   INDEX                                                       NX-G06 0202P - 0812P
   Liability disclaimer
   The present publication is drawn up by of information only and does not constitute an offer binding upon Mitsubishi Electric Hydronics & IT
   Cooling Systems S.p.A.
   Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. has compiled the content of this publication to the best of its knowledge. The data
   contained herein are subject to change without notice. Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A. explicitly rejects any liability for
   any direct or indirect damage, in the broadest sense, arising from or related to the use and/or interpretation of this publication. All content is
   copyrighted by Mitsubishi Electric Hydronics & IT Cooling Systems S.p.A.
The units highlighted in this publication contain R454B [GWP100 466] fluorinated greenhouse gases.
Functions
                          Cooling
Refrigerant
                          R454B
Compressors
                          Scroll compressor
Fan
                          Axial fan
Exchangers
                          Plates heat exchanger
Other features
Eurovent
To find out more about how our products contribute to enhanced green
certification rating and energy performance of a building, please refer
to:
https://www.melcohit.com/GLOBAL/Company/Green-Certifications/
QR%20code/
Outdoor unit for the production of chilled water with hermetic rotary Scroll
compressors, low-GWP and ozone-friendly refrigerant R454B, axial-flow
fans, plate heat exchanger, micro-channel full-aluminum air coils and
thermostatic or electronic expansion valve, according to the model. The
range is composed by units equipped with two compressors in a
single-circuit configuration.
                                   Size
                                   First 3 digits
                                   Compressors size
                                   Last digit
                                   Number of compressors
                                   P Plates heat exchanger
                                   Versions
                                   K
                                   Key efficiency, compact version
                                   LN-K
                                   Low Noise, Key efficiency and compact version
                                   SL-K
                                   Super Low noise, Key efficiency and compact
                                   version
                                   CA
                                   Class A of efficiency
                                   LN-CA
                                   Low Noise, Class A of efficiency
                                   SL-CA
                                   Super Low noise version, Class A of efficiency
                                   Configurations
                                   -
                                   Basic function
                                   D
                                   Partial condensing heat recovery function
                                   Product
                                   NX-G06
                                   Chiller, air source for outdoor installation
                                   Refrigerant gas R454B
3.2 Chiller, air source for outdoor installation                               -   general door lock isolator
Outdoor unit for the production of chilled water with hermetic rotary Scroll   -   control circuit transformer
compressors, low-GWP and ozone-friendly refrigerant R454B, axial-flow          -   IP44 protection
fans, plate heat exchanger, micro-channel full-aluminum air coils and          -   power circuit with electric bus bar distribution system (sizes 702, 712,
thermostatic or electronic expansion valve, according to the model. The            802, 812)
range is composed by units equipped with two compressors in a                  -   numbered cables
                                                                               -   electric circuit breakers for compressors and fans
single-circuit configuration.
                                                                               -   remote ON/OFF terminals
                                                                               -   terminals for cumulative alarm block
3.3 Structure                                                                  -   relays for remote pump(s) activation for both circuits (only for units
Structure specifically designed for outdoor installation. Basement and
                                                                                   without hydronic pumps)
frame in hot-galvanised shaped sheet steel with a suitable thickness. All      -   antifreeze electric heater for heat exchanger
parts polyester-powder painted to assure total weather resistance.             -   electronic controller
- Compressors fastened to unit's frame with ani-vibration mountings.           -   multi-language user keypad with LCD display
- Compressor compartment separated from ventilation section.                   -   Power supply 400V/3ph/50Hz+N+PE for units:
- Compressor compartment with soundproofing anclosure (thickness of            -   versions K, sizes 0152P..0352P
   30 mm on sides and on top, 15 mm on bottom) (versions LN-K, SL-K,               versions LN-K, sizes 0152P..0302P
   LN-CA, SL-CA).                                                                  versions SL-K e LN-CA, sizes 0152P..0202P
                                                                                   versions CA, sizes 0152P..0262P
3.4 Compressor                                                                 -   Power supply 400V/3ph/50Hz+PE for units:
Hermetic scroll compressors in tandem layout complete with oil sump            -   versions K sizes 0402P..0812P
heater, electronic overheating protection with centralised manual reset            versions LN-K sizes 0352P..0812P
and a two-pole electric motor.                                                     versions SL-K e LN-CA sizes 0252P..0812P
                                                                                   versions SL-CA
3.5 Plant side heat exchanger
Braze welded AISI 316 plate heat exchanger. The heat exchanger is lined        3.10 Certification and applicable directives
on the outside with 9 mm thick closed-cell neoprene lagging to prevent         The unit complies with the following directives and relative amendments:
condensation, with a thermal conductivity of 0,33 W/mK at 0°C. The heat        - EUROVENT Certification program
exchanger is fitted with a differential pressure switch to monitor the         - CE Declaration of conformity certificate for the European Union
correct flow of water when the unit is operating, thus preventing ice form     - Machine directive 2006/42/EC
forming inside; if no flow is detected, the frost protection function is       - ElectroMagnetic compatibility directive 89/336/EEC + 2004/108/EC
activated using a special heater.                                              - Low Voltage directive 2006/95/EC
The heat exchanger comes standard with safety pressure release valve           - PED Directive 2014/68/EC
                                                                               - ISO 9001 Company´s Quality Management System certification
(water side) (10 bar).                                                         - ISO 14001 Company´s Environmental Management System
3.6 Source side heat exchanger                                                    certification
Full-aluminum microchannel coil.
- Longitudinal V-shaped coil module: Coil structure made with an               3.11 Tests
                                                                               Tests performed throughout the production process, as indicated in
   open-angle Longitudinal V-shaped layout.
- Horizontal V-shaped coil module: Coil structure made with an                 ISO9001.
   open-angle Horizontal V-shaped layout.                                      Performance or noise tests can be performed by highly qualified staff in
                                                                               the presence of customers.
3.7 Fan section source side                                                    Performance tests comprise the measurement of:
Axial electric fans, protected to IP 54, with external rotor and               - electrical data
plastic-coated aluminium blades. Housed in aerodynamic hoods complete          - water flow rates
with safety grille. Electric motor with built-in overload protection.          - working temperatures
Fans diameter: 450 mm, 800 mm or 910 mm according to the unit's size           - power input
and version.                                                                   - power output
Electric motor with 4 poles, 6 poles or 8 poles according to the unit's size   - pressure drops on the water-side exchanger both at full load (at the
and version.                                                                   conditions of selection and at the most critical conditions for the
- Continuous adjustment of the fan speed on units:                             condenser) and at part load conditions.
- versions K, sizes 0152P..0352P                                               During performance testing it is also possible to simulate the main alarm
   versions LN-K, sizes 0152P..0302P                                           states.
   versions SL-K e LN-CA, sizes 0152P..0202P                                   Noise tests are performed to check noise emissions according to
   versions CA, sizes 0152P..0262P                                             ISO9614.
- Pressostatic fan’s control:
- versions K sizes 0402P..0802P                                                3.12 R454B REFRIGERANT
- Adjustment of the fan speed with auto-transformer on units:                  The refrigerant used in these units is R454B, one of the most
- versions LN-K sizes 0352P..0802P                                             eco-sustainable refrigerants for replacing traditional R410A, thanks to the
   versions SL-K sizes 0252P..0802P                                            76% lower GWP.
   versions LN-CA sizes 0252P..0812P                                           Unlike R410A, R454B is classified as A2L according to ISO 817. The first
   versions SL-CA, sizes 0152P..0812P                                          digit defines toxicity (A: NON-TOXIC), while the last digits define the
                                                                               flammability level (2L: MILDLY FLAMMABLE - low burning velocity). It is
3.8 Refrigerant circuit
Main components of the cooling circuit:                                        classified by PED Directive into Group 1.
- single circuit in tandem compressors                                         The main characteristics of this refrigerant and some additional guidelines
- total ratio between refrigerant charge and cooling capacity* lower than      are reported below. Despite the minimal risk, the indications provided
   0,12 g/W (versions K, LN-K, SL-K, CA)                                       cannot replace a more detailed risk analysis if required, also based on
- total ratio between refrigerant charge and cooling capacity* lower than      any regulations in force in the installation area.
   0,15 g/W (versions LN-CA, SL-CA)                                            Further and more detailed guidelines are available in the dedicated area
- plate heat exchanger                                                         of the website www.melcohit.com (Guidelines) or in the dedicated
- drier filter with replaceable cartridge                                      addendum of the general installation and maintenance manual.
- refrigerant line sight glass with humidity indicator                         Main characteristics of R454B refrigerant:
- electronic expansion valve                                                   - Safety classification (ASHRAE / ISO 817): A2L
- high and low pressure transducers
- high and low pressure safety valves, conveyed to external discharge          - PED Group: 1
- safety switching device for limiting the pressure                            - Ozone Depletion Potential (ODP) (R11=1): 0
- crankcase heater on each compressor                                          - AR5 (AR4) GWP (CO2=1): 467 (466)
- * Cooling capacity according to Eurovent conditions: water(in/out)           - Composition (Wt %): 68,9% R32, 31,1% R1234yf
   12/7°C, outdoor temperature 35°C                                            - LFL@23°C, 50% RH (% v/v): 11,7
                                                                               - UFL@23°C, 50% RH (% v/v): 22,0
3.9 Electrical and control panel                                               - Burning velocity (cm/s): 5,2
Electrical and control panel built to EN60204-1 and EC204-1 standards,         - Minimum Ignition Energy (mJ) (ASTM E582-13): 100-300
complete with:
-
                                                                                3.14 Versions
                                                                                /K - Key efficiency, compact version
                                                                                Key efficiency, compact version.
3.15 Configurations
- , standard unit
Standard unit for production of chilled water
     The following table shows the structure of all the available NX-G06 sizes/version:
       Structure                                                                                                Size
       Longitudinal V              202           252           262            302           352           402          452    502       552       602       702       802
                                                                                                                                          (1)
       Version                                                                Net cooling capacity (kW) - EN14511 -
       K                           50             56            62             74            85            98          110    122       138       159       182
       LN-K                        50             56            63             72            86            95          108    120       134       156       172
       SL-K                        50             56            63             75            85            96          109    119       135       147
       CA                          53             60            67             81            92           103          117    132       154       171       193       218
       LN-CA                       53             61            68             79            90           103          115    129       148       166       190       212
       SL-CA                       53             60            66             79            90           102          114    127       145       165       187       209
     (1) Plant (side) cooling exchanger water (in/out) 12°C/7°C; Source (side) heat exchanger air (in) 35°C.
The following table shows the controller of all the available NX-G06 sizes/version:
                                                                                                                Size
                                                                                                          402          452    502       552       602       702       802
       Version                     202           252           262            302           352
                                                                                                          412          462    512       562       612       712       812
       K
       LN-K                                W3000
       SL-K
       CA                                                                                               W3000+
       LN-CA
       SL-CA
The following table shows fan diameters (mm), fan motor types and std ventilation controls of all the available NX-G06 sizes/version:
                                                                                                                Size
                                                                                                          402          452    502       552       602       702       802
       Version                     202           252           262            302           352
                                                                                                          412          462    512       562       612       712       812
                                 Ø450           Ø450          Ø450          Ø450           Ø450          Ø800       Ø800      Ø800      Ø800      Ø800      Ø800      Ø800
       K
                                4 poles        4 poles       4 poles       4 poles        4 poles       6 poles    6 poles   6 poles   6 poles   6 poles   6 poles   6 poles
                                 Ø450           Ø450          Ø450          Ø450           Ø800          Ø800       Ø910      Ø910      Ø910      Ø800      Ø800      Ø800
       LN-K
                                4 poles        4 poles       4 poles       4 poles        6 poles       6 poles    6 poles   6 poles   6 poles   6 poles   6 poles   6 poles
                                 Ø450           Ø800          Ø800          Ø800           Ø910          Ø910       Ø800      Ø800      Ø800      Ø800      Ø800
       SL-K
                                4 poles        6 poles       6 poles       6 poles        6 poles       6 poles    6 poles   6 poles   6 poles   6 poles   6 poles
                                 Ø450           Ø450          Ø450          Ø800           Ø800          Ø910       Ø910      Ø800      Ø800      Ø800      Ø800      Ø800
       CA
                                4 poles        4 poles       4 poles       6 poles        6 poles       6 poles    6 poles   6 poles   6 poles   6 poles   6 poles   6 poles
                                 Ø450           Ø800          Ø800          Ø800           Ø910          Ø800       Ø800      Ø800      Ø800      Ø800      Ø800      Ø800
       LN-CA
                                4 poles        6 poles       6 poles       6 poles        6 poles       6 poles    6 poles   6 poles   8 poles   8 poles   8 poles   8 poles
                                 Ø800           Ø910          Ø910          Ø910           Ø800          Ø800       Ø800      Ø800      Ø800      Ø800      Ø800      Ø800
       SL-CA
                                6 poles        6 poles       6 poles       6 poles        6 poles       8 poles    8 poles   8 poles   8 poles   8 poles   8 poles   8 poles
     Note:
     The unit's operating limit depends on its ventilation control. Optional devices are available to enlarge the operating limits.
     Please refer to the dedicated data book section and to ElcaWorld selection software.
 808 - EC fans
 This option is available only for /CA, /LN-CA, /SL-CA versions.
 These fans are suitable to operate up to 46°C of outdoor
 temperature. In case of higher temperatures, fans with oversized
 motors must be used. For the quotation of these components,
 please contact our sales department.
 6196 – Kiplink
 6198 – Kiplink + keyboard
 5941 – With set point compensation
 5925 – Energy meter for W3000
 4185 – Serial card BACNET OVER IP
 4186 – Serial card KONNEX
 4187 – M-net W3000 kit
 4188 – Serial card MODBUS TCP/IP
 4189 – Serial card SNMP
 These options are available only for models equipped with
 W3000+ controller.
 The acquired data are then compared with the design data of
 each single unit at any different working conditions, thus allowing
 to implement control strategies based on dynamic algorithms
 which take into account the real operating conditions.
    NX-G06/K                                                                                      0202P 0252P 0262P 0302P 0352P 0402P 0452P 0502P 0552P 0602P
    Power supply                                                                       V/ph/Hz    400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50   400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
    PERFORMANCE
    COOLING ONLY (GROSS VALUE)
    Cooling capacity                                                         (1)           kW 49,84           56,52      62,39      74,51      84,98       97,89    109,9    122,3    138,5    159,0
    Total power input                                                        (1)           kW 16,80           19,05      21,78      24,87      29,10       33,00    37,44    41,84    48,66    53,78
    EER                                                                      (1)        kW/kW 2,964           2,958      2,862      2,992      2,921       2,967    2,939    2,926    2,844    2,955
    ESEER                                                                    (1)        kW/kW
    COOLING ONLY (EN14511 VALUE)
    Cooling capacity                                                       (1)(2)          kW 49,70           56,40      62,30      74,40      84,70       97,60    109,6    122,0    138,2    158,7
    EER                                                                    (1)(2)       kW/kW 2,920           2,930      2,830      2,960      2,860       2,910    2,880    2,870    2,800    2,910
    ESEER                                                                  (1)(2)       kW/kW   -               -          -          -          -           -        -        -        -        -
    Cooling energy class                                                                        -               -          -          -          -           -        -        -        -        -
    COOLING WITH PARTIAL RECOVERY
    Cooling capacity                                                         (3)            kW 51,71          58,64      64,73      77,31      88,17       101,6    114,0    126,9    143,7    165,0
    Total power input                                                        (3)            kW 16,25          18,42      21,05      24,05      28,13       31,99    36,27    40,52    47,10    52,11
    Desuperheater heating capacity                                           (3)            kW 14,10          16,11      18,55      20,86      24,64       25,89    29,85    33,78    39,87    42,65
    EXCHANGERS
    HEAT EXCHANGER USER SIDE IN REFRIGERATION
    Water flow                                                               (1)             l/s 2,383        2,703      2,984      3,563      4,064       4,681    5,255    5,850    6,623    7,605
    Pressure drop                                                            (1)            kPa 33,4           30,8       30,6       31,3       49,9        46,0     47,2     45,2     48,0     45,4
    PARTIAL RECOVERY USER SIDE IN REFRIGERATION
    Water flow                                                               (3)             l/s 0,681        0,778      0,895      1,007      1,189       1,250    1,441    1,631    1,924    2,059
    Pressure drop                                                            (3)            kPa 10,6           13,9       18,4       11,4       16,0        17,6     16,5     21,1     19,8     22,6
    REFRIGERANT CIRCUIT
    Compressors nr.                                                                          N°      2     2     2     2     2     2     2     2     2    2
    Number of capacity steps                                                                 N°      2     2     2     2     2     2     2     2     2    2
    No. Circuits                                                                             N°      1     1     1     1     1     1     1     1     1    1
    Regulation                                                                                    STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS
    Min. capacity step                                                                        %     50    50    50    50    50    50    50    50    50    50
    Refrigerant                                                                                   R454B R454B R454B R454B R454B R454B R454B R454B R454B R454B
    Refrigerant charge                                                                       kg    5,60  7,20  7,30  8,60  9,20  11,0  12,2  12,4  13,9  15,9
    Oil charge                                                                               kg    5,40  5,40  5,40  5,40  5,40  5,40  8,00  10,6  10,6  10,6
    Rc (ASHRAE)                                                              (4)         kg/kW     0,11  0,13  0,12  0,12  0,11  0,11  0,11  0,10  0,10  0,10
    FANS
    Quantity                                                                                 N°       4          4          4          6          6           2        2        2        2       3
    Air flow                                                                               m³/s     4,92       5,32       5,32       7,41       7,41       11,34    11,34    11,34    11,74    17,04
    Fans power input                                                                        kW      0,25       0,25       0,25       0,25       0,25        2,00     2,00     2,00     2,00     2,00
    NOISE LEVEL
    Sound Pressure                                                           (5)          dB(A)      52         52         52         53         54          56       56       56       57       58
    Sound power level in cooling                                           (6)(7)         dB(A)      84         84         84         85         86          88       88       88       89       90
    SIZE AND WEIGHT
    A                                                                        (8)            mm     1825       2395       2395       2395       2395         2825     2825     2825     3360     3980
    B                                                                        (8)            mm     1195       1195       1195       1195       1195         1195     1195     1195     1195     1195
    H                                                                        (8)            mm     1865       1865       1865       1865       1865         1980     1980     1980     1980     1980
    Operating weight                                                         (8)             kg     520        570        580        600        610          700      790      860      930     1060
   Notes:
   1 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   2 Values in compliance with EN14511
   3 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C; Plant (side) heat exchanger recovery water (in/out) 40,00°C/45,00°C.
   4 Rated in accordance with AHRI Standard 550/590 (2011 with addendum 1).
   5 Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   6 Sound power on the basis of measurements made in compliance with ISO 9614.
   7 Sound power level in cooling, outdoors.
   8 Unit in standard configuration/execution, without optional accessories.
   - Not available
     Certified data in EUROVENT
    NX-G06/K                                                                                    0702P
    Power supply                                                                       V/ph/Hz 400/3/50
    PERFORMANCE
    COOLING ONLY (GROSS VALUE)
    Cooling capacity                                                         (1)           kW 181,9
    Total power input                                                        (1)           kW 63,24
    EER                                                                      (1)        kW/kW 2,878
    ESEER                                                                    (1)        kW/kW
    COOLING ONLY (EN14511 VALUE)
    Cooling capacity                                                       (1)(2)          kW 181,6
    EER                                                                    (1)(2)       kW/kW 2,830
    ESEER                                                                  (1)(2)       kW/kW   -
    Cooling energy class                                                                        -
    COOLING WITH PARTIAL RECOVERY
    Cooling capacity                                                         (3)            kW 188,7
    Total power input                                                        (3)            kW 61,23
    Desuperheater heating capacity                                           (3)            kW 51,09
    EXCHANGERS
    HEAT EXCHANGER USER SIDE IN REFRIGERATION
    Water flow                                                               (1)             l/s 8,698
    Pressure drop                                                            (1)            kPa 45,9
    PARTIAL RECOVERY USER SIDE IN REFRIGERATION
    Water flow                                                               (3)             l/s 2,466
    Pressure drop                                                            (3)            kPa 21,8
    REFRIGERANT CIRCUIT
    Compressors nr.                                                                          N°      2
    Number of capacity steps                                                                 N°      2
    No. Circuits                                                                             N°      1
    Regulation                                                                                    STEPS
    Min. capacity step                                                                        %     50
    Refrigerant                                                                                   R454B
    Refrigerant charge                                                                       kg    16,0
    Oil charge                                                                               kg    10,6
    Rc (ASHRAE)                                                              (4)         kg/kW     0,09
    FANS
    Quantity                                                                                 N°   3
    Air flow                                                                               m³/s 17,04
    Fans power input                                                                        kW 2,00
    NOISE LEVEL
    Sound Pressure                                                           (5)          dB(A)      58
    Sound power level in cooling                                           (6)(7)         dB(A)      90
    SIZE AND WEIGHT
    A                                                                        (8)            mm     3980
    B                                                                        (8)            mm     1195
    H                                                                        (8)            mm     1980
    Operating weight                                                         (8)             kg    1080
   Notes:
   1 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   2 Values in compliance with EN14511
   3 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C; Plant (side) heat exchanger recovery water (in/out) 40,00°C/45,00°C.
   4 Rated in accordance with AHRI Standard 550/590 (2011 with addendum 1).
   5 Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   6 Sound power on the basis of measurements made in compliance with ISO 9614.
   7 Sound power level in cooling, outdoors.
   8 Unit in standard configuration/execution, without optional accessories.
   - Not available
     Certified data in EUROVENT
    NX-G06/LN-K                                                                                   0202P 0252P 0262P 0302P 0352P 0402P 0452P 0502P 0552P 0602P
    Power supply                                                                       V/ph/Hz    400/3+N/50 400/3+N/50 400/3+N/50 400/3+N/50   400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
    PERFORMANCE
    COOLING ONLY (GROSS VALUE)
    Cooling capacity                                                         (1)           kW 49,63           56,41      62,90      71,67       86,34    95,43    108,3    120,2    134,3    156,3
    Total power input                                                        (1)           kW 17,20           18,90      21,49      26,26       28,90    33,42    36,49    41,05    49,15    53,99
    EER                                                                      (1)        kW/kW 2,884           2,984      2,926      2,726       2,986    2,856    2,967    2,925    2,735    2,894
    ESEER                                                                    (1)        kW/kW
    COOLING ONLY (EN14511 VALUE)
    Cooling capacity                                                       (1)(2)          kW 49,50           56,30      62,80      71,50       86,10    95,20    108,0    119,9    133,9    156,0
    EER                                                                    (1)(2)       kW/kW 2,850           2,950      2,890      2,700       2,930    2,810    2,920    2,880    2,690    2,850
    ESEER                                                                  (1)(2)       kW/kW   -               -          -          -           -        -        -        -        -        -
    Cooling energy class                                                                        -               -          -          -           -        -        -        -        -        -
    COOLING WITH PARTIAL RECOVERY
    Cooling capacity                                                         (3)            kW 51,49          58,52      65,26      74,36       89,58    99,01    112,4    124,7    139,3    162,1
    Total power input                                                        (3)            kW 16,63          18,27      20,77      25,37       27,96    32,32    35,29    39,70    47,51    52,22
    Desuperheater heating capacity                                           (3)            kW 14,46          16,02      18,33      22,58       23,83    27,86    30,52    34,59    41,82    44,98
    EXCHANGERS
    HEAT EXCHANGER USER SIDE IN REFRIGERATION
    Water flow                                                               (1)             l/s 2,373        2,697      3,008      3,427       4,129    4,564    5,181    5,749    6,422    7,473
    Pressure drop                                                            (1)            kPa 33,1           30,6       31,1       28,9        51,5     43,7     45,9     43,7     45,2     43,9
    PARTIAL RECOVERY USER SIDE IN REFRIGERATION
    Water flow                                                               (3)             l/s 0,698        0,773      0,885      1,090       1,150    1,345    1,473    1,670    2,019    2,171
    Pressure drop                                                            (3)            kPa 11,2           13,7       17,9       13,4        14,9     20,4     17,2     22,2     21,8     25,2
    REFRIGERANT CIRCUIT
    Compressors nr.                                                                          N°      2     2     2     2     2     2     2     2     2    2
    Number of capacity steps                                                                 N°      2     2     2     2     2     2     2     2     2    2
    No. Circuits                                                                             N°      1     1     1     1     1     1     1     1     1    1
    Regulation                                                                                    STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS
    Min. capacity step                                                                        %     50    50    50    50    50    50    50    50    50    50
    Refrigerant                                                                                   R454B R454B R454B R454B R454B R454B R454B R454B R454B R454B
    Refrigerant charge                                                                       kg    6,10  7,50  7,60  8,30  9,80  10,9  12,6  13,6  13,8  15,0
    Oil charge                                                                               kg    5,40  5,40  5,40  5,40  5,40  5,40  8,00  10,6  10,6  10,6
    Rc (ASHRAE)                                                              (4)         kg/kW     0,12  0,13  0,12  0,12  0,11  0,12  0,12  0,11  0,10  0,10
    FANS
    Quantity                                                                                 N°       4          6          6          6           2        2        2        2        2       3
    Air flow                                                                               m³/s     4,47       5,49       5,49       5,49        8,24     8,24    10,21    10,21    10,21    13,35
    Fans power input                                                                        kW      0,25       0,16       0,16       0,16        1,10     1,10     1,15     1,15     1,15     1,20
    NOISE LEVEL
    Sound Pressure                                                           (5)          dB(A)      47         48         48         48          51       51       52       52       52       53
    Sound power level in cooling                                           (6)(7)         dB(A)      79         80         80         80          83       83       84       84       84       85
    SIZE AND WEIGHT
    A                                                                        (8)            mm     2395       2395       2395       2395         2825     2825     3360     3360     3360     3980
    B                                                                        (8)            mm     1195       1195       1195       1195         1195     1195     1195     1195     1195     1195
    H                                                                        (8)            mm     1865       1865       1865       1865         1980     1980     1980     1980     1980     1980
    Operating weight                                                         (8)             kg     570        600        600        610          730      750      920      990     1010     1110
   Notes:
   1 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   2 Values in compliance with EN14511
   3 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C; Plant (side) heat exchanger recovery water (in/out) 40,00°C/45,00°C.
   4 Rated in accordance with AHRI Standard 550/590 (2011 with addendum 1).
   5 Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   6 Sound power on the basis of measurements made in compliance with ISO 9614.
