transformer must be twisted for
the full-line voltage and for 57.7 percent, line current. The more noteworthy number of turns in the
twisting, together with the protection between turns, require a bigger and more costly loop than the star
association. Another inconvenience with delta associated three stage transformers is that there is no
normal association.

In the star-star course of action yy-and delta-wye every transformer has one terminal associated with a
typical intersection, or impartial point with the three outstanding closures of the essential windings
associated with the three-stage mains supply. The quantity of turns in a transformer twisting for star
association is 57.7 percent, of that required for delta association.

The star association requires the utilization of three transformers, and if any one transformer progresses
toward becoming deficiency or incapacitated, the entire gathering may wind up debilitated. In any case,
the star associated three stage transformer is particularly helpful and conservative in electrical power
dispersing frameworks, in that a fourth wire might be associated as a nonpartisan purpose of the three star
associated secondaries as appeared.4.2.4 Transformer Star and Star Connections

The secondary current in each phase of a star-connected group of transformers is the same as that for the
line current of the supply, then IL = IS.

©Daffodil International University 23


4.2.3 Star-Delta Turns Ratio

In like manner, for a delta– star associated transformer, with a 1:1 turns proportion, the transformer will
give a 1:√3 advance up line-voltage proportion. At that point for a delta-star associated transformer the
turns proportion moves toward becoming:

4.2.4 Delta-Star Turns Ratio

At that point for the four essential setups of a three-stage transformer, we can list the transformers
optional voltages and flows as for the essential line voltage VL and its essential line current IL as
appeared in the accompanying table.
Three-phase Transformer Line Voltage and Current:

Primary-Secondary Line Voltage Line Current


Configuration Primary or Secondary Primary or Secondary

Delta – Delta

Delta – Star

Star – Delta

Star – Star

©Daffodil International University 24


4.2.5 Three Phase Transformer Construction

Fig 4.11: primary and secondary coil winding

The three-appendage center sort three-stage transformer is the most well-known technique for

three-stage transformer development enabling the stages to be attractively connected. Transition

of every appendage utilizes other two appendages for arrival way with the three attractive

motion's the center created by the line voltages contrasting in time-stage. In this manner the

motion in the center stay almost sinusoidal wave creating optional voltage of supply.

©Daffodil International University 25


CHAPTER 5

5.1 Bus-bar Trunking System (BBT)

Transport bar trunking frameworks (BBT) comprise of protected copper or aluminum transport bars

encased in a trunking. Utilize a master epoxy pitch covering to protect every conductor, the covering is

connected to the transport bars utilizing an in-house created and industry driving procedure. Transport bar

trunking is measured in plan and is provided in pre-manufactured lengths and accessible in a scope of

conductor setups. It item go regularly incorporates elbows, T-connectors, feeder units, board spines and

different other standard or custom segments that make it easy to arrange for any application.

5.2 Bus-bar highlights of character:

1) Easy to configuration control conveyance and clear system structure,

2) Easy building and establishment probability

3) Law starts vitality and high short out esteem.

4) Fast and straightforward establishment with least devices.

5) During establishment, there is no waste or scrap. So it's condition amicable.

6) Easily be expelled and re-utilized where required

©Daffodil International University 26


5.3 Specifications

Fig:

bus-bar trunking system

5.4 Bus-bar Trunking system benefits than Cable

Serial No. Bus-bar Trunking system Cable


I Features :
Completing it great, subsequently add Improper cabling may ruins the feel of building
to style of building

Numerous floor building power Multiple floor building power encouraging


bolstering should be possible with must be finished with different link sets. This
single Bus trunking system make the total framework awkward.
Power tap off should be possible from Not conceivable. Extra links to be laid till the
the single framework introduced.. On specific floor.
the off chance that the heap transforms
we need to simply supplant the Tap off
boxes of higher rating
II Voltage Dropped :
The voltage drop of bus trunking is less Dropped voltage more than BBT
when contrasted with cables.

III Structural :
Case of 3200A(Cu) measurement is: Cables structure 700mm wide i.e., link plate
151(w)x340(h) and light in weight. and so on is overwhelming and possesses more
space.
Add up to run is comprised of various Single length different cables are introduced,
components which are joint together.

©Daffodil International University 27


Subsequently making the total making it support not inviting.
framework upkeep friendly.

Simple retrofitting of the component is Easy retrofitting of the component is beyond


conceivable in the event that the area the realm of imagination on the off chance that
and shopper load the area and buyer stack

Completely Can’t be altered. Fit and overlook Insulation Needs to kept up on customary
encased system2 premise.

