Saes P 111
Saes P 111
SAES-P-111
Grounding
Document Responsibility: Electrical Systems Designs and Automation Standards
Committee
Contents
1 Scope ................................................................................................................................ 6
3 References ........................................................................................................................ 6
4 Terminology....................................................................................................................... 9
5 General ........................................................................................................................... 10
10 Equipment Grounding................................................................................................... 19
12 Fence Grounding.......................................................................................................... 24
13 Tank Grounding............................................................................................................ 25
Page 2 of 27
Summary of Changes
Paragraph Number
Change Type Technical Change(s)
(Addition, Modification,
Previous Revision Current Revision Deletion, New)
09 October 2019 09 November 2021
Addition of definitions
4 4 Addition
section.
Measurements of earth
4.5 5.5 Modification resistivity using four-point
method as per IEEE 81.
Grid/electrode resistance
per fall-of-potential or
NA 5.6 Addition
slope method as per
IEEE 81.
Soil model selection
based on soil
NA 5.7 Addition
measurements
variations.
Modification of the
5.1 6.1 Modification conductor material
selection requirements.
Modification of the
5.1 6.2 Modification ground rod material
selection requirements.
Addition of bitumastic
NA 6.3 Addition paint and mastic tape for
exothermic connections.
Addition of reference to
GIS requirements per
NA 7.2 Addition
IEEE 80 and TES-P-
119.10.
Ground grid burial depth,
conductor sizing,
NA 7.3 Addition
conductor spacing and
GPR limit.
Page 3 of 27
Paragraph Number
Change Type Technical Change(s)
(Addition, Modification,
Previous Revision Current Revision Deletion, New)
09 October 2019 09 November 2021
Restricting the use of
other calculation methods
of step and touch
6.4 7.5 Modification
potentials including finite
element method to multi
ground grid connection
Exception for the backup
NA 7.5.2 Addition protection duration for
34.5kV and 13.8kV.
Ground fault current and
NA 7.5.3 Addition ground grid design for
low voltage level
Two-layer soil resistivity
NA 7.5.6 Addition
measurement
Reference to NGR
NA 9.3.5 Addition design, installation and
testing
Grounding requirement
NA 9.6 Addition for directly connected MV
generator(s)
Grounding requirement
NA 9.7 Addition
for LV generator
Exception of cable armor
10.1 10.1 Deletion
as equipment grounding.
Cable tray system
NA 10.4 Addition bonding and grounding
requirements
Shield/Sheath/Armor
NA 10.8 Addition
grounding requirements
Reference to surge
NA 10.17 Addition
arresters grounding
Grounding requirements
NA 12.4 Addition for fences made of non-
conductive materials
Maximum intervals for
12.1 13.1 Modification
tanks grounding points
Saudi Aramco: Company General Use
Page 4 of 27
Paragraph Number
Change Type Technical Change(s)
(Addition, Modification,
Previous Revision Current Revision Deletion, New)
09 October 2019 09 November 2021
Requirements for
external floating roof
12.1 13.2 Modification
tanks with primary and
secondary seals
Requirements for
external floating roof
NA 13.3 Addition
tanks with primary seals
only
Lightning protection
13.3 14.3 Modification requirements for
hydrocarbon facilities
Update of Isokeraunic
13.3 14.3 Modification level and annual flash
density calculation
Page 5 of 27
1 Scope
Any conflicts between this document and other applicable Mandatory Saudi
Aramco Engineering Requirements (MSAERs) shall be addressed to the
EK&RD Manager.
Any deviation from the requirements herein shall follow internal company
procedure SAEP-302.
3 References
Page 6 of 27
Page 7 of 27
Underwriters Laboratories
UL 96 Lightning Protection Components
UL 96A Installation Requirements for Lightning Protection
Systems
UL 467 Grounding and Bonding Equipment
Page 8 of 27
4 Terminology
4.1 Acronyms
4.2 Definitions
Grounding Electrode: A conductor that have a direct contact with earth for
grounding a power system.
Page 9 of 27
Touch Potential: The potential difference between the ground potential rise
(GPR) and the surface potential at the point where a person is standing while at
the same time having a hand in contact with a grounded structure.
5 General
Grounding/ earthing and/or bonding for electric power distribution systems shall
be designed and installed in accordance with relevant parts of IEC 60364-5-54,
IEC 61892, API RP 2003, NFPA 70, IEEE Standards 80, and 142.