   7 Sound power level in cooling, outdoors.
   8 Unit in standard configuration/execution, without optional accessories.
   - Not available
     Certified data in EUROVENT
    NX-G06/LN-K                                                                                 0702P
    Power supply                                                                       V/ph/Hz 400/3/50
    PERFORMANCE
    COOLING ONLY (GROSS VALUE)
    Cooling capacity                                                         (1)           kW 172,2
    Total power input                                                        (1)           kW 65,29
    EER                                                                      (1)        kW/kW 2,637
    ESEER                                                                    (1)        kW/kW
    COOLING ONLY (EN14511 VALUE)
    Cooling capacity                                                       (1)(2)          kW 171,9
    EER                                                                    (1)(2)       kW/kW 2,600
    ESEER                                                                  (1)(2)       kW/kW   -
    Cooling energy class                                                                        -
    COOLING WITH PARTIAL RECOVERY
    Cooling capacity                                                         (3)            kW 178,7
    Total power input                                                        (3)            kW 63,13
    Desuperheater heating capacity                                           (3)            kW 55,06
    EXCHANGERS
    HEAT EXCHANGER USER SIDE IN REFRIGERATION
    Water flow                                                               (1)             l/s 8,237
    Pressure drop                                                            (1)            kPa 41,2
    PARTIAL RECOVERY USER SIDE IN REFRIGERATION
    Water flow                                                               (3)             l/s 2,658
    Pressure drop                                                            (3)            kPa 25,4
    REFRIGERANT CIRCUIT
    Compressors nr.                                                                          N°      2
    Number of capacity steps                                                                 N°      2
    No. Circuits                                                                             N°      1
    Regulation                                                                                    STEPS
    Min. capacity step                                                                        %     50
    Refrigerant                                                                                   R454B
    Refrigerant charge                                                                       kg    15,4
    Oil charge                                                                               kg    10,6
    Rc (ASHRAE)                                                              (4)         kg/kW     0,09
    FANS
    Quantity                                                                                 N°   3
    Air flow                                                                               m³/s 13,35
    Fans power input                                                                        kW 1,20
    NOISE LEVEL
    Sound Pressure                                                           (5)          dB(A)      53
    Sound power level in cooling                                           (6)(7)         dB(A)      85
    SIZE AND WEIGHT
    A                                                                        (8)            mm     3980
    B                                                                        (8)            mm     1195
    H                                                                        (8)            mm     1980
    Operating weight                                                         (8)             kg    1120
   Notes:
   1 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   2 Values in compliance with EN14511
   3 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C; Plant (side) heat exchanger recovery water (in/out) 40,00°C/45,00°C.
   4 Rated in accordance with AHRI Standard 550/590 (2011 with addendum 1).
   5 Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   6 Sound power on the basis of measurements made in compliance with ISO 9614.
   7 Sound power level in cooling, outdoors.
   8 Unit in standard configuration/execution, without optional accessories.
   - Not available
     Certified data in EUROVENT
    NX-G06/SL-K                                                                                   0202P 0252P 0262P 0302P 0352P 0402P 0452P 0502P 0552P 0602P
    Power supply                                                                       V/ph/Hz    400/3+N/50   400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
    PERFORMANCE
    COOLING ONLY (GROSS VALUE)
    Cooling capacity                                                         (1)           kW 50,18            56,53    63,24    74,64    84,96    96,00     108,9     119,4    134,9   146,9
    Total power input                                                        (1)           kW 16,89            18,86    21,28    25,45    28,35    32,57     36,52     41,57    48,74   57,31
    EER                                                                      (1)        kW/kW 2,970            2,989    2,967    2,925    3,004    2,945     2,984     2,870    2,770   2,564
    ESEER                                                                    (1)        kW/kW
    COOLING ONLY (EN14511 VALUE)
    Cooling capacity                                                       (1)(2)          kW 50,10            56,40    63,10    74,50    84,70    95,70     108,6     119,0    134,5   146,5
    EER                                                                    (1)(2)       kW/kW 2,930            2,960    2,930    2,900    2,940    2,900     2,930     2,830    2,720   2,530
    ESEER                                                                  (1)(2)       kW/kW   -                -        -        -        -        -         -         -        -       -
    Cooling energy class                                                                        -                -        -        -        -        -         -         -        -       -
    COOLING WITH PARTIAL RECOVERY
    Cooling capacity                                                         (3)            kW 52,07           58,65    65,61    77,44    88,14    99,60     113,0     123,8    139,9   152,4
    Total power input                                                        (3)            kW 16,33           18,25    20,59    24,61    27,41    31,49     35,32     40,19    47,12   55,39
    Desuperheater heating capacity                                           (3)            kW 14,22           15,50    17,66    21,38    23,89    27,67     30,59     35,10    41,09   48,74
    EXCHANGERS
    HEAT EXCHANGER USER SIDE IN REFRIGERATION
    Water flow                                                               (1)             l/s 2,400         2,703    3,024    3,569    4,063    4,591     5,207     5,708    6,449   7,023
    Pressure drop                                                            (1)            kPa 33,9            30,8     31,4     31,4     49,8     44,3      46,4      43,1     45,5    38,7
    PARTIAL RECOVERY USER SIDE IN REFRIGERATION
    Water flow                                                               (3)             l/s 0,686         0,748    0,852    1,032    1,153    1,335     1,477     1,694    1,984   2,353
    Pressure drop                                                            (3)            kPa 10,8            12,8     16,6     12,0     15,0     20,1      17,3      22,8     21,0    29,6
    REFRIGERANT CIRCUIT
    Compressors nr.                                                                          N°      2     2     2     2     2     2     2     2     2    2
    Number of capacity steps                                                                 N°      2     2     2     2     2     2     2     2     2    2
    No. Circuits                                                                             N°      1     1     1     1     1     1     1     1     1    1
    Regulation                                                                                    STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS
    Min. capacity step                                                                        %     50    50    50    50    50    50    50    50    50    50
    Refrigerant                                                                                   R454B R454B R454B R454B R454B R454B R454B R454B R454B R454B
    Refrigerant charge                                                                       kg    7,00  7,30  8,60  10,0  10,3  12,2  14,0  15,0  15,1  15,4
    Oil charge                                                                               kg    5,40  5,40  5,40  5,40  5,40  5,40  8,00  10,6  10,6  10,6
    Rc (ASHRAE)                                                              (4)         kg/kW     0,14  0,13  0,14  0,14  0,12  0,13  0,13  0,13  0,11  0,11
    FANS
    Quantity                                                                                 N°       6           2        2        2        2        2         3        3         3      3
    Air flow                                                                               m³/s     4,66        6,50     6,50     6,50     8,46     8,46      9,88     9,88     10,74   10,74
    Fans power input                                                                        kW      0,16        0,75     0,75     0,75     0,79     0,79      0,75     0,75      0,90    0,90
    NOISE LEVEL
    Sound Pressure                                                           (5)          dB(A)      45          46       46       46       47       48        49       49        50     50
    Sound power level in cooling                                           (6)(7)         dB(A)      77          78       78       78       79       80        81       81        82     82
    SIZE AND WEIGHT
    A                                                                        (8)            mm     2395         2825     2825     2825     3360     3360     3980      3980      3980   3980
    B                                                                        (8)            mm     1195         1195     1195     1195     1195     1195     1195      1195      1195   1195
    H                                                                        (8)            mm     1865         1980     1980     1980     1980     1980     1980      1980      1980   1980
    Operating weight                                                         (8)             kg     590          700      710      710      810      830      990      1060      1070   1110
   Notes:
   1 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   2 Values in compliance with EN14511
   3 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C; Plant (side) heat exchanger recovery water (in/out) 40,00°C/45,00°C.
   4 Rated in accordance with AHRI Standard 550/590 (2011 with addendum 1).
   5 Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   6 Sound power on the basis of measurements made in compliance with ISO 9614.
   7 Sound power level in cooling, outdoors.
   8 Unit in standard configuration/execution, without optional accessories.
   - Not available
     Certified data in EUROVENT
    NX-G06/CA                                                                                     0202P 0252P 0262P 0302P 0352P 0402P 0452P 0502P 0562P 0612P
    Power supply                                                                       V/ph/Hz    400/3+N/50 400/3+N/50 400/3+N/50   400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
    PERFORMANCE
    COOLING ONLY (GROSS VALUE)
    Cooling capacity                                                         (1)           kW 52,80           59,95      66,81       81,64    92,73    103,6    117,0    132,3    153,9    171,3
    Total power input                                                        (1)           kW 15,59           17,95      20,27       24,80    28,22    31,39    35,66    39,89    45,80    51,88
    EER                                                                      (1)        kW/kW 3,385           3,352      3,291       3,290    3,287    3,299    3,277    3,316    3,360    3,301
    ESEER                                                                    (1)        kW/kW
    COOLING ONLY (EN14511 VALUE)
    Cooling capacity                                                       (1)(2)          kW 52,70           59,80      66,70       81,40    92,40    103,3    116,8    132,0    153,6    171,0
    EER                                                                    (1)(2)       kW/kW 3,330           3,290      3,240       3,240    3,200    3,230    3,210    3,250    3,290    3,240
    ESEER                                                                  (1)(2)       kW/kW   -               -          -           -        -        -        -        -        -        -
    Cooling energy class                                                                        -               -          -           -        -        -        -        -        -        -
    COOLING WITH PARTIAL RECOVERY
    Cooling capacity                                                         (3)            kW 54,78          62,20      69,32       84,71    96,21    107,5    121,4    137,2    159,7    177,7
    Total power input                                                        (3)            kW 15,10          17,37      19,62       24,07    27,37    30,42    34,54    38,70    44,48    50,34
    Desuperheater heating capacity                                           (3)            kW 12,58          14,68      16,76       18,57    21,62    24,74    28,55    30,25    33,74    39,17
    EXCHANGERS
    HEAT EXCHANGER USER SIDE IN REFRIGERATION
    Water flow                                                               (1)             l/s 2,525        2,867      3,195       3,904    4,435    4,956    5,597    6,326    7,361    8,191
    Pressure drop                                                            (1)            kPa 37,5           34,6       35,1        37,5     59,4     51,6     53,6     52,9     59,3     52,7
    PARTIAL RECOVERY USER SIDE IN REFRIGERATION
    Water flow                                                               (3)             l/s 0,607        0,709      0,809       0,896    1,044    1,194    1,378    1,460    1,629    1,891
    Pressure drop                                                            (3)            kPa 8,44           11,5       15,0        9,07     12,3     16,1     15,1     16,9     14,2     19,1
    REFRIGERANT CIRCUIT
    Compressors nr.                                                                          N°      2     2     2     2     2     2     2     2     2    2
    Number of capacity steps                                                                 N°      2     2     2     2     2     2     2     2     2    2
    No. Circuits                                                                             N°      1     1     1     1     1     1     1     1     1    1
    Regulation                                                                                    STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS
    Min. capacity step                                                                        %     50    50    50    50    50    50    50    50    50    50
    Refrigerant                                                                                   R454B R454B R454B R454B R454B R454B R454B R454B R454B R454B
    Refrigerant charge                                                                       kg    7,30  7,90  8,00  9,30  12,4  12,5  12,9  17,5  19,8  20,3
    Oil charge                                                                               kg    5,40  5,40  5,40  5,40  5,40  5,40  8,00  10,6  10,6  10,6
    Rc (ASHRAE)                                                              (4)         kg/kW     0,14  0,13  0,12  0,12  0,14  0,12  0,11  0,13  0,13  0,12
    FANS
    Quantity                                                                                 N°       6          6          6           2        2        2        2        3        4       4
    Air flow                                                                               m³/s     7,41       7,41       7,41       11,34    11,74    12,53    12,53    17,04    22,68    22,68
    Fans power input                                                                        kW      0,25       0,25       0,25        2,00     2,00     1,84     1,84     2,00     2,00     2,00
    NOISE LEVEL
    Sound Pressure                                                           (5)          dB(A)      53         53         54          56       56       58       58       58       59       59
    Sound power level in cooling                                           (6)(7)         dB(A)      85         85         86          88       88       90       90       90       91       91
    SIZE AND WEIGHT
    A                                                                        (8)            mm     2395       2395       2395         2825     3360     3360     3360     3980     3160     3160
    B                                                                        (8)            mm     1195       1195       1195         1195     1195     1195     1195     1195     2250     2250
    H                                                                        (8)            mm     1865       1865       1865         1980     1980     1980     1980     1980     2170     2170
    Operating weight                                                         (8)             kg     580        590        600          710      780      830      920     1060     1460     1480
   Notes:
   1 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   2 Values in compliance with EN14511
   3 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C; Plant (side) heat exchanger recovery water (in/out) 40,00°C/45,00°C.
   4 Rated in accordance with AHRI Standard 550/590 (2011 with addendum 1).
   5 Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   6 Sound power on the basis of measurements made in compliance with ISO 9614.
