Test registration form
Equipment brand              Entry            Technical indicators                 10kV       630A    16KA
Type of equipment            630A
                                                                     Voltage of operating circuits
Series №                     13094
Consumer                   GBS MMC            Opening relay             220V DC                Protection relay
Customer                                      Closing relay             220V DC
                                                                                                  220V DC
Order                       20401062          Motor                     220V AC
                                            1.Mechanical tests
                                                         Checking the integrity of
Overview
                                                         tire joints
Characteristic
                                                         Ground blade inspection
matches
Assembly                                                 Checking the grounding
compatibility                                            sequence
IP 3XC inspection                                        Operator safety interlocks
                                                         Checking the fuse opening
IP 2 verification
                                                         mechanism
                                  2.Insulation test of low voltage circuits
                             Frequency range             Voltage                                               Time
The circuit under test                                                        Maximum current (mA)
                                  (Hz)                    (kV)                                               (seconds)
   Operating cycle                 50                       1                             0                      3
                      3.Testing of dielectric leakage currents at medium voltage
                                Frequency range               Voltage               Maximum leakage            Time
      Phases
                                     (Hz)                      (kV)                   current (mA)           (seconds)
        1.1                           50                        28                         2,4                   60
        1.2                           50                        28                         2,4                   60
        1.3                           50                        28                         2,3                   60
   Voltage
                    The vanishing      The marginal
  indicator                                              Testing of the quality
                    limit value of         cost                                        100A DC Constant Current
brand and Un
                       lighting         of lighting
   voltage                                                  indicators of the
                                                           earthing separator       L1=27
                                                                                                                   mV
    OVİ-E                2 kV              7,2 kV            (Voltage drop)         L2=28
                                                                                                                  max=30
                                                                                    L3=27
                                        Opening             Attachment
 Testing of auxiliary circuits                                                  Motor circuit          Protection relay
                                    electromagnetic        electromagnet
    -15% Un in tension
       Un in tension
    +10% Un in tension
                                                                   Phases                         11        12     13
       Measurement of the connection
                                                       Measured resistance (micro Om)
        resistance of the main circuits
                                                       Required resistance (micro Om)
                                          L1   L2     L3   Compliance of voltage transformer           L1    L2     L3
 Leakage and phase compatibility
                                                                  wiring to circuit and
   of current transformer wiring
                                                             phases and Medium voltage test
   Brand of current transformers           LZBI9-10          Testing of power circuits (2kV)
   Factor of current transformers           200/5-5        Voltage transformer brand and factor
                                                             Functionality of emergency           Accident indicator
  Testing of protection          The brand of the relay
                                                                   response teams                      lamps
         relays
                                     Micom P116
Tester:
Laboratory chief: