Desigo
Desigo
Copyright
Technical specifications and availability subject to change without notice.
Issued by:
Siemens Switzerland Ltd
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 58 724-2424
www.siemens.com/buildingtechnologies
Edition: 2017-09-18
Document ID: CM110664en_03
2 | 377
Siemens CM110664en_03
2017-09-18
Table of Contents
3 | 377
Siemens CM110664en_03
2017-09-18
7.2 Routing System Events............................................................................ 130
7.3 Sources and Causes of COVs ................................................................. 130
7.4 COV Reporting ........................................................................................ 130
8 Alarm Management ........................................................................... 134
8.1 Alarm Sources ......................................................................................... 134
8.2 Alarm Example ........................................................................................ 136
8.3 Effects of BACnet Properties on Alarm Response .................................... 139
8.4 Alarm Response of the Function Blocks ................................................... 148
8.5 Alarm Functions....................................................................................... 156
8.6 Alarm Management by Notification Class ................................................. 158
8.7 Alarm Routing over the Network .............................................................. 162
8.8 Alarm Queuing ........................................................................................ 165
8.9 Common Alarms ...................................................................................... 166
8.10 Alarm Suppression .................................................................................. 167
8.11 Alarm Message Texts .............................................................................. 169
9 Calendars and Schedulers ................................................................. 171
9.1 Schedule ................................................................................................. 172
9.2 Calendar.................................................................................................. 177
9.3 Wildcards ................................................................................................ 177
9.4 Alarm Messages ...................................................................................... 178
10 Trending .......................................................................................... 179
10.1 Trend Functions....................................................................................... 179
10.2 Editing Parameters .................................................................................. 181
10.3 Processing Trend Data in Desigo CC....................................................... 182
11 Reports............................................................................................ 183
12 Data Storage .................................................................................... 184
12.1 Data Categories.......................................................................................184
12.2 Program Data .......................................................................................... 184
12.3 Libraries .................................................................................................. 185
12.4 Project Data............................................................................................. 186
12.5 Plant Data ............................................................................................... 187
12.6 Data Transfer Processes ......................................................................... 187
12.7 Texts ....................................................................................................... 189
13 Network Architecture ......................................................................... 190
13.1 BACnet Architecture (MLN & ALN)........................................................... 190
13.2 LonWorks Architecture (ALN) .................................................................. 203
13.3 KNX Architecture (ALN) ........................................................................... 205
13.4 KNX PL-Link Architecture (FLN) .............................................................. 206
13.5 DALI Architecture (FLN)........................................................................... 208
14 Remote Access ................................................................................ 210
14.1 Remote Access Methods ......................................................................... 210
14.2 Choosing a suitable Access Technology .................................................. 211
14.3 Technical Details ..................................................................................... 213
15 Management Platform ....................................................................... 214
15.1 User Functions ........................................................................................ 216
4 | 377
Siemens CM110664en_03
2017-09-18
15.2 Main Components....................................................................................219
15.3 Access and Security ................................................................................220
15.4 Event Management..................................................................................221
15.5 Installation, Setup and Engineering ..........................................................222
15.6 Graphics Libraries....................................................................................224
15.7 Graphics Engineering ..............................................................................225
15.8 Virtual Environment .................................................................................226
16 Automation Stations.......................................................................... 228
16.1 Device Object ..........................................................................................229
16.2 Device Info Object ...................................................................................230
16.3 Error Sources and Monitoring Functions ..................................................231
16.4 Operating States......................................................................................232
16.5 Data Storage ...........................................................................................236
17 Logical I/O Blocks............................................................................. 238
17.1 General Functions ...................................................................................239
17.2 Input Blocks .............................................................................................254
17.3 Output Blocks ..........................................................................................257
17.4 Value Objects ..........................................................................................260
17.5 Value Objects for Operation .....................................................................263
17.6 Addressing the I/O Blocks ........................................................................263
17.7 Discipline I/Os..........................................................................................274
17.8 Reliability Table .......................................................................................275
17.9 Slope [Slpe] and Intercept [Icpt] ...............................................................277
17.10 Addressing entries for PXC…-U, PTM and P-Bus ....................................282
18 Room Automation ............................................................................. 289
18.1 Desigo Room Automation ........................................................................289
18.1.1 Configurable .............................................................................290
18.1.2 Programmable ..........................................................................297
18.1.3 Rooms and Room Segments ....................................................301
18.1.4 Central Control Functions and Grouping....................................302
18.1.5 Desigo Room Automation and the Management Level ..............303
18.1.6 Desigo Room Automation and the Automation Level .................303
18.2 Desigo RXC.............................................................................................303
18.2.1 Product Range Overview ..........................................................305
18.2.2 RXC Applications ......................................................................307
18.2.3 RXC and the Management Level...............................................308
18.2.4 RXC and the Automation Level .................................................310
18.2.5 Mapping LonWorks in the LonWorks System Controller ............310
18.2.6 Groups in the LonWorks System Controller ...............................311
18.2.7 System Functions .....................................................................313
18.3 Desigo RXB .............................................................................................314
18.3.1 Product Range Overview ..........................................................315
18.3.2 RXB and the Management Level ...............................................316
18.3.3 RXB and the Automation Level .................................................316
18.3.4 RXB Applications ......................................................................316
18.3.5 Mapping RXB in the PX KNX System Controller ........................317
5 | 377
Siemens CM110664en_03
2017-09-18
19 Desigo Open .................................................................................... 318
19.1 Integration on Management Level ............................................................ 319
19.2 Integration on Automation Level............................................................... 321
19.3 Integration on Field Level......................................................................... 323
19.4 Integration on Room Level ....................................................................... 325
20 Desigo S7 Automation Stations........................................................... 326
20.1 Product Range Overview ......................................................................... 327
20.2 System Limits .......................................................................................... 329
20.3 Alarm Management ................................................................................. 329
20.4 Control Concept....................................................................................... 331
20.5 Desigo S7 Block Library........................................................................... 332
20.6 Operating States...................................................................................... 333
20.7 Error Sources and Monitoring Functions .................................................. 333
21 System Configuration ........................................................................ 335
21.1 Technical Limits and Limit Values ............................................................ 337
21.2 Networks ................................................................................................. 338
21.2.1 Desigo Room Automation System Function Group .................... 339
21.3 Devices ................................................................................................... 341
21.3.1 PXC..D Automation Stations / System Controllers ..................... 341
21.3.2 LonWorks System Controllers ................................................... 343
21.3.3 Automation Stations with LonWorks Integration ......................... 344
21.3.4 PX Open Integration (PXC001.D/-E.D) ...................................... 344
21.3.5 PX Open Integration (PXC001.D/-E.D + PXA40-RS1) ............... 344
21.3.6 PX Open Integration (PXC001.D/-E.D + PXA40-RS2) ............... 345
21.3.7 PX KNX Integration (PXC001.D/-E.D) ....................................... 345
21.3.8 TX Open Integration (TXI1/2/2-S.OPEN) ................................... 345
21.3.9 Number of Data Points on Desigo Room Automation Automation
Stations 345
21.3.10 Number of Data Points for PXC3............................................... 348
21.3.11 Number of Data Points for DXR2............................................... 348
21.3.12 PXM20 Operator Unit ................................................................ 349
21.3.13 PXM20-E Operator Unit ............................................................ 350
21.3.14 PXM10 Operator Unit ................................................................ 350
21.3.15 PXA40-W0 Web Controller Option Module ................................ 350
21.3.16 PXA40-W1/W2 BACnet/IP Web Controller Option Module ......... 351
21.3.17 Desigo Touch and Web - PXG3.W100 Web Interface................ 352
21.3.18 PXG3.L and PXG3.M BACnet Routers ...................................... 353
21.3.19 SX OPC .................................................................................... 354
21.3.20 Desigo CC ................................................................................ 354
21.3.21 Desigo Insight ........................................................................... 355
21.3.22 Desigo Xworks Plus (XWP) ....................................................... 355
21.3.23 Desigo Automation Building Tool (ABT) .................................... 356
21.4 Applications ............................................................................................. 356
21.4.1 Peak Demand Limiting (PDL) .................................................... 356
22 Compatibility..................................................................................... 357
22.1 Glossary .................................................................................................. 357
6 | 377
Siemens CM110664en_03
2017-09-18
22.2 Desigo Version Compatibility Definition ....................................................358
22.3 Desigo V6.1 System Compatibility Basics ................................................359
22.3.1 Compatibility with BACnet Standard ..........................................359
22.3.2 Compatibility with Operating Systems .......................................360
22.3.3 Compatibility with SQL Servers .................................................361
22.3.4 Compatibility with Microsoft Office .............................................362
22.3.5 Compatibility with Web Browsers ..............................................362
22.3.6 Compatibility with VMware (Virtual Infrastructure)......................362
22.3.7 Compatibility of Software/Libraries on the Same PC ..................363
22.3.8 Hardware and Firmware Compatibility .......................................363
22.3.9 Backward Compatibility .............................................................363
22.3.10 Engineering Compatibility..........................................................363
22.3.11 Compatibility with Desigo Configuration Module (DCM) .............363
22.4 When to Upgrade to Desigo V6.1 .............................................................364
22.4.1 Automation Level Desigo PX / Desigo Room Automation ..........365
22.4.2 Desigo TX-I/O ...........................................................................368
22.4.3 TX Open ...................................................................................368
22.4.4 Desigo RX ................................................................................369
22.4.5 Libraries ....................................................................................369
22.5 Upgrade to Desigo V6.1...........................................................................369
22.5.1 Upgrade PX / Desigo Room Automation Automation Level ........370
22.5.2 Upgrade RX Room Automation .................................................372
22.5.3 Upgrade PX (CAS) Libraries .....................................................372
22.5.4 Upgrade Desigo Room Automation Libraries .............................372
22.6 Siemens WEoF Clients ............................................................................373
22.6.1 Desigo Software .......................................................................373
22.6.2 Third-Party Engineering Software..............................................373
22.7 Migration Compatibility.............................................................................373
22.8 Hardware Requirements of Desigo Software Products .............................374
22.9 VVS Desigo V6.1 .....................................................................................375
7 | 377
Siemens CM110664en_03
2017-09-18
Preconditions of this Document
1
9 | 377
Siemens CM110664en_03
2017-09-18
System Overview
2 Management Level
2 System Overview
The Desigo building automation and control system has three levels:
● Management level
● Automation level
● Field level
BACnet/IP
Desigo TRA
Desigo RX
KNX
10660Z36_02_en
Valves Acvatix
10 | 377
Siemens CM110664en_03
2017-09-18
System Overview
Management Level
2
Task Activity
Observing the operational status of the plant or Reading current values of all process variables, data objects and parameter
building settings
Receiving and acknowledging alarms
Overview of all pending alarms
Recording and analyzing trends
Observing the operational status of the building Overview of failed automation stations and network interruptions
automation and control system Signaling of anormal hardware or software states in an automation station or in
the associated field devices
Manipulating the operational status of the plant or Modifying parameter settings (for example, setpoints of control programs)
building Setting values for physical outputs of automation stations
Modifying system and management objects, especially calendars and time
schedules
Devices for operation and The following devices let you operate and monitor the system:
monitoring ● Desigo CC management platform either locally and/or with web operation
● PXM touch panels and operating devices
Operation and monitoring There are four operation and monitoring types:
types ● Generic operation
● Limited (station-specific) generic operation
You can limit the generic view to one or more selected automation stations
(including alarm display).
● Engineered (project-specific) operation
You can generate a project-specific view in the engineering phase.
● Limited (user-specific) operation in Desigo CC
Management platform Desigo CC can be installed on one computer, with full server and client
functionality, or on several separate computers. Web Clients, Windows App
(ClickOnce) Clients and installed Clients can be added.
Remote management Desigo CC can operate and monitor the automation level via a public network.
11 | 377
Siemens CM110664en_03
2017-09-18
System Overview
2 Automation Level
D-MAP programming The starting point for the engineering of the application functions is the range of
language user-friendly application blocks and function blocks in the D-MAP (Desigo Modular
Application Programming) programming language. D-MAP is optimized for
applications for technical building installations and is based on the IEC 1131
standard. The graphical user interface of the Xworks Plus (XWP) [➙ 43]
engineering software ensures an efficient approach.
System functions All PX automation stations have comprehensive system functions, such as alarm
mangement, time schedules, trend histories, time synchronisation, global data
distribution, and life check, that work completely autonomously.
BACnet communication Devices on the automation level communicate with each other and with the
for maximum openness management platform and the operating devices via the BACnet protocol.
The use of BACnet/IP or BACnet/LonTalk underlines the openness of the system
and allows the easy integration of systems and components from third-party
manufacturers.
12 | 377
Siemens CM110664en_03
2017-09-18
System Overview
Automation Level
2
PX Open PX Open system controllers let you integrate third-party devices via Modbus, M-
Bus, KNX and other protocols. System functions, such as alarm management, time
schedules, trend data storage and flexible programming are available.
Operating devices
The various operator units cover all the various requirements in terms of location
and function.
PXG3.W100 web interface The PXG3.W100 web interface lets you operate and monitor PX automation
stations that are engineered in the PXG3.W100. It is the system interface for the
PXM40/50 touch panels. It allows the homogenous operation on-site via PXM40/50
and remotely via a standard web browser.
PXM40 and PXM50 touch The PXM40 (10,1") and PXM50 (15,6") touch panels let you operate several PX
panels automation stations and monitor technical building installations in technical rooms.
The touch panels can be mounted in control cabinets. They are used in
combination with the PXG3.W100 web interface. Its user interface is optimized for
touch handling. If a fault occurs, a text message or email can be sent via a PXC
Modular (IP version).
PXM20/PXM20-E network The network capable PXM20 and PXM20-E operating units let you operate PX
capable operating units automation stations connected to a BACnet network.
PXM10 local operating The PXM10 operating unit lets you locally operate the PXC automation station it is
unit connected to. The device has a user friendly single button operation with an LCD
display.
PX Web The web solution in PXC Modular (BACnet/IP) together with the PXA40-Wx
optional module allows the generic operation of all values of the PX automation
stations from a web client. If a fault occurs, text messages or emails can be sent.
You can set up a graphical operation with a supplied tool.
See Desigo PX Automation system for HVAC and building services - System
overview (CM110756).
13 | 377
Siemens CM110664en_03
2017-09-18
System Overview
2 Room Automation
14 | 377
Siemens CM110664en_03
2017-09-18
System Overview
Desigo Open
2
The room automation stations communicate with each other and other system
components via BACnet/IP (DXR2.E…) or BACnet MS/TP (DXR2.M...).
The room automation stations support different I/O mixes, protocols (KNX S-Mode
and KNX PL-Link for IP and KNX PL-Link for MS/TP) and power supplies
(240/24V). Operating devices, buttons, sensors, and actuators for lighting and
shading can be connected to the room automation stations via KNX PL-Link.
The room automation stations contain preloaded applications, but are also freely
programmable. A comprehensive library of proven, standardized applications is
available.
The DXR2.. room automation stations have an integrated web server for IP
communication with QMX7.E38 touch room operator units. Engineering access is
available via the web interface.
15 | 377
Siemens CM110664en_03
2017-09-18
System Overview
2 Workflow and Tools
● ABT Pro and ABT Site (Automation Building Tool) let you engineer,
commission and service Desigo Room Automation (BACnet) system
components.
● RXT10 lets you commission and service RXC room controllers.
● PX KNX-Tool lets you commission and service PX KNX.
● Desigo CC Graphics Generator lets you automatically generate Desigo CC
plant graphics using information from the System Definition Unit (SDU) and
XWP.
● System Definition Unit (SDU) lets you define application texts in different
languages.
● PX Open MONITOR lets you debug PX Open programs.
● TX Open tool lets you configure and commission TX Open modules.
● BIM tool lets you:
– Commission TX-I/O modules and the Bus Interface Modules (BIM)
– Simulate programs without I/O modules on the test rack
– Configure the colors of the I/O status LED on the TX-I/O modules
● Desigo Automation Level Migration Tool lets you copy engineering parameters,
such as I/O addresses, texts, data point parameters, PID controller parameters
and trend objects, of a Visonik controller to a PX automation station.
● Desigo Point Test (DPT) lets you test data points for field devices and PX
automation stations during commissioning.
Preloaded applications Some automation stations contain preloaded applications, but are also freely
programmable. A comprehensive library of proven, standardized applications is
available and can be used instead of the preloaded applications.
XWP to PXC XWP communicates with the PX automation station via BACnet/IP or
communication BACnet/LonTalk. The CFC or Parameter Editor can communicate online with the
PX automation stations. This is a useful aid both for commissioning and testing the
automation stations, and for operation and monitoring. The pin values and some
attributes of the compounds and blocks can be modified online.
To commission a Lon-based PX automation station, XWP must be connected to
the same LonWorks network as the automation station. The program or program
changes can be downloaded via BACnet router or PTP connection, which can also
be used for monitoring and operation. The functionality to configure and
commission the BACnet router is integrated in the XWP Network Configurator.
16 | 377
Siemens CM110664en_03
2017-09-18
System Overview
Topologies
2
2.6 Topologies
Small system
Web client
PXM40/50
Touch panel
BACnet/IP
Ethernet
PXM10 Integration
PXM20
BACnet/LonTalk
Integration
Figure 3: A typical small system on BACnet/LonTalk
17 | 377
Siemens CM110664en_03
2017-09-18
System Overview
2 Topologies
Medium system
Desigo
Management station
BACnet/IP 10660Z35en_01
Ethernet
Integration Integration
PXM10
Operator unit BACnet/LonTalk
TXI..
TX Open
PXC12/22/36.D
Compact KNX
Integration
DXR2.E...
°C
°C
QMX3 AQR25..
Room units Room
sensor
Large system
E-Mail
Desigo
Management station
PXM40 / 50
Web clients Desigo touch panel BACnet
Third-party system
@
DSL-
BACnet/IP Modem 10660Z34en_01
DSL-
Modem
PXC50/100/ TXM1.. TXI..
200-E.D TX-I/O TX Open
PXG3.W100 PXG3.L PXG3.M BACnet
Modular Web interface Router Router Third-party
PXC12/22/36-E.D PXC001-E.D PXC001-E.D integration
Compact System controller System controller
Third-party
PTM-I/O integration PXC50/100/ TXM1..
Modules 200-E.D TX-I/O
integration
PXM10 Modular
Operator unit BACnet/LonTalk
Sinteso
DXR2.E CERBERUS PRO
PXC12/22/36.D
Compact BACnet MS/TP
Desigo TRA
PXC3... TXM1..
Modular TX-I/O
Third party RXB DXR2.M DXR2.E...
devices QAX5...
DALI
KNX
KNX
° C ° C ° C
° C ° C ° C
GLB/GDB...1EKN RXM21/39.1
VAV compact controller Fan coil unit I/O boxes
PX site
PX site is a means of structuring large PX projects. Desigo room automation
stations are not part of a PX site.
18 | 377
Siemens CM110664en_03
2017-09-18
System Overview
Communication Principles
2
In a PX site one PX automation station is defined as the primary server and all
other PX automation stations are defined as backup servers. Every automation
station can be defined as the primary server.
The primary server carries out system functions, such as time synchronization, life
check and the distribution of global data:
● Time synchronization: The primary server distributes the current time to the
backup devices.
● Life check: The backup servers detect the failure of the primary server and the
primary server detects the failure of the backup servers. If a server fails, an
alarm message is sent. If the primary server fails, another automation station
must be defined manually as the primary server.
● Distribution of global data: Global objects are available on all PX automation
stations. The primary server synchronizes changes, for example, calendar
object, notification class object, that are made on the primary server to the
backup servers.
Handling a PX Site in When an operating device starts, it searches for all primary servers and offers a log
Desigo clients in to the PX site.
A Desigo CC site can contain several PX sites and third-party devices. Desigo CC
registers itself as a global alarm recipient for the PX site on the primary server.
19 | 377
Siemens CM110664en_03
2017-09-18
System Overview
2 Communication Principles
If the network performance is not satisfactory, the following actions may help:
● Use the same automation station for items of equipment with frequent process
interaction.
● Divide the network into segments via BACnet router and an Ethernet/IP
backbone.
● Isolate the automation station from the network when downloading an
application.
BACnet and IP network BACnet supports various application services which are transmitted to all BACnet
structuring devices (broadcasts). Global broadcasts are blocked by the IP router. BACnet
solves this problem by using a BACnet Broadcast Management Device which
ensures that IP broadcasts only appear in one IP segment. The logical BBMD
functionality can be configured in every BACnet router and in every PX automation
station with BACnet/IP. One BBMD can be configured per BACnet/IP port. Devices
with BBMD must have a static IP address.
BACnet over MS/TP MS/TP stands for Master Slave / Token Passing. Each device on the link is
considered the master when it has the token. If it does not have immediate need to
use the token, it passes the token along to the next device. All devices on the link
which do not currently have the token are regarded as slaves, and listen to any
messages the current master may have for it. As all devices take turns being
master, the link is effectively peer-to-peer.
Use of other network IP networks (besides the other technologies mentioned above) provide the network
technologies infrastructure Desigo devices are connected to. In case a Desigo installation is
spatially distributed (for example, several buildings on a campus, multiple branches
in a country) the connection of these local IP networks (LANs) normally is done
using a Wide Area Network (WAN) or a point-to-point transmission line. These can
be based on non-IP technologies but typically are transparent for IP traffic. In this
way, all the BACnet devices connected via an IP network can communicate with
each other.
Client/Server A BACnet device can assume two different roles within a system, the role as a
server and the role as a client. These roles are defined as follows:
● Client: A system or device which uses another device via a BACnet service
(service request) for a specific purpose. The client (for example, Desigo CC,
operator unit) requests a service from a server.
● Server: A system or device which responds to a given service request. The
server (for example, PXC automation station, Desigo Room Automation room
automation station) performs a service for a client.
Most system devices in Desigo can act either as a client or as a server, but they
normally each carry out their more typical role. An automation station is normally a
BACnet server, which supplies process data to other system devices. The
automation station can also act as a client, when it, for example, subscribes to a
process value from another automation station.
20 | 377
Siemens CM110664en_03
2017-09-18
System Overview
Communication Principles
2
D-MAP program
Process and
configuration Application
data process
(Visualisation)
BACnet objects
10660Z37_01_en
BACnet protocol
BACnet standard device The BACnet standard defines several device profiles that simplify to judge (and
profile test) a device's capabilities against a specified function set. Desigo always tries to
work with such profiles and prove their fulfillment by independent test laboratories
and respective BTL logos and BACnet certificates.
● The PXC3 and DXR2 room automation stations comply with the B-ASC
standard device profile.
● The PXC automation stations comply with the B-BC standard device profile.
● The Desigo CC management platform complies with the B-AWS standard
device profile.
For a complete list with additional details, see BACnet Protocol Implementation
Conformance Statement (PICS) (CM110665) and the products page of the BIG-EU
website (www.big-eu.org).
BACnet protocol version Desigo is based on BACnet protocol versions 1.12 and 1.13:
● Desigo CC is based on version 1.13.
● The PXC3 and DXR2 room automation stations are based on version 1.13.
● The PX automation stations are based on version 1.12.
● PXM20 are based on version 1.12.
AMEV guideline Desigo complies with the AMEV guideline BACnet 2011 Version 1.2 with the
following profiles:
● Desigo CC: AMEV profile MOU-B
● Desigo PX: AMEV profile AS-B
21 | 377
Siemens CM110664en_03
2017-09-18
System Overview
2 Data Maintenance
Desigo room automation BACnet is used to exchange information between PX automation stations and
DXR2 and PXC3 room automations stations and the management platform.
Desigo RX The Desigo RXB room automation range communicates via KNX S-Mode (EIB)
and the RXC room automation range communicates via LonWorks standard.
Restrictions for LonWorks A LonWorks network cannot be segmented with LonWorks routers, as the
message length for BACnet is 228 bytes for performance reasons. Commercially
available LonWorks routers do not have sufficiently large buffers for this length. No
other media (power lines, infrared, etc.) can be used either.
22 | 377
Siemens CM110664en_03
2017-09-18
System Overview
Data Maintenance
2
Displaying process data settings. The data (copy) required by a client is normally updated via the BACnet
and parameter settings protocol on an event-driven basis and with a short time delay.
All process data and parameter settings, even those that are not mapped to
BACnet objects (engineering setting), can be monitored and operated in Xworks
Plus (XWP). BACnet clients only see what is available via BACnet.
If several clients modify the same process data, the last change is accepted.
Volatile and non-volatile The majority of the process data is volatile data, which is recalculated when the
process data and automation stations are restarted. However, certain process data is retained even
parameter settings after an automation station restart, for example, self-adaptive control parameters,
run-time totalizers, etc., which are specifically identified as such in a function block.
Even in the event of a program change, this non-volatile process data remains in
memory and can be read back with XWP.
All parameter settings are non-volatile, that is, they are retained in the event of a
power failure.
Readback All non-volatile PX process data and parameter settings can be read back into
XWP. However, parameter settings in the operator unit cannot be read back into a
tool.
Global parameter settings Some parameter settings are identical in all automation stations, for example, date
and time, calendar function blocks and Notification Class function blocks. To
ensure consistency, they are held in global objects which are automatically
replicated in the system.
Archived data
Setting parameters can be logged and archived. Archived data illustrates the
response of process or system variables or events over a time period. For example,
trend data can be moved from the trend database into archive files. Archived data
are typically lists of one or more of the aforementioned variables and are preferably
stored and processed on the management level. Only small amounts of data are
archived at the automation level. Such data is normally forwarded to the
management level.
Ensuring consistency Archived data only requires a consistency check in cases where it has been moved
from one application to another, for example, from the automation level to the
management level. The data origin is not deleted until a check has been carried
out to ensure that the data has been transferred in full. This data is stored in the
non-volatile memory.
Irregularities in the logging of archived data are recorded in the data itself.
The life of the data is determined either by the user or by a configurable application
which automatically condenses or deletes this archived data.
23 | 377
Siemens CM110664en_03
2017-09-18
System Overview
2 Data Maintenance
Metadata
Metadata is project-independent data from standard BACnet objects (for example,
analog input, schedule, etc.) which needs to be known by a tool or a client, for
example, texts for predefined BACnet enumeration, maximum size of arrays, data-
type information, fixed operating limits, etc. The metadata is loaded into the
relevant clients or tools at HQ and (except texts) cannot be modified after delivery.
Text, like the text for BACnet enumeration referred to above, must be localized
(language translation) and distributed to the clients and tools. This is part of the
localization process.
D-MAP program
The D-MAP program is an executable program, and contains instances of the
function blocks with the associated process data and parameter settings, the
configuration and description data and the interconnection and order of processing
of function blocks.
The D-MAP program can be modified during operation either by reloading the
complete program including any changes, or by delta (differential) loading. Delta
loading only reloads the changes.
The D-MAP program is generated in XWP/ABT from the information in the program
charts, compiled and downloaded into the automation station.
Libraries (LibSet)
The Desigo Library Set (LibSet) is a set of mutually interdependent libraries that
belong to a given Desigo system version.
Firmwareblocks
The library contents are continuously extended. Every LibSet Extension of Desigo
(LED) is a comprehensively tested collection of solutions covering all the
necessary parts of the Desigo system.
The LibSet version number defines which LED runs on which system version. The
first part of the version number represents the applicable system version.
A LED includes the latest library per automation station type (PXC, PXC00(-E).D,
PXX-L11/12, PXKNX) for the latest Valid Version Set.
New LEDs are delivered at regular intervals. The individual LEDs are consecutively
numbered (LED0 to LED16).
24 | 377
Siemens CM110664en_03
2017-09-18
System Overview
Data Maintenance
2
DESIGO-LibSet-HQ-230020-02
LibSet version number When a LibSet version number is released (new LED), the incremental part of the
and LED version number is increased accordingly, for example: Desigo-LibSet-HQ-410080-
10 > Desigo-LibSet-HQ-410080-20
The remaining numerical values in the decade (for example, 11 to 19) can be used
by the RCs for localization versions.
If the version number changes, the LibSet number is reset to 10 again. If the scope
of the Desigo application changes, the LED number is also incremented, for
example: LED02 > LED03
The following table shows the relationship between LED and LibSet version
numbers and an overview of current and planned application content for the
Desigo LibSet.
LED01 PXC: Additional applications for ventilation and heat generation Desigo LibSet-HQ-220031-04 October 2003
and distribution
LED02 All RXC applications for refrigeration generation and distribution Desigo LibSet-HQ-220041-02 December 2004
LED03 PXC: Applications for refrigeration generation and distribution Desigo-Libset-HQ-220041-06 March 2004
RXC: Additional combined applications (INT..)
LED04 PXC: Air quality and domestic hot water applications and recovery Desigo-Libset-HQ-220041-08 June 2004
function after power failure
LED06 PXC: Additional applications for ventilation and domestic hot water Desigo LibSet-HQ-230010-02 January 2005
Desigo Insight: Update to genie library for Visonik, Unigyr and
Integral
LED07 PXC: Additional solutions for ventilation facilities, refrigeration Desigo-Libset-HQ-230010-06 November 2005
plants, heating functions, heating plants and universal functions
LED08 PXC: Like LED07 and compounds for QAX, RX Desigo-Libset-HQ-235040-02 November 2005
DI: Genies for lab management integration
PXR: Compounds for Lab Management integration
25 | 377
Siemens CM110664en_03
2017-09-18
System Overview
2 Data Maintenance
LED11 Like LED10 and RXB and RXL integration solutions Desigo-Libset-HQ-236040-02 July 2006
LED12 PXC: Solution for combined heating/cooling circuit, room model, Desigo-Libset-HQ-237030-02 February 2007
quality monitoring of control circuits, leakage suppression Desigo-LibSet-HQ-236050-04
PX/KNX: New integration compounds
LED14 PXC: Additional applications for ventilation facilities, Desigo-LibSet-HQ-400210-10 March 2009
heating/refrigeration circuit, heating circuit
Heat storage tank and trend
LED15 PXC: Energy-efficient application AirOptiControl for ventilation and Desigo-Libset-HQ-410090-10 April 2010
air conditioning plants
Compounds to integrate Grundfos and Wilo pumps
26 | 377
Siemens CM110664en_03
2017-09-18
System Overview
Views
2
Key:
* The PXC3 room automation station supports several firmware versions independent of the
functional content of the application library.
Desigo CC The application libraries for Desigo CC are delivered as extension modules for the
respective system versions. For information about compatibility, see Desigo CC
System Description (A6V10415500).
2.9 Views
There are four views:
● Technical view
● User view
● System view
● Program view
PXM20
10523Z05en_01
Site
BACnet
objects
Figure 9: The technical, user, and program view in the building automation and control system
Technical view
The technical view illustrates the technical building services equipment, such as
HVAC systems and associated elements, in the building automation and control
system. The technical view is always present and can be used as a substitute for
the user view if the user does not have his own user designation.
User view
Freely defined and The user view is optional in a project. The user view is based on user designations,
structural user view for example: PL7’FL3’ELE”HEAT.STPT
The structure and syntax of the user designations can be defined for each specific
project and customer. Example of a structure: Installation/building/room/plant
element/signal
User view via the User Desigo supports different user views, depending on the application:
Designation (UD) In Xworks Plus (XWP) a User Designation (UD) can be entered for function blocks
or compounds in addition to the Technical Designation (TD) and description. This
27 | 377
Siemens CM110664en_03
2017-09-18
System Overview
2 Views
entry is carried through in the system and can be evaluated by clients. The UD
allows customers to use their own preferred designations for the plant without
changing the technical structure. The UD can be used in the management platform
in addition to the TD. The detailed view in the PXM20 operator units shows the UD
as information.
User Designation for You can define the user view for Desigo Room Automation as follows:
Desigo Room Automation ● Define a structure for the user view
● Copy Desigo Room Automation objects into the user view
● Define UDs that can be used as object names
System view
The system view shows the standard system hierarchy (BACnet view):
● Network, topology
● Device and third-party device view
● Flat representation (no hierarchy) of all BACnet objects in one device
The system view provides access to all BACnet devices (including third-party
BACnet devices) and all BACnet objects. A third-party client displays this view of a
PX device.
The system view is used in the PXM20 only for third-party devices.
Program view
The engineering and program view corresponds to the XWP/ABT view. The
structure is matched to the automation station. Within an automation station, the
view is program oriented: nested CFC charts (compounds) and function block
instances.
Per User Technical view User view System view Program view
1 Operator (without technical Main view Main view No access No access
training)
2 Operator (with technical training) Main view Main view Occasionally No access
3 Engineer (Desigo CC), User Main view Main view Occasionally No access
(PXM...)
Flexible object name engineering causes a greater engineering effort and must
thus be requested specifically by the customer.
Each BACnet object has an object name for identification on the BACnet network.
This object name must be unique within the automation station. The Technical
Designation (TD) is used as default for the object names. The TD is a technical
28 | 377
Siemens CM110664en_03
2017-09-18
System Overview
Views
2
identifier and is used to identify the plant and associated elements in the technical
view.
You can select how the object name is created for each standard BACnet object.
This especially applies to BACnet multivendor projects, where a special object
name structure is required.
Defaults and rules The following defaults and rules apply when you engineer the object name in the
XWP Hierarchy Viewer:
● The Free Designation (FD) can be max.69 characters.
● Only ISO-Latin-1 code points from [32..127] and [160..255] may be used. This
excludes all characters from [0..31] and [128..159]. These ISO-Latin-1 code
points are identical to Unicode code points.
● No lead or post blanks [32] may exist and object names containing only blank
characters are not possible.
The FD values and the object name selection are transferred automatically to the
automation station or exported to the management platform during compiling or
loading in the CFC.
The CFC Editor checks during compilation if the object name is unique for each
automation station under the following rules:
● The same resulting object name may exist only once per automation station.
This also applies to the device object that must be unique in the BACnet
internetwork.
● The resulting object name may not correspond to a TD of another object in a
Device. The TD is used to resolve BACnet references.
Exceptions for object Object names cannot be engineered in CFC charts or compounds. These elements
name assignment always define the TD and the object name is always the same as the TD.
Special blocks, such as Heatcurve and Discipline I/Os generate reduced value
objects in the background whose object name per default is the TD during
compilation.
Free definition of the The device ID (the object ID of the device object) can be freely defined. Range:
Device ID 0…4'194'303
29 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
3 Coverage of the Technical Process
DCM •
XWP • • • •
ABT • • • •
30 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
Coverage of the Technical Process
3
DCM •
ABT • • • •
Apogee tools • • • •
Desigo tool • • •
Sales DCM supports system design and quantity determination during the sales process.
Price calculation, offer preparation and tracking, and invitation of tenders are
supported by country-specific tools.
Planning The planning tools are country-specific and comprise the following:
● Network planning, design and documentation
● Cable planning and design (network cables, field device cables)
● Texts for equipment plates
● Building planning (system components in the building, room segmentation)
● Plant planning and documentation (plant schematics, function description)
● Planning of the groupings for Desigo Room Automation
● Order lists
Engineering Most of the Desigo system components are engineered offline, before they are
commissioned. This way you can verify and document the configuration (for
example, for the uniqueness of addresses), and define work packages for
subcontracting.
XWP and ABT are Desigo engineering tools and allow the following:
● Engineering the primary equipment, room automation, BACnet router
● BACnet references for the integration from/to third party systems
● Interfaces to ElektroCAD, Pharma Validation
● Exports for documentation
● Export for engineering in Desigo CC
The tool export:
● Generates information for illustrating the generic operation (technical hierarchy,
User Designation hierarchy)
● Contains information for efficiently generating graphics (mapping functions to
symbols and graphic templates in Desigo CC).
Installation XWP and ABT allow the following:
● Creating order lists that can be used for ordering the devices
● CAD export for connecting to ElektroCAD for designing control cabinets
● Parallel working of several subcontractors/engineers in a project
● Creating pack and go's for commissioning and the point test for subcontractors
● Loading configurations
● Creating commissioning data point lists
Commissioning XWP and ABT allow the following:
● Commissioning of the systems (loading programs, program function test)
● Online trending during commissioning
● Diagnostics during commissioning
● Parallel working of several commissioning engineers in the project
Service XWP and ABT allow the following:
31 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
3 Coverage of the System
Tools for Desigo PX The following tools are used for Desigo PX:
● DCM: For designing the system and determining the necessary quantities
● XWP: For configuring and commissioning BACnet routers
● LNS Tool: For loading applications into the RXC controllers
● ACS: For configuring, commissioning and operating Synco and RXB devices
● PX KNX Tool: For configuring the KNX side of the PX KNX system controller
● AL Migration Tools: For migrating Unigyr, Visonik and Integral to Desigo
32 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
Coverage of the System
3
Utilities
Desigo Configuration Module
BIM Tool
TX Open Tool
Hierarchy Viewer
Report Viewer
DPT Tool
Room Automation
RXC Integration
RXC
Third-party
LNS Tool
RXT10
Tools for Desigo Room The following tools are used for Desigo Room Automation:
Automation ● DCM: For designing the system and determining the necessary quantities
● XWP/ABT:
– For configuring, programming and loading PXC3/DXR2 room automation
stations
– For integrating KNX devices into Desigo Room Automation (on KNX PL
Link Bus)
– For engineering and commissioning PXC3, TX-IO, In-Room Bus DALI and
KNX PL Link
33 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
3 Main Tasks
Network Configurator
Utilities
Point Configurator
CFC
Desigo Configuration Module
Hierarchy Viewer
Report Viewer
ETS
KNX PL-Link
VAV
FNCL
> ABT-SSA for KNX PL-Link
Switch
> ABT-SSA/ETS for KNX S-Mode
Presence
QMX3
KNX S-Mode
DALI
DALI > ABT-SSA for DALI
34 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
Main Tasks
3
Sales support
Desigo Configuration Module (DCM) supports the calculation of the Desigo
configuration for the sales process.
You can verify if:
● The Desigo configuration is technically correct, that is, the solution that was
sold can be implemented with Desigo
● The system limits have been taken into account, that is, the number of possible
devices and functions in the network is verified
● The quantity is correct, that is, correct device types for the automation and
room functions, field devices, accessories and licenses
● Services are correctly calculated
● The design for the review with the customer is well documented
● Prices are correct (regional companies can add their prices to the DCM
database)
35 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
3 Main Tasks
Table 6: Desigo PX
Level A You can create solutions with the available options and variants with little prior
training and detailed knowledge.
The device is preconfigured and can be configured for the specific project. The
functions are predefined. You can configure the application using options and
variants. You can set the function of the application and the peripheral devices with
a configuration tool. The solutions are delivered by HQ as verified and documented
solutions.
