0 ratings0% found this document useful (0 votes) 110 views11 pages61267660
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content,
claim it here.
Available Formats
Download as PDF or read online on Scribd
Carrier |
Arete den Be
pflow Gas-
INTRODUCTION
S8GA.GC_Upflow GasFired Furnaces are
AG.A, certified for installation on combustible
flooring in alcoves, basements, closets or utility
rooms. See 1 and Table 1 for furnace
physical data, See Table 2 for
Furnaces may be matched with certain 28
Series cooling coils to form combination heating/
cooling systems (sec Table 3) and employed with
humidifiers and electronic air cleaners to form
complete controtled-environment systems
These units are tested and approved for use
with natural gas. Approved kits are available for
converting S8GA units so that they can be fired
with liquified petroleum (LP) gases.
Furnaces are shipped fully assembled. S8GA
heating/cooling models are equipped with a printed
circuit center which provides a central control
connection point for furnace components and
field-added accessories. All internal electric and gas
controls are factory assembled and wired.
When unpacking unit, should any in-transit
damage be observed, file claim with transportation
agency
This publication covers fumace installation. It
also shows terminal connections used for wiring
accessories to furnace For accessory installation
details, refer to applicable installation literature.
INSTALLATION
Location Selection
When selecting a location for the furnace,
observe the following’
L. Install furnace close to chimney and as cen-
tralized as possible with respect to distribution
system
2. Locate cooling coil (if used) downstream from.
Furnace.
3. Ensure adequate door clearance for service
4, Ensure adequate ventilation, (See Combustion
Air.)
5. Follow local and national utility codes.
a. Allow AG.A. certified safety clearance of 1
in. from sides, top, and type B vent; 6 in
from unlisted vent; 0 in. at rear
b. Provide service clearance of 30 in. at front
of unit,
c. Insert vibration isolating material (cork or
rubber) under furnace to make seal, To slip
© O camer
ired Furnaces
O
S SOA) CC
ar,
“7
material underneath furnace, tip it first on
one side and then on the other, Make a
positive seal on alll four sides
d. Consult ANS Z21,30, Installation of Gas
Appliances and Gas Piping
Installation Procedures
Install ductwork, filters and vents; complete
external piping and wiring; and provide for come
bustion end recirculating air
DUCTWORK RECOMMENDATIONS
1. Install locking-type dampers in all branch or
individual duets to balance out system,
ol.
spre ak
Sree.
Foun
ENN,
(Fed Foner
If ovaw oven
a —— + fie
(ners,
ae
Fou xo
eee.
Sie
Seance
3 anon
notes:
T Allow AGA safety elaarance of 1 in trom sides, top,
‘yf vont, Gin from aniisted vont, Oia at Fear
2 Corte etmension drawings mvatahie‘on ues.
Fig. 1 — Dimensions
Form S8GA,GC-1StIGA,GC FURNACE
SERIES
DIMENSIONS (i)
100
Cosing Only
Height
‘Nish Plenum
Supply Air Opening
Return AirOpening
Me
ae
4
FILTER* Mounting Side
Size 126% (in) 1e%
AGA. RATINGS!
Input (1000 Brh)
Table 1 — Dimensions and Physical Data
80 1
| 200.
100 | 25
a0 | 200 | oo | 100 {200 G64.
