Temperature

Thermocouple
Industrial assembly
Model TC10-0
WIKA data sheet TE 66.01

for further approvals


see page 2

Applications
■ Chemical and petrochemical industries
■ Machinery, plant and tank measurement
■ Oil and gas industries
■ Power and utilities
■ Pulp and paper

Special features
■ Sensor ranges from -40 ... +1,260 °C [-40 ... +2,300 °F]
■ For mounting in all standard thermowell designs
■ Spring-loaded measuring insert (replaceable)
■ Explosion-protected versions
■ Fixed fitting (welded) measuring insert

Description

Thermocouples in this series can be combined with a large


number of thermowell designs. Use without a thermowell is
permitted when using a fixed (welded) fitting. Thermocouple, model TC10-0, industrial assembly

A wide variety of possible combinations of sensor,


connection head, insertion length, neck length, connection to
thermowell etc. are available for the thermometers; suitable
for almost any thermowell dimension.

WIKA data sheet TE 66.01 ∙ 11/2021 Page 1 of 13


Representation of the components

Tapered threads

3112147.02
Parallel threads

3112287.01
[Ø0,55 inch]

Legend:
 Connection head A (U2) Insertion length (tapered threads)
 Neck tube A (l1) Insertion length (parallel threads)
 Connection to thermowell l5 Measuring insert length
 Measuring insert Ød Measuring insert diameter
 Transmitter (option) NL Nominal length
 Flame path fitting N (MH) Neck length

Overview of approvals for explosion protection

Approval Explosion protection


Ex i (gas) Ex i (dust) Ex d (gas) Ex d (dust) Ex e (gas) Ex n (gas)
Zone 0, 1, 2 Zone 20, 21, 22 Zone 1, 2 Zone 21 Zone 1, 2 Zone 2
ATEX x x x x x x
IECEx x x x x x x
FM - - x x - -
CSA - - x x - -
EAC x x x x - x
Ex Ukraine x x x x - -
INMETRO x x - - - -
CCC x x x x x x

→ For detailed information, see page 11

WIKA data sheet TE 66.01 ∙ 11/2021 Page 2 of 13


Measuring element

Measuring element
Type of sensor Thermocouple per IEC 60584-1 or ASTM E230
Types K, J, E, N, T
Hot junction ■ Ungrounded (standard)
■ Grounded (welded to the sheath)

Marking of the polarity The colour coding at the positive poles of the instrument decides the
correlation of polarity and terminal
Single thermocouple

Dual thermocouple

Validity limits of the class accuracy per EN 60584-1


Type K Class 2 -40 ... +1,200 °C [-40 ... +2,192 °F]
Class 1 -40 ... +1,000 °C [-40 ... +1,832 °F]
Type J Class 2 -40 ... +750 °C [-40 ... +1,382 °F]
Class 1 -40 ... +750 °C [-40 ... +1,382 °F]
Type E Class 2 -40 ... +900 °C [-40 ... +1,652 °F]
Class 1 -40 ... +800 °C [-40 ... +1,472 °F]
Type N Class 2 -40 ... +1,200 °C [-40 ... +2,192 °F]
Class 1 -40 ... +1,000 °C [-40 ... +1,832 °F]
Type T Class 2 -40 ... +350 °C [-40 ... +662 °F]
Class 1 -40 ... +350 °C [-40 ... +662 °F]
Validity limits of the class accuracy in accordance with ASTM-E230
Type K Standard 0 ... 1,260 °C [32 ... 2,300 °F]
Special 0 ... 1,260 °C [32 ... 2,300 °F]
Type J Standard 0 ... 760 °C [32 ... 1,400 °F]
Special 0 ... 760 °C [32 ... 1,400 °F]
Type E Standard 0 ... 870 °C [32 ... 1,598 °F]
Special 0 ... 870 °C [32 ... 1,598 °F]
Type N Standard 0 ... 1,260 °C [32 ... 2,300 °F]
Special 0 ... 1,260 °C [32 ... 2,300 °F]
Type T Standard 0 ... 370 °C [32 ... 698 °F]
Special 0 ... 370 °C [32 ... 698 °F]

→ For detailed specifications for thermocouples, see IEC 60584-1 or The actual operating temperature of the thermometer
ASTM E230 and Technical Information IN 00.23 at www.wika.com. is limited both by the maximum permissible working
temperature and the diameter of both the thermocouple and
The table shows the temperature ranges listed in the
the sheathed cable, as well as by the maximum permissible
respective standards, in which the tolerance values (class
working temperature of the thermowell material.
accuracies) are valid.

For the tolerance value of thermocouples, a cold junction


temperature of 0 °C has been taken as the basis.

WIKA data sheet TE 66.01 ∙ 11/2021 Page 3 of 13


Connection head

European designs per EN 50446 / DIN 43735

Model Material Cable entry Ingress protection Cap Surface Connection


thread size (max.) 1) to neck
IEC/EN 60529 tube
BS Aluminium ■ M20 x 1.5 IP65 2) Flat cover with Blue, painted ■ M24 x 1.5
■ ½ NPT 2 screws (RAL 5022) ■ ½ NPT

JS BS BSZ-H
BSZ, BSZ-K Aluminium
BSZ-H, BSZ-HK ■ M20 x 1.5
BSS IP65 2) BSS-H Raised
BVS hinged BVS (NuG) Blue, painted 1/4000■ M24 x 1.5 5/6000 7/8

■ ½ NPT cover with cylinder (RAL 5022) ■ ½ NPT


head screw

BSZ, BSZ-K BSZ-H, BSZ-HK BSS BSS-H BVS BVS (NuG) 1/4000 5/6000 7/8000 7/8000 DIH50 andere Anschluss

Model Explosion protection


Without Ex i (gas) Ex i (dust) Ex e (gas) Ex t (dust)
Zone 0, 1, 2 Zone 20, 21, 22 Zone 1, 2 Zone 21, 22
BS x x - - -
BSZ-H x x x x 3) x 3)

North American designs


Model Material Cable entry Ingress protection Cap Surface Connection
thread size (max.) 1) to neck
IEC/EN 60529 tube
KN4-A Aluminium ■ ½ NPT IP65 2) Screw-on lid Blue, painted ■ M24 x 1.5
■ M20 x 1.5 (RAL 5022) ■ ½ NPT
KN4-P 4) Polypropylene ½ NPT IP65 2) Screw-on lid White ½ NPT

1/4000 F Aluminium ■ ½ NPT IP66 2) Screw-on lid Blue, painted ½ NPT


ndere Anschlussgehäuse KN4-P BVC

■ ¾ NPT (RAL 5022)


■ M20 x 1.5
1/4000 S Stainless steel ■ ½ NPT IP66 2) Screw-on lid Natural finish ½ NPT
S (NuG) 1/4000 5/6000 7/8000
¾DIH50
■7/8000 NPT andere Anschlussgehäuse KN4-P BVC

■ M20 x 1.5
7/8000 W Aluminium ■ ½ NPT IP66 2) Screw-on lid Blue, painted ½ NPT
■ ¾ NPT (RAL 5022)
■ M20 x 1.5
7/8000 S Stainless steel ■ ½ NPT IP66 2) Screw-on lid Natural finish ½ NPT
5/6000 7/8000 7/8000 DIH50 andere Anschlussgehäuse
¾ NPT
■ KN4-P BVC

■ M20 x 1.5

Model Explosion protection


Without Ex i (gas) Ex i (dust) Ex t (dust) Ex nA (gas)
Zone 0, 1, 2 Zone 20, 21, 22 Zone 21, 22 Zone 2
KN4-A x x - - -
KN4-P 4) x - - - -
1/4000 F x x - - -
1/4000 S x x - - -
7/8000 W x x - - -
7/8000 S x x - - -

1) IP ingress protection of the connection head. The IP ingress protection of the complete TC10-0 instrument does not necessarily have to correspond to the connection head.
2) Ingress protections, describing temporary or permanent immersion, on request; Suitable sealing/cable gland required
3) Only ATEX and CCC
4) On request

Other connections heads are available.

