EVO Moduler EN
EVO Moduler EN
AHU N o 18.08.003
Range : EVO
aera.com.tr
AERA was founded in 2016 by national and international
Chillers
A E R A A I R I N N O V A T I O N 3
STANDARDS
EVO-M Modular Air Handling Units introduce comfortable air to indoors with high energy efficiency and European Norm
compatible design. Below required norms and standards are applied during the design process;
EN 1886
Air Handling units are classified according to their casing performance with the European Norm; EN1886. Testing and
classification procedures are explained in the standard.
D1 <4
D2 <10
D3 > 10
4
Casing Air Leakage
This is a key parameter to understand for one hand if all the energy consumption used in the fan is used to generate the
exact airflow of the operation set-point, and on the other hand to understand if we have infiltration of non-handling air inside
the AHU. The casing air leakage test is performed after the mechanical strength test. It performed by subjecting the unit
to an internal negative pressure of 400 Pa, measuring the leakage rate through the casing. Then the same procedure is
repeated but now subjecting the unit to an internal positive pressure of 700 Pa, and leakage rate shall be measured.
Casing Air Leakage @ + 700 Pa Casing Air Leakage @ + 400 Pa
Leakage Maximum leakage rate Leakage Maximum leakage rate
Class (f700) ( l x s-1xm-2 ) Class (f400) ( l x s-1xm-2 )
L3 1,9 L3 1,32
L2 0,63 L2 0,44
L1 0,22 L1 0,15
6
5
1. AHU under test
2. AHU test pressure gauge
3. Bleed valve as alternative to variable speed fan
4. Variable Speed Fan
5. Air Flow Measurement
7 6. Inlet Plate
7. Outlet Plate
Because of the leakages through the internal design of the filter assembly, the filter of the unit may not be performing
as its specification. This criteria is especially important for buildings with high IAQ demands, for example hospitals and
laboratories. In the filter bypass leakage test, the unit is subjected to an internal positive and negative pressure of 400 Pa
2 3
2
4
6
3 4
5
7
1
5
A E R A A I R I N N O V A T I O N 5
STANDARDS
Thermal Transmittance
Air Handling Units are sized in heating/cooling capacity by neglecting the losses from the casing. Especially for the outdoor
installaitons, according to the temperature difference between the supplied air and outdoor air, significant losses may
happen with poorly designed casings. EVO product family is designed with 50 mm Mineral Wool insulated panels to
reduce the thermal leakage from the casing. Adequate design is carried out for weakest surfaces like corners, locks and
hinges and duct connection panels.
Thermal transmittance is measured and calculated with 20K temperature difference between the outdoor air and inside
the unit.
Because of the thermal losses in an air handling units components like section connections, structural profiles, doors
and hinges, casing corners and panel internal/external sheet metal, the installation properties of the casing can not be
homogenous through the whole casing. Places such of those where the insulation properties are reduced are called the
Thermal Bridges. If the Thermal Bridges can not be avoided, there will be significant amount of heat loss and condensaiton
will occur on these surfaces damaging Air Handling Units casing.
The test is performed in conditions when the difference in average temperature between the interior and exterior temperatures
is steady at 20 K. The point at the highest temperature on the outer surface of the casing shall be measured. The ratio
between the difference between the interior average air temperature and the maximum external surface temperature and
the average temperature difference between the air on the interior and exterior of the unit determines the thermal bridge
factor.
ti2 Ti - tsmax
ti1
ta1 ta6 kb =
ti - ta
250
25 ti6
0
ti5
k b = Δtmin / Δtair
ti4 ti10
250 ta3
ti3 ti9 Where:
Height from floor
ti8 ti14
ta2
300~400 mm
250
ti7
ti3 Δtmin: is the smallest temperature difference,
ti12 Δtmin = ti - tsmax
100
250
ti11
250 ti16 Δtair: Temperature difference between the interior
100
ta5 tn4
ti15
and exterior air, Δtair = ti - ta
100
100
100
6
Below rendered psychometric chart presents the outdoor air conditions where condensation will start in an Air Hadnling
unit with different Thermal Bridging classes. From the diagram it can be read that for an outdoor air temperature of -12°C
inside the unit casin and 24°C installaiton space, condensation will not start before 18%RH for TB4, 28%RH for TB3, 40%
for TB2 and 57% for TB1.