Level B The device can be configured for the specific project. You can assemble the
application using library elements. This is a major advantage of the Desigo
application libraries. Even though assembling a solution is relatively easy, the
functions of the solutions are powerful. Using many options and variants, you can
customize the standard solutions to your project requirements.
Level C The device is preconfigured and can be configured for the specific project. You can
assemble the application using library elements. You can program the application
with default function modules with predefined interfaces. You can program using
simple programming functions.
Level D This level offers full flexibility, but requires detailed knowledge of the application's
structure, the programming tools, BACnet and the Desigo system functions. You
can program in CFC (Continuous Function Chart) with basic function modules. You
can use all available programming functions. You must ensure that the programs
you develop fit together regarding execution, priorities, auto-connecting in the tool,
interface usage, etc.
This level offers full flexibility, but requires detailed knowledge of the application's
structure and the programming tools. You must ensure that the functions of the
program work. You must ensure that the programs you develop fit together with all
36 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
Main Tasks
3
Level E elements in the library and that they are well tested and documented. You must
take care of the compatibility, the versioning and the library packaging.
37 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
3 Tools for Different Roles
Design Engineer Can carry out a project. System and room automation
Can select and configure solutions from the library.
Balancer Can balance rooms regarding air and water supply. Room automation
Table 8: Roles
38 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
Working with Libraries
3
ABT Package XWP ABT ABT ABT Site ABT Site not ABT Site not
licensed licensed
ABT-SSA Access Point Test • • • •
via role and Operate and monitor
password Balancer • • • •
• • • •
ABT-SSA
39 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
3 Workflow for Primary Systems
1. Step: Part of the project is transferred from the Branch Office Server to a
computer in the plant.
2. Step: Parts of the transferred project can be transferred to local computers. This
is called a sequential check-out.
Parts of the project, such as the building or network topology are checked out in
read-only mode, so that all users always have the project overview.
Working in parallel during Several users can work on different automation stations in the same project at the
engineering same time. To do this, data is transferred from the central data storage on the
Branch Office Server to the local hard disks. For example, individual automation
stations are being commissioned at the customer's site while some automation
stations are still being engineered at the office.
Working in parallel during Several users can work on different automation stations in the same project at the
commissioning plant at the same time. To do this, the components to be loaded are transferred
(Pack & Go), so that the user, for example, can load the configuration or program
and then perform the point test. The test results are saved in the automation
station and can be viewed and transferred back to the engineering database by the
commissioning engineer at any time.
Working in parallel during A service technician can connect with the plant by remote and make changes. To
service do this, data is transferred from the Branch Office Server to the local hard disk.
After the technician is done, the changes are transferred back to the Branch Office
Server, so that the project database is up-to-date again.
Subcontracting Project-specific solutions can be developed outside the project organisation and
specific tasks, such as configuration and point test can be outsourced to
subcontractors.
If you outsource specific tasks, make sure that:
● The work packages for the subcontracting can be easily transferred to the
subcontractor
● The subcontractor's work can be documented
● The changed data can be transferred back to the engineering database
XWP Hierarchy Viewer Create project structure (the building structure is system-oriented):
and XWP Network ● Create project structure
Configurator
● Create building topology (building, building parts, etc.)
● Create system topology (sites)
40 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
Workflow for Room Automation Classic
3
41 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
3 Desigo Configuration Module (DCM)
ABT Site > Building Create Desigo Room Automation project structure (the building structure is room-
oriented):
● Create building topology (buildings, floors)
● (Optional) Create user-specific building topology (UD structure)
● Create network topology (define address ranges)
● Create documentation (XWP Report Manager)
ABT Pro and ABT Site > Create project library:
Configuration ● Program automation stations (ABT Pro)
● Create templates for type-based automation stations (ABT Site > Configuration)
● Create templates for room control units
ABT Site > Building Create instances in the building:
● Create automation stations, or rooms, based on the project-specific library per
floor
● Edit room parameters
ABT Site > Startup Commission:
● Configure and load automation stations (node setup)
● Carry out point test (ABT-SSA) (subcontracting)
● Parameterize (ABT-SSA)
All projects are password-protected.
42 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
Desigo Xworks Plus (XWP)
3
Desigo Room Automation The Desigo Room Automation level lets you create highly complex building
level structures with the sublevels building, floor, zone, room, and room segment for
Desigo Room Automation.
The required hardware is calculated from the specified functions and/or data points
and/or KNX PL-Link and KNX devices. The specification follows a model function
set that is then assigned to the structure within the Desigo Room Automation level.
In addition, multiple model function sets can be created in a project and each of
them assigned as needed. A structure at the Desigo Room Automation level may
have multiple, assigned model function sets, and a model function set can be
assigned to different structures. As Desigo Room Automation often uses the same
structures and functions, you can indicate a multiplier on each sublevel within the
Desigo Room Automation level.
Automation level At the automation level you can calculate the required hardware based on
specified data points.
You can choose and calculate many variants using presettings. Variants include,
for example, the automation station type or I/O module type, larger automation
stations, or if plants are to be distributed among multiple automation stations. You
can also consider other criteria, such as available panel sizes.
Room automation You can choose solutions with LON and/or KNX. You can choose predefined
solutions with drag & drop and then equip them with the required field devices. This
way you can create a sample room and replicate it as required.
Third-party devices You can integrate third-party devices with protocols, such as LON, KNX, ModBus,
M-bus or OPC, on all levels.
43 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
3 Desigo Xworks Plus (XWP)
44 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
Desigo Xworks Plus (XWP)
3
You can configure I/Os and I/O modules and connect I/O channels with the I/Os.
You can design the integration of the room automation and the third party
integration. The import function lets you integrate third party data points on the
automation level. You can import data point information via a standardized
interface (SDF format). The BACnet reference browser lets you address BACnet
references. You can import BACnet references via a standardized EDE import file
(CSV or XLS format).
The Xworks Hierarchy Viewer shows the technical hierarchy per PX and the
technical hierarchy as it is shown, for example, in the generic view in Desigo CC.
You can define the user designation (UD) and the free designation (FD). You can
define the structure of the user designation with the field lengths and the
separators and assign the data points in the structure of the user designation. You
can verify the consistency of the user designation and free designation in the entire
project and assign the technical designation (TD = default value), the user
designation (UD) or the free designation (FD) to the object name (ON).
45 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
3 Desigo Xworks Plus (XWP)
If you use the solution library, you do not have to program in CFC.
46 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
Desigo Xworks Plus (XWP)
3
The CFC Classic editor shows all blocks that are used in the program, nested
plans, all available CFC block libraries and the selected plan with the plan
interfaces to other plans. This view is available offline for programming and online
for checking the signal flow. The CFC Classic editor lets you compile programs,
that is, create loadable programs.
Additional editors In addition to the graphic programming, you can configure the programs in the
following editors:
● Parameter Editor: Lets you parameterize attributes.
● I/O Address Editor: Shows all I/Os of an automation station.
● Plant Control Editor: Lets you configure the plant controls for ventilation and
energy generation.
● Solution Configurator: Lets you configure solutions, that are from the CFC
library or have been generated from the Xworks Project Configurator.
● Simulation: Lets you simulate programs of a modular automation station
without hardware on the computer.
● Alarm display: Continuous update and local caching of all alarm status changes
during commissioning. Lets you view, acknowledge and reset alarms.
47 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
3 Desigo Xworks Plus (XWP)
You can select one or more automation stations for the documentation, per
automation station, plant or system node. You can select document templates and
verify reports in a preview.
BIM Tool
The BIM Tool is used for TX-I/O modules that are integrated with a BIM on
automation stations. The BIM was used on old automation stations for integrating
I/O modules.
TX Open Tool
The TX Open Tool lets you configure TX Open modules. You can define the TX
Open integration and commission the TX Open modules. To commission TX Open,
load a configuration into the modules with the TX Open Tool.
See TX Open Tool online help (CM111005).
RXT10 Tool
The RXT10 Tool lets you configure and commission RXC controllers.
In RXT10 you can select and configure the RXC applications. Then you define the
assignments in the rooms. After the room types have been tested, the applications
are multiplied and commissioned. Then you integrate the room automation (PXR).
Create the building hierarchy and design the rooms on CFC data. Finally group the
system functions and commission the PX application.
48 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
Desigo Automation Building Tool (ABT)
3
ABT Pro
In ABT Pro you program automation stations (project-specific solution). Project-
specific solutions can be created in the Center of Competence (CoC) and used as
project-specific types in the project in ABT Site.
ABT Pro contains the CFC Plus editor for programming in CFC.
49 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
3 Desigo Automation Building Tool (ABT)
50 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
Programming in D-MAP
3
ABT-SSA
In ABT-SSA (Setup & Service Assistant) you commission I/Os and carry out the
point test.
See Desigo TRA - Setup & Service Assistant (CM11105).
In ABT-SSA you can:
● Assign network points (DALI to device), make points available
● Test if the points work
● Define parameters, for example, time, desired value, default value, etc.
XWP XWP is the programming tool for the PX automation station and incorporates all
system elements. XWP shows the structural view of the system with the plant,
partial plant, aggregates, and components, and, for example, the compound
functional unit for a valve.
51 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
3 Programming in D-MAP
Figure 26: Structural view (left pane) of the system and compound for a valve (right pane) in XWP
52 | 377
Siemens CM110664en_03
2017-09-18
Desigo Workflow, Tools and Programming
Programming in D-MAP
3
Primary
I/O
PX Prim I/O
Prim
Prim
I/O
Central
Central
Central
I/O
CenGen CenHvac CenLgt CenShd I/O
I/O Reference
PXC3 CenGen
CenGen CenHvac
CenHvac CenLgt
CenLgt CenShd
CenShd I/O
I/O
I/O
room
DXR2 CenGen
CenGen CenHvac
CenHvac CenLgt
CenLgt CenShd
CenShd I/O
I/O
CenGen
CenGen
CenHvac
CenHvac
CenLgt
CenLgt
CenShd
CenShd
I/O
Room
Room
Room
Room
RCoo Room
RHvacCoo
Room RLgtCoo RShdCoo
RCoo RHvacCoo RLgtCoo RShdCoo
RCoo RHvacCoo RLgtCoo RShdCoo
PXC3 RCoo RHvacCoo RLgtCoo RShdCoo
DXR2 RCoo
RCoo
RHvacCoo
RHvacCoo
RLgtCoo
RLgtCoo
RShdCoo
RShdCoo
Scene
Room Segment
Room Segment
Room Segment
Room Segment I/O
Hvac Room Segment Lgt Shd I/O
Hvac Room Segment Lgt Shd I/O
Hvac Room Segment Lgt Shd I/O
Room Segment
HvacRoom Lgt Shd I/O
Hvac Segment
Lgt Shd I/O
Hvac RoomSegment
Segment
Lgt Shd I/O
Hvac Room Lgt
Room segment Shd I/O
Hvac Lgt Shd I/O
Hvac Lgt Shd I/O
Hvac Lgt Shd I/O
PXC3 Hvac Lgt Shd I/O
I/O
DXR2
Hvac Lgt Shd I/O
I/O
Lgt
Lgt
Shd
Shd
I/O
Grouping Direct reference
TR Brgt Psc
53 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Programming in D-MAP
4 Control Concept
Supply chain model
In building automation and control, media, such as warm water, cold water, warm
air, and cold air are generated using energy, such as oil, gas, and electricity, and
distributed to consumers.
Each medium can be assigned a supply chain. The supply chain starts at the
generation or handling of the medium. The distribution system then transports the
medium to one or several consumers. A supply chain for building services systems
comprises the following links:
Consumers The consumer supplies the energy contained in the hot water medium to the room
as per the requested demand (for example, via a radiator).
Distribution The distribution system transports the medium from the producer to the consumer
and adjusts it to the individual requirements (minimum losses).
Production The production consists of a boiler where hot water is treated by means of energy
(for example, heating oil, gas) and provided to the process.
Supply chains of various The following illustration shows a schematic view of the supply chains for the
media media air, hot water, and cold water with their respective production (treatment),
distribution (for example, heating circuit, pre-control), and the consumers.
The supply chain for the medium electricity, which normally begins at supply or at
production, if electricity is produced on-site (for example, cogeneration plant,
photovoltaic) is also shown.
54 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Programming in D-MAP
4
Figure 29: Supply chains for the mediums air, hot water and cold water
A tree structure opens to the right for the individual supply chains. In other words,
one or more generators supply multiple primary controllers and each primary
controller for its part supplies one or more consumers or other primary controllers.
From the air supply chain point-of-view, air treatment is a part of production
(handling). From the hot water and cold water point-of-view, air treatment (or air
heater/cooler) belongs to consumption.
The air supply chain comprises the central air treatment plant, optionally
supplemented by pressurization control and air posttreatment.
Supply flow In each supply chain, the medium flows from the producer, through the distribution
system to the consumer. This flow within the supply chain is referred to as the
supply flow.
Supply chain structure A supply chain consists of at least one producer and one consumer. It can also
have multiple chain links, that is, producers, distributors, and consumers, and be
structured as follows:
1. One producer with one distributor and one consumer.
2. One producer with two distributors in series and one consumer.
3. One producer with two distributors in parallel and two consumers in parallel.
4. Multiple producers, distributors, and consumers in parallel.
55 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Programming in D-MAP
Producer In practice, however, there are often multiple producer units, for example, boilers
with the same or similar power, or a mixture of different units, for example, boiler
combined with a solar plant and cogeneration plant (usually with additional storage
units).
Logical producer From the distributor and consumer point-of-view, there is only one single producer
within the supply chain, the logical producer, with exactly one supply point as the
interface to the distribution network. This logical producer knows nothing about the
structure of the distribution network and the connected consumers. Also, neither
the distributor nor the consumer knows whether the producer consists of one or
multiple units.
Distribution components The distributor or distribution transports the medium within the supply chain. In this
process, energy losses and energy consumption of pumps and fans is to be kept to
a minimum.
Conversion Conversion (transformation) of the medium, for example, in a heat exchanger, is
assigned to a supply chain of distribution. A change of temperature (for example,
pre-control in the heating circuit) is also seen as conversion. Pre-controllers can be
arranged in series (cascading).
Consumers The following consumers, for example, belong to the various supply chains:
56 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Programming in D-MAP
4
Coordinator and In addition to the three chain links producer, distributor, and consumer, there are
dispatcher the logical links named coordinator and dispatcher.
Supply chains for a room You can define different consumer needs for a room, such as heat, refrigeration
and fresh air.
Heat demand The hot water supply chain exists for heat demand. The medium hot water is
prepared in hot water generation and distributed via a heating circuit. The heat is
emitted to the room as needed via a heating surface. If air is the carrier of heat, this
is done via pre-control and air posttreatment.
Refrigeration demand The cold water supply chain exists for refrigeration demand. The medium cold
water is prepared in cold water generation and distributed via a cooling circuit. The
refrigeration is emitted to the room as needed via a cooling surface. If air is the
carrier of refrigeration, this is done via pre-control and air posttreatment.
Fresh air demand The need for fresh air is met by the air supply chain, where the medium is
produced by the air treatment plant, distributed via the ducting, possibly adjusted to
differing requirements of the room by an air posttreatment plant, and transferred to
the room via air outlets.
57 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Programming in D-MAP
Plant A plant consists of partial plants, aggregates, and components, which, as a rule,
form a supply chain with the chain links producer (here: boiler), distributor (pre-
control, heating circuit), and consumer (radiator).
Operator interventions Commands are executed at each link of the chain through operating interventions
via HMI commands. The impact on the plant (or the process) takes place via the
corresponding function unit and automation station.
Functional units Functional units represent the software map of chain links and plant elements. The
functional units contain all control, monitoring, and limiting functions that are
necessary for operation.
Information signals Energy demand information can be passed on implicitly via the medium within the
supply chain, for example, if the hot water supply temperature falls because of a
rise in heat consumption, more heat energy must be produced.
Information can also be represented by an explicit signal and transferred via a
signal path (for example, via a bus). The following explicit signals have been
defined in the Desigo system:
Operating signal Producer to consumer A plant informs the downstream plants about its currently effective operating state.
This signal is only used as an exception and is therefore switched depending on
the situation.
Override signal Producer to consumer The producer demands a certain operating mode from a consumer. Forced
signals are more the exception than the rule and are therefore not implemented in
sample plants. Forced signals are used for solar plants and wood furnaces among
others, where the minimum heat production cannot be controlled.
In addition to the functional units, there are two further elements that belong to the
supply chain on the software side:
58 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Control Concept and Control Blocks
4
59 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Control Concept and Control Blocks
Structure control functions In this way, complex control and monitoring functions of a plant can be logically
subdivided to allow for clear assignment of the function unit or the real element of
the plant. The higher-level control concentrates on the control and monitoring of
the overall plant, while the sub-control function units assume internal control and
monitoring of the given elements for the function unit.
Standardization of control Moreover, plant security and available was increased through standardized control
functions and monitoring functions which would result in considerable expense using
conventional methods.
Standardized control and monitoring functions:
● Unambiguous selection of operating mode
● Uniform fault-related shutdown
● Comprehensive status monitoring
● Switching sequence for ventilation systems
● Output stage control for heat generating plant
● Reporting of local intervention
● Avoidance of unnecessary attempts at switching
● Prevention of inadmissible switching operations
● Protection of plant by preventing switch-on or switch-off
60 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Control Concept and Control Blocks
4
Command control CMD_CTL Superposed control block for sequence control. The block ensures that individual
plant aggregates are switched on or off sequentially in a certain order. The block
monitors aggregates and can send alarms. It is optimized for controlling air
handling plants, but can be used for other applications. The block is used on the
hierarchy level plant/partial plant.
Power control PWR_CTL Superposed control block for power control. The block is used for control and
monitoring of the performance of a number of energy producers (multiple boiler
systems, refrigeration machines). Depending on the request power demand,
energy produces are switch on or off in stages. PWR_CTL is optimized for
controlling heating and refrigeration plants. The block is used on the hierarchy
level plant/partial plant.
I/O blocks with control BO Output blocks implemented per BACnet standard and therefore including a priority
functionality MO mechanism (priority array) that is well suited for control tasks. The priority array
[PrioArr] be used through data flow interconnections and BACnet commanding.
AO
Moreover, the block integrate the following control functionality:
- Motor control (pump, burner, etc.), one- to four-speed [BO, MO]
- Fan control, one- to four-speed [BO, MO]
Value blocks with control BVAL Value objects or value blocks are implemented per BACnet standard and
functionality MVAL therefore includes output blocks via the priority mechanism. These blocks are
referred to as data points that can communicate within the system with the I/O
AVAL
modules via BACnet. These blocks are primarily used as the communication
interface between superposed control [CMD_CTL, PWR_CTL] and the
aggregates.
Rotation block ROT_8 The Rotation block switches the operating mode on and off for a maximum of
eight functional units in accordance with a selected mode of rotation (sequence or
hours run). The change of operating mode is based on demand, hours run,
occurrence of a fault or manual intervention (override).
The block is used to process the functional units (for example, aggregates or
components) as a function of run-time or faults. These blocks are used, for
example, for double pumps, that are changed over based on runtime.
Control hierarchy
Control hierarchy is the map of the functional assignment and linking of those
function blocks included in the control concept for a plant. The structure of the
control hierarchy is subject to certain rules. A distinction is drawn between higher-
level plant control and local control of the functional units.
Superposed control Within the hierarchical structure, higher-level control functions are typically
assigned to the partial plant level. All the variables which are influencing factors on
the overall plant are weighted and combined to give the effecting plant operating
mode. In respect of each of the possible plant operating modes, a control strategy
can be defined for each underlying functional element. This makes it possible to
develop specific plant scenarios, such as fire control, smoke extraction, frost
control, on/off-switch control.
Local control Within the hierarchical structure, local control of the function elements is typically
assigned to the partial plant level. The main function of local control is to respond
to faults. The functional unit itself determines how the outputs are to be controlled
in the event of a fault. Interlocks between functional units (for example, damper/fan)
must be implemented locally. Local control prevents the risk of damage to plant, in
the event that the command control parameters are set incorrectly.
61 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Control Concept and Control Blocks
The control hierarchy in the following figure considers only the example application
for ventilation.
A-Transport
OpSta
EnCrit
DmpShofEh Ag:DmpShof
EnCrit
CMD_CTL
On
FanSu
Ag: V(A,C-F) Fan1St
SmextPrg
En
OpSta
SmextEh Cp:BI
EnCrit
E,U
BI
SmextEh
On/P14 Open/P14
ErcRo DmpShof
EnCrit
On
SmextSu Cp:BI
E,U
BI
SmextSu
En
On/P14
FireDet Cp:BI
E,U
EmgOff
EmgOff
BI
ManSwi Cp:Ml
On
MI
En
TSu
ValSfty
SpErcTSu EnSfty
Frost
BO
KickDmp
Dstb
En
Sequence table
ValPgm OpSta
EnPgm PrVal
M
E,H
On
OpModSwi Cp:MI
E,H
Ax: DMUX8_BO
En
OpMSwiCnv
MI
BVAL
En
AO
PrVal FbVal
PrVal
On
OpModMan
Cp:MVAL_OP
MVAL
En
ValSfty
En
TSu
O&M
EnSfty
KickDmp
BO
Dstb
Frost
ValPgm OpSta
DefVal:Off
Sched
Cp:BSCHED
BVAL
On
AO
En
En
PrVal FbVal
PrVal
62 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Control Concept and Control Blocks
4
63 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Control Concept and Control Blocks
Priority mechanism Within the Desigo PX system, the BACnet priority mechanism is used for the I/O
output blocks and in the value blocks. This priority mechanism provides a series of
prioritized levels at which intervention is possible, for use with the control functions
in HVAC plant and the associated components.
The following priority levels are available with blocks AO, BO, MO (and blocks
AO_RED, BO_RED, MO_RED) and AVAL, BVAL and MVAL.
64 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Control Concept and Control Blocks
4
Operator level Local manual intervention The operator level is where components are overridden manually. Here the
operator unit may be used to force the output of an I/O function block. This
Superposed manual operation overrides all operations at a lower priority level.
intervention
Automatic level Local control The automatic level is used for local control functions and for superposed BACnet
commanding.
General BACnet commanding
The following figure illustrates the structure of [PrioArr] and the influence of local
and higher-level control.
Priorities 1, 4, 7, 15 Priority 6 Priorities 2, 5, 8, 14, 16
Local control Control within block Higher control
via data flow interconnection via BACnet command
AO BO MVAL
CMD_CTL
3
e.g. anti-icing
ValCrit / EnCrit
protection
Critical value
5
6 Monitoring hours
7 Desigo CC
e.g. local manual Manual operation
switch ValOp / EnOp 8
13
14
Local control Program control
15 ValPgm / EnPgm
PrVal
Local override The override switch overrides the block's switching value and determines in this
way the switching value for the field device. Local override has priority over an
active manual operation at the same time, that is, priority over local override.
Status monitoring [AO, BO, MO, AVAL, BVAL, MVAL]
The process is monitored via the feedback signal, and in the case of switching
blocks, also via the ramp-up and ramp-down parameters set in [TbTiDly]. If the
feedback value deviates from the present value [PrVal] and the delay in [TbTiDly]
has not yet expired, the process is in a transitional state. The status monitoring
function shows the status at the transient state [TraSta] output. This output can be
used to switch on any subsequent components.
65 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Control Concept and Control Blocks
Reliability monitoring is always active for the RED blocks since no [OaServ] is
available. Superposed control does not distinguish this state and plant safety is
not provided under certain circumstances.
66 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Local Control Design
4
Plant fault receivers. Depending on the alarm function [AlmFnct] set in the block, you may
have to acknowledge the alarm and reset it after eliminating the alarm.
The faulted block on output [Dstb] is reset only after the user action is run. The
plant ramps up only after an alarm reset since both the local control, as a rule, with
this output is blocked for a fault and as superposed control triggered a plant fault.
The alarm reset can be triggered:
● By triggering a common reset in the common alarm block CMN_ALM
● Via an alarm client
Temp: AI
OR
100 %
CritActv
TraSta
TraSta
FbVal
FbVal
PrVal
PrVal
Dstb
Dstb
Pu Cp: BO
Example forced set-up A limit value [HiLm] is defined for the temperature in block AI Temp. As soon as
this threshold is reached, the output [Dstb] switches the valve via Enable [EnSfty]
for the analog output value to 100%. At the same time, the pump is switched to off
by Enable [EnSfty] for the Binary Output BO.
Example of fault-related The block BI ThOvrld monitors the state of the pump’s thermal switch. If the contact
shutdown is triggered, the function block is activated based on the parameterized reference
value [RefVal] for [Dstb] output. The pump is shutdown through Enable [EnSfty] of
the Binary Output BO. The Binary Output BO further monitors the contact’s
feedback. In the event of a fault, where the feedback is interrupted, for example,
the block reports the fault and shuts down itself via the back wired output [Dstb].
The pump can only be switched on again only after the fault is eliminated and the
alarm message is reset as required.
The following figure shows a local fault-related shutdown related to superposed
plant control. The compound mapped here as an example was reduced to make is
easier to recognize the structure of the local control.
67 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Local Control Design
15: ValPgm
14: EnPgm
13. ValCrit
12. EnCrit
Off
Ort
Ax:OR
P15 Pgm P4 Crit
CritActv
PrVal
Dstb
CmdVal Cp:BVAL Or2 Ax.OR
TCtr
PID_CTR
0% On Off
ValCrit
EnCrit
P15 Pgm P4 Crit
KickDmp
CritActv
TraSta
FbVal
PrVal
PrVal
Dstb
Dstb
Pu 1St: BO
R/sCtl
Interlocks
The following figure shows a solution where a fan is only enabled after the damper
is completely open.
68 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Local Control Design
4
[On/Off]
OpMod
Yes
En Val En Val En Val En Val E,H
P15 Pgm P4 Crit
PfmActv
SftyActv
CritActv
TraSta
PrVal
Dstb
[On/Off] Damper Cp:BO
OpMod
Yes
Off
SftyActv
CritActv
TraSta
PrVal
Dstb
Fan Cp:BO
Figure 37: Local interlocks for damper/fan
Local interlocks A command to ramp-up the plant [OpMod] =On, the damper output changes to
[TraSta] = Yes, indicating that a transient state is now active, in other words, the
damper is moving. This information is formed on the one hand from the
parameterized damper run time [TbTiDly] and, on the other hand, from the
feedback contact for the damper's mechanical stop.
The valve is blocked via input [EnSfty] as long as the damper is either blocked or
moving, in other words, an intervention via the operator unit directly on the fan is
prevented. When the transient state ends and the damper is open, the Enable
[EnSfty] is cancelled and the fan switched on via the program value [ValPgm].
Enable of the program value [EnPgm] is a constant in this example.
Interlock among The targeted interlocking is employed in a modified form from the superposed plant
aggregates control. To allow, for example, plant control to access the fan during smoke
extraction control, the interlock is not implemented by enabling the safety value
[EnSfty], but rather by enabling the critical value [EnCrit].
The fan is set to Off by the damper via Enable [EnCrit] until the damper is fully
open. The fan can only then start. The damper is held open via [EnCrit] as long as
the fan is running to prevent a mistaken operation that could destroy the plant.
69 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Superposed Plant Controls
BACnet Reference
Open
ValCrit
EnCrit
OpSta
DmpShofOa Ag: DmpShof FanSu Ag: Fan1St
OpSta
EnCrit
ValCrit
Figure 38: Cross-aggregate interlocking of damper/fan
The operating state [OpSta] for both aggregates are formed within the compounds
as illustrated in the previous example from the AND link for [PrVal] and [TraSta].
70 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Superposed Plant Controls
4
[PrioArr] are deleted in the commanded blocks when restarting the PX controller,
with the exception of local, manual interventions to priority 8.
Special Desigo S7 Interconnection in CFC and not referencing is used for superposed control blocks
features to communicate with the commanding aggregates! The control concept is
otherwise the same as the one for Desigo PX.
Determining plant A superposed plant control generally has different sources such as plant switch,
operating mode scheduler program or important fault messages, from which the resulting plant
operating mode must be determined.
The ENSEL_MS (Enable Selector Multistate) and ENSEL_BO (Enable Selector
Boolean) blocks are available for evaluating the resulting plant operating mode in
the firmware library of Desigo. As a rule, the block is placed before plant control as
illustrated in the following figure. All potential influences are interconnected,
prioritized by importance on the block and the corresponding required plant
operating mode is determined.
Example:
● A fire detector as a high priority (P04) and requires the plant operating mode
EmergOff.
● The smoke extraction switch has the highest priority (P01) and demands plant
operating mode smoke extraction.
● The scheduler has a low priority (P11) and demands plant operating modes
Stage 1, Stage 2 and Off.
The output [Val] for ENSEL_MS now supplies the CMD_CTL the resulting plant
operating mode for additional processing. It is important that the multistate
enumerations for both blocks ENSEL_MS and CMD_CTL are the same. The
multistate values are not text, but rather numbers based.
71 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Superposed Plant Controls
A-Transport
FanEx
Ag: V(A,C-F) Fan1St
OpSta
EnCrit
DmpShofEh Ag:DmpShof
EnCrit
CMD_CTL
On
SmextPrg
FanSu
Ag: V(A,C-F) Fan1St
En
SmextEh Cp:BI
E,U
SmextEh
OpSta
EnCrit
En
On/P14 Open/P14
E,U
ErcRo DmpShof
EnCrit
On
SmextSu
En
FireDet Cp:BI
E,U
On/P14
EmgOff
En
EmgOff
TSu
On
Frost
En
Sequence table
On
OpModSwi Cp:MI
E,H
Ax: DMUX8_BO
TSu
En
On
Cp:MVAL_OP
OpModMan
TOa
En
O&M
TSu
En
DefVal:Off
Frost
Cp:BSCHED
Sched
TOa
On
En
En
The block CMD_CTL controls and monitors output and value blocks mapped on
BACnet. Communications is based on BACnet referencing rather than
interconnections to optimize the costs of engineering. The following blocks can be
used with CMD_CTL: AO, BO, MO and AVAL, BVAL and MVAL.
The sequence is determined in the CMD_CTL in a table. The command for the
individual aggregates and the components can be determined based on the plant
operating mode.
The main functionality of the block CMD_CTL is the sequential control of
aggregates and components dependent on the preset plant operating mode
72 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Superposed Plant Controls
4
[ValPgm]. For this purpose the switch-on sequence is defined by the order in the
function table [FnctTb]. The switch-off sequence is the reverse of the switch-on
sequence. Independent switch-on and switch-off sequences are not implemented
in this block.
Switched on block can be monitored for their states. There is no monitoring of the
OFF status.
Prior to switching on a block a test is made to see if the conditions for executing a
command are given. The switch-on process is not even available for active switch
on delay, minimum switch off times or a switch command with a higher command
(for example, a maintenance switch). This Look Ahead mechanism is described in
greater detail in this chapter.
This block does not contain interlocks of individual functional units within
aggregates. These are implemented locally via the data flow between the relevant
blocks.
Plant Control Editor The block parameters are set in the Plant Control Editor.
The upper part of the dialog box serves primarily to provide a quick online overview
of the present plant operating mode. You can also define exception value which
become active as a plant operating mode during a plant fault.
The upper part of the table configures the sequences. The switch-on sequence of
the objects, the monitoring mode and the switch on and off types for the sequence
controllers can be defined here.
The lower part of the table is used to define the plant operating modes. You can
define what command at what priority is command per plant operating mode for
each sequence element.
The following priorities for commanding are available:
● Priority 2: Life safety, automatic
● Priority 5: Plant safety, automatic
● Priority 14: Specific command object
● Priority 16: System control
You can enable a command priority with the value Not command for plant
operating modes where the local control is intended to assume control of the
aggregate.
[DefVal] applies when the [PrioArr] for the corresponding block is empty, that is, not
active recognition set, at that time.
Function workflows in A series of safety, monitoring and switch actions are conducted for each change to
CMD_CTL the plant operating mode in block CMD_CTL. The following table includes an
overview of function workflows:
73 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Superposed Plant Controls
Step 1: Safety function If all switch commands for a given plant operating mode have the priority Life
AllLifeSafety safety, it is referred to as the AllLifeSafety plant operating mode.
A pending AllLifeSafety plant operating mode in the [ValPgm] is executed
immediately in all cases and maintained regardless of previously existing and
newly occurring faults in the plant – human life takes precedence over plant safety.
If the AllLifeSafety mode includes switch-on commands, then the preset delay
times (Delay and Timeout) will be observed. However, in the case of the Timeout
setting, the switching sequence will continue even in the absence of any feedback
signal. Interlocks cannot therefore be guaranteed, with the exception of local
interlocks implemented via Priority 1 (life safety, manual).
Priority 1 (life safety, manual) cannot be overwritten in the AllLifeSafety.
Step 2: Preview Look Before changing to a different plant operating mode, in which referenced blocks
Ahead are to be enabled, block CMD_CTL checks to ensure that all the aggregates can
actually be enabled. For this purpose, the entries in the priority array [PrioArr] for
the switching sequence blocks are checked in advance. If switch commands of a
higher priority are found to be active (for example, a minimum switch-off time or the
OFF-command of a repair switch), then CMD_CTL waits to implement the new
plant operating mode until the full switching sequence can be implemented. Only
referenced blocks, for which a switch-on command exists in the new plant
operating mode, are checked, and only if the operating-state monitoring feature
has been enabled.
The following priorities are checked:
● Priority 1 [EnSfty/ValSfty], life safety, manual.
● Priority 7 [EnSwi/ValSwi], manual operation, for example, manual switch.
● Priority 8 [EnOp/ValOp], manual operation, operating unit.
● Priority 6 [TiMinOff], minimum switch off time.
Priority 6 is checked only for a switch on command to determine whether the
aggregate is still within the minimum switch off time. In this case, it waits until the
switch off time expires and only then switches on.
Priority 4 (plant safety, manual [EnCrit/ValCrit]) is not considered during the check,
since local mutual locking via data flow interconnection, such as depicted in the
figure Cross-aggregate interlocking of damper/fan, would change this value during
the switch-on process.
The present operating mode remains until it is certain that all impacted aggregates
with active operating state supervision can be switched to the new set state. A
process alarm is triggered in CMD_CTL of a monitored block is not switched on.
The exception value [EcptVal] is active as the new plant operating mode in this
case. The online diagnostics for the Plant Control Editors determines which
element is the cause of the fault.
74 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Superposed Plant Controls
4
Step 3: Abort sequence On-going switch sequences are aborted when delay times are still active.
Exception: An alarm is generated when a fault occurs as part of internal monitoring
of the block. The demanded plant operating mode is determined in this cased by
the exception value [EcptVal]. If the switch sequence is active, but not completed, it
is NOT aborted, but rather is completed.
Step 4: Ramp-down The ramp-down sequence is started first for the new plant operating mode. This
sequence shuts down all aggregates that must be switched off per the new plant operating
mode. The shut down takes place in the table sequence from right to left, in other
words, the last aggregate in the switch sequence is the shut down first. The
parameterized times for the time off delay are active during ramp down to off. The
time off delay can be activated using a fixed delay time or a maximum timeout or
deactivated using the immediate option. The length of the delay for timeout
depends on the switch off state of the monitored sequence elements. Transition to
the next sequence occurs as soon as it reports switched off, that is, the process
value of the block [PrVal] = Off. It switches after the timeout time expires when the
shut-down message is not sent.
If a sequence element with a life-safety or plant-safety priority is switched off, the
preset delay times will be ignored.
Step 5: Step-up sequence The step-up sequence is then started for the new plant operating mode. The
remaining aggregates are switched on per the data in the function table. The
switch on takes place in the table sequence from left to right, in other words, the
first aggregate in the switch sequence is the switched on first.
The parameterized times for the time on delay is active during step-up.
The step-up delay can be activated using a fixed delay time or a maximum timeout
or deactivated using the immediate option. The length of the delay for timeout
depends on the switch on state of the monitored sequence elements. Transition to
the next sequence occurs as soon as it reports switched on, that is, the process
value of the block [PrVal] <> Off. It switches after the timeout time expires when
the switch on message is not sent.
When a sequence element with a life-safety or plant-safety priority is switched on,
the preset delay times will take effect first.
Step 6: Monitoring switch A process alarm (off normal) is generated when the monitored aggregate is not
on state switched on after the sequence delay time expires.
The current switch sequence is immediately aborted when the current plant
operating mode is not AllLifeSafety and the exception value [EcptVal] is selected
as the operating mode.
If, however, the exception value [EcptVal] is already the plant operating mode, the
switch sequence is not aborted and the plant operating mode does not change.
Switch on aggregates The following figure shows the switch response and monitoring mechanism for
block CMD_CTL.
The system initially checks if the new plant operating mode is an AllLifeSafety
mode. The Look Ahead check takes place in the second step, followed by the
check and abort of on-going sequences. The next step is to run the shut-down
series, where objects 8 and 4 are switched off to the extent they have not yet be
shut down. The sequences are then switched on one after the other in the follow-
on switch on series.
75 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Superposed Plant Controls
Object nr. 1 2 3 4 5 6 7 8
Operating states
Priority Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd
Sequence 1
Objects 1, 2 and 3 are switched on in parallel.
Switch-on 1 Switch-on 2 Switch-on 3 As soon as 1 and 3 transmit an On signal
or the 30 sec. timeout expires,
the transition to the next sequence starts.
Timeout 0:30
Sequence 2
in stage X, and is therefore skipped.
(Off)
4 5
Sequence 3
Objects 6 and 7 are switched on in parallel.
Switch-on 6 Switch-on 7 The state monitoring mechanism waits
8 max. 2 minutes for objects 6 and 7 to
transmit an On signal.
Object 8 is inactive in stage X.
Timeout 2:00
The set time (delay or timeout) marks a switch on or off sequence that may consist
of one or more objects. The times apply for the entire sequence and take effect,
when a switch on or step up command or a switch off or ramp down command is
demanded.
Switch on occurs in parallel per sequence. A check of the switch on state occurs
only in the switch on type timeout. The next sequence is only started after either all
monitored objects report a switched on state or the timeout period expires.
Operating state monitoring of the objects for monitoring, as depicted in the
following figure, only become active after the step-up process for a sequence is
completed.
76 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Superposed Plant Controls
4
Object nr. 1 2 3 4 5 6 7 8
Operating states
Priority Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd
Object switch-on:
Switch-on procedure completed: Check if switch-on
State monitoring active state reached
Sequence 3
Object nr. 1 2 3 4 5 6 7 8
Operating states
Priority Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd
Monitoring is active from the point when the corresponding sequence successfully
completes the switch on process, that is, the process value for block [PrVal] is not
equal to Off and the transient state is completed [TraSta] = No.
The [PrVal] of the block will be monitored. Hence, only those events which affect
[PrVal] can be detected, that is:
● Local fault shut down using interconnection of fault [Dstb] to enable safety,
manual [EnSfty].