5.1 For 1 kV nominal voltage and below, grounding and ground systems shall be in
accordance with IEEE Std. 142 and meet the requirements of ANSI/NFPA 70
(NEC), and IEEE C2, as supplemented or amended by this standard.
This includes:
a) Residential facilities.
b) Recreational facilities.
c) Schools.
d) Office buildings (including those associated with plants and
industrial facilities).
e) Swimming pools and fountains including equipotential bonding
requirements stated in the Saudi Building Code (SBC) and/or NEC.
5.4 Grounding and ground system requirements for specific facilities are as follows:
a) Health Care Facility grounding shall meet additional requirements of
NFPA 99 and IEEE Std. 602;
b) Communications System grounding shall be in accordance with the
SAES-T-Series;
Saudi Aramco: Company General Use
Page 10 of 27
It is intended that the terminology used in this standard be consistent with the NEC.
5.5 Measurements of earth resistivity shall be made using the four-point method as
per IEEE Std. 81. Unless physical obstacles are faced, probe spacing shall be
increased gradually up to three times the grid length. At least two perpendicular
measurements profiles shall be conducted.
5.7 If variations in soil measurements are not significant, any of the uniform soil
model equations in IEEE Std. 80 can be used. For other type of non-uniform
soil structures that show distinct variations in the soil measurements, the two-
layer model approach presented in IEEE Std. 81 appendix B shall be used to
approximate the equivalent two-layer earth structure.
Annealed copper clad steel wires can be used for grounding tower
structures of 69 kV and above overhead transmission lines in outside
facilities.
Page 11 of 27
All underground conductors that are not part of an IEEE 80 step- and touch-
potential grid shall be insulated for corrosion control and to eliminate interference
with cathodic protection systems.
In soils with less than 70 ohm-meters resistivity, copper clad steel shall be
used and meet the requirements of UL 467 or equivalent.
Soils in Saudi Aramco areas which are lower than 70 ohm-meters resistivity
normally have high salt content and are corrosive to copper. Galvanized
steel is very durable in low resistivity soils. Buried bare copper has a
detrimental effect on pipeline cathodic protection.
Page 12 of 27
6.3 Below ground connections to grounding grids and ground rods, or between
conductors and/or grounding rods, shall be made using one of the following
methods:
a) By thermite welding
Note 6.3 (a):
6.4 Above ground grounding system connections shall be made in accordance with
NEC.
Exception 6.4:
To structural steel, by compression type connectors bolted to bare steel.
6.6 Underground ground conductors that are within 3 meters of a buried metal
pipeline or metal piping, shall be insulated or sleeved with PVC conduit.
7 Substation Grounding
Per Section 5, the design for the substation grid and the associated overall
plant grounding system shall account for hazards due to transferred potentials
caused by a fault in the substation.
7.1 All electrical equipment in the substation, substation yard, and within 5 meters
of the substation fence shall be connected to the grid or to a ground bus
connected to the grid.
Page 13 of 27
Note 7.1:
7.2 Special considerations for gas-insulated substations (GIS) shall be as per IEEE
Std. 80 section 10 and TES-P-119.10 section 13.
7.3 The design package for ground grids and systems for substations with
equipment operating at above 15 kV shall be performed and submitted for
review.
Note 7.3:
Grounding grid shall be buried at a depth ranging 0.5 to 1.5 m below final
ground grade, typical conductor spacing range from 3 m to 15 m. For the typical
conductor size ranging from 2/0 AWG (70 mm2) to 500 kcmil (240 mm2).
GPR shall not exceed 5kV and shall be minimized, as low as possible, to
safeguard communication and microprocessor-based equipment.
7.4 Cross section for conductors utilized in substation ground grids shall be 70
mm² (2/0 AWG) or greater.
7.5 Calculations of allowable and actual step and touch potentials shall be done in
accordance with IEEE Std. 80 using the following parameters:
Note 7.4:
7.5.3 Ground fault current shall be the higher of the symmetrical line-to-line to
ground (LLG) or line to ground (LG) fault currents. The fault current shall
not be based on local faults with local grounded neutral.