10 11 11 12 12 13 13
5 0 5 0 5 0 5
30
10 34 15
0 0
0.96
30 32 14
0.98
30 5
0.94
TB2 (kb=0,60) 24°C, 40 % r. h. 90 31
80 30 28
13
W 5
ET
BU 27
75 LB
0.92
TE 26
M 13
PE 0
70 RA 25
TU
25 RE
-° 24
20 25
65 C 12
23 5
25 21 0
J/
20
ENTHALPY - kJ / kg
PY
SPEC
AL
19 11
50 5
°C
TH
90%
IFIC
P-
EN
20 15 18
EM
20
VOLU
1
45
NT
17
11
TB
0.88
80%
0
TIO
ME m
16
RA
40 20
TU
³/kg
15
%
SA
25
10
5
70
35 14
15 13
2
%
30
TB
10
60
10 12 0
15
20 11
0.86
25
%
50
15 10 95
10
10
3
% 9
10 15
TB
0.84
10
%
40
8
90
5
5 7
TB 4
85
-5 0 5
0 8% 0
0.80
-1 20% 4
0
6%
-5 IDITY 80
-1 HUM 3
TIVE
0.78
5
-10 RELA 4%
%10 -10 2
0.76
-15
2%
0.74
0.72
-20 1 75
-40
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60
DRY BULB TEMPERATURE - °C
70
15 20 25 30 35 40 45 50 55 60 65
Casing of an air handling units not only helps to reduce the thermal and air leakages but also reduces the transferred sound
from the casing to the supplied air. The sound insulaiton of the casing is named as the Transition Loss and measured for
1/3 Octave Band and listed in the casing specifications.
A E R A A I R I N N O V A T I O N 7
STANDARDS
All manufacturers are legally obliged to follow ECO-DESIGN directives, which are a set of
the European Union's regulations that state use of energy for energy-consuming products.
LOT6 of the directive reviews the ventilation devices and air handling units and is affective
in the European Parliament with the EU directive number 1253/2014 and 1254/2014. The
ECO-DESIGN directives, prepared by the European Council for the purpose of replacing
low energy-efficient products in the market with those of high efficiency, have been
accepted as a prerequisite for CE marking with the dates specified and the entry of non-
conforming devices into EU countries is prohibited.
Within the scope of the ECO-DESIGN directive, which has been in force since January 1st 2016, a number of sub-limit
values have been defined for air handling units, such as fan, heat recovery exchanger and filter efficiency. There are also
directives concerning the operation of the air handling unit.
The Directive has been created for ventilation devices and air handling units where some
For which applications does the
or all of the air contaminated by human activity or building emissions in the interior is
ECO-DESIGN directive apply?
replaced by fresh air from outside.
8
Unidirectional Ventilation Units (UVU)
* Nominal Effective power supply at nominal external pressure and air flow, including electric power supply (kW), fan motors and drives of
motors.
In the Directive, the limit value for minimum fan efficiency and SFPint is specified as follows:
Maximum allowed SFP int value for model Plate / Rotary q* < 2m /s
2 3
1.200 + E - 300 x q / 2 - F 1.100 + E - 300 x q / 2 - F
device HR q ≥ 2m /s 3
900 + E - F 800 + E - F
HR efficiency addon, E Plate / Rotary HR ( t-67) x 30 ( t-73) x 30
Model Unit 0 0
No M filter 160 150
Filter correction coefficient, F
No F filter 200 190
No M + F filter 360 340
Variable speed drive requirement Yes Yes
Obligation to monitor pressure drop for filters No Yes
* 1 EN 308 conditions are internal and external weather conditions where condensation has not occurred and should be taken as
follows. OUTDOOR AIR CONDITIONS: 5 °C ROOM CONDITIONS: 25 °C, 28 % RH
* 2 Air flow at the working point of the device (m 3/s)
A E R A A I R I N N O V A T I O N 9
STANDARTLAR
According to EN 13779, the SFP is calculated as the ratio of the fans of the air supply unit provided by the unit.
OUTSIDE AIR
does not take the ducting system ∆Pext, EHA
inefficiencies into consideration.
This provides a more accurate
comparison between units. The
internal losses to be taken into
account in the SFPint calculation are
pressure losses in the heat recovery
exchanger, filter and housing.
SUPPLY AIR
Sample Calculator: The table below
EXHAUST AIR
Where the ventilation unit is not designed for a single operating point, compliance with the ECO-DESIGN directive should
be indicated on the unit operating curves. The following chart shows an ECO-DESIGN performance curve for an air
handling unit with variable airflows.
PERFORMANCE CURVE
1400
1200
External Static Pressure (Pa)
1000
AIR PERFORMANCE CURVE
800 ECO DESIGN 2018
ECO DESIGN 2016
600
MAXIMUM RECOMMENDED AIR VOLUME (m3/h)
0
0
250
500
750
1000
1250
1500
1750
2000
2250
2500
2750
3000
3250
3500
3750
4000
10
EUROVENT
The following steps should be taken while calculating the class of the air handling unit;
It is assumed that the air handling unit belongs to a class and the values belonging to this class are noted in the table.
For the design working point, the fan static pressure increase, external static pressure loss, cross-sectional speed,
fan power and, if the unit belongs to subgroup 1, the HRS heat recovery exchanger efficiency and pressure drop are
calculated.
