Ycc 036 FM
Ycc 036 FM
INSTALLATION 18-EB21D1-11
OPERATION Library
Product Section
Product
Service Literature
Unitary
Packaged Gas/Electric
MAINTENANCE Model
Literature Type
Sequence
YCC
Installation, Operation, Maintenance
1I
ALL phases of this installation must comply with Date November 2003
NATIONAL, STATE AND LOCAL CODES File No. SV-UN-RT-YCC-IOM-1I 11/03
Supercedes YCC-IOM-1H
Model:
YCC018F-L YCC036F-H YCC036F-M Package Convertible
YCC024F-L YCC042F-M
YCC030F-L YCC048F-M Gas/Electric
YCC030F-M YCC048F-H
YCC036F-L YCC060F-M BAYLIFT002A Lifting Lug Kit 1-1/2 - 5 Ton
IMPORTANT — This Document is customer property and is to remain with this unit. Please return to service information pack upon completion of work.
Since Trane has a policy of continuous product and product data improvement,
it reserves the right to change design and specification without notice.
© 2003 American Standard Inc. All rights reserved Dwg. No. X664209 P01
10/03
GENERAL INFORMATION
IMPORTANT: Read this entire manual before IMPORTANT: DO NOT CONNECT GAS PIPING TO THE UNIT
beginning installation procedures. UNTIL A LINE PRESSURE TEST HAS BEEN COMPLETED.
INSPECTION
1. Check for damage after the unit is unloaded. Report promptly,
to the carrier, any damage found to the unit. Do not drop the
unit.
NOTICE
Warnings and Cautions appear at appropriate locations throughout this manual.
Read these carefully.
FIELD SUPPLIED
SUPPORTS
AT EACH END
OF CURB
ROOFING
ROOF INSULATION
FIELD SUPPLIED
CANT STRIP
ROOF DECK
FIELD SUPPLIED
RIGID INSULATION
ROOF MOUNTING
CURB
SUPPLY AIR
DUCT RETURN AIR
DUCT
SEE NOTE 1
SEE NOTE 2
FIELD SUPPLIED
SUPPORTS
AT EACH END
OF CURB
ROOFING
ROOF INSULATION
FIELD SUPPLIED
CANT STRIP
ROOF DECK
FIELD SUPPLIED
RIGID INSULATION
ROOF MOUNTING
CURB
NOTES:
1. The YCC042,048F-M:YCC036F-H models extend SUPPLY AIR
out past this end of the curb ONLY. DUCT RETURN AIR
DUCT
2. Only the YCC048F-H,060F models extend past both
the end and the side of the curb as illustrated.
RECOMMENDED SERVICE
CLEARANCE
BACK * 6.0" CLEARANCE TO
COMBUSTIBLE MATERIAL
LEFT SIDE 30.0"
BOTTOM 0.0"
RIGHT SIDE 24.0"
BACK 1.0"
FRONT 42.0"
LEFT SIDE 6.0"
* 18" WITH FRESH AIR ACCESSORY
* 30" WITH ECONOMIZER RIGHT SIDE 6.0"
FRONT SIDE 12.0"
TOP 36.0"
MODEL A B C D E F
YCC018F-L
KNOCKOUTS FOR 1/2" AND 1"
YCC024F-L 55-1/4 36 25-3/16 12-15/16 36-3/4
CONDUIT
YCC030F-L
YCC030F-M
KNOCKOUTS FOR 3/4" AND 1-1/4"
YCC036F-L 55-1/4 36 29-3/16 12-15/16 36-3/4
CONDUIT
YCC036F-M
YCC036F-H
KNOCKOUTS FOR 3/4" AND 1-1/4"
YCC042F-M 62-3/4 36 29-3/16 14-1/2 27-1/2
CONDUIT
YCC048F-M
YCC048F-H KNOCKOUTS FOR 3/4" AND 1-1/2"
64-5/16 45 33-3/8 14-13/16 27-15/16
YCC060F-M CONDUIT
HEATER EXCHANGER
TUBES
NOTE
SUPPLY OPENING
RETURN OPENING
D
A
SERVICE SERVICE
CLEARANCE CLEARANCE
LINES LINES
SUPPLY AIR
C RETURN AIR B
SIDE RAIL
WOOD NAILER
2. Location of the unit must allow service clearance around it. 1. The Roof Mounting Curb, (field assembled
Clearance of the unit must be given careful consideration. See BAYCURB030,038,033,034A), or a field fabricated curb must
Figure 6. be in place before the unit is hoisted to the roof top.
