DSEG8680 Operator Manual
DSEG8680 Operator Manual
057-327 ISSUE: 4
DSEG8680 Operator Manual
E-mail: sales@deepseaelectronics.com
Website: www.deepseaelectronics.com
Operator Manual
The DSE logo and the names DSEGenset®, DSEATS®, DSEPower® and DSEControl® are UK
registered trademarks of Deep Sea Electronics Ltd.
Any reference to trademarked product names used within this publication is owned by their respective
companies.
Deep Sea Electronics Ltd reserves the right to change the contents of this document without prior
notice.
Typeface: The typeface used in this document is Arial. Care must be taken not to mistake the upper-case letter I with the numeral 1. The numeral
1 has a top serif to avoid this confusion.
TABLE OF CONTENTS
Section Page
1 INTRODUCTION .................................................................................................. 6
1.1 CLARIFICATION OF NOTATION ............................................................................................ 7
1.2 GLOSSARY OF TERMS .......................................................................................................... 7
1.3 BIBLIOGRAPHY ...................................................................................................................... 9
INSTALLATION INSTRUCTIONS ..................................................................................... 9
2 MANUALS ......................................................................................................... 10
TRAINING GUIDES ........................................................................................................ 11
THIRD PARTY DOCUMENTS ........................................................................................ 12
3 Bus Tie Controller Application Menu ............................................................. 13
4 SPECIFICATION................................................................................................ 14
4.1 OPERATING TEMPERATURE .............................................................................................. 14
SCREEN HEATER OPERATION (WHEN FITTED) ....................................................... 14
4.2 REQUIREMENTS FOR UL .................................................................................................... 14
4.3 TERMINAL SPECIFICATION ................................................................................................ 15
4.4 POWER SUPPLY REQUIREMENTS ..................................................................................... 15
MODULE SUPPLY INSTRUMENTATION DISPLAY ...................................................... 15
4.5 VOLTAGE & FREQUENCY SENSING .................................................................................. 16
4.6 CURRENT SENSING ............................................................................................................. 16
VA RATING OF THE CTS ............................................................................................... 17
CT POLARITY ................................................................................................................. 18
CT PHASING................................................................................................................... 18
CT CLASS ....................................................................................................................... 18
4.7 INPUTS ................................................................................................................................... 19
DIGITAL INPUTS ............................................................................................................ 19
4.8 OUTPUTS ............................................................................................................................... 19
CONFIGURABLE VOLT-FREE RELAY OUTPUTS C & D ............................................. 19
CONFIGURABLE DC OUTPUTS E, F, G, H, I, J, K, L ................................................... 19
4.9 COMMUNICATION PORTS ................................................................................................... 20
4.10 COMMUNICATION PORT USAGE .................................................................................... 21
USB SLAVE PORT (PC CONFIGURATION) .................................................................. 21
USB HOST PORT (DATA LOGGING) ............................................................................ 21
RS485 PORT................................................................................................................... 22
4.10.3.1 RECOMMENDED PC RS485 SERIAL PORT ADD-ONS ....................................... 23
ETHERNET PORT .......................................................................................................... 24
4.10.4.1 MODBUS TCP ......................................................................................................... 24
4.10.4.2 ETHERNET PORT USED FOR PLC COMMUNICATION ....................................... 24
4.10.4.3 DIRECT PC CONNECTION..................................................................................... 25
4.10.4.4 CONNECTION TO BASIC ETHERNET ................................................................... 26
4.10.4.5 CONNECTION TO COMPANY ETHERNET INFRASTRUCTURE ......................... 27
4.10.4.6 CONNECTION TO THE INTERNET ........................................................................ 28
4.10.4.7 FIREWALL CONFIGURATION FOR INTERNET ACCESS .................................... 29
AMSC (ADVANCED MULTI-SET COMMUNICATIONS) LINK ....................................... 30
REDUNDANT AMSC LINK ............................................................................................. 31
DSENET® (EXPANSION MODULES) ............................................................................. 33
4.11 SOUNDER .......................................................................................................................... 34
ADDING AN EXTERNAL SOUNDER ............................................................................. 34
4.12 DIMENSIONS AND MOUNTING ........................................................................................ 35
DIMENSIONS .................................................................................................................. 35
PANEL CUTOUT ............................................................................................................. 35
WEIGHT .......................................................................................................................... 35
FIXING CLIPS ................................................................................................................. 36
4.12.4.1 CABLE TIE FIXING POINTS ................................................................................... 36
CARD TEXT & LOGO INSERT ....................................................................................... 37
SEALING GASKET ......................................................................................................... 37
1 INTRODUCTION
This document details the installation and operation requirements of the DSEG8680 module and is
part of the DSEGenset® range of products.
The manual forms part of the product and should be kept for the entire life of the product. If the
product is passed or supplied to another party, ensure that this document is passed to them for
reference purposes.
This is not a controlled document. DSE do not automatically inform on updates. Any future updates of
this document are included on the DSE website at www.deepseaelectronics.com
The DSEG8680 series is designed to provide differing levels of functionality across a common
platform. This allows the generator OEM greater flexibility in the choice of controller to use for a
specific application.
Synchronising and Load Sharing features are included within the controller, along with the necessary
protections for such a system.
The user also has the facility to view the system operating parameters via the text LCD display.
The DSE8680 is an intelligent control module designed to control a generator bus-tie breaker. The
control module features technology that automatically manages the synchronising and check-sync
across the breaker using the DSE Advanced Multi-Set communications (AMSC) link when opening
and closing the bus-tie breaker.
The powerful ARM microprocessor contained within the module allows for incorporation of a range of
complex features:
The DSE Configuration Suite PC Software allows alteration of selected operational sequences,
timers, alarms, and operational sequences. Additionally, the module’s integral front panel
configuration editor allows adjustment of this information.
Module access and critical operational sequences and timers for use by qualified engineers, can be
protected by a security code. Selected parameters can be changed from the module’s front panel
using the Running Editor.
The module is housed in a robust plastic case suitable for panel mounting. Connections to the module
are via locking plug and sockets.
Term Description
RTD An RTD (Resistance Temperature Detector) is a sensor whose resistance
changes as its temperature changes. The resistance increases as the
temperature of the sensor increases.
SCADA Supervisory Control And Data Acquisition. A system that operates with
coded signals over communication channels to provide control and
monitoring of remote equipment
SIM Subscriber Identity Module. The small card supplied by the GSM/CDMA
provider that is inserted into the cell phone, GSM modem or DSEGateway
device to give GSM/GPRS connection.
SMS Short Message Service. The text messaging service of mobile/cell phones.
SNMP Simple Network Management Protocol. An international standard protocol for
managing devices on IP networks.
TCP TCP (Transmission Control Protocol) is a standard that defines how to
establish and maintain a network conversation via which application
programs can exchange data.
USB Universal Serial Bus
WAN Wide Area Network
WEEE Waste Electrical and Electronic Equipment
1.3 BIBLIOGRAPHY
This document refers to, and is referred by the following DSE publications which are obtained from
the DSE website: www.deepseaelectronics.com or by contacting DSE technical support:
support@deepseaelectronics.com.
INSTALLATION INSTRUCTIONS
2 MANUALS
Product manuals are obtained from the DSE website: www.deepseaelectronics.com or by contacting
DSE technical support: support@deepseaelectronics.com.
TRAINING GUIDES
Training guides are provided as ‘hand-out’ sheets on specific subjects during training sessions and
contain specific information regarding to that subject.
Reference Description
IEEE Std C37.2-1996 IEEE Standard Electrical Power System Device
ISBN 1-55937-879-4 Function Numbers and Contact Designations. Institute of Electrical and
Electronics Engineers Inc
ISBN 0-7506-1147-2 Diesel generator handbook. L.L.J. Mahon
ISBN 0-9625949-3-8 On-Site Power Generation. EGSA Education Committee.
NOTE: The DSE module’s USB port is inactive when the Application page is entered.
NOTE: It is not possible to Firmware Update the module when the Application menu is
entered.
NOTE: Care must be taken when updating the module’s firmware as this resets the
configuration files for the Bus Tie Controller (BTC) application back to its factory defaults.
NOTE: When a new software application is selected, the relevant software application’s
configuration file must be configured using the DSE Configuration Suite.
The DSEG8680 module contains a single Bus Tie Controller software application:
The application allows load switching and the option of load capacity requirements.
4 SPECIFICATION
4.1 OPERATING TEMPERATURE
Module Specification
DSEG8680 -30 ºC +70 ºC (-22 ºF +158 ºF )
Display Heater Variant -40 ºC +70 ºC (-40 ºF +158 ºF )
WARNING!: More than one live circuit exists, refer to section 5.3 entitled Typical Wiring
Diagram.
Specification Description
Screw Terminal Tightening
4.5 lb-in (0.5 Nm)
Torque
Conductors Terminals suitable for connection of conductor size 13 AWG to 20
AWG (0.5 mm² to 2.5 mm²).
Conductor protection must be provided in accordance with NFPA
70, Article 240
Low voltage circuits (35 V or less) must be supplied from the
engine starting battery or an isolated secondary circuit.
The communication, sensor, and/or battery derived circuit
conductors shall be separated and secured to maintain at least ¼”
(6 mm) separation from the generator and mains connected circuit
conductors unless all conductors are rated 600 V or greater.
Current Inputs Must be connected through UL Listed or Recognized isolating
current transformers with the secondary rating of 5 A max.
