NORA Silver Chapter 9
NORA Silver Chapter 9
Chapter 9
Ignition Systems
Chapter 9
Ignition Systems
Ceramic
Insulator
Ignition
Transformer
Oilburners use one of two types of higher with intermittent ignition because
electric ignition control systems: the spark burns nitrogen, creating NOx.
Interrupted ignition: the ignition spark
remains on for only a short time at the A strong spark
beginning of each burner operating cycle, The spark across the electrode gap at the
and is turned off once flame is established. tips of the electrodes must be strong
enough to withstand the velocity of the air
Intermittent ignition: the spark that
being blown through the air tube by the
ignites the oil vapors remains on as long as
burner fan. The air being blown through
the burner runs. Intermittent ignition used
the air tube forces the ignition spark to
to be called “constant ignition,” and some
form an arc toward the oil spray. This arc
manufacturers call intermittent ignition
extends into the spray causing the oil
“constant duty ignition.”
vapors to ignite, and the flame to establish.
The ignition voltage must be high enough
Interrupted ignition to create a spark that is hot enough to ignite
is better the oil. In some cases, widening the spark
Over time, the industry has switched will produce better ignition.
between interrupted and intermittent
ignition. Interrupted ignition has proven The transformer
superior because having the spark on The AC transformer is a device that
during the entire burn cycle detracts from receives electricity at one voltage and
performance for several reasons: delivers it at another voltage, either higher
• Electrode life is significantly reduced. or lower.
Figure 9-2:
Step-up transformers are used for ignition Transformer wiring
purposes on oilburners.
Generally, it will be found that ignition
transformers are made up of 90 to 100
Iron Magnetic
turns of fine wire in the secondary coil to Core Field
one turn of stout wire in the primary coil.
In the example, you will note there are
60,000 turns in the secondary and 690 turns
in the primary coil, a ratio of about 90 to
1. In Figure 9-3 on following page, we can Primary
Secondary
see what the ignition transformer looks like E = 115V
1 1
Transformer Wiring
E = 10,000 V
2
with its outer case removed. I = 23 ma
2
As voltage increases,
amps decrease
This is a good time to explain a most
important characteristic of transformers,
see Figure 9-2. The rule: If the voltage (E)
flowing out of a transformer is increased,
the current, or amperage (I), is always
decreased proportionately. For instance, if
the voltage is doubled, the current will be
cut in half. In the case of the transformer in
our example, the primary voltage of 115
volts is increased 90 times to 10,000 volts
in the secondary coil, where the current
flow (I2) is 23 milliamperes, which is 23/
1000ths of one ampere. Although not
shown in the example, the current flowing
in the primary coil can be determined by
multiplying .023 x 90, or about 2 amperes,
which is average for ignition transformers. Warning! All high voltage circuits, especially AC
This can be proven in the field by checking circuits, are potentially hazardous. Depending on the
amperage in the primary circuit with an size of the person, contact area and time, and voltage
amperage meter. characteristics (magnitude, frequency, and path),
electric shock can occur and cause bodily damage,
Moisture proofing burns, or death. Use extreme caution at the input or
It is important that both the primary and output end of an ignition transformer!
secondary coils of the ignition transformer
Secondary Primary
Coil No.1 Coil No.1
Secondary
Lead Direction of
Magnetic Flux
Laminated Steel
Magnetic Shunt
Secondary
Lead
Laminated
Steel Core
Mid Point of
Coils Grounded Secondary Primary
Here Coil No. 2 Coil No. 2
Figure 9-3:
Construction
of an ignition
transformer are covered with a tar-like compound, 3. The style of transformer high tension
whereas solid state ignitors feature epoxies clips
which serve the purpose of moisture 4. Secondary coil voltage
proofing the device. Epoxy, by its very
nature, is somewhat more resistant to 5. Primary coil voltage
moisture and acts as an excellent corrosion 6. Transformer body size
inhibitor and heat conductor.
Wiring ignition
If you must replace transformers
a transformer Wire the ignition transformer into the
When ordering replacement transform- burner circuit as follows:
ers, several facts must be known:
For intermittent ignition, attach a wire
1. The size of the mounting base and from the transformer or ignitor to the
location of mounting holes neutral wire, and the other wire to the
2. The position of high tension orange motor wire from the primary
terminals control. See Figure 9-4 for wiring a
Figure 9-4:
Wiring a primary
intermittent
igntion
Figure 9-5:
Wiring a primary control
interrupted ignition
Thermostat
Jumper
the resistance from each ignitor post to former output terminals to within ½
ground, Figure 9-8. Normally, the ignitor to ¾ of an inch apart. Place a
is considered good if the resistance from milliammeter in series with the hot
each post to ground has no more than a line going to the ignitor and turn it
10% difference between posts. Each on, Figure 9-10. Again, the reading
manufacturer is different and they should should stay steady and not vary for
at least five minutes with a strong
blue spark throughout the test while
Figure 9-8: Ohmmeter test
staying within 10% of the rated
amperage draw for the device.
tube, especially when the air tube is long; if of the porcelains and electrodes so that,
they are provided, use them. after adjustment, they cannot shift from
vibration or other causes and alter their
Buss bars are non-insulated heavy gauge
strips of metal that are made by the position. In many cases, the electrode
oilburner manufacturer to the length and holder is incorporated with the air spinner
shape to fit a certain model of burner; they or turbulator.
are not interchangeable with other models.