|
m a
Max ESP (in)
BURNERS No
7 leo 566A ans 8906 vedo
59 = Era Ste esse
Dera parmenent ori tte
| Ratings shown for elevations wp to 2000
Hidect #8 of inp capacity fr
BLOWER,
'58G¢ Mortels Only BGA Models Only
[Ar toma ran may be calculates sing the following fork
28° Tae aprciicwt of sn x GD eI i
Foy levatons bows 2000 cay » BONNE eapocity
10 saves eve TO x chm
Table 2 — Blower Data
586A, GC DIRECT DRIVE
FURNACE - 080" zip 100
SERIES 100 [200 ys 20 00
Hp c as % 4 4%
ESP (in. wal 73] wi | 50! 30 | 50 x0 | 0 3 2 | %
piacere ea) v2a0 [175 80.950 | 1750 [1980
__tnon co) _ eae
BLOWER - - 586A BELT DRIVE =a
FURNAce 56 io 5 {se | _
SERIES ido {300 | i) 300" | 18D 300
MOTOR |
Nom Size (in) | 12% x6, 609% fom :
He ke EB w] LK % | % %
Pep tes Jae Psp] ae] sa fae fs pose | cas
aL i a7 » | 7 | ® a B B v
BuPs: 1 4 oe eo) leas 9a) eileues 2 3
ESP (in. wa)* | 20| sa] 20 [ So af | 6] | % ®) 6] BH HW] 9 [w] s6
pene [pe P3000 725190 240i poesia oon] vars 00 l2000 "9550 [aio fren ‘i
}986C Oweet Drive Models Only
BL = Bolt Lenath
BMPS — Bion Noto Putiey Soting fu
es ternal Statie Pesaro
PPD = Pulley igen Diameter (Fonge 2 1
SEEET 5G Dicct Drive Mudols Only
Fite in pace
[Win dice drive motor sot at “High” spond
{Bo no cpa tower motor pulley yar! ein shown
NOTE? Het a Application Bota itearure for fan performance saves
rrnsopen trom cloud austin)
=29in)Use tapered fittings or starter collars between
ducts and plenum,
3. Use exible duct connection (asbestos cloth)
between furnace and discharge plenum
Install acoustical insulation in warm air plenum,
install sound traps in short run ducts
5. Run return air connections under floor or run
full size return from space outside enclosed
area. Use one or both sides of furnace for
conneetions. Jf outdoor air is used, combina-
tion of outdoor and rerum air requires duct
design and diverting dampers so installed that
volune of circulating air entering furnace
cannot be reduced or restricted helow that
which would normally enter thru circulating air
intake of furnace
Table 3 — Furnace-Coil-Plenum Combinations
com PLENUM
FURNACE |
Medel | Series
Séca,ecoso | 100 |
saccos | 200 |
seoaoao | 200,300
38GA,6C100 | 100,200
S8Ga,cci00 | 300
58GA,GC125 | 100,200
Zen€.AFOO2
ane,arooe | 29Ae700021
S8GAi25 | 300 28AE,AFOOS,
pak AFOO4 |
58GA150 | 100,300 | 28A€,AF005 | 28AE900031
S58GA175, 10,300 BAE,AFOOS |
FILTERS Filters are shipped from factory in
blower compartment of furnace (See Fig 2) To
gain access, remove bottom front panel. Filters are
factory mounted for either side or bottom return
(ee Table 1), If the particular application calls for
mounting the filter in a position other than that
indicated, the filter can be cut according to the
measurements specified in Table 4 Filter bracket
can be relocated to secure filter when it is
repositioned.
1 To install side-mounted filter, cut return air
opening in furnace side as shown in Fig. | and
‘Table |. Position filter and secure in place with
filter bracket provided. (See Fig. 2.)
2. To install botton-mounted filter, remove tray
at bottom of blower compartment (see Fig. 2)
Position filter and secure in place with filter
bracket provided
If an accessory return air duct is used, follow
procedures outlined in the installation instruc-
ions for that accessory
VENTS -- Vent fumace to permanent chimney or
thru roof with vent of approved design. (Type B
vent is recommended.) Observe local ordinances.
6 BOTTOM TAB FOR
Setar won
8 oA
a
Fig. 2 — Installing Filter
Table 4 — Field-Cutting Factory-Supplied Filters
For Other Than Factory-Specified Mounting
Factory. | ‘
suppLied | MOUNTING
FILTER (in.)) Side | Bottom
FURNACE
Model 38 | Series
| 080 100 ~ | han 26%
| “060 |00. 300
| te | oe
Ihe lie
on 3 | | fora
125 300
175,200 100,300 | 25%4.26%
050 | 200 |
Gc | 100 100,200 LiStx26%
} ro | 300” eee
1
ize flue pipe connections same as furnace
vent connection. (See Fig. 1 and Table 1)2. Run pipe as directly as possible with minimum,
number of turns.