Communication Circuits Must be connected to communication circuits of UL Listed
equipment
DC Output Pilot Duty 0.5 A
Mounting Suitable for flat surface mounting in Type 1 Enclosure Type rating
with surrounding air temperature -22 ºF to +122 ºF (-30 ºC to +50
ºC)
Suitable for pollution degree 3 environments when voltage sensing
inputs do not exceed 300 V. When used to monitor voltages over
300 V device to be installed in an unventilated or filtered ventilation
enclosure to maintain a pollution degree 2 environment.
Operating Temperature -22 ºF to +122 ºF (-30 ºC to +50 ºC)
Description Specification
Range 0 V to 70 V DC (Maximum continuous operating voltage of 35 V DC)
Resolution 0.1 V
Accuracy 1 % full scale (±0.35 V)
NOTE: Details for 4 mm² cables are shown for reference only. The connectors on the DSE
modules are only suitable for cables up to 2.5 mm².
The VA burden of the module on the CTs is 0.5 VA. However, depending upon the type and length of
cabling between the CTs and the module, CTs with a greater VA rating than the module are required.
Example:
If 1.5 mm² cable is used and the
distance from the CT to the measuring
module is 20 m, then the burden of the
cable alone is approximately 15 VA.
As the burden of the DSE controller is
.5 VA, then a CT with a rating of at
least 15 VA + 0.5 VA = 15.5 VA must
be used. 0.5 VA, then a CT with a rating of at least 15 VA + 0.5 VA = 15.5 VA must be used. If 2.5
mm² cables are used over the same distance of 20 m, then the burden of the cable on the CT is
approximately 7 VA. CT’s required in this instance is at least 7.5 VA (7 + 0.5).
CT POLARITY
NOTE: Take care to ensure correct polarity of the CT primary as shown above. If in doubt,
check with the CT supplier.
Take care to ensure the correct polarity of the CTs otherwise the power flow direction across the bus
tie breaker will be incorrect and will make power sharing and ramping malfunction. Take note that
paper stick-on labels on CTs that show the orientation are often incorrectly placed on the CT. It is
more reliable to use the labelling in the case moulding as an indicator to orientation (if available).
Labelled as Labelled as
p1, k or K p2, l or L
To Generator To Load
Polarity of CT Primary
CT PHASING
Take particular care that the CTs are connected to the correct phases. For instance, ensure that the
CT on phase 1 is connected to the terminal on the DSE module intended for connection to the CT for
phase 1.
CT CLASS
Ensure the correct CT type is chosen. For instance, if the DSE module is providing over current
protection, ensure the CT can measure the overload level required to protect against, and at the
accuracy level required.
For instance, this may mean fitting a protection class CT to maintain high accuracy while the CT is
measuring overload currents.
Conversely, if the DSE module is using the CT for instrumentation only (current protection is disabled
or not fitted to the controller), then measurement class CTs can be used. Again, bear in mind the
accuracy required. The DSE module is accurate to better than 1% of the full-scale current reading. To
maintain this accuracy, fit a Class 0.5 or Class 1 CT.
4.7 INPUTS
DIGITAL INPUTS
Description Specification
Number 12 configurable digital inputs
Arrangement Contact between terminal and ground
Low Level Threshold 2.1 V minimum
High Level Threshold 6.6 V maximum
Maximum Input Voltage +50 V DC with respect to plant supply negative
Minimum Input Voltage -24 V DC with respect to plant supply negative
Contact Wetting Current 7 mA typical
Open Circuit Voltage 12 V typical
4.8 OUTPUTS
Description Specification
Normally used for load switching control
Type Fully configurable volt-free relays.
Output C normally closed and Output D normal open.
Rating 8 A resistive at 250 V AC
CONFIGURABLE DC OUTPUTS E, F, G, H, I, J, K, L
Description Specification
Type Fully configurable, supplied from DC supply terminal 2.
Rating 2 A resistive at module supply.
Description Specification
Type B USB 2.0
USB Slave Port For connection to PC running DSE Configuration Suite
Max distance 5 m (16 feet)
Type A USB 2.0
USB Host Port Capability to add a maximum of 16 GB USB storage device for data
recording only
Isolated
Data connection 2 wire + common
Half Duplex
Data direction control for Transmit (by s/w protocol)
1 x RS485 Serial Port
Max Baud Rate 115.2 kbaud subject to configuration
External termination required (120 )
Max common mode offset 70 V (on board protection transorb)
Max distance 1.2 km (¾ mile)
Ethernet Auto detecting 10/100 Mbit Ethernet port.
NOTE: DSE stock 2 m (6.5 feet) USB type A to type B cable, DSE Part Number: 016-125.
Alternatively, they are purchased from any PC or IT store.
NOTE: The DC supply must be connected to the module for configuration by PC.
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite PC Software Manual.
The USB port is provided to give a simple means of connection between a PC and the controller.
Using the DSE Configuration Suite Software, the operator is then able to control the module, starting
or stopping the engine, selecting operating modes, etc.
Additionally, the various operating parameters (such as coolant temperature, oil pressure, etc.) of the
engine are available to be viewed or changed.
DSEG8680 Controller
USB Type A connection for an external USB storage device of maximum 16 GB for instrumentation
data logging. A 16 GB external USB storage device allows for 33 weeks, 4 days and 20 minutes’
worth of data, assuming 20 parameters were configured to be logged, each with a Log Interval of 1
second.
RS485 PORT
NOTE: When the RS485 Port Usage is configured to “PLC Comms”, all other modules’
Port Usage must be configured to “Gencomm”. This allows the module configured as “PLC
Comms” to act as a master and read from the module(s) configured to “Gencomm”.
For details on how to configure the PLC Editor to read via its RS485, refer to DSE Publication:
057-314 Advanced PLC Software Manual which is found on our website:
www.deepseaelectronics.com
NOTE: For a single module to PC connection and distances up to 5 m (16 feet) the USB
connection method is more suitable and provides for a lower cost alternative to RS485 (which
is more suited to longer distance connections).
The RS485 port on the controller support the Modbus RTU protocol and is for connection to a single
Modbus master device only.
The DSE Modbus register table for the controller is available upon request from the DSE Technical
Support Department.
RS485 is used for point-to-point cable connection of more than one device (maximum 32 devices)
and allows for connection to PCs, PLCs, and Building Management Systems (to name just a few
devices).
One advantage of the RS485 interface is the large distance specification (1.2 km when using Belden
9841 (or equivalent) cable. This allows for a large distance between the module and a PC running the
DSE Configuration Suite software. The operator is then able to control the module, starting or
stopping the engine, selecting operating modes, etc.
The various operating parameters (such as coolant temperature, oil pressure, etc.) of the remote
engine are viewed or changed.
Many PCs are not fitted with an internal RS485 serial port. DSE DOES NOT recommend the use of
USB to RS485 convertors but can recommend PC add-ons to provide the computer with an RS485
port.
The DSEG8680 has one RS485 ports which are configurable using the Configuration Suite Software.
An example of configuring the RS485 connection using the DSE Configuration Suite Software is
shown below:
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite Software Manual.
NOTE: DSE have no business tie to Brainboxes. Over many years, our own engineers
have used these products and are happy to recommend them.
NOTE: For further details of setting up the devices below, refer to the manufacture whose
details are below.
Remember to check these parts are suitable for your PC. Consult your PC supplier for further advice.
Supplier:
Brainboxes
Tel: +44 (0)151 220 2500
Web: http://www.brainboxes.com
Email: Sales: sales@brainboxes.com
ETHERNET PORT
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite Software Manual.
NOTE: For a single module to PC connection and distances up to 5 m (16 feet) the USB
connection method is more suitable and provides for a lower cost alternative to Ethernet
(which is more suited to longer distance connections).
NOTE: DSE stock 2 m (6.5 feet) Ethernet Cable, DSE Part Number: 016-137. Alternatively,
they can be purchased from any PC or IT store.
Ethernet is used for point-to-point cable connection of more than one device and allows for
connection to PCs, PLCs, Building Management Systems and SNMP Managers (to name just a few
devices) or to other DSE modules using the PLC Editor.
One advantage of the Ethernet interface is the ability to interface into an existing LAN (Local Area
Network) connection for remote connection via an internet connection. This allows for a large distance
between the module and a PC running the DSE Configuration Suite software or any external device.
The operator is then able to control the module, starting or stopping the engine, selecting operating
modes, etc through various means.
The Ethernet port on the controller supports the Modbus TCP protocol and is for connection for up to
five Modbus master devices. The various operating parameters (such as coolant temperature, oil
pressure, etc.) of the remote engine are viewed or changed.
The DSE Modbus register table for the controller is available upon request from the DSE Technical
Support Department.
NOTE: For details on how to configure the PLC Editor to read through the TCP/IP, refer to
DSE Publication: 057-314 Advanced PLC Software Manual which is found on our website:
www.deepseaelectronics.com
The DSE module can communicate with other DSE modules using the Ethernet Port, this is
configured from the PLC Editor to allow it read specific GenComm registers from other modules over
the TCP/IP to perform certain tasks in the PLC.
When the DSE module is configured to communicate with the other modules via the TCP/IP it
becomes a Modbus TCP Master, hence care must be taken on the slave TCP modules not to exceed
their total supported five Modbus TCP masters.
Requirements
Network Cable
NOTE: DSE stock 2 m (6.5 feet) Ethernet Cable, DSE Part Number: 016-137. Alternatively,
they can be purchased from any PC or IT store.
