HCVR-3 Datasheet

The HCVR-3 is a 3 zone conventional releasing fire alarm control panel that can be configured to activate releasing from a single zone or combination of zones. It has a LCD display to show the countdown timer during activation. The panel is fully programmable, has a single board construction, and is compatible with a wide range of detection devices and releasing valves.

Uploaded by

JOSE BAQUERO
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
128 views2 pages

HCVR-3 Datasheet

The HCVR-3 is a 3 zone conventional releasing fire alarm control panel that can be configured to activate releasing from a single zone or combination of zones. It has a LCD display to show the countdown timer during activation. The panel is fully programmable, has a single board construction, and is compatible with a wide range of detection devices and releasing valves.

Uploaded by

JOSE BAQUERO
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

HCVR-3 - CONVENTIONAL RELEASING FIRE ALARM CONTROL PANEL

STANDARD FEATURES
• UL 864 Listed and FM Approved
• Three detection zones
• Any single zone or any combination of zones can be
configured to release
• Fully programmable using simple menu options
• Simple, single board construction
• Installer friendly
• Compatible with wide range of detection devices
DESCRIPTION
• Configurable first stage NAC delays

The HCVR-3 is a 3 zone conventional releasing fire • Configurable detection delays


alarm control panel that is UL Listed and FM Approved • Built-in Manual Release switch and separate circuit
for releasing.
• Compatible with FirePro Xtinguish™
The HCVR-3 can be configured to activate releasing by
a single zone or combination of any two zones. The • Compatible with various releasing valves
LCD display is used to show the countdown timer • Configurable releasing delays up to 60 seconds in 5
during activation of the releasing sequence. second intervals
The HCVR-3 is fully programmable using simple menu • Configurable releasing duration up to 5 minutes in 5
options. The panel is a single board construction which second intervals
provides an easy replacement solution. It is also
compatible with a wide range of devices. • Releasing countdown timer displayed on the LCD
• Supports up to seven HCVR-SDU or HCVR-AB
• Built-in relays for Fire, Trouble, Stage 1, Stage 2,
Extract and Local Fire

PRODUCT LISTINGS

California State
Fire Marshal
7165-0410:0206
S6468 3046396

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Phone: 714-522-2246 Fax: 714-522-2268
Technical Support: 714-670-3229 or technicalsupport@hochiki.com Page 1 of 2 F0154 Rev.01 04/2023
HCVR-3 - CONVENTIONAL RELEASING FIRE ALARM CONTROL PANEL
SPECIFICATIONS
Supply Voltage 115VAC (50hz/60hz) or 230VAC (50hz/60hz)
Power Supply DC Rating 24V 3 Amps
Mains Supply Fuse 1.6 Amps 250V
Dimensions 14.5" (W) x 12.2" (H) x 3.5" (D)
Weight 12.3 lbs. w/o batteries
Color Red or gray
Material 1.2mm mild steel
Max. Battery Size 7Ah 12V (2 per panel)
RS-485 Serial Bus Maximum line impedance 120 Ohms
Trouble Contact Rating 30VDC 1 Amp
Local Fire Contact Rating 30VDC 1 Amp
Fire Contact Rating 30VDC 1 Amp
1st Stage Contact Rating 30VDC 1 Amp
2nd Stage Contact Rating 30VDC 1 Amp
EXTRACT Output 30VDC 1 Amp contacts for (NO) and (C)
EXISTING Output Rating 18 to 28VDC 1 Amp max load for 5 minutes and voltage reversing DC
NAC Output Rating 0.5 Amp per output
Detection Zone End of line resistor 6K8 Ohms 5% resistor
NAC Output 10K Ohms 5% resistor
Stand by Current 86 mA
Alarm Current 620 mA
Operating Humidity 95% RH Non-Condensing
Operating Temperature -5°C to +40°C (23°F to 104°F)

HOCHIKI AMERICA COMPATIBLE DEVICES


MODEL DESCRIPTION MAX
PANEL ACCESSORIES
HCVR-SDU Remote Status Display Unit 7
HSVR-AB Ancillary Board 7
HCVR-SQA Sequential Activator 20
HCVR-DS Disconnect Switch 1
DETECTORS
SLR-24H Photoelectric Smoke Detector w/heat 20 per zone
SLR-835 Photoelectric 8-35V Smoke Detector 20 per zone
SLR-835/-835W Photoelectric 8-35V Smoke Detector 20 per zone
SLR-835-BH-2W Photoelectric 8-35V Smoke Detector w/heat 20 per zone
SLV-24V/-24/-24N Photoelectric Smoke Detector 20 per zone
SOE-24V, SOE-24H Photoelectric Smoke Detector 20 per zone
SOC-24V / SOC-24VN Photoelectric Smoke Detector 20 per zone
SIJ-24 Ionization Smoke Detector 20 per zone
DCD-135 135° Fixed Temperature Rate of Rise Heat Detector 20 per zone
DCD-190 190° Fixed Temperature Rate of Rise Heat Detector 20 per zone
BASES
NS6-220 6" base, 93mA draw, 24V 20
NS4-220 4" base, 93mA draw, 24V 20
PULL STATION/ABORT SWITCH
HPS-SAK/HPS-DAH/HPS-SAH/HPS-DAK Conventional Manual Pull Station for Fire Suppression Release n/a
HCVR-AS Abort Switch n/a
RELEASING VALVES
HV2185328 ASCO Solenoid 1
8210G207 ASCO Solenoid 1
11601 Viking Solenoid 1
11602 Viking Solenoid 1
11592 Viking Solenoid 1
11591 Viking Solenoid 1
11596 Viking Solenoid 1
11595 Viking Solenoid 1
2823A-2NB-A4F6 Snap-tite Solenoid 1
EA45 (510006) Sevo Systems Solenoid 1
K-45-8017 Kidde Solenoid (equivalent to 486500-01) 1
B6793-859 Kidde Solenoid (equivalent to 81-100000-001) 1
753-E Series Victaulic Solenoid 1
305350 Ci IS8B Fire Eater Solenoid 1
305451 Ci IS8B Fire Eater Solenoid 1