WIKA data sheet TE 66.01 ∙ 11/2021 Page 4 of 13


Measuring insert

Measuring insert
Versions Vibration-resistant, sheathed cable (mineral-insulated cable, MI cable)
Optimal heat transfer Requirement ■ Correct measuring insert length
■ Correct measuring insert diameter

Bore diameter of the Max. 1 mm [0.04 in] larger than measuring insert diameter
thermowell
Gap width For joint width > 0.5 mm [> 0.02 in] between thermowell and measuring insert:
→ Negative impact on heat transfer
→ Unfavourable response behaviour of the thermometer
Measuring insert ■ 3.0 mm
diameter Ø d ■ 6.0 mm
■ 8.0 mm
■ 1/8 in or 0.125 in [3.17 mm]
■ 3/16 in or 0.188 in [4.75 mm]
■ 1/4 in or 0.250 in [6.35 mm]
Other measuring insert diameters on request
Insertion length When fitting the measuring insert into a thermowell, it is very important to determine the correct insertion
length (= thermowell length for bottom thicknesses of ≤ 5.5 mm [≤ 0.22 in]). In order to ensure that the
measuring insert is firmly pressed down onto the bottom of the thermowell, the insert must be spring-loaded
(spring travel: 0 ... 10 mm [0 ... 0.39 in]).
Spring travel Max. 10 mm [0.39 in]

Ex d version: Due to the use of a flame path fitting and its fitting tolerances, the use of standard measuring inserts for
replacement requirements is not allowed!

Design prepared for Design with mounted NAMUR NAMUR


NAMUR
transmitter mounting transmitter
Spring-loaded screw
Connection
Insulation washer
terminal
[2,36]

[2,36]
Terminal plate
[0,06]

[0,06]
1,560

60
1,5

Ø42 Ø42 Ø42 33 33


33
[Ø1,65][Ø1,65]
[Ø1,65] [1,30] [1,30]
[1,30]

11466252.04
Ød Ød
Ød
l5

l5

Ø6 Ø6 Ø6
[Ø0,23]
[Ø0,23][Ø0,23]

Ø8 Ø8 Ø8
[Ø0,31]
[Ø0,31][Ø0,31]

Legend:
l5 Measuring insert length
Ø d Measuring insert diameter

WIKA data sheet TE 66.01 ∙ 11/2021 Page 5 of 13


Transmitter

Transmitter models Model T16 Model T32


Transmitter data sheet TE 16.01 TE 32.04
Figure

Output
4 ... 20 mA x x
HART® protocol - x
Input ■ Type K ■ Type K
■ Type J ■ Type J
■ Type E ■ Type E
■ Type N ■ Type N
■ Type T ■ Type T
Explosion protection Option Option

Possible mounting positions for transmitters Model T16 Model T32


BS ○ -
BSZ-H ● ●
KN4-A ○ ○
KN4-P ○ ○
1/4000 ○ ○
7/8000 ○ ○

Legend:
○ Mounted instead of terminal block
● Mounted within the cover of the connection head
- Mounting not possible

The mounting of a transmitter on the measuring insert is possible with all the connection heads listed here. The fitting of a
transmitter in the (screw) cap of a North American design connection head is not possible.
Mounting of 2 transmitters on request.
For a correct determination of the overall measuring deviation, the sensor and transmitter measuring deviations must be
added.

Functional safety with model T32


temperature transmitter (option) SIL IEC 61508 / IEC 61511

In safety-critical applications, the entire measuring → For detailed specifications, see Technical information
chain must be taken into consideration in terms of the safety IN 00.19 at www.wika.com.
parameters. The SIL classification allows the assessment of
the risk reduction achieved by the safety installations.

Selected TC10-0 thermocouples, in combination with


a suitable temperature transmitter (e.g. model T32.1S,
TÜV-certified SIL version for protection systems developed
in accordance with IEC 61508), are suitable as sensors for
safety functions to SIL 2.

WIKA data sheet TE 66.01 ∙ 11/2021 Page 6 of 13


Operating conditions

Operating conditions
Ambient and storage temperature -40 ... +80 °C [-40 ... +176 °F]
Vibration resistance The information on vibration resistance refers to the tip of the measuring insert.
→ For detailed specifications on the vibration resistance of Pt100 sensors, see Technical
information IN 00.17 at www.wika.de.
Standard 6 g peak-to-peak, wire-wound measuring resistor or thin film
Option ■ Vibration-resistant probe tip, max. 20 g peak-to-peak, thin-film measuring resistor
■ Highly vibration-resistant probe tip, max. 50 g peak-to-peak, thin-film measuring resistor

IP ingress protection per IEC/EN 60529

First index number Degree of protection / Short description Test parameters


Degrees of protection against solid foreign bodies (defined by the 1st index number)
5 Dust-protected Per IEC/EN 60529
6 Dust-tight Per IEC/EN 60529
Degrees of protection against water (defined by the 2nd index number)
4 Protected against splash water Per IEC/EN 60529
5 Protected against water jets Per IEC/EN 60529
6 Protected against strong water jets Per IEC/EN 60529
7 1) Protected against the effects of temporary immersion in water Per IEC/EN 60529
8 1) Protected against the effects of permanent immersion in water As agreed upon

1) Ingress protections, describing temporary or permanent immersion, on request

Standard ingress protection of model TC10-0 is IP65.