   7 Sound power level in cooling, outdoors.
   8 Unit in standard configuration/execution, without optional accessories.
   - Not available
     Certified data in EUROVENT
    NX-G06/LN-CA                                                                                  0202P 0252P 0262P 0302P 0352P 0402P 0452P 0502P 0562P 0612P
    Power supply                                                                       V/ph/Hz    400/3+N/50   400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
    PERFORMANCE
    COOLING ONLY (GROSS VALUE)
    Cooling capacity                                                         (1)           kW 52,81            60,95    67,86    79,36    90,65    103,1     115,8     128,8    147,8   165,8
    Total power input                                                        (1)           kW 15,98            18,19    20,40    24,17    27,31    31,02     35,29     39,35    43,82   50,64
    EER                                                                      (1)        kW/kW 3,300            3,352    3,328    3,281    3,322    3,326     3,280     3,277    3,374   3,277
    ESEER                                                                    (1)        kW/kW
    COOLING ONLY (EN14511 VALUE)
    Cooling capacity                                                       (1)(2)          kW 52,70            60,80    67,70    79,20    90,30    102,8     115,4     128,5    147,5   165,5
    EER                                                                    (1)(2)       kW/kW 3,250            3,300    3,270    3,230    3,240    3,250     3,210     3,210    3,300   3,220
    ESEER                                                                  (1)(2)       kW/kW   -                -        -        -        -        -         -         -        -       -
    Cooling energy class                                                                        -                -        -        -        -        -         -         -        -       -
    COOLING WITH PARTIAL RECOVERY
    Cooling capacity                                                         (3)            kW 54,79           63,24    70,40    82,33    94,05    107,0     120,2     133,7    153,3   172,1
    Total power input                                                        (3)            kW 15,46           17,63    19,76    23,41    26,44    30,05     34,17     38,10    42,42   49,00
    Desuperheater heating capacity                                           (3)            kW 13,41           14,27    16,25    19,62    22,33    24,75     28,56     31,91    35,80   41,88
    EXCHANGERS
    HEAT EXCHANGER USER SIDE IN REFRIGERATION
    Water flow                                                               (1)             l/s 2,525         2,915    3,245    3,795    4,335    4,932     5,538     6,160    7,067   7,931
    Pressure drop                                                            (1)            kPa 37,5            35,8     36,2     35,5     56,8     51,1      52,5      50,2     54,7    49,4
    PARTIAL RECOVERY USER SIDE IN REFRIGERATION
    Water flow                                                               (3)             l/s 0,647         0,689    0,784    0,947    1,078    1,194     1,379     1,540    1,728   2,022
    Pressure drop                                                            (3)            kPa 9,60            10,9     14,1     10,1     13,1     16,1      15,1      18,8     15,9    21,8
    REFRIGERANT CIRCUIT
    Compressors nr.                                                                          N°      2     2     2     2     2     2     2     2     2    2
    Number of capacity steps                                                                 N°      2     2     2     2     2     2     2     2     2    2
    No. Circuits                                                                             N°      1     1     1     1     1     1     1     1     1    1
    Regulation                                                                                    STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS
    Min. capacity step                                                                        %     50    50    50    50    50    50    50    50    50    50
    Refrigerant                                                                                   R454B R454B R454B R454B R454B R454B R454B R454B R454B R454B
    Refrigerant charge                                                                       kg    7,20  8,00  10,3  10,4  11,3  13,1  13,1  14,1  23,6  23,7
    Oil charge                                                                               kg    5,40  5,40  5,40  5,40  5,40  5,40  8,00  10,6  10,6  10,6
    Rc (ASHRAE)                                                              (4)         kg/kW     0,14  0,13  0,15  0,13  0,13  0,13  0,11  0,11  0,16  0,14
    FANS
    Quantity                                                                                 N°       6           2        2        2        2        3         3         3        4      4
    Air flow                                                                               m³/s     5,49        8,24     8,24     8,70    10,21    12,35     12,35     13,35    16,85   16,85
    Fans power input                                                                        kW      0,16        1,10     1,10     1,10     1,15     1,10      1,10      1,20     0,93    0,93
    NOISE LEVEL
    Sound Pressure                                                           (5)          dB(A)      48          49       49       50       52       52        52       53        54     54
    Sound power level in cooling                                           (6)(7)         dB(A)      80          81       81       82       84       84        84       85        86     86
    SIZE AND WEIGHT
    A                                                                        (8)            mm     2395         2825     2825     3360     3360     3980     3980      3980      3160   3160
    B                                                                        (8)            mm     1195         1195     1195     1195     1195     1195     1195      1195      2250   2250
    H                                                                        (8)            mm     1865         1980     1980     1980     1980     1980     1980      1980      2170   2170
    Operating weight                                                         (8)             kg     590          700      710      780      820      920      990      1070      1460   1480
   Notes:
   1 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   2 Values in compliance with EN14511
   3 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C; Plant (side) heat exchanger recovery water (in/out) 40,00°C/45,00°C.
   4 Rated in accordance with AHRI Standard 550/590 (2011 with addendum 1).
   5 Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   6 Sound power on the basis of measurements made in compliance with ISO 9614.
   7 Sound power level in cooling, outdoors.
   8 Unit in standard configuration/execution, without optional accessories.
   - Not available
     Certified data in EUROVENT
    NX-G06/SL-CA                                                                                0202P 0252P 0262P 0302P 0352P 0412P 0462P 0512P 0562P 0612P
    Power supply                                                                       V/ph/Hz 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
    PERFORMANCE
    COOLING ONLY (GROSS VALUE)
    Cooling capacity                                                         (1)           kW 53,11         59,72     66,44     78,67     90,71    101,8     113,9     127,7    145,6   165,4
    Total power input                                                        (1)           kW 15,93         17,65     19,87     23,73     27,54    30,10     34,29     38,87    43,94   49,10
    EER                                                                      (1)        kW/kW 3,340         3,373     3,337     3,321     3,298    3,382     3,321     3,283    3,317   3,369
    ESEER                                                                    (1)        kW/kW
    COOLING ONLY (EN14511 VALUE)
    Cooling capacity                                                       (1)(2)          kW 53,00         59,60     66,30     78,50     90,40    101,5     113,5     127,4    145,3   165,1
    EER                                                                    (1)(2)       kW/kW 3,280         3,330     3,290     3,260     3,220    3,310     3,250     3,220    3,250   3,310
    ESEER                                                                  (1)(2)       kW/kW   -             -         -         -         -        -         -         -        -       -
    Cooling energy class                                                                        -             -         -         -         -        -         -         -        -       -
    COOLING WITH PARTIAL RECOVERY
    Cooling capacity                                                         (3)            kW 55,10        61,96     68,93     81,62     94,12    105,6     118,2     132,5    151,0   171,6
    Total power input                                                        (3)            kW 15,42        17,09     19,23     22,95     26,65    29,12     33,16     37,58    42,49   47,49
    Desuperheater heating capacity                                           (3)            kW 12,88        14,35     16,32     19,77     22,57    25,05     28,79     32,87    36,94   41,10
    EXCHANGERS
    HEAT EXCHANGER USER SIDE IN REFRIGERATION
    Water flow                                                               (1)             l/s 2,540      2,856     3,177     3,762     4,338    4,867     5,447     6,106    6,962   7,911
    Pressure drop                                                            (1)            kPa 38,0         34,4      34,7      34,9      56,8     49,7      50,8      49,3     53,1    49,1
    PARTIAL RECOVERY USER SIDE IN REFRIGERATION
    Water flow                                                               (3)             l/s 0,622      0,693     0,788     0,954     1,090    1,209     1,390     1,587    1,783   1,984
    Pressure drop                                                            (3)            kPa 8,85         11,0      14,2      10,3      13,4     16,5      15,3      20,0     17,0    21,0
    REFRIGERANT CIRCUIT
    Compressors nr.                                                                          N°      2     2     2     2     2     2     2     2     2    2
    Number of capacity steps                                                                 N°      2     2     2     2     2     2     2     2     2    2
    No. Circuits                                                                             N°      1     1     1     1     1     1     1     1     1    1
    Regulation                                                                                    STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS STEPS
    Min. capacity step                                                                        %     50    50    50    50    50    50    50    50    50    50
    Refrigerant                                                                                   R454B R454B R454B R454B R454B R454B R454B R454B R454B R454B
    Refrigerant charge                                                                       kg    7,70  9,00  9,70  9,80  11,7  14,2  14,9  17,4  21,6  23,5
    Oil charge                                                                               kg    5,40  5,40  5,40  5,40  5,40  5,40  8,00  10,6  10,6  10,6
    Rc (ASHRAE)                                                              (4)         kg/kW     0,15  0,15  0,15  0,13  0,13  0,14  0,13  0,14  0,15  0,14
    FANS
    Quantity                                                                                 N°      2         2         2         2        3         4         4         4        5      6
    Air flow                                                                               m³/s    6,50      8,46      8,46      8,46     9,88     12,20     12,20     12,20    15,25   18,30
    Fans power input                                                                        kW     0,75      0,79      0,79      0,79     0,75      0,51      0,51      0,51     0,51    0,51
    NOISE LEVEL
    Sound Pressure                                                           (5)          dB(A)      46       47        47        47       48        49        50       50        51     52
    Sound power level in cooling                                           (6)(7)         dB(A)      78       79        79        79       80        81        82       82        83     84
    SIZE AND WEIGHT
    A                                                                        (8)            mm     2825      3360     3360      3360      3980      3160     3160      3160      4335   4335
    B                                                                        (8)            mm     1195      1195     1195      1195      1195      2250     2250      2250      2250   2250
    H                                                                        (8)            mm     1980      1980     1980      1980      1980      2170     2170      2170      2170   2170
    Operating weight                                                         (8)             kg     700       790      800       810       890      1280     1370      1440      1690   1750
   Notes:
   1 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   2 Values in compliance with EN14511
   3 Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C; Plant (side) heat exchanger recovery water (in/out) 40,00°C/45,00°C.
   4 Rated in accordance with AHRI Standard 550/590 (2011 with addendum 1).
   5 Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   6 Sound power on the basis of measurements made in compliance with ISO 9614.
   7 Sound power level in cooling, outdoors.
   8 Unit in standard configuration/execution, without optional accessories.
   - Not available
     Certified data in EUROVENT
    NX-G06/K                                                        0202P     0252P     0262P    0302P   0352P   0402P   0452P   0502P   0552P   0602P
    Prated,c                                  (1)         kW         49,7      56,4      62,3     74,4    84,7    97,6   109,6   122,0   138,2   158,7
    SEER                                    (1) (2)        -         4,01      4,07      4,02     4,00    4,05    3,87    3,85    3,85    3,90    3,86
    Performance ηs                          (1) (3)        %        157,0     160,0     158,0    157,0   159,0   152,0   151,0   151,0   153,0   151,0
    NX-G06/K                                                        0702P
    Prated,c                                  (1)         kW        181,6
    SEER                                    (1) (2)        -         3,88
    Performance ηs                          (1) (3)        %        152,0
    NX-G06/LN-K                                                     0202P     0252P     0262P    0302P   0352P   0402P   0452P   0502P   0552P   0602P
    Prated,c                                  (1)         kW         49,5      56,3      62,8     71,5    86,1    95,2   108,0   119,9   133,9   156,0
    SEER                                    (1) (2)        -         4,01      4,06      4,07     3,98    3,88    3,88    3,94    3,96    3,99    3,93
    Performance ηs                          (1) (3)        %        157,0     159,0     160,0    156,0   152,0   152,0   155,0   155,0   157,0   154,0
    NX-G06/LN-K                                                     0702P
    Prated,c                                  (1)         kW        171,9
    SEER                                    (1) (2)        -         3,86
    Performance ηs                          (1) (3)        %        151,0
    NX-G06/SL-K                                                     0202P     0252P     0262P    0302P   0352P   0402P   0452P   0502P   0552P   0602P
    Prated,c                                  (1)         kW         50,1      56,4      63,1     74,5    84,7    95,7   108,6   119,0   134,5   146,5
    SEER                                    (1) (2)        -         4,06      3,89      3,89     3,96    3,97    4,00    4,00    3,94    3,94    3,86
    Performance ηs                          (1) (3)        %        160,0     153,0     152,0    155,0   156,0   157,0   157,0   155,0   155,0   151,0
    NX-G06/CA                                                       0202P     0252P     0262P    0302P   0352P   0402P   0452P   0502P   0562P   0612P
    Prated,c                                  (1)         kW         52,7      59,8      66,7     81,4    92,4   103,3   116,8   132,0   153,6   171,0
    SEER                                    (1) (2)        -         4,05      4,12      4,16     3,97    3,95    4,02    4,12    3,99    3,99    4,03
    Performance ηs                          (1) (3)        %        159,0     162,0     163,0    156,0   155,0   158,0   162,0   157,0   157,0   158,0
    NX-G06/CA                                                       0712P     0812P
    Prated,c                                  (1)         kW        192,8     217,6
    SEER                                    (1) (2)        -         4,12      3,94
    Performance ηs                          (1) (3)        %        162,0     155,0
    NX-G06/LN-CA                                                    0202P     0252P     0262P    0302P   0352P   0402P   0452P   0502P   0562P   0612P
    Prated,c                                  (1)         kW         52,7      60,8      67,7     79,2    90,3   102,8   115,4   128,5   147,5   165,5
    SEER                                    (1) (2)        -         4,12      3,89      3,92     3,99    4,03    3,91    4,00    4,00    4,27    4,17
    Performance ηs                          (1) (3)        %        162,0     153,0     154,0    156,0   158,0   153,0   157,0   157,0   168,0   164,0
    NX-G06/LN-CA                                                    0712P     0812P
    Prated,c                                  (1)         kW        190,1     212,0
    SEER                                    (1) (2)        -         4,36      4,14
    Performance ηs                          (1) (3)        %        171,0     162,0
    NX-G06/SL-CA                                                    0202P     0252P     0262P    0302P   0352P   0412P   0462P   0512P   0562P   0612P
    Prated,c                                  (1)         kW         53,0      59,6      66,3     78,5    90,4   101,5   113,5   127,4   145,3   165,1
    SEER                                    (1) (2)        -         3,99      3,99      4,05     4,20    4,06    4,16    4,22    4,25    4,30    4,30
    Performance ηs                          (1) (3)        %        157,0     157,0     159,0    165,0   159,0   163,0   166,0   167,0   169,0   169,0
    NX-G06/SL-CA                                                    0712P     0812P
    Prated,c                                  (1)         kW        186,7     208,5
    SEER                                    (1) (2)        -         4,41      4,21
    Performance ηs                          (1) (3)        %        173,0     165,0
    Notes:
    (1) Parameter calculated according to [REGULATION (EU) N. 2016/2281]
    (2) Seasonal energy efficiency ratio
    (3) Seasonal space cooling energy efficiency
    The units highlighted in this publication contain R454B [GWP100 466] fluorinated greenhouse gases.