Depending on the velocity, the pressure correction factors ΔPx is calculated if it belongs to subgroups 1 then ΔPy and
ΔPz are additionally calculated.
The reference power consumption (Pair side-ref) for the associated air line (fresh air or exhaust) is calculated.
Finally, the reference power consumption factor (fs-Pref) is calculated. If this value is equal to 1 or smaller, the unit meets
the requirements of the first accepted class. If it is greater than 1, the same procedure should be repeated by adopting
a lower subclass.
A E R A A I R I N N O V A T I O N 11
STANDARTLAR
{ ( Vsınıf
( {
1.4
∆P x = (∆Ps-dahili - ∆Ps-HRS) * 1-
Vs
∆Ps-internal = Δps– static - Δps– external internal pressure drop across components; exclusive system effect pressure
drops [Pa]
∆Ps-static = useful fan static pressure increase measured between fan inlet and fan outlet [Pa]
∆Ps-external = external (ductwork system) pressure drop [Pa]
∆Ps-HRS = HRS pressure drop [Pa] (0 if no HRS or subgroup 2 or 3)
Vclass = value from Table 2 [m/s]
Vs = velocity in AHU filter (fan if no filter) cross section [m/s]
∆P y = ∆Ps-HRS - ∆Pclass
Pair side-ref = fan reference power [kW] (use Psup–ref for supply air side Pext–ref or extract air side)
q v-s = air volume flow rate [m 3/s]
NG ref = Fan Efficiency Grade corresponding to the class value (see Table 2)
a,b = coefficients as per Table 3 below.
Pair side-ref a b
≤ 10 kW 4.56 10.5
> 10 kW 1.1 2.6
The values from the calculations made in the previous steps are used in the following formula. If the result is less than or equal
to 1, the unit meets the requirements of the accepted energy class, otherwise the same procedure must be repeated by
adopting a lower subclass.
Ps-bes + Ps-emş
fs-Pref = ≤1
Pbes-ref + Pemş-ref
fs-Pref = absorbed power factor
Ps-sup = active power supplied from the mains, including any motor control equipment, to selected supply air fan [kW]
Ps-ext = active power supplied from the mains, including any motor control equipment, to selected extract air fan [kW]
Psup-ref = supply air fan reference power [kW]
Pext-ref = extract air fan reference power [kW]
12
VDI 6022
A E R A A I R I N N O V A T I O N 13
STANDARTLAR
EN 13053: Ventilation for buildings - Air handling units - Rating and performance for units, components and sections
The performance tests of air handling units and components and the classification of velocity, total power consumption
and system energy efficiency in the unit are made according to EN 13053 standard.
V1 ≤ 1.6
V9 > 3.6
P3 ≤ Pm ref x 0.95
( (
∆Pstat 0.925 0.95
P4 ≤ Pm ref x 1.00 Pm ref = * (qv + 0.8)
450
P5 ≤ Pm ref x 1.06
P m ref [kW] reference power input
∆P stat [Pa] sstatic pressure at the fan section
P6 ≤ Pm ref x 1.12
qv [m 3/s] air flow
P7 > Pm ref x 1.12
H1 ≤ 71
e1:1
ηe = ηt x
( 1-
1
ε (
η e [%] Energy Efficiency
H2 ≤ 64 η t [%] Thermal efficiency under dry conditions
ε [-] Performance Coefficient
H3 ≤ 55
If supply air and exhaust air flows are not equal and no
H4 ≤ 45 information is available on efficiency, the efficiency is
calculated using the following empirical formula.
H5 ≤ 36
( (
Exhaust air flow 0.4
ηt = ηt 1:1 x
H6 - Fresh air flow
The filter pressure losses during design should be calculated by taking the arithmetic mean of the initial and final pressure
losses. The final pressure drops according to the filter classes are indicated in the standard with the following values.
G1 - G4: 150 Pa
M5 - F7: 200 Pa
F8 - F9: 300 Pa
14
CLIMATIC TEST CHAMBER
The air handling units produced in our company are tested and certified by independent organizations and also subjected
to tests in the AERA-ANEMO laboratory in order to carry out the design verification procedures.
The ANEMO laboratory, which is designed in accordance with the European Norms and Directives used, carries out tests
according to the following criteria;
• EN 308 Heat exchangers-Test methods for determining the performance of heat recovery devices from air to air and
waste gases
• EN 1886 Ventilation for Buildings - Air Handling Units - Mechanical Performance
• EN 13053 "Air handling units - Classification and performance for devices, components and cells"
• EN 13779 "Performance requirements for ventilation and room conditioning systems"
• European Union Energy Commission (EU) No 1253/2014 "ECO-DESIGN requirements for ventilation equipment"
• EN 305 "Performance specifications for heat exchangers and test procedures for performance measurement"
• ISO 5167-4: 2003 "Flow measurement with differential pressure measurement devices placed in circular cross-section
pipes - Part 4: Venturi pipes"
For air performance tests, two sealed and isolated volumes are used for indoor and outdoor conditions. The thermal
efficiency and capacity tests of air handling units and air performance tests can be carried out in 5200 m3 / h air flow and
-20°C outside and +37°C indoor conditions.