The specified degrees of protection apply under the following


conditions:
■ Use of a suitable thermowell
(without suitable thermowell: IP40)
■ Use of a suitable cable gland
■ Use of a cable cross-section appropriate for the gland or
select the appropriate cable gland for the available cable
■ Adhere to the tightening torques for all threaded
connections

WIKA data sheet TE 66.01 ∙ 11/2021 Page 7 of 13


Thermowell (option)

Thermowell selection
Model Data sheet Illustration
TW10 TW 95.10

TW15 TW 95.15

TW20 TW 95.20

TW25 TW 95.25

TW30 TW 95.30

TW31 TW 95.31

TW50 TW 95.50

TW55 TW 95.55

Special thermowells on request

WIKA data sheet TE 66.01 ∙ 11/2021 Page 8 of 13


Approvals

Logo Description Country


EU declaration of conformity European Union
EMC directive 1)
EN 61326 emission (group 1, class B) and immunity (industrial application)
RoHS directive

Optional approvals

Logo Description Country


EU declaration of conformity European Union
ATEX directive
Hazardous areas
- Ex i Zone 0 gas II 1G Ex ia IIC T1 ... T6 Ga
Zone 1 mounting to zone 0 gas II 1/2G Ex ia IIC T1 ... T6 Ga/Gb
Zone 1 gas II 2G Ex ia IIC T1 ... T6 Gb
Zone 20 dust II 1D Ex ia IIIC T125 ... T65 °C Da
Zone 21 mounting to zone 20 dust II 1/2D Ex ia IIIC T125 ... T65 °C Da/Db
Zone 21 dust II 2D Ex ia IIIC T125 ... T65 °C Db
- Ex d Zone 1 gas II 2G Ex db IIB + H2 T6 ... T4 Gb
Zone 1 gas II 2G Ex db IIC T6 ... T4 Gb
Zone 21 dust II 2D Ex tb IIIC T85 °C Db IP66
- Ex e Zone 1 gas II 2G Ex eb IIC T1 ... T6 Gb 3)
Zone 2 gas II 3G Ex ec IIC T1 ... T6 Gc X
Zone 21 dust II 2D Ex tb IIIC TX °C Db 3)
Zone 22 dust II 3D Ex tc IIIC TX °C Dc X
- Ex n Zone 2 gas II 3G Ex nA IIC T1 ... T6 Gc X
Zone 22 dust II 3D Ex tc IIIC TX °C Dc X
IECEx - in combination with ATEX International
Hazardous areas
- Ex i Zone 0 gas Ex ia IIC T1 ... T6 Ga
Zone 1 mounting to zone 0 gas Ex ia IIC T1 ... T6 Ga/Gb
Zone 1 gas Ex ia IIC T1 ... T6 Gb
Zone 20 dust Ex ia IIIC T125 ... T65 °C Da
Zone 21 mounting to zone 20 dust Ex ia IIIC T125 ... T65 °C Da/Db
Zone 21 dust Ex ia IIIC T125 ... T65 °C Db
- Ex d Zone 1 gas Ex db IIB + H2 T6 ... T4 Gb
Zone 1 gas Ex db IIC T6 ... T4 Gb
Zone 21 dust Ex tb IIIC T85 °C Db IP66
- Ex e 2) Zone 1 gas Ex eb IIC T1 ... T6 Gb 3)
Zone 2 gas Ex ec IIC T1 ... T6 Gc X
Zone 21 dust Ex tb IIIC TX °C Db 3)
Zone 22 dust Ex tc IIIC TX °C Dc X
- Ex n 2) Zone 2 gas Ex nA IIC T1 ... T6 Gc X
Zone 22 dust Ex tc IIIC TX °C Dc X
FM USA and Canada
Hazardous areas
- Ex d (XP) Division 1 gas Class I, division 1, group B, C, D, T6 type 4/4X
Division 1 dust Class II or III, division 1, group E, F, G type 4/4X
CSA
Safety (e.g. electr. safety, overpressure, ...)
Hazardous areas USA and Canada
- Ex d (XP) Division 1 gas Class I, division 1, groups B, C, D, T6 type 4/4X
Division 1 dust Class II, groups E, F, G
Division 1 dust Class III, T6 type 4/4X
- Ex d (FP - CAN) Zone 1 gas Ex d IIC Gb T6/T5/T4
Ex d IIB + H2 Gb T6/T5/T4
- Ex d (FP - USA) Zone 1 gas Class I, zone 1, AEx d IIC Gb T6/T5/T4
Zone 1 gas Class I, zone 1, AEx d IIB + H2 Gb T6/T5/T4