    Certified data in EUROVENT
                             SIZE
        NX-G06 /K /0202P            NX-G06 /LN-CA /0712P
        NX-G06 /K /0252P            NX-G06 /LN-CA /0812P
        NX-G06 /K /0262P            NX-G06 /SL-CA /0202P
        NX-G06 /K /0302P            NX-G06 /SL-CA /0252P
        NX-G06 /K /0352P            NX-G06 /SL-CA /0262P
        NX-G06 /K /0402P            NX-G06 /SL-CA /0302P
        NX-G06 /K /0452P            NX-G06 /SL-CA /0352P
        NX-G06 /K /0502P            NX-G06 /SL-CA /0412P
        NX-G06 /K /0552P            NX-G06 /SL-CA /0462P
        NX-G06 /K /0602P            NX-G06 /SL-CA /0512P
        NX-G06 /K /0702P            NX-G06 /SL-CA /0562P
       NX-G06 /LN-K /0202P          NX-G06 /SL-CA /0612P
       NX-G06 /LN-K /0252P          NX-G06 /SL-CA /0712P
       NX-G06 /LN-K /0262P          NX-G06 /SL-CA /0812P
       NX-G06 /LN-K /0302P
       NX-G06 /LN-K /0352P
       NX-G06 /LN-K /0402P
       NX-G06 /LN-K /0452P
       NX-G06 /LN-K /0502P
       NX-G06 /LN-K /0552P
       NX-G06 /LN-K /0602P
       NX-G06 /LN-K /0702P
       NX-G06 /SL-K /0202P
       NX-G06 /SL-K /0252P
       NX-G06 /SL-K /0262P
       NX-G06 /SL-K /0302P
       NX-G06 /SL-K /0352P
       NX-G06 /SL-K /0402P
       NX-G06 /SL-K /0452P
       NX-G06 /SL-K /0502P
       NX-G06 /SL-K /0552P
       NX-G06 /SL-K /0602P
        NX-G06 /CA /0202P
        NX-G06 /CA /0252P
        NX-G06 /CA /0262P
        NX-G06 /CA /0302P
        NX-G06 /CA /0352P
        NX-G06 /CA /0402P
        NX-G06 /CA /0452P
        NX-G06 /CA /0502P
        NX-G06 /CA /0562P
        NX-G06 /CA /0612P
        NX-G06 /CA /0712P
        NX-G06 /CA /0812P
      NX-G06 /LN-CA /0202P
      NX-G06 /LN-CA /0252P
      NX-G06 /LN-CA /0262P
      NX-G06 /LN-CA /0302P
      NX-G06 /LN-CA /0352P
      NX-G06 /LN-CA /0402P
      NX-G06 /LN-CA /0452P
      NX-G06 /LN-CA /0502P
      NX-G06 /LN-CA /0562P
      NX-G06 /LN-CA /0612P
                               SIZE
       NX-G06 /D /K /0202P            NX-G06 /D /LN-CA /0712P
       NX-G06 /D /K /0252P            NX-G06 /D /LN-CA /0812P
       NX-G06 /D /K /0262P            NX-G06 /D /SL-CA /0202P
       NX-G06 /D /K /0302P            NX-G06 /D /SL-CA /0252P
       NX-G06 /D /K /0352P            NX-G06 /D /SL-CA /0262P
       NX-G06 /D /K /0402P            NX-G06 /D /SL-CA /0302P
       NX-G06 /D /K /0452P            NX-G06 /D /SL-CA /0352P
       NX-G06 /D /K /0502P            NX-G06 /D /SL-CA /0412P
       NX-G06 /D /K /0552P            NX-G06 /D /SL-CA /0462P
       NX-G06 /D /K /0602P            NX-G06 /D /SL-CA /0512P
       NX-G06 /D /K /0702P            NX-G06 /D /SL-CA /0562P
      NX-G06 /D /LN-K /0202P          NX-G06 /D /SL-CA /0612P
      NX-G06 /D /LN-K /0252P          NX-G06 /D /SL-CA /0712P
      NX-G06 /D /LN-K /0262P          NX-G06 /D /SL-CA /0812P
      NX-G06 /D /LN-K /0302P
      NX-G06 /D /LN-K /0352P
      NX-G06 /D /LN-K /0402P
      NX-G06 /D /LN-K /0452P
      NX-G06 /D /LN-K /0502P
      NX-G06 /D /LN-K /0552P
      NX-G06 /D /LN-K /0602P
      NX-G06 /D /LN-K /0702P
      NX-G06 /D /SL-K /0202P
      NX-G06 /D /SL-K /0252P
      NX-G06 /D /SL-K /0262P
      NX-G06 /D /SL-K /0302P
      NX-G06 /D /SL-K /0352P
      NX-G06 /D /SL-K /0402P
      NX-G06 /D /SL-K /0452P
      NX-G06 /D /SL-K /0502P
      NX-G06 /D /SL-K /0552P
      NX-G06 /D /SL-K /0602P
       NX-G06 /D /CA /0202P
       NX-G06 /D /CA /0252P
       NX-G06 /D /CA /0262P
       NX-G06 /D /CA /0302P
       NX-G06 /D /CA /0352P
       NX-G06 /D /CA /0402P
       NX-G06 /D /CA /0452P
       NX-G06 /D /CA /0502P
       NX-G06 /D /CA /0562P
       NX-G06 /D /CA /0612P
       NX-G06 /D /CA /0712P
       NX-G06 /D /CA /0812P
     NX-G06 /D /LN-CA /0202P
     NX-G06 /D /LN-CA /0252P
     NX-G06 /D /LN-CA /0262P
     NX-G06 /D /LN-CA /0302P
     NX-G06 /D /LN-CA /0352P
     NX-G06 /D /LN-CA /0402P
     NX-G06 /D /LN-CA /0452P
     NX-G06 /D /LN-CA /0502P
     NX-G06 /D /LN-CA /0562P
     NX-G06 /D /LN-CA /0612P
   cPf: cooling power correction factor                                       For data concerning other kind of anti-freeze solutions (e,g, propylene
   cQ: flow correction factor                                                 glycol) please contact our Sale Department.
   cdp: pressure drop correction factor
        NX-G06 /D /LN-K /0552P              400/3/50      84,5       4,083   10,86    9,40     401     412      -      2,694    0,92
        NX-G06 /D /LN-K /0602P              400/3/50      60,6       4,694   10,86    11,5     446     412      -      3,194    0,92
        NX-G06 /D /LN-K /0702P              400/3/50      46,8       5,389   11,94    13,6     503     277      -      3,722    1,22
          NX-G06 /SL-K /0202P             400/3+N/50      454        1,444   4,444    3,30     138      -       -        -       -
          NX-G06 /SL-K /0252P               400/3/50      325        1,639   4,833    3,60     156      -       -        -       -
          NX-G06 /SL-K /0262P               400/3/50      265        1,806   4,833    4,10     174      -       -        -       -
          NX-G06 /SL-K /0302P               400/3/50      190        2,167   4,833    5,00     213      -       -        -       -
          NX-G06 /SL-K /0352P               400/3/50      233        2,472   6,111    5,80     242      -       -        -       -
          NX-G06 /SL-K /0402P               400/3/50      162        2,861   8,667    6,60     270      -       -        -       -
          NX-G06 /SL-K /0452P               400/3/50      132        3,222   9,750    7,40     305      -       -        -       -
          NX-G06 /SL-K /0502P               400/3/50      102        3,611   10,86    8,50     345      -       -        -       -
          NX-G06 /SL-K /0552P               400/3/50      84,5       4,083   10,86    9,40     401      -       -        -       -
          NX-G06 /SL-K /0602P               400/3/50      60,6       4,694   10,86    11,5     446      -       -        -       -
        NX-G06 /D /SL-K /0202P            400/3+N/50      454        1,444   4,444    3,30     138     1767     -      0,972    0,43
        NX-G06 /D /SL-K /0252P              400/3/50      325        1,639   4,833    3,60     156     1767     -      1,056    0,43
        NX-G06 /D /SL-K /0262P              400/3/50      265        1,806   4,833    4,10     174     1767     -      1,194    0,43
        NX-G06 /D /SL-K /0302P              400/3/50      190        2,167   4,833    5,00     213     871      -      1,444    0,61
        NX-G06 /D /SL-K /0352P              400/3/50      233        2,472   6,111    5,80     242     871      -      1,583    0,61
        NX-G06 /D /SL-K /0402P              400/3/50      162        2,861   8,667    6,60     270     871      -      1,833    0,61
        NX-G06 /D /SL-K /0452P              400/3/50      132        3,222   9,750    7,40     305     613      -      2,028    0,73
        NX-G06 /D /SL-K /0502P              400/3/50      102        3,611   10,86    8,50     345     613      -      2,306    0,73
        NX-G06 /D /SL-K /0552P              400/3/50      84,5       4,083   10,86    9,40     401     412      -      2,694    0,92
        NX-G06 /D /SL-K /0602P              400/3/50      60,6       4,694   10,86    11,5     446     412      -      3,194    0,92
           NX-G06 /CA /0202P              400/3+N/50      454        1,444   4,444    3,30     138      -       -        -       -
           NX-G06 /CA /0252P              400/3+N/50      325        1,639   4,833    3,60     156      -       -        -       -
           NX-G06 /CA /0262P              400/3+N/50      265        1,806   4,833    4,10     174      -       -        -       -
           NX-G06 /CA /0302P                400/3/50      190        2,167   4,833    5,00     213      -       -        -       -
           NX-G06 /CA /0352P                400/3/50      233        2,472   6,111    5,80     242      -       -        -       -
           NX-G06 /CA /0402P                400/3/50      162        2,861   8,667    6,60     270      -       -        -       -
           NX-G06 /CA /0452P                400/3/50      132        3,222   9,750    7,40     305      -       -        -       -
           NX-G06 /CA /0502P                400/3/50      102        3,611   10,86    8,50     345      -       -        -       -
           NX-G06 /CA /0562P                400/3/50      84,5       4,083   10,86    9,40     401      -       -        -       -
           NX-G06 /CA /0612P                400/3/50      60,6       4,694   10,86    11,5     446      -       -        -       -
           NX-G06 /CA /0712P                400/3/50      46,8       5,389   11,94    13,6     503      -       -        -       -
           NX-G06 /CA /0812P                400/3/50      46,8       5,861   11,94    13,6     568      -       -        -       -
         NX-G06 /D /CA /0202P             400/3+N/50      454        1,444   4,444    3,30     138     1767     -      0,972    0,43
         NX-G06 /D /CA /0252P             400/3+N/50      325        1,639   4,833    3,60     156     1767     -      1,056    0,43
         NX-G06 /D /CA /0262P             400/3+N/50      265        1,806   4,833    4,10     174     1767     -      1,194    0,43
         NX-G06 /D /CA /0302P               400/3/50      190        2,167   4,833    5,00     213     871      -      1,444    0,61
         NX-G06 /D /CA /0352P               400/3/50      233        2,472   6,111    5,80     242     871      -      1,583    0,61
         NX-G06 /D /CA /0402P               400/3/50      162        2,861   8,667    6,60     270     871      -      1,833    0,61
         NX-G06 /D /CA /0452P               400/3/50      132        3,222   9,750    7,40     305     613      -      2,028    0,73
         NX-G06 /D /CA /0502P               400/3/50      102        3,611   10,86    8,50     345     613      -      2,306    0,73
         NX-G06 /D /CA /0562P               400/3/50      84,5       4,083   10,86    9,40     401     412      -      2,694    0,92
         NX-G06 /D /CA /0612P               400/3/50      60,6       4,694   10,86    11,5     446     412      -      3,194    0,92
         NX-G06 /D /CA /0712P               400/3/50      46,8       5,389   11,94    13,6     503     277      -      3,722    1,22
         NX-G06 /D /CA /0812P               400/3/50      46,8       5,861   11,94    13,6     568     277      -      4,361    1,22
         NX-G06 /LN-CA /0202P             400/3+N/50      454        1,444   4,444    3,30     138      -       -        -       -
         NX-G06 /LN-CA /0252P               400/3/50      325        1,639   4,833    3,60     156      -       -        -       -
                                                                                                             Maximum values
                                 Power
                                                                         Compressor                                                    Fans (1)                           Total (1)(2)
             SIZE                supply
                                 V/ph/Hz                    F.L.I.             F.L.A.                   L.R.A.                F.L.I.              F.L.A.         F.L.I.      F.L.A.         S.A.