Precision measurement equipment and data acquisition software are used for determining the thermal and mechanical
performance of the unit such as efficiency, thermal bridging, thermal transmittence and air leakage.
AIRFLOW AIRFLOW
MEASUREMENT MEASUREMENT
STATION STATION
AIR CONDITIONER
AIRFLOW
MEASUREMENT
STATION
AIRFLOW
MEASUREMENT
STATION
AIR CONDITIONER
HUMIDIFIER
All of the equipment used during the test is periodically checked and calibrated by the accredited institutions. The main
test and auxiliary equipment found in the ANEMO laboratory;
A E R A A I R I N N O V A T I O N 15
SELECTION SOFTWARE
16
Components such as coils, exchangers, etc. may cause
prolonged delivery times of air handling units. As a part of
AERA's rapid delivery policy, such components are kept
in stock at the capacity values used frequently. In the
selection software, the components with stock are shown
to the user. If the unit configuration is formed with these
components, the selected EVO Modular Air Handling Unit
is produced with quick delivery option.
A E R A A I R I N N O V A T I O N 17
CASING DESIGN
EVO Modular Air Handling Unit's casings are engineered with today's standards, according to future needs. By eliminating
the defects of traditional casings, high thermal and acoustical performance have been achieved, mechanical strength
and corrosion resistance have been increased. As a result, a compact body that provides easy operation and service has
emerged.
Performance values were calculated prior to the actual product testing, using modern engineering methods developed by
3D computerized design and analysis during design stage. Subsequently, these values were verified with tests made in
accordance with relevant standards in our modern testing laboratory.
PVC Frame
The panels to prevent the formation of thermal bridging are made up of sheet metals and sealing gaskets that are fixed on
a specially designed PVC frame. Since the inner and outer panel sheets are not connected, thermal bridging from metal
surfaces is prevented.
With the help of the PVC frame used, continuous and homogeneous insulation was obtained on the panels. With this
structure on the sides of the panel, the thickness remain the same for each surface. The air gap in the PVC profile increases
the thermal resistance of the profile and reduces the total heat transfer coefficient.
Unit Components
The components that may cause thermal bridging due to the connection between the inner and outer air flow in the central
body are locks and hinges and similar connection components. This connection is evaded by connecting all components
externally and a seamless insulation is provided on the casing.
PANEL
DRAIN PAN
18
EASE OF INSTALLATION
Adjustable Feet
Planar disturbances at the installation site result in the fact that the central covers can not be fully opened or closed, a gap
is formed around the panels, leakage occurs, internal components are damaged and service difficulties occur. To prevent
this, the EVO Modular Air Handling Units are designed with adjustable feet to ensure that the unit is parallel to the ground
plane. Adjustable feet also help maintain the minimum drainage height from the drain pan.
Filter Frame
The filters in the unit are serviced by removing the service covers from the front of the unit as standard. In the applications
up to the EVOXX20 model where the space is limited, the filters can be slidable and service can be done from the front.
This allows a shortening of up to 600 mm in length of the device.
Module Connectors
In EVO Modular Air Handling Units, sections are grouped so that the total length does not exceed 2500 mm. If the total
length exceeds 2500 mm, the unit is divided into modules so that the length of each module does not exceed 2500 mm
and the modules are joined on site. Air leakage may occur due to improper mounting during the assembly of modules, which
affects performance. EVO Modular Air Handling Units have specially designed connecting plates and module connectors
with 3 dimensional planes so that the module connections can be done easily and accurately.
Outdoor Protection
EVO Modular Air Handling Units are designed to operate under atmospheric conditions. In AERA Selection software,
the electrical components of the device are revised after entering the information that the device will work in the external
environment and a roof plate is applied to the unit against rain and snow accumulation. It is recommended that the
roofing plate be sloped to prevent snow accumulation in areas where snowfall is intense. Roof plate is manufactured from
polyester coated sheet with high corrosion resistance.
The lock and hinge mechanisms used in the units can be adjusted to ± 3 mm on all three axes. Axis problems caused by
the mounting location, etc., are resolved as a standard feature in all devices.
A E R A A I R I N N O V A T I O N 19
COMPONENTS
FILTERS
In EVO Modular Air Handling Units, pre-filters, middle-class filters and fine class filters are used according to particulate
holding characteristics. Filters are produced as cassette, compact and bag type and selected the software according to
the specification of the project. Depending on demand, Active Carbon filters can also be applied to retain odor and other
chemical particles.