Requirements
Ethernet
Cable
Ethernet Router
or ADSL Router
NOTE: DSE stock 2 m (6.5 feet) Ethernet Cable, DSE Part Number: 016-137.Alternatively,
they can be purchased from any PC or IT store.
Requirements
PC Network
Ethernet Router Wall
or ADSL Router Connection
Sockets Ethernet
Cable
NOTE: DSE stock 2 m (6.5 feet) Ethernet Cable, DSE Part Number: 016-137.Alternatively,
they can be purchased from any PC or IT store.
Requirements
DSL or ADSL
Router Ethernet
INTERNET Cable
The DSL/ADSL
router routes
external network
DSL or ADSL traffic
Router
Optional ‘Local’
PC Remote From Site PC
Generator Site
NOTE: An Ethernet Patch Cable can use for this type of connection and can be purchased
from any PC or IT store.
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite Software Manual.
As modem/routers differ enormously in their configuration, it is not possible for DSE to give a
complete guide to their use with the module. However, it is possible to give a description of the
requirements in generic terms. For details of how to achieve the connection to your modem/router you
are referred to the supplier of your modem/router equipment.
The module makes its data available over Modbus TCP or SNMP V2c and as such communicates
over the Ethernet using a Port configured via the DSE Configuration Suite software.
You must configure your modem/router to allow inbound traffic on this port. For more information you
are referred to your WAN interface device (modem/router) manufacturer.
It is also important to note that if the port assigned is already in use on the LAN, the module cannot be
used, and another port must be used.
As the module makes its user interface available to standard web browsers, all communication uses
the chosen port. It is usual for a firewall to make the same port outgoing open for communication.
Network Address and Port Translation (NAPT) allows a single device, such as the modem/router
gateway, to act as an agent between the Internet (or "public external network") and a local (or
"internal private") network. This means that only a single, unique IP address is required to represent
an entire group of computers.
For our application, this means that the WAN IP address of the modem/router is the IP address we
need to access the site from an external (internet) location.
When the requests reach the modem/router, we want this passed to a ‘virtual server’ for handling, in
our case this is the module.
Result: Traffic arriving from the WAN (internet) on port xxx is automatically sent to IP address set
within the configuration software on the LAN for handling.
NOTE: A termination resistor MUST be fitted to the first and last unit on the AMSC link.
For connection details, refer to section 5.3.4 entitled Typical Arrangement of AMSC Link.
NOTE: DSE recommend Belden 9841 (or equivalent) cable for AMSC communication. This
is rated to a maximum cable length of 250 m. DSE Stock Belden 9841 cable, DSE Part Number:
016-030.
The AMSC link is the interconnection cable between all DSE synchronising controllers and must not
be connected to any device other than DSE equipment designed for connection to the AMSC link.
Description Specification
Cable Type Two core screened and shielded twisted pair
Cable Characteristics 120 , Low capacitance
Recommended Cable Belden 9841, Belden 9271
NOTE: For additional length, the DSE124 CAN & AMSC Extender
is available. For more information, refer to DSE Publication: 057-116
Maximum Cable DSE124 Operator Manual
Length
250 m (273 yards) when using Belden 9841 or direct equivalent.
125 m (136 yards) when using Belden 9271 or direct equivalent.
AMSC Topology “Daisy Chain” Bus with no stubs (spurs)
120 .
AMSC Termination
Must be fitted externally to the first and last module.
Maximum DSEG8680 The maximum number of DSEG8680 modules on an AMSC link is 64.
Modules
NOTE: The redundant AMSC link connectivity is only available in DSEG8xxx modules.
Contact DSE technical support: support@deepseaelectronics.com for more information.
NOTE: A termination resistor MUST be fitted to the first and last unit on the AMSC link.
For connection details, refer to section 5.3.4 entitled Typical Arrangement of AMSC Link.
NOTE: DSE recommend Belden 9841 (or equivalent) cable for AMSC communication. This
is rated to a maximum cable length of 250 m. DSE Stock Belden 9841 cable, DSE Part Number:
016-030.
The AMSC link is the interconnection cable between all DSE synchronising controllers and must not
be connected to any device other than DSE equipment designed for connection to the AMSC link.
Upon the main AMSC link failing for any reason, the user can configure the DSE8xxx MKII modules to
revert the Redundant AMSC Link connection using the CAN Port connection. An example of
configuring the Redundant AMSC Link connection the DSE Configuration Suite Software is shown
below:
Description Specification
Cable Type Two core screened and shielded twisted pair
120 impedance
Cable Characteristics
Low capacitance
Belden 9841
Recommended Cable
Belden 9271
Continued Overleaf…
Description Specification
Redundant AMSC “Daisy Chain” Bus with no stubs (spurs)
Topology
Redundant AMSC 120 .
Termination Must be fitted externally to the first and last module.
Maximum DSEG8680 • The maximum number of DSEG8680 modules on an AMSC link
Modules is 64.
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite PC Software Manual.
NOTE: As a termination resistor is internally fitted to the controller, the controller must be
the ‘first’ unit on the DSENet® link. A termination resistor MUST be fitted to the ‘last’ unit on
the DSENet® link. For connection details, refer to section 5.3.3 entitled Typical Arrangement of
DSENet®.
NOTE: DSE recommend Belden 9841 (or equivalent) cable for DSENet® communication.
This is rated to a maximum cable length of 1.2 km. DSE Stock Belden 9841 cable, DSE Part
Number: 016-030.
DSENet® is the interconnection cable between the host controller and the expansion module(s) and
must not be connected to any device other than DSE equipment designed for connection to the
DSENet®
Description Specification
Cable Type Two core screened and shielded twisted pair
120
Cable Characteristics
Low capacitance
Belden 9841
Recommended Cable
Belden 9271
1200 m (¾ mile) when using Belden 9841 or direct equivalent.
Maximum Cable Length
600 m (656 yards) when using Belden 9271 or direct equivalent.
DSENet® Topology “Daisy Chain” Bus with no stubs (spurs)
120 . Fitted internally to host controller. Must be fitted externally to the
DSENet® Termination
‘last’ expansion module.
4.11 SOUNDER
The module features an internal sounder to draw attention to warning, electrical trip, and shutdown
alarms.
Description Specification
Sounder Level 64 db at 1m
If an external alarm or indicator is required, this can be achieved by using the DSE Configuration
Suite PC software to configure an auxiliary output for Audible Alarm, and by configuring an auxiliary
input for Alarm Mute (if required).
The audible alarm output activates and de-activates at the same time as the module’s internal
sounder. The Alarm mute input and internal Lamp Test / Alarm Mute button activate ‘in parallel’
with each other. Either signal mutes both the internal sounder and audible alarm output.
Example of configuration to achieve external sounder with external alarm mute button:
DIMENSIONS
PANEL CUTOUT
220 mm x 160 mm
(8.66” x 6.30”)
WEIGHT
0.76 kg
(1.67 lb)
FIXING CLIPS
The module is held into the panel fascia using the supplied fixing clips:
• Withdraw the fixing clip screw (turn anticlockwise) until only the pointed end is protruding from the
clip.
• Insert the three ‘prongs’ of the fixing clip into the slots in the side of the module case.
• Pull the fixing clip backwards (towards the back of the module) ensuring all three prongs of the
clip are inside their allotted slots.
• Turn the fixing clip screws clockwise until they contact the panel fascia.
• Turn the screw a quarter of a turn to secure the module into the panel fascia. Care must be taken
not to over tighten the fixing clip screws.
Fixing clip
Fixing clip
fitted to module
Cable tie fixing points are included on the rear of the module’s case to aid wiring. This additionally
provides strain relief to the cable loom by removing the weight of the loom from the screw connectors,
reducing the chance of future connection failures.
Care must be taken not to over tighten the cable tie (for instance with cable tie tools) to prevent the
risk of damage to the module case.
The module has two slots available for Logo Designs and Card Text for use with the LED indicators.
Logo Slot
Card Text
Slot
SEALING GASKET
The gasket provides improved sealing between module and the panel fascia. The gasket is
incorporated into the module as shown below. Ensure correct fitment to the panel facia to maintain
the integrity of the seal.
Gasket
incorporated
into module
Standard Description
IEEE C37.2 Continued…
(Standard Electrical
Power System Device 26 – Apparatus thermal device
Function Numbers and 27AC – AC undervoltage relay
Contact Designations) 27DC – DC undervoltage relay
29 – Isolating contactor or switch
30 – Annunciator relay
37 – Undercurrent or underpower relay (USING INTERNAL PLC
EDITOR)
42 – Running circuit controller
44 – Unit sequence relay
46 – Reverse-phase or phase-balance current relay
48 – Incomplete sequence relay
50 – Instantaneous overcurrent relay
51 – AC time overcurrent relay
52 – AC circuit controller
55 – Power factor relay (USING INTERNAL PLC EDITOR)
59AC – AC overvoltage relay
59DC – DC overvoltage relay
62 – Time delay stopping or opening relay
71 – Level switch
74 – Alarm relay
78 – Phase-angle measuring relay
79 – Reclosing relay (USING INTERNAL PLC EDITOR)
81 – Frequency relay
83 – Automatic selective control or transfer relay
86 – Lockout relay
In line with our policy of continual development, Deep Sea Electronics, reserve the right to change
specification without notice.
ENCLOSURE CLASSIFICATIONS
4.13.1.1 IP CLASSIFICATIONS
IP65 (Front of module when module is installed into the control panel).
Protection against contact and ingress of solid objects Protection against ingress of water
0 No protection 0 No protection
1 Protected against ingress solid objects with a 1 Protection against dripping water falling vertically. No harmful
diameter of more than 50 mm. No protection against effect must be produced (vertically falling drops).
deliberate access, e.g., with a hand, but large
surfaces of the body are prevented from approach.
2 Protected against penetration by solid objects with a 2 Protection against dripping water falling vertically. There must be
diameter of more than 12 mm. Fingers or similar no harmful effect when the equipment (enclosure) is tilted at an
objects prevented from approach. angle up to 15° from its normal position (drops falling at an angle).
3 Protected against ingress of solid objects with a 3 Protection against water falling at any angle up to 60° from the
diameter of more than 2.5 mm. Tools, wires etc. with vertical. There must be no harmful effect (spray water).
a thickness of more than 2.5 mm are prevented from
approach.
4 Protected against ingress of solid objects with a 4 Protection against water splashed against the equipment
diameter of more than 1 mm. Tools, wires etc. with a (enclosure) from any direction. There must be no harmful effect
thickness of more than 1 mm are prevented from (splashing water).
approach.
5 Protected against harmful dust deposits. Ingress of 5 Protection against water projected from a nozzle against the
dust is not totally prevented but the dust must not equipment (enclosure) from any direction. There must be no
enter in sufficient quantity to interface with harmful effect (water jet).
satisfactory operation of the equipment. Complete
protection against contact.
6 Protection against ingress of dust (dust tight). 6 Protection against heavy seas or powerful water jets. Water must
Complete protection against contact. not enter the equipment (enclosure) in harmful quantities
(splashing over).
NOTE: There is no direct equivalence between IP / NEMA ratings. IP figures shown are
approximate only.
1 Provides a degree of protection against contact with the enclosure equipment and against a limited amount of falling dirt.
IP30
2 Provides a degree of protection against limited amounts of falling water and dirt.
IP31
3 Provides a degree of protection against windblown dust, rain, and sleet; undamaged by the formation of ice on the
enclosure.
IP64
3R Provides a degree of protection against rain and sleet; undamaged by the formation of ice on the enclosure.
IP32
4 (X) Provides a degree of protection against splashing water, windblown dust and rain, hose directed water, undamaged by
the formation of ice on the enclosure. (Resist corrosion).
IP66
12/12K Provides a degree of protection against dust, falling dirt and dripping noncorrosive liquids.
IP65
13 Provides a degree of protection against dust and spraying of water, oil, and noncorrosive coolants.
IP65
5 INSTALLATION
The module is designed to be mounted on the panel fascia. For dimension and mounting details, see
the section 4.12 entitled Dimension and Mounting.
NOTE: Availability of some terminals depends upon module version. Full details are given
in the section 4.3 entitled Terminal Specification..
To aid user connection, icons are used on the rear of the module to help identify terminal functions.
An example of this is shown below.
NOTE: When the module is configured for operation with an electronic engine, Fuel and
Start output requirements may be different. For further details on connection to electronic
engines, refer to DSE Publication: 057-004 Electronic Engines And DSE Wiring
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite PC Software Manual.
Pin Cable
Description Notes
No Size
DC Plant Supply Input 2.5 mm²
1 Connect to ground where applicable.
(Negative) AWG 13
DC Plant Supply Input 2.5 mm²
2 Supplies the module and DC Outputs E, F, G, H, I & J
(Positive) AWG 13
3 Not Connected
4 Not Connected
5 Not Connected
6 Not Connected
1.0 mm²
7 DC Output E Plant Supply Positive from terminal 2. 2 A DC rated.
AWG 18
1.0 mm²
8 DC Output F Plant Supply Positive from terminal 2. 2 A DC rated.
AWG 18
1.0 mm²
9 DC Output G Plant Supply Positive from terminal 2. 2 A DC rated.
AWG 18
1.0 mm²
10 DC Output H Plant Supply Positive from terminal 2. 2 A DC rated.
AWG 18
1.0 mm²
11 DC Output I Plant Supply Positive from terminal 2. 2 A DC rated.
AWG 18
1.0 mm²
12 DC Output J Plant Supply Positive from terminal 2. 2 A DC rated.
AWG 18
1.0 mm²
13 DC Output K Plant Supply Positive from terminal 2. 2 A DC rated.
AWG 18
1.0 mm²
14 DC Output L Plant Supply Positive from terminal 2. 2 A DC rated.
AWG 18
15 Not Connected
16 Not Connected
17 Not Connected
18 Not Connected
19 Not Connected
20 Not Connected
21 Not Connected
22 Not Connected
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite PC Software Manual.
NOTE: Screened 120 impedance cable specified for use with CAN must be used for the
AMSC link.
DSE stock and supply Belden cable 9841 which is a high quality 120 impedance cable
suitable for CAN use (DSE part number 016-030)
NOTE: As a termination resistor is internally fitted to the controller, the controller must be
the ‘first’ unit on the DSENet® link. A termination resistor MUST be fitted to the ‘last’ unit on
the DSENet® link. For connection details, refer to section 5.3.3 entitled Typical Arrangement of
DSENet®.
Pin Cable
Description Notes
No Size
23 Not Connected
24 Not Connected
25 Not Connected
0.5 mm²
26 CAN Port H Use only 120 CAN or RS485 approved cable
AWG 20
Redundant
0.5 mm²
AMSC 27 CAN Port L Use only 120 CAN or RS485 approved cable
AWG 20
2
28 CAN Port Screen Shield Use only 120 CAN or RS485 approved cable
0.5 mm²
29 DSENet® Expansion B Use only 120 CAN or RS485 approved cable
AWG 20
0.5 mm²
30 DSENet® Expansion A Use only 120 CAN or RS485 approved cable
AWG 20
DSENet® Expansion
31 Shield Use only 120 CAN or RS485 approved cable
Screen
0.5 mm²
32 CAN Port H Use only 120 CAN or RS485 approved cable
AWG 20
AMSC
0.5 mm²
1 33 CAN Port L Use only 120 CAN or RS485 approved cable
AWG 20
34 CAN Port Screen Shield Use only 120 CAN or RS485 approved cable
35 Not Connected
36 Not Connected
37 Not Connected
38 Not Connected
39 Not Connected
NOTE: The below table describes connections to a three phase, four wire supply. For
alternative wiring topologies, see the section 5.4 entitled Alternate Topology Wiring Diagrams.
Pin Cable
Description Notes
No Size
1.0mm²
40
Normally Closed Volt-Free AWG 18
Normally configured to control load switching device
Relay Output C 1.0mm²
41
AWG 18
1.0mm²
42
Normally Open Volt-Free Relay AWG 18
Normally configured to control load switching device
Output D 1.0mm²
43
AWG 18
1.0 mm² Connect to Bus L1 (U) output (AC)
44 Bus L1 (R) Voltage Sensing
AWG 18 (Recommend 2 A fuse)
1.0 mm² Connect to Bus L2 (V) output (AC)
45 Bus L2 (S) Voltage Sensing
AWG 18 (Recommend 2 A fuse)
1.0 mm² Connect to Bus L3 (W) output (AC)
46 Bus L3 (T) Voltage Sensing
AWG 18 (Recommend 2 A fuse)
1.0 mm²
47 Bus Neutral (N) Input Connect to Bus Neutral terminal (AC)
AWG 18
NOTE: The below table describes connections to a three phase, four wire Bus supply. For
alternative wiring topologies, see the section 5.4 entitled Alternate Topology Wiring Diagrams.
Pin Cable
Description Notes
No Size
1.0 mm² Connect to Bus L1 (U) output (AC)
48 Bus L1 (U) Voltage Sensing
AWG 18 (Recommend 2 A fuse)
1.0 mm² Connect to Bus L2 (V) output (AC)
49 Bus L2 (V) Voltage Sensing
AWG 18 (Recommend 2 A fuse)
1.0 mm² Connect to Bus L3 (W) output (AC)
50 Bus L3 (W) Voltage Sensing
AWG 18 (Recommend 2 A fuse)
1.0 mm²
51 Bus Neutral (N) Input Connect to Bus Neutral terminal (AC)
AWG 18
CURRENT TRANSFORMERS
WARNING!: Do not disconnect this plug when the CTs are carrying current.
Disconnection will open circuit the secondary of the C.T.’s and dangerous voltages may then
develop. Always ensure the CTs are not carrying current and the CTs are short circuit
connected before making or breaking connections to the module.
NOTE: The module has a burden of 0.5 VA on the CT. Ensure the CT is rated for the
burden of the controller, the cable length being used and any other equipment sharing the CT.
If in doubt, consult your CT supplier.
NOTE: Take care to ensure correct polarity of the CT primary as shown below. If in doubt,
check with the CT supplier.
Pin Cable
Description Notes
No Size
2.5 mm²
52 CT Secondary for Bus1 or Bus 2 L1 Connect to s1 secondary of L1 monitoring CT
AWG 13
2.5 mm²
53 CT Secondary for Bus 1 or Bus L2 Connect to s1 secondary of L2 monitoring CT
AWG 13
2.5 mm²
54 CT Secondary for Bus1 or Bus 2 L3 Connect to s1 secondary of L3 monitoring CT
AWG 13
2.5 mm²
55 Connected as required AWG 13
Common for CTs connected to L1, L2, 2.5 mm² Connect to s2 secondary of L1, L2, L3
56
L3 (s2) AWG 13 monitoring CTs
57 Not Connected
58 Not Connected
5.2.5.2 CT CONNECTIONS
s1 is the secondary of the CT that connects to the DSE Module’s input for the CT measuring
s2 is the secondary of the CT that is connected with the s2 connections of all the other CTs and
connected to the CT common terminal of the module.
Labelled as Labelled as
p1, k or K p2, l or L
Polarity of CT Primary
DIGITAL INPUTS
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite PC Software Manual.
Pin Cable
Description Notes
No Size
0.5 mm²
59 Configurable Digital Input A Switch To Negative
AWG 20
0.5 mm²
60 Configurable Digital Input B Switch To Negative
AWG 20
0.5 mm²
61 Configurable Digital Input C Switch To Negative
AWG 20
0.5 mm²
62 Configurable Digital Input D Switch To Negative
AWG 20
0.5 mm²
63 Configurable Digital Input E Switch To Negative
AWG 20
0.5 mm²
64 Configurable Digital Input F Switch To Negative
AWG 20
0.5 mm²
65 Configurable Digital Input G Switch To Negative
AWG 20
0.5 mm²
66 Configurable Digital Input H Switch To Negative
AWG 20
0.5 mm²
67 Configurable Digital Input I Switch To Negative
AWG 20
0.5 mm²
68 Configurable Digital Input J Switch To Negative
AWG 20
0.5 mm²
69 Configurable Digital Input K Switch To Negative
AWG 20
0.5 mm²
70 Configurable Digital Input L Switch To Negative
AWG 20
RS485
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite PC Software Manual.
NOTE: A 120 Ω termination resistor must be fitted across terminals A and B if the DSE
module is the first or last device on the R485 link.
NOTE: Screened 120 impedance cable specified for use with RS485 must be used for
the RS485 link.
DSE stock and supply Belden cable 9841 which is a high quality 120 impedance cable
suitable for CAN use (DSE part number 016-030)
Pin Cable
Description Notes
No Size
71 RS485 Port Screen Shield Use only 120 CAN or RS485 approved cable
RS485 72 RS485 Port B (+)
0.5 mm² Connect to RXD+ and TXD+
1 AWG 20 Use only 120 CAN or RS485 approved cable
0.5 mm² Connect to RXD- and TXD-
73 RS485 Port A (-)
AWG 20 Use only 120 CAN or RS485 approved cable
74 Not Connected
75 Not Connected
76 Not Connected
NOTE: The USB connection cable between the PC and the module must not be extended
beyond 5 m (16 feet). For distances over 5 m, it is possible to use a third-party USB extender.
Typically, they extend USB up to 50 m. The supply and support of this type of equipment is
outside the scope of Deep Sea Electronics.
CAUTION!: Care must be taken not to overload the PCs USB system by connecting more
than the recommended number of USB devices to the PC. For further information, consult
your PC supplier.
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite PC Software Manual.
Cable
Description Notes
Size
Socket for connection to PC with DSE 0.5 mm² This is a standard USB type
Configuration Suite Software AWG 20 A to type B connector.
NOTE: For further details on how to add and remove a USB storage device, refer to
section 6.3.7.1 entitled Data Logging.
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Software Manual.
Storage
Description Notes
Size
Genset manufacturers and panel builders may use these diagrams as a starting point; however
always refer to the completed system diagram provided by the system manufacturer for complete
wiring detail.
Further wiring suggestions are available in the following DSE publications, available at
www.deepseaelectronics.com to website members.
NOTE: The below diagram is applicable for the following AC topologies: 3 Phase 4 Wire
Star, 3 Phase 4 Wire Delta L1-N-L2, 3 Phase 4 Wire Delta L1-N-L3 and 3 Phase 4 Wire Delta
L2-N-L3. For further details of module configuration to suit these different topologies, refer to
DSE Publication: 057-326 DSEG8680 Configuration Suite Software Manual.
EARTH SYSTEMS
The typical wiring diagrams located within this document show connections for a negative earth
system (the battery negative connects to Earth).
When using a DSE module with a Positive Earth System (the battery positive connects to Earth), the
following points must be followed:
Follow the typical wiring diagram as normal for all sections except the earth points.
All points shown as Earth on the typical wiring diagram are connected to battery negative (not earth).
Where neither the battery positive nor battery negative terminals are connected to earth the following
points must be followed:
Follow the typical wiring diagram as normal for all sections except the earth points.
All points shown as Earth on the typical wiring diagram are connected to battery negative (not earth).
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite Software Manual.
NOTE: Screened 120 impedance cable specified for use with CAN must be used for the
DSENet® (RS485) connection.
DSE stock and supply Belden cable 9841 which is a high quality 120 impedance cable
suitable for DSENet® use (DSE part number 016-030)
Twenty (20) devices can be connected to the DSENet®, made up of the following devices :
NOTE: For further information on the maximum number of modules that can be
connected to the AMSC link and Redundant AMSC link, refer to sections 4.10.5 & 4.10.6
entitled AMSC (Multi-Set Communications) Link and CAN Port (Redundant AMSC).
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite Software Manual.
NOTE: Screened 120 impedance cable specified for use with CAN must be used for the
AMSC link connection.
DSE stock and supply Belden cable 9841 which is a high quality 120 impedance cable
suitable for AMSC link (DSE part number 016-030)
NOTE: A termination resistor MUST be fitted to the first and last unit on the AMSC link.
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Software Manual.
NOTE: The Bus/Load CT is NOT REQUIRED in a system including only one DSEG8680
controller. For further information regarding the advantages of a Bus/Load CT, refer to section
Error! Reference source not found. entitled Bus/Load Current Transformer, or refer to DSE
Publication: 056-007 Advantages of Bus/Load CT.
The controller is factory configured to connect to a 3 Phase, 4 Wire Star connected system. This
section details connections for alternative AC topologies. Ensure to configure the controller to suit the
required topology.
3 PHASE 3 WIRE L1 L2 L3
3 PHASE, 4 WIRE L1 L2 L3
NOTE: The below diagram is applicable for the following AC topologies: 3 Phase 4 Wire
Star, 3 Phase 4 Wire Delta L1-N-L2, 3 Phase 4 Wire Delta L1-N-L3 and 3 Phase 4 Wire Delta
L2-N-L3. For further details of module configuration to suit these different topologies, refer to
DSE Publication: 057-326 DSEG8680 Configuration Suite Software Manual.
NOTE: The below diagram is applicable for the following AC topologies: 3 Phase 4 Wire
Star, 3 Phase 4 Wire Delta L1-N-L2, 3 Phase 4 Wire Delta L1-N-L3 and 3 Phase 4 Wire Delta
L2-N-L3. For further details of module configuration to suit these different topologies, refer to
DSE Publication: 057-326 DSEG8680 Configuration Suite Software Manual.
This example shows the Bus/Load CT in the common load feed for a three phase four wire system,
but the same philosophy is applicable to the other topologies
6 DESCRIPTION OF CONTROLS
CAUTION: The module may instruct an engine start event due to external influences.
Therefore, it is possible for the engine to start at any time without warning. Prior to performing
any maintenance on the system, it is recommended that steps are taken to remove the battery
and isolate supplies.
NOTE: The following descriptions detail the sequences followed by a module containing
the standard ‘factory configuration’. Always refer to your configuration source for the exact
sequences and timers observed by any module in the field.
Control of the module is via push buttons mounted on the front of the module with
Auto Mode A TO
, Alarm Mute/Lamp Test , Open/Close Bus , Manual functions and
Reset .
For normal operation, these are the only controls which need to be operated.
Details of their operation are provided later in this document.
Logo Display
Menu
Navigation Status LEDs
Module Display
Card Text
Display
Breaker LED
Bus Segment 1 Bus Segment 2
Available LED Available LED
Left Blank Reset Alarms Manual Mode Auto Mode Alarm Mute & Right Blank
Button Lamp Test Button
(PLC Use) (PLC Use)
Icon Description
Auto Button
This button silences the audible alarm in the controller, de-activates the Audible
Alarm output (if configured) and illuminates all the LEDs on the module’s facia
as a lamp test function.
There are two controller buttons (left and right) which provide various control
options for the breaker:
Manual
This mode allows manual control of the functions. Once in Manual mode the
module will respond to the breaker button , toggling the bus breaker.
Reset
Menu Navigation
Used for navigating the instrumentation, event log and configuration screens.
Status Page
Status
Bus Closed 15:54 Section
Configurable L-N 0v
Instrumentation
Display Section
L-L 0v
0.0 Hz
6.3 VIEWING THE INSTRUMENT PAGES
NOTE: Depending upon the module’s configuration, some display screens may be
disabled. For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite PC Software Manual.
Selecting Pages
Next
Home
page
Page
etc
Once selected, the page remains on the LCD display until the user selects a different page, or after an
extended period of inactivity (LCD Page Timer), the module reverts to the home display.
NOTE: The display screen will cycle through each instrument parameter unless the scroll
buttons are pressed.
NOTE: The screens in the following examples may not be representative of the current
model but are used for a guide for functionality only.
Configuring Timers
The LCD Page timers are configurable using the DSE Configuration Suite Software.
The screenshot
shows the factory
settings for the
timers, taken from the
DSE Configuration
Suite PC Software.
If an alarm becomes active while viewing the status page, the display shows the Alarms page to draw
the operator’s attention to the alarm condition. The complete order and contents of each information
page are given in the following sections.
STATUS
NOTE: Press the Scroll buttons on the Home Page to view other Configurable
Status Screens if configured. For further details of module configuration, refer to DSE
Publication: 057-151 DSEG8680 Configuration Suite PC Software Manual.
