LPMDL 110x User Guide EN 4.9.6
LPMDL 110x User Guide EN 4.9.6
ThingsLog LPMDL-110X
v.4.9.6
Power supply - LPMDL-110X is able to operate in low power mode (on battery), with a solar power supply, or
with a 12V power supply.
Intelligence - the data is transmitted over a widely distributed, cellular network and is automatically gathered
in the ThingsLog platform.
Pulse metering - LPMDL-110X has the ability for an independent counting of pulse output meters for water,
gas, electricity, and heating. With a single data logger, you can meter two meters for example for cold and hot
water, or if your meters are in proximity distance you can meter with a single device gas, electricity, and
heating.
Analog sensors metering - LPMDL-110X has 4 inputs for connecting analog sensors with 4-20 mA output. An
example could be connecting two pressure sensors or one pressure and one temperature sensor.
Combined monitoring - LPMDL-110X can fulfill use cases where a single logger has to be monitored by one
water meter and two pressure sensors. For example monitoring of pressure reduction areas by
measurements of pressure sensors before and after the pressure reduction valve and its water meter.
Alarms and notifications - LPMDL-110X together with the ThingsLog platform is able to monitor consumption
and notify the customer or the utility company for leaks, high or low consumption, fraud, or thresholds
bridging of certain sensor values or a combination of a sensor and metered value.
Application - LPMDL-110X fulfills various use cases in Water, Electricity, and Gas distribution utilities but also
many other use cases in property management, hotel, manufacturing, condominium sub-metering, or in
common need is spread.
Ability to work in any environment - LPMDL-110X has IP68 dust and leakage protection and is suitable for
any kind of home or industrial usage.
155 mm / 6.1 in
Height 52 mm / 2.04 in
Width 70 mm / 2.75 in
● Solar PV panel
Power supply options for external sensors: ● Directly powered from the logger power
supply, requires low power sensor with
and consumption less than 10uA (check
5.1)
● Control-switched powered from the
logger power supply, requires sensors
with current consumption less than 20
mA (check 5.2)
● Sensors that require power supply > 3.6V,
requires additional step-up convertor,
3 Nomenclature
The name of the logger is formed as follows:
LPMDL-110X-EE-YYYY-ZZZZ-AA-RR-SSS
X – Modem
1 - GSM only (depricated)
2 - NB-IoT only (depricated)
3 - LoRa EU (depricated)
4 – GSM/4G
5- LoRa (30-EU, 31 - NA, 32 AU/AS)
6 - CatM1/NB-IoT/GSM
ЕE - Power supply
RR - Relay outputs
00 - No relay outputs
11 - 2 relay outputs
GNSS GPS/GLONASS/Galileo/BDS/SBAS/QZSS
Physical data transmission layer GSM/LTE
4.2 2G/NB-IoT/CatM1
4.3 LoRa/LoRaWAN
Requires 1x3.6V Li-SOCl2 battery with 20F super capacitor, with current leakage less than 10uA. The
capacitor should be connected in parallel to the battery.
The battery should be connected to the board on the board socket marked with a red rectangle in the
picture below. The polarity of the connection is denoted with + and - signs on the board.
NOTE: if you connect the supercapacitor parallel to the battery, you need to make sure that the battery
is charged to a voltage that is near the voltage of the battery. Otherwise, the supercapacitor can drain
significant current from the battery, which can damage the battery or even cause fire.
Requires additional power supply module. The module is marked on the picture with a red rectangle.
Note that when you use 12V Power supply you should not connect a battery to the connection
terminal described in the previous section.
When the module is attached the power supply should be connected: pin 1 - to the positive terminal of
the power supply; pin 2 - to the negative terminal of the power supply.
The inverter module should be connected as it is marked with a red rectangle in Figure 3.
This option requires a low-power sensor with and consumption of less than 10uA. The lifetime of the
battery strongly depends on the current consumption of the sensors and should be taken into account
for the calculations. For more information about the power consumption of the data logger consult
with section 6.
This option is applicable only to the battery power supply. It requires sensors with a current
consumption of less than 20 mA. This option also required an analog switch module marked with a red
rectangle in the figure below.
The switch is controlled by the data logger. It is turned on for the adc_read time parameter
configured in the service mode of the logger. For more information see the CLI User Guide. Input 1 must be
connected to the positive terminal of the power supply. Input 2 must be connected to the negative terminal
of the power supply.
6.3 Sensors that require a power supply > 3.6V, require an additional step-up converter
This option is applicable only for battery power supply. It requires sensors with a current
consumption of less than 20 mA. This option also required a step-up converter module marked with a red
rectangle in the figure below. The step-up converter converts the voltage of the battery from 3.6 to 12 V, with
the same switching mechanism described in the previous section for the control-switched sensor supply.