3. Maintain minimum piteh of 1/4 in, per linear
fon horizontal runs, Pitch should not exceed
75%h of vertical vent
4 Maintain minimum angle of 60 degrees from
vertical for vent pipe crossovers in attic,
Rigidly support pipe with hangers or straps
6. Do not connect into a chimney serving an
open firepla
If chimney is used, total equivalent straight
Iength of flue piping between fumace and flue
pipe connection at chimney must not be
greater than 75% of vertical height of chimney
above flue pipe connection
8 Install flue pipe to extend thru chimney wall
but not beyond inside wall of Flue.
9 Minimum vertical stack height is $ ft Extend
flue pipe at Ieast 3 ft above roof and 2 ft above
any object within a 15-ft radius. Ensure that
vent outlet terminates in an approved cap with,
a venting capacity not less than that of the
vent (See Table | for vent sizes.)
10 Insulate flue pipe where it passes near com
bustible material. Undenwriter'’s Laboratories
(UL) require that uninsulated flue pipe be
installed with a minimum clearance of 6 in
from combustible materials Vent piping which
meets_with National Board of Fire Under
writer's Specifications for type B vents, may
be installed with a clearance of I in. from
combustible materials
If other gas appliances are vented into common
flue, flue area must equal largest vent area plus
one-half total areas of other vent connectors
GAS PIPING ~ Install piping per national and local
codes, and ANS 221.30.
1, Furnish gas line from main gas supply to
furnace
Size supply pipe per volumne of gas used and
allowable pressure drop. (See Table 5 ) Supply
pipe size must at least equal that of furnace gas
connection.
3. Install drop pipe adjacent to, but not in front
of furnace
4, Install manual shutoff valve on gas piping per
local codes,
5. Install tee for drip leg in pipe at same elevation
as gas inlet connection to unit, provide ground
joint union between tee and furnace controls.
6. Extend drip leg and cap it
7 Test for pressure and leaks.
CAUTION: Never use open lame for leak testing.
Table 5 — Pipe Sizing”, Capacity For Natural Gas,
Cu Ft/Hr
pine size | PIPE LENGTH UD)
(in) | 10 | 20,! 30 | 40 | 50 | 0 | 70] 80
% | 2/97] 73] 3 | 56) so] 46]
2 | 2m) 90 | se 2G) 8) 2/8
A 5B | 380 | 28 23 | 18 | 8 078
Ix |b] | 80 [to | 245 |e | |e,
"Based on pressure drop of 0 in wg; 0 6 5p F 5
Without elaowe
WIRING ~ Fig. 3 shows the printed circuit control
center, which is factory-installed on S8GA
hneating/cooling furnaces. Fig. 4 illustrates the field
power and control wiring for 58GA.GC heating
only furnaces; Fig, 5 illustrates the field power and
control wiring for the S8GA_ heating/cooling
models; Fig. 6 illustrates. the field power and
control wirng for the S8GC heating/cooling
models
as
BeceSSSaY
wel
Fig, 3 — 58GA Printed Circuit Control Center,
Cover Removed
When wiring units, make sure that all national
and local codes are followed. Check against loo
wiring connections,
When msking aluminum conductor comnections
to copper conductors or terminals, use only con-
neetors which are UL approved (marked A1/Cu
with the UL symbol) for the application. (UL
approved connectors will be tin. plated, have
separator bars for placement between conductors
to prevent direct contact between aluminum and
copper, and have large bearing surfaces to minimize
pressures for minimum cold flowing of the alu-
minum and subsequent loosening of the joint.)