Filters are components that determine the pressure drop in air handling units to a significant extent. AERA selection software
considers fan calculations by taking the average of the initial and final pressure drops of the filters during fan selection in
line with Eurovent criteria.
The filter class should be selected according to the size and type of particles desired to be held. The following table shows
the particle sizes that are frequently seen in air conditioning systems and the recommended filter type to use.
HEPA FILTERS
MIDDLE CLASS FILTER
STEAM
AIR POLLUTING PARTICLES
PARTICLE SIZE
In order to monitor filter pollution and service times, pressure gauges can be installed on the unit. U manometers or
differential pressure gauges show instantaneous readings, they can also inform the building automation system with a filter
alarm if desired.
20
ROTOR
The part where the rotor rotates and the heat is transferred
is called the matrix and it is formed by wrapping the high
strength aluminum sheets with each other by giving a
curly form.
As well height (gap between wraps) increases, the amount of heat transfer and pressure drop is reduced. The decrease in
well height increases the transfer of heat and pressure drop. In EVO Modular Air Handling Units, condensing type rotors with
a 1.6 mm well height are used as standard. For higher heat transfer requirements, rotors with 1.8 mm, 2.0 mm or 2.5 mm
well height can be selected from the selection software for 1.4 mm can be chosen for lower pressure drop requirements.
Rotors are produced in three different types by changing the matrix material used to meet different moisture transfer needs
The table below shows the heat and moisture transfer efficiencies of these three materials at different blwell heights.
% 90
% 80
% 70
% 60
% 50
% 40
% 30
% 20
% 10
%0
1.4
1.5
1.6
1.7
1.8
1.9
1.4
1.5
1.6
1.7
1.8
1.9
1.4
1.5
1.6
1.7
1.8
1.9
A E R A A I R I N N O V A T I O N 21
COMPONENTS
Condensing rotors are used in applications where moisture transfer is usually MOLECULAR STRUCTURE
required during winter months and in summer where moisture transfer is not OF THE COATING MATERIAL
required. Moisture transfer to supply air takes place in the winter when extracted
air condensates, whereas moisture transfer does not happen in summer because
the possibility of condensation is very low. The smell and the chemical particles
of the condensing air are transferred to supply air together with moisture. For
this reason, it is not recommended to use condensing rotors in applications
where there are smell and chemical particles in the exhausted air. 3Å H H
O
Enthalpy rotors are made by coating Silicagel over aluminum surface which
enables moisture transfer. Silicagel absorbs humidity in the air and transfers it
to the other air flow. Silicagel also allows the transfer of water-soluble molecules
between air flows. It is not recommended to use it in applications where chemical WATER MOLECULE 2.8Å
particles are present in the exhaust air.
Sorption rotors are the result of the coating of Zeolite and such derivatized
materials, which allows very high moisture transfer to the aluminum surface.
Since water molecules can penetrate into the coating material, high moisture
transfer occurs. The interspace between the molecules of the coating material
allows only the passage of water molecules, blocking the passage of chemical
substances such as odor.
In EVO modular air handling unit selection, rotors are always designed to COUNTER FLOW
provide counter air flow. There is a loss of 35% in the heat and moisture transfer WORKING PRINCIPLE
efficiencies when no counter flow is generated in the rotor.
Sealing Gaskets
Due to the structure of the rotor there is air leakage between inside and outside
of two surfaces. Gaskets previously used was able to reduce air leakage just
under 3%. Evo Modular Air Handling unit's special sealing gaskets can reduce
the air leakage under 1%.
SPECIAL GASKET
STANDART GASKET
22
By selecting the configuration as
EXHAUST STATIC
shown in the figure in EVO Modular AIR PRESSURE
Air Handling Units, the static
SUPPLY
pressure values between the two OUTDOOR
AIR AIR
air flows on the rotor will be very
close to each other, so the leakage
+
between the flows will be minimized. 0
It is advisable to configure the units
this way in modular air handling units
just like compact units.
STATIC
PRESSURE
-
SUPPLY AIR
SUPPLY AIR
PURGE SECTOR
A E R A A I R I N N O V A T I O N 23
COMPONENTS
SUPPLY AIR
Heating Coils
Frost Protection
L
COI
Frost protection independent of the control system in the ING
heating coils is provided upon request. In a system with L
O
CO
Cooling Coils
24
For removing the condensate formed in the cooling coils from the system, drain pans manufactured from stainless steel are
used as standard.Drain pans are by welding and manufactured with double curved design to speed up the release of the
condensate water. A ball siphon is supplied as standard with each machine against the transfer of chemical particles such
as odor.