● Local shut down of the block in a higher priority application program.
● Switch-off by manual operation of the output module if the I/O module returns
the manual setting value.
● Block switched off via HMI operation or manual switch in control panel
Command control is only in a position to recognize fault-related deviations and act
accordingly when the interconnection of all relevant faults [Dstb] occur locally on a
monitored output of value block to [EnSfty]. Its default value [DefVal] becomes the
process value [PrVal], if a referenced output or value block is out of service
77 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Superposed Plant Controls
[OoServ]. The state monitoring of the plant cannot operate correctly, since [PrVal]
no longer reflects the actual state of the aggregate.
To reduce the frequency with which aggregates are switched on and off, it is
possible to define a minimum switch-off time [TiOffMin] in the aggregates. The
look-ahead mechanism in the CMD_CTL block prevents the switching of the whole
sequence if the minimum off-time in one aggregate with active state-monitoring has
not yet expired. The output [TraSta] shows the transitional state and [PrVal]
remains unchanged, at the last value. The new plant operating mode will be
implemented only when all the aggregates to be enabled in the switching sequence
can actually be enabled.
A minimum off-time should always be set for aggregates incorporating a rotating
mass (for example, fans).
Operating mode The following figure shows a changeover from operating mode Stage Y to Night
changeover cooling.
All objects were switched on in Stage Y. During the changeover to Night Cooling,
the system initially checks whether the new plant operating mode is an
AllLifeSafety mode. The Look Ahead check takes place in the second step;
followed by the check and abort of on-going sequences.
In the next step, the switch off series is conducted where the sequence elements of
switch off sequence 1 are switched off in parallel. It transitions to the second
sequence after the delay time expires. Object 5 is commanded to Off with plant
safety, priority 5. For plant safety or life safety (priority 2), the delay times or
timeouts have no effect. The transition to switch-off sequence is immediately since
object 4 is already switched on.
Sequence 1 Sequence 2 Sequence 3
Object nr. 1 2 3 4 5 6 7 8
Operating states
On On
Priority Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd Spec. cmd
Sequence 1
Delayed 0:30
Delayed 1:00
Sequence 3
Delayed 2:00
Objects 3 and 2 are switched at the same time as object 5. Object 1 remains
switched on.
Alarm management Block CMD_CTL is alarmable and differentiates process from system alarms.
A process alarm occurs, when:
78 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Superposed Plant Controls
4
Out of service The block can be taken out of commissioning using [OoServ]. The following occurs
when switching [OoServ] to On:
● Immediately abort of switch on and off sequences and monitoring.
● All objects are commanded with a release of the priorities: Life safety (2), plant
safety (4), specific command control (14) and system control (16)
79 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Superposed Plant Controls
Figure 45: Overview of PWR_CTL for control and monitoring of energy producers
Plant Control Editor The block parameters are set using the Plant Control Editor.
The upper part of the dialog box serves primarily to provide a quick online overview
of the block. The maximum power controlled by the block is set with the maximum
power parameter [MaxPwr]. The value must be greater than 0 kW in order for the
block to work. Any changes in this limit value have a direct effect in online mode. If
no limit value is required, the maximum power must be set at an appropriately high
value.
The Aggregates tab is used to set the control variables of the aggregates (boiler,
refrigeration machine).
80 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Superposed Plant Controls
4
The active profile table is defined by entering the profile number [PrfNr] as an input
parameter, or by selecting it from the Profile dropdown list in the Plant Control
Editor. This input parameter can be interconnected, so that the profile can be
changed as a function of other events (faults, summer mode, boiler operating
hours, etc.). If the profile is changed during operation, the power output [PrPwr] is
switched in accordance with the power profile in the new profile table.
The profile definition determines the order in which individual aggregates are to be
switched on or off. The following information must be entered for every sequence
entry:
● Object: Selected from the previously referenced aggregates.
● Stage limitation: Limit up to which the aggregate may be enabled.
● Control type: Specifies whether the enabled stages are to be switched
permanently or released to the control system.
– Fixed: The total power provided by a given switch stage is switched on or
off permanently. This option can be used, for example, for a specific base
load which is required to be present at all times. The command is
implemented with Priority 14.
– Enable: The power actually required from the released switch stage is
determined by local control of the aggregates. The command is
implemented with Priority 16.
For each sequence step, the function block only ever releases the last aggregate
marked Release to the control system. It displays this released object [RlsObj], with
the released object stage [RlsObjSt], at the output. All other aggregates are fixed at
81 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Superposed Plant Controls
the released stage value. If none of the aggregates is marked Release, the
aggregate of the current sequence step is released to the control system.
On/Off switching of When PWR_CTL is switched on [ValPgm = On], the first step in the sequence of
PWR_CTL the current profile is executed immediately. In this case, the switch-on delay is not
valid. If the trigger for default power is on [PwrTrg = On], the aggregate is switched
directly to the default power level [DefPwr].
A switch-off command [ValPgm = Off], disables all the energy producers defined in
the profile table with Priority 14.
Out of service If the PWR_CTL function is taken out of service [OoServ = On], then all referenced
aggregates are switched OFF with Priority 14, without taking account of delay
times. The monitoring of the aggregates is disabled.
Demand signals The current power demand is determined locally in the energy producers. In the
event of a power deficit or surplus, the aggregate will send the appropriate demand
signal to the PWR_CTL block. The demand signal from the aggregate can be
generated, for example, on the basis of the boiler setpoint deviation and the
primary flow. The demand signals of the separate aggregates are combined and
transmitted to the [StepUp] or [StepDn] input of the PWR_CTL block. After expiry of
the relevant delay times, the block executes the appropriate sequence step to
increase or reduce the power, as necessary.
When both [StepUp] and [StepDn] demand signals are present simultaneously,
[StepDn] takes priority.
Direct switching of a load In cases where the power is to be increased or decreased without observing the
delay times, the default-power trigger input [PwrTrg] can be used to switch to a
defined default power level [DefPwr]. From the current profile, and taking account
of the current power output, the PWR_CTL block determines the sequence steps
required to cover the power demand and implements them directly.
Power display The block has two outputs at which it displays the current total power of the energy
producers. This consists firstly of the controlled power output [CtldPwr]. This output
represents the total power switched by the PWR_CTL block.
The other output, the present power output [PrPwr], shows the additional power
output of energy producers that are not directly switched by PWR_CTL. To do this,
PWR_CTL evaluates the priority array [PrioArr] of the MVAL blocks. In this way it
can detect, for example, that an energy producer has been switched manually
[Prio8] to a given stage.
Configuration error The entries in the two configuration tables are checked cyclically for validity.
● A fault alarm is generated under the following circumstances:
● Aggregates no longer accessible from PWR_CTL, owing, for example, to
retrospective modifications to the technical hierarchy, affecting the references
of the energy producers
● Retrospective changes to the stage-limit value in the aggregate, making the
value configured in the profile table too high
● No multistate value object
● Reference block no longer available: For example, deleted with delta download
● Several references to the same block
● Empty profile table
In the event of a fault alarm, all aggregates still accessible by PWR_CTL are
switched OFF permanently.
Alarm management The PWR_CTL block in the system is an alarm-generating block with a
configurable alarm class [AlmCl] and alarm function [AlmFnct].
An Offnormal process alarm is generated:
82 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Superposed Plant Controls
4
● When the step-up demand signal [StepUp] persists for longer than the
monitoring time deviation [TiMonDev], and there are no further sequence steps
to increase the power.
● When the step-up demand signal [StepUp] persists for longer than the
monitoring time deviation [TiMonDev] plus the step-up delay time of the next
sequence step, AND a step-up would cause the maximum power limit [MaxPwr]
to be exceeded.
The process alarm is reset to normal:
● When a sequence step with an increase in power becomes possible again.
Another sequence step with an increase in power becomes possible when the
[MaxPwr] limit will no longer be exceeded, or when a further sequence step
with a power increase is present.
● When there is no further [StepUp] demand signal
The text of process alarms can be defined to suit customer requirements.
Switching alternatives Various switching alternatives can be defined by entries in the profile table. Note
that where one or more step-up sequence steps (intended to increase the power)
would, in practice, result in a drop in the power output, all steps in the step-up
sequence are enabled automatically until a sequence entry is reached, at which
the power output actually does increase as required. See also the following
example.
The power data in the object table and the sequence entries in the profile table in
Figure Example of aggregate table together give the power profile illustrated in
Figure Example of profile entries with a drop in power (Profile 2) .
Profile 1
In the main application of the PWR_CTL function, a new energy producer is added
for each sequence entry in the profile table. For this purpose, an aggregate only
needs to be entered in the sequence table once.
In the event of a power demand, which the boiler transmits to the PWR_CTL
function in the form of the [StepUp] demand signal, a further boiler stage /
sequence step is enabled when the step-up delay has expired. When a boiler
reaches the stage limit, the function switches to the next boiler or boiler stage after
expiry of the switch-on delay. The last-enabled boiler stage is released to local
power control, while all other boilers are fixed at their current power output.
If the power needs to be reduced, this is transmitted to the PWR_CTL function via
the [StepDn] demand signal. The sequence steps are then executed in reverse
order, with the defined switch-off and step-down delay times.
83 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Superposed Plant Controls
Profile 2
Profile 2 shows that the order in which boiler stages are to be enabled has been
changed, and that sequences which will cause a drop in the power output have
been defined in the power profile. In the example illustrated, Boiler 3, which is
currently delivering 200 kW, is switched OFF via sequence entry 2. Boiler 1, which
could achieve a power output of 150 kW with its enabled stages, is defined as the
next object in the sequence. This results in a drop in the power output, causing the
function block to enable all sequence steps automatically until an actual increase in
power is achieved.
In sequence entry 4, Boiler 2 is enabled up to stage 2, giving a further 150 kW
output. Boilers 1 and 2 are thus enabled simultaneously up to stage 2, to prevent a
drop in power. The effective delay time for the simultaneous switching process is
determined the maximum delay time of the boilers concerned. Since it is Boiler 1
which has the longest delay (15 minutes), the simultaneous switching operation will
be delayed for this period of time.
84 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Superposed Plant Controls
4
Online diagnostics A diagnostics screen for the PWR_CTL block is available online in Xworks Plus
(XWP).
85 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Closed-Loop Control Strategy
86 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Closed-Loop Control Strategy
4
Control action The PID_CTR block can be configured as a P, PI or PID controller. The following
parameter settings are used to define the control action:
● Gain [Gain]
● Integral action time [Tn]
● Derivative action time [Tv]
As an option, the gain [Gain] can be influenced with the [GainFac] input. It can be
useful to correct the gain factor in this way when controlling outside air dampers,
for example, as the effect of the damper positions can depend on the outside air
temperature. The correction factor is defined with the gain scheduling block
ADAGAIN.
The actuator runtime can be set. Specifying the actual actuator run-times makes it
possible to tune the controller more accurately to the actuator concerned, so
improving the control quality of the control system.
Correcting range The correcting range is limited by specifying the minimum and maximum output
variable. In this process, the minimum of the two values is always set as the
maximum value. In other words, the maximum value may be below the minimum
value; there is no need to update the minimum value.
Neutral zone [Nz] [Nz] is a zone on either side of the setpoint, within which the controller does not
respond. As soon as the difference between the setpoint [Sp] and the measured
value [Xctl] is less than half of the [Nz], the output is driven for a further 7 cycles,
so that the measured value [Xctl] is as close as possible to the middle of the [Nz].
The output signal [Yctr] then remains constant. The output signal is only re-
adjusted when the parameters move outside the [Nz] again.
87 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Closed-Loop Control Strategy
Tracking [Track] [Track] is used, for example, where the PI(D) controller, operates as a limit
controller, for example, acting on a valve or actuator via an intermediary minimum
or maximum selector block. The tracking input ensures the availability of the
controller during the period in which it is blocked by the minimum or maximum
selector block. During this time, its integrator (and, hence, its output) is maintained
at the value of the signal received, so that if the limit conditions are violated, it is
able to respond immediately. [Track] is also used in conjunction with special
actuators with positioning feedback.
Direct/reverse-acting [Actg] is a characteristic parameter of the controller and indicates the relationship
control action [Actg] between the setpoint deviation and the change in energy flow. A distinction is
made between direct action and indirect [Actg].
● Direct control [Actg]: As the controlled variable rises, the controller output
increases, and as the controlled variable falls, so the controller output
decreases.
Example: Cooling or dehumidification – as the measured value rises above the
setpoint, so the flow of energy is required to increase.
● Indirect control [Actg]: As the controlled variable decreases, the controller
output decreases.
Example: Heating or humidification – as the measured value falls below the
setpoint, so the flow of energy is required to increase.
Inversion [Inv] [Inv] of the output signal is required, for example, for air dampers. The outside air
and exhaust air damper must close in response to an increasing heating demand.
The inversion of the manipulated variable affects only the output signal [Yctr] and
not the action of the controller.
88 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Closed-Loop Control Strategy
4
Sequence controller
Sequence controllers are used primarily in ventilation and air conditioning systems
to control the temperature and humidity. Other applications are also possible, for
example, in heating systems.
Each controlled aggregate functional unit incorporates a universal PID controller
function block, PID_CTR, as a sequence-controller element.
The statements made about the universal PID controller also apply to the use of
the PID_CTR function block as a sequence-controller element.
The sequence-controller elements coordinate their own interaction independently.
Interaction is coordinated with coordination signals [FmHigher] and [ToLower],
which are mutually exchanged by adjacent sequence-controller elements. This is
the only link between the sequence-controller elements. This process allows the
setting of individual parameters for each individual controller or aggregate, and
hence effective optimization of the entire plant.
89 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Closed-Loop Control Strategy
● If all the sequence elements have the same parameter values, the sequence
responds in exactly the same way as a single PI(D) controller whose output
variable is distributed to individual aggregates within the plant.
● The controller output and the integrator of the sequence element is limited in
the range [YctrMin] to [YctrMax]. For this purpose, the high limit of the last
enabled sequence element of the heating and cooling sequence is limited with
an anti-windup strategy (limitation of I/portion on manipulated variable limits).
All other limit values are controlled by straightforward selection of the minimum
or maximum value.
● The rate of change of the output of each sequence element is limited to the
speed of the connected actuator. This helps improve control quality.
● The type of operation of each element (heating/cooling or
humidification/dehumidification) can be selected individually for each element.
● Only one element of the sequence can have a controlling function. When the
output of a controlling sequence element reaches [YctrMin] or [YctrMax],
control is transferred to the nearest adjacent active element ("ON").
Naming convention The term higher is applied to sequence elements that correspond to higher set
points in the sequence diagram (normally cooling or dehumidification).
The term lower is applied to sequence elements that correspond to lower set points
in the sequence diagram (normally heating, energy recovery or humidification).
Configuration of a Essentially, the sequence controller consists of individual PID_CTR blocks. with
sequence controller each PID_CTR block acting as a sequence-controller element for an aggregate.
The PID_CTR blocks are connected (from "Low" to "High") in the same order as
the control sequences (1…n) of the sequence controller. Accordingly, the
connection of the PID_CTR blocks must take account of the intended operating
range (for example, for heating) and the order of switching.
90 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Closed-Loop Control Strategy
4
When the type of operation changes, the neutral zone is defined by the set points
(for example, heating setpoint / cooling setpoint).
Options for connecting The PID_CTR blocks can be connected to form a sequence controller via:
sequence controller ● Direct connection
elements
● SEQLINK connection
Direct connection
The individual PID_CTR blocks are connected directly with each other. The
[ToLower] pins are connected to the [FmHigher] pins, and the [FmLower] pins are
connected to the [ToHigher] pins.
SEQLINK connection
With this method, the individual PID_CTL blocks are connected via the SEQLINK
block. The sequence linker block SEQLINK is a wiring block with no function other
than that of connecting other blocks.
91 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Closed-Loop Control Strategy
The connection is made between the pins of block PID_CTL and a location on the
SEQLINK block. The order in which the PID_CTR blocks are connected must be
the same as that of the sequence. The connections to the SEQLINK block need
not be continuous: connected pins and unused pins may be interspersed.
For example, 1 = Re-heater, 2 = Pre-heater, 3 = Dampers, 6 = Cooling coil.
Figure 65: Example: Output from elements 4 and 6 [TknSta] = HEL_CSEQ Output from elements 3 and
5 [TknSta] = CEL_HSEQ
92 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Closed-Loop Control Strategy
4
Cascade control
The CAS_CTR block integrated into the Desigo system is a PI master controller for
room supply air cascade control. It delivers three supply air set points on the basis
of the difference between the measured room temperature and the room setpoint.
Compared with control without a cascade, for example, cascade control improves
the dynamics of the control process.
If the temperature in a ventilated room is below the setpoint, for example, the
supply air temperature must be increased, at least for a brief period, in order to
raise the temperature to the room setpoint. This can be achieved by measuring
and controlling not only the room temperature, (that is, the value which actually
concerns the user), but also the supply air temperature, whose setpoint depends
on the difference between the room setpoint and the room temperature.
If the room temperature is lower than the room setpoint, the supply air setpoint is
adjusted in proportion to the room control differential, and the supply air
temperature is increased via the supply air control loop.
The master controller generates the setpoint for the auxiliary variable (for example,
the supply air temperature) on the basis of the difference between the primary
setpoint and the primary controlled variable (for example, the room setpoint and
the room temperature).
The master controller must include an integrator function (I component), because
even under static conditions (that is, when the measured value and the setpoint are
equal) there is generally a negligible control deviation, which means that the
controller output must be at a different operating point. For improved control
dynamics, a P-component should be connected in parallel with the integrator. This
is why the master controller in this case has a PI control structure.
93 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Closed-Loop Control Strategy
Even when the primary controlled variable (room temperature) is identical to its
setpoint, the auxiliary controlled variable (supply air temperature) must generally
be at a value other than 0, (that is, setpoint ≠ 0). This is only possible if the output
of the master controller is not equal to 0, even if the P component = 0. In other
words, the master controller must have an I-component which remains constant
when the control differential = 0. This is why the master controller has a
proportional and an integral component. It is a numerical PI controller for use as a
master controller in a room/supply air cascade.
To save energy in the ventilation plant, various room set points are selected for
different types of air handling (heating/cooling and humidification/dehumidification).
The master controller in the cascade must therefore be able to generate different
supply air set points, depending on how the kind of air treatment (heating/cooling
or humidification/dehumidification).
The supply air controller must determine whether the heating or cooling sequence
is to be activated and the decision-making strategy does not affect the calculation
of the two supply air set points. Within the cascade control loop, the supply air set
points always move parallel to each other, and their offset is determined by the
integral component.
If the air handling plant includes an energy recovery aggregate, this aggregate may
be either reverse-acting (for example, heating) or direct-acting (for example,
cooling) depending on the relationship between the condition of the outside air and
the condition of the exhaust air.
To avoid external calculation of the energy recovery setpoint, this, too, is done by
the master cascade controller, and made available to the energy recovery
aggregate, if there is one, at a separate output pin:
In a humidity control system with various physical control variables, the initial value
of the integrator should be predefined.
Example:
If the humidity of the supply air is measured with an absolute humidity value [g/kg],
while the room air humidity is measured in terms of relative humidity [%Hu], an
initial value must be defined for the I-component, otherwise the mean value from
[SpLoR] and [SpHiR] will be used as the initial value. If the room set points are
expressed in terms of relative humidity, then the initial value for the integrator will
start at a numerically high value, and decrease as a function of the preset integral
action time [Tn]. The result of this can be that even if the room needs to be
dehumidified, the humidifier is enabled in the controller start-up phase until the
integrator reaches its correct value.
94 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Desigo Room Automation
4
To prevent this, the current measured supply air humidity value is linked to the
initial value of the integrator, or a fixed parameter value is defined for the integrator.
If control accuracy is critical (for example, no deadband or zero-energy control
zone), then the current measured value is linked to the initial value of the integrator,
or a fixed parameter value is defined for the integrator.
3 3
2
1
Figure 71: Room application sample with different mechanical and electrical installations
HVAC zone The room typically is considered 1 HVAC zone influenced via a common
automation and control strategy regardless of number and type of installed HVAC
plant components (for example, radiator, chilled ceiling, fan coil unit).
Lighting zone All lamps operated/automated together are grouped into a lighting zone regardless
of number and type of the installed lamps. A room typically has one or several
lighting zones.
Shading zone All shading products (blinds) operated/automated together are grouped into a
shading zone regardless of number and type of the installed shading products. A
room typically has one or several shading zones.
95 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Desigo Room Automation
96 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Desigo Room Automation
4
Thermal room load Room coordination supports room temperature control via blinds control. The
analysis various HVAC data is analyzed to determine the thermal room load and the
associated signal definition for blinds control:
● Load if energy must be supplied to the room via the blinds position
● Unload if no additional energy must be supplied to the room via the blinds
position
Blinds control determines the optimal blinds position in dependence of room
occupancy and solar position (thermal radiation and glare).
Green Leaf Manual room user manipulations (for example, manual lighting and shading
(RoomOptiControl) commands, or manual changes to the room temperature setpoint) can result in
inefficient energy operation. Each zone and each technical installation is checked
for inefficient definitions to be pointed out to the room user. Room coordination
then summarizes the results and visualizes them on the room operator unit. The
room user can then reset all manual entries (which lead to inefficient plant
operation) by one single pressure of a button.
Room common alarm One common alarm is set up for each room to keep down the number of set up
system alarms. To this end, room coordination acquires status information
(normal/alarm) for each zone and each technical installation, and determines the
room-wide alarm state as a common alarm.
Figure 73: Examples for HVAC plant families in a room: radiators (right), Fan coil units (center), VAV
(left)
97 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Desigo Room Automation
HVAC supply chain HVAC plants in a room consume energy. The supply chains outside the room
requirements supply air, water, or electricity to the room. Linked existing energy sources and
consumers are called supply chain. An air supply chain or a water supply chain
thus is an HVAC system with a supply/consumer relationship to the HVAC plant in
the room.
The supply equipment typically supplies more than one room, and the HVAC plant
in the room often is a consumer of multiple supply chains.
HVAC control basically has the same objectives as the entire HVAC plant:
● Maintain the room temperature in the selected comfort range
● Adapt the room temperature range to room user needs
● Supply, extract, and recirculated air to satisfy air quality and comfort needs
● Adapt the air flows to room user needs
Energy saving requirements:
● Devices for sequential control of a heating and cooling sequence and thus:
– Preventing sequence overlap (simultaneous heating and cooling)
– Using the most efficient energy source
● Reducing the temperature as soon as comfort mode no longer is needed
● Reducing ventilation as soon as it is no longer needed
Coordination of the HVAC supply chain:
● Operation of supply chain equipment as per user demand
● Optimization of operating levels (temperature, pressure) of the supply plant
● Prevention of damages to HVAC equipment
HVAC control structure An HVAC control application in the room is connected to the following:
● HVAC plant in the room via sensors and actuators
● Room coordination application
● Centralized coordination application for HVAC supply chain(s)
● Building operator via BAC workstations
● Building automation and control functions for scheduling
● Room user
98 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Desigo Room Automation
4
Supply Chain
Room Coordination
Functions
User Request
WndCont PscDet
99 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Desigo Room Automation
100%
0% TREff
Speed 3
Speed 2
Speed 1
FanSpdMin=Off TREff
SpH SpC
AND AND
Max
100 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Desigo Room Automation
4
Operating modes The HVAC plants in the room adapt to the room's comfort requirements. For
example, ventilation is:
Active while the room is occupied
Off, as soon as the room no longer is occupied
The following illustrations show sequence control for an HVAC plant in the room for
operating modes Comfort and Economy. Sequence control acts on heating and
cooling equipment and a multi-speed fan.
Plant operating mode Comfort
100%
VlvPos VlvPos
0% TREff
HclHw01 CclChw01
AirFlReqHeat AirFlReqCool
Speed 3
Speed 2
FanSpd
Speed 1
FanSpdMin=Off TREff
FanMultiSpd01
SpH SpC
100%
VlvPos VlvPos
0%
HclHw01 CclChw01
AirFlReqHeat AirFlReqCool
Speed 3
Speed 2
FanSpd
Speed 1
FanSpdMin=Off TREff
FanMultiSpd01
SpH SpC
The available operating modes determine both operation and basic control strategy
in the automation and control system at three different levels:
● The room operating modes determine the operation of HVAC equipment in a
room in terms of current use by the user. The room operating modes defined
for the room are available in all HVAC control applications in the room.
● The HVAC plant operating modes determine the operation the HVAC plant in
the room with regard to existing, physical plant processes. The HVAC plant
operating modes are defined specifically for 1 HVAC plant in the room.
● The device operating modes determine the operation of the HVAC devices in a
room by predefining their tasks and implementation method. The device
operating modes are defined specifically for each individual HVAC device.
The following table shows the plant and device operating modes of a plant with
heating coil, cooling coil, and fan. Project-specific adaptations of both plant and
device operating modes can be implemented by adapting the operating mode table.
101 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Desigo Room Automation
Plant operating mode Fan operating mode Heating coil operating mode Cooling coil operating mode
Off Off Off Off
In addition, setpoints and setpoint limits define room and device operating modes.
They can vary depending on the selected HVAC plant operating mode. Four
different setpoints are provided for heating and cooling in the room.
SpC
SpH
t
RClmOpMod Eco Cmf Eco
00:00 06:00 18: 00 24:00
Figure 81: Setpoints for room heating and cooling
The HVAC control applications in the room dynamically enable and disable the
setpoints to achieve the desired combination of energy-saving Economy and
demand-based Comfort operating mode.
Command priorities An HVAC control application simultaneously achieves several goals. Functions
with different objects may conflict when they are implemented. In this case, the
command priority determines which command value has priority in the priority array
of the BACnet objects.
HVAC control applications in a room are programmed to accept commands at
many different levels, including operating mode variable level. As a result, HVAC
control applications control the controlled output objects at a priority commensurate
with the active priority of the operating mode variable. The following figure shows
how commands and priorities are passed in the application.
102 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Desigo Room Automation
4
Fire Detector
16 15 14 13 ... 8 7 6 5 4 3 2 1 RClmOpMod
FcuPltMod01
Off
C ... 8 7 6 5 4 3 2 1
16 15 14 13 PltOpMod
The BACnet objects in the system support 16 priority levels. The HVAC control
applications apply these levels as follows:
Emergency mode 2 Automatic commands related to personal safety Propagated response to Emergency
mode commands
Protection mode 5 Automatic commands to avoid damage to equipment Programmed response to equipment
safety conditions
Automatic control 9 Unassigned - commands for comfort and energy conservation None
Automatic control 10 Unassigned - commands for comfort and energy conservation None
Automatic control 11 Unassigned - commands for comfort and energy conservation None
Automatic control 12 Unassigned - commands for comfort and energy conservation None
103 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Desigo Room Automation
Automatic control 14 Unassigned - commands for comfort and energy conservation None
Automatic control 15 Typical automatic commands for comfort and energy Typical automatic commands
conservation
Automatic control 16 Unassigned - commands for comfort and energy conservation None
Adaptation to another An HVAC control application comprises several different members of an HVAC
HVAC plant room family. It contains application-specific components (CFC) matching existing
HVAC devices in the room. Components no longer matching existing HVAC
devices in the room are either added, removed, or replaced to control a slightly
different HVAC plant with different HVAC devices.
Room HVAC Plant Room
TEx
TR
TSu
FanMulti01 HclHw01 CclChw01
TOa
DmpOa01 Fan1Spd01 HclHw02 CclChw02
FanVarSpd01 HclEl01
Often, more must be done than merely adding or removing components (CFCs). If,
an HVAC device, for example, is to be added, the following must be added or
removed:
● Information in the operating mode table
● Corresponding BACnet objects to operate the new device
Shading control
Products and Suitable façade products and intelligent control allow for optimum satisfaction of
requirements various requirements for shading.
Façade products and their control required to protect against environmental
influences or to make use of the same are the primary issue:
● Shading to protect against glare
● Using daylight
104 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Desigo Room Automation
4
Influences on blinds Blinds control requires much information on environmental influences and user
control interactions to be able to best satisfy requirements.
The blinds control can be influenced by, for example:
● Smoke, fire alarm
● Maintenance switch
● Wind, rain, humidity, temperature
● Intrusion alarm
● Date/Time
● Solar radiation
● Geographical position
● Horizon limitation
105 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Desigo Room Automation
● Presence detector
● Local operator
● Saving and retrieving scenes
● Central operation (operation, scenes, override)
● Desigo CC
● Commissioning/Test
Blinds position on a building, room purpose, and allocation of rooms to an
organizational unit determine the type of information acting on blinds control.
Example:
● Wind speed monitoring acts on all blinds of a building or building wing
● Automatic shading acts on all blinds of façade or part of a facade
● A scheduler program acts on all rooms of a renter
● Local manual operation acts on all blinds of a room, or on a single blind
Color key:
● Gray: Complete building
● Blue: Façade or part of a facade
● Green: Rooms of a renter, for example, one floor
● Orange, red: Local, manual operation
The functions are grouped into local and central functions depending on whether
the function acts on one or multiple blinds in a room, or on an entire group of blinds,
for example, on all blinds of a facade. The following table shows the grouping by
local and central functions for the examples from the figure above.
Local manual operation Automatic shading Wind speed monitoring Scheduler program
Central function n/a Determination of optimal Measuring of wind speed Commanding of a position
shading position in Monitoring of wind speed in dependence of daytime
dependence of sun
position Commanding of wind
protection position
Local function Commanding of manual Decision on which position Positioning of blinds Positioning of blinds
position is commanded
Positioning of blinds automatically
Positioning of blinds
106 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Desigo Room Automation
4
Function Description
Automatic shading Automatic determination of optimum blinds position based on current room use, solar
radiation, outdoor brightness, solar position, and HVAC status. In simple terms, this
function prevents glare in occupied rooms and uses solar energy for heating in
unoccupied rooms, or protects the building against undesired heat-up.
Manual operation (room, central) Manual operation allows users to themselves determine the blinds position via buttons. If
manual operation overrides a lower-priority function, a scheduler program or local
presence information will reactivate the function.
Presence-based influence Locking of automatic operation upon entering a room, and activation of automatic
(room) operation upon leaving a room. The presence-based function generally acts on the same
priority as manual operation.
Scheduler program A scheduler program opens, closes blinds at specific times, or commands them to a
specific shading position. Furthermore, automatic operation can be activated or
deactivated via scheduler program. Another priority may need to be commanded
depending on purpose. If, for example, automatic operation should be activated at noon,
manual operation must be overridden by allowing the scheduler program to act on the
priority for manual operation. If the blinds are to be closed at night without allowing for
manual operation, a higher priority must be commanded.
Automatic shading at high priority For example, to prevent overheating it may be necessary to use automatic shading at
higher priority, which limits or prevents manual operation in certain situations.
Manual operation at high priority Manual operation at high priority allows for positioning blinds and overriding low-priority
(room, central) functions. For example, local operation can be overridden during, for example, a
presentation. Or it can be ensured that neither automatic shading nor a scheduler will
drive the blinds up or down at an undesired time.
Product protection, local Risks impacting a blind only, for example, protection against collision with a service door
opening outward, are included in local product protection.
Product protection, central Environmental influences impacting a group of blinds are included in the central functions
for product protection. A common function in this category is protection of blinds against
damage from strong winds.
Maintenance position, central For maintenance or cleaning, blinds are commanded or blocked to a specific position at
high priority enabling staff to carry out all required work without risking injury due to
moving blinds.
Protection, central Blinds can be moved/driven up to provide escape or access routes for emergency
personnel in the event of a fire.
A very simple control contains just one or two functions; a complex plant may use
many or all available functions. In addition, the response of individual functions
may require parameterization depending on the requirements. The following figure
shows an example of a plant including all functions.
107 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Desigo Room Automation
Maintenance position
(blinds maintenance, window cleaning)
Product protection local (avoiding
collisions)
Product protection central
(wind, rain, frost)
Selection of priority
(button)
Execute
Manual operation at high priority (btton,
resulting drive
management station)
command
Scheduler program
Manual operation
(button, management station)
Presence-induced activation/
deactivation of automatic mode
Lighting control
Products and Suitable lighting products and intelligent control allow for optimum satisfaction of
requirements various requirements.
Lighting products and their control are the primary means to create optimum
lighting conditions for building users:
● Optimum workspace conditions (bright or darkened rooms)
● Optimum lecturing/teaching conditions (presentation)
● Comfort in living spaces
● Mood lighting in entertainment spaces (restaurants, bars, etc.)
Other requirements may be:
● Energy savings
● Lighting of objects, products
● Façade lighting
● Intrusion protection
Lighting products control in addition must ensure the safety of persons. Examples:
● Switching on lights in case of fire
● Escape route lighting
A multitude of different lamps exists to satisfy the various needs, such as:
● Incandescent light bulbs
● Halogen lamps
● Fluorescent tube lamps
● Compact fluorescent tube lamps
108 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Desigo Room Automation
4
109 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
4 Desigo Room Automation
The functions are grouped into local and central functions depending on whether
the function acts on one or multiple lamps in a room, or on an entire group of lamps,
for example, on all lamps of a renter. The following table shows grouping by local
and central functions for the examples from the figure above.
Local function Commanding of manual brightness Switching on lighting Switch on/off lighting
Adapting lighting
Function Description
Automatic control Automatic switch-on/switch-off based on brightness, constant lighting control.
In simply terms, this function achieves optimum lighting conditions automatically in
occupied rooms, and switches off lighting when rooms are unoccupied.
Manual operation (room, central) Manual operation allows users to themselves determine brightness via buttons. If manual
operation overrides a lower-priority function, a scheduler program or local presence
information will reactivate the function.
Presence-based influence (room) Automatic switch-on when dark upon entering a room, and automatic switch-off when
leaving a room. The presence-based function generally acts on the same priority as
manual operation.
Scheduler program Lighting can be switched on/off at specific times using a scheduler program. Furthermore,
automatic control can be activated or deactivated via scheduler program. Another priority
may need to be commanded depending on purpose. If, for example, automatic control
should be activated at noon, manual operation must be overridden by allowing the
scheduler program to act on the priority for manual operation. If lighting is to be switched
off at night without allowing for manual operation, a higher priority must be commanded.
Manual operation at high priority (room, Manual operation at high priority allows for influencing lighting blinds and overriding low-
central) priority functions. For example, this function allows for ensuring that neither motion
detectors nor scheduler programs can switch on/off lighting at the wrong time during a
lecture/presentation.
Maintenance, central For maintenance or cleaning, lighting is switched on/off at high priority enabling staff to
carry out all required work without risk of injury or being interrupted.
Protection, central Lighting can be switched on in the event of a fire alarm to light escape routes or support
emergency crew access.
A very simple control contains just one or two functions, A complex plant may use
many or all available functions. In addition, the response of individual functions
may require parameterization depending on the requirements. The following figure
shows an example of a plant including all functions.
110 | 377
Siemens CM110664en_03
2017-09-18
Control Concept
Desigo Room Automation
4
Maintenance
Selection of priority
(button)
Execution of
Manual operation at high priority (button, resulting lighting
management station) command
Scheduler program
Manual operation
(button, management station)
Presence-induced influence
Automatic control
111 | 377
Siemens CM110664en_03
2017-09-18
Technical View
5 Standard Plant Structures
5 Technical View
The technical view illustrates the technical building services equipment, such as
HVAC systems and associated elements, in the building automation and control
system.
Area Gubelstrasse
Burner
Sensor
KNG:ABdb6'AHU3Fl'FanSu
The technical view helps organize measured and controlled physical variables from
specific, technical installations in a building. The technical view is modeled with
structure objects. The structure of the technical view represents the hierarchy of
the technical installations. Objects representing variables, such as setpoints or
operating modes supplement the view.
Plant types The technical view contains all the conceptual objects in the system. The following
plant types have been defined for descriptions and categories:
● Primary plant: All physical plants that are directly controlled from the
automation level, for example, heating systems, ventilation systems, etc.
● Room automation: Individual room controls.
● Global objects: Data objects which exist simultaneously in several automation
stations at the automation level, for example, an exception calendar for the
time schedules of all plants. These objects are combined as a virtual plant in a
global area and can be invoked as such (global data).
The technical view can be used for other disciplines integrated via PX Open. The
technical view and the associated technical designations can be set up in the
compounds library.
112 | 377
Siemens CM110664en_03
2017-09-18
Technical View
Standard Plant Structures
5
Plant
Partial plant,
Aggregate,
Component
Total max. 6
recursions (max. 7
levels)
Figure 91: Structure for primary plants
Elements Site: A site is a self-contained area in terms of location, function and organization,
usually a building or a group of buildings (facility). A site can comprise several
plants. Example: Building 6
Plant: A plant consists of partial plants, aggregates and components. A plant can
comprise several partial plants. Aggregates and components can be directly
subordinate to a plant. Example: Ventilation system, heating system
Partial plant: A partial plant can comprise various aggregates. Components can be
directly subordinate to a partial plant. Example: Central supply air treatment, air
distribution, hot water supply (one or more boilers)
Aggregate: An aggregate can comprise various components. Example: Exhaust air
fan
Component: A component can comprise several components, which can comprise
several components themselves. Example: Pumps (motors), dampers, valves,
sensors, detectors, limit switches, contactors, selector switches, remote/local
switches
Engineering model BACnet/System model
Site Site
1
n n
Element type:
Hierarchy element Hierarchy object Element type:
auxil. element
plant
plant (primary) Element type area
area CFC Editor: Compound
subarea
subarea
section
section Element type
1 1 Structured view object
Total max. 6 Element type
Assignable to PX recursions
(nesting)
n n
Element type:
Function element Block object Element type:
auxil. element
partial plant
partial plant Element type
CFC Editor: Compound aggregate
aggregate
Function block component
component
Function room
room
Element type Standard BACnet object
1 Element type
Element type: auxiliary element, plant, partial plant, aggregate, component, area, subarea, section, room
113 | 377
Siemens CM110664en_03
2017-09-18
Technical View
5 Standard Plant Structures
Global objects
Structure
Site
Global area
Component
Elements Site: A site is a self-contained area in terms of location, function and organization,
usually a building or a group of buildings (facility). Example: Building 6
Global area: The global area contains all the global components of the site. There
is one global area per site.
Global objects are data objects which exist simultaneously in several automation
stations at the automation level, for example, an exception calendar for the time
schedules of all plants. These objects are combined as a virtual system in a global
area and can be invoked as such.
Component: A global area may contain several components, such as 3 calendars,
18 notification classes for alarm distribution. Each component is present on all
automation stations of the site. For operation, however, each component is visible
only once.