After insulation has been stripped from
aluminum conductor, coat conductor end with
corrosion inhibitor (Burdy “Penetrox A” or
equivalent), and wire brush aluminum surface thru
inhibitorCAUTION: Do not wire brush connectors and
iugs. Tin plating will be broken.
After cleaning, recoat aluminum conductor
with inhibitor, and make up connection, (Coat
entire connection.) If applicable, wrap connection
for moisture and/or electrical protection
cas, eee
valve PILOT.
Buk
But amet
¥ SoMBINATION
‘0 THERMOSTAT | SOMBINATION FAN
2 switen
BLK Bux.
[__ispneron sox | eux
\ guage
: t |
wet
eK
OIRECT ORIVE MOTOR = BELT DRIVE MOTOR
LEGEND
— Factory Power Wiring (118 Volt)
Fiske Control Wiring (24 Voit)
tory Conteot Wiring (24 Volt)
@ wire
notes
1 To change direct drive motor speed, move Mac ead to desire
terminal on motor Factory spied selection is Tor sveran®
conditions For optimum speed selection, refer to Blower Speed
Adjustment
2. Whenever replacing origina wie supplied with faronor use AWN
{80.0} wire or equivalent
3 Motor furnished with overload protection
44 Total electrical load sts tha 12 amps
Fig, 4 — 58GA,GC Field Power and Control Wiring,
Heating Only Diagram
Field Power Wiring ~ (See Fig 4 thru Fig. 6.)
58GA,GC Heating Only and S8GC Heating/Cooling
Models
L. Connect separate 115-volt, single-phase, 60-Hz
power supply thru hole in side of unit casing to
115-olt pigtails
2. If required by local codes, install fuse and
manual switch between main box and fumace.
S8GA Heating/Cooling Models and S8GA200100
Model
1, Connect separate 115-volt, single-phase, 60-Hz
power supply to terminals Ly and L on the
printed circuit control center. (See Fig. 3.)
If required by local codes, install fuse and
manual switch between main box and fumace.
3. When adding an clectronie air cleaner to the
system, connect air cleaner fo terminals EAC]
and EAC. These terminals supply. 115-volt
power to the electronic unit
4, When adding a tine-voltage humidifier to the
system, connect humidifier to terminals HU,
and HU. Humidifier has its own contro!
wiring, which is independent of the furnace
except for the power connections provided at
HU} and HU
ige (24 volt) humidifier is installed,
an accessory plug-in humidifier
relay in the printed circuit control center
6. When replacing a single-speed motor with a
dualspeed motor, be sure to remove jumper
between HI and LO on the control center.
Field Control Wiring — (See Fig, 4 thru Fig. 6.)
58GC Heating Only Models
1. Connect two 24-volt leads from accessory
thermostat to low-voltage pigtails R and W.
58GC Heating/Cooling Models
1. Connect four 24-volt leads from accessory ther-
mostat to low-voltage pigtails C,G, R,and W.
58GA Heating/Cooling Models and 58GA200100
Model
1. For heating with constant fan control, connect
leads from room thermostat subbase to ter
minals W, G, and R on the low-voltage terminal
strip. (See Fig. 3.) This hook-up is used wher
heating only with manual fan control at the
thermostat is desired.
Connect accessory thermostat to fumace and
cooling unit. Connect terminals W,G, R, and ¥
on tie thermostat subbase to identically labeled
terminals on the low-voltage terminal. strip.
Connect yellow and black low-voltage leads
from the remote condensing unit to the two C
terminals on the low-voltage terminal strip.