This is the ‘Status’ page, the page that is displayed when no other page has been selected, and the
page that is automatically displayed after a period of inactivity (LCD Page Timer) of the module
control buttons.
L-N 0v
L-L 0v
0. 0 Hz
6.3.1.1 DISPLAY CONFIGURATION
The screen content may vary depending upon configuration. Below is an example of the Displayed
Pages being changed to show Battery related information.
The Displayed Pages section allows a maximum of 10 pages to be displayed. The pages available
are shown in the list below:
• Battery Voltage
• Bus Current
• Bus Power
• Left AMSC Power
• Left Bus- Bus Tie Controllers Connected
• Left Bus- Mains Controllers Connected
• Left Bus Frequency
• Left Bus Phase Rotation
• Left Bus Sets On AMSC Bus
• Left Bus Sets On Load
• Left Bus Voltage L-L
• Left Bus Voltage L-N
• Right AMSC Power
• Right Bus- Bus Tie Controllers Connected
• Right Bus- Mains Controllers Connected
• Right Bus Frequency
• Right Bus Phase Rotation
• Right Bus Sets On AMSC Bus
• Right Bus Sets On Load
• Right Bus Voltage L-L
• Right Bus Voltage L-N
• Synchroscope
LEFT BUS
Contains electrical values of the Bus, measured, or derived from the module’s voltage and current
inputs.
Press the Scroll buttons scroll through the Left Bus parameters.
L1- N 0v
L2- N 0v AC Voltages on Left Bus
L3- N 0v
L2- L3 0v
L3- L1 0v
Bus Current
L1 0A
L2 0A Left Bus Current
L3 0A
0A
Current
L1 0kW
L2 0kW Left Bus Load
L3 0kW
L1 0kVA
L2 0kVA Left Bus Load
L3 0kVA
L1 0kVr
L2 0kVr Left Bus Load
L3 0kVr
L1 0kW
L2 0kVA Left Bus Load
L3 0kVAr
L1 0.00
L2 0.00 Left Bus Load
L3 0.00
Active Config
230V
The current
50.0HZ active
configuration
3 Phase, 4 Wire
Active Config
Synchroscope
✓ 0.00Hz ✓ 0V Synchroscope
Battery Voltage
Battery 24.0 v
Battery Voltage
AMSC
AMSC ID 2 AMSC ID, Bus
Segment
numbers and
Left Segment 1 User Priority
Right Segment 2
User Priority 1
AMSC1 connected
64
0000 0000 0000 0000 AMSC map of
G8660 modules
0000 0000 0000 0000
0000 0000 0000 0000
0000 0000 0000 0000
1
RIGHT BUS
Contains electrical values of the Bus, measured, or derived from the module’s voltage and current
inputs.
Press the Scroll buttons scroll through the Left Bus parameters.
L1- N 0v
L2- N 0v AC Voltages on Right Bus
L3- N 0v
L2- L3 0v
L3- L1 0v
Bus Current
L1 0A
L2 0A Right Bus Current
L3 0A
0A
Current
L1 0kW
L2 0kW Right Bus Load
L3 0kW
L1 0kVA
L2 0kVA Right Bus Load
L3 0kVA
L1 0kVr
L2 0kVr Right Bus Load
L3 0kVr
L1 0kW
L2 0kVA Right Bus Load
L3 0kVAr
L1 0.00
L2 0.00 Right Bus Load
L3 0.00
Active Config
230V
The current
50.0HZ active
configuration
3 Phase, 4 Wire
Active Config
Synchroscope
✓ 0.00Hz ✓ 0V Synchroscope
Battery Voltage
Battery 24.0 v
Battery Voltage
AMSC
AMSC ID 2 AMSC ID, Bus
Segment
numbers and
Left Segment 1 User Priority
Right Segment 2
User Priority 1
AMSC1 connected
64
0000 0000 0000 0000 AMSC map of
G8660 modules
0000 0000 0000 0000
0000 0000 0000 0000
0000 0000 0000 0000
1
ALARMS
When an alarm is active, the Internal Audible Alarm sounds and the Common Alarm LED, if
configured, illuminates.
The audible alarm is silenced by pressing the Alarm Mute / Lamp Test button.
The LCD display jumps from the ‘Information page’ to display the Alarm Page
1/1 Alarms
Digital Input B
Electrical Trip
EVENT LOG
The module maintains a log of past alarms and/or selected status changes.
At the time of writing, the modules log can store the last 250 log entries.
Under default factory settings, the event log is configured to include all possible options; however, this
is configurable by the system designer using the DSE Configuration Suite software.
When the event log is full, any subsequent event overwrites the oldest entry. Hence, the event log
always contains the most recent events. The module logs the event type, along with the date and
time. If the module is configured and connected to a modem, an SMS message is sent on any logged
event.
To view the event log, repeatedly press the Next or Previous Page buttons until the LCD
screen displays the Event Log page.
1 Event Log
Digital Input B
Electrical Trip
Continuing to press the Scroll Down button cycles through the past events after which, the
display shows the most recent alarm, and the cycle begins again.
To exit the event log and return to viewing the instruments, press the Next or Previous Page
buttons to select the next instrumentation page.
COMMUNICATIONS
NOTE: The Modbus Master can be another DSE module communicating through its PLC. For further
details see section 4.10.3 entitled RS485 Ports in this document.
Serial Port
Baud 115200
Slave ID 10
RS485
The modules operate as a Modbus RTU slave device.
In a Modbus system, there is only one Master, typically a PLC, HMI system, PC SCADA system, or
another DSE module using its PLC Comms.
This master requests for information from the Modbus slave (The module) and may (in control
systems) also send request to change operating modes etc. Unless the Master makes a request, the
slave is ‘quiet’ on the data link.
The factory settings are for the module to communicate at 115200 baud, Modbus slave address 10.
‘Master inactivity timeout’ should be set to at least twice the value of the system scan time. For
example, if a Modbus master PLC requests data from the module once per second, the timeout
should be set to at least 2 seconds.
The DSE Modbus document containing register mappings inside the DSE module is available upon
request from support@deepseaelectronics.com. Email the request along with the serial number of the
DSE module to ensure the correct information is sent.
RS485 Modbus RTU diagnostic screens are included; press the Scroll Down button when
viewing the RS485 Serial Port instruments to cycle to the available screens. If experiencing RS485
Modbus RTU communication problems, this information aids troubleshooting.
RS485 Port 1
Shows the state of the RS485
communication lines. These can help
Link Quality 0% diagnose connection problems.
0%
during the packet timeout
Lost Rate Lost Rate: The number of messages that
are discarded (invalid messages)
Warning=(ReadRegister(10,0306,1) >> 11) & 1): reads (hex) 0306 and looks at bit 12 (Warning
alarm present)
ElectricalTrip=(ReadRegister(10,0306,1) >> 10) & 1): reads (hex) 0306 and looks at bit 11
(Electrical Trip alarm present)
Whilst in the Communication section, press the Scroll Down button to access more
information about the USB Slave Connection status.
Network settings are configured using DSE Configuration Suite PC Software. The module must be
rebooted for the changes to take effect.
USB Connection
Connected/Inactive: Indicates the
connection status of the USB Slave
Connected Connection which is normally used
for module configuration.
DHCP Enabled
Network
Subnet Mask: The
Subnet mask configured network
subnet mask of the
module.
0.0.0.0
Network
Gateway Address: The
Gateway address configured network
gateway address of the
module.
0.0.0.0
Network
DNS Address: The
DNS address configured network
DNS address of the
module.
0.0.0.0
Network
DHCP
Host DHCP: The DHCP settings
Domain of module if configured.
unique to every Ethernet
Vendor device.
MISCELLANEOUS
Whilst in the Miscellaneous section, press Scroll Down button to access more information
about the data logging settings.
Inserting a USB storage device to the USB host connector on the rear of the module displays the
following change to the page.
Data Logging
Log to internal memory
Logging inactive If external USB storage
Do not remove USB drive device is connected
Data Logging
Data Logging
Memory Remaining
Memory space remaining, this depends
on what size memory drive is fitted
2032 (Max 16GB) or allocated internal (2MB)
memory left available.
ABOUT
Contains important information about the module and the firmware versions. This information may be
asked for when contacting DSE Technical Support Department for advice.
Use the Scroll buttons to access more information about the module.
About
Variant: DSEG8680
Variant G8680 Model: the module type.
Model Bus Tie USB ID: Unique identifier for
PC USB connection
USB ID 1BAD1DEA
Bootstrap: Bootstrap
About software version
Bootloader: Firmware
Bootstrap V3.1.3 Update bootloader software
Bootloader V3.1.1. version
LCD Heater
Heater Fitted Heater Fitted/Not Fitted:
Temperature Indicates if the module has a
display heater fitted to
enable operation at lower
temperatures.
32ºC
7 OPERATION
7.1 BUS TIE CONFIGURATION
There are two possible configurations for the Bus tie controller which can enabled on the Application
page in the Configuration Software.
BUS TIE
The Bus Tie Configuration enables control of two bus segments on the left (Segment 1) and right side
(Segment 2).
LOAD SWITCHING
The Bus Tie controller can be used for load switching by selecting Load Switching in the Configuration
Suite.
Load
All generators are started using the Remote Start input and when the generators become available,
they close onto a dead bus.
As the DSEG8680 breaker is open, the two sides are separate systems. This means a DSE8600 on
either side attains their own token to know it is safe to close onto the dead bus. Both sides of the
bus-tie are working independently with the load demand scheme.
