62 12110 Installation
62 12110 Installation
TM
62-12110 Rev. A
TM
Unit may start automatically at any time even if the switch is in the OFF position. Use proper lockout/tagout
procedures before inspection/servicing. All unit inspection/servicing by properly trained personnel only.
1.1 Parts
Table 1–1 Supra Installation Parts List
NOTE
In order for eSolutions to communicate with the Summit Micro use in the
Supra product line, an EPROM with DataTrak™ must be installed. As of
January 2020, the latest part number for the EPROM is 12-00648-3D8.
1 62-12110
1.2 Tools
The following tools are required for units that need bracket and harness mounting holes drilled into the frame:
1.2.2 Crimping
Hand crimp connections shall be made with proper tool. One such example is below.
Glue lined heat shrink tubing shall always be carefully applied. Heat shall be added slowly as
excessive temperatures can cause damage to low melting point insulation
Check by visual inspection to make sure that there are glue rings presented all the way around
both ends of the heat shrink tube as the indication of good seals.
Splitting of heat shrink tubing due to over-temperature or over-shrinking is not allowable.
Charring of the heat shrink tubing is also not allowable.
Heat shrink tubing shall not be used in areas where there is vibration as it results in some loss
of flexibility of the harness.
1.3 Schematics
The eSolutions wiring schematic and installation diagrams can be found in Section 3
2 62-12110
1.4 Installation
Unit may start automatically at any time even if the switch is in the OFF position. Use proper lockout/
tagout procedures before inspection/servicing. All unit inspection/servicing by properly trained
personnel only.
a. Place bracket 68-08632-00 under the control box as shown in Figure 1.3 below.
Bracket
Drill three 68-08632-00
0.397” holes
Bracket
68-08689-01
3 62-12110
b. Mark the three mounting holes.
c. Remove the plate and prepare to drill the holes from the outside of the control box.
NOTE
Before drilling holes for the mounting plate, make sure no wires are in the area where the drill will
breakthrough to the inside of the box.
d. Drill three 0.397” (Drill size X) holes in the bottom of the control box. Remove any burrs from
drilling out of the control box.
e. Install three Rivnuts (34-06051-104) into the three holes.
f. Attach the mounting plate to the control box using three 34-01341-25 bolt
g. Install the eSolutions module to the mounting plate on the bottom of the control box using three
M5 Nylock nuts (34-01184-05) and flat washers (34-00944-05).
h. Position the 24-pin connector towards the rear of the unit and the two antenna connections
towards the front.
24-pin connector
eSolutions module
(3G - 12-00770-00;
le
4G 12-00843-00)
antenna connection side
(shown without the antenna
protective cap)
cap)
Front Back
24-pin connector
eSolutions module
antenna connection
side (shown with the
antenna protective cap)
Front Back
4 62-12110
1.4.1 Power Harness Installation
1. For Supra 560, 660, 760 ,860, 950MT and 960 units prior to serial number TFP91605321, install
power harness (22-03090-00) as follows:
SP80B Connect
Pass-through to fuel heat
grommet (constant 12 VDC
power)
SP81A terminal
(awitched 12
VDC power)
SATPWR
SP81B butt
1RP connector (switched
12 VDC power)
Ground
a. Remove the pass-through grommet on the control box as shown and install the 22-03090-00
harness.
Install harness
Remove pass- 22-03090-00
through
grommet
b. Locate/disconnect the 1J plug on the relay board and then locate pin 12 on the connector (950MT uses
3J-12).
5 62-12110
1J Socket
(950MT uses 3J)
1J socket pin 12
1J Plug (950MT uses 3J-12)
(950MT uses 3J)
1J plug pin 12
(950MT uses 3J-12)
c. Use pin extractor tool (07-00254-00) and remove the 1J-12 pin (Supra 5, 6, 7, 8, and 960 only).
d. Cut the terminal off the 1J-12 (3J-12 on 950MT only) wire as near to the terminal as possible.
