Subpart S
Electrical Hazards
                      Video
       Designed by:
      Major Components
 Examination of Equipment
 Working Clearances
 Overcurrent Protection
 Grounding
 Wiring Methods
 Electrical Boxes
 Flex Cord & Cable
 Hazardous Locations
 Safe Work Practices
    Revision of Subpart S
OSHA is revising its electrical installation standard in
§§1910.302 through 1910.308 of Subpart S and
definitions in §1910.399 in order to reflect the most
current practices and technologies in the industry
The revised standard strengthens employee
protections and adds consistency between OSHA's
requirements and many state and local building
codes which have adopted updated National Fire
Protection Association (NFPA) and National Electrical
Code (NEC) provisions.
              Copyright 2000 PROSAFE Solutions
    Revision of Subpart S
It updates Subpart S requirements to the 2000
edition of the NFPA 70E, which is based on the 1999
edition of the NEC. The updated standard includes
an alternative method for classifying and installing
equipment in Class I hazardous locations, new
requirements for ground-fault circuit interrupters, and
new provisions on wiring for carnivals and similar
installations.
Federal Register a Final Rule Publish date – February
14, 2007.
Goes into effect on August 13, 2007
             Copyright 2000 PROSAFE Solutions
Examination of Equipment
 Electrical equipment must be free of
 recognized hazards that are likely to cause
 death or serious physical harm to
 employees.
Examination of Equipment
 Safety of equipment must be determined
 using the following considerations:
 Suitability for installation and use
 Mechanical strength and durability
 Electrical insulation
 Heating effects
 Arcing effects
 Classification
             Marking
 Electrical equipment must be marked
 with the manufacturer’s name,
 trademark or other identification
 Other markings must be provided giving
 voltage, current, wattage, or other
 ratings as necessary
 Markings must be durable enough to
 withstand the environment
       Identification
Each disconnecting means must be
 legibly marked to indicate its
 purpose, unless located and
 arranged so that its purpose is
 evident
Markings must be durable enough
 to withstand the environment
600 volts, Nominal, or Less
Working Clearances:
 Working space around electrical
  equipment
 This section refers to a person qualified
  to work on electrical equipment, usually
  an electrician
      Working Clearances
 Working space in front of live parts
 (operating at 600 volts or less) must be at
 least three feet
 The workspace in front of electrical
 equipment must not be less than 30 inches
 wide
 Working spaces may not be used for
 storage
Proper Clearances!
       600 Volts or Less
Guarding of live parts.
 Any person who is in the vicinity of
  electrical equipment must be protected
  against accidental contact
 Location must be accessible only to
 qualified persons
 Permanent, substantial partitions or
 screens
       600 Volts or Less
Guard against accidental contact by:
 Location on a suitable elevated balcony or
   platform
 Elevation of 8 feet or more above the floor
   or other working surface
       600 Volts or Less
 Enclosures or guards must be installed in
 locations where electrical equipment is
 exposed to physical damage.
         Over 600 Volts
 Sufficient space must be provided and
 maintained around electrical equipment to
 permit safe operation and maintenance
Illumination (Over 600 Volts)
 Adequate illumination must be provided for
 working spaces around electrical equipment
 The lights and switches must be arranged so
 that persons wont contact live parts
    Unguarded Live Parts
 Unguarded live parts above the working
 space must be maintained at elevations not
 less than specified in Table S-3
 The minimum is 8 feet
Identification of Conductors
  The grounded conductor is an energized
    circuit that is connected to earth through
    the system ground. It is commonly
    referred to as the neutral.
  The grounding conductor is not energized
    under normal conditions. It is energized
    only if there is a leak or fault in the
    normal current path and directs current
    back to the source.
Identification of Conductors
The National Electric Code requires that:
 The grounded conductor (neutral) be
   continuous white or natural gray
 The equipment grounding conductor be
   green, green with yellow stripes or bare
  Polarity of Connections
 No grounded conductor may be attached
 to any terminal or lead so as to reverse
 designated polarity
 Reversed polarity is a condition when a
 neutral conductor is incorrectly connected
 to the “hot” terminal of a plug, receptacle
 or other connector.
    Overcurrent Protection
600 volts or less.
 Conductors and equipment must be
   protected from overcurrent.
 Fuses and circuit breakers are designed
   to disconnect a circuit from its supply
   source when a maximum allowable heat
   is reached.
  Overcurrent Protection
600 volts or less
 Overcurrent devices must be readily
   accessible
 Must not be located where they will be
   exposed to physical damage or in the
   vicinity of easily ignitable material
             Grounding
 The path to ground from circuits,
 equipment, and enclosures must be
 permanent and continuous
              Grounding
 Tools likely to be used in wet and conductive
 locations need not be grounded if supplied
 through an isolating transformer with an
 ungrounded secondary of not over 50 volts
            Grounding
 Tools and appliances protected by an
 approved system of double insulation,
 need not be grounded
 They must be distinctively marked
  Double Insulated Tools
 Work with GFCIs
 Casing must be labeled
 Tool must be inspected
 Extension cord must be three-prong
        Wiring Methods
 No wiring system of any type may be in
   ducts used to transport dust, flammable
   vapors, or ventilation of commercial-type
   cooking equipment.