3. When adding a low-voltage humidifier to the
system, install a plug-in humidifier relay in
receptacle HR on the control center. Connect
humidifier directly to terminals Hand H on the
low-voltage terminal strip. Connect leads from
low-voltage humidistat in the conditioned
space, to terminals HS and HS on the low-
voltage terminal strip.foev reewostar
onwecron
wre
a
a
ay lL
Bitter suppl =
a] hfe} sf “ SA
aay ek | (Be mes
WMOIER
f™ on Ieee Ss
fen : ae
0 one =
(RECT RIVE HOTOR
COMPONENT ARRANGEMENT
umoieien
Siuwostar |
1
1
pote |
Sgregs |
ehh SBF ba,
pt SF bee fe
fe pepe 5 “MOTOR :
BLOWER peeetl ig, grime ob? a
MOTOR Fan aE MED Loo com
MeO HIS t
ia! i
TERMINAL
JUMPER
ELT ORIVE WIRING
Bows
RELAY
LEGEND
cna Ft Pom rng 175 —
— Factory Power Wiring (115 Volt) 1 To change cirect drive motor speed, move black or red lead to de
TH prin crt Cott Contr Weg 118 Yor aes eis ealraiel ce ay eon aaa
Fins Coo! Wiring (24 Vom tondilars Por optimum Seo bon. eter 0 Blower Spor
TIE aaory conor ing 24 or _ ee =
TT trite Cac Conrt Carer Wing (24 Vo heer gore i ;
@ serom Tonvel — Fett Connecion Pains (118 Vol and ese orev h ero potetion
2avony 4 Total electrical load is less than 12 amps
Bin Quek Conroe Trial ~ Facto ive Cantons
5 Freleinsated acceory humiaifer rly
(175 Volt one 24 Vor)
Fig. 5 — 58GA Field Power and Control Wi
jing, Heating/Cooling With Accessories Diagrams
6~
IMPORTANT: Set adjustable heat anticipator
Gf provided) to agree with ampere value of
combination gas valve. Failure to make adjust-
ment will result in unsatisfactory temperature
control.
“HEAT
VALVE ANTICIPATOR
(Aigha Fetes) TF 555
rashew (Unite) 7000
LEGEND
— Factory Power Wiring 1118 Vos
= Field Controt Wiring (24 Vet)
Foetory Controt Wicing (24 Von)
@ wire
1 To changeairsctdrive mator speed, move black or red ead 0 de
sired terminal on motor Factory specd selection f for average
onions For optimum speed section, rele to Blower Spal
180.C) wire or equivtent
4A Total etc cal lad i less than 12 amps
51 turnace i usid witha cooling unit that or equipped witha
love voltage transformer, connect black Iasd 10 bie Ieod on
6 Used only when cooling unit i eawioped with low voltage
Fig. 6 — 58GC Field Power and Control Wiring,
Heating/Cooling Diagram
COMBUSTION AIR ~ See ANS 221.30.
1 If furnace is installed in a confined area, such
as a closet or a utility room, provide air for
combustion.
a. Provide two air openings to interior space of
equal area, one located near the fop of the
enclosure and one at the bottom
b. Make sure that openings have free area not
fess than 100 sq in. in area, plus an
additional 1 sq in. for each 1000 Btu in
excess of 100,000 Btu input
¢. Air may come from under-the-floor space
and from attic with openings in floor and
ceiling
4. Air may come from attic, with one opening
in ceiling and with a duct bringing air from
attic to an opening within 12 in. of the
floor
©. Air may come thru ducts or joist spaces
freely communicating with the outdoors.
f, Where openings to interior spaces are im-
practical, follow the methods outlined in
ANS 221.30.
If furnace is installed in an unconfined area,
such as in a full basement, it can normally be
assumed that infiltration will provide sufficient
air in building of conventional frame, brick or
stone construction. In buildings of unusually
tight construction, provide a permanent open-
ing to the outdoors with a minimum free area
of not less that 1 sq in, per 4000 Btuh total
input ratings of all appliances in space.
Consult local codes for special requirements
CAUTION: Whenever gas appliance is installed
in any area where corrosive atmosphere or
chlorine or chlorinated compounds are present.
bring combustion air into combustion area of
furnace from outdoor source. Failure to do this
can cause excessive corrosion in furnace heat
exchanger.