IMPORTANT: Air outlet duct must have 1" clearance to 2. The Roof Mounting Curb (frame) must be installed on a flat,
combustible material downstream from the unit. level section of the roof (maximum of 1/4" per foot pitch)
and provide a level mounting surface for the unit. In
3. Check the handling facilities to ensure the safety of personnel addition, be sure to provide sufficient height above the roof
and the unit(s). to prevent water from entering the unit.
4. CAUTION MUST BE TAKEN AT ALL TIMES TO AVOID NOTE: This unit was shipped for horizontal installation. Con-
PERSONAL INJURIES AND/OR DAMAGE TO EQUIPMENT vert to downflow per instructions:
5. The unit must be mounted level for proper drainage of water Remove covers from the downflow supply and return air open-
through the holes in the base pan. ings and place them over the horizontal supply return air
openings (painted side out) and secure with sheet metal screws.
6. The unit must not be exposed to direct roof water runoff. See Figure 5.
7. Flexible duct connectors must be of a flame retardant material. 3. Be sure the mounting curb spans structural members (trusses)
All duct work outside of the structure must be insulated and of the roof, thereby providing sufficient support for the weight of
weatherproofed in accordance with local codes. the unit, the curb, the duct(s), and any factory or field installed
accessories. See Figures 1, 2, 9, 10, and 11.
8. Holes through exterior walls must be sealed in accordance with
local codes. 4. Be sure the hole in the structure for the ducts is large enough
to accommodate the fabricated ducts and the insulation sur-
9. All fabricated outdoor ducts should be as short as possible. rounding them. See Figure 6.
2. Any reduction of the unit clearances indicated in these illustra- The air inlet hood in the combustion blower access panel must
tions may result in condenser coil starvation or the recirculation have adequate clearance around air openings into the combus-
of warm condenser air. Actual clearances which appear to be tion area. See Outline Drawing, Figure 4. continued on next page
inadequate should be reviewed with a local engineer.
Dwg. No. X664209 P01 Page 7
LOCATIONS AND RECOMMENDATIONS
continued from page 7 15. Access and service clearances for the unit must be given
careful consideration when locating the duct entrance open-
Examine all flue product-carrying areas of the furnace, its vent ings. Figure 4 provides unit dimensions.
system, and the main burner for safe operation. A periodic
inspection of the furnace should be made at the start of each 16. All fabricated outdoor ducts should be as short as possible.
heating season.
CLEARANCES
Replacement parts list for this Gas/Electric Air Conditioner may
be obtained by contacting your local manufacturer representa- 1. The recommended clearances for single-unit installations are
tive. illustrated in Figures 4 and 6. These minimum requirements are
not only an important consideration when determining unit
6. Location of the unit must allow for service clearance around it. placement, but they are also essential to ensure adequate
Clearance of the unit must be given careful consideration. See serviceability, maximum capacity, and peak operating effi-
Figure 4. ciency.
7. IMPORTANT: Air outlet duct must have one (1) inch clear- 2. Any reduction of the unit clearances indicated in these illustra-
ance to combustible material downstream from the unit. tions may result in condenser coil starvation or the recirculation
of warm condenser air. Actual clearances which appear to be
8. Exhaust vents or other sources of contaminated air should not inadequate should be reviewed with a local sales engineer.
be near the unit’s air inlet, if outside air is to be introduced as
make-up air or a ventilation feature is to be used. IMPORTANT:
9. Check the handling facilities to ensure the safety of personnel 1. Remove the Flue and Air Inlet Hood with the gasket from the
and the unit(s). return air section of the unit.