       Wiring Methods
 Temporary electrical power and lighting
 wiring may be of a class less than would
 be required for a permanent
 installation.
         Wiring Methods
Temporary wiring.
 Uses permitted, 600 volts or less.
 During and for remodeling, maintenance
   repair, demolition or similar activities.
         Wiring Methods
Uses permitted, 600 volts or less.
 For experimental or developmental work
 For a period not to exceed 90 days for
 Christmas decorative lighting, carnivals, and
 similar purposes.
        Wiring Methods
Temporary wiring.
Uses permitted, over 600 volts.
 Only during tests, experiments and
   emergencies.
        Wiring Methods
 Lamps for general illumination must be
 protected from accidental contact or
 breakage.
 Protection can be provided by an elevation
 of 7 feet or by a suitable fixture with a
 guard.
        Wiring Methods
 Flexible cords and cables must be protected
 from accidental damage. Sharp corners or
 projections must be avoided.
 Protection must be provided when passing
 through doorways or other pinch points.
Conductors Entering Boxes
 Conductors entering boxes, cabinets, or
 fittings must be protected from abrasion.
 Unused openings in cabinets, boxes, and
 fittings must be effectively closed.
Proper Example!
 Electrical Box Covers
 All pull boxes, junction boxes, and
 fittings must be provided with
 approved covers.
 Metal covers must be grounded.
    Electrical Box Covers
 Outlet boxes must have a cover or a
 faceplate.
 Outlet box covers with holes for flexible
 cords must have bushings or smooth, well-
 rounded surfaces.
Switchboards & Panelboards
 Panelboards must be mounted in
 approved cabinets or boxes and must be
 dead front.
 Others are accessible only to qualified
 persons.
  Flexible Cords & Cables
Allowed uses:
 Pendants
 Wiring fixtures
 Portable lamps or appliances
 Elevator cables
 Wiring cranes or hoists
 Flexible Cords & Cables
Allowed uses:
 Connect stationary equipment to facilitate
 frequent interchange
 Prevent transmission of noise or vibration
 For removal for maintenance/repair
   Flexible Cords & Cables
May not be used:
 As a substitute for the fixed wiring of a
  structure
 Where run through holes in walls, ceilings
  or floors
  Flexible Cords & Cables
May not be used:
 Where run through doorways, windows, or
 similar openings
 Where attached to building surfaces
 Where concealed behind building walls,
 ceilings, or floors
   Flexible Cords & Cables
 Flexible cords must be used only in
 continuous lengths without splice or tap
 Damaged cords must be properly repaired
 or removed from service
   Flexible Cords & Cables
 Hard service flex cords, No. 12 or larger,
 may be repaired if spliced so that the
 splice retains the insulation, outer sheath
 properties, and usage characteristics of
 the original cord
                Splices
Conductors must be spliced with:
 Splicing devices suitable for the use
 Brazing, welding or soldering (with a
 mechanically and electrically secure joint
 before soldering & then soldered)
               Splices
 All splices and joints must be covered
 with an insulation equivalent to that of
 the conductors
  Flexible Cords & Cables
 Flexible cords must be connected to
 devices so that strain relief is provided to
 prevent pull off from being directly
 transmitted to joints or terminal screws.
 Equipment for General Use
 A receptacle installed in a wet or damp
 location must be suitable for the location.
      Hazardous Locations
Electrical installations.
 Equipment, wiring, and installations of
  equipment in hazardous (classified)
  locations must be intrinsically safe,
  approved for the location, or safe for the
  location.
    Hazardous Locations
      Class I locations
 Locations in which flammable gasses or
 vapors are or may be present in the air
 in quantities sufficient to produce
 explosive or ignitable mixtures.
    Hazardous Locations
     Class I, Division 1
   Location in which hazardous
   concentrations of flammable gases or
   vapors may exist:
 Under normal operating conditions
 Because of repair or maintenance
  operations or leakage
 Because of breakdown or faulty operation
    Hazardous Locations
     Class I, Division 2
  Location in which flammable gases or
  vapors are:
 Normally confined within closed
  containers or systems
 Normally kept below hazardous
  concentrations by ventilation
 Normally kept below hazardous
  concentrations by positive-pressure
  ventilation (adjacent to Division 1)
     Hazardous Locations
      Class II Locations
 Locations which are hazardous because
 of the presence of combustible dust.
    Hazardous Locations
     Class II, Division 1
   Location where combustible dust may be
   present due to:
 Normal operations
 Mechanical failure or abnormal operation
  of machinery or equipment
 Combustible dust of an electrically
  conductive nature may be present.
    Hazardous Locations
     Class II, Division 2
Location where:
 Combustible dust will not normally be in
   suspension in ignitable quantities
 Dusts may be in suspension as a result of
   an infrequent malfunction of handling or
   processing equipment.
     Hazardous Locations
      Class III Locations
 Locations that are hazardous because of
 the presence of easily ignitable fibers
 but in which such fibers are not likely to
 be in suspension in the air in quantities
 sufficient to produce ignitable mixtures.
    Hazardous Locations
    Class III, Division 1
 Locations in which easily ignitable
 fibers or materials producing
 combustible flyings are handled,
 manufactured or used.
     Safe Work Practices
 Covers work practices rather than
 electrical equipment and installations
 This should be a part of your
 Lockout/Tagout program