                                               n            [kW]                [A]                       [A]                 [kW]                 [A]           [kW]         [A]           [A]
            0202P             400/3+N/50 2                2 x 10.5            2 x 16.6                2 x 123                0,250                  1            22,00          38          144
            0252P             400/3+N/50 2                2 x 11.5            2 x 18.3                2 x 138                0,250                  1            24,00          41          161
            0262P             400/3+N/50 2                2 x 13.1            2 x 20.8                2 x 145                0,250                  1            27,20          46          170
            0302P             400/3+N/50 2                2 x 15.4            2 x 24.9                2 x 172                0,250                  1            32,20          56          204
            0352P             400/3+N/50 2           1x15.4 + 1x21.4     1x24.9 + 1x34.2          1x172 + 1x211              0,250                  1            38,30          66          243
            0402P               400/3/50       2          2 x 21.4            2 x 34.2                2 x 211                2,000                  4            46,80          76          253
            0452P               400/3/50       2      1x21.4 + 1x27      1x34.2 + 1x42.5          1x211 + 1x210              2,000                  4            52,40          85          253
            0502P               400/3/50       2            2 x 27            2 x 42.5                2 x 210                2,000                  4            58,00          93          260
            0552P               400/3/50       2      1x27 + 1x34.5      1x42.5 + 1x55.1          1x210 + 1x326              2,000                  4            65,50         105          376
            0602P               400/3/50       2          2 x 34.5            2 x 55.1                2 x 326                2,000                  4            75,00         122          393
            0702P               400/3/50       2          2 x 37.8            2 x 62.3                2 x 326                2,000                  4            81,60         136          400
   (1) Values calculated referring to the version with the maximum number of fans working at the max absorbed current
   (1)(2) Safety values to be considered when cabling the unit for power supply and line-protections
Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Give the typical operating conditions of units designed for outdoor installation, which can be associated (according to reference document IEC 60721) to the following classes:
   - climatic conditions class 4K4H: air temperature range from -20 up to 55°C (*), relative humidity range from 4 up to 100%, with possible precipitations, at air pressure from 70 and 106 kPa and
   a maximum solar radiation of 1120 W/m2
   - special climatic conditions negligible
   - biological conditions class 4B1 and 4C2: locations in a generic urban area
   - mechanically active substances class 4S2: locations in areas with sand or dust representative of urban areas
   - mechanical conditions class 4M1: locations protected from significant vibrations or shocks
   The required protection level for safe operation, according to reference document IEC 60529, is IP43XW (protection against access, to the most critical unit's parts, of external devices with
   diameter larger than 1 mm and rain).
   The unit can be considered IP44XW protected, i.e. protected against access of external devices (with diameter larger than 1 mm) and water in general.
(*) for the unit’s operating limits, see “selection limits” section
                                                                                                             Maximum values
                                 Power
                                                                         Compressor                                                    Fans (1)                           Total (1)(2)
             SIZE                supply
                                 V/ph/Hz                    F.L.I.             F.L.A.                   L.R.A.                F.L.I.              F.L.A.         F.L.I.      F.L.A.         S.A.
                                               n            [kW]                [A]                       [A]                 [kW]                 [A]           [kW]         [A]           [A]
            0202P             400/3+N/50 2                2 x 10.5            2 x 16.6                2 x 123                0,250                  1            22,00          38          144
            0252P             400/3+N/50 2                2 x 11.5            2 x 18.3                2 x 138                0,160                  1            23,90          41          160
            0262P             400/3+N/50 2                2 x 13.1            2 x 20.8                2 x 145                0,160                  1            27,10          45          170
            0302P             400/3+N/50 2                2 x 15.4            2 x 24.9                2 x 172                0,160                  1            31,70          54          201
            0352P               400/3/50       2     1x15.4 + 1x21.4     1x24.9 + 1x34.2          1x172 + 1x211              2,000                  4            40,80          67          244
            0402P               400/3/50       2          2 x 21.4            2 x 34.2                2 x 211                2,000                  4            46,80          76          253
            0452P               400/3/50       2      1x21.4 + 1x27      1x34.2 + 1x42.5          1x211 + 1x210              1,840                  4            52,10          84          253
            0502P               400/3/50       2            2 x 27            2 x 42.5                2 x 210                1,840                  4            57,70          93          260
            0552P               400/3/50       2      1x27 + 1x34.5      1x42.5 + 1x55.1          1x210 + 1x326              1,840                  4            65,20         105          376
            0602P               400/3/50       2          2 x 34.5            2 x 55.1                2 x 326                2,000                  4            75,00         122          393
            0702P               400/3/50       2          2 x 37.8            2 x 62.3                2 x 326                2,000                  4            81,60         136          400
   (1) Values calculated referring to the version with the maximum number of fans working at the max absorbed current
   (1)(2) Safety values to be considered when cabling the unit for power supply and line-protections
Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Give the typical operating conditions of units designed for outdoor installation, which can be associated (according to reference document IEC 60721) to the following classes:
   - climatic conditions class 4K4H: air temperature range from -20 up to 55°C (*), relative humidity range from 4 up to 100%, with possible precipitations, at air pressure from 70 and 106 kPa and
   a maximum solar radiation of 1120 W/m2
   - special climatic conditions negligible
   - biological conditions class 4B1 and 4C2: locations in a generic urban area
   - mechanically active substances class 4S2: locations in areas with sand or dust representative of urban areas
   - mechanical conditions class 4M1: locations protected from significant vibrations or shocks
   The required protection level for safe operation, according to reference document IEC 60529, is IP43XW (protection against access, to the most critical unit's parts, of external devices with
   diameter larger than 1 mm and rain).
   The unit can be considered IP44XW protected, i.e. protected against access of external devices (with diameter larger than 1 mm) and water in general.
(*) for the unit’s operating limits, see “selection limits” section
                                                                                                             Maximum values
                                 Power
                                                                         Compressor                                                    Fans (1)                           Total (1)(2)
             SIZE                supply
                                 V/ph/Hz                    F.L.I.             F.L.A.                   L.R.A.                F.L.I.              F.L.A.         F.L.I.      F.L.A.         S.A.
                                               n            [kW]                [A]                       [A]                 [kW]                 [A]           [kW]         [A]           [A]
            0202P             400/3+N/50 2                2 x 10.5            2 x 16.6                2 x 123                0,160                  1            22,00          37          143
            0252P               400/3/50       2          2 x 11.5            2 x 18.3                2 x 138                1,200                  4            25,40          44          164
            0262P               400/3/50       2          2 x 13.1            2 x 20.8                2 x 145                1,200                  4            28,60          49          174
            0302P               400/3/50       2          2 x 15.4            2 x 24.9                2 x 172                1,200                  4            33,10          58          205
            0352P               400/3/50       2     1x15.4 + 1x21.4     1x24.9 + 1x34.2          1x172 + 1x211              1,150                  2            39,10          64          240
            0402P               400/3/50       2          2 x 21.4            2 x 34.2                2 x 211                1,150                  2            45,10          73          250
            0452P               400/3/50       2      1x21.4 + 1x27      1x34.2 + 1x42.5          1x211 + 1x210              1,200                  4            50,80          85          253
            0502P               400/3/50       2            2 x 27            2 x 42.5                2 x 210                1,200                  4            57,60          97          264
            0552P               400/3/50       2      1x27 + 1x34.5      1x42.5 + 1x55.1          1x210 + 1x326              1,200                  4            65,10         109          380
            0602P               400/3/50       2          2 x 34.5            2 x 55.1                2 x 326                1,200                  4            72,60         122          393
   (1) Values calculated referring to the version with the maximum number of fans working at the max absorbed current
   (1)(2) Safety values to be considered when cabling the unit for power supply and line-protections
Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Give the typical operating conditions of units designed for outdoor installation, which can be associated (according to reference document IEC 60721) to the following classes:
   - climatic conditions class 4K4H: air temperature range from -20 up to 55°C (*), relative humidity range from 4 up to 100%, with possible precipitations, at air pressure from 70 and 106 kPa and
   a maximum solar radiation of 1120 W/m2
   - special climatic conditions negligible
   - biological conditions class 4B1 and 4C2: locations in a generic urban area
   - mechanically active substances class 4S2: locations in areas with sand or dust representative of urban areas
   - mechanical conditions class 4M1: locations protected from significant vibrations or shocks
   The required protection level for safe operation, according to reference document IEC 60529, is IP43XW (protection against access, to the most critical unit's parts, of external devices with
   diameter larger than 1 mm and rain).
   The unit can be considered IP44XW protected, i.e. protected against access of external devices (with diameter larger than 1 mm) and water in general.
(*) for the unit’s operating limits, see “selection limits” section
                                                                                                             Maximum values
                                 Power
                                                                         Compressor                                                    Fans (1)                           Total (1)(2)
             SIZE                supply
                                 V/ph/Hz                    F.L.I.             F.L.A.                   L.R.A.                F.L.I.              F.L.A.         F.L.I.      F.L.A.         S.A.
                                               n            [kW]                [A]                       [A]                 [kW]                 [A]           [kW]         [A]           [A]
            0202P             400/3+N/50 2                2 x 10.5            2 x 16.6                2 x 123                0,250                  1            22,50          40          146
            0252P             400/3+N/50 2                2 x 11.5            2 x 18.3                2 x 138                0,250                  1            24,50          43          163
            0262P             400/3+N/50 2                2 x 13.1            2 x 20.8                2 x 145                0,250                  1            27,70          48          172
            0302P               400/3/50       2          2 x 15.4            2 x 24.9                2 x 172                2,000                  4            34,70          58          205
            0352P               400/3/50       2     1x15.4 + 1x21.4     1x24.9 + 1x34.2          1x172 + 1x211              2,000                  4            40,80          67          244
            0402P               400/3/50       2          2 x 21.4            2 x 34.2                2 x 211                1,840                  4            46,50          76          253
            0452P               400/3/50       2      1x21.4 + 1x27      1x34.2 + 1x42.5          1x211 + 1x210              1,840                  4            52,10          84          253
            0502P               400/3/50       2            2 x 27            2 x 42.5                2 x 210                2,000                  4            60,00          97          264
            0562P               400/3/50       2      1x27 + 1x34.5      1x42.5 + 1x55.1          1x210 + 1x326              2,000                  4            69,50         114          385
            0612P               400/3/50       2          2 x 34.5            2 x 55.1                2 x 326                2,000                  4            77,00         127          398
            0712P               400/3/50       2          2 x 37.8            2 x 62.3                2 x 326                2,000                  4            84,50         140          398
            0812P               400/3/50       2            2 x 42            2 x 68.4                2 x 298                2,000                  4            94,00         157          387
   (1) Values calculated referring to the version with the maximum number of fans working at the max absorbed current
   (1)(2) Safety values to be considered when cabling the unit for power supply and line-protections
Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Give the typical operating conditions of units designed for outdoor installation, which can be associated (according to reference document IEC 60721) to the following classes:
   - climatic conditions class 4K4H: air temperature range from -20 up to 55°C (*), relative humidity range from 4 up to 100%, with possible precipitations, at air pressure from 70 and 106 kPa and
   a maximum solar radiation of 1120 W/m2
   - special climatic conditions negligible
   - biological conditions class 4B1 and 4C2: locations in a generic urban area
   - mechanically active substances class 4S2: locations in areas with sand or dust representative of urban areas
   - mechanical conditions class 4M1: locations protected from significant vibrations or shocks
   The required protection level for safe operation, according to reference document IEC 60529, is IP43XW (protection against access, to the most critical unit's parts, of external devices with
   diameter larger than 1 mm and rain).
   The unit can be considered IP44XW protected, i.e. protected against access of external devices (with diameter larger than 1 mm) and water in general.
(*) for the unit’s operating limits, see “selection limits” section
                                                                                                             Maximum values
                                 Power
                                                                         Compressor                                                    Fans (1)                           Total (1)(2)
             SIZE                supply
                                 V/ph/Hz                    F.L.I.             F.L.A.                   L.R.A.                F.L.I.              F.L.A.         F.L.I.      F.L.A.         S.A.