Note 7.5.3:
Page 14 of 27
In many cases, the available ground fault current at the low voltage level
is the highest fault current in the substation. However, this fault current
shall not be considered in sizing the grid conductors nor in determining
GPR, step and touch potentials, with presence of one of the following:
7.5.4 In calculations of the grid current, the current division factor shall be site
specific as per Annex C of IEEE Std. 80. If no detailed analysis is
conducted, the current division factor shall be 1.0.
Note 7.5.4:
The current division factor is used to account for the current that returns
to the source through an overhead ground wire rather than through the
substation ground grid and earth.
7.5.5 The resistivity of the surface material shall be assumed based on Table
1.
Table 1 – Resistivity of Surface Material
Note 7.5.5:
Page 15 of 27
7.5.6 Calculations of mesh voltage and ground potential rise shall be based on
actual measured soil resistivity. Soil resistivity of backfill material used
for ground grids and ground rods shall be the same as or less than that
of the surrounding soil.
Note 7.5.6:
For two layers soil model, where the upper layer has the higher soil
resistivity, deep driven rods shall be considered to be in contact with the
lower soil resistivity layer.
The result of all test performed shall be documented on Saudi Aramco pre-
commissioning form SA-P-080, or an equivalent form containing the same
information.
7.7 New ground grids shall be provided with test stations (wells) to facilitate future
tests. Test wells shall be reasonably distributed to cover the entire grid evenly.
8 Grounding Electrodes
8.1.4 The ground electrode for system grounding shall consist of either (1) rod
or (2) a combination of rod and a grid or loop of bare copper conductors
buried a minimum of 500 mm. Multiple rods shall be interconnected by
Saudi Aramco: Company General Use
Page 16 of 27
Minimum conductor burial depth and length requirements of the NEC are
applicable for “Ground Rings” encircling a building or structure that
constitutes the only made electrode for the building. Minimum burial
depth requirements of this paragraph apply to conductors used to
interconnect rods or other made electrodes.
8.2 When required, supplementary grounding electrodes per NEC Article 250 shall
be provided in outdoor industrial areas, process plant areas, and in substations
not covered by Section 7. Resistance to ground of each supplementary
grounding electrode system shall be minimum 25 ohms as specified in NEC.
8.3 If an above ground bus or loop is used for extending the supplementary
grounding electrodes, this bus or loop shall have two connections.
8.4 Conductors used for interconnecting ground rods shall be minimum of 70 mm²
(2/0 AWG).
9 System Grounding
Systems fed from a transformer with a primary voltage less than 600 V shall be
grounded in accordance with NEC rules for separately derived systems.
9.2.1 The ground resistance of made electrodes (ground ring and/or ground
loop) used for system grounding shall not exceed 5 ohms.
Page 17 of 27
9.3.1 The ground resistance of made electrodes (ground rods and/or ground
grid) used for system grounding shall not exceed 5 ohms.
9.4.1 The ground resistance of made electrodes (ground rods and/or ground
grid) used for system grounding shall not exceed 1 ohm.
9.7 Low voltage generators shall be solidly grounded. When the available ground
fault current exceeds the three-phase fault current resulting in a short circuit
overduty, each generators shall be effectively grounded through a neutral
grounding reactor to reduce the ground fault current to a value in the range of
60 and 100% of the three-phase fault current as stipulated in IEEE Std. 142.
Page 18 of 27
9.9 All grounding electrodes used for system grounding in plants, bulk distribution
facilities, or other industrial areas shall be interconnected to form a single
ground system. The grounding electrode used for system grounding (including
separately derived systems) for each area in the facility or plant shall have a
minimum of two connections to the ground grid or ground loop used in the area.
This requirement can be met by connections to the grounding electrode of the
substation(s) which supply the area.
9.10 Provided that the motor controller has ground fault detection and the
transformer is located at the same well site as the pump being served, the
system grounding of dedicated (captive) transformers supplying electric
submersible pumps in water or oil well applications shall be determined by the
ESP system supplier.
10 Equipment Grounding
10.1 Equipment grounding conductor shall be provided with each power circuit or
inside the multiconductor cable jacket. An insulated copper conductor shall be
installed in the same conduit, cable tray, cable trench or shall otherwise
accompany the power conductors. Sizing of equipment grounding conductor
shall be as per NEC Article 250.