Strip the insulation off the wire 0.25".
Supra 950MT only - use pin extractor tool (07-00254-00) and remove the 3J-12 pin.
6 62-12110
Cut the terminal
strip insulation
0.25”
e. Crimp the butt splice end of the 12 VDC switched power wire to the unit wire 1J-12 (3J-12 on
950MT only).
f. Insert the terminal end of the 12 VDC switched power wire into the 1J plug pin 12 position (3J-12 on
950MT only).
g. Plug in the 1J (3J on 950MT only) to the relay board.
7 62-12110
1J plug
New terminal for 1J plug, (950MT uses 3J)
pin 12 position
(950MT uses 3J-12)
22-03090-00
NOTE
See Tools: Stripping Wire, Crimping, Heat Shrink
SP80C
F27A/ST3
SP80B
22-03090-00
8 62-12110
i. Attach the ground wire from harness 22-03090-00 to the low voltage ground stud in the control box.
Low voltage
ground stud
Ground
NOTE
When stacking the ground lugs, they should be positioned in a manner that seating
interference is avoided
j. Attach Ty-Wrap (54-00079-02) and secure the harness (22-03090-00) inside the control box.
9 62-12110
2. Install the 22-03130-00 harness for Supra 5,6,7,8 and 950/960 prior to serial number TFP91605321
as follows:
a. Apply dielectric grease (02-00311-02) to the 24-pin connector on the eSolutions harness and
plug to the eSolutions module
b. Plug in 2RP plug (on the 22-03130-00 harness) to the 1RP plug (on the 22-03090-00 harness).
c. Plug in SATPWR plug (on the 22-03130-00 harness) to SATPWR plug (on the 22-03090-00
harness).
d. Plug in SATCOM plug (on 22-03130-00 harness) to Serial Port plug (SPA, SPB, SPC on the unit
harness)
NOTE
Reference Figure 1.14 for illustration of correct configuration.
eSolutions
Harness
(22-03130-00)
24-pin connector
SATPWR to SATPWR
2RP to 1RP
eSolutions
Harness
(22-03130-00)
Power
Harness
Unit Harness (22-03090-00)
Figure 1.14 - Power and Communication for all Supra 5,6,7,8 and 960 Units before S/N TFP91605321
10 62-12110
For 960 Units after Serial Number TFP91605321
For Supra 960 after serial number TFP91605321 only, connect the eSolutions module harness to
the mating unit engine harness connectors and all applicable options (fuel sensor, door switch,
power control switch, etc.)
1. Connect the eSolutions module harness (22-03130-00) to the mating unit engine harness
connectors and all applicable options (fuel sensor, door switch, power control switch, etc.). See
Figure 1.15.
NOTE
Anti-fretting dielectric grease (P/N 02-00311-02) must be applied to each electrical connection.
Supra 960
Unit Harness
Figure 1.15 - Power and Communication for 960 Units after S/N TFP91605321
2. Check all harness securing locations to make sure that harness is neatly secured with no loose
sections or potential chafing points.
3. Reinstall unit doors.
11 62-12110
Main unit harness
from control box
Antenna wire to
module harness
Route antenna
cable inside the
clamp supporting
main engine
harness
1. Use two self-tapping screws (34-01276-08) to secure the antenna (12-00844-00) to the top of the
Supra frame as shown below.
Ty-Wrap
Align antenna
mounting plate with
the notch in sheet
metal for 90 degree
bend
2”
Figure 1.17 - Installing the Antenna (560, 660, 760 and 860 Units)
NOTE
There are two thicknesses of sheet metal below the Y bracket on top of the unit. Move the antenna
in 2” from the edge to avoid the two thicknesses.
12 62-12110
2. Route the antenna harness as shown in the illustrations below and secure.
Edge Clip
58-01441-00
Push-In
Ty-Wrap
58-05100-00
3. Secure the remainder of the antenna harness and the eSolutions harness as shown in the series of pictures.
Continue along
engine harness.