                                               n            [kW]                [A]                       [A]                 [kW]                 [A]           [kW]         [A]           [A]
            0202P             400/3+N/50 2                2 x 10.5            2 x 16.6                2 x 123                0,160                  1            22,00          37          143
            0252P               400/3/50       2          2 x 11.5            2 x 18.3                2 x 138                2,000                  4            27,00          44          164
            0262P               400/3/50       2          2 x 13.1            2 x 20.8                2 x 145                2,000                  4            30,20          49          174
            0302P               400/3/50       2          2 x 15.4            2 x 24.9                2 x 172                2,000                  4            34,70          58          205
            0352P               400/3/50       2     1x15.4 + 1x21.4     1x24.9 + 1x34.2          1x172 + 1x211              1,840                  4            40,40          67          243
            0402P               400/3/50       2          2 x 21.4            2 x 34.2                2 x 211                2,000                  4            48,80          80          257
            0452P               400/3/50       2      1x21.4 + 1x27      1x34.2 + 1x42.5          1x211 + 1x210              2,000                  4            52,40          85          253
            0502P               400/3/50       2            2 x 27            2 x 42.5                2 x 210                2,000                  4            60,00          97          264
            0562P               400/3/50       2      1x27 + 1x34.5      1x42.5 + 1x55.1          1x210 + 1x326              0,930                  2            65,20         107          378
            0612P               400/3/50       2          2 x 34.5            2 x 55.1                2 x 326                0,930                  2            72,70         119          390
            0712P               400/3/50       2          2 x 37.8            2 x 62.3                2 x 326                0,930                  2            81,20         135          393
            0812P               400/3/50       2            2 x 42            2 x 68.4                2 x 298                0,930                  2            89,60         151          380
   (1) Values calculated referring to the version with the maximum number of fans working at the max absorbed current
   (1)(2) Safety values to be considered when cabling the unit for power supply and line-protections
Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Give the typical operating conditions of units designed for outdoor installation, which can be associated (according to reference document IEC 60721) to the following classes:
   - climatic conditions class 4K4H: air temperature range from -20 up to 55°C (*), relative humidity range from 4 up to 100%, with possible precipitations, at air pressure from 70 and 106 kPa and
   a maximum solar radiation of 1120 W/m2
   - special climatic conditions negligible
   - biological conditions class 4B1 and 4C2: locations in a generic urban area
   - mechanically active substances class 4S2: locations in areas with sand or dust representative of urban areas
   - mechanical conditions class 4M1: locations protected from significant vibrations or shocks
   The required protection level for safe operation, according to reference document IEC 60529, is IP43XW (protection against access, to the most critical unit's parts, of external devices with
   diameter larger than 1 mm and rain).
   The unit can be considered IP44XW protected, i.e. protected against access of external devices (with diameter larger than 1 mm) and water in general.
(*) for the unit’s operating limits, see “selection limits” section
                                                                                                             Maximum values
                                 Power
                                                                         Compressor                                                    Fans (1)                           Total (1)(2)
             SIZE                supply
                                 V/ph/Hz                    F.L.I.             F.L.A.                   L.R.A.                F.L.I.              F.L.A.         F.L.I.      F.L.A.         S.A.
                                               n            [kW]                [A]                       [A]                 [kW]                 [A]           [kW]         [A]           [A]
            0202P               400/3/50       2          2 x 10.5            2 x 16.6                2 x 123                1,200                  4            23,40          41          147
            0252P               400/3/50       2          2 x 11.5            2 x 18.3                2 x 138                1,150                  2            25,30          41          161
            0262P               400/3/50       2          2 x 13.1            2 x 20.8                2 x 145                1,150                  2            28,50          46          170
            0302P               400/3/50       2          2 x 15.4            2 x 24.9                2 x 172                1,150                  2            33,00          54          201
            0352P               400/3/50       2     1x15.4 + 1x21.4     1x24.9 + 1x34.2          1x172 + 1x211              1,200                  4            40,40          71          248
            0412P               400/3/50       2          2 x 21.4            2 x 34.2                2 x 211                0,930                  2            46,50          78          254
            0462P               400/3/50       2      1x21.4 + 1x27      1x34.2 + 1x42.5          1x211 + 1x210              0,930                  2            52,10          86          254
            0512P               400/3/50       2            2 x 27            2 x 42.5                2 x 210                0,930                  2            57,70          94          262
            0562P               400/3/50       2      1x27 + 1x34.5      1x42.5 + 1x55.1          1x210 + 1x326              0,930                  2            66,20         109          380
            0612P               400/3/50       2          2 x 34.5            2 x 55.1                2 x 326                0,930                  2            74,60         124          395
            0712P               400/3/50       2          2 x 37.8            2 x 62.3                2 x 326                0,930                  2            82,10         137          395
            0812P               400/3/50       2            2 x 42            2 x 68.4                2 x 298                0,930                  2            90,50         153          383
   (1) Values calculated referring to the version with the maximum number of fans working at the max absorbed current
   (1)(2) Safety values to be considered when cabling the unit for power supply and line-protections
Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Give the typical operating conditions of units designed for outdoor installation, which can be associated (according to reference document IEC 60721) to the following classes:
   - climatic conditions class 4K4H: air temperature range from -20 up to 55°C (*), relative humidity range from 4 up to 100%, with possible precipitations, at air pressure from 70 and 106 kPa and
   a maximum solar radiation of 1120 W/m2
   - special climatic conditions negligible
   - biological conditions class 4B1 and 4C2: locations in a generic urban area
   - mechanically active substances class 4S2: locations in areas with sand or dust representative of urban areas
   - mechanical conditions class 4M1: locations protected from significant vibrations or shocks
   The required protection level for safe operation, according to reference document IEC 60529, is IP43XW (protection against access, to the most critical unit's parts, of external devices with
   diameter larger than 1 mm and rain).
   The unit can be considered IP44XW protected, i.e. protected against access of external devices (with diameter larger than 1 mm) and water in general.
(*) for the unit’s operating limits, see “selection limits” section
   Working conditions
   Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Sound power on the basis of measurements made in compliance with ISO 9614.
   Such certification refers specifically to the sound Power Level in dB(A). This is therefore the only acoustic data to be considered as binding.
   Sound power level in cooling, outdoors.
   Working conditions
   Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   Working conditions
   Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Sound power on the basis of measurements made in compliance with ISO 9614.
   Such certification refers specifically to the sound Power Level in dB(A). This is therefore the only acoustic data to be considered as binding.
   Sound power level in cooling, outdoors.
   Working conditions
   Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   Working conditions
   Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Sound power on the basis of measurements made in compliance with ISO 9614.
   Such certification refers specifically to the sound Power Level in dB(A). This is therefore the only acoustic data to be considered as binding.
   Sound power level in cooling, outdoors.
   Working conditions
   Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   Working conditions
   Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Sound power on the basis of measurements made in compliance with ISO 9614.
   Such certification refers specifically to the sound Power Level in dB(A). This is therefore the only acoustic data to be considered as binding.
   Sound power level in cooling, outdoors.
   Working conditions
   Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   Working conditions
   Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Sound power on the basis of measurements made in compliance with ISO 9614.
   Such certification refers specifically to the sound Power Level in dB(A). This is therefore the only acoustic data to be considered as binding.
   Sound power level in cooling, outdoors.
   Working conditions
   Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
   Working conditions
   Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Sound power on the basis of measurements made in compliance with ISO 9614.
   Such certification refers specifically to the sound Power Level in dB(A). This is therefore the only acoustic data to be considered as binding.
   Sound power level in cooling, outdoors.
   Working conditions
   Plant (side) cooling exchanger water (in/out) 12,00°C/7,00°C; Source (side) heat exchanger air (in) 35,0°C.
   Average sound pressure level at 10m distance, unit in a free field on a reflective surface; non-binding value calculated from the sound power level.
11.1.1
                                                                                                                                                                                                                                                                                                          NX-G06 0202P - 0812P
R454B
   DIMENSIONAL DRAWINGS                                 NX-G06 0202P - 0812P
   [ SI System ]
11.1.5
                                                                                                                                                                                                                                                                                                          NX-G06 0202P - 0812P
R454B
   DIMENSIONAL DRAWINGS                               NX-G06 0202P - 0812P
   [ SI System ]
                                                                                                      PIPE                                     PIPE
                                                                                    NOMINAL                               NOMINAL
                                                                                                    OUTSIDE                                  OUTSIDE
                                                                                    PIPE SIZE                             PIPE SIZE
                                                                                                   DIAMETER                                 DIAMETER
                                                                                    ø inches          ø mm                 ø inches             ø mm
                                                                                       ¾               26,7                    4                114,3
                                                                                       1               33,7                   4½                127,0
                                                                                      1¼               42,4                    5                139,7
                                                                                      1½               48,3                    6                168,3
                                                                                       2               60,3                    8                219,1
 TYPE = B                               TYPE = F
                                                                                      2½               76,1                    10               273,0
 Male threaded pipe                     Grooved coupling with male
                                        threaded counter-pipe user side                3               88,9                    12               323,9
                                                                                      3½               101,6                   14               355,6
 UNI EN 10226-1
 Pipe threads where pressure-tight joints are made on the threads - Designation, dimensions and tolerances
 Used terminology:
 Rp: Internal cylindrical threads where pressure-tight joints are made on the threads
 Rc: Internal conical threads where pressure-tight joints are made on the threads
 R: External conical threads where pressure-tight joints are made on the threads
 Internal cylindrical threads: R letter followed by p letter
 Internal conical threads: R letter followed by c letter
 External conical threads: R letter
  DESIGNATION                      DESCRIPTION
                                   Internal cylindrical threads where pressure-tight joints are made on the threads, defined by standard UNI ISO 7/1
  UNI EN 10226-1 - Rp 1 1/2
                                   Conventional ø 1 1/2”
                                   Internal cylindrical threads where pressure-tight joints are made on the threads, defined by standard UNI ISO 7/1
  UNI EN 10226-1 - Rp 2 1/2
                                   Conventional ø 2 1/2”
                                   Internal cylindrical threads where pressure-tight joints are made on the threads, defined by standard UNI ISO 7/1
  UNI EN 10226-1 - Rp 3
                                   Conventional ø 3”
                                   External conical threads where pressure-tight joints are made on the threads, defined by standard UNI ISO 7/1
  UNI EN 10226-1 - R 3
                                   Conventional ø 3”
                                   Internal cylindrical threads where pressure-tight joints are not made on the threads, defined by standard
                                   UNI ISO 228/1
  UNI ISO 228/1 - G 4 B
                                   Tolerance class B for external thread
                                   Conventional ø 4”
                                   Flange Nominal Diameter: 80 mm
  DN 80 PN 16
                                   Nominal Pressure: 16 bar
 NOTE:
 Conventional diameter value [in inches] identifies short thread designation, based upon the relative standard.
 All relative values are defined by standards.