WIKA data sheet TE 66.01 ∙ 11/2021 Page 9 of 13


Logo Description Country
EAC (option) Eurasian Economic
Hazardous areas Community
- Ex i Zone 0 gas 0Ex ia IIC T6 ... T1 Ga X
Zone 1 gas 1Ex ia IIC T6 ... T1 Gb X
Zone 20 dust Ex ia IIIC T80 ... T440 °C Da X
Zone 21 dust Ex ia IIIC T80 ... T440 °C Db X
- Ex d Zone 1 gas 1Ex d IIC T6 ... T4 Gb X
Zone 21 dust Ex tb IIIC T85 °C Db X
- Ex n Zone 2 gas 2Ex nA IIC T6 ... T1 Gc X
Ex Ukraine Ukraine
Hazardous areas
- Ex i Zone 0 gas II 1G Ex ia IIC T1 ... T6 Ga
Zone 1 mounting to zone 0 gas II 1/2G Ex ia IIC T1 ... T6 Ga/Gb
Zone 1 gas II 2G Ex ia IIC T1 ... T6 Gb
- Ex d Zone 1 gas II 2G Ex db IIB+H2 T6 ... T4 Gb
Zone 1 gas II 2G Ex db IIC T6 ... T4 Gb
Zone 1 mounting to zone 0 gas II 1/2G Ex db IIC T6 ... T4 Ga/Gb
Zone 21 dust II 2D Ex tb IIIC T85 °C Db
INMETRO Brazil
Hazardous areas
- Ex i Zone 0 gas II 1G Ex ia IIC T1 ... T6 Ga
Zone 1 mounting to zone 0 gas II 1/2G Ex ia IIC T1 ... T6 Ga/Gb
Zone 20 dust Ex ia IIIC T125 ... T65 °C Da
Zone 21 mounting to zone 20 dust Ex ia IIIC T125 ... T65 °C Da/Db
CCC 3) China
Hazardous areas
- Ex i Zone 0 gas Ex ia IIC T1 ~ T6 Ga
Zone 1 gas Ex ia IIC T1 ~ T6 Gb
Zone 1 mounting to zone 0 gas Ex ia IIC T1 ~ T6 Ga/Gb
Zone 2 gas Ex ic IIC T1 ~ T6 Gc
Zone 21 dust Ex iaD 21 T65/T95/T125°C
- Ex d Zone 1 gas Ex d IIB+H2 T4~T6 Gb
Zone 1 gas Ex d IIC T4~T6 Gb
Zone 21 dust Ex tD A21 IP66 T85°C
- Ex e 2) Zone 1 gas Ex eb IIC T1~T6 Gb
Zone 2 gas Ex ec IIC T1~T6 Gc
- Ex n 2) Zone 2 gas Ex nA IIC T1 ~ T6 Gc
GOST Russia
Metrology, measurement technology
KazInMetr Kazakhstan
Metrology, measurement technology
- MTSCHS Kazakhstan
Permission for commissioning
BelGIM Belarus
Metrology, measurement technology
- UkrSEPRO Ukraine
Metrology, measurement technology
Uzstandard Uzbekistan
Metrology, measurement technology

1) Only for built-in transmitter


2) Only for connection head model BSZ, BSZ-H, 1/4000, 5/6000 or 7/8000 (see “Connection head”)
3) Without transmitter

Instruments marked with “ia” may also be used in areas only requiring instruments marked with “ib” or “ic”. If an instrument with
“ia” marking has been used in an area with requirements in accordance with “ib” or “ic”, it can no longer be operated in areas
with requirements in accordance with “ia” afterwards.

