Data Center Electrical Diagram

Uploaded by

Azaz NAqvi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
119 views1 page

Data Center Electrical Diagram

Uploaded by

Azaz NAqvi
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

I/C SUPPLY FROM GENSET I/C SUPPLY FROM K-ELECTRIC

4x1C,70sqmm + ECC,1x35sqmm 4x1C,70sqmm + ECC,1x35sqmm


PVC/XLPE/PVC CABLES PVC/XLPE/PVC CABLES

MDB-1

~
~

~
~
R Y B R Y B
400A TP X X 400A TP
MCCB MCCB
Icu=36KA Icu=36KA
GENSET BY PASS K- ELECTRIC BY PASS
MECHANICAL
EVR INTERLOCK
MDB-1

~~
RS-485
DPM BY PASS

MECHANICAL INTERLOCK
E 400/230V,50Hz
Icu=30KA 200A 200A 32A 32A 32A 32A 16A 16A 16A 16A 10A 10A 10A 10A 50A 50A 50A 50A
TP TP SP SP SP SP SP SP SP SP SP SP SP SP TP TP TP TP
MCCB MCCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCCB MCCB MCCB MCCB
6KA 6KA 6KA 6KA 6KA 6KA 6KA 6KA 6KA 6KA 6KA 6KA 15KA 15KA 15KA 15KA
X 25KA X 25KA X X X X X X X X X X X X X X X X

C1' C2' AC1' AC2' AC3' AC7' TB1' TB2' TB3' TB7' L1' L2' L3' L7' CVR1' CVR2' CVR3' CVR4'

FOR APM-150-1 FOR DATA CENTER SPLIT AC TOTAL NOS 7 FOR DATA CENTER TECHNOLOGY BOX FOR DATA CENTER LIGHTING TOTAL NOS 7 FOR DATA CENTER INROW COOLING 1 TO 4
AND UPS DB-1 TOTAL NOS 7

I/C SUPPLY FROM GENSET I/C SUPPLY FROM K-ELECTRIC


4x1C,70sqmm + ECC,1x35sqmm 4x1C,70sqmm + ECC,1x35sqmm
PVC/XLPE/PVC CABLES PVC/XLPE/PVC CABLES

MDB-2

~
~

~
~
R Y B R Y B
400A TP X X 400A TP
MCCB MCCB
Icu=36KA Icu=36KA
GENSET BY PASS K- ELECTRIC BY PASS
MECHANICAL
EVR INTERLOCK
MDB-2
~~

RS-485
DPM BY PASS

MECHANICAL INTERLOCK
E 400/230V,50Hz
Icu=30KA 200A 200A 32A 32A 32A 32A 16A 16A 16A 16A 10A 10A 10A 10A 50A 50A 50A 50A
TP TP SP SP SP SP SP SP SP SP SP SP SP SP TP TP TP TP
MCCB MCCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCB MCCB MCCB MCCB MCCB
25KA 25KA 6KA 6KA 6KA 6KA 6KA 6KA 6KA 6KA 6KA 6KA 6KA 6KA 15KA 15KA 15KA 15KA
X X X X X X X X X X X X X X X X X X

C1' C2' AC1' AC2' AC3' AC7' TB1' TB2' TB3' TB7' L1' L2' L3' L7' CVR1' CVR2' CVR3' CVR4'

FOR APM-150-2 FOR DATA CENTER SPLIT AC TOTAL NOS 7 FOR DATA CENTER TECHNOLOGY BOX FOR DATA CENTER LIGHTING TOTAL NOS 7 FOR DATA CENTER INROW COOLING 1 TO 4
AND UPS DB-2 TOTAL NOS 7

DISCLAIMER NOTE: Please note that the final drawings will be subject to client approval.

System Integrator . CLIENT:

CIVIL AVIATION AUTHORITY


TITLE:

SINGLE LINE DIAGRAM


DRAWN BY:

CHECKED BY:

APPROVER-1 (CMC):
AZAZ HASNAIN

ATHER REHAN
SHEET NO

2 OF 9
BASE VERSION
REV 1
NAME.
ABU BAK
ABU BAK
DATE
07/07/2023
08/09/2023
COMPUTER MARKETING PROJECT: MDB 1 AND MDB 2 DWG.NO:
REV 2 M.NAEEM 09/10/2023
COMPANY PVT LTD. CAA (TIER-3-DCF) 02-CAA-04-2024 31/10/2023
DATE: 16-04-2024 FINAL VERSION M.NAEEM