Use existing white
clamps to secure.
13 62-12110
Figure 1.20 - Ty-Wrap Locations (760 and 860 Units)
Edge clip
(58-01428-00)
14 62-12110
34-60324-30 (x2)
Captive Head with
12-00844-00
threadlock
4G Antenna
Route antenna harness along existing harness and secure with ty-wraps every 6 to 8”
Antenna
harness
routing
Figure 1.23 - Routing and Securing the Antenna Harness (950 and 960 units)
15 62-12110
Insert screw 34-01336-16
and washer 34-60095-46
thru existing hole into the
harness standoff.
Reinstall the protective cap on the antenna end of the eSolutions module with two T10 screws.
16 62-12110
1.5 Options
Installation instructions are provided with each option kit. Refer to schematics in Section 3 for additional
information.
17 62-12110
2. Field Commissioning eSolutions System
The eSolutions Module must have >12.2 VDC for a minimum of 15 minutes before it can be
commissioned. This will ensure that if the unit went into hibernation due to a low battery, the
eSolutions module will be awake and will communicate properly.
NOTE
Before commissioning the eSolutions system, ensure the following:
• Summit software must have DataTrak®.
• The proper Fleet Code must be available before commissioning the system with uCon.
The Fleet Code is email from Carrier Transicold after the customer’s Service Plan is
ordered on TransCentral.
NOTE
Field commissioning should be done outdoors to ensure proper cellular/satellite signal.
NOTE
In order to download and install the USB adapter proper driver, make sure your
laptop is connected to the Internet when you plug in the USB adapter.
18 62-12110
2.2.1 Configuring Vista, Windows 7 or Later
First, download a free copy of uCon from the following website: http://www.umonfw.com/ucon/index.html
1. Click the word <Download Here> and follow the directions to download the uCon program.
2. Save the file to the Desktop. If necessary, add <.exe> file extension.
3. Once you have completed the installation of the uCon program and have a desktop icon on your
computer, double click the icon to open the program.
4. Disconnect the RP plug (or adapter cable) from the engine harness.
6. Reconnect the RP plug, and look for green and amber LED on the eSolutions module. This LED will
only flash the first time.
7. Remove the Console Cap from the 4-wire console connector on the eSolutions harness.
9. Connect a Serial to USB adapter to the 9-pin connector on the commissioning cable.
10. Connect the USB adapter to the USB port on laptop.
11. Start uCon. Double click the uCon icon on your desktop to start the program.
13. Click OK
19 62-12110
2.2.2 Configuring Windows 98, 2000 and XP
NOTE
Communications Port 1 is the most common for a laptop. Some laptops may use
Communications Port 2. USB to serial converts require that you check with your
7. Click File>Save As. Enter the name “115200” and save the setup file on your desktop.
8. A HyperTerminal session called “115200” has now been setup and can be used in the future to
communicate with the eSolutions System.
NOTE
Periodic software revisions may change some of the screen options that are
displayed during commissioning. The eSolutions software version is displayed on the
eSolutions User Menu. These instructions display modified screens as software
versions starting with software version 5.62.
1. Open the uCon (or HyperTerminal) application and press the space bar. The eSolutions user
menu will open. At this point you are connected to the eSolutions module.
20 62-12110
2. From the User menu, press <C> to commission unit. Enter Installer ID: 0014
4. Press Enter.
21 62-12110
5. Enter the Asset ID. This is usually the trailer number. Press Enter.
6. Enter the Asset ID (usually the trailer number) again and press Enter.
7. Select Profile Configuration. Select <0> unless special instructions are provided by Carrier Transicold.
22 62-12110
8. Fuel Configuration:
• <0> = No fuel level sensor
• <1> = The fuel level sensor is attached to the unit engine harness
• <2> = The fuel level sensor is attached to the eSolutions harness
NOTE
For Supra products choose either <0> or <2> depending on the application
23 62-12110
11. Enter tank size in gallons and press <Enter>.
24 62-12110
12. Door 1 Configuration:
• <0> = No door switch is attached
• <1> = Door switch is attached to the unit engine harness
• <2> = Door switch is attached to the eSolutions harness
NOTE
For Supra products choose either <0> or <2> depending on the application
25 62-12110
2.3.1 Test 1
a. Verify that the Micro is OFF. The micro needs to be completely OFF with no temperatures displayed.
b. Press <C> to continue.