114 | 377
Siemens CM110664en_03
2017-09-18
Technical View
Standard Plant Structures
5
Area, Subarea,
Section
Room
Elements Site: A site is a self-contained area in terms of location, function and organization,
usually a building or a group of buildings (facility). A site can comprise several
plants. Example: Building 6
Area: An area is typically a building, and can comprise subareas, sections,
components and subcomponents. Example: Building
Subarea: A subarea is typically the wing of a building and can comprise several
sections. Rooms can be directly subordinate to a subarea. Example: Building wing,
staircase
Section: A section is typically a floor in a building and can contain various rooms.
Example: Floor
Software objects, which need to be displayed and operated even though they do
not exist as physical elements in a real building, are also treated both as sections
(for example, via grouping criteria, such as east facade or emergency group 12)
and as components (for example, group object for distribution of centrally
determined control variables to several rooms).
Room: A room is a section of a building that is delimited by walls, ceilings, floors,
windows and doors. Example: Individual room, hall
115 | 377
Siemens CM110664en_03
2017-09-18
Technical View
5 Standard Plant Structures
Building
Floor
Room
Room segment
Functional unit
Component
Figure 96: Structure for room automation with Desigo Room Automation
116 | 377
Siemens CM110664en_03
2017-09-18
Technical View
Technical Text Labels
5
117 | 377
Siemens CM110664en_03
2017-09-18
Technical View
5 Technical Text Labels
Item Rule
Address structure Comprises at least one hierarchical object and one function object
Has a variable length (site + 1..8 hierarchy and function objects + pin name)
Is independent of the automation station, that is, does not contain a designation for an
automation station
Must be unique for each site
Syntax Site designation Consists of upper and lower case letters, and numbers (must start with a letter): [a..z,
A..Z, 0..9].
Is case insensitive, for example, Imax and IMAx are treated the same.
Other partial designations Consist of upper and lower case letters ([A..Z] and [a..z]) and/or numbers 0 to 9.
Is case insensitive, for example, Imax and IMAx are treated the same.
Function block attributes The main attributes of the function block are:
● Name: Name of the function block based on the key of the TD. Example:
ThOvrld
● Description: Additional description. For generic operation it is shown as text in
an operator unit. Example: Thermoelectrical ovrld
● Element type: Block in plant-engineering terms. Example: Component
● Main value: Main value of the function block. It is set during engineering.
Example: PrVal
118 | 377
Siemens CM110664en_03
2017-09-18
Technical View
Technical Text Labels
5
119 | 377
Siemens CM110664en_03
2017-09-18
Global Objects and Functions
6 Ensuring Data Consistency
120 | 377
Siemens CM110664en_03
2017-09-18
Global Objects and Functions
Roles in the System
6
Xworks Plus (XWP) and all BACnet clients can only modify the data of global
objects in the primary server.
Life check The primary server monitors the backup servers and the third-party BACnet devices of a site.
The primary server can monitor the Desigo Room Automation server.
Time synchronization The primary server synchronizes the time of the backup servers and the third-party BACnet devices of
the site.
The primary server can synchronize the Desigo Room Automation server time.
Replication The primary server replicates the global objects and properties (device object) to the backup servers
of a site. A backup server accepts changes of global objects only from the primary server.
Life check The backup servers monitor the primary server of the site.
Backup servers can monitor Desigo Room Automation servers.
Time synchronization The backup server can synchronize the time of the Desigo Room Automation server and of the third-
party BACnet devices.
121 | 377
Siemens CM110664en_03
2017-09-18
Global Objects and Functions
6 Life Check
Life check The Desigo Room Automation server / third-party BACnet device is monitored by the primary server or
the backup server.
Table 28: The role of the Desigo Room Automation server and third-party BACnet device
122 | 377
Siemens CM110664en_03
2017-09-18
Global Objects and Functions
Time Synchronization
6
Add and delete devices For life check and replication the primary server has a list [BckUpSrv] of all known
devices of a site. The primary server automatically adds newly commissioned
devices on the site to this list. Devices which are removed from the site must be
deleted manually in Xworks Plus (XWP) from the list in the primary server.
Check if all devices are The primary server performs a life check at regular intervals, to check that all
online devices of its site are online. The interval between life checks is defined by the
synchronization request period [SynReqp]. During this period, the backup servers
are checked one after the other in a cyclical process. The interval between two life
checks can be calculated as follows: t ≈ SynReqp / Number of backup servers .
A short synchronization request period and a large number of backup servers may
involve a substantial communications load. Take this into account when setting the
synchronization request period in Xworks Plus (XWP).
If one or more devices are not online, the primary server generates an alarm signal.
The alarm is reset as soon as all devices are online again and have been detected
by the primary server. This ensures that problems, such as the failure of a device,
the termination of the HVAC-application processing of a device, or faulty
configuration (for example, two primary servers in one site) are detected.
Monitor if the life check Each backup server monitors its own periodic life check by the primary server. If a
checks the backup server life check fails, or if no primary server has ever carried out any life checks on this
backup server, the backup server generates an alarm. The backup server resets
the alarm as soon as the primary server carries out a life check.
123 | 377
Siemens CM110664en_03
2017-09-18
Global Objects and Functions
6 Examples of Global Objects
The primary server transmits the time in UTC format (Coordinated Universal Time)
to the other automation stations (backup servers) and in UTC format or local time
format to the third-party BACnet devices.
The backup server then triggers time synchronization of its recipients configured in
Xworks Plus (Desigo Room Automation server, third-party server, third-party
BACnet devices). This can be in either UTC or local time format.
Periodic synchronization The time synchronization interval is defined in the property
TimeSynchronizationInterval [TiSynIvl] (default value: 150 minutes). The property
can be configured in Xworks Plus (XWP) and adapted to the specific situation via a
switchable [AlgnIvl] offset [IvlOfs]. How these three properties function is defined in
the BACnet standard and implemented accordingly.
Add and delete devices For time synchronization, the primary server has a list [TiSynRcp] containing the
recipients configured in Xworks Plus (XWP) and all known backup servers of its
site.
The primary server automatically adds newly commissioned backup servers on the
site to the list [TiSynRcp].
Backup servers which are removed from the site must be removed manually from
the primary server list in Xworks Plus (XWP).
Link the system time of a The network-capable operator units do not belong to a site. The primary server
site with operator units does not update the time in the operator units. The client can read and update the
time, if required.
Daylight saving time The daylight saving time changeover does NOT take place in the primary server.
changeover Each automation station makes this switch independently.
The date of the daylight saving changeover is set as a parameter in the primary
server. The primary server replicates the date on the backup server. The official
(Central European) changeover date is set as default.
The local time in an automation station is a calculated variable. The calculation is
based on the internal time in UTC format, the property UTC offset [UtcOfs] and the
date of the summer and winter time changeover.
See Desigo CC User Guide (A6V10415471).
124 | 377
Siemens CM110664en_03
2017-09-18
Global Objects and Functions
Examples of Global Objects
6
Periodic repetition for the resolution of references across devices. Default value:
900 s.
● COV resubscription interval [CovRI]
Time within which the automation station resubscribes to a subscribed value.
Default value: 1800 s.
Local properties Local properties which refer to the functionality of the life check / replication:
● Server type [SvrTyp]
Defines if the device acts as a primary server or a backup server. Default:
backup.
● Primary device [PrimDev]
Device object ID of the primary server of the site or an invalid value if the
primary server is not known (read-only, set automatically by the primary server).
● Last engineering time, global object [GOEngTi]
Time stamp of the last structure modification of the global objects by Xworks
Plus (XWP).
● Last online modification of global objects [GOChgTi]
Time stamp of the last online modification of a global object in Xworks Plus
(XWP) (modified by the primary server, read-only).
Locked Locked
Reset Reset Reset
DESIGO PX
125 | 377
Siemens CM110664en_03
2017-09-18
Global Objects and Functions
6 Examples of Global Objects
Local Notification Class Object: Individual object (unique object) that exists only on
a particular automation station.
Reading of objects by a client: A client may read the global notification class
objects from any automation station.
Reasons for replication: Keeping the setting parameters consistent for all
automation stations of a site when modifications occur (adding or deleting
configured recipients from recipient list, changing priorities).
Desigo CC PXM20
10664Z05en_07
The number of global Notification Class objects is limited to 18 (six alarm classes
each with three possible alarm functions).
Calendar object
There are global and local calendar objects.
126 | 377
Siemens CM110664en_03
2017-09-18
Global Objects and Functions
Examples of Global Objects
6
Desigo CC
10664Z06en_07
Global calendar object: A logical object at site level. It exists in identical form (as a
replicated object) on each automation station of a site.
Local calendar object: Individual (unique) object that exists only on a particular
automation station.
Local processing: Schedule objects in an automation station may reference the
replicated calendar objects in the device. A client may read the global calendar
objects from any automation station.
Reasons for replication: Global exceptions (bank holidays, general holidays, etc.)
can be modified centrally in one location for the entire site. Ensures continuity of
operation if the master fails.
127 | 377
Siemens CM110664en_03
2017-09-18
Global Objects and Functions
6 Examples of Global Objects
Desigo CC
10664Z07en_07
128 | 377
Siemens CM110664en_03
2017-09-18
Events and COV Reporting
Sources and Causes of System Events
7
BACnet Device Info Object The BACnet Device Info Object detects the causes of system events which apply to the automation
station as a whole. The following causes are detected:
- Change of operating state (start and stop the program)
- Restart after a power-up
- Primary server has found a new backup server on the network
- Backup server has found the primary server
129 | 377
Siemens CM110664en_03
2017-09-18
Events and COV Reporting
7 Routing System Events
SimpleAck
SimpleAck
t t t
Event texts Each system event has a message text assigned to it. For the system events
related to the operating hours counter, a user-specific text can be set up in Xworks
Plus (XWP). Predefined system texts are available for the other system events.
130 | 377
Siemens CM110664en_03
2017-09-18
Events and COV Reporting
COV Reporting
7
COV notifications The COV server reports every COV individually to each COV client which has
subscribed to it. The BACnet service ConfirmedCOVNotification is used for this
purpose. It contains the values of [PrVal] and [StaFlg]. The service is a Confirmed
Service, which means that the COV client must acknowledge the notification
(SimpleAck). This ensures that when a COV client ceases to be available, this will
be recognized by the COV server. If no SimpleAck message is received, the
transmitting device tries to send the information again (three times).
For system limits, see chapter System Configuration.
Connection terminated If a COV client cannot be contacted, the COV server ceases to send COV
notifications to that client. The transmission of COV notifications to a COV client is
resumed when the COV client re-subscribes.
Checking the connection To ensure that the COV service is maintained over a long period, a maximum time
period without COV reporting can be set in the BACnet Device Info Object via the
BACnet property COV Resubscription Interval [CovRI]. The client must subscribe
with SubscribeCOV again before [CovRI] expires.
COV clients and COV Desigo CC
servers COV
Client
Automation level
COV
Client PXM20
Block A Block Z
COV
Client
COV
Server
Block V
COV
10664Z46en_07
Server Block B Block Q
The local PXM10 operator unit is not a BACnet client and cannot, therefore, be
used as a COV client.
See PXM10 operator unit: User's guide (CM110397).
131 | 377
Siemens CM110664en_03
2017-09-18
Events and COV Reporting
7 COV Reporting
SimpleAck
ation
COVNotific
Co irmed
nf
SimpleAck
cation
COVNotifi
Confirmed
SimpleAck
t t
Figure 109: COV reporting between COV client and COV server
The BACnet client subscribes to the COV server as a COV client using the BACnet
service SubscribeCOV. The server sends a SimpleAck acknowledgement.
Immediately after the acknowledgement, the COV server transmits an initial
ConfirmedCOVNotification. The COV client acknowledges receipt of the value with
a SimpleAck acknowledgement. The COV connection between the COV server
and COV client is now established, and ConfirmedCOVNotifications are sent
whenever a trigger for the subscribed COV occurs.
The BACnet service SubscribeCOV includes a time limit for the COV connection.
However, the COV client re-registers with the COV server before this limit expires,
thus ensuring that the connection is maintained. A COV connection ends when the
subscription period expires and is not renewed, or when the COV client can no
longer be contacted, causing the COV server to stop sending notifications.
In addition to the SubscribeCOV service, a SubscribeCOV Property service is
implemented, for example, for the operation of plant graphics in Desigo CC. This
enables the system to respond with appropriate speed to changes in the high or
low limit.
SimpleAck
ation
COVNotific
Confirmed
SimpleAck
ation
COVNotific
Confirmed
SimpleAck
t t
132 | 377
Siemens CM110664en_03
2017-09-18
Events and COV Reporting
COV Reporting
7
When an automation station connects, the BACnet service WhoHas searches the
entire network for the object referred to in the COV client. The automation station
concerned responds to the COV client with the BACnet service IHave. If the COV
client cannot find the COV server, it repeats the WhoHas request after the time
period defined in the BACnet Device Info Object Property Name resolution interval
[NamRI] until the COV server is found.
The COV client registers for a limited period as a COV client with the COV server
using the BACnet service SubscribeCOV. The server sends a SimpleAck
acknowledgement. The value is then sent to the COV client for the first time by the
COV server, using the BACnet service ConfirmedCOVNotification. The COV client
acknowledges receipt of the value with a SimpleAck acknowledgement. The COV
connection between the COV server and the COV client is established from this
point on. According to the global property COV renewal interval CovRI of the
BACnet Device Info Object, the COVsubscription is renewed. The lifetime used for
SubcribeCOV is twice the COV renewal interval CovRI. The COV connection ends
when the subscription period expires and is not renewed, or when the COV client
can no longer be contacted, causing the COV server to stop sending notifications.
133 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Sources
8 Alarm Management
Alarms indicate faults in the HVAC plant and building automation and control
system, and let you initiate corrective action, where appropriate. The management
of alarms (generation, signaling, acknowledgement) is in compliance with the
BACnet standard.
There are two alarm types:
● OFFNORMAL
● FAULT
OFFNORMAL OFFNORMAL alarms (process alarms) occur when a process variable assumes an
inadmissible value. What is inadmissible is determined during engineering. The
relevant parameters are stored in all alarm-generating objects. An OFFNORMAL
alarm always indicates a fault in a plant, while the automation system itself works
properly.
Examples of OFFNORMAL alarms:
● Temperature in HTHW circuit is too high or too low
● Alarm generated by fire detection system
● A damper-motor feedback signal has not been received
● A time schedule cannot execute a command
FAULT FAULT alarms are faults in the automation system itself (internal alarms). You
cannot define the cause of a FAULT alarm during engineering. Nor is it possible for
the user to suppress or otherwise influence the monitoring of FAULT alarms.
FAULT alarms are intrinsically linked to the system. A FAULT alarm always takes
precedence over an OFFNORMAL alarm from the same alarm source, because in
the case of a FAULT alarm, there is some uncertainty about the reliability of the
alarm source.
Examples of FAULT alarms:
● Faulty sensor (open circuit, short circuit, etc.)
● Buffer for storage of non-volatile data full
● Access to an I/O module failed
● Bus open circuit (RX integration)
134 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Sources
8
1 Discipline I/Os, Groups, Time Scheduler and Trend Log Multiple support only system alarms, that
is, only alarms of the FAULT type. Both function blocks can transmit more than one system
alarm. The parameters [Rlb] and [MsgTxt] provide detailed information about the cause of the
most recent alarm message. The messages are transmitted in the order in which they occur,
irrespective of the importance of the alarm.
Only these alarm sources incorporate Intrinsic Reporting, and can thus generate
their own alarms. If any other value of a function block needs to be monitored for
an alarm (for example, the control signal for a controller block), an Event
Enrollment object must be added.
Alarm-generating function blocks include a range of interface variables which can
be set as parameters to determine the alarm response (Input Property) or to supply
the relevant alarm state information (Output Property). These interface variables
are described further below. Some of the interface variables are common to all
alarm-generating block types, while others are specific to certain types of alarm-
generating blocks.
135 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Example
Alarm state event states The alarm state machine can assume one of three basic states (event states
[EvtSta]):
● NORMAL: There is no alarm condition present
● OFFNORMAL: Alarm caused by an OFFNORMAL condition
● FAULT: Alarm caused by a FAULT condition
With analog blocks, the OFFNORMAL state is explicitly subdivided into the sub-
states HIGH LIMIT and LOW LIMIT, which are described in detail further below.
The current state of the alarm state machine in an alarm-generating block is
displayed externally in the form of the output variable [EvtSta] (event state) of the
block concerned.
State transitions The following table shows the state transitions between the alarm states:
TO_NORMAL1 The current OFFNORMAL alarm condition has disappeared, and there is NORMAL
no other alarm condition present.
TO_NORMAL2 The current FAULT alarm condition has disappeared, and there is NORMAL
currently no other alarm condition.
System events may also occur within each alarm state. These message functions
do not affect the alarm state.
Because FAULT alarms take priority over OFFNORMAL alarms, the state transition
from FAULT to OFFNORMAL only occurs under very special circumstances.
If, while in the OFFNORMAL state, a FAULT alarm condition occurs, there is then a
state transition TO_FAULT (because as stated above, FAULT takes priority over
OFFNORMAL).
136 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Example
8
Zustandsmaschine 1
RefVal 3 4
∆? PrVal disturbed Belt
PrVal
2
3 7 disturbance
appears
OR 6
Pop Up Desigo CC
Txt:........................
3 ACK
RESE 5
Auto
ON Pop Up
OFF
Txt:........................
9 ACK
RESE
Key:
A State machine
B CFC program
D Desigo CC popup
E PXM… Values (in a PXM10 alarm handling is only possible for connected PXCs or PXRs)
F PXM… Popup (in a PXM10 alarm handling is only possible for connected PXCs or PXRs)
137 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Example
138 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Effects of BACnet Properties on Alarm Response
8
6. The fault has been cleared. When DPMon.Dstb = 0, then Cmd.EnSfty → 0 and
hence Cmd.PrVal → Cmd.ValPgm=1, that is, the fan motor is enabled. Then,
with Cmd.TraSta = 1 (transient state), the fan ramp-up time is allowed to expire,
that is, DPMon.RefVal is held at 1 during the transient state. Only after expiry
of the ramp up time does DPMon.RefVal revert to 0.
7. The ventilation system is already running (from step 6 on), that is, the fan
blades start rotating, the pressure builds up and the differential pressure
monitor detects delta p = X again, that is, DPMon.PrVal → 1. The alarm
monitoring function is active again. After expiry of the time [TiMonDvn], this
determines that there is no alarm condition present, because [DPMon.PrVal(0)
<> DPMon.RefVal (1)]. The system then operates 100% correctly as described
under step 1 above.
To simplify the time chart shown above, the connection to DPMon.EnAlm has not
been included.
139 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Effects of BACnet Properties on Alarm Response
Event enable EnEvt Event enable Event_Enable Pulse Converter I/O/V I/O/V I/O/V
Command Control1
Power Control1
AlarmCollection
Trend Logs
Event Enrollment
Loop
Event state EvtSta Event state Event_State Discipline I/O1 I/O/V I/O/V I/O/V
Group1
Pulse Converter
Trend Logs
Device-Info1
Command Control1
Power Control1
AlarmCollection
Event Enrollment
Loop
Message text MsgTxt/EvtMsg Message text Message_Text Discipline I/O1 I/O/V I/O/V I/O/V
Group1
Pulse Converter
Command Control1
Power Control1
Loop
Event Enrollment
140 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Effects of BACnet Properties on Alarm Response
8
Present value PrVal Present value Present_Value Pulse Converter I/O/V I/O/V I/O/V
Command Control1
Power Control1
AlarmCollection
Loop
141 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Effects of BACnet Properties on Alarm Response
Event time stamp TiStmEvt Event time stamp Event_Time_Sta Device-Info1 I/O/V I/O/V I/O/V
mps Discipline I/O1
Group1
Pulse Converter
Trend Logs
Command Control1
Power Control1
AlarmCollection
Event Enrollment
Loop
142 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Effects of BACnet Properties on Alarm Response
8
Hi limit [HiLm]
This parameter (data type Real) determines the high alarm limit. If [PrVal] exceeds
the high limit value [HiLm] for longer than the period defined under [TiMonDvn], an
OFFNORMAL alarm condition prevails, namely: HIGH_LIMIT.
143 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Effects of BACnet Properties on Alarm Response
the alarm state must persist without interruption for a period of time at least
equivalent to the duration of [TiMonDvn], before it has any effect. The BACnet
standard only supports a [TiMonDvn] for a monitoring period and the associated
alarm delay. This is equivalent to the standard BACnet property Time_Delay.
In certain applications, different end-switch monitoring periods are required for
Open and Close commands and for the Idle state.
For this reason, the additional properties [TiMonOff] und [TiMonOn] have been
introduced for the binary input, binary output, binary value and multistate output
objects.
The definitions of the set point and the measured value depend on the object type:
Table 34: The set point and the measured value depend on the object type
Examples The following example shows the use of the three time periods [TiMonDvn],
[TiMonOn], [TiMonOff]. For another example, see Alarm Example.
It is assumed that a fire damper has two separate feedback mechanisms (end
switches). This means that the damper is commanded via the commands Open
and Close. The first end switch, the Open switch delivers the signals Fully open or
Not fully open. The second end switch, the Closed switch delivers the signals Fully
closed or Not fully closed. The following is an example of how to connect the BO
(binary output for commanding and integrating the Open switch) and BI (the binary
output for the closed switch):
144 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Effects of BACnet Properties on Alarm Response
8
Given the feedback signal [FbVal] Fully open, the Open and Close commands
follow the time sequence shown below, making use of all three deviation
monitoring times [TiMonDvn].
Since the BO block can handle the feedback of two different addresses, the fire-
protection damper solution can be further simplified by direct connection of the
Closed switch (Addr. 1) and Open switch (Addr. 2). In cases where both end
switches are simultaneously On or simultaneously Off, the BO block treats the
[FbVal] as invalid. Throughout this period, therefore, the alarm monitoring function
will return the value Alarm = OFFNORMAL. The circuit and time sequence for
normal and error conditions are as follows:
145 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Effects of BACnet Properties on Alarm Response
Figure 119: Circuit and time sequence for normal and error conditions
Figure 120: Fire protection damper timing with BO and two feedback addresses
Figure 121: Fire protection damper timing with BO and two feedback addresses
146 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Effects of BACnet Properties on Alarm Response
8
the automation station. All the alarm-generating blocks (including the BACnet
Device Info Object) are only monitored in the operational status RUN. Corresponds
to the standard BACnet Property Out_of_Service.
Reliability [Rlb]
The value under [PrVal] is only plausible if [Rlb] = NO_FAULT_DETECTED.
When [Rlb] <> NO_FAULT_DETECTED, this is precisely the condition for a FAULT
alarm.
The BACnet Device Info Object is an exception. The value of [Rlb] for the BACnet
device object is NO_FAULT_DETECTED, except in the case of the fault
FLASH_FULL (FAULT condition). This is equivalent to the standard BACnet
property Reliability.
Name Value
State 1 STEP 1
State 2 STEP 2
State 3 STEP 4
147 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Response of the Function Blocks
148 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Response of the Function Blocks
8
In Desigo S7 the monitoring described are not reported from the device object, but
rather from an MV object.
FAULT alarms
The condition described below causes a FAULT alarm to be generated in the
BACnet Device Object:
149 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Response of the Function Blocks
Flash is full The automation station checks periodically whether there is at least one free page
(64 kB) in the flash memory. This bit is set if the flash memory falls below this value.
The bit is reset when the flash memory contains at least one free page again.
Alarm response of the BACnet Device Object is also parameterized or depicted by
the number of variables, but the display differs: The BACnet Device Object is not
displayed by a D-MAP function block, but rather only visible via BACnet. The
variables described are therefore only accessible as properties of the BACnet
Device Object.
Binary Output
The alarm handling process in the binary output function block is essentially
different from that of the binary input and binary value blocks.
150 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Response of the Function Blocks
8
● An OFFNORMAL alarm occurs when the current values of the variables [PrVal]
and [FbVal] differ from each other for a time period at least equivalent to the
delay time specified in [TiMonDvn], [TiMonOff] or [TiMonOn].
● An existing OFFNORMAL alarm will disappear when the current [PrVal] und
[FbVal] are again identical and remain so for a period at least equivalent to the
time specified in the variable [TiMonDvn].
● A FAULT alarm is generated when the [Rlb] property of the function block
assumes any value other than NO_FAULT_DETECTED. In particular, this is
the case when the [Rlb] property changes from a value not equal to
NO_FAULT_DETECTED to another value not equal to
NO_FAULT_DETECTED.
In the case of the binary output, [Rlb] errors may originate both from the [PrVal]
(or associated physical output) and from the [FbVal] (or associated physical
input).
● A FAULT alarm will disappear as soon as the variable [Rlb] changes from a
value not equal to NO_FAULT_DETECTED back to the value
NO_FAULT_DETECTED.
151 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Response of the Function Blocks
Multistate output
The alarm handling procedure for the Multistate Output function block is different
from the alarm handling procedure for the Multistate Input and Multistate Value
function blocks, but follows the same principles as for the Binary Output block:
152 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Response of the Function Blocks
8
Power Control
An OFFNORMAL alarm is generated:
● The UP command is issued but the maximum stage has already been reached
● The UP command causes MaxPower to be exceeded
● Table_No is set outside the admissible range
A FAULT alarm is generated when:
● A referenced object is not found
● A referenced object is not a multistate value object
● Object_No. is outside the admissible range
● StepLimit is outside the range of the referenced object
● The function table is empty
Pulse Converter
Alarm response An OFFNORMAL alarm is generated, when [PrVal]:
153 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Response of the Function Blocks
● [PrVal] has remained above the high alarm limit specified by the [HiLm]
variable for a period of time longer than the period specified in [TiMonDvn]
(HIGH_LIMIT)
● or [PrVal] has remained below the low alarm limit specified by the [LoLm]
variable for a period of time longer than the period specified in [TiMonDvn]
(LOW_LIMIT)
An existing OFFNORMAL (HIGH_LIMIT) alarm will disappear when [PrVal] has
remained below the value ([HiLm] + [Nz]) for longer than the time specified in the
variable [TiMonDvn]
An existing OFFNORMAL (LOW_LIMIT) alarm will disappear when [PrVal] has
remained below the value ([HiLm] + [Nz]) for longer than the time specified in the
variable [TiMonDvn]
● A FAULT alarm is generated as soon as the [Rlb] property of the function block
assumes any value other than NO_FAULT_DETECTED. In particular, this is
the case when [Rlb] changes from a value not equal to
NO_FAULT_DETECTED to another value not equal to
NO_FAULT_DETECTED.
● A FAULT alarm will disappear as soon as the [Rlb] property of the function
block changes from a value not equal to NO_FAULT_DETECTED back to the
value NO_FAULT_DETECTED.
Trend Log
Alarm response The Trend Log function has an Intrinsic Reporting mechanism, but does not issue
OFFNORMAL alarms.
● A FAULT alarm is generated as soon as the [Rlb] property of the function block
assumes any value other than NO_FAULT_DETECTED. In particular, this is
the case when [Rlb] changes from a value not equal to
NO_FAULT_DETECTED to another value not equal to
NO_FAULT_DETECTED.
● A FAULT alarm will disappear as soon as the [Rlb] property of the function
block changes from a value not equal to NO_FAULT_DETECTED back to the
value NO_FAULT_DETECTED.
Event message An event is generated when:
● The record count exceeds the record count value [RecCnt] set via the
notification threshold [NotifThd], that is, the local non-volatile trend memory is
overflowing.
Event Enrollment
The Event Enrollment object monitors referenced BACnet properties in other
objects. The referenced property can be located in the local device or in another
device.
154 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Response of the Function Blocks
8
Event algorithms Monitoring details for a property value are defined by means of event algorithms.
An event algorithm has a specific parameter. Event algorithms are the same as for
Intrinsic Reporting. Intrinsic Reporting uses a subset of the possible event
algorithms of Event Enrollment.
Table 36: Event types and states and their parameters and data types
Event notification An Event Enrollment object also monitors the status flag property of an object with
referenced property. If the FAULT flag of the referenced object is set, the Event
Enrollment object generates a Fault alarm.
Loop object
Alarm response The Loop object contains intrinsic reporting.
An OFFNORMAL alarm occurs when:
155 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Functions
● [XCtr] exceeds the limit (SetPoint + ErrorLimit) longer than the specified time
(HIGH_LIMIT) defined in variable [TiMonDvn]
● [XCtr] drops below the limit (SetPoint – ErrorLimit) longer than the specified
time (LOW_LIMIT) defined in variable [TiMonDvn]
An existing OFFNORMAL alarm (HIGH_LIMIT) disappears again when [XCtr]
drops below the value (SetPoint + ErrorLimit – Deadband) longer than the specified
time defined in variable [TiMonDvn].
An existing OFFNORMAL alarm (LOW_LIMIT) disappears again when [XCtr]
exceeds the value (SetPoint – ErrorLimit + Deadband) longer than the specified
time defined in variable [TiMonDvn].
FAULT alarm:
● A FAULT alarm occurs immediately as soon as [Rlb] of the function block has a
value other than NO_FAULT_DETECTED. This is true in particular when [Rlb]
changes from a value that is not equal to NO_FAULT_DETECTED to another
value that is not equal to NO_FAULT_DETECTED.
● A FAULT alarm disappears immediately as soon as [Rlb] of the function block
changes again from a value that is unequal to NO_FAULT_DETECTED to the
value NO_FAULT_DETECTED.
Standard pattern
There are three standard categories of alarm, or alarm functions, reflecting the type
of acknowledgement required:
● Simple alarm
● Basic alarm
● Extended alarm
Each alarm source is assigned (via a Notification Class, see further below) to one
alarm function only. No further distinction is made at this stage between
OFFNORMAL and FAULT alarms.
Simple alarm Neither incoming alarms (disturbance appears) nor disappearing alarms
(disturbance disappears) require acknowledgement.
Basic alarm Acknowledgment is required for incoming alarms only, but not for alarms that have
been cleared (that is, acknowledgement required but not reset).
156 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Functions
8
Extended alarm Locking alarm with acknowledgement of incoming alarms (disturbance appears)
and cleared alarms (disturbance disappears). Alarms in this category require both
acknowledgement and reset.
While testing the system, it may not be possible to reset an alarm. The reason is
that an Extended Alarm is not reset until it has been acknowledged, and the time
delay has expired.
Key:
The alarm remains locked until the fault has disappeared and has been
acknowledged and a reset has been carried out. For example:
The burner system is restarted when the service engineer has acknowledged the
alarm, cleared the fault and reset the alarm. The alarm state of every alarm-
generating object is managed within the object itself. The state machines above
illustrate this for each of the alarm functions.
Simple message The alarm function simple message is the same function as the simple alarm. State
transitions, however, are not indicated as events, but alarms.
157 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Management by Notification Class
For HVAC applications and response in the system, the functionality is identical to
simple alarm: Simple alarm without acknowledgement of incoming and outgoing
faults. The only difference is EventNotification as alarm or event.
Customized alarm Any alarm function under BACnet can be used. The following behavior can be
defined for customized alarms:
● EventNotification can occur as either event or alarm
● Acknowledgement: For each change of state (TO-OFFNORMAL, TO-NORMAL,
and TO-FAULT) can be defined whether or not an acknowledgement is
required.
[AckTra] Acknowledged This feature is used to represent the acknowledgement status, or to handle
transitions information about which state transitions currently still require acknowledgement.
The value of [AckTra] is based on the alarm function, the current [EvtSta] and the
monitoring of acknowledgements already received.
[AckTra] consists of three flags, one each for TO-OFFNORMAL, TO-NORMAL and
TO-FAULT. The flags have the following meanings:
● The flag is always FALSE when there has been a relevant state transition and
an acknowledgement is required, because this is a requirement of the alarm
function and no acknowledgement has yet taken place.
● The flag is TRUE when no acknowledgement of the state transition is required.
This may be the case because the alarm function does not require
acknowledgement, or because no state transition has occurred, or because a
state transition that has occurred has already been acknowledged.
[TiAck] Time of Time of the last acknowledgement (time stamp).
acknowledgement
Each alarm-generating object is assigned one notification class [NotifCl] only, but
one notification class can be used by more than one alarm-generating object. This
158 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Management by Notification Class
8
makes it possible to create a Notification Class object for each group of alarms (for
example, HVAC alarms, fire alarms etc.). Each alarm source in a given alarm
group is assigned to the [NotifCl] for that group.
There are global and local notification class objects:
● Global notification class: One set of max. 18 global notification class objects
per site. Global notification classes are replicated and thus exist on all Desigo
PX of a site in identical form.
● Local notification class: On Desigo PX, local notification classes can be
engineered, but are NOT replicated.
● Desigo Room Automation supports exclusively local notification classes.
Interface definition The notification class function block [NotifCl] is the means by which functionality is
transferred from the BACnet standard into the CFC environment.
This function block contains the instance number of the Notification Class (an
integer). which must be identical to the value entered in the subordinate alarm
sources. This makes it possible to create a unique reference.
The number must not be modified online.
In Desigo S7 all Notification Classes are compiled in a function block.
Notification class number There are 18 predefined global notification classes. The notification class is
identified with the two independent variables AlarmFunction and AlarmClass, and
referenced in the alarm source:
● AlarmFunction [Simple(1), Basic(2), Extended Alarm(3)]
● AlarmClass [UrgentAlarm (1), HighPrioAlarm (2), NormalAlarm (3),
LowPrioAlarm (4), UserDefinedAlarm (5) and OffLineTrend (6)]
Formula The notification class number is calculated as follows:
NotificationClass# := 10 * AlarmClass + AlarmFunction
This gives the following notification classes:
UrgentAlarm Simple 1, 1, 5 11
UrgentAlarm Basic 1, 1, 5 12
UrgentAlarm Extended 1, 1, 5 13
Critical alarms
HighPrioAlarm Simple 2, 2, 6 21
HighPrioAlarm Basic 2, 2, 6 22
HighPrioAlarm Extended 2, 2, 6 23
Normal alarms
NormalAlarm Simple 3, 3, 7 31
159 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Management by Notification Class
NormalAlarm Extended 3, 3, 7 33
Non-critical alarms
LowPrioAlarm Simple 4, 4, 8 41
LowPrioAlarm Basic 4, 4, 8 42
LowPrioAlarm Extended 4, 4, 8 43
UserDefinedAlarm Simple 5, 5, 9 51
UserDefinedAlarm Basic 5, 5, 9 52
UserDefinedAlarm Extended 5, 5, 9 53
Offline trends
The To-Normal priority must
be such that it is less than or
equal to the Alarm Priority
Limit of the device object (for
Remote Mgmt)
OffLineTrend Simple 2, 2, 2 61
OffLineTrend Basic 2, 2, 2 62
OffLineTrend Extended 2, 2, 2 63
160 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Management by Notification Class
8
Site "Muri"
BACnet PTP
BACnet PTP
Router
Operator units:
● Permanently connected operator units (and hence, alarm receivers) are
addressed by their Device Name.
● Operator units (and hence alarm receivers) with a point-to-point connection
(PTP connection) are addressed with a Remote Area Site identifier and their
Device Name. For example:
B=fff for permanent connection
B=kkk:aa for point-to-point connection (PTP connection)
● Adjustments are required during the addressing process so that there is no
conflict between the names of operator units and the plant or room
management designations.
Permanent and point-to-point connections:
● For alarm receivers, the address syntax (see further below) indicates the type
of connection: permanent or PTP connections.
● Desigo PX automation stations with half-routers must know the Remote Area
Site designators of their remote alarm receivers to enable an PX automation
station to resolve the remote alarm receiver designator.
161 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Routing over the Network
B=
Permanently
DeviceIdentifier connected
alarm receiver
Not case-sensitive
A..Z
a..z
0..9
Element Description
DeviceName Device name. In plain text so that the user can understand it.
Example: CC 01
DeviceIdentifier Device Identifier. Alternative syntax for the alarm receiver of a third-
party manufacturer. If the alarm receiver has a special address range
or if DeviceName does not work.
Example: [13456]
RemoteAreaSiteName Remote area site name. In plain text so that the user can understand it.
Example: Chur
Temporary alarm Temporary alarm receivers are not defined at the engineering stage. They can be
receivers connected to or removed from the network at any time during operation. If a
temporary alarm receiver is connected to the network, it will perform the following
activities for every alarm server:
162 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Routing over the Network
8
● The alarm recipient enters its address in the BACnet property recipient list
[RecpList] of the BACnet device object of the automation station, using the
BACnet service AddListElement.
● Read information about all currently existing alarms, and all currently
outstanding acknowledgements, from the automation station (BACnet service
GetEventInformation). This ensures that the alarm receiver – irrespective of
when it was connected – displays the current alarm status of the system.
After making these entries, the temporary alarm receiver, while connected, will
receive all alarm messages from the automation station in accordance with the
routing mechanisms described below.
If an automation station cannot transfer an alarm message to a temporary alarm
receiver (for example, because it is no longer connected to the network), the
address of the receiver concerned will be removed from the [RecpList]. All alarm
messages destined for that receiver will then be deleted.
Preconfigured alarm The preconfigured alarm receivers are entered in the notification class object:
receivers ● In the [DestList] for Desigo PX
● In the [RecpList] for Desigo Room Automation
SimpleAck
SimpleAck
t t t
This procedure is carried out for every change in alarm state on an alarm server:
TO_OFFNORMAL, TO_FAULT und TO_NORMAL. The data record Confirmed
Event Notification contains the following information:
● BACnet address of the alarm server
● Object ID of the alarm-generating object
163 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Routing over the Network
● Time stamp
● Alarm priority
● Initial and final state of the transmitted state transition (this is used to determine
whether the state transition is TO_OFFNORMAL, TO_FAULT or TO_NORMAL)
● Acknowledgement required [AckReq]: Does the notified state transition require
acknowledgement or not?
● Alarm text
● Other technical details
Based on this information, the alarm client can present the alarm in a
comprehensible way; it may also read additional information automatically from the
alarm server, and if required, return any acknowledgement to the correct address.
If a temporary alarm receiver does not confirm receipt with a SimpleAck message
(via the Confirmed Event Notification input), the alarm server will try three times
more to transmit the alarm to the relevant alarm receiver. The message for this
alarm client will then be lost and its reference will be deleted from the [RecpList] of
the BACnet device object.
Alarm acknowledgement This process is performed for all acknowledgements made on an alarm client.
over the network
SimpleAck
SimpleAck
t t t
Acknowledge and reset The alarm can be acknowledged by any alarm client. The AcknowledgeAlarm data
record contains information as to which alarm is being acknowledged and other
details related to this alarm and the acknowledging alarm client. The alarm
acknowledgement is confirmed with a SimpleAck message by the alarm server
which generated the alarm. All other alarm clients in the network will be sent a
Confirmed Event Notification to notify them of the alarm acknowledgement. They,
in turn, will send a SimpleAck message to acknowledge the receipt of this
notification, the objective being to ensure that all clients have up-to-date and
consistent information.