10. Caution must be taken at all times to avoid personal The screws that attach the flue and air inlet hood will be installed
injuries and/or damage to the equipment. in their proper location at the factory. Therefore, they must be
removed and then used to attach the flue and air inlet hood.
11. The unit must be mounted level for proper drainage of water
through the holes in the base pan. 2. Remove the packaging material from the components and
secure the Flue and Air Inlet Hood with the gasket to the unit
12. The unit must not be exposed to direct roof water runoff. with sheet metal screws as illustrated in Figure 16 on page 14.
13. Flexible duct connectors must be of a flame retardant material. NOTE: Outdoor air or other requirements during heating
All duct work outside of the structure must be insulated and operation that result in supply air temperatures below 80
weatherproofed in accordance with local codes. degrees F or return air temperatures below 50 degrees F may
cause flue gas condensate to form and is to be avoided.
14. Roof flashing must be installed to seal the roof curb cavity and
must conform to local building codes.
INSTALLATION
UNIT SUPPORT PLACING AND RIGGING
If the unit is to be roof mounted, check the appropriate building 1. Before preparing the unit for lifting, check the outline drawing for
codes for weight distribution requirements. Refer to the applicable center of gravity for lifting safety. Because of placement of
roof curb mounting instruction. Check the unit’s nameplate for internal components, the unit’s weight may be unevenly distrib-
supply voltage required. Determine if adequate electrical power is uted. Approximate unit weights are given in Figure 2, page 3.
available. The furnace may be installed on Class A, B, or C roofing
material. NOTE: Accessory BAYLIFT002AA, a kit of four (4) lifting lugs, is
required for rigging the unit for hoisting. See Figure 7, insert B.
LOCATION AND CLEARANCES
2. Insert the four lifting lugs in the openings provided in the drip lip
Installation of the unit should conform to local building codes or, in on the perimeter of the unit. See Figure 7, insert B. A tap or jerk
the absence of local codes, to the National Fuel Gas Code, to the lug will overcome the interference that arises due to the
ANSIZ223.1, Latest Revision, and the National Electrical Code. nipple on the lug.
Canadian installations must conform to CSA and local codes.
3. Before hoisting the unit, be sure that the proper method of
Select a location that will permit adequate combustion and ventila- rigging is used, with straps or slings and spreader bars for
tion air in accordance with Section 5.3, Air For Combustion and protection during lifting. Always test-lift the unit to determine the
Ventilation, of the National Fuel Gas Code, ANSIZ223.1, Latest exact unit balance and stability before hoisting it to the installa-
Revision, or applicable provisions of the local building code. tion location.
7
SPREADER BARS
OUTDOOR COIL
END OF UNIT
UNIT CORNER
DRIP LIP
BAYLIFT002A
DIMPLE LIFTING LUGS
CURB CORNER
EXISTING
SHEET METAL
SCREW
HOLD-DOWN
BRACKET WITH
“A” CURB
FLANGE OF
CURB
1. The frame must be located and secured by bolting or welding 6. Insulate any ductwork outside of the structure with at least two
to the roof. Flashing is required. (2) inches of insulation and then weatherproof. There must be
a weatherproof seal where the duct enters the structure.
2. The hole in the roof must be prepared in advance of installing
the unit. 7. Complete the installation according to the instructions in the
following sections of this manual.
3. Secure the ducts to the roof.
WEATHER-PROOF
DUCT FLUE
ANGLE IRON
FRAME
FLUE
INLET HOOD
SUPPLY AIR
ROOF FLASHING
For ground level installations, the unit should be positioned on a pad 2. Attach the supply and return air ducts to the unit.
the size of the unit or larger. The unit must be level on the pad. The
pad must not come in contact with the structure (See Figure 11.) Be 3. Insulate any ductwork outside of the structure with at least 2
sure the outdoor portion of the supply and return air ducts are as inches of insulation and weatherproof. There must be a weather-
short as possible. proof seal where the duct enters the structure.