Exceptions 10.1:
Note 10.1:
10.2 Regardless of whether or not this standard permits conduit or cable tray to be
relied on as the equipment grounding conductor, the conduit, or cable tray
installations must meet NEC bonding and grounding requirements for such use.
Page 19 of 27
10.5 A cable concentric neutral, if properly sized and not used as a current carrying
grounded circuit conductor (3 phase 3 wire system; no neutral loads are
served), may be used as the equipment grounding conductor.
Note 9.5:
The cable must meet the requirements of 15-SAMSS-502 that requires an overall
jacket to protect the concentric neutral.
10.6 Electrical submersible pump motors in oil and water well service do not require
a dedicated equipment grounding conductor, provided the motor controller has
ground fault detection. The well head must be bonded by an approved means
to the ground bus at the motor controller or supply transformer.
For 69 kV cables and above, IEEE Std. 575 shall be utilized for design aspects of
sheath-bonding methods for single-conductor cables depending on cable
lengths.
Page 20 of 27
Note 10.8:
When splicing single core armored to unarmored cable, the induced voltage of
the armor layer at the splice point shall be calculated to ensure that it is within the
cable jacket tolerance.
Where EMT is permitted it may be grounded and bonded in accordance with the
NEC.
Isolated sections of rigid metal conduit that are buried at all points at least
0.5 meters below grade are not required to be grounded. (e.g., Conduit sleeves
for road crossings.)
Conduit sleeves used to enclose power cables transitioning from above grade to
below grade are required to be grounded only at the above grade end.
10.10 Metallic cable trays shall be bonded to the local ground grid or ground electrode
at both end points ensuring that bonding continuity is met throughout all the
racks in the system.
10.11 Ground busses in switchgear, switchboards, and motor control centers shall
have two connections to the local ground grid or the main ground electrode.
10.12 Electrical manholes shall be grounded using two ground rods located close to
diagonally opposite corners of the manhole. These rods shall be connected to
each other, to a ground loop or bus accessible from inside the manhole, and,
Saudi Aramco: Company General Use
Page 21 of 27
where applicable, to a minimum 120 mm² (4/0 AWG) grounding conductor that
is connected to the local (within 15 m) grounding grid.
10.14 The following equipment shall be connected to the local ground grid, grounding
electrodes, or supplementary grounding electrodes described in Section 8.
This is in addition to equipment grounding conductors running with the power
conductors that are required by the NEC and this standard.
Exception 10.14:
10.14.1 All structural steel supports (including coated structural steel) that
support insulators, electrical equipment, process equipment or piping
and structural steel columns shall be connected with a minimum of two
connections at opposite corners of each structure, connections shall
be made at least every 25 m (i.e., No part of the base of the structure
shall be more than 25 m from a grounded support or column). For
pipe-rack designs that do not have horizontal structural steel
connecting the adjacent vertical steel supports, each vertical support
must be grounded.
10.14.4 Motor Operated Valves (MOV), lower voltage motors and transformers
are grounded through the associated equipment grounding conductor.
10.14.5 The following equipment when not bolted to grounded structural steel
shall be connected to a supplementary grounding electrode:
Page 22 of 27
10.15 Manually operated switches for overhead power lines shall have operating
platforms and be grounded as shown on Standard Drawing AA-036572.
10.16 Minimum conductor size used for connection of equipment to ground rods or
ground grid shall be based on the calculated short circuit level at the equipment
but not less than 25 mm² (#4 AWG).
Exception 9.16:
11.1 The main ground electrode for the platform shall consist of a copper cable or
copper bar minimum size 120 mm² (4/0 AWG) which is connected to two
platform legs. In addition, the main ground electrode shall be connected to the
structural steel in a minimum of two locations at opposite sides of the main
substation area. Connections to the platform legs, structural steel and any
splices in this main ground electrode shall be made by exothermic welding or
brazing. System grounding connections shall be made directly to this ground
electrode.
11.2 Tanks of medium and high voltage transformers and ground busses for
switchgear and motor control centers shall have two paths for current to flow to
this ground electrode. The main ground electrode is not required on platforms
that do not have transformers or generators which require system grounding
connections.
11.3 Where two or more platforms which require main ground electrodes are
connected by walkways, two insulated conductors, minimum size 120 mm²
(4/0 AWG) shall be installed between the respective main ground electrodes.