CIRCULATING AIR SUPPLY
ordinancesand ANS 221.30.
1 Do not take circulating air from same space as
combustion air. Supply may be any mixture of
outdocr and return air with minimum tempera-
ture of 50 F.
Duets and diverting dampers should have been
installed so that volume of circulating air
entering furnace is unrestricted.
Consult local
START-UP AND SERVICE
IMPORTANT: Remove shipping bracket (see
Fig. 7) securing heat exchanger. On direct drive
models, remove blower shipping bracket (see
Fig. 7). On belt drive models. remove wood
shipping Blocks (two) under motor support side
rails.DIRECT ORIVE BLOWER
On bet drive blowers, remove sioad shipping blocks under snator
appar side rails
7 — Removing Shipping Brackets
Initial Start-Up,
When first lighting furnace pilot
Open all warm air registers
Set room thermostat to lowest setting,
If humidifier is installed with system, open
water supply valve.
4, If line voltage switch is provided in furnace
circuit, tum it to “OFT” position
ig. 8 and Fig, 9) to
5. Tum gas cock dial (see
“OLY” position.
6. Wait approximately 5 minutes to allow gas
which may have accumulated in burner com-
partment to escape.
7. Turn gas cock dial to “Pilot” position
8. On Robertshaw 7000 valves depress and hold
gas cock dial while lighting pilot bumer. If
valve is equipped for 100% shutoft, allow pilot
to burn approximately one-half minute before
releasing dial (Robertshaw 7000 valve) or
before depressing automatic pilot reset button
(Essex TF 555 valve). If pilot does not remain
lighted, repeat operation allowing longer
period before releasing dial or depressing
button, If necessary, adjust pilot. (S
Burner Adjustment.)
9. Turn gas coek dial to “On” position
10, Set room thermostat at desired temperature
position
IMPORTANT: For the Robertshaw 7000
models equipped with a pressure regulator, do
not adjust regulator if dial is positioned be-
tween “Pilot™ and “On” positions on the gas
cock dial.
-¢ Pilot
3 ‘Steew ee
5
Tissetes
NOTE Robertshaw (Unitrot! 7000 (Usad on 68GA Furnaces)
as cove Dias
eT
Pile pram
a Dr RREE EE
SPRITE
ofr 100% stot
‘sad on Boe
Fig, 8 — Combination Gas Valves
Pilot Burner Adjustment
| Remove pilot adjustment cap. (See Fig. 8.)
2. Adjust pilot key to provide properly sized
flame. (ignition flame should extend outward
and upward approximately 1.5 in. from the
stem of the pilot.) Turn screw clockwise for
high flame or counterclockwise for low flame.
Replace pilot adjustment cap.
Combustion Air Adjustment
Airgas mixture controls are provided on
furnaces to enable adjustment of the primary airsupply to get proper flame characteristics. (See Fig
91) Adjust the controls as follows:
1
After furnace has been operating for 15
minutes, loosen air setting screw on each
bumer
Close air setting until yellow tips appear in
flame. Then, open air setting until yellow tips
disappear and flame has soft blue cone.
Secure air settings in position by ti
each air setting serew,
htening,
ainsoas
MRTURE CONTROL
———
sca >=
aR cas
MIXTURE CONTROL
sace
Fig. 9 — 58GA,GC Gas Burners and Manifold
Assemblies
Blower Speed Adjustment
Adjust on installation for nameplate tempera-
lure rise. (See Table 1.)
To
ensure reliability of heat exchanger it is
recommended that temperature rise be set below
‘maximum to ensure that femperature rise will not
exceed maximun requirements should filter be-
come excessively dirty
a
For direct drive speed change, make change at
plug-in power terminal located in blower com
partment. Move line lead to desired speed
indicated
Speeds on 3-position power terminal are High
(1), medium (2), and low (3) Speeds on 4-
position power terminal are* High (1), Medium-
High (2), Medium-Low (3), and Low (4).