[JR7][IR8]
Before the DSEG8680 is requested to close its breaker it must attain a token that is different to the
tokens of the DSEG8600s.Once it has this token it will gain control of one side of the generator bus
(depending on configuration) and synchronizes it to the other. Once in sync the DSEG8680 closes its
breaker and releases its token and then both sides of the bus are considered as one. If the Close Bus
Input is removed, the DSEG8680 opens its bus breaker without requiring a token Once the breaker is
open, both sides become independent again and each attain their own token.
The Left Segment and Right Segment numbers are used to identify Bus segments.
This is illustrated in the example below.
Example
Hint: If
the Bus Tie Controller is
closed then Bus Segment 2 (Left)
and Bus Segment 3 (Right)
become a Segment Group.
2. Segment Groups are dynamic, being created, destroyed, and altered as the system operates.
3. A Load Share Scheme operates within a single Segment Group.
4. A Load Demand Scheme operates within a single Segment Group.
5. A Segment Group can have one and only one Master Token, though it may have none if no
module requires one.
6. A Master Token controls one and only one Segment Group.
7. A module is considered to be in a Segment Group that contains a segment that the module is
directly connected to, i.e., it is broadcasting that segment number in its Configuration
Broadcast message.
8. All modules must continually perform the task of building a map of the segment groups. This
is done using the segment numbers in the Configuration Broadcast message from each
module and the state of the bus breakers in the Bus Tie and Mains Controllers. A closed
breaker in these modules joins two segment groups to form one larger one.
WARNING!: The Left Bus Segment number and Right Bus Segment number cannot be the
same! This is critical for safe control!
The controller will first request a control token and once received the bus tie will close the breaker. If
the “Bus Closed” auxiliary input fails to indicate that the breaker is closed, the bus tie will open the
breaker again and raise an alarm.
The configuration options to allow the bus breaker to close onto a dead bus are:
• If module is in manual mode, then the breaker button that is pressed determines which bus is
controlled. If the left button is pressed then generation on the left bus will be controlled to
synchronise the busses. Similarly, if the right button is pressed then generation on the right
bus is controlled.
• If the breaker is being closed by a GenComm simulated button press message then the
decision is the same as above based on whether the left or tight breaker button is being
simulated.
• If the breaker is being closed by a GenComm control key then the message determines which
bus is controlled: Close Left or Close Right.
• If the module is in auto mode and there is a digital input for “Close Bus Tie” and there is
another digital input for “Control Right Side of Bus Tie” then this second signal determines
which side of the bus tie is controlled when the close signal becomes active; if it is inactive
then the left side is controlled, and if its active the right side is controlled.
• If the module is in auto mode and there is a digital input for “Close Bus Tie” and there is no
digital input for “Control Right Side of Bus Tie” then a setting in the config determines which
side of the bus tie is controlled.
If a suitable bus to control can be determined, the bus tie will negotiate on that bus for the master
token, to allow it exclusive generator control.
If the controller fails to get the token in a configured time, an “ nable to Obtain Master Token” alarm is
raised.
Two output sources are available to indicate when the master token has been obtained for each side
of the breaker. These can be used to drive the user-defined LEDs in order to indicate when a bus is
being controlled for ramping or synchronising.
Once the master token is obtained, the tie will synchronise the busses and close the breaker. If the
bus tie cannot control a suitable bus for synchronisation, a check-sync will be performed instead to
determine if the breaker can be closed.
If a “Bus Closed” auxiliary input fails to indicate that the breaker is closed, the bus tie will open the
breaker again and raise an alarm.
Failure to synchronise/check-sync in a configurable time will result in a “failed to Sync” alarm.
7.6 RAMPING ON
At the end of the synchronisation phase, the G8680 will close the bus tie. If there is generation on the
busses on both sides of the breaker then the generators will almost certainly be no longer sharing
power equally. The bus tie must now equalise the power sharing if it can.
Before closing the breaker, the bus tie will record the overall power levels from the two bus segments,
information which is available from the AMSC. Once the bus tie breaker is closed the bus tie will
switch the generators on both sides to constant power mode. It will then set new power levels (via the
AMSC) for the generators for them to share the load equally (as a percentage of their capability).
Once this sharing has been achieved, the bus tie will signal the SEGMENTS_COMBINED flag to
indicate that the two power segments are now a single group and will release the master control
token. This will allow another module to take control of the combined segment to apply the configured
power scheme.
NOTE: The following descriptions detail the sequences followed by a module containing
the standard ‘factory configuration’. Always refer to your configuration source for the exact
sequences and timers observed by any module in the field.
MANUAL MODE
Activate Manual mode be pressing the pushbutton. An LED indicator beside the button
confirms this action.
Manual mode allows the operator to open and close the left and right breakers by manually toggling
the left and right breaker buttons.
The open/close breaker digital input has no effect in MANUAL mode.
AUTOMATIC MODE
Activate auto mode by pressing the A TO pushbutton. An LED indicator beside the button confirms
this action.
Auto mode will allow the DSE8680 to monitor the open/close breaker input and control the tie breaker
accordingly.
The fascia mounted breaker control button has no effect in AUTO mode.
Breaker LED
There are two breaker control buttons, designated the left and right bus buttons. They are only active
when the module is operating in manual mode.
Their function differs depending on the state of the two busses and the state of the bus tie breaker
itself.
• If the bus tie is closed, pressing either breaker button causes an open request to be made.
• If the bus tie is open, and one or more busses are dead, then a close request is made, and
the breaker will be closed based on the configuration options in effect (which may prevent
closure under various combinations of live and dead busses).
• If the bus tie is open, and both busses are live, then an attempt will be made to synchronise
the busses before closing the bus tie. If the left button was pressed, then the left bus will be
controlled, and synchronised with the right. If this is not possible (for example if there is a
mains supply connected to the left bus or there are no controllable generators on that bus)
then an alarm will be raised, and the breaker will not close. Similarly, if the right button is
pressed, the right bus will be controlled, and synchronised with the left.
The breaker control buttons can also be simulated via GenComm. In that case the button
operation is the same.
The bus and breaker states are indicated on the front of the module by three green LEDs as follows:
• Left Bus LED: This is illuminated to show that the bus is available.
• Right Bus LED: This is illuminated to show that the bus is available.
• Breaker LED: This shows the state of the breaker auxiliary input.
Note that a bus is available if it has voltage and frequency within the minimum and maximum bus
availability settings and can thus be synchronised. If the LED is extinguished, it is outside these
ranges.
NOTE: If a bus available LED is extinguished this does not indicate a dead bus.
BREAKER CONTROL
When the breaker is closed using the breaker button (or simulated buttons) the synchronisation
direction (left to right or right to left) is determined by which button is pressed. However, when using a
digital input or GenComm control key to close the breaker, the direction is not specified. Instead, two
user-configurable options and 1 digital input are used to determine the bus to control when
synchronising.
8 PROTECTIONS
8.1 ALARMS
NOTE: For further details of module configuration and available alarms, refer to DSE
Publication: 057-326 DSEG8680 Configuration Suite PC Software Manual.
When an alarm is active, the Internal Audible Alarm sounds and the Common Alarm output if
configured, activates.
Example
1/1 Alarms
Electrical Trip
The audible alarm is silenced by pressing the Alarm Mute / Lamp Test button.
The LCD display jumps from the ‘Information page’ to display the Alarm Page
In the event of an alarm, the LCD displays the appropriate text. If an additional alarm, then occurs, the
module displays the appropriate text.
Example:
LED Indicator
illuminates when
a Digital Input is
active.
Example:
In the event of an alarm the LCD jumps to the alarms page and scroll through all active alarms.
By default, warning alarms are self-resetting when the fault condition is removed. However, enabling
All Warnings Are Latched causes warning alarms to latch until reset manually. This is enabled using
the DSE Configuration Suite in conjunction with a compatible PC.
Fault Description
Fault Description
Fault Description
Battery High Voltage Output The module detected that a battery charger connected by
1 DSENet® had issued a Battery High Voltage alarm on its Output 1.
Battery High Voltage Output The module detected that a battery charger connected by
2 DSENet® had issued a Battery High Voltage alarm on its Output 2.
Battery Low Voltage The module detected that its DC supply voltage had fallen below
IEEE 37.2 – 27 DC Undervoltage the Plant Battery Undervolts Warning Trip level for the configured
Relay delay timer.
The module detected that a battery charger connected by
Battery Low Voltage Output 1
DSENet® had issued a Battery Low Voltage alarm on its Output 1.
The module detected that a battery charger connected by
Battery Low Voltage Output 2
DSENet® had issued a Battery Low Voltage alarm on its Output 2.
The module detected that a battery charger connected by
Battery Temperature Sensor
DSENet® had issued a Battery Temperature Fail alarm on its
Fail Output 1
Output 1.
The module detected that a battery charger connected by
Battery Temperature Sensor
DSENet® had issued a Battery Temperature Fail alarm on its
Fail Output 2
Output 2.
The module detected the bus voltage asymmetry had risen above
Bus Asymmetry High
the configurable Trip level for the configured delay timer.
The module detected the bus voltage negative sequence had risen
Bus Over Negative Sequence
above the configurable Trip level for the configured delay timer.
The module detected the bus voltage zero sequence had risen
Bus Over Zero Sequence
above the configurable Trip level for the configured delay timer.
Bus Under Positive The module detected the bus voltage positive sequence had fallen
Sequence below the configurable Trip level for the configured delay timer.
The module detected that its internal calibration has failed. The
Calibration Fault unit must be sent back to DSE to be investigated and repaired.