Spring clips are similar to buss bars, Electrode testing
except that contact with the transformer is and setting
maintained by spring tension. After some Figure 9-12 shows one method for
time, these clips can lose their tension and testing the porcelain insulator of an
prevent proper and desired contact. They electrode for spark leakage. A neon test
should be checked whenever the burner is lamp, with one probe touching the ceramic
serviced. insulator, the other end of the test lamp
free, is shown. By moving the one end of
Electrodes the test lamp over the surface of the
porcelain, it can be easily determined
Electrodes are metal rods made of
whether or not the ceramic insulator is
specialized steels, and partially covered
with a ceramic (porcelain) insulator,
Figure 9-11. These insulators are usually Figure 9-12:
made in two major external diameters Electrode test
(7/16" and 9/16"). As we can see in Do Not Touch
Figure 9-13, these porcelains come in
various lengths. They may be ordered in
individual lengths 4" to 30", or they may
be sized on the job through the use of a
special tool for cutting the porcelain
Figure 9-11: insulator. Neon Test
Electrodes
The porcelains serve two
purposes: They securely
position the electrode rods and Porcelains
they serve as insulators, Wire
protecting the metal rod
against shorting out to the
nozzle assembly. These
insulators are center bored to
fit the metal electrode rods, cracked. If the insulator is defective, the
either 1/8" or 3/32" in neon test lamp will glow when the probe
diameter. reaches the defect.
Electrode holders permit Figure 9-13 is a setting for electrodes
secure and correct mounting when one is not available from the manu-
Correcting faulty junction box. If they are electrode tips are permitted to operate
ignition is loose, tighten them while extending into the oil spray, it will
important. securely. Also check for promote a carbon bridge between the
Delayed or faulty loose connections at all electrode tips, thus shorting out the spark
ignition is the terminals and make sure and ultimately causing ignition failure.
prime cause of
that wire nuts are tight. Clean the electrode tips and set them
puffback.
2. Test the trans- properly.
former. If the trans- 7. Electrodes too close to the nozzle.
former is defective, replace it. It has already been outlined that the
3. Loose connections at electrodes set too close to the nozzle will
either the secondary terminals promote spark shorting out from the
of the transformer, or loose electrode tip to the nozzle, thus creating a
connections where the high tension leads delayed ignition or ignition failure. Set
or buss bars are fastened to the elec- electrode tips according to prescribed
trodes. If these connections are found to be procedure.
loose, attempt to tighten them. If this fails 8. Spark gap too wide. If the spark
to solve the problem, replace the connec- gap is too wide, either there will be no
tors. Also clean out any dust or dirt that spark at all, or the spark will short out at
may have accumulated in or around the some other point along the ignition system.
secondary terminals of the transformer. As Again, set tips as instructed previously.
previously outlined, check the high voltage However, we are learning that in many
leads to determine if the insulation has applications today, and due to the changes
become defective. in fuel oil, a slightly wider than normal gap
4. Remove the porcelain insulators may result in smoother ignition. Ignition of
from the electrode holder to determine fuel is not an exact science and so a couple
whether they are cracked. In many cases of settings may have to be tried to find the
the porcelains will crack beneath the clamp best results.
of the electrode holder. Replace cracked or 9. Insulators not held securely. In the
crazed porcelains, even though they are still event the electrode support bracket is loose,
functioning properly. or the porcelains do not fit properly in the
5. Carbonized insulator. Carbon bracket, it is possible that the electrodes
accumulations on the ceramic insulators may move out of adjustment because of
will conduct electricity, thus causing the burner vibrations. Set electrodes and
spark to short out against either the nozzle tighten the electrode support bracket
adapter, nozzle line, or the electrode holder. securely, but do not overtighten because
The carbon must be removed with a solvent that may crack the ceramic insulators.
or cleaner. Then the insulators must be
10. Puffbacks may be caused by lack
dried and checked for cracks and/or spark
of draft. If it is discovered that the ceramic
leakage. The procedure for checking for
insulators are heavily sooted and/or
spark leakage has been outlined.
carbonized and the electrode tips are
6. Electrodes in oil spray. If the properly gapped and properly set, then it is
Figure 9-14:
Ignition service
help chart
1. 120V ac input wires Brings 120 volt to primary coil Wires must not be pinched against housing
when transformer is closed
5. Insulating compound Keeps moisture out, conducts heat Should not be leaking out
6. Metal cover Protects internal of transformer Should not be punctured or severely dented
7. Mounting base plate Mounts transformer to Must not be bent and cause air to leak
burner housing from around transformer
8. Transformer output Insulates high voltage from ground 1. Must not be cracked
ceramic insulator and opposing terminal. Holds 2. Must be totally clean
ignition spring dimensions
9. Ignition spring terminals Transmits high voltage to 1. Must make good, clean contact to
electrode rods electrode rods
10. Electrode rods Transfers high voltage to electrode tips Must be clean
11. Electrode insulators Mounts electrodes and insulates Must be clean and not cracked
each electrode from ground
12. Arc gap and electrodes Specified gap (1/8” - 5/32”) allows arc 1. Too close causes delayed ignition
to jump to other terminal and ignite 2. Too wide results in no ignition and
possible damage to secondary
3. Clean and properly adjust