Optional
electric heater
10
HUMIDIFIERS 10
0
5
95
90 30
Humidifiers are used to increase the humidity of indoor air, 85
g
fresh air is heated by internal heaters. The capacity and
/k
70
kJ
model of the humidifier are determined in the Selection 65 25
Y-
ALP
60
NEMLENDİRME
software according to the desired air conditions and are
TH
55
HU Y C
reflected in the report together with all the selection criteria
EN
O
Y C
50
TI
M OO
B
IT FI
RA
ID L
ID CI
IF IN
M PE
45 20
of the humidifier.
YI G
HU S
NG
40 COOLING HEATING
35
DE BY
IN ING
30
DEHUMIDIFYING
HU HE
OL FY
G
20
M AT
CO IDI
25
ID IN
15
BY UM
IF G
YI
H
10
NG
DE
10
5
0
-5
-1
0 0
-1
5
-10
-40
-20 -15 -10 -5 0 5 10 15 20 25 30 35 40 45 50 55 60
KURU TERMOMETRE SICAKLIĞI - °C
Isothermal Humidifiers
A E R A A I R I N N O V A T I O N 25
COMPONENTS
Drinable water taken from the tap is increased in temperature inside a detachable
type cylinder with built-in immersion type resistance and steam is produced.
The cylinder, made of plastic, is equipped with high temperature protection and
level control element to prevent the resistances from running with incomplete
water. The cylinder can easily be removed and cleaned. With the effective
microprocessor control on it, the desired humidity value can be achieved with
high accuracy (± 1%). Suitable for use in hygienic applications, the humidifier has
VDE, GS and CE certificates. The special cleaning system ensures the removal
of sediments and other particles in the cylinder and increases the service life.
Adiabatic Humidifiers
Adiabatic humidifiers are used in the HEF2E series for adiabatic cooling or
humidification in EVO Modular Air Handling Units. They have low energy
consumption and manufactured with the VDI 6022 hygiene certificate. The
system is designed to have high efficiency and low pressure drop, it has a
flame retardant glass fiber humidifier pad, circulation pump, flow balancing
valves, droplet eliminators and level sensors. Optionally step controlled, simple
or advanced automation and ultraviolet lamp sterilization system can be installed
with the humidifier.
26
FANS
In EVO Modular Air Handling Units, different types of fans can be selected according to required flow rate and static
pressure requirements of the project and the variability of these needs. Depending on the requirements of the users, plug
type fans with direct coupling motors or EC motors, forward inclined or backward inclined belt and pulley connected fans
can be used. Fan-array applications which reduces the sound pressure of the project and reduces the size of the unit can
also be selected.
These fans are used in medium/high static pressure applications and they
belong to high efficiency class. Since the fan and motor are directly coupled
to each other, the losses in the belt / pulley system are eliminated. The plug
type fans must be driven with a frequency converter in order to run them at
the design conditions and to set the speed. The wing structure is an aerofoil
structure to enhance aerodynamic efficiency. They can be used in all aspirators,
including applications where the air should not be in touch with the motor, fresh
air handling units, units with recirculation, heat recovery ventilators and hygienic
air handling units.
A E R A A I R I N N O V A T I O N 27
COMPONENTS
All EC motor plug type fans used in EVO Modular Air Handling Units are in
compliance with European Union Energy Norm (ERP) with very high efficiency.
They have electronic components for easy operation according to many control
systems (Constant Air Volume CAV, Constant Static Pressure / Variable Air
Volume, VAV)
All EC Motor Plug Fans used in EVO Modular Air Handling Units have MODBUS
communication protocol, control signals and alarm information can be transferred
to the main control panel just with a dual cable.
Fan Laws
The speed, power and pressure interactions in the fans used in the EVO Modular Air Handling Units are predictable and
explained in the fan laws. Using these laws and the change in the fan rpm, it is possible to obtain an estimate of what the
pressure and power values will be at the new working point.
POWER
FLOW
( ( ( (
Q1 N SP1 N1 2 P1 N1 3
= 1 = =
Q2 N2 SP2 N2 P2 N2
Reducing the RPM by 10% decreases the Reducing the RPM by 10% decreases the
Varying the RPM by 10% decrases or static pressure by 19% and an increase in power tequirement by 27% and an increase
increases air delivery by 10%. RPM by 10% increases the static pressure in RPM by 10% increases the power require-
by 21% ment by 33%
28
MIXING CHAMBER
ECONOMISER
A E R A A I R I N N O V A T I O N 29
COMPONENTS
SOUND ATTENUATOR Pod width (B) = 200 / Pod length (S) = 100 mm
Pressure
EVO Modular Air Handling Units have a silent design
value
Damping [dB] for medium frequency [Hz]
Length
thanks to low velocity criteria in construction and
mm
component selection that prevent turbulence in casign
design. In cases where the units are located adjacent to 63 125 250 500 1K 2K 4K 8K ξ
living volumes, where it is desired that the sound of unit 500 3 5 10 19 24 20 15 11 5.7
has to be even lower, sound attenuators can be used. 1000 5 8 15 33 44 36 23 15 6.6
1500 7 12 21 46 50 50 32 19 7.5
Silencers can be installed in the units or in the air ducts
2000 9 16 27 50 50 50 40 23 8.5
when space is limited. The silencers located in the unit
2500 11 20 33 50 50 50 49 27 9.4
have higher sound damping characteristics and lower
sound pressure levels than the silencers in the air duct Dp pressure loss is calculated from the pressure value.