11.4 Equipment grounding shall be done per Section 10 of this standard except that
required local supplementary grounding of motors, low voltage transformers,
etc. which are not in the main substation area may be done by using a bonding
jumper that is connected to structural steel or deck plate by brazing or
Saudi Aramco: Company General Use
Page 23 of 27
12 Fence Grounding
12.1.1 Substation fences shall not be PVC coated and shall be grounded in a
minimum of two locations to the local ground grid or loop.
12.1.2 All fences (including grillwork and gates used to control access to the
area under the substation) for substations containing equipment fed
from solidly grounded systems operating at above 1,000 V line to line
shall be bonded to a grounding conductor buried approximately 1 m
outside the fence and parallel to the fence. A second conductor shall
be buried 1 m inside the fence if the substation ground grid does not
extend into this area. The grounding conductor(s) shall be connected
to the substation ground grid at a minimum of four locations spaced
equally around the loop. The fence shall be connected to the
grounding conductor(s) at intervals not exceeding 15 m. Corner posts
and gateposts shall be connected to the grounding conductor. Gates
shall be bonded to the gateposts with flexible connectors. Grillwork
and gates used to control access to the area under the substation
shall meet the bonding and grounding requirements for substation
fencing.
Page 24 of 27
Specific
No Fences Location Grounding Coating
Notes
Shall be bonded at the
All fences within 3 meters
nearest fence post to the shall not be PVC
2 of a ground grid or ground
ground grid or ground Coated
electrode
electrode.
Shall be grounded at
Fences that pass under a intervals not exceeding 15
shall not be PVC
3 transmission line operating m per 11.2.1 on that
coated
at 34.5 kV and above portion of the fence within
100 m of the power line.
Shall have a bond between
Fences that cross over a the grid or conductors and
ground grid, or conductors the nearest post. If the shall not be PVC
4 S1
that connect two ground crossing area is extensive, coated
grids the bond is required every
50 m.
Specific Note(s):
S1 If the ground conductors used to connect the ground grids are insulated and sleeved
with PVC conduit at points within 10 m of the fence, then the bond is not required.
12.3 Non-substation fences, other than described in 12.2, constructed with concrete
posts and PVC coated fencing material are not required to be grounded.
Note 12.3:
13 Tank Grounding
13.1 The shells of onshore storage tanks in hydrocarbon service shall be grounded
as follow:
13.1.2 Each point shall be bonded to the area ground grid or to a local
electrode. The tank shell to remote earth resistance shall not exceed
10 ohms.
Page 25 of 27
13.2 Bonding of tanks with internal floating roof shall fully comply with the API 650
Annex H requirement. A minimum of four stainless steel strap conductor 0.4
mm thickness X 50 mm wide shunts shall be uniformly distributed.
13.3 External floating roof tanks shall have stainless steel shunts between the tank
roof and the metal sealing ring. The shunts shall be uniformly spaced not more
than 3 meters apart. The shunts shall be installed above the primary seals, and
bolted to the sealing ring and the roof in accordance with library drawing DB-
950387. The resistance between sealing ring and the roof shall not exceed 0.03
ohm.
14 Lightning Protection
14.1 Lightning protection system design and installation shall be based on:
• NFPA 780, UL 96, UL 96A, and IEEE Std. 998.
• or IEC 62305-1,2,3,4.
14.2 The following facilities shall have lightning protection system without a need for
risk assessment:
14.2.2 Schools;
14.2.3 Hospitals;
External roof tanks bonding shall be installed per section 13. Bypass conductors
shall not be installed.
Page 26 of 27
Tank trucks, tank cars, tanks, other large containers, associated filling
apparatus, and other equipment which during normal operation can cause
accumulation of sufficient static charge to cause an ignition of hydrocarbon
vapors in the area shall be bonded and grounded in accordance with relevant
parts of API RP 2003, IEC 60364-5-54, IEC 61892.
Revision Summary
25 December 2012 Major revision.
24 January 2017 Major revision incorporating various comments received from key standard stakeholders
such as Power Systems Engineering Department, Inspection Department and PMT.
The new revision address one major topic on grounding conductor requirements for 69 kV
and above power cables.
09 November 2021 Major revision incorporating various comments received from key standard stakeholders
such as Power Systems Engineering Department, Inspection Department and PMT.
The new revision is primarily to incorporate enhanced generator, tank and fence grounding
requirements.
Page 27 of 27