Input 1 must be connected to the positive terminal of the power supply. Input 2 must be connected to the
negative terminal of the power supply.
During this mode the Data Logger consumes continuously less than 6.5 uA current.
However if one attaches sensors to the battery of the logger the sensor current should be taken into
account for the calculation of the battery lifetime.
If the data logger reads pulses from a dry contact then in this mode it consumes 50 uA if the contact is
on. The pulses are counted even if the logger is in sleep mode.
On a predefined period the data logger wakes up and saves the values from the low-power
asynchronous counters into its RAM memory.
If the logger is configured to read analog values, then it turns on the external sensor's power supply
and waits adc_read time in order for the sensor to be settled. During this time one has to consider the
power consumption of the battery when the sensor is on.
In this mode the logger transmits readings stored in its internal memory to the ThingsLog platform.
The power consumption depends on the network technology, network coverage, and signal level.
For the average signal level, the power consumption is 0.33 mAh per transmission for 4G network.
8 Functional specification
● Pulse metering: the logger supports pulses generated by reed contacts, halll sensors or S0 pulse
outputs of water, gas, and electricity meters
● Analog sensor metering: The logger supports analog sensors with output from 4 to 20 mA or 0-3V
● Digital sensor metering: i2c and 1-wire
● Data transmission: LPMDL-110X supports 2/4G, CAT-M1, NB-IoT and LoRaWAN
● Low powered: Preinstalled interchangeable long-life battery able to support more than 5000
transmissions of millions of individual counter values
● Average battery life: 5 years
● Antenna: Internal or optional external SMA
● Secured configuration
● Certified for both industrial and home usage
Important Please read the complete information, the specifications, the installation
information instruction and the electrical interconnect schema prior to working with this
product.
Health and safety All installation work has to be performed in accordance with the local
rules for installation regulations on health and safety at work in electrical systems as well as the
regulations governing the electrical system and networks.
Only engineers or technicians with product expertise that has previously read
and understood this guide should install this product.
Installation and Installation is done in accordance with the instructions in this document.
maintenance Incorrect installation may cause damage to the logger and inaccurate
measurements. That is why the installation, and the initial configuration must be
done with due attention.
Incorrect installation results in violation of warranty conditions and failure of the
warranty.
An example of improper installation is to connect the pulse or analog input of
the device shortly or to a power source.
If you need to connect the logger to equipment in an ATEX zone 0, 1,2 please do
so outside the zone and through an external IC circuit barrier.
Transport and Store in dry rooms without access to water or other liquids at temperatures not
storage lower than -20 ° C and not higher than 60 ° C in the original package.
Transportation is allowed to happen accidentally at temperatures below -20 ° C
Subsequent Once installed, the data logger should be cleaned using a dry or lightly
maintenance moistened cloth, explicitly prohibiting the use of aggressive and abrasive
detergents.
Every six months, it is desirable for the user of the logger to check the enclosure
integrity and the integrity and waterproofness of the cable and connecting
terminals to the measured device or sensor.
Recycling When recycling the product and its disposal, local and national legislation and
regulations must be observed. If you hesitate, please return the appliance, we
will recycle it for you.
Table II Health and safety instructions
10 Physical installation
● Prior to installing the logger please review the health and safety instructions described in Chapter
4.
● The data logger comes with an installation manual and an optional attachment kit
● In order to attach the logger you will need a wall with stiff, flat surface close to the meter or the
sensor that you would like to measure.
● Mark and drill holes with size 4x25 mm for attaching the logger to the wall.
● Attach the logger input/outputs to the connecting cable.
● Attach the corresponding connecting cable input/outputs to the meters/sensors.
11 Input/output ports
1) Power supply:
a) output for external sensors - for models: LPMDL-110X-EE-YYYY-ZZZZ-АА-RR-
S12/LAS/LNS.
(1) S12 is 12V power supply. It is switched by the logger for a short period of time
(settling time parameter) configured in the logger, during the measurements.
(2) LAS is 3.6V or 4.5V depending on the logger battery. It is switched by the logger for a
short period of time, during the measurements.
(3) LNS is 3.6V or 4.5V depending on the logger battery. I am not switched by the logger
so the sensors should be low power.
b) input from external source – for models: LPMDL-110X-EE-YYYY-ZZZZ-LLLL--АА-RR-
L1/L0-000
(1) The external power supply can be in the range from 5-12V.
c) not connected – for models: LPMDL-110Х-ЕЕ-YYYY-ZZZZ-LLLL--АА-RR-00-000
2) Ground
3) ON/OFF alarm input 1. The alarm on the transition from OFF (opened circuit - the pin is not
grounded) to ON (closed circuit - the pin is grounded)
4) ON/OFF alarm input 2. The alarm on the transition from OFF (opened circuit - the pin is not
grounded) to ON (closed circuit - the pin is grounded)
5) Ground
6) Pulse input 2
a) can be dry contact (reed contact) – for models: LPMDL-110X-ЕЕ-2R0S-ZZZZ-LLLL-АА-RR-
SSS
b) S0 (open collector) – for models LPMDL-110X-ЕЕ-0R2S/1R1S-ZZZZ-LLLL-АА-RR-SSS
7) Pulse input 1
a) can be dry contact (reed contact) – for models:
LPMDL-110X-ЕЕ-2R0S/1R1S-ZZZZ-LLLL-АА-RR-SSS
b) S0 (open collector) – for models: LPMDL-110X-ЕЕ-0R2S-ZZZZ-LLLL-АА-RR-SSS
8) Ground
9) ON/OFF output 1 (open collector)
b. Circuit
2. Connect 2 analog 4-20 mA and 2 analog 0-3V inputs. The analog sensors 4-20 mA are powered by an
external power supply (non-low power case). The logger is powered by an external power supply.
b. Circuit
Circuit
Circuit
13 User guide
13.1 Login to ThingsLog platform
1. In order to perform the initial configuration you should have an account for the ThingsLog IoT
platform. If you don’t have an account please contact us at support@thingslog.com.
3. You should be able to see a device list with the devices associated to your profile.
3. From the menu choose “Config” and then a similar configuration dialog will appear.
● Record period - Could be Minutes or Hours. This is the period on which the logger will log in
memory the reading values from the pulse inputs or the period on which it will perform low
power reading of its analog current inputs.
4. Pulse sensors
Pulse sensors are typically meters connected to a pulse input port or buttons. To enable the port
please slide the slider to the right and enter. Once the port is enabled you have to set the following.
● Digits - Number of digits - equals to the number of digits on the display of the meter
● Fraction - Number of digits after the decimal pointer on the display of the meter
● Sensor type – the type of the sensor could be water, gas, power, etc meter.
● Units type – the dimension of the metered values – m3, kw, etc.
● Pulse per unit – how much of the measured value is equal to one pulse
5. Analog sensors
To enable analog sensor readings (connected to the analog inputs) just slide the slider to the right
and configure:
● Sensor type – the type of analog sensor we are measuring
To enable the ON/OFF alarm sensors slide the slider to the right. The sensors have to be normally
open ON/OFF sensors. If the port is enabled and the sensor goes from OFF to ON the logger will wake
and will transmit an instant alarm.
To enable the ON/OFF relay sensors slide the slider to the right. The sensors have to be normally
open ON/OFF sensors. If the port is enabled and the device gets an ON/OFF relay command it will
trigger the port.
8. Delete old counters - once you are ready with the inputs configuration decide do you want to keep
the old values or not. If not choose “NO” else choose “YES”.
This will start a 1000-second counter. You will have to touch the logger with a magnet prior to the
counter expiry. This will put the logger into configuration mode and it will try to obtain its configuration
from the server.
10. If the logger gets configured successfully you will be able to see the following message on your
screen.
● Record period
● Transmission period
● Enable/disable ports
● Set high/low-level alarms
● Change K factors (pulse per m3)
● Set on/off alarms
What could be changed but loggers will ignore the changes is:
If you need to change those you have to be physically close to the meter and the logger and attempt normal
configuration with a magnet.
To reconfigure the logger over the air use the same “Config” menu as we do for normal setup.
The logger will obtain its new configuration on the next successful transmission.
13.4.1 Readings
From the readings menu the user has access to the readings gathered by the logger. The user can select a
time interval and export the readings to a file in csv/excel file format.
13.5.1 Dashboard
Navigate from the menu to the “Dashboard” where you can verify the operational status of your
loggers.
● HIGH_CONSUMPTION - alarm indicating consumption higher than a certain preconfigured level over
a certain period. For example 1m3 over 1 hour.
● MISSED_TRANSMISSION - alarm indicating that the transmission from the logger did not happen.
● LOW_FLOW - alarm indicating that the flow time interval is lower than the expected value per
second.
● HIGH_CONSUMPTION - alarm indicating that the consumption time interval is lower than the
expected one.
● ALL_ZERO_CONSUMPTION - alarm signaling zero consumption through a certain time period. For
there is no consumption for 24 hours. This could potentially indicate a fault meter.
● DEVICE_REMOVED - alarm indicating that the meter has been disconnected from the logger.
● LOW_BATTERY - alarm indicating that the battery of the logger is under 20%.