IV Level of Protection:

No Special security is to be taken for Special assurance is to be taken for


establishment as bus-bars are presently establishment in OUTDOOR territory
accessible up to IP68 insurance class
V Walled in area :
It comprises of bus-bars in a defensive Cables are just protected with various layers of
walled in area, including straight PVC.
lengths, fittings, gadgets and
accessories.
High Short circuit quality and high fire Low Short circuit quality and low fire insurance
protection
VI Termination :
Coordinate end through bus-bars The strategy for link end is exceptionally
unwieldy
Termination is straightforward and Additional underpins are required to hold the
easy links inside the board
Have an exceedingly conservative Cables are for the most part introduced in packs
structure and can be bowed up to 90 and with such a cross segment, to the point that
degree. they can not be bowed firmly.
VII Time & Cost Consumption :
Measuring bus-bars the fashioner just It is important to ensure each link
needs to make figuring on a solitary exclusively with a wire and when laying the
riser which diminishes configuration links in groups it is important to stay them
time and costs. legitimately so they can withstand the
electro dynamic powers created in case of a
short out. Along these lines, the originators
need to invest more energy in counts.
VIII Utilization of extra things :

No extra backings are required. Heavy work is required to lay the links

No additional gaps/patterns are Holes to be made in the organ plate for settling
required. link

No needed cable tray , supported on Cable tray or the digging must needed

©Daffodil International University 28


wall.
No link plate is required, upheld on Cable plate or the burrowing of the trench is
roof/wall. required to lay the links

Configuration checked switchgear get Limits rely upon the laying technique and link
together, limits from maker's catalogue gathering. The de rating factor must be
resolved/determined

IX Halogen Free :
Free of halogen It may have halogen.

Chapter 6
©Daffodil International University 29
CONCLUSIONS
All objective parts of this field study I can assign and collect data. This system is able to detect
objects within the sub-station. Amplitude of the sub-station are attached , materials , and size.
The technique could utilized for the exchange of power the nation over through the electrical
cables.the circuit was not providing the most proficient or greatest effectiveness, because of the
center misfortunes not measuring up to the copper misfortunes. The greater the reflector, the
better the reflection, and the more grounded the reflection flag is. the extraordinary capacity to
adjust to different conditions and encompassing conditions. So in the event that you expands the
voltage out, the current out must reductions. On the off chance that you venture up the voltage ,
with the goal that voltage yield is twofold the voltage input.Subsequent to experiencing all the
harsh occasions of activity the short experience has opened up the scientists eyes to a more
extensive world. For every one of the slip-ups that have made and the quantity of deadlocks that
the analyst has incidentally caught himself in, the specialist trusts he will experience one more
day to be a superior individual in this specialized field. It is proudly that the analyst declares his
consummation of this undertaking as per the necessity of destinations that have been expressed
in the early sections.

Through this field think about, the specialist has picked up a great deal of learning in KAVR its
related family particularly on the most proficient method to utilize the catch includes and
controlling the info yield ports and clocks. A ton of important data likewise acquired amid this
field think about which isn't instructed in classes all through five years of study. Close to,
different aptitudes, for example, correspondence, critical thinking, self-learning abilities and self-
working capacity have been produced in the specialist himself accomplishing this point.

REFERENCES

©Daffodil International University 30


[1] P. Kleinschmidt and V. Magori, auto transformer for exact loading effect and object
identification.Proc, IEEE, 1985, Vol.1, pp.457-462.

[2] D. Marioli. E. Sardini and A. Taroni. transformer and angular position control, IEEE
Trans, lustrum. Meas. Vol.37, N.4. December 1988, pp.578581.

[3] C. Laughlin, cell type and core type: keeping your data load, loss less Rev., April 1989,
pp.85-89.

[4] G. Hayward and Y. Corfu. A digital hardware correlation system for fast ultrasonic data
acquisition in peak power limited applications, IEEE Trans.. Ferro Freq. Control, Vol.35,
N.6, November 1988, pp. 800-808.

[5] PT canconervativetive, National Semiconductor Special Purpose Linear

Devices Datebook, 1989, pp. 977-9/84.

[6] construction of transformer, Murata Products 1991, 1991, p. 77.

[7 ]Honeywell auto trasnformer Series 942.Honeywell Data Sheet Ell01, 1989.

[8] S. Koki’s, Z. Figure, single phase Measurements and Technologies, Chapman and Hall,
London, 1996.

[9] http://www.its.bth.se/bil_lab/Datablad/autotransformer.PDF

[10] http://en.wikipedia.org/wiki/transformer

[11] http://en.wikipedia.org/wiki/shell_type

[12] (PDF) Single-Image core type by A Smart Mobile Device. Available from:
https://www.electronis-tutorials.ws/publication/308308750Image_transformer_threee-
phase_by_A_Smart_Device [accessed Dec 26 2018].

©Daffodil International University 31

You might also like