For belt drive speed change (S8GA furnaces),
perform the following.
a. Loosen setserew on adjustable hub of motor
sheave,
b- Rotate hub clockwise to increase or counter-
chekwise {0 decrease speed and. tighten
setserew on flat hub section
Belt Adjustment
Adjustment is correct if one-finger pressure
depresses center of belt 1 inch. Each blower
speed change on a S8GA furnace requires a belt
adjustment
1. Loosen motor support plate cap screws.
2. Slide motor for correct tension fir to loosen or
out to tighten
3. Retighten cap screws.
Fan and Limit Control
| Constant air circulation provides even tempera-
ture control. The fower the fan switch setting,
the bager the fan will continue to run after
bumers tum off.
2. After running fumace for 15 sninutes, restrict
the return air supply by blocking the filters or
by closing the return registers to test limit
switch operation.
3. Allow furnace to shut down on high limit. Fan
‘must continue to run.
4. Remove restriction Burners should come on in
afew minutes.
5. Adjust fan control “Off” setting per installation
needs. “On” setting is 25 F above “Off”
setting, differential is not adjustable.
Input Adjustment
1, Turn off all other gas appliances on same meter,
2. Set thermostat high enough to ignite burners,
Check cu ft of gas bumed per 5 minutes.
Multiply value by 12 to determine input (in
thousands of Btuh). Rating should be within
5% of nameplate input rating,
4. To adjust input, remove combination gas valve
cap covering regulator adjusting screw. (See
Fig. 8.)
5. With a small screwdriver, rotate adjustment
serew clockwise to increase or counterclockwise
to decrease pressure. Do not change pressure
more than + 0.3 in. we,
6. Replace regulator adjustment serew cap,
IMPORTANT: Refer to operating and main-
tenance instruction literature to ensure better,
longer, and more reliable service from your new
Carrier furnace.TROUBLESHOOTING
Burner Will Not Operate
POWER FAILURE — Power switch off — set 10
on, blown fuse — replace; defective wiring —
replace.
NO POWER TO CONTROLS ~ Thermostat set too
low, dirty or defective — reser, clean or replace as
applicable, defective transformer — replace; faulty
limit switch — replace; blown fusestat — replace.
BURNER WILL NOT IGNITE — Low gas pressure
or no gas to unit — check if manual shutoff valve is
closed, check gas supply, check for clogged gas line
and clean or repair, adjust gas pressure with all
appliances operating, faulty thermocouple — cheek
with millivoltmeter and replace if necessary; pilot
light extinguished ~ locate cause and relight.
pilot — clean
Burner Operates, But Heating Inadequate
UNIT UNDERSIZED ~ Size selected incorrectly
never overfire, replace with properly sized unit.
10
FUEL INPUT TOO LOW — Wrong orifice size
replace orifice; regulator set too low ~ readjust.
THERMOSTAT OPENS TOO SOON — Wrong
anticipator setting — readjust, thermostat out of
calibration — recalibrate; thermostat set wrong
check and reset as necessary, wrong thermostat
location — relocate
LIMIT SWITCH CYCLES BURNER — Dirty filters
= clean or replace, faulty fan switch or motor —
repair or replace, blower speed too low — readjust;
fan switch set too high — readjust, duct system
restricted — remove restriction.
Poor Combustion and Flame Characteristics
SMOKY FLAME — Insufficient air — adjust air
inlet, flue restriction — remove restriction, down-
draft — eliminate downdraft using flue caps on
vents
NOISY BURNER — Too much air — adjust air
inlet, incorrect input — make correction as
required.For replacoment items use Cartier specified parts
[Manufacturer sores the right to change any produet specif cations without notice
CARRIER AIR CONDITIONING COMPANY + SYRACUSE, NEW YORK
Tab 10 Fou S8GA,60-151 New Printed in USA 870 Cordes ana Catalog No 595-805