Proceed with the installation as follows: 4. Complete the installation according to the instructions in the
following sections of this manual.
1. Place the unit on the pad and the five (5) rubber isolators
provided.
OUTDOOR AIR
DISCHARGE
SUPPLY AIR
RETURN AIR DUCT
DUCT
SIDING
OUTDOOR AIR
INTAKE
FLUE
INLET HOOD
SUPPORT PAD
FOUNDATION
EXTERIOR
WALL
INSULATE ISOLATORS
WEATHERPROOF FLEXIBLE DUCT
CONNECTORS (1 PER CORNER
OR RAIN SHIELD AND 1 UNDER
UNIT CONTROL BOX)
● Trapped.
The first elbow in the ductwork leaving the unit should be no closer
than two feet from the unit, to minimize noise and resistance.
AIR PROOF
THIS SEAM
UNIT BASE
UNIT EXTERIOR
WEATHERPROOF
FIELD DUCT THIS SEAM
UNIT DUCT
UNIT DUCT FLANGE FIELD DUCT
FLANGE
AIR PROOF
THIS SEAM
FIELD
DUCT
UNIT DUCT FLANGE
UNIT BASE
UNIT EXTERIOR
WEATHERPROOF
UNIT DUCT THIS SEAM
FLANGE UNIT DUCT
WATERPROOF SEAM FLANGE FIELD DUCT
WITH BUTYL OR
SILICONE
NOT RECOMMENDED
FIELD DUCT
HORIZONTAL
DOWNFLOW
The following warning complies with State of California law, Proposition 65.
●
WARNING: This product contains Wash clothes separately from other clothing: rinse
washer thoroughly.
fiberglass wool insulation! Fiberglass dust and ceramic
fibers are believed by the State of California to cause ● Operations such as sawing, blowing, tear-out, and
cancer through inhalation. Glasswool fibers may also spraying may generate fiber concentrations requiring
cause respiratory, skin, or eye irritation. additional respiratory protection. Use the appropriate
NIOSH approved respirator in these situations.
PRECAUTIONARY MEASURES
FIRST AID MEASURES
● Avoid breathing fiberglass dust.
Eye Contact - Flush eyes with water to remove dust.
● Use a NIOSH approved dust/mist respirator. If symptoms persist, seek medical
attention.
● Avoid contact with the skin or eyes. Wear long-
sleeved, loose-fitting clothing, gloves, and eye Skin Contact - Wash affected areas gently with soap
protection. and warm water after handling.
2.Determine the exact length of pipe needed. Before connecting the unit to the gas supply line, be sure to
determine the gas pressure in the line.
3.Read the BTUH input nameplate on the furnace.
If the gas supply pressure is excessive (above 13.8 inches water
4.Use the multiplier opposite the specific gravity of the gas given in column or 1/2 psig), install a pressure regulator either at the supply
Table 1 below and insert in the following formula: source or in the branch circuit serving the unit. Once the regulator
is installed, set it to provide a maximum pressure of 13.8" W.C. to
TABLE 1 the gas valve for natural gas with a minimum supply pressure of 5.0"
W.C. Maximum supply pressure of 13.8" W.C. to the gas valve for
SPECIFIC propane with a minimum pressure of 11.0" W.C.
MULTIPIER
GRAVITY
MULTIPIERS TO BE USED .50 1.10 NOTE: Maximum pressure to the gas valve for natural gas
WHEN THE SPECIFIC .55 1.04 is 13.8" W.C. Minimum pressure is 5.0" W.C. Maximum
GRAVITY OF THE GAS IS .60 1.00 pressure to the gas valve for propane is 13.8"W.C. Minimum
OTHER THAN 0.60 .65 .962 pressure to the gas valve is 11.0" W.C.
THIS TABLE IS BASED ON PRESSURE DROP OF 0.3 INCH W.C. AND 0.6 SP.GR. GAS
3.Install a drip leg at least six (6) inches in depth next to the
union as shown in Figure 14. This drip leg is required to
collect any sediment that may be deposited in the line.