Local alarm Alarms can also be acknowledged and reset locally on the alarm server. The alarm
acknowledgement is acknowledged internally in the alarm server that generated the alarm. Confirmed
Event Notifications are now transmitted to all alarm clients, to notify them that the
alarm has been acknowledged. The alarm clients, in turn, send a SimpleAck
message to acknowledge their receipt of the Confirmed Event Notification.
SimpleAck
SimpleAck
t t t
164 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Queuing
8
Disabling the routing of [EnEvt=TRUE]. This does not affect the alarm monitoring of the object, that is, the
alarms alarm state machine is always kept up to date.
165 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Common Alarms
166 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Suppression
8
In Desigo S7 the Common Alarm block in the CFC is nested with the block
generating the alarm.
167 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Suppression
168 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
Alarm Message Texts
8
169 | 377
Siemens CM110664en_03
2017-09-18
Alarm Management
8 Alarm Message Texts
For Desigo PX if no alarm message text has been entered for an alarm source, or
if the alarm message text for a given state (for example, TO_FAULT) has been left
blank, an alarm message text will be generated from the existing descriptions.
Project-spec.
Description
Description
Standard
Longer messages are divided into segments with forward slashes // so that the
client can display the message over several lines. Each segment may contain a
maximum of 70 characters, with a maximum of three segments separated by // for
any one message.
Non-configured message System alarms and events of the BACnet Device Info Object use text messages
texts which cannot be configured, for example, Battery low.
Predefined, language- System alarms and events of the BACnet Device Info Object use non-configured
dependent text text messages whose contents are language-dependent. These language-
dependent texts are organized into text groups with a predefined server system
text scope, and can be translated. The translated text groups are loaded into the
automation station via BACnet description information.
170 | 377
Siemens CM110664en_03
2017-09-18
Calendars and Schedulers
Alarm Message Texts
9
171 | 377
Siemens CM110664en_03
2017-09-18
Calendars and Schedulers
9 Schedule
9.1 Schedule
Weekly schedule [WeekSchd]
The weekly schedule [WeekSchd] consists of seven 24-hour profiles, one for each
day of the week. By default, the priority level assigned to the weekly schedule is 16
(the lowest priority). The weekly schedule is active unless there is an exception
schedule.
For system limits, see chapter System Configuration.
24-hour profiles A 24-hour profile is a list of time-and-value pairs. The present value remains at the
[PrVal] output until the processing of the next time-and-value pair causes a new
value to be written to the output.
If there is no schedule entry with a switch time of 00:00 in the daily profile, the
default value determines the resulting Present_Value (=Rule schedule default
value).
If the daily profile encompasses an empty list of schedule entries, the default value
[DefVal] determines the resulting Present_Value (=Rule schedule default value).
Figure 142: Evaluate exception day program, weekly program and Schedule_Default
172 | 377
Siemens CM110664en_03
2017-09-18
Calendars and Schedulers
Schedule
9
173 | 377
Siemens CM110664en_03
2017-09-18
Calendars and Schedulers
9 Schedule
Key:
1 An exception profile applies to more than one day. On the second day, the exception profile is
inactive, because another profile with a higher priority is active for the whole day.
2 An exception program without the entry NULL. This exception profile is active for the whole day
and ends automatically in the automation station at 24:00 hours by the NULL entry.
3 Several exceptions with the same priority on the same day, but without overlapping times. The
exception profiles do not interfere with each other as an exception begins with the first time entry
and ends with NULL.
4 Several exception profiles with the same priority on the same day with overlapping times. These
exception profiles affect each other, as several exceptions with the same priority level are active
simultaneously. In such cases, the rule is that if the switch commands are the same, the first
time-entry applies (in this example 13:00 to NULL). With non-identical switch commands, the
latest time-entry applies.
Output signals
[PrVal] [NxVal] [NxTi] The scheduler sends the following output signals:
● [PrVal]
● [NxVal]
● [NxTi]
The [NxVal] und [NxTi] output signals support the optimum start/stop control of the
plant. When determining [NxVal] and [NxTi] in the time schedule, the current day
and the next two days are taken into account. This results in a time window of 48 to
72 hours, depending on the current time and the next switch entry. If there is no
change in [PrVal] within the time window, then [NxVal] is the same as [PrVal] and
[NxTi] is equivalent to the current date plus 3 days (00:00h).
[DefVal] This default value [DefVal] appears at the [PrVal] output when there is no active
entry in the time schedule, or when the entries are all NIL, or when the time period
is outside the active period.
[EnDef] The [EnDef] variable enables or disables the [DefVal] variable.
The function block variables [DefVal] and [EnDef] are mapped to the
Schedule_Default property. The property Schedule_Default can have the value
[DefVal] or NIL.
174 | 377
Siemens CM110664en_03
2017-09-18
Calendars and Schedulers
Schedule
9
The NIL value in the Schedule_Default property is the release value for the active
priority of the object controlled by the scheduler. Do not confuse it with the NIL
value in the exception schedule used to prioritize the time entries.
Figure 144: Schedule function blocks for analog, binary, and multistate
In Desigo PX the CAL (calender) and SCHED (schedule) function blocks can be
created online.
Commanded objects
The schedule can influence other commandable objects, irrespective of whether or
not they are in the same automation station.
The schedule is thus a grouping object and contains a list of group members, in the
form of a list of name references [NamrList]. These group members are the
commanded objects, that is, the objects to be switched. The list can contain up to
five entries.
175 | 377
Siemens CM110664en_03
2017-09-18
Calendars and Schedulers
9 Schedule
Time resolution
The smallest unit in the scheduler program is one minute and in the calendar one
day. The schedule may be dependent on the calendar. In the PX automation
stations, the calendar function block is automatically processed before the
scheduler function block. The superposed cycle for processing the calendar and
scheduler begins at the start of the new minute of the system time.
A PX automation station incorporates an automatic load shedding mechanism. The
result is that a switch command at time x is executed within a time-period defined
by time x + 1 minute.
176 | 377
Siemens CM110664en_03
2017-09-18
Calendars and Schedulers
Calendar
9
System time
Schedules and calendars are based on the same global time. This ensures that all
automation stations on a site have the same time base.
9.2 Calendar
Function block Calendar The calendar object is a function block from the firmware library. It contains a list of
dates [DateList] with, for example, a date or a date range.
The date list [DateList] uses Boolean logic to control the calendar outputs. [PrVal]
activates an exception profile if the calendar object is referenced by a schedule
object. The outputs tomorrow [Tmw] and day after tomorrow [DayAfTmw] support
the optimum start/stop control of the plant.
Standard BACnet object The SCHED (schedule) and CAL (calender) function blocks in the firmware library
Calendar correspond to the SCHED and CAL standard BACnet objects. Standard BACnet
object can be operated via the BACnet clients.
The calendar and schedule can be linked at the BACnet level by references. There
is no data flow link between the calendar and schedule function blocks in the CFC
chart.
9.3 Wildcards
A wildcard character (*) generates a repetition and is an abbreviated way of listing
individual entries. For example, writing 3.* is a short way of representing 3.1., 3.2.,
3.3., 3.4., 3.5., etc.
All data structures of the scheduler or calendar objects support dates with
wildcards. Date ranges and time specifications do not support wildcards. Invalid
weekdays are ignored.
177 | 377
Siemens CM110664en_03
2017-09-18
Calendars and Schedulers
9 Alarm Messages
Date entries with The following table shows examples of date entries containing wildcards:
wildcards
Date Meaning
23.April.2001 /Monday 23.April.2001, Monday
23.April.2001 /* 23.April.2001
23.April.* /Monday Each April 23rd, each year if the weekday is a Monday
*.April.* /Tuesday Each day in April of each year if the weekday is a Tuesday
31.*.* /* Each January 31, March 31, May 31, … of each year
or each February 28/ 29, April 30,... of each year
If a date contains a wildcard in the month or year, the last day of the month is used
for the day, if the value of the day is greater than the maximum number of days in
the month.
Week and day with The following table shows an example of entering a week and day (WeekNDay)
wildcards using wildcards. During the evaluation, a wildcard is replaced by the corresponding
value of the current date. If the WeekNDay generated in this way is equivalent to
the current date, this is an exception day.
178 | 377
Siemens CM110664en_03
2017-09-18
Trending
Trend Functions
10
10 Trending
Trend data provide important information about the processes in a building
automation and control system. For example:
● Monitoring of the control system for optimization purposes
● Logging the room temperature in association with the set temperature
● Logging of temperature and humidity trends for the pharmaceutical industry
Offline/Online trend There are two types of trend data:
● Offline trend:
The recorded trend data are saved in the automation station and uploaded to
Desigo CC periodically or as needed. The data can be analyzed in Desigo CC.
A connection is needed only during the data upload. Trend objects are needed
in the automation station.
Offline trend is mostly used for long term data logging.
● Online trend:
Arbitrary data points can be saved as online trends.
A permanent connection is needed. No trend objects are needed in the
automation station.
Online trend is mostly used for temporary data logging.
Trend Log Objects The trend data is saved in the buffer of the Trend Log and Trend Log Multiple
objects in the automation station.
The Trend Log object can only record one value of a data point. The Trend Log
Multiple object can record up to six different values of a data point.
The Trend Log object cannot be set up online, but must be set up in advance,
offline in the application. A Technical Designation (TD) determines (BACnet
reference) which object is to be logged. This presupposes that the referenced
object is visible via BACnet (not No Element). The reference and the parameters
can be defined and modified online or offline.
When the number of trend log entries reaches a definable threshold (Notification
Threshold [NotifThd]), the Trend Log object generates an event. The Trend Log
object sends out an alarm which is defined in a notification class specified for
Trend Log.
The trend log data acquired can only be read, and if necessary, archived, with a
BACnet Client configured for this purpose, for example, Desigo CC. The status of a
Trend Log object is not affected by reading out trend log data. It is not possible to
reload sampled data into Xworks Plus (XWP).
A BACnet client cannot reserve a Trend Log object. Every BACnet client can
access the Trend Log object. In the case of access or modifications undertaken by
several clients, the rule is that the most recent one always takes priority.
179 | 377
Siemens CM110664en_03
2017-09-18
Trending
10 Trend Functions
Single Run The trend data is saved until the available memory area is full. You can define the
buffer size [BufSize] within the range 2 to 5,000 entries. You can define the Single
Run function with the parameter Stop when full.
Logging Type The parameter Logging Type [LogTyp] defines the logging type. The values are:
● POLLED: Periodic Sampling
● COV: COV Sampling
● TRIGGERED: Triggered Sampling
By setting the parameters accordingly, you can define combinations of Continuous
Run / Single Run and Periodic Sampling / COV Sampling / Triggered Sampling.
Periodic Sampling In Periodic Sampling data is acquired by sampling and storing values in a regular
cycle. Periodic Sampling is supported by the trend log object and the trend log
multiple object.
COV Sampling In COV Sampling data is stored based on a change of value (COV) of the
referenced parameter. A COV subscription can be applied to all supported data
types (analog, Boolean and multistate). The amount of change required to initiate a
COV is set as a parameter in the object to be referenced. COV Sampling is
supported only by the Trendlog object.
180 | 377
Siemens CM110664en_03
2017-09-18
Trending
Editing Parameters
10
Triggered Sampling In Triggered Sampling an application (for example, via data flow interconnection)
determines when values are acquired/logged and saved. Triggered Sampling is
supported by the Trendlog object and the Trendlog Multiple object.
181 | 377
Siemens CM110664en_03
2017-09-18
Trending
10 Processing Trend Data in Desigo CC
With a full loading procedure, any previously sampled data will be lost. With
differential or delta loading the data will not be lost.
The PXM20 stores modified parameters in its internal memory cache. To display
the data actually written, you must exit from the trend log object and re-select it.
182 | 377
Siemens CM110664en_03
2017-09-18
Reports
11
11 Reports
You can create reports in Desigo CC about the functioning of the building
automation and control system.
You can configure:
● The elements in the report (such as tables, plots, logos, form controls, text and
so on), and their layout.
● Filters (such as name, condition, time, and/or row) to populate the elements of
the report with information. For example, if you want a report on a room's
activity data over the past month, you could define a name filter and a time filter
in an activities table.
● The formatting of the report elements and the page layout.
● The output type (PDF or XLS) and the output destination (file, email, or printer).
You can save your report definition for later use, run it, or schedule the report to be
run at a specified time.
You can use reports as a reference or as a troubleshooting mechanism. Reports
are helpful during system operation.
For example, you can:
● View a mixed report containing:
– A table displaying details of all active events for a floor of a building
– A table displaying a history report of events
– A trends plot displaying the temperature variations gathered from
temperature sensors
● Export trend data for statistical analysis to:
– An XLS file
– A CSV file (according to the EMC requirement)
● Schedule production of a report using macros and reactions
● Send a report by email, print it or save it as a PDF
You can export and import report definitions and logos.
You can also create and configure reports for operating procedures. These reports
are used during assisted treatment to enter information about how the alarm or
event is being handled.
183 | 377
Siemens CM110664en_03
2017-09-18
Data Storage
12 Data Categories
12 Data Storage
Large volumes of data are created in the Desigo system during engineering,
commissioning and plant operation. The data is processed, saved, and archived as
needed in accordance with type, generation, and meaning in the various system
components.
Setting parameters Values that affect the program elements. Setpoints, default values, limit values,
address settings
Configuration parameters Data in the form of defined constants, or data that Description data, templates, profile,
influences the appearance or operability of the plant. metadata
Process data Physical process variables of the plant during operation. Measured values, state variables,
History or saved process data are plant data. calculated values
Data ownership Data ownership is based on the practical allocation of data to its owner. The owner,
usually an organizational entity, a person, or a group of people, checks the data
and is responsible for its scope and content. Data ownership shows in which
Desigo system product the data is located and which tools are available for its
management. Data ownership is divided in four groups.
The following table shows the four data ownership groups.
Libraries Collection of predefined, specific, and tested Library manager (HQ/RC) Project/Library engineer
program elements.
Libraries can be copied and customized.
Project data All data for the customer project or customer Contractor Plant operator
plant. Project engineer
Plant data Data from the customer plant saved Plant operator Customer
permanently following commissioning.
184 | 377
Siemens CM110664en_03
2017-09-18
Data Storage
Libraries
12
12.3 Libraries
Libraries are needed during engineering. You can create loadable applications
using libraries. Library elements are compiled from system basic components. For
example, the Desigo CC graphic library contains default graphics for visualizing
plants during engineering.
You can copy and customize or extend libraries. Every engineering level has a
library. Libraries can cover many combinations.
DXR2 automation stations are delivered with preloaded applications and only need
to be configured.
There are three library types:
● HQ libraries are tested, well documented and delivered with the system version.
Every new Desigo version contains new libraries.
● RC libraries are tested, well documented and contain country-specific
characteristics. They are optional, independent or an addendum to the HQ
library. Not all RCs offer comprehensive libraries.
● Project-specific libraries are not tested and documented.
Application libraries Application libraries contain plant-specific functions (heating, cooling, control of
electrical equipment, etc.) or templates for subsystem bindings. You can set up
and manage libraries with the Xworks Plus (XWP) and Automation Building Tool
(ABT) engineering tools.
PX libraries The functional units of the PX application libraries are defined by compounds. You
can copy, change and extend the compounds of the PX library.
Application libraries for PX and Desigo S7 are designed using the same application
principles and are provided via Xworks Plus during project engineering.
PXC3/DXR2 libraries The functional units of the PXC3/DXR2 application libraries are defined by
application functions. You can copy, change and extend the application functions
of the PXC3/DXR2 library.
Parameterization The library elements have plant-specific or function-specific setting and
configuration parameters:
● Setting parameters: The default values are defined by the application and
usually do not require adjustment.
● Configuration parameters: The default values can be adapted as needed.
185 | 377
Siemens CM110664en_03
2017-09-18
Data Storage
12 Project Data
Graphics libraries Graphics libraries contain graphics that represent the operating elements of the
firmware and application libraries. The graphics are used in Desigo CC to visualize
and operate plants. The elements of the graphics libraries depend on the elements
of the application libraries. Any changes to the application libraries must therefore
also be made to the graphics libraries.
The graphics libraries for Desigo PX, PXC3/DXR2, and Desigo S7 are identical.
RXC/RXB room RXC/RXB room applications are configured in XWP by selecting the required
applications functions or sample rooms. Data import in XWP to address the room devices is
carried out in different tools, depending on the RX device.
PXC3 room applications PXC3 room applications are programmed and configured in XWP/ABT by selecting
and configuring the applications required for the rooms and room segments
(application functions).
TX-I/O modules The configuration of TX-I/O modules depends on the PX automation station:
● PX automation station with island bus connection: The XWP/ABT tools transfer
the configuration data (IOC) to the target automation station PX/PXC3.
● PX automation station with P-bus connection: The configuration data (IOMD)
from XWP is loaded into the I/O modules via the TX-I/O tool.
The IOC/IOMD configuration data is saved as project data.
Back up and restore Project data is stored offline in XWP/ABT and Desigo S7 engineering tools. The
backup and restore function creates a backup of the data and, in case of data loss,
restores the data to the PX automation station.
186 | 377
Siemens CM110664en_03
2017-09-18
Data Storage
Plant Data
12
The backup copy contains all necessary data of a PX automation station to ensure
the automation station is fully functional after data restoration. You can back up
and restore data on third-party automation stations. You can save engineering data
on PX compact automation stations.
Backup Data from the PX automation stations are saved as a backup copy on Desigo CC.
The data is exported and saved as BACnet data.
To back up the data:
● The PX automation station must be connected and available (online).
● The PX automation station must support backup and restore.
● The building automation and control system must work smoothly.
Restore You can restore data backed up on Desigo CC to the corresponding PX
automation stations. The restored PX automation station automatically restarts
after data restoration.
187 | 377
Siemens CM110664en_03
2017-09-18
Data Storage
12 Data Transfer Processes
Offline generation
Full code generation Full code generation:
● Checks the overall application consistency (limits, identifiers)
● Converts the application into loadable units
● Generates the appropriate description data for configuration
You must compile the code to get the required performance. You cannot engineer
a compiled program.
Online loading
Full download The full download transfers all loadable units into the automation station.
Delta download The delta download:
● Copies additional blocks into the automation station
● Deletes blocks which are no longer valid
● Updates parameter settings
The delta download is faster than a full download. You do not need to interrupt the
operation of the automation station.
The delta download helps prevent unintentional parameter changes. Online
changed process data and settings parameters are protected against unintentional
overwriting, provided the process data was not changed in the tool.
Download options You can define what happens in the automation station before and after the
download. You can define if:
● Parameters are read back before the download
● The program starts and/or the I/O bus is turned on after the download
Online readback
During readback of non-volatile process values and parameter settings the data in
the automation station is aligned with the project data in the tool.
Readback comprises two steps:
1. Current parameter settings and non-volatile process values in the PX/PXC3
automation station are read from the automation station and copied to the data
storage.
2. The values are updated in the CFC data storage or PXC3 program and
configuration data storage.
The following data can be read back from PX/PXC3 to the project data storage in
the XWP/ABT tools:
● Setting parameters changed in the PX/PXC3 automation station
● Changed, non-volatile process values or configuration data
Advantages Reading back data has the following advantages:
● Outdated data in XWP/ABT is overwritten by current data and thus is available
again for reloading programs in the PX/PXC3 automation station.
● During online changes of background variables (for example, calendar), data
between CFC and XWP/ABT and the automation station is retained.
188 | 377
Siemens CM110664en_03
2017-09-18
Data Storage
Texts
12
Offline import
You can import configuration and description data for the plant into Desigo CC.
This is the same as the data downloaded to the automation station.
12.7 Texts
If you work with HQ or RC libraries, the texts are from a text database. These texts
can be automatically translated, because they have a unique ID. Project-specific
texts that are not from the text database cannot be automatically translated.
189 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
13 BACnet Architecture (MLN & ALN)
13 Network Architecture
The Desigo system is divided into three network levels:
● Management Level Network (MLN)
● Automation Level Network (ALN)
● Field Level Network (FLN)
BACnet Internetwork
Field Level
IP segment 9
Network
PXC3/DXR2 #1 PXC3/DXR2 #2
RXB #1 RXB #2
This classification is based on the functions performed at a given level, rather than
on the communications protocol or medium. The MLN and ALN use the BACnet
protocol. The transport protocol (Data Link Layer) is LonTalk or IP. The FLN uses
LonWorks, KNX and MS/TP technology.
190 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
BACnet Architecture (MLN & ALN)
13
Key:
Internetwork In BACnet, the BACnet internetwork is defined as the largest BACnet unit. It
consists of one or more BACnet networks. Only one active connection can exist
between any two BACnet devices in a BACnet internetwork.
All bus subscribers from the ALN and MLN, including BACnet third-party devices,
are part of the BACnet internetwork. The devices in the FLN are part of the Desigo
system but not part of the BACnet internetwork, because they do not communicate
via BACnet.
Network Desigo devices use LonTalk (BACnet/LonTalk), IP (BACnet/IP) or MS/TP (BACnet
MS/TP) as their transport protocol. If different transport protocols are used,
different physical networks are created, which must be connected to the PXG3
router. BACnet routers connect networks on the BACnet network layer and
transmit messages via the network number.
If the transport protocol changes, the BACnet network also changes. For example,
BACnet devices that use LonTalk as their transport protocol are always located in
a different network than devices that use IP as their transport protocol. This also
applies to PTP connections.
Desigo devices use LonTalk (BACnet/LonTalk) or IP (BACnet/IP) as their transport
protocol and MS/TP (BACnet MS/TP) to integrate third-party devices. If different
transport protocols are used, different BACnet networks are automatically created,
which must be connected to the PXG3 BACnet router. Multiple BACnet
internetworks can be created on an IP segment by using different UDP port
numbers.
191 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
13 BACnet Architecture (MLN & ALN)
Desigo establishes PTP connections only between operator units and a network.
Operator units duplicate a virtual network since PTP connections demand a
network at both ends.
Desigo CC does not use PTP.
Segment Large networks are structured, that is, divided into several (logical) network
segments for reasons of security, performance, size and (limited) address range of
network devices. The segments must then be connected to routers of the
corresponding transport protocol (for example, LonWorks router, IP router).
In most cases it is not necessary to divide a BACnet/LonTalk network into several
LonWorks segments (ALN). However, if it does prove necessary, it is not possible
to use a LonWorks router, because this limits the length of the data packets. An L-
switch (Loytec) can be used as a router on the ALN.
BACnet MS/TP networks cannot be segmented, because there are no associated
routers.
With BACnet/IP some IP segments may be connected by IP routers. Since the IP
router prevents broadcasting, the connection must be activated with the BACnet
Broadcast Management Device (BBMD).
Physical segment Physically, (cable) networks cannot be expanded as desired. Depending on
electrical transmission properties and the data link layer based on it, repeaters
must be added at specific cable lengths to amplify the signal. This divides the
network into multiple, physical segments. A repeater does not impact the
transmission protocol; it merely electrically connects two physical networks.
Dividing up the network into several physical segments may be necessary in
LonWorks technology.
See RXC Installation Guide (CA110334).
The physical segments are connected with physical or logical repeaters. Due to the
limited buffer size of logical repeaters, only physical repeaters may be used on the
ALN. Only one physical repeater may be located between any two nodes.
MS/TP is transmitted on a two-wire cable as per EIA-485/RS-485*. The length of
the physical segment can be max. 1,200 m and can be extended with EIA-485
repeaters.
*TIA standard (Telecommunications Industry Association): TIA-485-A Electrical
Characteristics of Generators and Receivers for Use in Balanced Digital Multipoint
Systems (ANSI/TIA/EIA-485-A-98) (R2003)
Desigo site A site is an independent and self-contained logical entity within the building
automation and control system. This type of structuring is not defined by BACnet,
and is therefore largely independent of the BACnet network topology. The BACnet
devices bound to a site can therefore be placed anywhere within a BACnet
internetwork. A site cannot extend across a PTP connection. Communication
occurs only within the site, but data can be exchanged with any device on the
BACnet internetwork.
Only automation stations (PXC/PXC3) and LonWorks system controllers
(PXC...D+PXX-L11/12)) are assigned to the sites, by special structuring of the
Device ID and Device Name. SX Open and Desigo S7 cannot be assigned to a site.
These products are considered third-party devices for the purposes of a site.
192 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
BACnet Architecture (MLN & ALN)
13
VMAC
BVLL BZLL
BVLLv6
ISO8802-2 Type 1 LonTalk
MS/TP PTP
Data Link Layer UDP/IP UDP/IPv6 (IEEE802.2) (EIA 709.1)
ZigBee
ISO8802-2 Type 1
(IEEE802.2)
Ethernet Ethernet
Physical Layer IEEE TP/FT 10
ISO8802-3 ISO8802-3 ARCNET EIA-485 EIA-232
802.15.4 (EIA-709.1)
(IEEE802.3) (IEEE802.3)
Application layer
The BACnet application layer defines services, objects and their characteristics.
From the network viewpoint, the Device object is important. The object ID and the
object name must be unique within the BACnet internetwork.
Application Layer
Network Layer
0000000001 xxxxxxxxxx
(1...999)
193 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
13 BACnet Architecture (MLN & ALN)
Device name The device name is the object name of the BACnet device object.
Guidelines Different rules for object names apply for configuring TD (Technical Designation),
UD (User Designation), or FD (Free Designation):
● The TD is generated from predefined partial names, separated by an
apostrophe ('), that show the technical hierarchy with plant, partial plant, and
component. The TD is supplemented by site name and pin name.
● The names may consist of upper- and lowercase letters and numbers 0 to 9.
The site name is separated by a colon (:) and the pin name by a period (.). The
maximum total length is 30 characters.
● The UD is formed similar to the TD based on partial names. However, users
determine the partial names, structure, and separators. The names consist of
upper- and lowercase letters, numbers 0 to 9, and separators, such as _-;=’,
etc. The maximum total length (including site name and pin name) is 80
characters.
● The FD is a freely assigned name consisting of letters, numbers and a few
special characters, limited within the system only by uniqueness and length.
The maximum total length is 80 characters, ten of which, plus one separator,
are reserved for the site name.
Class A No rules
Class B1 Meaningful text for the user (this text is used as a reference
for the alarm recipient)
Class B2 Model name + device ID Model name + “ “ + 8 character device ID (hexadecimal). The
device name for temporary devices is generated
automatically.
Class C Site name + automation station name Site name + “:“ + automation station name
Category Site number Device number Device ID Site name Device name Device name
A – 1 0x02000001 – Third-party 1 Third-party 1
B2 – 15 0x02100401 – – PXM20TMP0210040f
194 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
BACnet Architecture (MLN & ALN)
13
Category Site number Device number Device ID Site name Device name Device name
C 1 3 0x02200403 Cham PXC... #1 Cham:PXC... #1
Table 49: Examples from the topology at the beginning of the chapter
BACnet device The BACnet device parameters are written to the devices during commissioning.
parameters These parameters include the following values:
Designation Description
Max APDU Length Accepted Maximum length of application message (Application Protocol Data Unit) supported for this
device. The length depends on the transport medium used, and the capacity of the device
buffer. The length of the APDU must always be less than the length of the smallest NPDU
(Network Protocol Data Unit) between the different bus subscribers.
Beispiel There are two IP networks linked by a PTP connection. The two IP bus subscribers could have
a maximum APDU length of 1476 octets. However, since the maximum NPDU length of the
PTP connection is 500 octets, the maximum APDU length of both devices must be set to 480
octets.
Range: 1000...5000 ms
APDU Timeout Timeout for an acknowledged message. This value must be identical throughout the
internetwork.
Range: 1000...5000 ms
Number of APDU Retries Number of retries in the event of an APDU or APDU segment timeout. This value must be
identical throughout the internetwork.
Range: 1...5
Default value: 3
Window size To transfer large data packs, BACnet uses the windowing algorithm. Windowing
means that instead of acknowledging individual segments separately, the
acknowledgement applies to a specific number of segments, referred to as a
window.
Definitions for Desigo The window size is permanently set to four for all Desigo devices, so that for
segmented messages, only every fourth segment is acknowledged.
Network layer
The most important information in the network layer is the network number of the
BACnet network.
195 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
13 BACnet Architecture (MLN & ALN)
Application Layer
Network Layer
Network number The network number is the unique identification of the BACnet network. There are
stationary and temporary networks:
● Stationary networks are defined during commissioning and then remain
unchanged.
● Temporary networks are created when a tool (for example, XWP/ABT) dials
into a network via PTP.
Range/Value Description
0 Reserved for applications with only one BACnet network in a BACnet internetwork, that is, where there are
no BACnet routers.
1...65280 Network number for stationary BACnet networks. You can select any network number in this range.
We recommend that you form categories, for example:
65281...65534 Reserved for temporary BACnet networks. Not yet used in Desigo.
Router parameters The router parameters are written to the BACnet router during commissioning. The
following information is required for each port (logical connection to network):
Designation Description
Network Number Network number of the directly connected network.
Max NPDU Length Max. message length supported in this network. This value depends on the transport medium
used.
Default: 228
Default: 501
Default: 1497
Hop counter Every BACnet that is routed to another BACnet network has a hop counter. The
counter reading is reduced by one with each pass of the BACnet router. When the
counter reads 0, the message will not be routed further. This prevents continuously
circulating messages.
196 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
BACnet Architecture (MLN & ALN)
13
Definitions for Desigo For Desigo the hop counter is initialized with a fixed value of 5. This means that a
message can pass through a maximum of four BACnet routers.
Application Layer
Network Layer
Addressing under Physical address, neuron ID: The Neuron ID is the physical address for a
LonWorks technology LonWorks device. It is a unique 48-bit (6 byte) identifier which is assigned to each
neuron chip during manufacturing.
Logical address: The logical LonTalk address is written to the LonWorks node
during commissioning on the network side.
Domain ID: The domain ID is the highest unit in the LonWorks addressing system.
Data can only be exchanged within a domain. A gateway is required for inter-
domain communication. The domain ID can be 0, 1, 3 or 6 octets in length. A
domain can consist of up to 255 subnets.
Subnet ID: The subnet is a logical collection of up to 127 nodes within a domain.
The bus traffic within a subnet can be kept local by using BACnet routers. Subnets
must never be defined across a router.
Node ID: Unique identifier within the subnet. Each node can be addressed uniquely
within a domain by the subnet ID and the node ID.
Group ID: The group address is a type of addressing. The group address is not
used in BACnet.
On the ALN, the following rules apply to Desigo:
Subnet ID 1…255 The subnet ID is a consecutive number that starts with one. The subnet ID
is incremented by one when a subnet is full (no free node IDs).
Node ID 1…100 This range is for automation stations (PXC), system controllers (PXC...)
and system devices (BACnet routers).
121…127 Temporary operator units and tools (XWP/ABT) look for a free node ID in
this range.
197 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
13 BACnet Architecture (MLN & ALN)
Application Layer
Network Layer
Below the BVLL, BACnet relies on UDP (User Datagram Protocol). Unlike TCP
(Transmission Control Protocol), UDP supports broadcast messages. The
connection monitoring (carried out by TCP) is resolved in the Application Layer.
All media, such as ethernet, are available if supported by IP as physical layers.
For detailed information on the IPv6 data link layer, see Ethernet, TCP/IP, MS/TP
and BACnet basics (CM110666).
IP addresses The IP address of stationary and temporary operator units can be set automatically
via DHCP (Dynamic Host Configuration Protocol) provided that there is a DHCP
server in the network. The use of DHCP is not recommended with automation
stations and BACnet routers. DHCPv6 is currently not supported for IPv6.
DHCP is not allowed for devices using integrated BBMD functionality.
The IP addresses must be agreed upon with the IT department.
RFC1918 defines three specific address areas for private networks. IP addresses
within these ranges are not routed:
10.0.0.0 - 10.255.255.255 Subnet mask: 255.0.0.0
172.16.0.0 - 172.31.255.255 Subnet mask: 255.240.0.0
192.168.0.0 - 192.168.255.255 Subnet mask: 255.255.0.0
For IPv6, IP addresses and private address ranges are defined differently. See
Ethernet, TCP/IP, MS/TP and BACnet basics (CM110666).
IP address: Host address of the network subscriber.
Subnet mask: Subnet mask of the IP segment in which the device is located. This
value must be aligned with the other IP devices.
The subnet mask is required for the identification of broadcast messages and for
communication across IP segments. The subnet mask and target IP address
enable the transmitting IP device to decide whether the data packet can be
delivered directly to the target device or if it must be forwarded via the default
gateway.
For IPv6, the subnet mask corresponds to the network prefix. See Ethernet,
TCP/IP, MS/TP and BACnet basics (CM110666).
Default gateway: IP address of the IP router. This value is relevant for
communication across IP segments.
UDP port number For BACnet/IP to use UDP, a UDP port number must be defined. Only devices with
the same UDP port number can communicate with each other.
Port numbers are divided into the following classes by the IANA (Internet Assigned
Numbers Authority):
● Well Known Port Numbers: Fixed port numbers assigned by IANA (0… 1023)
● Registered Port Numbers: Numbers registered with IANA (1024…48151)
● Dynamic and/or Private Ports Dynamically assigned or privately used port
numbers (49152…65535)
198 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
BACnet Architecture (MLN & ALN)
13
Designation Description
IP address IP address of the BBMD.
Broadcast mask If the BBMD is to be addressed via direct broadcast (one-hop distribution) the subnet mask of the
BBMD must be specified. Since not all IP routers support this mechanism, direct broadcasts are
not supported by default. Two-hop-distribution is always possible. The broadcast mask is then
255.255.255.255.
Not required for IPv6.
Foreign device A foreign device is a (remote) BACnet device in a remote IP segment. It registers
with a BBMD in order to send or receive broadcast messages. Registration with a
BBMD involves making an entry in its Foreign Device Table (FDT). The registration
must be renewed at regular intervals.
199 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
13 BACnet Architecture (MLN & ALN)
The foreign device does not send broadcast messages, but passes them as
unicast messages to the BBMD for distribution. The BBMD in turn passes incoming
broadcast messages as unicast messages to the foreign devices in its FDT.
In the Desigo system, Desigo CC, XWP/ABT, and PXM20-E can be operated as
foreign devices. IPv6 does not support foreign devices
Examples from the Desigo ● IP Segment 1: Desigo CC 1 does not have to be configured as a foreign device,
topology because this IP segment contains a BBMD.
● IP Segment 2: PXM20-E does not have to be configured as a foreign device,
because this IP segment contains a BBMD.
● IP Segment 2: Desigo CC 3 does not have to be configured as foreign device,
because this IP segment contains a BBMD.
● IP Segment 3: This segment only contains Desigo CC 2. To enable Desigo CC
2 to receive and send broadcast messages, it must register with a BBMD as a
foreign device. It does not matter with which BBMD it registers.
Foreign device If a BACnet device operates as a foreign device, the IP address and UDP port
parameters number of the BBMD must be specified.
Designation Description
IP Address of BBMD IP address of the BBMD with which the foreign device registers.
UDP Port of BBMD UDP port number of the BBMD with which the foreign device is registered. The default is 0xBAC0.
The recording interval (Time-To-Live) for Desigo products is set at 300 seconds (=
5 minutes).
Application Layer
Network Layer
PTP connections are only possible between Desigo CC, XWP/ABT und PX. PTP
connections between PXs are not permitted.
PX devices which can be reached via PTP always belong to a separate site. With
reference to the topology at the beginning of the chapter, the site named Baar must
not be combined with the sites named Zug or Cham. Several PXs per site can be
used as half routers. When establishing a communication, the best-performing
connection is always selected. Redundancy is not allowed, that is, several
simultaneously active connections in a given BACnet network are not allowed.
With Desigo CC, a separate, independent, internal BACnet internetwork is created
for each Data Link Layer type. Routing between LonTalk, IP or PTP is therefore not
possible.
The following parameters are required for each half router:
200 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
BACnet Architecture (MLN & ALN)
13
Designation Description
Local network number The BACnet network number to which the half router belongs.
With PX, the local network number is the same as the device's own network number.
Desigo CC supports all three different Data Link Layers (IP, LonTalk and PTP). They are handled
internally as independent BACnet internetworks. This means that routing between the different
Data Link Layers is not possible. Therefore, the local network number can be allocated to IP
and/or LonTalk independently of the networks. However the local network number must be unique
among all networks which could possibly be reached from Desigo CC via a PTP connection.
Recommendation:
If Desigo CC has an additional Data Link Layer (IP and/or LonTalk), the local network number of
this network should be used (example in the beginning of the chapter: For Desigo CC 2, the local
network number of BACnet network #4 should be adopted).
In Desigo CC with only one PTP connection, the local network number must be in the range 1000
to 1099. (Example: Desigo CC 3 -> #1000).
COM parameter For the PX half router, the COM port to which a modem or null modem is connected must be
specified.
Modem parameters The modem parameters contain individual settings for the relevant modem types. Predefined
parameter sets are available for the PX half router.
The following parameters are required for each PTP connection starting from a PX
half router:
Designation Description
Remote network number This network number determines the BACnet network in which the remote partner device is
located. In the Desigo system this is the local network number of Desigo CC.
Remote area name The remote area name stands for a peer-to-peer remote network number of the network
containing Desigo CC.
During configuration, the remote area number lets you assign a clear name to the (remote) alarm
recipient rather than a network number.
Telephone number The telephone number for access to the remote device.
Performance index The performance index refers to the quality of the router data connection. If multiple PX half-
routers are available in a PX site, and if a connection to a remote network is to be established, the
router with the best performance index is selected. If no connection is established, the router with
the next best performance index automatically tries to connect.
For each PTP connection in Desigo CC, only the telephone number needs to be
defined.
Application Layer
Network Layer
201 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
13 BACnet Architecture (MLN & ALN)
Addressing MS/TP Each device has its own unique MAC address. The MAC address is one octet long
devices and defined as follows:
● 0-127 reserved for master devices
● 0-254 reserved for slave devices
● 255 reserved for broadcasts
The MAC address can be set via DIP switch (hardware) or related configuration
tools (software) for each device.
Structuring MS/TP is transmitted via two-core cables as per EIA-485/RS-485. The maximum
length of a segment is 1200 meters. 64 devices are allowed on a segment.
Different segments can be interconnected via repeaters to form a larger EIA-485-
network. The specific electrical properties, such as polarity, common signal ground,
terminating resistances, etc. must be taken into account. The actual, possible
network size and maximum transmission rate primarily depend on the network
structure. Establishing a network in daisy chain form is best.
BACnet/IP
10664Z42_06
MS/TP ...