(Vs≤6.0 m / s) due to low velocities (Vs≤2.0 m / s) ∆p = 0,6 x v2 x ξ
v is the speed at the cross section of the silencer.
Silencer sections are produced in 600, 1000 and 1500
mm lengths. For optimum pressure drop and sound
S
damping level, silencer pods 200 mm wide are placed
at 100 mm distance from each other. Sound absorption
level and pressure drop criteria for standard lengths are
indicated on the table. b
Flow
The sound damping values tested by ISO 7235 for
200
silencers are given in the selection software and in the
a
report output according to the selection criteria. The
silencers are designed in accordance with the hygiene
criteria of VDI 6022 and DIN 1946 (parts 1 and 2).In order
to periodically clean the silencer pods, appropriate service
panels are designed on the unit casing and the pods are
designed to be easily removable.
30
ELECTRICAL HEATER
A E R A A I R I N N O V A T I O N 31
ADVANCED CONTROL SYSTEMS
HEATERS
Electrical Heaters
Electrical heaters are used for purposes such as increasing supply air temperature, preheating fresh air from the outside,
bringing the supply air to the desired temperature after dehumidification process. With SENSO PLUS control, electric
heaters are driven in steps or proportional manner according to desired set temperature to save energy. All safety and
operating equipment required by the electric heater is supplied standard with the SENSO PLUS control.
Heating Coil
Heating coils are used for increasing the supply air temperature and for bringing the supply air to the desired temperature
after dehumidifying process. Hot water coils can be driven by proportional control via 2 or 3 way valves. With the SENSO
PLUS control, frost protection mechanism is available as standard to prevent the temperature of the supply water from
reaching freezing conditions in extreme cold climates. If the return water temperature falls below a certain value set on the
control, the heating valve is switched to the 100% open position and a run signal is sent to the heating water circulation
pump. If the temperature still does not rise to the desired value, the device is stopped and the user is given a freeze alarm.
DX (Condensing) Coil
They are used for increasing the supply air temperature and for bringing the supply air to the desired temperature
after dehumidifying process. They can be step controlled with on/off method, maximum 16 step settings are available.
COOLERS
Cooling Coil
Cooling coils are used to lower the supply air temperature and dehumidification process. Cooling coils are controlled with
2 or 3 way valves. Run signal will be sent to cold water circulation pump when necessary.
DX (Evaporator) Coil
They are used to lower the supply air temperature and dehumidification process. They can be step controlled with on/off
method, maximum 8 step settings are available.
Changeover Coils
These coils can have cooling in the summer season and heating in the winter season. Their capacities are usually selected
according to cooling conditions. Heating and cooling capacity is controlled and has frost protection during heating season.
32
FAN
PRESSURE [Pa]
Nominal air flow and reduced air flow are defined as
two control values. SENSO PLUS control measures the
air pressure drop in the suction ports of the fans and SYSTEM
compares the air flow with the set value to produce a CURVE
working signal for the frequency converter or EC fan.
PRESSURE [Pa]
a working signal to frequency converter or EC Fan that
will change the fan speed by continuously measuring the SYSTEM
static pressure created in the supply air duct and CURVE
comparing it with the value defined in the system. When
a VAV damper opens or closes, higher or lower external
static pressure needs can be met with constant pressure
control within the fans operating curve. This way extreme 400
noise in the ducts, unbalanced airflow distribution in FAN
different volumes is prevented. SPEED
A E R A A I R I N N O V A T I O N 33
ADVANCED CONTROL SYSTEMS
FILTERS
PRESSURE [Pa]
The pressure drops of the filters used to clean the air,
can be controlled by SENSO PLUS control. Users
are notified about the filter cleaning and replacement
intervals. Pressure drop control can be made according FINAL PRESSURE DROP
to a constant pressure drop (Static) or variable air flow
300
(Dynamic). Especially with units designed with variable DYNAMIC ALARM LIMIT
speed fans, Dynamic Filter Control enables filter service STATIC ALARM LIMIT
200
at the right time. CLEAN FILTRE PRESSURE DROP
100
HEAT EXCHANGERS
In EVO Modular Air Handling Units with plate type heat exchangers, there is a by-pass damper in order to be able to deliver
the outside air directly into the exchanger without entering the heat exchanger under suitable weather conditions. The
SENSO PLUS control uses temperature sensors to determine when the by-pass will be turned on and off. This function,
also known as Free Cooling, saves energy by opening the by-pass dampers when the outside air is suitable.