4.Before connecting the piping circuit to the unit, bleed the air
from the supply line. Then cap or plug the line and test the
pressure at the tapped shut-off cock. The pressure reading
should not exceed 13.8 inches water column.
6.After installation of the gas pipe in the unit, the pipe chase
opening should be closed with the filler/barrier plug pro-
vided.
MANIFOLD PRESSURE
Check the manifold pressure at the unit gas valve. Do not
exceed the recommended pressure shown on the unit name-
plate.
NOTES:
1.THE OUTLET FLUE RESTRICTOR IS REQUIRED
WHEN THE FURNACE IS OPERATED ON LOW INPUT
(AN OUTLET FLUE RESTRICTOR MAY BE REQUIRED
ON HIGH INPUT).
ELECTRICAL WIRING
ELECTRICAL CONNECTIONS
GROUNDING: THE UNIT MUST BE ELECTRICALLY GROUNDED
Electrical wiring and grounding must be installed in accordance with IN ACCORDANCE WITH LOCAL CODES OR THE NATIONAL
local codes or, in the absence of local codes, with the National ELECTRIC CODE.
Electrical Code ANSI/NFPA 70, Latest Revision.
NOTE: Unit must be grounded for ignitor to operate prop-
ELECTRICAL POWER erly. Gas pipe to unit is not an adequate ground. Ground
the unit internally as provided. See wiring diagram for
It is important that proper electrical power be available for the unit. location.
Voltage variation should remain within the limits stamped on the unit
nameplate. CONTROL WIRING (CLASS II)
DISCONNECT SWITCH Low voltage control wiring should not be run in conduit with power
wiring unless Class 1 wire of proper voltage rating is used. Route
Provide an approved weatherproof disconnect either on the side of the thermostat cable or equivalent single leads of No. 18 AWG
the unit or within close proximity and within sight of the unit. colored wire from the thermostat subbase terminals through the
rubber gromment on the unit. See Figures 3 and 4 for the control
OVER CURRENT PROTECTION entry location. Make connections as shown on the unit wiring
diagram and in Figure 18.
The branch circuit feeding the unit must be protected as shown on
the unit rating plate. Do not short thermostat wires since this will damage the control
transformer.
POWER WIRING
Recommended wire sizes and lengths for installing the unit thermo-
The power supply lines must be run in weathertight conduit to the stat are provided in Table 5. The total resistance of these low
disconnect and into the bottom of the unit control box. Provide strain voltage wires must not exceed one (1) ohm. Any resistance in
relief for all conduit with suitable connectors. excess of 1 ohm may cause the control to malfunction because of
the excessive voltage drop.
Provide flexible conduit supports whenever vibration transmission
may cause a noise problem within the building structure.
TABLE 5
Be sure all connections are made tight. See Figure 18. THERMOSTAT WIRE SIZE AND MAXIMUM LENGTH
The thermostat heat anticipators should be set to .4 amps on single After all electrical wiring is complete, set the thermostat system
or two stage thermostats. switch in the OFF position so that the compressor will not run
and then apply power by closing the system main disconnect
IMPORTANT: Upon completion of wiring check all electrical
switch. This will activate the compressor sump heat. Do not change
connections, including factory wiring within the unit, make
the Thermostat System Switch until power has been applied long
sure all connections are tight. Replace and secure all electrical box
enough to evaporate any liquid R-22 in the compressor. It is
covers and access doors before leaving the unit or turning on the
recommended that the sump heater be energized for eight (8) hours
power to the unit.
prior to starting.
● Is the filter of the correct size and number? Is it clean and in place? COOLING SHUT DOWN
● Is the wiring properly sized and run according to the unit wiring Place the system selector in the OFF position or reset thermostat at
diagram? a setting above room temperature.
● Are all the wiring connections, including those in the unit, tight? Do not de-energize the main power disconnect except when unit is
to be serviced. Power is required to keep the heat pump compres-
● Has the unit been properly grounded and fused with the recom- sor warm and boil off refrigerant in the compressor.
mended fuse size? See Wiring Data.