Contact DSE Technical Support for more details.
The module detected that a battery charger connected by
Charger Fan Locked
DSENet® had a Charger Failure alarm.
The module detected that a battery charger connected by
Charger High Temperature
DSENet® had a High Temperature alarm.
The module detected that a battery charger connected by
Charger Mains High Current
DSENet® had a Mains High Current alarm.
Fault Description
NOTE: The fault condition must be resolved before the alarm can be reset. If the fault
condition remains, it is not possible to reset the alarm.
Electrical Trip Alarms are latching and stop the Bus Tie but in a controlled manner.. To restart the Bus
Tie controller the fault must be cleared, and the alarm reset.
Example:
Fault Description
Fault Description
Fault Description
Bus Under Positive The module detected the bus voltage positive sequence had fallen
Sequence below the configurable Trip level for the configured delay timer.
The module detected that its internal calibration has failed. The
Calibration Fault unit must be sent back to DSE to be investigated and repaired.
Contact DSE Technical Support for more details.
Fault Description
The module detected that another module on the AMSC link had
AMSC ID Error
the same GenSet AMSC ID configured.
The module detected that another module on the AMSC link was
incompatible. Check all the module firmware version numbers
(under About | Application Number on the modules’ displays) and
AMSC Old Version Unit
ensure all are the latest version firmware. Use the DSE
Configuration Suite Software to upgrade the firmware (Tools |
Update Firmware) of the older modules.
That module detected that the AMSC and Redudant AMSC
AMSC 1 and 2 Failure
communication failed, most likely caused by it being disconnected.
That module detected that the AMSC communication failed, most
AMSC 1 Link Failure
likely caused by it being disconnected.
That module detected that the number of modules on the AMSC
AMSC 1 Too Few Sets was less then the configured Minimum Modules on AMSC Link
setting.
That module detected that the Redudant AMSC communication
AMSC 2 Link Failure
failed, most likely caused by it being disconnected.
That module detected that the number of modules on the
AMSC 2 Too Few Sets Redundant AMSC was less then the configured Minimum Modules
on AMSC Link setting.
NOTE: Depending upon module configuration, some parameters in the ‘Running’ Editor
may not be available. For more information refer to DSE publication 057-151 DSEG8680
Configuration Suite PC Software Manual available from www.deepseaelectronics.com
• The ‘Running’ Configuration Editor is accessible without stopping the engine. All protections
remain active whilst using the ‘‘Running’ Configuration Editor.
Editor Display
Contrast
53%
Editor Display
Language
English (United Kingdom)
Editor Display
Commissioning Screens
Active
NOTE: Pressing and holding the Menu Navigation buttons provides the auto-repeat
functionality. Values can be changed quickly by holding the navigation buttons for a
prolonged period.
• Press and hold the Tick button for 5 seconds to access the editor.
• Press the Tick button to adjust the value (flashing) using the .Scroll buttons
NOTE: The editor automatically exits after 5 minutes of inactivity to ensure security.
• Press and hold the Tick button for 5 seconds to exit the editor and save the changes.
Editor Display
Commissioning Screens
Active
• Press the Tick button to adjust the value (flashing) using the .Scroll buttons
10 COMMISSIONING
10.1 BASIC CHECKS
Before the system is started, it is recommended that the following checks are made:
The unit is adequately cooled and all the wiring to the module is of a standard and rating compatible
with the system. Check all mechanical parts are fitted correctly and that all electrical connections
(including earths) are sound.
Check all mechanical parts are fitted correctly and that all electrical connections (including earths) are
good. The unit DC supply is fused and connected to the battery and that it is of the correct polarity.
Check the operation of the AMSC Link. Use the DSE Configuration Suite to check this in the SCADA |
BUS | AMSC Link page. Verify the number of Set On The Bus is equal to that of the number of
DSEG86xx modules.
Set the modules internal clock/calendar to ensure correct operation of the scheduler and event
logging functions. For details of this procedure, see section entitled Front Panel Configuration
If, despite repeated checking of the connections between the controller and the customer’s system,
satisfactory operation cannot be achieved, then the customer is requested to the DSE Technical
Support Department
10.2 METERING
CAUTION!: Failure to perform the Metering steps results in incorrect power factor and kW
calculations leading to problems with kW and kvar load sharing if not corrected.
WARNING!: Steps must be taken to ensure that when a CT is open circuit, the
system/generator is in a safe state to work around.
Check to ensure that the CTs on L1, L2 & L3 are connected to their respective connection on the DSE
module.
This is tested by loading the bus with a purely resistive load (around 10% of the main’s size) across
the three phases. If the CTs are wired correctly to the DSE module, it displays unity power factor (1.0
pf) across all three phases. If unity power factor is not displayed the CTs have been wired to the
wrong phases on the DSE module.
NOTE: Checking that the CTs are on the right phase MUST be completed prior to checking
if the CTs are in the correct direction. CTs on the wrong phase also cause negative kWs.
Check to ensure that the CTs on L1, L2 & L3 have been mounted for the correct orientation for current
flow and that the S1 and S2 have not been swapped over.
This is tested by loading the bus with a purely resistive load (around 10% of the main’s size) across
the three phases. If the CTs’ S1 and S2 are wired to correctly to the DSE module, it displays positive
kW. If negative kWs is displayed the CTs’ S1 and S2 have been swapped around.
10.3 COMMUNICATIONS
CAUTION!: Failure to perform the Communications steps results in the controllers being
unable to communicate to the other DSE controllers leading to problems during load sharing.
NOTE: For further details of module configuration, refer to DSE Publication: 057-326
DSEG8680 Configuration Suite Software Manual.
Check to ensure that all the modules are connected are communicating correctly on the AMSC link
and Redundant AMSC (if used).
This is tested by connecting the DSE module to a PC with the DSE Configuration Suite PC Software
installed and going to the SCADA | Bus | AMSC Link section. The information shown in this section
changes dynamically depending on whether the AMSC Link or Redundant AMSC Link is in use. The
number of Sets On The Bus must be the same as the number of DSEG8600 (Multi Set)s on the link.
The number of Mains Controllers On The Bus must be the same as the combined number of
DSEG8660s in Mains Controller mode.
If these numbers do not match up there is a fault on the active link. To find the module with the fault,
connect into each module individually until the Sets On The Bus or Mains Controllers On The Bus
reports 1.
If these numbers do match up, then the link which is currently in use is working correctly. To test the
other link, remove the active link connection from any module. All the modules should then alarm with
the same number link failure (AMSC 1 Link Failure or AMSC 2 Link Failure). If all the modules do not
have the same number link failure, then at some point the AMSC and CAN connections have been
crossed. If all the modules do have the same number link failure, the communication is automatically
transferred onto the other link. Check the numbers in SCADA again to ensure the other link is
operating correctly.
When a Bus Sensing Failed alarm is activated, it is important that each segment is isolated and that
breakers (G8660 bus breakers and G8680 ties) are opened.
Example
Example: If
a Bus Sensing Failed
Alarm is activated then opening
the Bus Tie Controller isolates Bus
Segment 2 and Bus Segment 3.
[JR9][IR10]
To check each segment is live, a generator needs to be powered up to ensure that there are no
modules with the Bus Sensing Failed alarm that are active. This ensures that there are no modules on
a different segment that have this segment ID. See section 3.8.5.2 in document 057-324 entitled
DSEG8660 Configuration Suite PC Software Manual for further information.
The user must then disconnect each module’s bus sensing on this segment and check that the alarm
occurs, this confirms that the modules on this segment are correctly configured.
WARNING!: The Bus Segment number and Load Segment number cannot be the same!
This is critical for safe control!
11 FAULT FINDING
NOTE: The below fault finding is provided as a guide checklist only. As the module can be
configured to provide a wide range of different features, always refer to the source of the
module configuration if in doubt.
11.1 STARTING
11.2 INSTRUMENTS
11.3 LOADING
Check:
• That the CT primary, CT secondary and VT ratio settings
are correct for the application.
• That the CTs are wired correctly with regards to the
direction of current flow (p1,p2 and s1,s2) and additionally
ensure that CTs are connected to the correct phase (errors
occur if CT1 is connected to phase 2).
Inaccurate measurements on • Remember to consider the power factor:
controller display (kW = kV A x Power Factor)
• The DSE8xxx MII modules are true RMS measuring so
gives more accurate display when compared with an
‘averaging’ meter such as an analogue panel meter or
some lower specified digital multimeter.
• Accuracy of the controller is better than 1% of full scale.
Voltage full scale is 415 V AC ph-N so accuracy is ±4.15 V
(1% of 415 V).
11.4 COMMUNICATIONS
11.6 MISCELLANEOUS
PACK OF PLUGS
INDIVIDUAL PLUGS
NOTE: A maximum of twenty (20) expansion modules can be connected to the DSEG8680
DSENet® Port
NOTE: DSENet® utilises an RS485 connection. Using Belden 9841 (or equivalent) cable
allows for the expansion cable to be extended to a maximum of 1.2 km.
DSE Stock and supply Belden 9841 cable. DSE Part Number 016-030.
13 WARRANTY
DSE Provides limited warranty to the equipment purchaser at the point of sale. For full details of any
applicable warranty, refer to the original equipment supplier (OEM)
14 DISPOSAL
14.1 WEEE (WASTE ELECTRICAL AND ELECTRONIC EQUIPMENT)
If you use electrical and electronic equipment you must store, collect, treat, recycle,
and dispose of WEEE separately from your other waste