Router
PXG3
DXR2 DXR2 DXR2 DXR2
BACnet address
Every BACnet device in the BACnet internetwork can be accessed via its BACnet
address.
The BACnet address is defined by the BACnet standard and comprises the
following elements:
202 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
LonWorks Architecture (ALN)
13
Designation Description
Network number Network number of the BACnet network in which the device is located. The network number is
only parameterized on devices with BACnet router functionality (including half router) and is
implicitly valid for all BACnet devices in the BACnet network.
BACnet MAC address Address specific to the transport protocol. This address is written to the device in the
commissioning phase.
BACnet MAC address for:
BACnet device address Each BACnet device has a device address. This address is written to the device
during the network commissioning process. The BACnet device address is unique
within the BACnet internetwork. The term BACnet device address is an in-house
term rather than an official BACnet term.
Designation Description
Device ID Object identifier of the BACnet device object. The device ID is unique within the BACnet
internetwork.
Device name The object name of the BACnet device object. The device name is unique within the BACnet
internetwork.
Structure
The following figure shows the structure of a Lon network in the FLN
203 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
13 LonWorks Architecture (ALN)
Key:
System devices
Gateway The gateway links trunks. It operates on the application layer of the ISO/OSI layer
model. The following LonWorks gateways are available:
The RXZ03.1 point coupler provides a fixed number and type of LonTalk network
variables (NV). Each side of the point coupler belongs to a trunk or LonWorks
project. The point coupler can be used to implement time-critical connections
between two trunks. The point coupler integrates third-party devices that have
been engineered with a different tool.
Loytec L-Proxy and Sysmic XFM-LL are freely programmable point couplers. The
XFM-LL device may be used, when depicted like a standard third-party device
(configuration via its own tool).
The PXX-L.. extension modules let you connect LonWorks devices to the PXC..D
modular series. This adds the grouping, schedule, trend, and alarm management
functions to the RXC room automation and allows the mapping of data points to
BACnet/IP or BACnet/LonTalk.
204 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
KNX Architecture (ALN)
13
Router The LonWorks router operates on the network layer of the LonWorks protocol. It
filters data packets based on their subnet ID or group ID. Subnets or groups must
never be defined across a router, that is, the subnet IDs and group IDs at each end
of the router must never be the same. Routers are used where there is heavy local
network traffic. They allow the unloading of unaffected devices from the network
traffic. In Desigo there are no large LonWorks networks, as the FLN is divided into
trunks. Routers are only required in exception cases.
L-Switch (Loytec) The L-Switch filters the package on the basis of the subnet/node ID or group ID. It
automatically learns the topology and forwards the data packets accordingly. The
L-switch does not have to be configured. Unlike the router, there is no need to take
account of any addressing limits (allocation of Subnet ID or Group ID).
Physical repeater LonWorks has physical and logical repeaters. The physical LonWorks repeater
does not filter the data packets. It regenerates the electrical signal. One physical
LonWorks repeater can be used in the path between any two devices within a
segment.
In logical repeaters, the data packet is processed by the neuron chip. This enables
several logical repeaters to be connected in series. The disadvantage is that the
logical repeater must be configured, and that owing to the limited size of the buffer,
it cannot be used for large data packets, that is, for BACnet/LonTalk.
Structure
The following figure shows the structure of the KNX network:
● KNX: KNX devices, for example, third-party KNX
● PX KNX: Automation station PXC001.D or PXC001-E.D and PX KNX firmware
205 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
13 KNX PL-Link Architecture (FLN)
Backbone line
Area 1 Area 3
EIB EIB
PX KNX
(3.1.y) EIB EIB
EIB EIB
Line 1 Line 2
Figure 164: KNX network topology
Line A KNX network consists of lines. Up to 64 devices can be connected to each line.
Area Up to 15 lines can be connected to a main line via line couplers (LC). This is called
an area.
Backbone line The topology can be expanded by means of a backbone line. Up to 15 areas can
be connected to the backbone line via backbone couplers (BC). Technically, these
are the same devices as line couplers.
Line/Backbone couplers Couplers separate the areas and lines. Couplers keep the bus traffic within bounds.
Datagrams that are only needed on one line should not create a load on the entire
network and hence have to be confined to that line. Respective filter tables are
created (ETS) when setting up the project/network.
Engineering Tool Software The KNX Engineering Tool Software (ETS) is used to create KNX projects. A bus
(ETS) interface is required to commission the devices with ETS.
For a detailed description of the KNX topology, see
http://www.knx.org/fileadmin/template/documents/downloads_support_menu/KNX_t
utor_seminar_page/basic_documentation/Topology_E1212c.pdf.
System Devices
PX KNX The PX KNX system controller maps KNX devices to BACnet objects. PX KNX also
supports different system functions, such as grouping, scheduling, alarming,
trending, etc.
The system controller must be positioned correctly in relation to the topology and
the load on the bus caused by the devices and connections (group addresses).
Bus power supply Each line and each area must include a bus power supply.
206 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
KNX PL-Link Architecture (FLN)
13
Siemens field devices can be connected to the KNX PL-Link using the KNX PL-
Link plug & play capability. KNX PL-Link devices are configured using the Desigo
tools. The KNX commissioning software (ETS) is not needed.
One or more KNX PL-Link devices are connected to the trunk of the corresponding
room automation station in a line topology.
A comprehensive library with preconfigured devices supports simple engineering.
The PXC3 room automation station allows for simultaneous integration of devices
with KNX PL-Link and KNX S-Mode on a single bus line. Devices with KNX S-
Mode are additionally commissioned using ETS.
Structure
The following figure shows an example of a logical network topology with KNX PL-
Link devices, a room automation station and several rooms.
BAC network
Automation
station
Power supply concept The PXC3 and DXR2 room automation stations have an integrated KNX power
supply to supply their trunks with the corresponding KNX PL-Link devices. This
allows simple installations, for example, an automation station with one or a few
room units, without an extra device for power supply to the KNX PL-Link network. If
many KNX PL-Link devices are connected, the power supply at the room
automation stations is shut off and an external KNX power supply must be used.
The following figure shows the concept of a built-in power supply unit (PSU):
Automation station
PSU
System devices
Third-party KNX devices can be integrated in KNX PL-Link networks via KNX S-
mode. The KNX Engineering Tool Software (ETS) is necessary to engineer and
commission these devices.
DXR2.M.. automation stations cannot integrate KNX S-Mode devices.
207 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
13 DALI Architecture (FLN)
Structure
A DALI system can be made up of control gear, control devices and bus power
supplies.
Control gear Control gear usually contains the power control circuit to drive lamps, or some
other type of output, such as on/off switching or 1 to 10 V analog signals.
Control devices Control devices can provide information to other control devices, such as light
intensity information, and can send commands to control gear. Input devices are a
type or a part of a control device that provides some information to the system,
such as a button press or movement detection. DALI application controllers are
also control devices, for example, they can send commands to control gear to
modify the lighting.
Bus power supplies At least one bus power supply must be present in a DALI system. This is
necessary to allow both communications on the bus, and to power any bus-
powered devices. The bus power supply does not need to be a separate unit – it
could be part of another device such as a LED driver or a sensor.
Bus wires A DALI system also includes the bus wires that are used to connect the DALI
terminals of the various devices in the system.
Addressing DALI allows the flexible addressing of devices.
At the simplest level, all devices are addressed simultaneously by broadcast
commands. This allows the control of lighting in a similar manner to 1 to 10 V
analog control, without requiring any configuration of the individual devices. If a
level (Direct Arc Power Command) is broadcast, then all control gear will act upon
that command, changing their output to the same new level.
With simple configuration, DALI devices can be given one of 64 short-addresses.
This allows individual control, configuration and querying of any single device in the
system.
DALI devices can also be group addressed. For example, a DALI LED driver could
be programmed to be in any combination of the 16 available groups. When a
command is sent to a group, only devices that are in that group are addressed.
System devices
PXC3...A The PXC3…A automation stations have a DALI bus for connecting up to 64 DALI
ballasts/drivers.
208 | 377
Siemens CM110664en_03
2017-09-18
Network Architecture
DALI Architecture (FLN)
13
PXC3.E16A The PXC3.E16A room automation station is optimized for lighting applications. It
has an onboard DALI interface for connecting up to 64 electronic ballasts or LED
drivers
209 | 377
Siemens CM110664en_03
2017-09-18
Remote Access
14 Remote Access Methods
14 Remote Access
The remote access is an access to resources via the internet or a point-to-point
connection.
The remote access is used to:
● Connect a remote location to Desigo CC, for example, for on-call service,
managing different locations or support by a specialist
● Remotely access Desigo CC
● Make a change, create an extension or search for errors using an engineering
tool
● Forward alarms as text messages or emails from PX Web, TP Web, or Desigo
CC
10664Z45en_02
Desigo CC
Metro ethernet
Modem
TV cabel
Mobile phone
BACnet/IP
Web interface
Automation station
Figure 167: Remote access methods
The following access networks can be used for the remote access:
● Telephone network
● TV cable network
● Other cable-based networks, such as metro ethernet
● Mobile networks
● Other RF-based access networks
210 | 377
Siemens CM110664en_03
2017-09-18
Remote Access
Choosing a suitable Access Technology
14
● There are different ADSL and VDSL variants. The DSL variants are country-
specific.
● The uplink (that is, the data flows from your private home or project to the
internet) and downlink (that is, the opposite direction) bandwidth are different.
Take this into account when you select a suitable internet access.
● The DSL line in parallel can be used for telephone calls.
● If you want to use telephony on the same line, you need a splitter in addition to
the DSL modem.
TV cable-based access
● This access is similar to DSL. You can access the system remotely via a cable
modem provided by the cable network operator.
211 | 377
Siemens CM110664en_03
2017-09-18
Remote Access
14 Choosing a suitable Access Technology
I want to use the remote access for... DSL LTE & GPRS TV cable Metro RF-based
UMTS ethernet
Remote access to Desigo CC o/+ o/+ - + + o/+
Alarm forwarding + + + + + +
Table 60: Which remote access technology is suitable for which task?
Key:
+ Good
The different access technologies are available with different bandwidth, for
example, DSL (o/+) can be fast or relatively slow.
Costs The costs are divided into monthly basic costs and usage costs. To optimize costs,
analyze your usage profile, that is, how many times per month do you use it and
how much data do you exchange per use.
A data flat rate ensures that the costs are capped. Choosing an inappropriate rate
plan for a mobile subscription could result in high costs.
Availability RF-based links and all mobile network-based transmission standards can suffer
from transmission problems due to bad weather especially at the cell border. The
bandwidth that can effectively be used in the project can vary over the day,
because the bandwidth is shared by all users. The bandwidth variations for cable-
based technologies are lower.
Recommendations To ensure a reliable remote access, use cable-based technologies even if the cost
is slightly higher. Use mobile networks or RF-based systems only if no alternative
is available. If you require a high availability remote access, you can additionally
establish a mobile network-based link as a fallback solution. To do this, use a
router that offers both a DSL and a GPRS/UMTS/LTE modem.
Every remote access can be attacked. Note the safety measures in the document
IT Security in Desigo Installations (CM110663).
Access to the PXC..D/-U automation stations via Xworks Plus (XWP) can be
protected with a password (password property for remote access [RemAcpwd]).
You can enter the password in the Device Property dialog in XWP.
Migrating from an analog Analog modems should not be used in new installations and are not future-proof
modem-based method due to the migration of the networks to Voice over Internet Protocol (VoIP).
ISDN also is not a future-proof technology and should therefore not be used.
If DSL is available, use DSL. Otherwise, use other cable-based internet access
networks. If you cannot use such a network, use a mobile network or an RF-based
access.
If a project is based on LON, use the PXG3.L router, to connect the remote access
on the IP side of the router.
212 | 377
Siemens CM110664en_03
2017-09-18
Remote Access
Technical Details
14
TV cable-based method
The operator provides the modem. Sometimes, you have to configure the modem.
Usually, the cable operator provides a preconfigured modem or the modem
configures itself automatically when you connect it for the first time. The modem
has an RJ45 connector to connect it to the IP network (the router) or a built-in
router. The router must be configured. Sometimes you need to enter an access
code received from the operator.
A separate DSL splitter for splitting TV and data signals is not necessary.
Metro Ethernet
Metro ethernet is usually not implemented in a BACS project and is therefore not
described in this document.
213 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
15 Technical Details
15 Management Platform
A building automation and control system encompasses all control functions of one
or more buildings.
In addition to typical HVAC systems, there is a need to integrate other areas of the
building, such as lighting and blind control systems, fire alarm systems and access
systems.
At completion the system comprises one or more superordinate management
platforms that let you centrally operate and monitor the individual plants, while
each plant's technical building equipment still continues to work autonomously.
Figure 168: Desigo CC lets you operate and monitor the plant
214 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
Technical Details
15
Main server The main server contains the project database and the software that monitors and
commands the system network. Clients connect to this server to monitor and
control the facility. If the same computer runs Microsoft IIS, the installation provides
web clients with access to the facility. The Desigo CC server installation always
includes an installed client with a user interface for monitoring and controlling the
facility. The main server has interface connections to the field (either directly or
using FEP) and provides a centralized database and other services to the
connected clients. The main server can support a number of clients that are
connected using a network (LAN) or Intranet (WAN).
Installed client The Installed Client is typically used for operators who are focused entirely on
monitoring and managing building systems. In this configuration, software
components used for event management are locked in place and cannot be moved
or covered by other applications. This ensures that critical events are never missed
or hidden. Installed Clients can optionally be configured to run in a closed mode
where only Desigo CC and other specifically identified applications are allowed to
run. In closed mode, the workstation is dedicated to running Desigo CC, with
access to the Start menu or other operating system and customer applications
available only to administrative users.
Web client (browser client) The web client is deployed on the intranet with full trust and allows access to local
resources. The system runs in the Internet Explorer browser (using HTTP or
HTTPS as communication protocol) and is downloaded on demand each time the
user launches the system as web application. When working in a browser, you can
have the same capabilities as those working on an Installed Client, or can be
restricted to have different access when connected remotely.
As web clients require low latency and high network bandwidth, they are
appropriate for intranet use. We do not recommend it for internet use.
See Desigo CC Installing the Web Client Application Certificate (A6V10415479).
215 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
15 User Functions
Windows app client The Desigo CC Windows App Client looks like the standard system software, but is
(ClickOnce) a light application that can be downloaded from the Desigo CC server when
connecting through a browser. When the Windows App Client is downloaded, it
runs like any other Windows application on the desktop. It can be launched from
the Start menu, desktop icon, quick-launch toolbar, and so on. This deployment
does not require administrative privileges. The Windows App Client runs in its own
pane, without the overhead of the internet browser application and menus.
Web server To use the Desigo CC Web and Windows App Clients, you must install the web
server. To install the web server, you must first install Microsoft IIS on the web
server computer. Usually the web server is on the Desigo CC server. It might be
located on a separate computer, if the customer's IT department requires the web
server to be installed in a separate controlled environment, or if it is preferred not to
use the resources of the system server for the Microsoft IIS tasks.
The web server lets you to access the system using the intranet and a web
browser. You can add only one web server. It lets you download all files required
for the Web Client and Windows App Client environments. It provides a system
web page to access the Web Client, the Windows App Client, and the system
documentation in the Internet Explorer browser. It also represents the endpoint of
the communication with the system server.
Front End Processor A Front End Processor (FEP) is a computer that provides additional connections
between building level devices (such as field panels) and Desigo CC. By providing
additional connections to the building level network, an FEP enables load
balancing for the network-based processing for a Desigo CC system.
System Dimensioning Desigo CC covers a wide variety of solutions so that it is impossible to define
Guide simple rules for determining the size. Therefore, a system dimensioning tool is
available that estimates the system size and disk storage space on the basis of
information available at the time of the offer, for example, the number and type of
physical points and the expected history data base contents.
216 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
User Functions
15
Scheduling The Scheduler allows you to schedule events for Desigo CC and field panels at
your facility. You can create daily or weekly schedules for Desigo CC and BACnet
devices. You can fully configure and monitor standard BACnet schedules,
calendars, command objects, and workstation-based schedules that can be used
to support systems without built-in scheduling capabilities. Schedules are
automatically associated with systems they control, so you can quickly navigate to
the schedules of any selected object. A Timeline Viewer lets you view the details of
multiple Desigo CCs and field panel schedules simultaneously, spanning a range
of time.
Reports The Desigo CC reporting tool includes standard reporting templates and lets you
create fully configurable reports with custom logos, headers, footers, and layouts
that include tabular and graphical system information. You can schedule reports
and save them in CSV or PDF formats.
217 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
15 User Functions
Event management Event management allows you to manage events throughout the system. You can
monitor and manage the progress of each event from initiation through resolution.
The full history of each event issue is recorded, and you can generate event-
related reports that you can view, save, and print.
Log Viewer The Log Viewer application provides an historic log of all user and system events
and activities that have occurred. You can retrieve these historic events and
activities for further analysis and investigation using sorting and filtering. Log views
can be saved and exported if required.
Detailed log The detailed log allows users to view the most recent records for any selected
object. The same content filtering and sorting functionality available in the Log
Viewer is possible in the detailed log.
Remote notification You can configure Desigo CC to automatically or manually send email or SMS
messages to specific recipients.
You can specify:
● What events the recipients should be notified for and when
● How notifications are escalated from one recipient to another until a notification
message is responded to
● If a message is periodically sent to the operators stating that the system is
running normally
● Which devices are used for the notification
Macros Macros are predefined lists of commands that enable a user to send out a group of
commands to specified devices with a single action. Some macros can be started
manually while others may be part of schedules defined for time-based functions or
automatic reactions. Macros are also used by the system to perform multiple
command actions. These predefined system macros are applied to specific control
actions, such as block commands to fire control panels and system backup
functions.
Reaction Processor Reactions are automations programmed in the system, so that when a specific
situation occurs on site, a command or a series of commands is automatically
executed.
You can define actions to be executed automatically when specific conditions are
verified. Conditions can be based on time, on events, on a change of values, or on
218 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
Main Components
15
a combination of some or all. When conditions are met, the Reaction Processor
executes a pre-configured list of commands.
Document management Desigo CC can handle the different types of document templates used in the
project. You can configure document templates in PDF, RTF, TXT, XLS, and HTML
format.
System Browser The System Browser displays objects in the building control system through
various views. You can search and filter objects, display object names and
descriptions, and drag objects into Trends, Schedules, and Reports.
History Database (HDB) Historical data is stored in an access-controlled MS SQL Server database. The
System Management Console lets you create a project History Database (HDB)
and link it to the active Desigo CC project on the main server. The history database
is used to log a wide range of user and system activities, such as:
● User and system activities
● Alarms and their treatment
● Faults that have occurred and are handled as batch messaging
● Values that are logged as trends
Project database The runtime data (process image) and the engineering data are stored in a file-
based database in a subdirectory of the project directory. The data is unencrypted
and database access can only be prevented by restricting access to the database
files. The project directory needs to get shared when deploying installed clients. It
is therefore important to restrict access on the db folder in the project directory to
the Windows account running the Desigo CC main server.
Desigo CC uses the Microsoft SQL database software. Microsoft SQL Express is
included on the product installation DVD (Microsoft SQL Server 2008 R2 Service
Pack 2, Express Edition, version 10.50.4000.0). Alternately, you can use an
existing Microsoft SQL Server installation (same version 10.50.4000.0). In this
case, the Desigo CC Installer will skip the Microsoft SQL Server installation. In both
219 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
15 Access and Security
Microsoft SQL Server cases, Microsoft SQL must first be installed and running on the computer where
the Desigo CC main server will be installed.
Microsoft IIS server A Microsoft Internet Information Services (IIS) server for Web Clients and Windows
App Clients can be installed on the Desigo CC server or on a separate installation
(web server).
License Manager Licensing ensures the operation of the system within the agreed system limits.
Only the system is allowed to change license data.
If a license becomes temporarily unavailable (for example, due to network
connection issues) the system continues to run fully operational for a grace period.
The system continues to check for the license and shuts down at the end of the
grace period, if none of the license checks succeed.
Exceeding the limits of the license (for example, by integrating more field system
data points than stated in the license) puts the system into courtesy mode. Phases
of courtesy mode accumulate until a total duration of 30 days is exceeded, then the
server shuts down. Unless new licenses are made available, after a manual restart
the system again goes into courtesy-mode exceeding and shut down.
Any unauthorized attempt to modify system license data directly in the database
(for example, changing the remaining time of a specific license mode) shuts down
the system.
220 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
Event Management
15
We recommend that you do not use wireless input devices. If you must use
wireless input devices, use only devices with proven encryption.
Communication ports and Which ports are used depends on the actual deployment and subsystem
protocols integration of the whole system.
See Desigo CC System Description (A6V10415500).
Event Bar When using profiles for critical event management, you can collapse the Event List
into a condensed list of event buttons in an area called the Event Bar, that remains
docked on the desktop for easy access. This lets you keep an eye on the current
situation at all times.
Client profiles To ensure the correct level of event management support for users in any situation,
a workstation and/or users can be easily assigned predefined profiles supporting
casual, intermediate, or dedicated event notification and management.
Fast treatment From the Event List or Event Bar, you can quickly select an event and perform all
the commands (for example, Acknowledge, Reset, Close or Suspend) from the
Event Detail Bar and Event List, without looking at treatment steps, viewing live
video or a map of the alarmed area, etc. The event descriptor (visible when the
Event List is expanded) contains a short description of the next action (which
command to select).
221 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
15 Installation, Setup and Engineering
When event treatment is in progress, you can send the available commands to the
source object causing the event or suspend treatment.
Investigative treatment From the Event List or Event Bar, operators can quickly open the System Manager
with focus on the source of the event, and all information (live video, recent history,
schedules, etc.) related to the event source.
Operating procedures Operating procedures consist of a sequence of steps or actions, which the operator
must, or is suggested to perform with the assisted treatment. For each step of a
procedure, the system provides instructions and operating tools. With appropriate
permissions, you can create, view, edit, or delete operating procedures.
Assisted treatment From the Event List or Event Bar, operators can quickly open the assisted
treatment to guide the operator through pre-configured operating procedures. Each
operating procedure is composed of steps - some of which may be mandatory - for
the user to complete (for example, to see the graphic of the object in alarm, fill-in a
treatment form, or automatically print the information of the event).
222 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
Installation, Setup and Engineering
15
Subsystem integration brought in through any interface, and to provide the same look, feel, and operation
through a common set of applications, without concern for the source of the data.
Desigo CC lets you configure connected subsystems directly and perform typical
automation station functions, such as scheduling and event generation, at the
management platform for connected systems that do not support those functions
directly.
Desigo CC supports the following subsystems:
● Desigo Building Automation system (Desigo PX V5.1 SP; V6)
● Desigo Room Automation system (V1.16; V1.2)
● Simatic S7 (S7-300; S7-400)
● Siclimat-X V4.1
● Sinteso Fire Safety System (FS20 EN MP5.2; FS20 DE MP5.2)
● Sinteso Fire Safety System (STT20 Centralisateur de Mise en Sécurité
Incendie)
● Intrunet Intrusion System (SPC MP3.4, connections using TCP-IP or UDP-IP
supported)
● Video through Milestone Video Management System
● Mass Notification System (Version 2.0) For a list of compatible Mass
Notification devices, please refer to the MNS documentation
● Third-party Building Automation and Fire Safety systems based on BACnet/IP
● Third-party subsystems through OPC (OPC DA V2.05/V3.00 standard)
● Third-party subsystems through Modbus/IP
● Integration through SNMP
● APOGEE Building Automation system (Apogee BACnet V3.1.2; V3.2.4; V3.3;
V3.4)
● XNET FireFinder XLS and MXL fire safety systems (FireFinder XLS V8 and
newer)
● Desigo Fire Safety FS20 UL systems (FS20 UL MP1.x, MP2.0)
Auto discovery Auto discovery lets you discover and import devices, which are already on the
network, into Desigo CC. You can set filters and detect your devices on the
network, which then display in the System Browser. You would typically use this
method for existing jobs, where field panels are already installed and online.
OPC server OLE for Process Control (OPC) is a widely accepted industrial communication
standard that enables the exchange of data between multi-vendor devices and
control applications without any proprietary restrictions. OPC is a client-server
technology and Desigo CC can acts as the server providing data to third party
clients.
Web services Using RESTful technology, Desigo CC provides alarm, object and time series data
via web based services to supervision management platforms or other third-party
external applications.
Language packs The Desigo CC software is delivered in English and can be extended with
additional languages. The following software language packs are supported:
● Arabic
● Chinese (simplified)
● Chinese (traditional)
● Czech
● Danisch
● Dutch
● English (default)
● Finnish
● French
223 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
15 Graphics Libraries
● German
● Italian
● Korean
● Norwegian
● Polish
● Portugese
● Russian
● Spanish
● Swedish
● Turkish
You can install 3 languages simultaneously. Every user can define his user
interface language.
Project and HDB backup Backing up Desigo CC requires saving independent parts on different servers or
PCs. We recommend that you save the backups of your project data to a different
machine from where they originally reside.
Two parts must be backed up:
● The entire customer project data, including all libraries, configurations, object
data (project backup).
● The historic data collected in the history databases (HDB backup).
Backups can be done either manually or by applying a macro in combination with a
management platform scheduler.
See Desigo CC System Management Console (A6V10415497).
224 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
Graphics Engineering
15
225 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
15 Virtual Environment
Graphics Library Browser The Graphics Library Browser lets you toggle between a view that displays all the
available symbols and graphic template objects in your project libraries.
AutoCAD import You can import AutoCAD drawings and select and manipulate the layers of the
AutoCAD drawings during and after the import process.
226 | 377
Siemens CM110664en_03
2017-09-18
Management Platform
Virtual Environment
15
● VMware®:
– Virtualization platform: VSphere 6.0
– Fault-tolerant software: ESXi 6.0b (build 2809209) managed by VCenter
Server Appliance v6.0.0 (build 2793784)
● Stratus®:
– Virtualization platform: KVM for Linux CentOS v7.0
– Fault-tolerant software: everRun Enterprise 7.2
– Virtualization platform: Citrix XenServer 6.0.2
– Fault-tolerant software: everRun MX 6.2 HotFix4 (build 6.2.9125.825-
HF:EA)
227 | 377
Siemens CM110664en_03
2017-09-18
Automation Stations
16 Virtual Environment
16 Automation Stations
The Desigo PX range is based on freely programmable automation stations. They
provide the infrastructure to accommodate and process system-specific and
application-specific functions. The PX range of automation stations comprises the
compact and modular series.
See Desigo PX - Automation system for HVAC and building services - System
overview (CM110756), Automation stations modular series PXC..D, PXC..-E.D,
PXA40-.. (CM1N9222) and Automation stations compact model PXC..D
(CM1N9215).
Control Functions
The D-MAP programming language lets you program and parameterize plants,
using function blocks and compounds. The graphics-based data-flow programming
in Xworks Plus (XWP) lets you implement all the necessary control strategies for
optimum operation.
System Functions
The distributed functions, which ensure the overall functioning and inter-operation
of all plants, are described in the following chapters and documents:
● For alarm strategy, see chapter Alarm Management.
● For time scheduling, see chapter Calendars and Schedulers.
● For access rights and user designations, see IT Security in Desigo Installations
(CM110663).
● For emergency operation and forced control, see chapter Control Concept.
● For wiring tests with Desigo Point Test Tool, see chapter Desigo Workflow,
Tools and Programming.
Cyclical Processing
One PX automation station contains one downloaded D-MAP program. A D-MAP
program cannot run on two automation stations, that is, there are no overlapping
programs across automation stations. A downloaded D-MAP program does not run
automatically. It must be started explicitly and is executed in accordance with the
cyclical processing principle, that is, all D-MAP blocks in an automation station are
processed in a repeating cycle.
Cycle time A minimum and maximum cycle time is defined for each automation station. If the
processing of all blocks is:
● Shorter than the minimum cycle time, the next processing cycle is delayed until
the minimum cycle time has elapsed.
● Longer than the maximum cycle time, the next processing cycle starts as soon
as possible.
The processing order of the individual blocks:
● Does not depend on their arrangement on the plan (D-MAP program)
● Can be set explicitly when creating the D-MAP program
Process image The values at the physical inputs and outputs are displayed in the automation
station via the process image. There are two instances of the process image:
● The frozen process image does not change during a processing cycle. D MAP
programs only read from or write to this instance of the process image.
● The active process image is continuously connected to the real plant.
228 | 377
Siemens CM110664en_03
2017-09-18
Automation Stations
Device Object
16
AI AO
Read Write
Frozen values
Process image
buffer
Current values
I/O scan
Values read in cycle 1 are processed in cycle 2. Output values calculated in cycle 1
are transferred to the peripherals in cycle 2.
229 | 377
Siemens CM110664en_03
2017-09-18
Automation Stations
16 Device Info Object
The serial number in the row Serial number SN=150120C61487 consists of:
● 15 = Year
● 01 = Month
● 20 = Day
● C = Hardware version
● 61487 = Consecutive number
230 | 377
Siemens CM110664en_03
2017-09-18
Automation Stations
Error Sources and Monitoring Functions
16
Properties for system The device object has an alarm mechanism, because system alarms and system
alarms and system events events, which cannot be assigned to a data point, may occur in an automation
station. The alarm state machine and alarm-relevant connections are mapped to
the BACnet properties of the device object.
Error Effect
Memory error, for example, faulty flash memory Desigo PX stops working.
Failure of backup server recognized by primary server Desigo PX recognizes the fault and transmits the relevant alarm.
Non-critical errors / Non-critical hardware and software errors are identified by Desigo PX and
configuration errors registered as a device object alarm.
Critical errors When a critical hardware or software error occurs, the automation station tries to
restart. If the same error is detected three times within 15 minutes, the automation
station switches to the COMA operating state. If the Fault LED is lit, the automation
station is in the COMA operating state.
Online properties for The values in the Online Properties window in Xworks Plus (XWP) give clues about
diagnostics the operation of the automation station.
231 | 377
Siemens CM110664en_03
2017-09-18
Automation Stations
16 Operating States
232 | 377
Siemens CM110664en_03
2017-09-18
Automation Stations
Operating States
16
Mains OFF
BACnet: Download
required
14: Load
BACnet: Operational
12: Reanimation
COMA 13: Master reset
4: RUN Cmd 15: Delta loading
BACnet: Operational
5: STOP Cmd
Operating states
Mains off ● No power supply
STOP
● I/O scan active
● Ready for wiring test (only possible without D-MAP program loaded) (PXM20,
for PTM modules only)
● D-MAP program processing stopped
● Communication with XWP: Master reset, complete loading and delta loading
allowed
● BACnet communication with Desigo CC and PXM20: ReadProperty,
WriteProperty, Who-Has, COVs, EventNotification, AcknowledgeAlarm
GetEventInformation
● COVs: For values changed by the operator, values cannot be changed by the
program
● Alarming: Alarm monitoring inactive, no new alarms or events are generated
(the device info object can still generate alarms and system events).
Notification of saved alarms and events is possible if recipient lists are set up.
GetEventInformation and AcknowledgeAlarm possible.
● Primary server in the STOP state: Primary server is not active, that is, no life
check, no time synchronization and no replication of global objects
● Backup server in the STOP state: The backup server is not active, that is, no
time synchronization and no replication of global objects by primary server. The
backup server will not accept changes to global objects by a client.
RUN ● I/O scan active
● Wiring test not allowed
● D-MAP program processing active
● Communication with XWP: Master reset and complete loading not allowed,
delta loading allowed
● BACnet communication with Desigo CC and PXM20: ReadProperty,
WriteProperty, Who-Has, COVs, EventNotification, AcknowledgeAlarm
GetEventInformation.
● COVs: For values changed by the program and operator
233 | 377
Siemens CM110664en_03
2017-09-18
Automation Stations
16 Operating States
Transitions
1 Power failure Power failure
2 Power restoration STOP Power restoration. Operating state before power failure was STOP.
Actions (cold start response):
● Cold start I/O scan: Default values for output modules
● Cold-start variable function blocks: Volatile variables are initialized with initial
value. Non-volatile variables retain their last value.
The STOP state is reached when the I/O scan is finished.
3 Power restoration RUN Power restoration. Operational status before power failure was RUN.
Actions (cold start response):
● Cold start I/O scan: Default values for output modules
● Cold-start variable function blocks: Volatile variables are initialized with initial
value. Non-volatile variables retain their last value.
● System event: Power restoration.
D-MAP processing starts when the first I/O scan is finished.
4 RUN Cmd Explicit command via dialog in XWP or BACnet (DeviceObject, Out of service
property [OoServ])
Actions (warm start action):
● Implicit warm start I/O scan: I/O scan continues to run
● Implicit warm-start variables function blocks: All variables retain their last value
● System event: Change to operating state
D-MAP processing starts.
5 STOP Cmd Explicit command via dialog in XWP or BACnet (DeviceObject, Out of service
property [OoServ])
Actions:
● System Event: Change to operating state
● Stop D-MAP processing at the end of current cycle
I/O scan continues.
6 Restart Restart of the automation station due to software error.
Actions (cold start response):
● Cold start I/O scan: Default values for output modules
● Cold start function block variables: Volatile variables are initialized with initial
value. Non-volatile variables retain their last value.
The STOP state is reached when the I/O scan is finished.
7 Restart Restart of the automation station due to software error.
234 | 377
Siemens CM110664en_03
2017-09-18
Automation Stations
Operating States
16
235 | 377
Siemens CM110664en_03
2017-09-18
Automation Stations
16 Data Storage
Summary
Every time the automation station restarts (Powerfail, Reset) a cold start is carried
out.
The operating state is stored as a non-volatile variable.
The operating state is mapped as follows to the system status [SysSta] property of
the device object:
236 | 377
Siemens CM110664en_03
2017-09-18
Automation Stations
Data Storage
16
PXM20
XWP
D-MAP Communication
Application
Flash RAM
Downloading the D-MAP 1. The D-MAP program (code and data blocks) is copied to the flash memory (1a).
program A copy of the data blocks is created in the RAM (1b) for later modification by the D
MAP program.
Read/Write via 2. When writing data, the data is written to the RAM (2a) and the flash memory (2b).
communication system Read access to the data is via the RAM (2c).
Processing the D-MAP 3. The D-MAP program code is read from the flash memory (3a). The program data
program is modified in the RAM (3b). Non-volatile process variables (for example, adaptive
control parameters, hours run, etc.) are written by the function blocks into the flash
memory (3c) at regular intervals (once per day) or saved in the battery supported
RAM.
Starting the automation 4. At each restart of the automation station, a copy of the data (data blocks) is
station created in the RAM (4) from the flash memory (including all communication and D-
MAP changes).
237 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Data Storage
Input blocks Output blocks Value blocks Value blocks for operation
Analog Input (AI, AI RED) Analog Output (AO, AO RED) Analog Input (AVAL) Analog Input (AVAL_OP)
Binary Input (BI, BI RED) Binary Output (BO, BO RED) Binary (BVAL) Binary (BVAL_OP)
Multistate Input (MI, MI RED) Multistate Output (MO, MO RED) Multistate (MVAL) Multistate (MVAL_OP)
Discipline I/O
Program view and system I/O blocks are displayed in two different views:
view ● The program view shows an I/O block with the pins and attributes required for
configuration purposes and to create the program. This is the display format
used in Xworks Plus (XWP).
● The system view shows the I/O blocks as standard BACnet objects. These
BACnet objects and the associated properties are then available to clients from
where they can be operated and monitored.
Desigo S7 In Desigo S7 the Step 7 Manager is used with CFC instead of XWP. PXM20
cannot be used. Use Desigo CC as a client.
All the blocks listed above are implemented in accordance with the BACnet
standard. Therefore additional functions are available, such as alarm management.
These blocks incorporate a mechanism which acts as an alarm source for blocks
238 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
General Functions
17
BACnet functions available as standard BACnet objects in the BACnet network. By use of various
BACnet services, a given event is displayed as an alarm event on the relevant
clients from where the alarm can be processed, that is, viewed, acknowledged
and/or reset.
In XWP these functions can be tracked via the relevant values at the block pins in
online test mode.
Priority mechanism
Basic function In order to evaluate the various defined setpoints received from the BACnet
command system and via the data flow connections, the AO, BO, MO, AVAL,
BVAL and MVAL blocks each incorporate a priority array [PrioArr].
All external sources write their defined setpoint and information bit (enable signal)
into this [PrioArr]. The block then evaluates these entries continuously, in order to
determine the valid present value [PrVal].
The [PrioArr] holds up to 16 different entries, each consisting of a setpoint
definition and the associated information bit (enable signal). The input number also
indicates the priority of the entry, where 1 is the highest and 16 the lowest priority.
Each priority level has a predefined meaning.
Determining [PrVal] The block continuously evaluates the valid present value at the output [PrVal]. It
selects the value that has the highest priority of those whose information bit
(enable signal) is also set. If none of the information bits is set, the default value
[DefVal] is processed.
Structure of the Priority Each priority level has a predefined meaning.
Array [PrioArr] In the [PrioArr], two adjacent priority levels each are reserved for life safety,
manual operation and plant operation.
239 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 General Functions
● The higher priority (lower number) of each pair is reserved for local control and
monitoring, close to the plant (priority 1, 4, 7 and 15).
● The lower priority (higher number) of each pair is reserved for higher level
control and monitoring (priority 2, 5, 8 and 16).
● Priority level 6 is specifically designed for switch-on and switch-off delays and
to maintain minimum ON and OFF times.
This ensures that, for example, an on-site EMERGENCY OFF command, initiated
at the plant level, takes priority over a safety function from a higher-level
subsystem.
Priorities 1, 4, 7, 15 Priority 6 Priorities 2, 5, 8, 14, 16
Local control Control within block Higher control
via data flow interconnection via BACnet command
AO BO MVAL
CMD_CTL
3
e.g. anti-icing
ValCrit / EnCrit
protection
Critical value
5
6 Monitoring hours
7 Desigo CC
e.g. local manual Manual operation
switch ValOp / EnOp 8
13
14
Local control Program control
15 ValPgm / EnPgm
PrVal
Priority 6 Priority entry 6 is used to forward the switch commands resulting from [PrioArr] to
the [PrVal] output after a delay. This enables you to implement both switch-on and
switch-off delays and minimum ON and OFF times.
For this purpose, the internal block logic imports the Present value [PrVal] into the
priority 6 entry. While the delay times referred to above are running, priority 6 is set
to active and so takes priority over priority levels 7…16. Outside these delay times,
priority 6 is always inactive.
Locating this function in the [PrioArr] between priorities 1…5 and 7…16 has the
following consequences:
● Commands with a priority level of 1…5 are always executed immediately,
irrespective of any currently active delay times.