2.3.2 Test 2
a. Verify the Micro is ON. The Micro needs to be completely ON. Wait until temperatures are displayed.
b. Press <C> to continue.
c. Text will be displayed in uCon program. If communication is established between eS and Summit
micro, then uCon will display:
26 62-12110
2.3.3 Test 3
NOTE
The door switch can be either normally open or normally closed. The commissioning
process will configure itself for each sensor.
2.3.4 Test 4
27 62-12110
Fuel Level Test: uCon will read the fuel level sensor and verify the current fuel level in the tank. Enter <Y> or
<N> accordingly.
NOTE
Technician must visually verify fuel level during this test.
NOTE
At this point, the unit should still be running after Test 2.
a) At the Start menu enter Command “-” and Enter Password “DFIX” to open the Fix menu.
b) Fix Command “I” will initiate decommission
c) Verify decommission by entering Yes / No. Enter Installer ID 0014
28 62-12110
3. Wire Harness Connector Pinout Table 3–2 Console (4-pin)
Table 3–1 DP24 CONSOLE Terminal Component
A DP24-20 (PC TX)
B DP24-21 (PC RX)
C DP24-17 (GND)
12 1
D DP24-4 (OFF Signal)
Unused Terminals: None
Table 3–3 Console Cap (4-pin)
CONSOLE CAP 4-pin Component
A C CAP-C (Jumper)
24 13 C C CAP-A (Jumper)
Unused Terminals: B, D
DP24 Terminal Component Table 3–4
3 SP-2 (GND) Table 3–5 SATPWR (2-pin)
CONSOLE-D SATPWR Terminal Component
4
(OFF signal) A DP24-5 (Switched PWR)
SATPWR-A Unused Terminals: B
5
Switched PWR
TEMP1 Table 3–6 SATCOM (3-pin)
6 SATCOM Terminal Component
(Remote Temp Sensor 1)
8 SATCOM-B (TX) A DP24-9 (eSolutions RX)
9 SATCOM-A (RX) B DP24-8 (eSolutions TX)
10 D3-C Unused Terminals: C
11 DS-A Table 3–7 D3 (3-pin)
TEMP3 D3 Terminal Component
12
(Remote Temp Sensor 3) A SP-2 -> DP24-3 (GND)
TEMP-2 SP-1 -> DP24-24
13 B
(Remote Temp Sensor 2) (Constant Power)
14 FLS-A (+) (12VDC) C DP24-10 (Data signal)
15 THS (Trailer Hook Switch) Unused Terminals: None
16 FLS-C (SIG)
Table 3–8 1RP (2-pin)
17 CONSOLE-C (GND)
1RP Terminal Component
19 FLS-B (-) (GND)
A SP-2 -> DP24-3
20 CONSOLE-A (PC TX)
B SP-1 -> DP24-24
21 CONSOLE-B (PC RX)
Unused Terminals: None
22 GND (Sensor)
24 SP-1 (Constant PWR) Table 3–9 2RP (2-pin)
Unused Terminals: 1, 2, 7, 18, 23 2RP Terminal Component
A SP-2 -> DP24-3
B SP-1 -> DP24-24
Unused Terminals: None
29 62-12110
3.1 eSolution Wire Harness
30 62-12110
3.2 eSolution Wire Harness
31 62-12110
32 62-12110
WARNING: Breathing diesel engine
exhaust exposes you to chemicals known to
the State of California to cause cancer and
birth defects or other reproductive harm.
33 62-12110