In extreme cold climates fresh air preheater can be used to prevent the air condensation on the plated type heat exchanger
from freezing and damaging the heat exchanger. If this is not enough, by-pass damper is opened to prevent the cold air
from passing over the heat exchanger. In such applications, referred to as heat exchanger frost protection, an afterheater
must be built in the device and this heater must be chosen to meet the necessary supply air conditions.
In EVO Modular Air Handling Units, when the SENSO PLUS control is used together with the rotary exchanger, the unit is
shipped with a variable speed rotor drive. By controlling the supply air temperature, the rotor revolutions are automatically
adjusted according to the required heat recovery. If the outside air conditions are appropriate, the rotor is stopped and
free cooling is performed.
DAMPERS
In EVO Modular Air Handling Units, if the SENSO PLUS control is used, the Economizer and Mixer dampers are automatically
adjusted according to the desired mixture air conditions and the amount of fresh air. The recirculation dampers, which
allow the use of variable indoor / fresh air, are also automatically adjusted according to desired supply air temperature.
Humidity control equipments are used to raise or lower the humidity of the supply air. With the SENSO PLUS control, the
humidifier / de-humidifiers can be controlled to bring the supply air to the desired humidity value.
The SENSO PLUS control also provides system control besides equipment control, which means that the devices can
be operated with the Yearly Timer Function according to the working periods: Daily, Weekly, Monthly or Yearly. In the
Timer Function, values such as weekly working days, vacation times, daylight savings time can be defined and reported
retrospectively.
Besides, the Support Function which is used to prevent the undesired conditions from occurring indoors even when the
device is not working. The indoor temperature from falling below or exceeding a certain value even during non-working
hours is ensured.
34
COMMUNICATION OPTIONS
USER INTERFACE
With SENSO PLUS control, a standard control panel with a keypad as a user interface is delivered, optionally touch screen
user interfaces are availible as well. There is also a web server embedded in the card for monitoring and controlling the
device through a computer. Settings for the controller can be done over the server, instantaneous operating values of the
unit can be seen, as well as retroactive working values can be followed.
SENSO PLUS control connects the web server over the internet and allows you to view and change the settings of your
unit on any computer / tablet or mobile phone anywhere in the world. No need for complicated network settings, only a
connected network cable is enough. With this feature, it is possible to monitor and control all units from different projects
on a single screen, so that all of the operating values, active alarms, settings can be observed and remotely changed.
Cloud control is an option provided with SENSO PLUS, which is especially convenient when it is important to serve multiple
devices within seconds, in different projects all around the world.
100 %
18.4 °C
100 %
24.7 °C 100 %
20.9 °C
SET TEMPERATURE: 24.0 °C
%100 %0
A E R A A I R I N N O V A T I O N 35
UNIQUE ADVANTAGES OF SENSO PLUS CONTROLS
TCP / IP connection: The integrated web control console provides platform-independent remote monitoring and setting.
Tablet, PC, smartphone provides you with 24/7 accessibility to your unit.
BACNet, Modbus, EXOline, LON and CLOUDigo communication ports provide easy integration into all automation
systems.
With the modular structure, components in the unit can be added or deactivated after the installation.
It provides a quick and easy configuration program from the computer and ease of operation with plug-and-play logic.
Energy is saved;
By providing fresh air as much as the volume needed, it optimizes the air conditioning load resulting from fresh supply air.
Runs all components at their optimum points to achieve the desired supply temperature.
It optimizes the heat recovery operation according to indoor and outdoor weather conditions, provides free cooling at
appropriate temperatures.
Provides filter service by constantly observing the pressure drops over the filters and informing the user accordingly.
It provides instant information about problematic components with advanced alarm signals.
All components of the control are supplied from a single point, so they fit perfectly and work seamlessly.
The optional CLOUDigo platform; The system, which allows you to extend and is designed with maximum convenience,
is ready to use when you plug in an ethernet cable. All devices using the SENSO PLUS control system can be viewed
and controlled from a single screen.
The devices continuously send data to the system and the data are recorded. Reports on energy efficiency can be
generated by analyzing detailed data within specific dates.
CLOUDIGO
36
AERA iKLiMLENDiRME TEKNOLOJiLERi SAN. VE TiC. AŞ
SALES OFFICE Varyap Meridian, Grand Tower A Blok No:130 Ataşehir, İSTANBUL - TR aera.com.tr
TEL
+90 216 504 76 86 FAX +90 216 504 76 90
FACTORY 3. Cadde No:13 Pancar OSB, Torbalı, İzmir - TR
TEL
+90 232 799 0 111 FAX +90 232 799 01 14
R&D CENTER 3. Cadde No:13 Pancar OSB, Torbalı, İzmir - TR