● Commands with a priority level of 7…16 are always overridden by any currently
active delay times.
Unlike all the other entries in [PrioArr], the commands and information bit for
priority 6 are generated exclusively by the BO, MO, BVAL and MVAL blocks. A
priority 6 entry cannot be written from an external source.
240 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
General Functions
17
The switch-on and switch- As soon as one of the commands with a priority of 7…16 determines the [PrVal]
off delay which will therefore cause the present state of [PrVal] to change, the entry for
priority 6 is set up as follows:
If the switch-on delay [DlyOn] or switch-off delay [DlyOff] is greater than 0:
1. Priority 6 adopts the still unchanged present value [PrVal].
2. Priority 6 is set to active.
3. The switch-on or switch-off delay timer starts.
4. After expiry of [TiOnMin] or [TiOffMin], priority 6 is set to inactive.
If the delay times [DlyOn] or [DlyOff] are equal to 0, no action is taken.
If the new value which determines [PrVal] is the same as the current [PrVal], then,
here too, no action is taken.
The minimum on/off time For each change at the output [PrVal] from OFF to Stage n or from Stage n to OFF,
the entry for priority 6 is set up as follows:
If the minimum ON-time [TiOnMin] or OFF-time [TiOffMin] is greater than 0:
1. Priority 6 adopts the new present value [PrVal].
2. Priority 6 is set to active.
3. The timer for the minimum on-time or off-time is started.
4. After expiry of [TiOnMin] or [TiOffMin], priority 6 is set to inactive.
If the minimum switch-times [TiOnMin] / [TiOffMin] are set to 0, no action is taken.
Constraints ● The functions described above are supported only by the BO, MO, BVAL and
MVAL blocks.
● With multistage switch commands, the monitoring periods are enabled only
when switching from OFF to Stage n or from Stage n to OFF. When switching
from one stage to another (for example, Stage 1 to Stage 2), the timer times
are not enabled.
● However, any timer times already running will continue to run.
Application ● Unnecessary on/off switching operations can be prevented by activating
minimum switch-on or switch-off times.
● Activating switch-on or switch-off delays ensures that run-on time delays are
maintained.
Information bit In order for a given value to be included in the evaluation of [PrioArr], its
information bit must be set.
The following applies to priority 1,4,7 and 15 (data flow connection): The relevant
information bit is set via pins [EnSfty], [EnCrit], [EnSwi] and [EnPgm].
The following applies to priority 2, 5, 8, 14 and 16 (BACnet command system):
When a given value is commanded via BACnet, the value concerned is entered in
the [PrioArr] and the associated information bit is set automatically.
The following applies to priority level 6: Both the value and the information bit are
handled by the block concerned.
241 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 General Functions
Can be used to ensure that run-on delay times are implemented. The timer periods [TiOnMin], [TiOffMin],
[DlyOn] and [DlyOff] can be configured in
blocks BO, MO, BVAL and MVAL.
7 Operating value Local manual operation, for example: Data flow interconnection via pins:
Reserved for manual operation. - Manual switch [ValSwi] und [EnSwi].
14 Program value Superposed control and monitoring of the BACnet command system. Access is via
Reserved for normal plant operation with plant. blocks:
monitoring and control. - CMD_CTL
- PWR_CTL (if control enable signal =
Fixed)
17 Default value [DefVal] The influence of [DefVal] depends on the BACnet command system. Access via:
If none of priorities 1…16 is active, then state of the block concerned: - CFC
the default value [DefVal] is processed Out-of-service [OoServ=False]: - PXM20
instead. [DefVal], like the values of priorities - Web client
7…16, is subject to the delay times of
priority 6.
[OoServ=True]:
[DefVal] is transmitted immediately to the
[PrVal] output.
242 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
General Functions
17
Example: Effect of
priorities 7...16 on [PrVal]
Prio Use
1 Prio 7…16 Assumption: The effective switch command from priority (7…16) is Off and is set to active.
2 Prio 7…16 The effective switch command from priority (7…16) switches from Off to Stage 2.
Prio 6 Priority 6 adopts the (still unchanged) present value [PrVal=Off] and is set to active.
At the same time, the switch-on delay [DlyOn] starts. Throughout the delay time, priority 6 remains active –
the associated value remains Off.
[PrVal] Since priority 6 overrides the effective switch command from priority (7…16), the [PrVal] output remains
Off.
Prio 6 The minimum switch-on time [TiOnMin] has expired. Priority 6 is released.
243 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 General Functions
Prio Use
[PrVal] When priority 6 ceases to take effect, the [PrVal] output is once again determined by the effective switch
command from priority (7…16).
[PrVal] remains at Stage 2.
5 Prio 7…16 None of the information bits for priorities (7…16) is active.
The resulting switch command is therefore determined by the default value [DefVal].
[PrVal] Since priority 6 overrides the effective switch command [DefVal], the [PrVal] output remains at Stage 2.
Prio 6 The minimum switch-off time [TiOffMin] has expired. Priority 6 is released.
[PrVal] Since neither priority 6 nor any of the information bits for priority entries (7…16) is active, the effective
switch command is determined by [DefVal].
The output value [PrVal] remains at Off.
8 Prio 7…16 At least one of the information bits for priorities (7…16) is active again.
The effective switch command from priority (7…16) is Stage 1.
Prio 6 Priority 6 adopts the (still unchanged) present value [PrVal=Off] and is set to active.
At the same time, the switch-on delay [DlyOn] starts. Throughout the delay time, priority 6 remains active –
the associated value remains Off.
[PrVal] Since priority 6 overrides the effective switch command from priority (7…16), the [PrVal] output remains
Off.
9 Prio 7…16 n/a
10 Prio 7…16 The effective switch command from priority (7…16) switches from Stage 1 to Stage 2.
Prio 6 The minimum switch-on time [TiOnMin] has expired. Priority 6 is released.
[PrVal] When priority 6 ceases to take effect, the [PrVal] output is once again determined by the effective switch
command from priority (7…16).
The [PrVal] output remains at Stage 2.
244 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
General Functions
17
Example: Effect of
priorities 1...5 on [PrVal]
Prio Use
1 Prio 1…5 Assumption: All information bits for priorities 1…5 are inactive.
2 Prio 1…5 At least one of the information bits for priorities (1…5) is active again. The effective switch command from
priority (1…5) is Off.
Prio 6 Since the effective switch command for priority (1...5) does not cause a change in the [PrVal] output,
priority 6 remains inactive.
3 Prio 1…5 The effective switch command from priority (1…5) switches from Off to Stage 1.
Prio 6 Priority 6 adopts the new present value [PrVal=Stage 1] and is set to active. At the same time, the
minimum switch-on time [TiOnMin] starts without waiting for the delay time [DlyOn].
Note: Entries for priorities (1…5) initialize only the minimum switch-on or switch-off times [TiOnMin] and
[TiOffMin] respectively, but not the switch-on and switch-off delays.
[TiOnMin] and [TiOffMin] times for which the timer has already started only take effect when all priorities
(1…5) are inactive, that is, when the [PrVal] will be determined by one of priorities (7…16).
[PrVal] Priorities 1…5 are reserved to implement safety functions, and are executed immediately, irrespective of
any priority 6 monitoring periods which may already be running.
The [PrVal] output is switched immediately from Off to Stage 1.
4 Prio 1…5 None of the information bits for priority entries (1…5) is active.
245 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 General Functions
Prio Use
Prio 6 The minimum switch-on time [TiOnMin] is still active. Priority 6 adopts the new target value from priority
(7…16).
Prio 6 The minimum switch-on time [TiOnMin] has expired. Priority 6 is released.
[PrVal] Since neither priority 6 nor any entries for priorities (1…5) are active, the output [PrVal] is now again
determined by the effective switch command from priorities (7…16).
The [PrVal] output remains at Stage 2.
Note: Switching from Stage 1 to Stage 2 does not re-start the minimum switch-on time [TiOnMin].
6 Prio 1…5 Assumption: All information bits for priorities 1…5 are inactive.
7 Prio 1…5 At least one of the information bits for priorities (1…5) is active again. The effective switch command from
priority (1…5) is Off.
Prio 6 Since the effective switch command for priority (1...5) does not cause a change in the [PrVal] output,
priority 6 remains inactive.
8 Prio 1…5 The effective switch command from priority (1…5) switches from Off to Stage 2.
Prio 6 Priority 6 adopts the new present value, [PrVal=Stage 2] and is set to active. At the same time, the
minimum switch-on time [TiOnMin] starts without waiting for the delay time [DlyOn].
Note: Entries for priorities (1…5) initialize only the minimum switch-on or switch-off times [TiOnMin] and
[TiOffMin] respectively, but not the switch-on and switch-off delays.
[TiOnMin] and [TiOffMin] times for which the timer is already running only take effect when all priorities
(1…5) are inactive, that is, when the [PrVal] will be determined by one of priorities (7…16).
[PrVal] Priorities 1…5 are reserved to implement safety functions, and are executed immediately, irrespective of
the switch state and of any priority 6 monitoring periods which may already be running.
The [PrVal] output is switched immediately from Off to Stage 2.
9 Prio 1…5 The effective switch command from priority (1…5) switches from Stage 2 to Off.
[PrVal] Priorities 1…5 are reserved to implement safety functions, and are executed immediately, irrespective of
the switch state and of any priority 6 monitoring periods which may already be running.
The [PrVal] output is switched immediately from Stage 2 to Off.
10 Prio 1…5 All information bits for priorities 1…5 are inactive.
Prio 6 The minimum switch-off time [TiOffMin] has expired. Priority 6 is released.
[PrVal] Since neither priority 6 nor any entries for priorities (1…5) are active, the output [PrVal] is now again
determined by the effective switch command from priorities (7…16).
The output value [PrVal] remains at Off.
246 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
General Functions
17
All switching I/O blocks have a configurable switching response. The switching
response determines the functioning of the block. The switching functions are
subject to the priority mechanism in the [PrioArr] and the switch command delay.
● Normal: Direct switching in stages taking into account runtimes (for example,
motors, burners, dampers, etc.).
● Motor: Switching in stages for rotating aggregates taking into account ramp-up
and ramp-down times (fan-belt protection).
● Trigger: Event-driven switching, last command takes precedence; integration of
a data point (EIB, LONMARK)
● Switch: Generation of an ON/OFF pulse of a defined duration.
● Push button with delay: Generation of an ON/OFF pulse of a defined duration.
The pulse can be extended whenever required.
● Release (Release Command): Issuance of a subsystem-specific release value
instead of Present_Value (=Relinquish_Default), if no priority is active in the
output object.
Motor •
Trigger • •
Switch • •
Release •
Normal Normal handling of the process values in the [PrioArr]. The configured runtimes are
active. The outputs can be switched directly or in stages.
Motor The Motor setting is used when there is a need to allow for ramp-up and ramp-
down times due to a rotating centrifugal mass. The programmed times in this
setting can be used, for example, to avoid overloading the fan belt when starting a
fan motor.
When the motor is switched down, the system checks on the basis of the ramp-up
time whether or not the current motor speed has been reached. The switch-down
command is not executed until the motor speed is stable. During the ramp-down
period, the effective command to the hardware is Off. When the ramp-down time
has elapsed, the new command is transmitted to the hardware.
247 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 General Functions
Trigger In the Trigger setting, the source of the last command takes precedence. The valid
value is written from the [PrioArr] to the [DefVal] and transmitted to the output. The
priority is then released again.
In this setting, Priorities 7…16 are treated equally; Priorities 1…5 have a blocking
effect.
The trigger function is used, for example, for the integration of LON data points.
Owing to the event mechanism, this function is not used for P-bus objects.
Switch The Switch setting is used to generate an ON or OFF pulse of a predefined
duration. A command via BACnet, or the activation of an Enable signal in one of
Priorities 7…16 via the data flow connection initiates an associated pulse (event).
The minimum switch-on time [TiOnMin] and/or minimum switch-off time [TiOffMin]
must be set. Setting both times can prevent fast switching operations. Priorities
1…5 have a blocking effect.
Pushbutton with delay The Pushbutton with delay function is like the Switch function, except an active
(time extension) pulse can be extended by another pulse at any time.
Runtimes
Switch-on/off delay Blocks: BO, MO, BVAL, MVAL
The switch-on/off delay when applied to the switching I/O blocks causes a delayed
output if the switch command was written via Priority 7…16. The delay time affects
Priority 6 as described. Switch commands via Priorities 1…5 are executed without
a delay.
When applied to the switching I/O blocks, the minimum switch-on/switch-off time
causes the output to be blocked for a period of time if the switch command was
written via Priority 7…16. The minimum switch-on/off time affects Priority 6 as
248 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
General Functions
17
Minimum switch-on/off already described in Section 24.2.1.3. However, switch commands via Priorities
time 1…5 are executed immediately irrespective of the minimum switch-on/off time.
Ramp-up/down time The ramp-up/down times (run-up/-down times) can be defined in a table for each
stage. These times apply to the two switch types [SwiKind] Normal and Motor.
The ramp-up time is the time taken by a motor when changing from a lower speed
to the next higher speed, to reach the new speed. This limits the current
consumption of the motor.
The ramp-down time is the time taken by the motor when switching down from a
higher speed, to reach the lower speed. This prevents feedback to the mains
supply network and protects the fan belt and the motor.
As a rule, the ramp-up and ramp-down times depend on the centrifugal mass
involved, and must be determined separately for each project.
Especially with single-speed motors, the times can be used as Open/Close
runtimes (for example, damper actuator from 0…100%). A moving damper can
thus be mapped in the system and the transition signal can, if required, be used for
control purposes.
Monitoring periods
Feedback monitoring / Blocks: BI, MI, BO, MO, BVAL, MVAL
process value monitoring The I/O objects have a monitoring function. The output objects monitor the
feedback signal from the plant. For this purpose, an address string must be
entered for the [FbAddr] feedback parameter [FbAddr] and the alarm function must
be enabled.
The input and value objects can monitor reference values. For this purpose, the
relevant reference values must be configured and the alarm function must be
enabled.
Deviation monitoring If the feedback value deviates from the output value [PrVal], a deviation alarm is
generated after a configurable time period, and the block status changes to In
Alarm. When the two values match again, and the configured time period has
expired, the alarm and status are reset. There is otherwise no automatic block
reaction, that is, if a switch response in the plant is required as a reaction to this
alarm, this response must be programmed in CFC via the Disturbance output
[Dstb].
Switch-on/off feedback It is also possible to configure the time period during which the maximum deviation
monitoring of the feedback signal may occur after a switch-on/off operation. If the deviation
persists after the monitoring time has expired, an alarm is generated and the status
of the block changes to In alarm. When the two values match again, and the
configured time period has expired, the alarm and status are reset. There is
otherwise no automatic block reaction, that is, if a switch response in the plant is
required as a reaction to this alarm, this response must be programmed in CFC via
the Disturbance output [Dstb].
No feedback monitoring If no feedback monitoring is required, and the address string is left blank, the
monitoring periods are used by the block for the internal generation of the transient
state [TraSta]. This means that the transient state signal for the switch-on/off
operation is set for the preset period of time. This is how a moving actuator, for
example, a damper, is displayed in the system.
249 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 General Functions
Limit monitoring
Blocks: AI, AO, AVAL
In the case of the analog I/O blocks, the present value [PrVal] can be monitored for
a high/low limit. If the alarm monitoring feature is enabled, a deviation alarm is
generated after a configurable time period, and the block status changes to In
Alarm. When the present value is within the limits again and the configured time
period has expired, the alarm and status are reset. There is otherwise no automatic
block reaction, that is, if a switch response in the plant is required as a reaction to
this alarm, this response must be programmed in Xworks Plus (XWP) via the
disturbance output [Dstb].
PXM20 PXM40/50
BACnet clients
Desigo PX
BACnet service, e.g.
WriteProperty (Present value)
Input block
F orced v
alue Out of Service Present value
Default value State flag
Reliability
Online test mode
in PX Design
10523Z15en
250 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
General Functions
17
PXM20 PXM40/50
BACnet clients
10523Z14en
251 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 General Functions
Priority 8 in [PrioArr]. After processing in the object, the value, other than NULL,
with the highest priority is then transmitted to [PrVal]. If there is no active priority,
the [DefVal] is transmitted.
Runtime totals
Runtime totalization can be implemented in the binary input, binary output and
multistate input and output blocks (BI, BO, MI and MO). Part of the overall range of
functions is defined by the BACnet standard. In order to provide the complete
range of runtime totalizing functions required in the field of building automation and
control, certain proprietary enhancements have been added here.
Function With a binary input object, the operating hours are determined on the basis of the
ON state of [PrVal] (that is, by measuring the time for which this value is active).
For multistate blocks, you can configure how many states are to be totalized.
These are combined and added in a totalizer (the various states cannot be
evaluated individually). In contrast to the input object, the output objects of the ON
state for [FbVal] is logged (not [PrVal]) to operating hours message of the output
objects.
There are two separate totalizers for runtime totalization:
● Runtime totalizer
● Overall runtime totalizer
Release Runtime totalization can be enabled via the [EnOph] pin (Enable operating hours
count). This is a binary value for binary objects, for multistate objects a list of
values released for counting.
Runtime totalizer Maintenance messages (events) are generated via the runtime totalizers. These
are typically reset when the maintenance has been carried out. The present
operating hours [PrOph] output can be used to connect the runtime totalization
feature for further use in the program (for example, for changeover of pumps or
boilers based on operating hours).
Resetting the runtime total The operating hours [Oph] input is used to reset the current runtime total. In online
test mode in Xworks Plus (XWP) via a BACnet client the present value can be
reset by overwriting it with a new value (usually 0). This reset does not affect the
total operating hours count (pins [OphTot] and [PrOphTot], total operating hours
and present total operating hours respectively).
252 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
General Functions
17
Overall runtime totalizer The total operating hours count records the total hours run by an aggregate. It is
only reset when the aggregate is replaced. The [PrOphTot] output is available for
further interconnection in the program.
Resetting the operating The [OphTot] input is used to reset the total operating hours. In online test mode in
hours total Xworks Plus (XWP) or via a BACnet client, the present value can be reset by
overwriting it with a new value (usually 0). This reset procedure simultaneously
sets the runtime totalizer (pins [Oph] and [PrOph]) to the same value.
This is necessary, for example, for an aggregate which is installed as a
replacement item, but which has previously been in operation elsewhere for some
time.
Maintenance message A maintenance message (event) can be generated either after a specified period of
operation or on a specified date. The operating hours limit value and the
maintenance date [OphLm]/[MntnDate] can be configured for this purpose. An
event message is generated when the limit value is exceeded or at 13:00 hours on
the preset date. At the same time, the binary output [MntnInd] (maintenance
indication) is set to active for further use in the program. After the operating hours
reset, this output reverts to inactive. At the same time, the time stamp of the last
reset is stored in the time stamp operating hours reset pin [TiStmOph].
Feedback value The following applies to output blocks: When a feedback is configured, operating
hours count is done based on the feedback value and not based on present value.
The maintenance interval can be further connected via the output present total
operating hours limit [PrOphLm].
Value range for run time The hours run are registered in 32-bit format, giving a maximum value of
totalizing 4,294,967,296. With a resolution in seconds, this gives a value range of over
49,000 days (more than 136 years).
Reliability [Rlb]
The reliability of the present value and of the physical input/output is represented
by the reliability pin [Rlb]. This makes it possible to detect and signal faults and
253 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Input Blocks
As these states are static, they must be set manually during commissioning.
254 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Input Blocks
17
Processing and displaying The measured raw value is converted into the measured present value in
the current value accordance with a conversion curve. This present value is available at [PrVal] for
further processing within the program.
Slope/Intercept The conversion curve is a linear function which takes the following form:
[PrVal] = Raw value * Slope + Intercept
The values for slope [Slpe] and intercept [Icpt] must be defined specifically for the
application concerned in accordance with the I/O system in use and the signal type.
For slope and intercept values for SBT products, see Slope [Slpe] and Intercept
[Icpt]. For sensors not listed, the following applies:
Calculating [Slpe] and The values for [Slpe] and [Icpt], which are to be entered in the block, must first be
[Icpt] calculated. These values are derived from the individual [Slpe] and [Icpt] values of
the signal type and the signal transducer in accordance with the following formula:
[Slpe] = (Slope SignalType / Slope SignalTransducer)
[Icpt] = (Intercept SignalTransducer / Slope SignalTransducer ) + Intercept SignalType
[Slpe] is calculated on the basis of:
[Slp] = (InterpolationPoint_y2 – InterpolationPoint_y1) / (InterpolationPoint_x2 –
InterpolationPoint_x1)
255 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Input Blocks
256 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Output Blocks
17
257 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Output Blocks
Feedback monitoring for To monitor the damper position of dampers with one end switch, the switch
dampers with one end position must be set by defining the polarity of the feedback signal [Bop].
switch OPEN end switch -> Feedback polarity [FbPol] set to NORMAL
CLOSED end switch -> Feedback polarity [FbPol] set to INVERTED
Feedback monitoring for The monitoring of dampers with two feedback signals (Open/Closed) is
dampers with two end implemented via the address string of the Feedback Address [FbAddr]. The first
switches address in the string must be that of the end switch which indicates that the
damper is closed. The end switch indicating that the damper is open is set in the
second part of the address string.
Example with PX modular:
258 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Output Blocks
17
259 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Value Objects
Analog Output
[PrioArr]
[PrVal]
[FbVal]
[FbVal] :=
Feedback Raw Value *Feedback Slope+ Feedback Intercept
If
[FbAddr]
Feedback_Raw_Value
The value [PrVal] from the program is converted into the physical positioning value
by use of a conversion curve. This present value is then available at [PrVal] for
further processing in the program while at the same time, the raw data is
transmitted to the associated I/O system, where it is converted into an electrical
signal to drive the field device.
The conversion curve is a linear function which takes the following form:
Raw Value [RwVal] = [PrVal] * Slope + Intercept
The values for slope [Slpe] and intercept [Icpt] must be defined specifically for the
application concerned in accordance with the I/O system in use and the signal type.
For slope [Slpe] and intercept [Icpt] values for SBT products, see Slope [Slpe] and
Intercept [Icpt].
260 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Value Objects
17
modules) in the plant. The value objects BVAL, AVAL and MVAL are used in the
program whenever BACnet-defined functions, such as commands, alarm
generation and runtime totalizing are required, or when a value is to be modified
via an operator unit. Value blocks look like all other blocks, and can be connected
with other blocks.
Typical applications Value objects are used typically in aggregates as command control links
(PWR_CTL or CMD_CTL). The command control mechanism passes the
commands to the value object and derives the status from the BACnet referencing
system.
A-Transport
OpSta
EnCrit
DmpShofEh Ag:DmpShof
EnCrit
CMD_CTL
On
FanSu
Ag: V(A,C-F) Fan1St
SmextPrg
En
OpSta
SmextEh Cp:BI
EnCrit
E,U
BI
SmextEh
On/P14 Open/P14
ErcRo DmpShof
EnCrit
On
SmextSu Cp:BI
E,U
BI
SmextSu
En
On/P14
FireDet Cp:BI
E,U
EmgOff
EmgOff
BI
ManSwi Cp:Ml
On
MI
En
TSu
ValSfty
SpErcTSu EnSfty
Frost
BO
KickDmp
Dstb
En
Sequence table
ValPgm OpSta
EnPgm PrVal
M
E,H
On
OpModSwi Cp:MI
E,H
Ax: DMUX8_BO
En
OpMSwiCnv
MI
BVAL
En
AO
PrVal FbVal
PrVal
On
OpModMan
Cp:MVAL_OP
MVAL
En
ValSfty
En
TSu
O&M
EnSfty
KickDmp
BO
Dstb
Frost
ValPgm OpSta
DefVal:Off
Sched
Cp:BSCHED
BVAL
On
AO
En
En
PrVal FbVal
PrVal
261 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Value Objects
Furthermore, the value objects can be used for alarm monitoring (reference values
or high/low limit value), or to determine and monitor operating hours. The value
objects designed specially for operation via BACnet client can be used, for
example, as a simple way of enabling the user to operate setpoints and switch
commands.
262 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Value Objects for Operation
17
Identical compound Another advantage is that the compound libraries are always identical. In the
libraries engineering phase, they are adapted to the I/Os in the project by assigning the
appropriate addresses. The process values (0…10V, 0…25mA, signal contacts,
etc.) from the connected field devices are registered directly at the physical inputs.
The physical outputs deliver the process values (0…10V, switching stages 0 / I /II /
III, etc.) directly to the connected field devices.
The process values are transmitted in the form of raw data via the relevant medium
(for example, PPS2); the conversion of the raw value takes place within the block.
Rules:
● Values from the plant are measured and processed in Input blocks (Analog,
Binary or Multistate).
● Values to the plant are processed and transmitted by Output blocks (Analog,
Binary or Multistate).
Program in XWP
10664-24Z01en
263 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Addressing the I/O Blocks
I/O systems
To enable the process value of the logical I/O block to be allocated to the
appropriate physical I/O, the relevant address must be assigned. The address is
assigned as follows:
● Via automated assignment by the Point Configurator to the CFC
● Direct allocation to the I/O block in Xworks Plus (XWP)
The logical I/O blocks are designed for universal use in various I/O systems. The
specific address structures and hardware definitions are determined by the I/O
system, for example, the failsafe control value for the island bus.
In Desigo, they are as follows:
● Physical I/Os
● Values in a Desigo room unit, accessible via the PPS2 interface (does not
apply to Desigo S7)
● Data in the same or in another automation station, referenced by its Technical
Designation and accessed without a connection, peer-to-peer via BACnet
services.
For addressing I/O from Desigo S7, see Desigo S7.
Address prefix
The addressing syntax indicates the origin of the raw value. The syntax must
correlate with the actual physical inputs.
The prefixes for the various subsystems are as follows:
● "T=" for TX-I/O modules on an island bus-capable automation station PXC....D
● "C=" for on-board I/Os of the Desigo PX compact automation stations
● "B=" for referencing to BACnet objects
● "Q=" for QAX room units
● "L=" for LonWorks addressing
● "S=" for Simatic S7 addressing
● "M=" for PX-OPEN addressing
● "D=" for PX Open Diagnostic Addressing
For addressing with "P=", see Addressing Entries for PXC…-U, PTM and P-Bus.
For addressing with "S=", "M=" and "D=", see the corresponding expert
documentation.
For more information on TX-I/O, see TX-I/O Assortment overview (CM2N8170) and
TX-I/O Functions and operation (CM110561).
264 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Addressing the I/O Blocks
17
The parameters no longer appear in the I/O address string for direct island bus
integration, but rather in the IOC (I/O configuration).
The only exception is the Info LED which must have the prefix "C=", because the
fixed address, 8.1, which is used for the Info LED may also be used by an I/O
module.
The Info LED for PX KNX and PX Open can also be addressed with C=8.1.
The following table shows the various address entries required when using the
modular series automation station in conjunction with TX-I/O-I/O modules.
Signal types shown in italics are used to map virtual modules for use with TX
OPEN at module level. Signal types AIS, AOS, DIS and DOS deliver a 16 bit value
with status information, while signal types AISL, AOSL, DISL and DOSL deliver a
32 bit value with status information. All other signal types deliver a 16/32 bit value
without status information.
While all the module types listed may be connected to any island bus addresses,
not all module types have 16 points.
PX Info LED 8 1
265 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Addressing the I/O Blocks
– 2 – 2 – 2 –
Key:
1 Syntax for PPS-2 signal: Q = Room device number.object number (profile number). Up to five
devices can be connected.
PX Compact from Desigo The existing UI and AO can be configured as AI, DI, CI, or AO.
V5.0 Signal type of no application is loaded (wiring test):
PXC12..D, U1…U4: xx = Y10S, U5…U8: xx = R1K
PXC22..D, U1…U4: xx = Y10S, U5…U16: xx = R1K
PXC36..D, U1…U6: xx = Y10S, U7…U24: xx = R1K
266 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Addressing the I/O Blocks
17
DO1
HMI / TOOL
Block
AI
I/O module Island bus
T R
10664-24z02en
AI
Island bus
If you wire it as in the figure above, Xworks Plus (XWP) determines multiple use
and generates an error message.
For the multiple use of output blocks, the plant will malfunction, because there will
then be two or more sources acting on one switching command. The effective
switching command (at the output) is the last one received (determined by the rule
"the last command takes precedence"). In other words, the order of processing
determines which source or origin will be linked to the output.
In CFC the same address can be allocated to two or more input or output blocks.
This multiple address allocation goes undetected when the program is compiled;
the automation station also fails to recognize the error (a reliability error is
generated and an error message is transmitted only in the case of multiple address
allocation with two different signal types).
Solution 1 Many systems include a requirement for the multiple use of sensors. A typical
example of this is an outdoor air temperature sensor shared across systems. The
following example illustrates the simplest form of the multiple use of sensors:
In CFC the current value is transmitted for further use in the program by
interconnecting the blocks. The logical I/O block (Analog Input, {AI}) occurs in the
program once only, and its hardware-specific parameters only need to be set once.
267 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Addressing the I/O Blocks
10664-24z03en
Block
I/O module
Analog input
Solution 2 The multiple use function can be implemented with a BACnet reference to the first
analog input block (Partial plant 1). In other words, the first block will receive the
island bus address at the [IOAddr] pin. The second analog input block (Partial plant
2) references the first AI (B=…) via the technical designation.
268 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Addressing the I/O Blocks
17
The examples below show a possible application for multistate input blocks in
conjunction with the physical I/O modules. The example on the left of the diagram
is a multiple I/O module, while the one on the right shows the mapping of several
individual I/O modules in one multistate input block.
Multistate output The multistate value from the program is converted in the Multistate Output block
into a switching command. Addressing is via [IOAddr]. For PX modular, the syntax
is as follows:
Syntax: T=Module.channel
Examples:
● Q-M1: T=1.1
● Q-M2: T=1.1
● Q-M3: T=1.1
● Q-M4: T=1.1
● Q250-P3: T=10.1
● DOS: T=24.7
Values with up to four stages can be processed. The signals to be registered,
which are addressed via Module.Channel, must always be of the same hardware
signal type. In the case of a multistate output on the hardware side, there is one
address only (this is only possible with PXC modular automation stations).
Error handling If an automation station does not support a given address (for example, incorrect
syntax) or a given I/O system, this will lead to a reliability error, which will be
displayed at the [Rlb] pin.
Advanced mapping The manual switch can be encoded on the PX Compact in various ways, for
(Multistate Input) example:
● (Auto/Off/On) or (Off/Auto/On)
● (Auto/Off/S1/S2) or (Off/Auto/S1/S2)
So avoid having to keep adapting the data types and text groups in the system, the
manual switch must always be represented in the same way within the system:
● (Auto/Off/On)
● (Auto/Off/S1/S2)
A prerequisite for this approach is that it must be possible in the multistate input
block to configure the hardware coding and mapping to the standardized manual
switch. This is made possible with parameters in the address.
1_n-Mapping (Multistate Syntax:
Input and Output) T = Module.channel
C=Module.channel;Module.channel;Module.channel;Module.channel (signal type,
a,b,c,d,e)
a represents [PrVal] for HW-I/O (0,0,0,0)
b represents [PrVal] for HW-I/O (1,0,0,0)
c represents [PrVal] for HW-I/O (0,1,0,0)
d represents [PrVal] for HW-I/O (0,0,1,0)
e represents [PrVal] for HW-I/O (0,0,0,1)
Example: T=2.1
For the TX I/O addressing no additional information in the address string is added.
All information (signal type, mapping table, mapping rules, for example, up-down,
etc.) is configured in the I/O Address Editor and loaded in the automation station
with the IOC file.
Example: C=2.1;2.2;2.3;2.4 (D20, 2, 1, 3, 4, 5)
269 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Addressing the I/O Blocks
1 1 0 0 0 Auto
3 0 1 0 0 Stage 1
4 0 0 1 0 Stage 2
5 0 0 0 1 Stage 3
1 1 0 0 0 Off
5 0 1 0 0 Comfort
7 0 0 1 0 Eco
9 0 0 0 1 StandBy
2 1 0 0 0 Stage 1
3 1 1 0 0 Stage 2
4 1 1 1 0 Stage 3
5 1 1 1 1 Stage 4
With Up/Down mapping, more than one hardware input or output may be active.
Binary Mapping (Multistate Application: Output of an integer in binary form.
Input and Output) Example: Binary electric heating coil.
Syntax: C=Module.channel;Module.channel;Module.channel;Module.channel
(signal type, BINARY)
Example: C=5.1;5.2;5.3;5.4(Q250,BINARY)
270 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Addressing the I/O Blocks
17
Example: C=2.1;2.2;2.3;2.4(D20,BINARY)
3 0 1 0 0 Stage 2
4 1 1 0 0 Stage 3
5 0 0 1 0 Stage 4
6 1 0 1 0 Stage 5
...
16 1 1 1 1 Stage 15
With binary mapping, more than one hardware input or output may be active.
BACnet addressing
Peer-to-peer Data can be exchanged via peer-to-peer communication.
communication The exchange takes place using the BACnet services defined in the BACnet
standard. The process employs mechanisms engineered in CFC which can be
tracked in online test mode, but which are based on BACnet objects and BACnet
services.
Engineering When engineering the exchange of data in CFC, it is important to take note of the
following:
● Addressing is via [IOAddr].
● Data is exchanged only between BACnet objects. The attributes of the I/O
blocks and pins must be defined appropriately, and the information must also
be made available in the form of a BACnet object. For this purpose, the
attributes of this block or I/O must be defined correctly.
● In BACnet terminology, the I/O block is a client which fetches the required
value from an object defined as the server. This process is carried out using
services defined by BACnet, for example: The client subscribes to the relevant
object (the server) using the SubscribeCOV service. The server then supplies
the value via the BACnet service COVReporting whenever it changes by the
programmed value, COVIncrement. ReadProperty (polling) is another BACnet
service. Here, the value is read at regular predefinable intervals.
● Addressing is carried out via the Technical Designation (TD). Note, however,
that this Technical Designation must first be made known to the client in the
form of a reference address.
● The data is exchanged both within a given automation stations, and across
automation stations.
Address syntax Addressing takes place via the input/output address [IOAddr] and always starts
with the prefix "B=".
The BACnet reference address is the same as the Technical Designation (TD) of
the value. The BACnet addressing syntax is as follows:
B=BACnetReference (BACnetConfig)
Example: B=Geb6'Lft3'FanSu'Mot'MntnSwi.PrVal(0)
Polling or COV procedure The FB variable PollCyc is used instead of the prior BACnetConfig parameter in
the I/O address syntax, to distinguish between COV or polling:
FB variable IOAddr. FB variable PollCyc
BACnetConfig = 0 -> COV (Change of Value)
271 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Addressing the I/O Blocks
PPS2 addressing
A PPS2 address is required when values are to be transmitted via the PPS2
interface. Addressing takes place via the input/output address [IOAddr] and always
starts with the prefix "Q=".
Address syntax Up to five room units can be connected to one Desigo PX automation station and
addressed via the PPS2 interface. The addressing syntax is as follows:
Q=RoomUnitNumber.Object(Profile)
Example: Q=1.40 (1)
The functions available in the room unit are mapped directly to the I/O blocks. The
following elements of the address are predefined:
Type (standard BACnet objects) Room unit Object Object description Profile1 Example
number
Analog input 1…5 24 Setpoint correction – Q=1.24
Key:
1 The Profile relates to the configuration number shown in the next table.
The room unit is configured with this configuration number and appended to the
Room temperature object. Other objects are not assigned a configuration number.
272 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Addressing the I/O Blocks
17
Only the relevant operating and process values are mapped in the I/O blocks,
rather than all objects of a room unit.
Six profiles have been defined to keep both the memory requirements and the
demands placed upon the user in practice to a reasonable level. If no profile
information is supplied, the predefined device-specific default value [DefVal] is
used. As an exception in the case of the QAX units, Profile No. 5 is used.
Configuration Profile
1 2 3 4 5 6
StandBy ON ON ON ON ON ON
Auto ON ON ON ON ON ON
Fan1 ON ON ON ON ON ON
KonfLCD
Symbol Standby ON ON ON ON ON ON
Symbol Auto ON ON ON ON ON ON
Symbol Fan1 ON ON ON ON ON ON
TempUnit °C °F °C °F °C °F
This profile (or configuration number) is always valid for one room unit only. It is
used to configure the objects ConfigLCD and EnableOperatingMode and to define
how the room unit is to operate (for example, °C or °F).
In principle, the profile can be attached to any other object.
This configuration applies only to the QAX33.1 and QAX34.1 room units.
Configuration of the object ConfigLCD is only relevant in the case of the QAX34.1,
as this is the only unit with a display in °C or °F.
The configuration of the object EnableOperatingMode is only relevant in the case
of the QAX33.1 or QAX34.1, as only these two room units have the option of
selecting Fan1, Fan2 or Fan3.
Where QAX units without an address switch are still in use, only one room unit per
automation station can be integrated. The room unit number in such cases is then
"1".
LonWorks addressing
There are two ways to integrate data points from LonWorks devices:
● via Discipline I/O
● via standard inputs/outputs (the latter approach is only sensible with a small
number of data points to be integrated, for example, from third-party devices)
Address syntax The block registers the control variables and output variables of the RX devices
(outside the CFC chart) in accordance with the information in the [IOAddr] property
(Input/output address).
Addressing starts with the prefix "L=".
273 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Discipline I/Os
KNX addressing
You can integrate data points from KNX devices as follows:
● See PX KNX, RXB integration - S-Mode (CM1Y9775)
● See PX KNX, RXB/RXL integration - Individual addressing (CM1Y9776)
● Address Info LED for PX KNX: D=1001
274 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Reliability Table
17
● Simple value
● Trigger value
● Commandable value
Simple value The input value can be connected via the data flow. In the engineering tool, this is
preceded by a function block or compound, for example, a Scheduler. However, if
the input value is not connected, it can also be modified via BACnet client. The
subsystem registers a change in the input value by comparing the value with the
process image and transferring it to the field devices.
Trigger value This input value is the logical image, or memory map, of an analog positioning
command and describes its properties. Within the program, the Present Value is
made available to the block as a program value. The block transfers the program
value to the subsystem, from where it is transmitted to the field device.
Writing to this value acts as a trigger. This makes it possible, for example, to
generate the output of the same value (for example, Lighting 100%, followed later
by 100% again). In this case the subsystem registers the trigger value and
transmits the value to the devices. This capability is required when the same
variable can be modified from several sources (for example, when Desigo CC
writes 100.0%, the local operator unit writes 0.0% and the Desigo CC user wants
to rewrite the value of 100.0%). The sources can be BACnet clients or system
function blocks.
Only analog trigger values may be used.