 As example, here below some values:
                                    ACCUMULATION
                          Version      Capacity
                                          [l]
           0402P          LN-CA         250
           0412P          SL-CA         500
                            CA
                                        200
                           LN-K
           0452P            K           140
                          LN-CA
                                        250
                           SL-K
           0462P          SL-CA         500
                            CA
                          LN-CA         250
           0502P           SL-K
                            K           140
                           LN-K         200
           0512P          SL-CA         500
                            K
                                        200
           0552P           LN-K
                           SL-K         250
                            CA
           0562P          LN-CA         500
                          SL-CA
                            K
           0602P           LN-K         250
                           SL-K
                            CA
           0612P          LN-CA         500
                          SL-CA
                            K
           0702P                        250
                           LN-K
                            CA
           0712P          LN-CA         500
                          SL-CA
                            CA
           0812P          LN-CA         500
                          SL-CA
                      HYDRONIC KIT 1 PUMP 2 POLES HYDRONIC KIT 1 PUMP 2 POLES                  HYDRONIC KIT 2 PUMPS 2           HYDRONIC KIT 2 PUMPS 2
                           LH + TANK (3152)            HH + TANK (3153)                        POLES LH + TANK (3155)           POLES HH + TANK (3156)
             Version extra L extra W extra H   extra   extra L extra W extra H      extra   extra L extra W extra H   extra   extra L extra W extra H   extra
                      [mm]    [mm]    [mm]     WGT      [mm]    [mm]    [mm]        WGT      [mm]    [mm]    [mm]     WGT      [mm]    [mm]    [mm]     WGT
                                                [kg]                                 [kg]                              [kg]                              [kg]
                CA        /     /        /      320        /        /        /        320      /       /       /      320        /       /       /       320
                K         /     /        /      250        /        /        /        250      /       /       /      250        /       /       /       250
              LN-CA       /     /        /      310        /        /        /        310      /       /       /      310        /       /       /       310
    0202P
               LN-K       /     /        /      320        /        /        /        320      /       /       /      320        /       /       /       320
              SL-CA       /     /        /      210        /        /        /        210      /       /       /      210        /       /       /       210
               SL-K       /     /        /      310        /        /        /        310      /       /       /      310        /       /       /       310
                CA        /     /        /      320        /        /        /        320      /       /       /      320        /       /       /       320
                K         /     /        /      320        /        /        /        320      /       /       /      320        /       /       /       320
              LN-CA       /     /        /      330        /        /        /        330      /       /       /      330        /       /       /       330
    0252P
               LN-K       /     /        /      310        /        /        /        310      /       /       /      310        /       /       /       310
              SL-CA       /     /        /      410        /        /        /        410      /       /       /      410        /       /       /       410
               SL-K       /     /        /      320        /        /        /        320      /       /       /      320        /       /       /       320
                CA        /     /        /      310        /        /        /        310      /       /       /      310        /       /       /       310
                K         /     /        /      310        /        /        /        310      /       /       /      310        /       /       /       310
              LN-CA       /     /        /      320        /        /        /        320      /       /       /      320        /       /       /       320
    0262P
               LN-K       /     /        /      320        /        /        /        320      /       /       /      320        /       /       /       320
              SL-CA       /     /        /      410        /        /        /        410      /       /       /      410        /       /       /       410
               SL-K       /     /        /      320        /        /        /        320      /       /       /      320        /       /       /       320
                CA        /     /        /      320        /        /        /        320      /       /       /      320        /       /       /       320
                K         /     /        /      320        /        /        /        320      /       /       /      320        /       /       /       320
              LN-CA       /     /        /      410        /        /        /        410      /       /       /      410        /       /       /       410
    0302P
               LN-K       /     /        /      320        /        /        /        320      /       /       /      320        /       /       /       320
              SL-CA       /     /        /      400        /        /        /        400      /       /       /      400        /       /       /       400
               SL-K       /     /        /      330        /        /        /        330      /       /       /      330        /       /       /       330
                CA        /     /        /      480        /        /        /        480      /       /       /      480        /       /       /       480
                K         /     /        /      380        /        /        /        380      /       /       /      380        /       /       /       380
              LN-CA       /     /        /      480        /        /        /        480      /       /       /      480        /       /       /       480
    0352P
               LN-K       /     /        /      380        /        /        /        380      /       /       /      380        /       /       /       380
              SL-CA       /     /        /      560        /        /        /        560      /       /       /      560        /       /       /       560
               SL-K       /     /        /      480        /        /        /        480      /       /       /      480        /       /       /       480
                CA        /     /        /      480        /        /        /        480      /       /       /      480        /       /       /       480
                K         /     /        /      390        /        /        /        390      /       /       /      390        /       /       /       390
    0402P     LN-CA       /     /        /      550        /        /        /        550      /       /       /      550        /       /       /       550
               LN-K       /     /        /      390        /        /        /        390      /       /       /      390        /       /       /       390
               SL-K       /     /        /      480        /        /        /        480      /       /       /      480        /       /       /       480
    0412P     SL-CA       /     /        /      860        /        /        /        860      /       /       /      860        /       /       /       860
                CA        /     /        /      480        /        /        /        480      /       /       /      480        /       /       /       480
                K         /     /        /      390        /        /        /        390      /       /       /      390        /       /       /       390
    0452P
              LN-CA       /     /        /      560        /        /        /        560      /       /       /      560        /       /       /       560
               LN-K       /     /        /      480        /        /        /        480      /       /       /      480        /       /       /       480
                      HYDRONIC KIT 1 PUMP 2 POLES HYDRONIC KIT 1 PUMP 2 POLES                  HYDRONIC KIT 2 PUMPS 2           HYDRONIC KIT 2 PUMPS 2
                           LH + TANK (3152)            HH + TANK (3153)                        POLES LH + TANK (3155)           POLES HH + TANK (3156)
             Version extra L extra W extra H   extra   extra L extra W extra H      extra   extra L extra W extra H   extra   extra L extra W extra H   extra
                      [mm]    [mm]    [mm]     WGT      [mm]    [mm]    [mm]        WGT      [mm]    [mm]    [mm]     WGT      [mm]    [mm]    [mm]     WGT
                                                [kg]                                 [kg]                              [kg]                              [kg]
    0452P      SL-K       /     /        /      560        /        /        /        560      /       /       /      560        /       /       /       560
    0462P     SL-CA       /     /        /      850        /        /        /        850      /       /       /      850        /       /       /       850
                CA        /     /        /      560        /        /        /        560      /       /       /      560        /       /       /       560
                K         /     /        /      390        /        /        /        390      /       /       /      390        /       /       /       390
    0502P     LN-CA       /     /        /      550        /        /        /        550      /       /       /      550        /       /       /       550
               LN-K       /     /        /      480        /        /        /        480      /       /       /      480        /       /       /       480
               SL-K       /     /        /      560        /        /        /        560      /       /       /      560        /       /       /       560
    0512P     SL-CA       /     /        /      860        /        /        /        860      /       /       /      860        /       /       /       860
                K         /     /        /      480        /        /        /        480      /       /       /      480        /       /       /       480
    0552P      LN-K       /     /        /      470        /        /        /        470      /       /       /      470        /       /       /       470
               SL-K       /     /        /      550        /        /        /        550      /       /       /      550        /       /       /       550
                CA        /     /        /      860        /        /        /        860      /       /       /      860        /       /       /       860
    0562P     LN-CA       /     /        /      860        /        /        /        860      /       /       /      860        /       /       /       860
              SL-CA       /     /        /      860        /        /        /        860      /       /       /      860        /       /       /       860
                K         /     /        /      550        /        /        /        550      /       /       /      550        /       /       /       550
    0602P      LN-K       /     /        /      550        /        /        /        550      /       /       /      550        /       /       /       550
               SL-K       /     /        /      550        /        /        /        550      /       /       /      550        /       /       /       550
                CA        /     /        /      860        /        /        /        860      /       /       /      860        /       /       /       860
    0612P     LN-CA       /     /        /      860        /        /        /        860      /       /       /      860        /       /       /       860
              SL-CA       /     /        /      860        /        /        /        860      /       /       /      860        /       /       /       860
                K         /     /        /      560        /        /        /        560      /       /       /      560        /       /       /       560
    0702P
               LN-K       /     /        /      570        /        /        /        570      /       /       /      570        /       /       /       570
                CA        /     /        /      910        /        /        /        910      /       /       /      910        /       /       /       910
    0712P     LN-CA       /     /        /      910        /        /        /        910      /       /       /      910        /       /       /       910
              SL-CA       /     /        /      910        /        /        /        910      /       /       /      910        /       /       /       910
                CA        /     /        /      910        /        /        /        910      /       /       /      910        /       /       /       910
    0812P     LN-CA       /     /        /      910        /        /        /        910      /       /       /      910        /       /       /       910
              SL-CA       /     /        /      910        /        /        /        910      /       /       /      910        /       /       /       910
                      HYDRONIC KIT 1 PUMP 2 POLES HYDRONIC KIT 1 PUMP 2 POLES                  HYDRONIC KIT 2 PUMPS 2           HYDRONIC KIT 2 PUMPS 2
                               LH (3164)                   HH (3165)                              POLES LH (3167)                  POLES HH (3168)
             Version extra L extra W extra H   extra   extra L extra W extra H      extra   extra L extra W extra H   extra   extra L extra W extra H   extra
                      [mm]    [mm]    [mm]     WGT      [mm]    [mm]    [mm]        WGT      [mm]    [mm]    [mm]     WGT      [mm]    [mm]    [mm]     WGT
                                                [kg]                                 [kg]                              [kg]                              [kg]
                CA        /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
                K         /     /        /      110        /        /        /        110      /       /       /      110        /       /       /       110
              LN-CA       /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
    0202P
               LN-K       /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
              SL-CA       /     /        /      110        /        /        /        110      /       /       /      110        /       /       /       110
               SL-K       /     /        /      110        /        /        /        110      /       /       /      110        /       /       /       110
                CA        /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
                K         /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
              LN-CA       /     /        /      130        /        /        /        130      /       /       /      130        /       /       /       130
    0252P
               LN-K       /     /        /      110        /        /        /        110      /       /       /      110        /       /       /       110
              SL-CA       /     /        /      130        /        /        /        130      /       /       /      130        /       /       /       130
               SL-K       /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
                CA        /     /        /      110        /        /        /        110      /       /       /      110        /       /       /       110
                K         /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
              LN-CA       /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
    0262P
               LN-K       /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
              SL-CA       /     /        /      130        /        /        /        130      /       /       /      130        /       /       /       130
               SL-K       /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
                CA        /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
                K         /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
              LN-CA       /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
    0302P
               LN-K       /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
              SL-CA       /     /        /      120        /        /        /        120      /       /       /      120        /       /       /       120
               SL-K       /     /        /      130        /        /        /        130      /       /       /      130        /       /       /       130
                CA        /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
                K         /     /        /      180        /        /        /        180      /       /       /      180        /       /       /       180
              LN-CA       /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
    0352P
               LN-K       /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
              SL-CA       /     /        /      210        /        /        /        210      /       /       /      210        /       /       /       210
               SL-K       /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
                CA        /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
                K         /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
    0402P     LN-CA       /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
               LN-K       /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
               SL-K       /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
    0412P     SL-CA       /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
                CA        /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
                K         /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
    0452P
              LN-CA       /     /        /      210        /        /        /        210      /       /       /      210        /       /       /       210
               LN-K       /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
                      HYDRONIC KIT 1 PUMP 2 POLES HYDRONIC KIT 1 PUMP 2 POLES                  HYDRONIC KIT 2 PUMPS 2           HYDRONIC KIT 2 PUMPS 2
                               LH (3164)                   HH (3165)                              POLES LH (3167)                  POLES HH (3168)
             Version extra L extra W extra H   extra   extra L extra W extra H      extra   extra L extra W extra H   extra   extra L extra W extra H   extra
                      [mm]    [mm]    [mm]     WGT      [mm]    [mm]    [mm]        WGT      [mm]    [mm]    [mm]     WGT      [mm]    [mm]    [mm]     WGT
                                                [kg]                                 [kg]                              [kg]                              [kg]
    0452P      SL-K       /     /        /      210        /        /        /        210      /       /       /      210        /       /       /       210
    0462P     SL-CA       /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
                CA        /     /        /      210        /        /        /        210      /       /       /      210        /       /       /       210
                K         /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
    0502P     LN-CA       /     /        /      210        /        /        /        210      /       /       /      210        /       /       /       210
               LN-K       /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
               SL-K       /     /        /      210        /        /        /        210      /       /       /      210        /       /       /       210
    0512P     SL-CA       /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
                K         /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
    0552P      LN-K       /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
               SL-K       /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
                CA        /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
    0562P     LN-CA       /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
              SL-CA       /     /        /      170        /        /        /        170      /       /       /      170        /       /       /       170
                K         /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
    0602P      LN-K       /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
               SL-K       /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
                CA        /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
    0612P     LN-CA       /     /        /      200        /        /        /        200      /       /       /      200        /       /       /       200
              SL-CA       /     /        /      190        /        /        /        190      /       /       /      190        /       /       /       190
                K         /     /        /      220        /        /        /        220      /       /       /      220        /       /       /       220
    0702P
               LN-K       /     /        /      220        /        /        /        220      /       /       /      220        /       /       /       220
                CA        /     /        /      240        /        /        /        240      /       /       /      240        /       /       /       240
    0712P     LN-CA       /     /        /      240        /        /        /        240      /       /       /      240        /       /       /       240
              SL-CA       /     /        /      240        /        /        /        240      /       /       /      240        /       /       /       240
                CA        /     /        /      250        /        /        /        250      /       /       /      250        /       /       /       250
    0812P     LN-CA       /     /        /      240        /        /        /        240      /       /       /      240        /       /       /       240
              SL-CA       /     /        /      240        /        /        /        240      /       /       /      240        /       /       /       240
   (1)   Values refer to nominal conditions                                Q      Plant (side) exchanger water flow
   CH    Cooling mode                                                      F.L.I. Pump power input
   Pf    Cooling capacity unit (Cooling mode)                              F.L.A. Pump running current
   Pt    Heating capacity unit (Heating mode)                              HU Pump residual pressure head (Units with hydronic group without mains filter)
   (1)   Values refer to nominal conditions                                Q      Plant (side) exchanger water flow
   CH    Cooling mode                                                      F.L.I. Pump power input
   Pf    Cooling capacity unit (Cooling mode)                              F.L.A. Pump running current
   Pt    Heating capacity unit (Heating mode)                              HU Pump residual pressure head (Units with hydronic group without mains filter)
   (1)   Values refer to nominal conditions                                Q      Plant (side) exchanger water flow
   CH    Cooling mode                                                      F.L.I. Pump power input
   Pf    Cooling capacity unit (Cooling mode)                              F.L.A. Pump running current
   Pt    Heating capacity unit (Heating mode)                              HU Pump residual pressure head (Units with hydronic group without mains filter)
   (1)   Values refer to nominal conditions                                Q      Plant (side) exchanger water flow
   CH    Cooling mode                                                      F.L.I. Pump power input
   Pf    Cooling capacity unit (Cooling mode)                              F.L.A. Pump running current
   Pt    Heating capacity unit (Heating mode)                              HU Pump residual pressure head (Units with hydronic group without mains filter)
   (1)   Values refer to nominal conditions                                Q      Plant (side) exchanger water flow
   CH    Cooling mode                                                      F.L.I. Pump power input
   Pf    Cooling capacity unit (Cooling mode)                              F.L.A. Pump running current
   Pt    Heating capacity unit (Heating mode)                              HU Pump residual pressure head (Units with hydronic group without mains filter)
   (1)   Values refer to nominal conditions                                Q      Plant (side) exchanger water flow
   CH    Cooling mode                                                      F.L.I. Pump power input
   Pf    Cooling capacity unit (Cooling mode)                              F.L.A. Pump running current
   Pt    Heating capacity unit (Heating mode)                              HU Pump residual pressure head (Units with hydronic group without mains filter)
   (1)   Values refer to nominal conditions                                Q      Plant (side) exchanger water flow
   CH    Cooling mode                                                      F.L.I. Pump power input
   Pf    Cooling capacity unit (Cooling mode)                              F.L.A. Pump running current
   Pt    Heating capacity unit (Heating mode)                              HU Pump residual pressure head (Units with hydronic group without mains filter)
   (1)   Values refer to nominal conditions                                Q      Plant (side) exchanger water flow
   CH    Cooling mode                                                      F.L.I. Pump power input
   Pf    Cooling capacity unit (Cooling mode)                              F.L.A. Pump running current
   Pt    Heating capacity unit (Heating mode)                              HU Pump residual pressure head (Units with hydronic group without mains filter)