CONVENTIONAL FIRE ALARM CONTROL PANEL                                                                                            1PM2 Series
■ Features
                                                                                  •     5 to 60 zone model available
                                                                                  •     Extra slim design
                                                                                  •     Highly reliable design by adopting durable LED
                                                                                        indicators and CPU
                                                                                  •     5 to 20 circuits for zone alarm bells available
                                                                                        (due to the model on purchased)
                                                                                  •     Alarm delay function
                                                                                  •     Alarm delay ON/OFF switch function
                                                                                  •     Trouble monitoring function
                                                                                  •     CPU trouble back-up function
                                                                                  •     Re-sounding mode of a panel buzzer
                                                                                  •     Signal transfers for detector resetting available
                                                                                  •     Equipped with high protection for Lightning surge
                                                                                  •     Interrupting function for emergency announce-
                                                                                        ments of silence zone alarms
                                                                                  •     3 alarm indicators for indicating the alarm inputs
                                                                                        from building facilities such as hydrants
                                                                                  •     CPU trouble back-up function
                         1PM2                                                     •     Capability for transferring the second fire signal
                                                                                  •     Signal transfer for Emergency PA facility also
                                                                                        equipped
■ Description                                                                     •     Easy wiring by Push-in terminals’ one-touch
The 1PM2 is a conventional fire alarm panel with a                                      connection
stylish wall-mount design supplied in 5 to 60 zone
formats. All detector circuits will be indicated with
lighting red LEDs in alarm conditions and flushing                                ■ Remote Test Function
in open circuit fault conditions. Slide-in paper labels
are included for clear zone identification. The alarm                             Remote test function is available on 2KW-P and
panel has an alarm delay function on every detector                               2KAD2-P detectors etc. with a dedicated testing
circuits to reduce false alarms, including a zone-by-                             device.
zone settable delay ON/OFF function.
1PM2 features a re-sounding function of panel                                                                                 2KW-P
buzzer by reception of any subsequence input from                                                                             - Distinguishes steam
manual alarm stations or other zones ensuring an                                                                                 and smoke
announcement of a fire spread after the buzzer
silenced. The alarm panel also has a maintenance                                                                              - Automatic sensitivity
switch to enable installation or maintenance works                                                                              compensation
to cut off the panel buzzer and zone alarms.                                                                                  - Suited for Shower
1PM2 to be equipped with a CPU for securing high                                                                                rooms and Kitchens
reliability features also a CPU trouble back-up function.                                                 * Operating Image
Even when the CPU falls down, basic functions are                                                                             2KAD2-P
secured to indicate alarm zones, to sound alarms and
to transfer the alarm signal.                                                                                                 - Remote-test available
The power consumption reduced 70% compared with                                                                               - Automatic sensitivity
Nittan’s previous models contributes to cost reduction.                                                                         compensation
                                                                                                                              - Suited for Condo-
                                                                                                                                miniums
                                                NOT TO BE USED FOR INSTALLATION PURPOSES.
                      Nittan reserves the right to make changes at any time without notice in prices, colours, materials,
                      components, equipment, specifications and models and also to discontinue models.                                   1PM2-DAT-00    Rev.0
■ Main Features
1. High reliability, advanced fire detection
Re-sounding mode of panel buzzer                             CPU trouble back-up function
                      After Panel alarm silence                                       Even when CPU is down,
                      by operator at fire, the                                        basic function is carried on, fire
                      panel buzzer automatically                                      signal can be received, zone
                      re-sounds by operation of                                       indication, alarm sounding,
                      manual alarm stations or by                                     fire alarm signal transfer, etc.
                      receipt of alarm signal from
                      other zones to announce fire
                      spread.
Alarm delay ON/OFF function                                  Outputs for Emergency PA system
                      Alarm delay function can                                        Outputs for interlocking to
                      be cancelled zone by zone                                       Emergency PA system are
                      individually.                                                   provided as standard.
2. Advanced functions for easy installation and maintenance
Lightning surge protection                                   Maintenance switch (All alarm silence)
                      Lightning surge protection                                      At maintenance work,
                      devices are provided as                                         unnecessary alarm sounding
                      standard to main circuits to                                    can be cut off by operating the
                      protect semiconductor parts.                                    maintenance switch (except
                                                                                      telephone calling sound).
                                                                                      Clicking sounds is made when
                                                                                      the maintenance switch is ON
                                                                                      to draw operator’s attention.
Alarm delay ON/OFF switch                                    Push-in type terminals
                      This switch can make                                            Push-in type terminals
                      the alarm delay function                                        are employed to improve
                      ineffective for installation and                                efficiency at installation.
                      mainenance work.
Auto reset switch                                            Self-checking function
                      When operation test of                      Monitoring;
                      detectors and manual alarm                  • Detector line open-circuit
                      stations are conducted, by                  • Circuit voltage low
                      pressing auto reset switch to               • CPU trouble
                      the reset side, fire test can               • Fuse blow
                      be conducted zone by zone                   • Disconnection of Standby battery
                      and the tested detector and                 • Emergency PA line open-circuit
                      the control panel shall be                                        .
                      automatically reset.
                                    NOT TO BE USED FOR INSTALLATION PURPOSES.
                                                    Page 2 of 6                                            1PM2-DAT-00     Rev.0
■ Indicators on Operation Panel
                                      [6]     [7]
  [1]
  [2]                                                                                        [10]                                              [15]
  [3]                                                                                        [11]                                              [16]
  [4]                                                                                        [12]
                                                                                             [13]                                              [17]
  [5]
                                                                                             [14]
                                  [8]       [9]
              [18] [19]       [20] [21] [22]                             [23]         [24]              [25]            [26] [27]
[1] FIRE (Red)                                                              [17] Other Alarms (Red)
     LED turns on when the panel is in an alarm condition.                      Each of the LEDs turns on when the panel receives alarm signals
[2] AC POWER (Green)                                                            from building facilities via LXn-C contacts.
     LED turns on when AC power is supplied to the main power circuit.      [18] RESET switch
[3] CIRCUIT VOLTAGE (Green)                                                     Activation of this switch resets the panel condition.
     LED turns on as long as the main circuit voltage of the control        [19] ALARM TRANSFER ISOLATION switch
     panel is within acceptable levels (approx. 20.4 V and greater).            Activation of this switch isolates an alarm signal transfer through
[4] SWITCH OPERATION (Red)                                                      GA-GB-GC contacts.
     LED flashes when the panel switches are ON or not normal state.        [20] GENERAL ALARM switch
[5] TELEPHONE (Green)                                                           Activation of this switch activates all the zone alarms and outputs
     LED turns on when a handset is plugged into a telephone jack of            alarm signals to an emergency PA facility.
     a manual alarm station or an annunciator panel.                        [21] HYDRANT STATION ISOLATION switch
[6] MAINTENANCE (Red)                                                           Activation of this switch isolates an alarm signal transfer through
     LED turns on during a maintenance mode.                                    H-H’ contacts.
[7] ZONE ALARM SILENCE INDICATOR (Red)                                      [22] EMERGENCY PA ISOLATION switch
     LED flashes when zone alarms are silenced.                                 Activation of this switch isolates an alarm signal transfer to an
[8] PANEL ALARM SILENCE switch                                                  emergency PA facility.
     Activation of this switch when a panel buzzer is sounding, turns       [23] FIER TEST switch
     off the sounding buzzer.                                                   Use this switch for conducting a fire indication test.
[9] ZONE ALARM SILENCE switch                                               [24] ZONE SELECTION TENS DIGIT switch
     Activation of this switch makes zone alarms silenced.                      This switch sets tens digit of testing zones during a fire indication
[10] ALARM DELAY (Red)                                                          test.
     LED turns on during a delay time of 60 sec, and flashes during         [25] ZONE SELECTION ONES DIGIT switch
     a general alarm delay switch is OFF.                                       This switch sets ones digit of testing zones during a fire indication
[11] CPU TROUBLE (Red)                                                          test.
     LED turns on when the CPU is in a fault state.                         [26] AUTO RESET switch
[12] FUSE FALUT (Red)                                                           Activation of this switch enables a non-latching test function which
     LED turns on when a fuse for zone alarm outputs is blown.                  allows manual alarm stations and detectors to be tested and the
                                                                                panel to resets automatically.
[13] BATTERY FAULT (Red)
     LED turns on when a standby battery is not connected to the            [27] BATERY TEST switch
     panel.                                                                     Activation of this switch enables a standby battery test.
[14] EMERGENCY PA (Red)
     LED flashes during emergency PA announcements, and turns
     on when an open circuit is detected on the emergency PA lines.
[15] MANUAL ALARM STATION (Red)
     LED turns on when a manual alarm station is
     activated.
[16] HYDRANT OPERATION (Red)
     LED flashes while a hydrant pump(s) is in operation.
                                                  NOT TO BE USED FOR INSTALLATION PURPOSES.
                                                                  Page 3 of 6                                                         1PM2-DAT-00       Rev.0
■ Typical Wiring Diagram
                                                                                                                                                                A
                                                                                                                                                          T
                                                                  L1                                          L            L               L
                           Fire Alarm Zones (24 VDC+)                                          Fixed Temp.          ROR
                                                                                                                                                      L
                                                                                                                                                               *1 CRE *2
    For Detectors                                                                              Heat                 Heat
                                                                                                                                   Smoke
                                                                                                                                           S              P
                                                                  Ln                                                                                  C
          and
                           Fire Alarm Common (-)                  C                                           C            C           C
 Manual Alarm Stations                                                                                                                          P
                           Telephone (+)                          T                                   T                                                             L *3
                           Response Lamp (24 VDC+)                A                                   C                                                  I+
                                                                  I1                                  I1
                           Fire Alarm Zone Indication (-)                                                                                                F
                                                                                                                  Announciator                           F'
                                                                   In                                 In
   For Announciator
                           Announciator Buzzer Silence (-)         IC                                IC
                                                                                                                                                         N
                           Announciator Buzzer (-)                 IB                                IB                                                  N'
                           Announciator Power Supply (24VDC+) I+                                     I+
                           Common Fire Alarm Signal                 F                                                                               Fire Protection
                           (Works compulsorily)             F  F’  F'                                                                                System, etc.
 For Fire Alarm Signal
                           Fire Alarm Signal                      GA
        Transfer
                           (Isolation switch                      GB                                  Security System, etc.
                            available)                GA GC GB    GC
   For Reset Pulse         Normally Closed                          N
       Transfer            (System Reset=Open)             N  N’    N'
                                                                  LX1
                           Other Alarm Input                      LX2
                                                                  LX3                                      Fire Extinguishing
 For Building Facilities
                           Other Alarm Common                      C                                          System, etc.
                           Other Alarm Signal Transfer             XA
                           (Non-Voltage, N/O)              XA  XC XC
                                                                   B1
                           Zone Alarm Output (24 VDC+)                                                                                                    *4
 For Zone Alarm Bells                                                                                  B                       B                     B
                                                                  Bm
                           Zone Alarm Common (-)                  BC
                                                                  EA1                               EL1
                           Zone Block Output
                                                                  EAn                               ELn
                                                                                                                  Emergency
  For Emergency PA         For Emergency PA Common                EC                                EC
                                                                                                                     PA
       System              First Alarm Signal Transfer            EF1                               EF
                                                                                                                   System
                           Second Alarm Signal Transfer           EF2
                           Microphone Operating Input             EB                                 EB
                                                                                               *5
                           (Silences zone alarms)                 EB'                                EB'
                                                                   PL
 For Indication Lamps      Power Output (25 VAC)                           LED      LED
                                                                  PL'
                           Output for Start                         H                                 H
                                                                                                                  Hydrant           AL
  For Hydrant Pump         (Non-Voltage, N/O)              H  H’    H'                               H'
                                                                                                                   Pump                        LED            LED
       Starter             Input for Confirmation of Start         XL                                XL
                                                                                                                  Starter           AL'
                           (Pump Activation=25VAC Input)           XL'                               XL'
  For Primary Power                                               P1                                220 VAC
                           Power Input (220 VAC)
       Source                                                     P2                                Exclusive
 For Earth Connection                                               E                               Power supply
                  *1: P = Manual Alarm Station
                  *2: The CRE is a dedicated end-of-line device which comes with the 1PM2 fire alarm control panel.
                  *3: Make sure to be used F-F’ and N-N’ terminals when use Remote indication lamps.
                  *4: Use the motor bells rated at 10 mA, 24 VDC.
                  *5: The end-of-line resister comes with the 1PM2 fire alarm control panel.
                                                  NOT TO BE USED FOR INSTALLATION PURPOSES.
                                                                    Page 4 of 6                                                                                1PM2-DAT-00   Rev.0
■ Dimensions
20 zones cabinet                                 40 zones cabinet                                              60 zones cabinet
         450                   100                           450                         100                           450                          100
                         760
                                                                            1060
                                                                                                                                     1250
        Specifications                                                                 1PM2-nLA
        Number of Zones              5           10             15             20          25             30           40           50              60
    Number of Bells (10 mA)          10                                        20                                                   30
     Number of Bell Blocks           5           10                                        15                                                20
     Primary Rated Current                                                                0.39 A
        Standby Battery                                              0.45 Ah                                                      1.2 Ah
         Mounting Type                                                              Wall-mounting type
        Dimensions (mm)                      W 450 x H 760 x D 100                             W 450 x H 1060 x D 100             W 450 x H 1250 x D 100
               Weight                                 18 kg                                              25 kg                              30 kg
                Notes                                              Not included: Dedicated Battery, Telephone Handset
■ Ordering Information
               Model                                                                  Description
                PTL-1           Telephone Handset
      Nicd-battery (0.45AH)     Ni-Cd Battery (0.45AH) for 1PM2-5LA – 30LA
      Nicd-battery (1.2AH)      Ni-Cd Battery for (1.2AH) for 1PM2-40LA – 60LA
               PSH-nL           Annunciator Panel with n Zone
               2KH2-LS          Optical Smoke Detector
           CKLD-KPT             Beam Type Smoke Detector
                LP05            Remote Station for Beam Detector
           1CD-70-LS            Fixed Temp. Heat Detector, 70°C
               2SC-LS           Rate of Rise Heat Detector
               2KW-P            Dual Wavelength Type Optical Smoke Detector with Remote testing function
           2KAD2-P              Optical Smoke Detector with Automatic sensitivity compensation and Remote testing function
                MTS1            Remote Testing and Address Setting Device for 2KW-P, 2KAD2-P and others
               LP01/1           Remote Station for MTG
                 3T             Common detector Base for LS type detector
                B6T2            Common detector Base for LS type detector for connecting a remote indication lamp
                B3-J            Detector Base for 2KW-P, 2KAD2-P, and others
               1MF1A            Manual Alarm Station with telephone jack
          BD-6-24-11            Local Alarm Bell (10 mA)
          PL-R4-LED             Indication Lamp (LED type)
               AL-4-24          Remote Indication Lamp
      SRT-01M6L-47SGB           Local Combined Box (vertical type) with telephone jack c/w Surface Mounting Box
                                             NOT TO BE USED FOR INSTALLATION PURPOSES.
                                                                   Page 5 of 6                                                               1PM2-DAT-00   Rev.0
■ Specifications
           Specifications                                                                 1PM2-nLA
               AC Power                   220 VAC ±10% 50/60 Hz
                                          Sealed Type Ni-Cd battery
            Standby Battery               5LA - 30LA Panel      : 0.45 Ah
                                          40LA - 60LA Panel     : 1.2 Ah
          Power Consumption               39 VA
          Nominal Delay Time              60 sec. (For smoke detector: 60 sec. For heat detector: 20 sec.)
              Dimensions                  5L - 20L Panel         : W 450 x H 760 x D 100 mm
                                          25L - 40L Panel        : W 450 x H 1060 x D 100 mm
                                          50L - 60L Panel        : W 450 x H1250 x D 100 mm
             LED Indicators               Fire alarm, AC power, Circuit voltage, Switch operation, Telephone, Maintenance, Zone alarm silence, Alarm
                                          delay, CPU trouble, Fuse fault, Battery fault, Emergency PA, Manual alarm station, Hydrant operation,
                                          Other alarm (3 windows)
               Functions                  CPU fault monitoring, Fuse fault indication, Cable break monitoring
        External Line Resistance          50 Ω and less
           End of Line Device             CRE
         Panel Alarm Sounder              Piezoelectric buzzer, automatic re-sounding type
             Trouble Alarm                Detector line open-circuit, CPU trouble, Zone Alarm Fuse blows, No battery connected, Emergency PA line
                                          open-circuit, Alarm inputs from external equipment
          Fire Alarm Transfer             			                                                Contact Capacity
                                          Common Fire Alarm         : F-F’ (Normally-Open)      1 A 24 VDC
                                          Fire Alarm                : GA-GB-GC (Form-C)         1 A 24 VDC
                                          Reset Pulse               : N-N’ (Normally-Close)     1 A 24 VDC
                                          External Equipment Alarms : XA-XC		                   1 A 24 VDC
                                          Emergency PA : EC EF1 EF2 EA1-EAn* EB EB’
                                                                            (Normally-Open)     1 A 24 VDC
                                          		                                         *n: 5LA=5, 10LA=10, 15LA-40LA=15, 50LA-60LA=20
  Output Current for Zone Alarms (Bell)   24 VDC    5L: 100 mA     10LA-30LA: 200 mA       40LA-60LA: 300 mA
  Output Current for Indication Lamps     25 VAC    400 mA
   Number of Connectable Detectors        Standard type       Smoke detector:      Max. 40 /zone, Total 20 x zones
                                                              Heat detector:       As required
                                          Thermistor type     Heat detector:       Max. 24 /zone, Total 12 x zones
                                          Detectors with test function:            Max. 20 /zone, Total 10 x zones
   Connectable Manual Alarm Station       1MF1A 1MI1A
    Connectable Annunciator Panel         Model PSH x 1 unit
         Operating Temperature            0°C to +40°C
           Primary Materials              Main Body: SPCC t1.6
                                          Door: SPCC t1.2
                                          Operation Panel: Flame retardant resin
              Body Color                  JPMA Color Code A22-90B Semi-gloss (off-white)
                                                             Page 6 of 6               1PM2-DAT-00   Rev.0