HEATING CYCLE
● Is the thermostat level, correctly wired, well located, and set for
the proper heat anticipation? NOTE: See Sequence of Heating Operation.
● Have the air conditioning systems been checked at the service These units are equipped with a solid-state ignition control that
ports for charge and leak tested if necessary? lights the burners each time the thermostat calls for heat. The
burners are extinguished during the OFF cycle.
● Does the condenser fan and indoor blower turn free without
rubbing, and are they tight on the shafts? The gas heating section of the unit can be started using the following
procedure:
● Has the indoor blower speed been determined and the proper
speed been set? See the Unit Wiring Diagram. 1. Be sure the thermostat is at its lowest setting and the power to
the unit is off.
● Has all work been done in accordance with applicable local and a. Turn the main shutoff valve on the gas supply line ON.
national codes?
b. Turn or switch the manual valve on the combination gas
● Are all covers and access panels in place to prevent air loss and valve ON position.
safety hazards?
2. Be sure the burner compartment access panel is in place.
STARTING THE UNIT IN THE COOLING MODE a. Turn on the electrical power to the unit.
CAUTION: Before starting the system on the cooling cycle, turn the b. Turn the thermostat to the highest setting in the heating
thermostat switch to OFF and close the unit disconnect switch. This cycle.
procedure energizes the compressor crankcase heater, vaporizing
any liquid refrigerant in the crankcase. This is a precaution against 3. As the thermostat calls for heat, the system cycles as follows:
foaming at startup which could damage the compressor bearings. a. The combustion blower is energized.
Allow the heater to operate a minimum of eight (8) hours. b. The pressure switch is closed.
NOTE: See the section on “Sequence of Operation” for a c. The gas valve opens and the ignitor lights the burner.
description of the cooling operating sequence. d. Cycle the thermostat on and off a few times to check out the
To start the unit in the cooling mode, set the thermostat system control system and burner operation characteristics.
switch to COOL and move the thermostat COOL indicator to a 4. With the burners operating, check the manifold pressure with a
setting below room temperature. The condenser (outdoor) fan manometer. Do not exceed recommended pressures.
motor compressor and evaporator (indoor) fan motor will operate
automatically. 5. Adjust the unit to obtain an air temperature rise with that
specified on the unit nameplate.
OPERATING PRESSURES
6. NOTE: For manifold pressures and orifice sizes for gas with
After the unit has operated in the cooling mode for a short period of other BTU ratings, contact the local gas utility. Manifold
time, install pressure gauges on the gauge ports of the discharge pressure should be 3.5 inches water column (+0.1). Input must
and suction line valves. Check the suction and discharge pressures not exceed the value shown on the rating plate.
and compare them to the normal operating pressures provided in
the unit’s SERVICE FACTS. 7. Set the heat anticipator of the thermostat to equal the amperage
draw of the gas valve, approximately 0.7.
● Has the thermostat been checked for calibration and the air ● Has the owner or maintenance personnel been given this manual
discharge grilles adjusted to balance the system? and the warranty? Has the owner or maintenance been in-
structed on proper operation and maintenance of this unit?
o
TROUBLESHOOTING CHART
SYSTEM FAULTS
REFRIGERANT CIRCUIT
Liquid Pressure Too high
Liquid Pressure Too Low
ELECTRICAL
Compressor & O.D. fan Do Not Start
This limited warranty is extended by American Standard Inc., to the original purchaser and to any
succeeding owner of the real property to which the Combination Gas Electric Air Conditioner is
originally affixed, and applies to products purchased and retained for use within the U.S.A. and
Canada.
If any part of your Combination Gas Electric Air Conditioner fails because of a manufacturing defect
within five years from the date of the original purchase, Warrantor will furnish without charge the
required replacement part. Any local transportation, related service labor, diagnosis calls, air filters,
refrigerant and related items are not included.
If the sealed motor-compressor fails or if the outdoor coil should become defective, either or both
events occurring because of a manufacturing defect within five years from the date of original
purchase, Warrantor will furnish without charge the required replacement compressor and/or
outdoor coil. Any local transportation, related service labor, diagnosis calls, refrigerant and related
items are not included.