Commandable value The input value is the logical image, or memory map, of an analog positioning
command and describes its properties. Within the program, the Present Value is
made available to the block as a program value. The block transfers the program
value to the subsystem, from where it is transmitted to the field device.
The commandable value is based on the BACnet priority-mechanism (which is the
same as for the output blocks – refer to Section 0). A commandable value can be
operated from various sources. Each source has its own priority. The sources are
mutually exclusive (interlock). The source with the highest priority prevails. for
example, Emergency = Priority 1, Façade control = Priority 6, Operator = Priority =
8). The sources can be BACnet operator units or system function blocks (grouping
function).
Only analog commandable values can be used.
1 No sensor.
4 Continuous loop.
5 Short circuit.
6 No output.
7 Unreliable other.
8 Process error
9 Multistate fault.
275 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Reliability Table
84 Memory full.
89 Reliable participant.
Signal types in the automation station which are not supported also generate
reliability error message 72.
276 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Slope [Slpe] and Intercept [Icpt]
17
277 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Slope [Slpe] and Intercept [Icpt]
Signal type Description Standard measuring Resolution on the Value range on the [Slpe] [Icpt]
measurement range bus bus
R1K LG-Ni 1000 -50 … 150 °C 1/100 °C -5000 ... 15000 0.01 0
Pt100_4 Pt100 -50 ... 600 °C 1/100 °C -5000 ... 40000 0.01 0
T1 PTC sensor -50 ... 150 °C 1/100 °C -5000 ... 15000 0.01 0
Ni1K LG-Ni 1000 -50 ... 180 °C 1/100 °C -5000 ... 18000 0.01 0
Pt1K375 Pt1000 (NA) -50 ... 180 °C 1/100 °C -5000 ... 18000 0.01 0
Pt1K385 Pt1000 (EU) -50 ... 600°C 1/100 °C -5000 ... 60000 0.01 0
NTC10K NTC sensor -40 ... 115 °C 1/100 °C -5000 ... 11500 0.01 0
NTC100K NTC sensor -40 ... 125 °C 1/100 °C -5000 ... 12500 0.01 0
I25/020 TX-I/O* DC 0 ... 20mA*) 0 ... 20 mA* 1/1000 mA 0 ... 20000 0.001* 0
U10 (Shunt 400 DC 0 ... 25mA*) 0 ... 25 mA* 1/1000 V 0 ... 10000 0.0025* 0
Ohm) TX-I/O*
Key:
* TX-I/O modules support only 0 ... 20 mA. For a range of 0 ... 25 mA, use the shunt for 400 Ohm
(0.1%, 1 W) and measure the voltage with U10.
I/O configuration PX The analog input block is used in the Desigo PX Compact PXC10 TL to PXC52
Compact automation station in cases where an LG Ni1000 sensor (signal type R1K) or DC
0…10 V (U10) is connected to device terminals X1…X16 of Module 001.
The following information results:
BACnet referencing Reference to a value in another BACnet object. As the referenced value is already
available as a converted or resulting value, no conversion is required, that is, [Slpe]
must be defined as 1 and [Icpt] as 0.
The measured value from a room unit connected via the PPS2 interface. In the
analog input block, only Objects 24 (setpoint correction) and 40 (room temperature)
278 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Slope [Slpe] and Intercept [Icpt]
17
PPS2 interface may be used. As the value is already available as a converted or referenced value,
no conversion is required, that is, [Slpe] must be defined as 1 and [Icpt] as 0.
Key:
* Value [Slpe] for Y250T is not a physical value, but rather a special code controlling output of the
AO to two relay outputs. This code differs between P-bus and island bus.
I/O configuration PX The analog output block is used in the PX compact automation stations, when
Compact valves or actuators with DC 0…10 V control signals, signal type Y10S, are
connected to device terminals Y1…Y8 of Module 004.
PPS2 interface Transfer of an analog control command to a room unit connected via the PPS2
interface. Only Object 195 (= Room temperature display) can be used in the analog
output block. As the value is already available as a converted or referenced value,
no conversion is required, that is, [Slpe] must be defined as 1 and [Icpt] as 0.
R2K5
P1K (0...2500 Ohm)
0 Ohm 0.1 1 0 1
Default = 1 Ohm 0.1 0 0 0
2 Ohm 0.1 -1 0 -1
3 Ohm 0.1 -2 0 -2
279 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Slope [Slpe] and Intercept [Icpt]
0 Ohm 0.01 1 0 1
Default = 1 Ohm 0.01 0 0 0
2 Ohm 0.01 -1 0 -1
3 Ohm 0.01 -2 0 -2
R250
P100 (0...250 Ohm)*
0 Ohm 0.01 0 0 0
Default = 1 Ohm 0.01 -1 0 -1
2 Ohm 0.01 -2 0 -2
3 Ohm 0.01 -3 0 -3
Key:
* PT-I/O modules P100 is a four-wire type Default line resistance = 0 Ohm
Line resistance not compensated
TX-I/O modules with Pt100_4 is a four-wire type Default line resistance = 0 Ohm
island bus integration Line resistance not compensated
TX-I/O modules with Pt100_4 is a four-wire type Default line resistance = 0 Ohm
BIM integration Line resistance not compensated
Line resistance [Slpe] [Icpt] Degrees per Ohm Degrees per Ohm
Pt 1K 385 3.85 0.259740
Ni1K 5 0.2
280 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Slope [Slpe] and Intercept [Icpt]
17
Line resistance [Slpe] [Icpt] Degrees per Ohm Degrees per Ohm
T1 9.57 0.104450 -50...0 °C
10.39 0.096246 0...50 °C
11.31 0.088417 50...100 °C
12.36 0.080893 100...150 °C
Pt100_4
BSG61
0 ... 5 V
10563A22
281 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Addressing entries for PXC…-U, PTM and P-Bus
Figure 208: Example of a circuit including the QAF64 which transmits more than 10 volts
PX Info LED 8 1
282 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Addressing entries for PXC…-U, PTM and P-Bus
17
1:n - Mapping
Signal types shown in italics are used to map virtual modules for use with I/O
OPEN at module level. Signal types AIS, AOS, DIS and DOS deliver a 16 bit value
with status information, while signal types AISL, AOSL, DISL and DOSL deliver a
32 bit value with status information. All other signal types deliver a 16/32 bit value
without status information.
While all the module types listed may be connected to any P-bus addresses, not all
module types have 16 channels.
Parameter values Parameter values for the analog output, binary output and multistate output blocks:
Y10S Failsafe function (emergency control function) if the transfer of data over the P-bus
fails (for longer than 4 seconds) or in the event of a power failure. (an operating
voltage of AC 24 V must be available).
NO -> Module output signal goes to 0 V.
KEEP -> Module output signal remains at previous value.
0...30 -> Module output signal 0 = 0 V, 1 = 0.33 V, etc. , … 30 = 10 V.
Y250T 1…13, 1…13 Runtime ranges for On/Off signals (the ranges do not need to be the
same for On/Off). Values 1…13 correspond to the following runtimes:
1 = 8.5 ...13 seconds
2 = 13 ... 18 seconds
283 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Addressing entries for PXC…-U, PTM and P-Bus
3 = 18 ...25 seconds
4 = 25 ...35 seconds
5 = 35 ... 48 seconds
6 = 48 ... 66 seconds
7 = 1.1 ... 1.6 minutes
8 = 1.6 ... 2.3 minutes
9 = 2.3 ... 3.2 minutes
10 = 3.2 ... 4.5 minutes
11 = 4.5 ... 6.3 minutes
12 = 6.3 ... 9.0 minutes
13 = 9.0 ... 11 minutes
The PTM1.2Y250T(-M) module can only implement one runtime. It therefore uses
the opening-command runtime for closing commands.
Q250_P, Q250A_P, 0, 1…600 -> Pulse times, where 0 = 0.5 seconds and then 1 = 1 second, 2 = 2
Q250_P3 …. seconds etc. up to 600 (=600 seconds).
Pulse times for island bus applications:
Values in the I/O address editor: 0...255 (corresponds to 0...25.5 seconds)
Default = 5 (corresponds to 0.5 seconds).
284 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Addressing entries for PXC…-U, PTM and P-Bus
17
Key:
1 For PXC10-TL the two Alarm1/2 buttons and the DIL switches1/2 are mapped to the modules
with the Address 3.
2 The manual switch can only be loaded into the application if the DIL switches (in the cover of the
PXC36-S) are set correctly.
3 Syntax for PPS-2 signal: Q=Romm device number.Object number (profile number). Up to five
devices can be connected.
4 The current UI and AO can all be configured as AI, DI, CI, or AO.
Signal type if no application is loaded (wiring test): X1...X16 = Y10S, Y1...Y8 = R1K.
Module 4 For Module 4, the universal outputs (UO for AO and DO) not only control
proportional actuators (AO), but can also be used as binary switch commands (DO).
Analog Output = 0…10 V
Binary Output = DC 0 or 24 V, max. 22 mA with the use of an additional external
relay.
285 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Addressing entries for PXC…-U, PTM and P-Bus
D1..D4
MD002
X10
X12
D1
GND
GND
GND
GND
CP+
CP -
X11
D2
D3
D4
D5
D6
D7
D8
X1..16 D5..D16
AC24V
26VA MD001 MD003
GND
GND
GND
GND
X13
X14
X15
X16
D9
51..62 = MD005 Y1..Y8 = MD004
286 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
Addressing entries for PXC…-U, PTM and P-Bus
17
● P=10.1 (Q250-P3,120)
● P=24.7 (DOS)
Values with up to four stages can be processed. The signals to be registered,
which are addressed via Module.Channel, must always be of the same hardware
signal type. In the case of a multistate output on the hardware side, there is one
address only (this is only possible with PXC modular automation stations).
Error handling If an automation station does not support a given address (for example, incorrect
syntax) or a given I/O system, this will lead to a reliability error, which will be
displayed at the [Rlb] pin.
3 1 0 0 0 Stage 1
2 0 1 0 0 Off
4 0 0 1 0 Stage 2
5 0 0 0 1 Stage 3
287 | 377
Siemens CM110664en_03
2017-09-18
Logical I/O Blocks
17 Addressing entries for PXC…-U, PTM and P-Bus
288 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo Room Automation
18
18 Room Automation
Desigo Room Automation Desigo Room Automation offers solutions with greater functionality and flexibility
allowing for energy-optimized plant operation without loss of comfort (efficiency
class A).
The DXR2 room automation stations are perfectly suited to exclusively automate
heating, ventilation, and air conditioning in a room. In addition, the DXR2 can be
extended with lighting and shading functions by adding devices with KNX PL- Link.
The PXC3 modular room automation stations are used in buildings with multiple
disciplines for room automation (HVAC, lighting, blinds) all combined in one system.
Desigo RX Desigo RX is a proven room automation product range featuring comprehensive
communications and application functions for individual rooms. The product range
consists of two series of communicating room controllers (RXC…, RXB…) with
operator units and predefined applications for HVAC, lighting, and blinds. Desigo
RX room automation is capable of autonomous operation. Integration of LonWorks
or KNX network via the system controllers provides for additional functionality.
Communication with sensors and KNX PL-Link KNX PL-Link KNX PL-Link KNX PL-Link
actuators in room (integration) KNX (with ETS)
DALI
Communication with room units KNX PL-Link KNX PL-Link KNX PL-Link KNX PL-Link
KNX PL-Link KNX PL-Link (PeripheraL Link) connects communicating room and field devices
(room devices, sensors, actors) with the PXC3 room automation station.
DALI DALI (Digital Addressable Lighting Interface) helps control lighting.
289 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo Room Automation
18.1.1 Configurable
With DXR2.. up to two rooms can be automated for heating, ventilation, air
conditioning, shading, and lighting.
The stations communicate with each other and other system components,
depending on the type, via BACnet/IP (DXR2.E…) or BACnet MS/TP (DXR2.M...).
The room automation stations have a set number of I/O data points and an
onboard interface to KNX to connect field devices. The automation stations are
delivered with preloaded applications and only need to be configured.
A comprehensive library of proven, standardized applications is also available and
can be used instead of the preloaded applications. Buttons, sensors, and actuators
for lighting and shading are connected to the room automation stations via the KNX
PL-Link.
The preloaded and proven standardized applications in the library are configured
using ABT Site and offer a great deal of flexibility since the inputs and outputs of
the DXR2… can also be configured in addition to the functions.
See Desigo Configurable Room Automation (BACnet) – Product Range Description
(A6V10866237).
Topologies
Desigo CC
BACnet/IP Ethernet
DXR2.E.. DXR2.E..
KNX PL-Link
KNX PL-Link
°C °C
°C °C
290 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo Room Automation
18
Desigo CC
BACnet/IP Ethernet
PXG3.L
Router PXC..-E.D
BACnet MS/TP
DXR2.M.. DXR2.M..
KNX PL-Link
KNX PL-Link
Compact AC 230 V Compact AC 24 V
°C °C
°C °C
AQR25... AQR25...
10664Z48en
Detector Detector
Room sensor QMX3... Room sensor QMX3...
Room Room
operator units operator units
Figure 211: Compact DXR2 room automation stations for BACnet MS/TP
Applications
The following tables show the functions of the different applications of the DXR2
room automation stations.
291 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo Room Automation
Application Functions
Fan coil unit ● Outside Air Damper
● Single Speed Fan , Multi Speed Fan or Variable Speed Fan
● Chilled water cooling coil
● Direct expansion evaporator cooling coil
● Heating/Cooling coil
● Hot water heating coil
● Electric heating coil modulating, single stage or two stage
● Room temperature control by two-pipe system with change-over
● Room temperature control by four-pipe system
● Supply air temperature cascade control
● Room dehumidification control
● Air volume flow control
● Rapid ventilation
● Green leaf
292 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo Room Automation
18
Application Functions
Fan powered box ● Supply air control
● External flow control for VAV with integrated flow controller and differential pressure sensor
● Internal flow controller and differential pressure sensor for damper actuator control
● Internal flow controller and velocity sensor for damper actuator control
● Single Speed Fan , Multi Speed Fan or Variable Speed Fan
● Chilled water cooling coil
● Heating/Cooling coil
● Hot water heating coil
● Electric heating coil modulating, single stage or two stage
● Room temperature control by two-pipe system with change-over
● Room temperature control by four-pipe system
● Supply air temperature cascade control
● Room air quality control
● Rapid ventilation
● Green leaf
293 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo Room Automation
Application Functions
Central functions ● 4x Control room operating mode groups with:
– Room mode and room setpoint distribution to rooms
– Start optimization switches the heating on at the appropriate time
– Three delayed distribution groups of room operating mode for big buildings
● 1x Seasonal compensation of room temperature setpoints
● 2x Demand controlled hot water supply group
● 2x Demand controlled chilled water supply group with:
– Condensation prevention shifts the base chilled water setpoint to avoid condensation at chilled
ceiling radiant devices
– Two pipe changeover control handles the heating / cooling changeover for a two-pipe system
– Free cooling manages the delivery of chilled water in situations where this can be done with
almost a zero expenditure of energy. For example, chiller plants with the possibility to cool the
water with the recoolers when outside conditions are favorable.
● 1x Demand temperature control group with:
– Relief function opens additional VAV without demand to ensure stable working of the primary
plant
– Changeover evaluation decide if the central air should be used for heating or for cooling
– Dew point evaluation is used to dehumidify at the primary air handling unit to avoid condensation
in the rooms
– Humidity demand evaluates room humidity to help the primary plant determine when to humidify
or dehumidify
– Override function allows a technician or balancer to override the VAV applications for balancing
and commissioning
● 1x Demand controlled pressure control by either:
– Supply VAV position evaluation helps to optimize fan speed by averaging the 10 highest supply
damper positions and providing this information to the central plant
– Extract VAV position evaluation helps to optimize fan speed by averaging the 10 highest extract
damper positions and providing this information to the central plant.
– Supply VAV flow deviation helps to optimize the fan speed by calculating the airflow deviation
through the supply VAV dampers
– Extract VAV flow deviation helps to optimize the fan speed by calculating the airflow deviation
through the extract VAV dampers
– Supply VAV flow saturation evaluation (air flow control loop cannot get enough air to reach
setpoint) evaluates the supply VAV saturation signals from the rooms to optimize the fan speed
– Extract VAV flow saturation evaluation (air flow control loop cannot get enough air to reach
setpoint) evaluates the extract VAV saturation signals from the rooms to optimize the fan speed
– Supply VAV setpoint evaluation with the summed setpoints of the supply VAV the fan's speed
can be set for an optimized fan speed when VAV positions and VAV flow rates are not known
– Extract VAV setpoint evaluation with the summed setpoints of the extract VAV the fan's speed
can be set for an optimized fan speed when VAV positions and VAV flow rates are not known
294 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo Room Automation
18
Application Functions
Central functions ● 2x VAV supply fire emergency group with off, extract, pressurization or purge
● 1x Central weather station with:
– Outside temperature
– Outside brightness
– Outside solar radiation
– Outside wind speed
– Outside precipitation
● 2x Light manual central operation group
● 1x Light central control group for emergency situations
● 4x Shading central facade functions with:
– Central weather station brightness calculation supports facade automatic function
– Glare protection function calculates the glare protection state by central weather station for all
facade
– Annual shading calculates the glare protection state for all facade by in-formation from annual
shading computer
– Thermal protection for unoccupied rooms by central global radiation sensor on weather station
– Three delayed distribution groups for central blind commands for big buildings
● 2x Shading manual central operation with 3 delayed distribution groups for big buildings
● 1x Shading service ensures central commanding of blind group with high priority
● 1x Shading central protection for all blinds with:
– Wind protection
– Precipitation protection
– Frost protection
– Three delayed distribution groups for big buildings
Communication
BACnet MS/TP1 DXR2.M09 DXR2.M09 DXR2.M10 DXR2.M11 DXR2.M12 DXR2.M12 DXR2.M18 DXR2.M18
-101A T-101A -101A -101A P-102A PX-102A/B -101A -102A
Applications
Room operating • • • • • • • •
295 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo Room Automation
VAV system • • •
Lighting • • • • • • • •
Shading • • • • • • • •
Central functions1 • •
Housing
DIN • • • • •
Flat • • •
Operating voltage
230V • • •
24V • • • • •
Digital inputs 1 1 1 1 1 1 2 2
Universal inputs 2 2 2 2 2 2 4 4
Relay outputs 3 1 3
Triac outputs 4 4 6 6 6 8 8
Pressure sensor 1 1
Maximum configuration
Key:
1 Cannot be combined with other applications.
2 Cannot be extended by KNX PL-Link inputs and outputs.
3 Total number of data point used by TX-I/O, KNX PL-Link and DALI. For details, see chapter
System Configuration.
296 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo Room Automation
18
Component Description
DXR2.E17C.. Room automation station, BACnet/IP, 24VAC, 17 I/Os, 30 data points
Table 97: Components for room pressurization and fume hood control
Table 98: Accessories for room pressurization and fume hood control
18.1.2 Programmable
The DXR2.. and PXC3.. room automation stations are programmable, based on
proven application blocks. Thus, solutions can be tailored to specific needs and
can achieve maximum efficiency and comfort.
See Range Description Desigo Room Automation (BACnet), Programmable Room
Automation - Emergency Lighting (A6V10640596), Programmable Room
Automation - Room Operation (A6V10640597), Programmable Room Automation -
Distributed Functions and Scenes (A6V10640598) and Programmable Room
Automation - Lighting Controls and DALI (A6V10640599).
297 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo Room Automation
Topology
Desigo CC
BACnet/IP Ethernet
PXG3.L
Router
BACnet MS/TP
KNX
KNX
DALI
Third-party °C
°C
C
°
°C
C
°
°C
°C
°C
°C
C
°
devices
KNX
Push button, Push button, Push button, Push button, Push button,
AQR25... Detector AQR25... Detector AQR25... Detector AQR25... Detector AQR25... Detector
Room sensor Room sensor Room sensor Room sensor Room sensor
11043z31en_02
GLB/
GDB..1E/KN
VAV compact
controller
Applications
A comprehensive block library for room automation is provided as part the scope of
delivery. The library contains predefined application functions for room climate,
lighting, shading, and superimposed room functions. The applications can be
combined with operating and display functions as required. The individual
application functions can be adapted to customer needs and are programmable.
The application functions do not depend on the selected field devices.
See Application Catalog.
Configuration of application functions
Many application functions are preconfigured and available in the library.
Retroactive configuration during engineering or commissioning is possible. Your
own configured application functions and entire rooms can be stored in a project
library.
Configuration of field devices
The application architecture does not depend on the field device interface. Field
devices can be connected directly to the PXC3 room automation station (via TX-I/O
modules) or via bus (KNX or DALI) or IP communication.
Many field devices are preconfigured and available in the library. Retroactive
configuration during engineering or commissioning is possible. Project-specific field
devices configured accordingly can be saved in a project library.
298 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo Room Automation
18
● Contain bus supplies for island bus, KNX PL-Link, and DALI. Internal bus
supplies can be extended for island bus and KNX PL-Link as needed.
● Have an integrated web server for IP communication with QMX7.E38 touch
room operator units.
See Room automation station PXC3.E7.. (CM1N9203) and Touch room operator
unit QMX7.E38 (CM1N9295).
QMX3 • • • •
QMX7 • • • • •
Programming • • • • •
Peripheral bus
DALI • • •
Maximum configuration
DALI ballasts 64 64 64
Integrated power supply for KNX (mA) 160 160 160 160 N/A
Key:
1 Dedicated devices with KNX PL-Link.
2 Total number of data points used by TX-I/O, KNX PL-Link and DALI. For details, see chapter
System Configuration.
TX-I/O modules
TX-I/O modules (TXM1) help connect field devices to the PXC3 room automation
station. Bus supply and interface modules (TXS1, TXA1) are available as an
accessory.
299 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo Room Automation
The following TX-I/O modules can be used with the PXC3 room automation station:
● TXM1.8T: Triac module with 8 outputs (AC 24 V) to control thermal and
motorized valve actuators (AC 24 V) for up to 4 actuators (3-point output) or 8
actuators (permanent contact or pulse width modulation).
● TXM1.6RL: Bistable relay module to switch lighting for up to 6 data points.
● TXM1.8RB: Relay module to control blind motors for up to 2 motors (3 end
switches) or 4 motors (2 end switches).
● TXM1.16D: Digital input modules for up to 16 data points.
● TXM1.8D: Digital input modules for up to 8 data points.
● TXM1.6R: Relay module for up to 6 data points.
● TXM1.8U: Universal module for up to 8 data points.
See TX-I/O Assortment overview (CM2N8170).
Housing
DIN • • •
Flat • • •
Operating voltage
230V • • •
24V • • •
Digital inputs 1 1 1 1 1 2
Universal inputs 2 2 2 2 2 4
Relay outputs 3 1 3
Triac outputs 4 4 6 6 8
Pressure sensor 1
Maximum configuration
Key:
300 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo Room Automation
18
1 Total number of data points used by TX-I/O, KNX PL-Link and DALI. For details, see chapter
System Configuration.
301 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo Room Automation
A room segment is the smallest indivisible element. A room comprises at least one
or several adjacent room segments. A room segment is defined and created only
once. Room segments are typically combined several times to rooms over the
course of a building's lifecycle.
302 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo RXC
18
Various sources are available for forming these central superposed functions:
● External system or third-party device
● System user via BACnet client
● Building user via BACnet client or local operator unit
● Scheduler or reaction program
● Superposed office based on grouping function
They are distributing after evaluating signals and commands via a Grouping
function.
One group master exists for each of the various categories which then forwards the
resulting information to all assigned group member (rooms). A group master can
for its part be a group member of a superposed group master.
303 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo RXC
Desigo CC
BACnet/IP or BACnet/LonTalk
PXX-L.. PXX-L..
Binding When a LonWorks network is designed, bindings are created with a LonWorks tool
(RXT10 commissioning and service tool or a standard LNS tool). A binding is the
connection of network variables of the same type between different nodes.
Network variables connected in this way communicate implicitly, that is, if a value
changes, the new value is transmitted automatically. Transmit and receive times
are also monitored, making it possible to react to communications errors.
Discipline I/Os Discipline I/Os are function block in the LonWorks system controller that gather
data from the RXC controller and make it available on the BACnet network.
Discipline I/Os are available for HVAC, lighting and blinds.
Floor Level Network (FLN) A Floor Level Network (FLN) is a communications network for room automation.
LonMark Interoperability The LonMark Interoperability Association is an association founded by the
Association manufacturers of LonWorks products, to define independent, interoperability
guidelines for LonWorks systems. The association is responsible for checking
compliance and for the certification of LonMark products.
LonWorks nodes LonWorks nodes are devices that are connected to the LonWorks bus and
communicate with other LonWorks nodes.
Network variables (NV) Network variables (NV) allow the exchange of data between different LonWorks
nodes. This type of communication is also called implicit, because transmission
and reception are automatic. Network variables may be input or output variables.
Room-based groups The discipline I/Os representing the RXC controllers in a room are combined in the
LonWorks system controller into a room-based group. The result is a room view.
Cross-room groupings A cross-room grouping contains all the control variables common to a given user
grouping (for example, North facade, Tenant A, West zone, etc.) and distributes
these control variables to the associated room or group members.
304 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo RXC
18
Standard Network A Standard Network Variable Type (SNVT) is a standard type of network variable,
Variable Type (SNVT) which simplifies the communication between LonWorks nodes. Only network
variables of the same type can be connected. The SNVTs are defined in the SNVT
Master List provided by LonMark.
Lighting and
blinds
VAV
Radiators and
chilled ceilings
Lighting and
blinds
HVAC
305 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo RXC
Desigo RXC applications The controllers and the QAX5.. flexible room units are loaded with application
software which contains the control program for the associated room or area.
Siemens Building Automation maintains a comprehensive library of applications
covering a wide range of HVAC and electrical applications.
See RXC application library Version 2 (CA110300).
Example: Fan coil system
T
T
LON Controller
FNC08 Four-pipe system with room supply air cascade control RXC21.5
RXC39.5
Common functions:
● Window contact, occupancy sensor, four operating modes
● Manual fan control with room unit
● Automatic fan control
● RXC20.5 single-speed, RXC21.5, RXC22.5 three-speed, RXC39.5 constant 0-
10V
● Options with two-pipe systems: Heating only, cooling or changeover via bus
using LonWorks technology
306 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo RXC
18
... ...
RXC application library The RXC application library contains application groups, each of which contains
applications of the same type. The RXC application library has a version number
which is defined in the RXC Valid Version Set. The Valid Version Set also defines
the version of each individual RXC application.
The structure described above can be seen in the documentation and in the
implementation of the RXT10 commissioning and service tool.
Application groups Similar application types are grouped into application groups. These differ from
each other in terms of how the functions are implemented. Thus, chilled ceiling with
radiator (CLC02) and chilled ceiling and electric radiator (CLC03) are two different
applications within the CLC group. The first of these two applications uses water
for heating, while the second uses electrical energy. The difference between
applications in the other groups follows a similar pattern.
The following application groups are available:
● 000: Basic applications (allow the RXC controllers to be used as I/O modules)
● RAD: Radiator applications
● CLC: Chilled ceiling applications
● FNC: Fan coil applications
● VAV: Variable air volume applications
● FPB: Fan-powered box applications (fan-assisted VAV)
● INT: Integrated applications (combined applications including lighting and/or
blinds)
● IRO: Integrated room operation applications (applications for the QAX50/51
flexible room units)
Individual applications The individual application is designed for typical HVAC systems as commonly used
in practice in individual rooms, for example:
● FNC10: Two-pipe system with changeover and outside air damper
● VAV06: Single duct supply and extract air system with electric re-heater
Applications are modular in structure, and cover a specific combination of functions
which are always implemented in the same way, for example, operating modes
and setpoint derivation are identical in all applications (including those in different
application groups). Similarly, fan speed control is identical in all FNC applications.
307 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo RXC
Y [% ]
100 H ea ting Co oling
0 TR
C om fort
P reC omfo rt
E co nomy
B uild in g prote ct io n
F r ost pr ote ct io n
Key:
Y Output signal
TR Room temperature
Configuring applications Each application has a defined number of configuration parameters with which the
application can be programmed for a specific project. These parameters consist
both of general values, for example, temperature setpoints, etc., and of specific
values for the respective application, for example, changeover configuration,
electric reheater, etc.
308 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo RXC
18
Engineered operation – A typical requirement in the case of room integration is a graphical representation
Plant Viewer of the building, showing the different floors and rooms. Desigo Insight supports the
generation of graphics and the integration of RXC.
For each RXC application, there is a predefined graphic (supergenie) in the Desigo
Insight graphics library, containing the main data points. The information contained
in the supergenies is the same as the information in the binding templates in the
RXT10 tool.
309 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo RXC
310 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo RXC
18
application. When mapping an application, however, only the specific data points
for that particular application are mapped to BACnet.
FNC04
FNC03 HVAC
discipline I/Os
FNC02
Inputs Outputs
Only application-
A discipline I/O specific data is
contains a mapped
superset of the FNC04
CLC03 data
CLC02
CLC01
FNC04
FNC03
FNC02
311 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo RXC
Room-based group
Room
RXC1 RXC2
Grouping across rooms A multi-room group contains all the control variables common to a given group of
users (for example, North facade, Tenant A, West zone etc.), and distributes these
control variables to the associated room or group members. For this reason, a
multi-room group contains two member lists, one for the referenced room and one
for the referenced group.
Multi-room groups take the form of blocks and are contained in the block library.
Referenced rooms Referenced rooms are referenced via the discipline I/O of the room-based groups.
Only rooms connected to the same LonWorks system controller can be referenced.
The addressed rooms cannot be modified online.
Referenced groups A multi-room group can also transmit values to another group, which may be
connected to the same or different LonWorks system controller. Up to five more
groups can be addressed. These references can be modified online.
X1 X1
X2 X2
Group objects
X3 X3
A2 __
R101'HVAC R101'HVAC
Room Room
R102'HVAC R102'HVAC
Members: Members:
A1 A1 A1 A1
A2 A2 A2 A2
312 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo RXC
18
HVAC functions:
● Changeover: Transmission of the changeover signal (LTHW or CHW in pipe
work)
● Setpoints: Basic setpoint correction and setpoint adjustments
● Emergency: Override of supply/extract air dampers in the event of fire/smoke
● Outdoor temperature: Distribution of outside air temperature
Electrical functions:
● Lighting: Transfer of lighting control and forced control of lighting
● Blind: Transfer of blind control and forced control of blinds
Time schedules:
● Building use: Transfer of values for the building use time schedule
● Room occupancy: Transmission of values for the room occupancy time
schedule
Floor
"Program" = System function Cmd R101'LightA
R102'LightB
Members:
X1
X2 R101'HVAC
X3 R102'HVAC
Members:
Emergency
Cmd R101'LightA
R102'LightB
Members:
R101'HVAC
R102'HVAC
Members:
313 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo RXB
Desigo CC
PXM20
BACnet
PXC50/100/ TX-I/O
200...D
PX KNX
system controller
TX-I/O
Group address / Binding A group address / binding is a connection of network variables of the same type
between different nodes. The group addresses / bindings are generated using ETS
(EIB tool software) when designing the KNX/EIB network. The bound network
variables communicate when changing the value and using a heartbeat.
Transmission and reception times are also monitored, allowing you to react to
communications errors.
Discipline I/Os Discipline I/Os are function blocks in the PX KNX system controller, which gather
data from the RXB controller and make it available on the BACnet network.
Discipline I/Os are available for HVAC functions.
The Konnex Association is an association founded by the manufacturers of
KNX/EIB products, to define interoperability guidelines for KNX/EIB systems. The
314 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo RXB
18
Konnex Association association is responsible for checking compliance and for the certification of
KNX/EIB products.
KNX/EIB nodes A KNX/EIB node is a device which is connected to the KNX/EIB bus and
communicates with other KNX/EIB nodes.
Network variables (NV) Network variables (NV) allow the exchange of data between different KNX/EIB
nodes. Network variables may be input or output variables.
Room-based groups The discipline I/Os representing the RXB controllers in a room are combined in the
PX KNX system controller into a room-based group. The result is a room view.
Cross-room groupings Cross-room groupings contain all the control variables common to a given user
grouping (for example, north facade, tenant A, west zone, etc.) and distribute these
control variables to the associated room or group members.
PX KNX system controller The PX KNX system controller comprises a PXC001(-E).D controller and loaded
PX KNX firmware. Communication takes place via BACnet/LonTalk (PXC001.D) or
BACnet/IP (PXC001-E.D). With the system controller, you can integrate the Synco
RMU710, RMU720, RMU730 and RMH760 controllers into Desigo.
PX KNX Tool The PX KNX tool is used to configure the PX KNX system controller on the KNX
side.
T
T
KNX/EIB Controller
315 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
18 Desigo RXB
Common functions:
● Window contact, occupancy sensor, four operating modes
● Manual fan control with room unit
● Automatic fan control (three speeds)
● Options with two-pipe systems: Heating only, cooling or changeover via
KNX/EIB bus
316 | 377
Siemens CM110664en_03
2017-09-18
Room Automation
Desigo RXB
18
317 | 377
Siemens CM110664en_03
2017-09-18
Desigo Open
19 Desigo RXB
19 Desigo Open
Desigo Open lets you integrate devices and systems from different manufacturers
into the Desigo system. Integration with Desigo Open offers:
● Standardized automated functions, operating and monitoring of the entire
building
● Single-station operation, common view and display. Simplified multidisciplinary
operation, common reporting and common alarm management.
● Peer-to-peer interaction, communication on the automation level, automated
interactions and data exchange
● Comfort combined with lower energy consumption. New opportunities to save
energy with systems that communicate among themselves. Improved
performance, efficiency evaluation, flexibility and ability to modify system
operation and configuration without re-cabling or new hardware.
● Engineering of integrated solutions in Xworks Plus (XWP)
● Reduced risk thanks to standard solutions. Clear functions that cover the most
important standard protocols.
Topology Third-party devices and systems can be integrated with Desigo on all levels.
Desigo CC
BACnet
Management level
Third-party system
10660Z04en_08
Third-party
system
BACnet/LonTalk or BACnet/IP
Router
Automation level
QAX9..
EnOcean
Room units
RXZ97.1/KNX
room level
Field and
Room level (Desigo Room Automation and DALI, KNX, EnOcean, LonWorks
RX)
318 | 377
Siemens CM110664en_03
2017-09-18
Desigo Open
Integration on Management Level
19
SDKs If a solution is not supported by HQ and RCs need a specific solution, HQ offers
Software Development Kits (SDKs) for experts. The regional companies can
develop their own solutions using Software Development Kits (SDKs).
The following SDKs are available:
● PX Open platform SDK
● TX Open platform SDK
Desigo CC
BACnet BACnet is a widely used communication protocol for building automation and
control networks. It defines a number of objects, services and data link layers. It is
an essential part of Desigo CC's openness for integrating any third-party devices,
using the BACnet/IP protocol. An online auto-discovery and alternatively an offline
EDE import are available for integrating third-party devices.
See BACnet 3rd party Integration Guide (A6V10446271).
BTL Desigo CC is compliant with BACnet revision V1.13 of the latest BACnet Standard
135-2012. The compliance and interoperability has been tested. For more
information, see (http://www.bacnetinternational.net/btl).
Modbus-TCP A native Modbus-TCP driver lets you integrate a Modbus TCP server and
subsequent Modbus RTU devices via a protocol converter. An offline importer
supports the engineering workflow for integrating Modbus data points.
See Modbus Integration Guide (A6V10438039).
OPC OLE for Process Control (OPC) is a communication standard for exchanging data
between windows based software applications and process control hardware
without any proprietary restrictions. It is a client/server technology, where one
application acts as the server providing data, and another acts as a client using
data. The most common specification Data Access (DA) defines a set of objects,
interfaces and method to facilitate the interoperability. OPC has been extended to
become a cross-platform communication standard, named OPC Unified
Architecture (OPC UA).
319 | 377
Siemens CM110664en_03
2017-09-18
Desigo Open
19 Integration on Management Level
For more information about OPC, see the documentation by the OPC Foundation
(www.opcfoundation.org) and the OPC Training Institute (www.opcti.com).
OPC DA client An OPC client interface lets you integrate any OPC server, using the Data Access
specification. An offline Importer supports the engineering workflow to integrate
OPC items.
See OPC Server Integration Guide (A6V10415483).
OPC DA server An OPC server option provides a freely configurable set of data points for
integration in any enterprise system, using the OPC DA standard. Each data point
(object) is represented by several OPC items, providing the relevant readable and
writable object property information.
See OPC DA Server Manual (A6V10415485).
The Desigo CC OPC server is officially tested and certified by the OPC foundation
(https://opcfoundation.org/products/view/251).
OPC UA server OPC Unified Architecture (OPC UA) clients can connect to the Desigo CC OPC DA
server using the OPC DA/UA wrapper, provided with the Desigo CC setup. The UA
wrapper meets the security model of mutual authentication for a trusted connection
between the OPC UA server and the OPC UA client.
See OPC DA Server Manual (A6V10415485).
Simatic S7 A native S7 Ethernet driver lets you integrate S7-300 and S7-400 or S7-400H PLC.
You can use the CP for Ethernet or the built-in PNIO interface on the S7 hardware.
An offline importer supports the engineering workflow for integrating S7 data points.
See Simatic S7 Integration Guide (A6V1042787).
SNMP Simple Network Management Protocol (SNMP) is a data communication protocol
for monitoring devices and applications on a network. It is an Ethernet based
protocol for retrieving management data from networked devices, and exposing
this data as properties.
SNMP gives you the capability to monitor a device, for example, a printer or UPS,
which is not directly configured on a computer, but can be reached through a
network link.
Device monitoring capabilities are provided by device manufacturers via a
Management Information Base (MIB) text file, which describes the structure of the
device management data. MIB files use a hierarchical namespace containing
object identifiers (OID). Each OID identifies a property that can be read or written
via SNMP.
Desigo CC has an SNMP Manager feature for reading and writing information from
SNMP agents.
See SNMP Application Guide (A6V10455382).
Web services Using RESTful technology, Desigo CC provides alarm, object and time series data
via web based services for supervising management platforms or other third-party
external applications.
SX Open
SX Open is a configurable third-party system - BACnet/IP gateway. It allows the
data exchange between third-party systems and the Desigo system in an IP
network. That means, Desigo automation stations (peer-to-peer communication) or
a BACnet management platform. Multiple BACnet servers can be defined in the
gateway and third-party data points can be mapped to standard BACnet objects.
The mapping supports functional and signal mapping. Alarms, trends and
schedules can be defined in the BACnet server. With SX Open you can integrate
any number of data points. There are two application types.
SX API is the basic software with an Application Programming Interface (API). With
the API you can independently develop other applications using Microsoft® