WBVF HHT Inverter: Overseas Field Support Team
WBVF HHT Inverter: Overseas Field Support Team
Overseas field
             support team
  - Index -
1. Layout
2. Monitor menu
3. Program menu
                  WBVF INVERTER Parameter
1. Layout
     Main NFB
     (AC380V)                          Inverter stack
                                       Main Board
    Contactor,
      Fuse
     VCON B’d
                                       Contactor
                                       E-Stop S/W,
                                         Buttons
     SAF B’d
        NFB
                                       Transformer
      (AC220V)
                                       -1-
                          WBVF INVERTER Parameter
1. Layout
 Menu category
                                           -2-
                           WBVF INVERTER Parameter
2. MONITOR
  1.1 BASIC
                                     Mroom_Drive         1
                                 Door_Closed
    WBST PMSM Ver
                                 WBST PMSM      [4.2K_rev]
                                 SPEED FBK :         0.0 r
SPEED FBK rpm It shows the actual speed of the motor (encoder feedback).
                                     Mroom_Drive          1
                                 Door_Closed
      SPEED REF     rpm          SPEED FBK :        23.7 r
                                 SPEED REF :        23.7 r
                                                                  -3-
                           WBVF INVERTER Parameter
2. MONITOR
  1.1 BASIC
INV. VOLTAGE V It shows the actual voltage of the motor in r.m.s(Root-Mean-Square value).
It shows the inverter DC LINK voltage. It is calculated as the following formula according to the input voltage.
                                                                     -4-
                         WBVF INVERTER Parameter
2. MONITOR
  1.1 BASIC
Initial angle error estimation. As the error gets bigger, ROTOR POSITION increases during the operation.
                                                                  * Example
                                                                                                      If Rotor position is over 2V,
                                   Mroom_Drive          1                 Mroom_Drive        1
                                                                                                       adjust U-angle by 0.1 until it
                               Door_Closed                            Door_Closed
      ROTOR POS                                                                                        becomes 2V or less .
                               DC LINK VOLT :      537 V              10. U angle
                               ROTOR POS :         0.1 V                                 2.16         Must push the reset button
                                                                                                       on the main board after
                            It should be ±1 V in inspection       After change U-angle to 2.06         change U-angle.
                            speed without main ropes.             and 2.26, check Rotor position
It shows the value of weight of the load sensor converted into the number of pulses.
                                  Mroom_Drive            1
                               Door_Closed
     LOAD PULSE                ROTOR POS :          0.1 V
                               LOAD PULSE :          854
                                                                -5-
                         WBVF INVERTER Parameter
2. MONITOR
  1.1 BASIC
        Item      Unit                                                     Description
                                                                               AUTO                   RELEVEL
                                   Mroom_Drive        1
                               Door_Closed                                    INITIAL                60MM DRIVE
     DRIVE MODE
                               DRIVE MODE :    INSPECT
                                                                             INSPECT                 LOW SPEED
                               INITIAL :           FAIL
                                                                               PLO                       ELD
STOP
                                                                                               To complete height
                                 ≡ Auto_Drive         20                                        measurement, every position
                               Door_Closed                                                      of the forced deceleration
      PLDL POS                 INITIAL :            OK                                          signals (PLDL, PLDH, PLUL,
                               PLDL POS :           OK                                          PLUH…) are should be correct
                                                                -6-
                             WBVF INVERTER Parameter
2. MONITOR
  1.2 I/O
                                                                    -7-
                                WBVF INVERTER Parameter
2. MONITOR
  1.2 I/O (Operation Time Chart)
                     Pattern Start
                     Point
SPEED Pattern
DCL (INPUT)
         Fwd. Rev
         (INPUT)
          RUN
          (OUTPUT)
          BKO
          (OUTPUT)
           ZSP (OUTPUT)
BKS (INPUT)
                                     ①②③④⑤⑥                                       ⑦ ⑧ ⑨ ⑩ ⑪
                           ①   Door Close Limit Signal ON
                                                                           ⑦   Zero Speed Signal OFF
                           ②   Forward/Reverse Signal (Up/Down) ON
                                                                           ⑧   Brake Output Signal OFF
                           ③   Inverter Run Signal ON
                                                                           ⑨   Brake Confirm Signal OFF
                           ④   Brake Output Signal ON
                                                                           ⑩   Forward/Revers Signal OFF
                           ⑤   Brake Confirm Signal ON
                                                                           ⑪   Door Close Limit Signal OFF
                           ⑥   Zero Speed Signal ON
                                                                     -8-
                           WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
                                       Mroom_Drive      1
                                   Door_Closed
         IGBT FAULT
                                   1. INVERTER SEL
                                           WB 110GT 7.5kW
                                                                                                              Inverter > Motor Capacity
         Mroom_Drive   1        Check the capacity of
     Door_Closed                Inverter and Motor.
     1. IGBT FAULT                                                                 Inverter Stack
         18:0122:1320:30
                            2. Check GATE Board power(24V), SMPS power and the Main Board.
                                                                     -9-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
                                                                                                                     Inverter      Sensing
                                                                                                                     Capacity      Resistor
                                                                                                                      3.9kW         60 Ω
                                                                                                                    5.5~7.5kW       30 Ω
                                                                                                                       11kW         20 Ω
                                                                                                                       15kW         30 Ω
                                                                                                                       22kW         20 Ω
                                                                                                                       30kW         15 Ω
                                        Inverter Stack                          Sensing resistors
                                                                   -10-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
          OC FAULT
                                                                                                      Check encoder power
                                                                                                       - Synchronous motor: 5V
                                                                                                       - Induction motor: 15V)
        Mroom_Drive   1                                                                                   and encoder signal.
     Door_Closed
     1. OC FAULT                                                                                      If the setting of initial angle is
                                                                                                       wrong, Over current can be
        18:0122:1320:30
                                                                                                       occurred.
                                                                  -11-
                             WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
          Error                                                                  Description / Check point
                           DC Link over-voltage (800V) occurred. Check 3-phsae input power. If input voltage is 560V or higher, over-voltage error
                           occurs
        OV FAULT
                           1. Check actual DC Link voltage and adjust DC Link Scale to make same both actual value and DC Link on HHT.
2. If OV FAULT occurs during the regeneration operation, measure with tester to check braking resistor is normal.
                                                                             -12-
                         WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
          Error                                                        Description / Check point
2. Check actual DC Link voltage and adjust DC Link Scale to make same both actual value and DC Link on HHT.
Fuse
2. MONITOR
  1.3 ERROR
                         Overload current is input to inverter to cause the error. The rated overload current is as follows.
       INV OV LOAD
                         1. Check inverter capacity and motor setting on HHT.
       Mroom_Drive   1
   Door_Closed
   1. INV OV LOAD                  Mroom_Drive      1
       18:0122:1320:30         Door_Closed
                               1. INVERTER SEL
                                       WB 110GT 7.5kW
                                                                                                               Inverter > Motor Capacity
                           Check the capacity of
                           Inverter and Motor.
                                                                                 Inverter Stack
                         2. During the running, the motor current should be lower than the rated current. If it is higher than the rated current, check
                         elevator balance.
            50%
                            120%~150% of the rated current        30 Sec.        Condition for Overload
            Load                                                                 current
                         3. For Synchronous motor, if the initial angle setting is incorrect, over-current may cause overload error.
       Balance check
                             For Induction motor, check if the encoder wiring is normal.
                                                                     -14-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
                           If the motor operates at the set value or higher, an error occurs. Over-speed setting value is set to 120% of
                           the rated speed, and it can be changed in FACTORY OS LEVEL
         OVER SPEED
                           1. Compare between the inverter stack with HHT menu.
        Mroom_Drive   1
                                     Mroom_Drive      1
     Door_Closed
                                 Door_Closed
     1. OVER SPEED
                                 1. INVERTER SEL
        18:0122:1320:30
                                         WB 110GT 7.5kW
                                                                                                        Inverter > Motor Capacity
                              Check the capacity of
                              Inverter and Motor.
                                                                                  Inverter Stack
                                                                 -15-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
                           It is caused by not initializing the inverter when the inverter main board is updated or it is replaced with a
                           new main board. Initialize in FACTORY INIT EEPROM. Memorize the inverter data before the initialization.
1. Check the EEPROM VERSION and then compare between update version and original version.
VERSION ERR
        Mroom_Drive   1
                                                  Auto_Drive          5               Auto_Drive      5   UP       Auto_Drive      5
     Door_Closed                 ENT
                                           Door_Closed                            Door_Closed                   Door_Closed
     1. VERSION ERR
                                           46. EEPROM VERSION                     47. INIT EEPROM               47. INIT EEPROM
        18:0122:1320:30                                            V1.44                            OFF                           ON
                                                                           -16-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
                           It is an error caused by the deviation between the reference speed and the actual speed of the motor and
                           it can be changed in INTERFACE SPD WID
        Mroom_Drive   1     Please check whether U, V, W bolt are fasten fully or not. Also check whether encoder cable made spacing from power line.
     Door_Closed
     1. SPD DISAGR
        18:0122:1320:30
                                                                       -17-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
                           3. During the activation, the motor current must be smaller than the rated current. If it is greater than the rated
                              current, check the elevator balance.
        Mroom_Drive   1
                                        Motor Shaft
     Door_Closed
     1. SPD DISAGR
        18:0122:1320:30
                                                                     -18-
                         WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
                                                                                                      MTH  THC
                                                                                                      N24  TH1
                                                                                                      MTH <--> RTH
        MTR OV HEAT
                                                                                                        (JUMPER)
       Mroom_Drive   1
    Door_Closed
    1. MTR OV HEAT
       18:0122:1320:30
                                                                  CN21
                                                                                             CN20
                                                                  -19-
                         WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
                          EEPROM defect error – there is a defect in the inverter data storage parts.
                          It is the memory defect in the main board, and you need to replace the main board.
                          1. first, write the original inverter data.
        EEPROM ERR
                          [1. inverter menu  2. program  please memo all data of program part.]
    Door_Closed
    1. EEPROM ERR
       18:0122:1320:30    2. Replace the main board.
                                                                        -20-
                         WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
1. Check whether the brake switch status and brake switch signal are correct or not.
BK SW FLT
                          2. Check brake relay according to the brake signal line. Refer to COL.5 in electric diagram.
       Mroom_Drive   1
    Door_Closed
    1. BK SW FLT
       18:0122:1320:30
                                                                   -21-
                         WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
1. Check the between UP and Down switch terminal connection. Refer to COL 6, 8 in electric diagram.
FR ERROR
                                 When press up or down button, check whether the signal simultaneous input.
                                 ONU, OND signals use P24 line. So please check whether the DC 24V line has jumper.
                                 For example,
       Mroom_Drive   1
    Door_Closed
    1. FR ERR
       18:0122:1320:30
                                                                   -22-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
                                                                     -23-
                         WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
                          The motor initial angle error is not big, so it may be activated, but as the speed gets higher,
                          the possibility error increases.
                          2. Set the initial angle so that BASIC  ROTOR POSITION value to be ±1V or less during the manual operation.
       Mroom_Drive   1
    Door_Closed            By Changing the U-angle value, make sure to set under ±1V ROTOR POS value.
    1. ANGLE ERR          [When change the u-angle value, please change by 0.03.  please press reset button  check the ROTOR POS value.]
       18:0122:1320:30
                                    Mroom_Drive          1             Mroom_Drive            1                   Mroom_Drive        1
                               Door_Closed                         Door_Closed                                Door_Closed
                               3. MOTOR                           11. U-ANGLE                                DC LINK VOLT :  537.1V
                               4. FACTORY                                                  2.14               ROTOR POS :       0.7V
                                                                  -24-
                           WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
              Error                                                         Description / Check point
                                                                     -25-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
U V W
EARTH FLT
                           2. Check if inverter output contactor(MC2) is properly working. Refer to COL.1, 3, 5, 9 in electric diagram.
        Mroom_Drive   1
     Door_Closed           2-1. Check the COL. 1 section in MC2 operation.
     1. EARTH FLT
        18:0122:1320:30
                                                                     -26-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
              Error                                                      Description / Check point
EARTH FLT
                                                                  -27-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
              Error                                                        Description / Check point
EARTH FLT
                                                                    -28-
                         WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
                                                                      -29-
                         WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
Because the motor initial angle error is big, the motor cannot be activated.
                          2. Set the initial angle so that BASIC  ROTOR POSITION value to be ±1V or less during the manual operation.
       Mroom_Drive   1
                           By Changing the U-angle value, make sure to set under ±1V ROTOR POS value.
    Door_Closed
    1. ANGLE OVER         [When change the u-angle value, please change by 0.03.  please press reset button  check the ROTOR POS value.]
       18:0122:1320:30
                                    Mroom_Drive          1             Mroom_Drive            1                   Mroom_Drive       1
                               Door_Closed                         Door_Closed                                Door_Closed
                               3. MOTOR                           11. U-ANGLE                                DC LINK VOLT :  537.1 V
                               4. FACTORY                                                  2.14               ROTOR POS :       0.7V
                                                                  -30-
                         WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
If the upper level controller is not working properly, disconnect the main power and apply the power again.
CP WATDOG
RESET SW
WD LED
       Mroom_Drive   1
    Door_Closed
    1. CP WATDOG
       18:0122:1320:30                1.   turn off Main power switch.
                                      2.   After 1 minute, turn on Main power switch.
                                      3.   If the same problem occurs, press reset button.
                                      4.   In spite that take action like this, if the problem remains, please change the main board.
                                                                    -31-
                         WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
       Mroom_Drive   1
    Door_Closed
                                               POWER line
    1. ENC UVW SEQ
       18:0122:1320:30                             U,V,W
                                                                    -32-
                         WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
                                                                                                              U            V             W
        OUTPUT ERR
                          2. Check if inverter output contactor(MC2) is properly working. Refer to COL.1, 3, 5, 9 in electric diagram.
       Mroom_Drive   1
    Door_Closed           2-1. Check the COL. 1 section in MC2 operation.
    1. OUTPUT ERR
       18:0122:1320:30
                                                                    -33-
                         WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
OUTPUT ERR
                                                                 -34-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
              Error                                                        Description / Check point
OUTPUT ERR
        Mroom_Drive
     Door_Closed
                      1                                                      Cathode
                                                                                               (ㅡ)                    0.70v           Normal
     1. EARTH FLT
        18:0122:1320:30                                      Gate
                                                                                                                0L                    Abnormal
                                                                    -35-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
2. If there is no problem in encoder power and board, it should replace the encoder.
                                                                   -36-
                           WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
              Error                                                        Description / Check point
2. If there is no problem in encoder power and board, it should replace the encoder.
                                                                    -37-
                          WBVF INVERTER Parameter
2. MONITOR
  1.3 ERROR
              Error                                                     Description / Check point
Due to the abnormal operation of the inverter current sensor or main board of current offset.
                                      Mroom_Drive        1
         OFFSET ERR
                                  Door_Closed
                                  3. CURRENT SCALE
                                                  26.86 m
                                                                   -38-
                                 WBVF INVERTER Parameter
2. MONITOR
  1.4 FLOOR DATA
PLDL, PLDM, PLDH, PLDH 2 POS mm Indicates the position of DOWN direction forced deceleration switches.
                                                  Indicates the position of UP direction forced deceleration switches. If there are difference
    PLUL , PLUM, PLUH, PLUH 2 POS        mm
                                                  between these data and switches’ actual position(±200mm), Auto drive is not available.
SDF POS / SUF POS mm Indicates the lowest / highest floor check signal position
PLDL / PLUL 650 1050 1500 1500 1500 1500 1500 1500
DLS / ULS
                                                                         -39-
                        WBVF INVERTER Parameter
3. PROGRAM
   2.1 CONTROL
02 E/L ROPING 2.0 • E/L ROPING It sets the roping value of the elevator.
                                         Input the current maximum number of rotations of the motor. The MAX RPM value according to t
 03 MAX RPM             95.5     RPM
                                        he elevator speed is as follows. (Input up to the first decimal point.)
05 INSPECT RPM 23.9 RPM • INSPECT RPM It is the number of motor rotations (RPM) during the manual operation.
06 CREEP RPM 3.2 RPM • CPEEP RPM CREEP It is the number of motor rotations (RPM) during CREEP operation.
07 RELEVEL RPM 3.2 RPM • RELEVEL RPM RELEVEL It is the number of motor rotations (RPM) during RELEVEL operation..
08 FLR INIT DRV MPM 30 MPM • FLR INIT DRV MPM It shows the overall height measurement speed.
                                        •   MAX FLOOR Enter the maximum floor. Make sure to enter before carrying out the overall heig
 10 MAX FLOOR            4        FL
                                        ht measurement.
                                        It adjusts the time to start decelerating during a secondary pattern long run operation. If this valu
 13 2th MIN LENGTH       60      mm
                                        e gets higher, deceleration starts earlier, resulting in a longer creep distance.
                                        It adjusts the time to start decelerating during a secondary pattern short run operation. If this valu
 14 2th MIN LENGTH S     60      mm
                                        e gets higher, deceleration starts earlier, resulting in a longer creep distance.
                                        •    FWD DIRECTION It is used when UP/DOWN is switched in accordance with the mounting posi
 17 FWD DIRECTION        UP
                                        tion of the motor.
                                                        -40-
                        WBVF INVERTER Parameter
3. PROGRAM
   2.1 CONTROL
18 GOVENNOR SEL FWD • GOVERNOR SEL It sets if the governor is used and the direction of it.
19 TQBIAS SELEC No use • TQBIAS SELEC It decides whether to use load compensation.
                                         •   LS DATA 0% When you use LS Board for load compensation, it reads the BASIC LOAD PULSE
 23 LS 0%L DATA          0.0
                                         value at no load state and inputs this value
                                         •   LS DATA 50% When you use LS Board for load compensation, it reads the BASIC LOAD PULSE
 24 LS 50%L DATA         0.0
                                         value at Balance state and inputs this value.
                                         •   TQ BIAS GAIN When you use LS Board for load compensation, after the input of LOAD PULSE
 25 LS TOQUE GAIN        0        %      0% value and LOAD PULSE 50%, it sets the TQ BIAS GAIN value to decide load compensation value
                                         . If you do not want the load compensation, you can input 0 for this value
                                         It is the data which sets the inertia of the controller in the elevator speed control system. Adjust thi
 26 SC JM                35      Kg/m2
                                         s value when vibrations occur in the elevator or motor.
                                         •   SC FF GAIN It shows the switching compensation gain value to improve excessive properties u
 27 SC FEED FWD GAIN     0.2
                                         pon a motor acceleration or deceleration.
                                                          -41-
                       WBVF INVERTER Parameter
3. PROGRAM
   2.1 CONTROL
36 VANE OFFSET 0.0 mm • VANE OFFSET It is the data setting the offset value of the VANE sensor
                                       Upon compensating the load (LV12 TQBIAS) using the load switch, the load compensation torque i
 43 LV12 UP 30%SW       0        %
                                       s generated by the set rate when the 30% switch is input.
                                       Upon compensating the load (LV12 TQBIAS) using the load switch, the load compensation torque i
 44 LV12 UP 70%SW      50%       %
                                       s generated by the set rate when the 70% switch is input..
                                       Upon compensating the load (LV12 TQBIAS) using the load switch, the load compensation torque i
 45 LV12 DN 30%SW      -50%      %
                                       s generated by the set rate when the 30% switch is input
                                       Upon compensating the load (LV12 TQBIAS) using the load switch, the load compensation torque i
 46 LV12 DN 70%SW       0        %
                                       s generated by the set rate when the 70% switch is input..
48 MOTOR THERMAL OFF • MOTOR THERMAL The data determining if motor overheating signal is used.
                                                       -42-
                          WBVF INVERTER Parameter
3. PROGRAM
   2.3 MOTOR
03 MOT RATING V 318 Vrms • RATING V It shows the rated voltage of MOTOR.
05 MOTOR POLES 32 POLES • MOTOR POLES It shows the number of poles of MOTOR.
                                              Since the standard encoder used by Hyundai Elevator is SINCOS encoder (2048PPR) of 32768 PULSE,
                                              32768 PULSE is set as the factory default value. If an encoder of a different number of pulses should
 06 ENCODER PPR          32768         P/R
                                              be used, enter the number of encoder pulses in PROGRAM \ MOTOR \ ENCODER PPR for speed fee
                                              dback.
08 IQSE RATE 21.2 Apeak • IQSE RATE It shows the maximum torque current.
                                              It shows how to judge initial angle. At the factory ship-out, the initial angle is already set and the dat
                                              a is written on the connector BOX, but it should be set again for Encoder failure and replacement. Th
 09 KNOW U ANGLE          YES                 e methods to find the initial angle are divided to inserting PULSE (ANGEL METHOD: “PULSE”) and inse
                                              rting DC (ANGEL METHOD: “DC ALIGN”). If there is no rope, both are possible, but DC insertion is pre
                                              cise, and if there is a rope, use PULSE insertion.
                                              It shows how to find the initial angle. If it is “PULSE”, it is PULSE insertion method, and if it is “DC ALI
 11 ANGLE MRTHOD       DC Inject
                                              GN”, it means DC insertion method.
                                                                -43-
                          WBVF INVERTER Parameter
3. PROGRAM
  2.4 FACTORY
01 INVERTER CAPACIT WB100GT 7.5kW • INVETER CAPACITY It sets the rated capacity of the inverter.
                                               •     MOTOR TYPE It determined if the operated motor is the induction motor or synchronous mot
02 MOTOR TYPE         Synchro. Motor
                                               or.
                                               •     INPUT VOLTAGE It sets the three phase input voltage of the inverter (Select 1 of 380V, 440V
05 INPUT VOLTAGE           380          Vac
                                               and 480V).
06 ELD INPUT VOLT 380 Vac • ELD INPUT VOLT It sets the ELD input voltage.
07 TORQUE LIMIT 160 % • TORQUE LIMIT It determines the maximum output current of the inverter.
                                               It shows the scale upon sensing the DC LINK voltage. If the actual DC link voltage doesn’t match th
08 SCALE DC VOLT          0.350
                                               e displayed DC LINK voltage, change this value (Refer to MONITOR\BASIC\DC LINK VOLT item).
                                               It shows the scale upon sensing the output current of the inverter. It is determined by the TURN R
09 SCALE CURRENT          24.42
                                               ATIO of the current SENSOR.
13 INV. OC LEVEL 45 Apeak • INV OC LEVEL It shows the over-current level of the inverter.
                                                                -44-
                                 WBVF INVERTER Parameter
3. PROGRAM
  2.4 FACTORY
17 ACCELATION 800 mm/s2 • ACCELERATION It sets the slope of the speed upon accelerating or decelerating
                                                     Set as shown below in accordance with the mounting direction of the encoder. If the encoder leaf
     18 ENCODER DIR                FWD               spring is facing the direction of the motor, set to “FWD”, and if the encoder leaf spring is facing th
                                                     e opposite direction, set to “REV”.
32 ENCODER TYPE SINCOS ENC • ENCODER TYPE It is the data setting the encoder type.
30 or less 0.5
60 0.7
30 or less 0.5
                                                              45~120                                                        0.6
             Synchronous motor
                                                             150~210                                                        0.7
                                                                      -45-
                       WBVF INVERTER Parameter
3. PROGRAM
  2.4 FACTORY
                                        Turn it off and measure upon resetting the SIN COS values. It is turned on automatically after meas
 33 SINCOS THETA        OFF
                                        uring..
                                        It shows the maximum value of the SIN wave upon using a SINCOS encoder. Upon setting the initi
 34 SIN MAX              0
                                        al angle with a SINCOS encoder, make sure to rotate the motor to set the SINMAX value.
                                        It shows the minimum value of the SIN wave upon using a SINCOS encoder. Upon setting the initia
 35 SIN MIN             1000
                                        l angle with a SINCOS encoder, make sure to rotate the motor to set the SINMIN value.
                                        It shows the maximum value of the COS wave upon using a SINCOS encoder. Upon setting the initi
 36 COS MAX              0
                                        al angle with a SINCOS encoder, make sure to rotate the motor to set the COSMAX value.
                                        It shows the minimum value of the COS wave upon using a SINCOS encoder. Upon setting the initi
 37 COS MIN             1000
                                        al angle with a SINCOS encoder, make sure to rotate the motor to set the COSMIN value SINCOS.
44 ERROR ERASE OFF • ERROR ERASE It erases the error saved in HHT.
46 EEPROM VERSION • EEPROM VERSION It shows the EEPROM version inside the MCU.
                                        •    INIT EEPROM Reset by setting it to 1 when a VERSION ERROR occurs as the current program
 47 INIT EEPROM         OFF
                                        version doesn’t match the EEPROM version or to set to the factory default value.
                                                       -46-
                           WBVF INVERTER Parameter
3. PROGRAM
  2.4 FACTORY
CURRENT SCALE
                                                                   -47-
                             WBVF INVERTER Parameter
3. PROGRAM
  2.4 FACTORY
INV OC LEVEL
2.9kW 14
3.9kW 22
5.5~7.5kW 45
11kW 65
15kW 85
22kW 150
30kW 200
-48-