In addition, if the steel heat exchanger fails because of a manufacturing defect within the sixth
through tenth year from the date of original purchase, Warrantor will furnish without charge a
replacement heat exchanger. Any local transportation, related service labor and diagnosis calls are
not included.
This limited warranty does not cover failure of your combination gas electric air conditioner if it is
damaged while in your possession, damage caused by unreasonable use of the combination gas
electric air conditioner and/or damage from failure to properly maintain the combination gas
electric air conditioner as set forth in the Use and Care manual (see Proper Maintenance
section).
This limited warranty applies to product installed on or after 10/1/2001 where product is
manufactured after 1/1/2000.This limited warranty is not retroactive to any installations prior to 10/1/
2001 or on product produced prior to 2000.
THE LIMITED WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER
WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS
OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL
WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow limitations on how long an implied limited warranty lasts or do not allow
the exclusion or limitation of incidental or consequential damages, so the above limitation or
exclusion may not apply to you.This limited warranty gives you specific legal rights, and you may
also have other rights which vary from state to state.
Parts will be provided by our factory organization through an authorized service organization in
your area listed in the yellow pages. If you wish further help or information concerning this limited
warranty, contact:
American Standard Inc. GW-632-1802
Troup Highway
Tyler,TX 75711-9010
Attention:
Dwg. Manager,
No. X664209 P01 After Sales Support Page 23
LIMITED WARRANTY
COMBINATION GAS ELECTRIC AIR CONDITIONER
YCZ, YCY, YCX, YCC, YCD, YCH, YCP, YHC and YSC
Models Less Than 20 Tons for Commercial Use*
(Parts Only)
his warranty is extended by American Standard Inc., to the original purchaser and to any succeeding owner of
the real property to which the Combination Gas Electric Air Conditioner is originally affixed, and applies to
products purchased and retained for use within the U.S.A. and Canada. There is no warranty against
corrosion, erosion or deterioration.
If any part of your Combination Gas Electric Air Conditioner fails because of a manufacturing defect within one
year from the date of the original purchase, Warrantor will furnish without charge the required replacement
part.
In addition, if the sealed motor-compressor fails because of a manufacturing defect within the second through
fifth year from the date of original purchase, Warrantor will furnish without charge the required replacement
compressor.
In addition, if the steel heat exchanger fails because of a manufacturing defect within the second through fifth
year from the date of original purchase, Warrantor will furnish without charge a replacement heat exchanger.
Warrantor’s obligations and liabilities under this warranty are limited to furnishing F.O.B. Warrantor factory or
warehouse at Warrantor designated shipping point, freight allowed to Buyer’s city, replacement parts for
Warrantor’s products covered under this warranty. Warrantor shall not be obligated to pay for the cost of lost
refrigerant. No liability shall attach to Warrantor until products have been paid for and then liability shall be
limited solely to the purchase price of the equipment under warranty shown to be defective.
THE WARRANTY AND LIABILITY SET FORTH HEREIN ARE IN LIEU OF ALL OTHER
WARRANTIES AND LIABILITIES, WHETHER IN CONTRACT OR IN NEGLIGENCE, EXPRESS
OR IMPLIED, IN LAW OR IN FACT, INCLUDING IMPLIED WARRANTIES OF
MERCHANTABILITY AND FITNESS FOR PARTICULAR USE, AND IN NO EVENT SHALL
WARRANTOR BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES.
Some states do not allow limitations on how long an implied warranty lasts or do not allow the exclusion or
limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
This warranty gives you specific legal rights, and you may also have other rights which vary from state to state.
American Standard Inc.
Troup Highway
Tyler, TX 75711-9010
Attention: Manager, After Sales Support
GW-606-4800
* This warranty is for commercial usage of said equipment and not applicable when the equipment is used for
a residential application. Commercial use is any application where the end purchaser uses the product for
other than personal, family or household purposes.