WIKA data sheet TE 66.01 ∙ 11/2021 Page 10 of 13


Explosion protection (option)
The permissible power, Pmax, as well as the permissible
ambient temperature, for the respective category can be
seen on the certificate for hazardous areas or in the operating
instructions.

Attention:
Only with the correspondingly suitable components is
operation in Ex hazardous areas permissible.

Transmitters have own certificates for hazardous areas.


The permissible ambient temperature ranges of the built-in
transmitters can be taken from the corresponding transmitter
operating instructions and approvals.

Certificates (option)

Certification type Measurement accuracy Material certificate


2.2 test report x x
3.1 inspection certificate x x
DAkkS calibration certificate x -

For calibration, the measuring insert is removed from the


thermometer. The minimum length (metal part of the probe)
for carrying out a measurement accuracy test 3.1 or DAkkS is
100 mm [3.94 in].
Calibration of shorter lengths on request.

The different certifications can be combined with each other.

→ Approvals and certificates, see website

WIKA data sheet TE 66.01 ∙ 11/2021 Page 11 of 13


1
Connection
2
to thermowell
3 4 5 6 7

The many possible designs ensure that the model TC10-0 thermocouple can be combined with almost all possible
thermowells. The most usual designs of connection are shown in the following drawings; further connections on request.

Versions with “nipple-union-nipple” neck tube Versions with non-divisible neck tube

14511079.01
[ca. 5 inch]

[ca. 5 inch]
ca.127 mm

ca.127 mm
1/2"NPT

M20x1,5 M20x1,5
KE

[N (MH)= 5,90 inch]


[N (MH)= 5,90 inch]

[N (MH)= 5,90 inch]

[N (MH)= 5,90 inch]


N (MH) = 150 mm

N (MH) = 150 mm

N (MH) = 150 mm

N (MH) = 150 mm
Ø14 mm
[Ø0,55 inch]
Ø14 mm
[Ø0,55 inch]

KE
KE

Gewinde (NPT)
Thread Thread
Gewinde Gewinde(NPT)
Thread

A (U2)
A (l1)
A (U2)

Thread
Gewinde
A (l1)

Ød Ød Ød Ød

Without neck tube Standard thread sizes of the male


Double threaded hex bushing
threads at the neck tube
(tube section)
Connection thread to the thermowell

KLI-ZCHG TX10-0 M.HA RO
G½B drawing numbe
TX10-0
■ G¾B TX10-0
material
■ M14 x 1.5 scale modified 03.09.21 ARGADEA reference
1:1 released 03.09.21 THIESR UV/DR 08
raw ■ M18
nominal x 1.5 comments

■ ½ NPT
part size
Check indicator
SIZE ISO 14405 GG units ALEXAND
■ ¾ NPT language mm
GER/ENG
ISO 8015 [inch]
1 2 3 4 5 6 7
Connection thread to the head
14111563.02

3160670.07

■ M20 x 1.5
■ ½ NPT
■ 3/4 NPT
■ M24 x 1.5

Legend:
A (l1) Insertion length (parallel threads)
A (U2) Insertion length (tapered threads)
l5 Measuring insert length
N (MH) Neck length
Ød Measuring insert diameter
tapered thread CT Thread cable entry
P Thread to the thermowell
KE Screw-in length by hand
- with ½ NPT approx. 8.1 mm [0.32 in]
The figures show examples of connection heads. - with ¾ NPT approx. 8.6 mm [0.34 in]

WIKA data sheet TE 66.01 ∙ 11/2021 Page 12 of 13


Ordering information
Model / Explosion protection / Process connection / Version and material of threaded connection / Thread size / Measuring
element / Connection method / Temperature range / Sensor diameter / Insertion length A / Neck length N(MH) / Certificates /
Options

© 11/2021 WIKA Alexander Wiegand SE & Co. KG, all rights reserved.
The specifications given in this document represent the state of engineering at the time of publishing.
We reserve the right to make modifications to the specifications and materials.

WIKA data sheet TE 66.01 ∙ 11/2021 Page 13 of 13


11/2021 EN

WIKA Alexander Wiegand SE & Co. KG


Alexander-Wiegand-Straße 30
63911 Klingenberg/Germany
Tel. +49 9372 132-0
Fax +49 9372 132-406
info@wika.de
www.wika.de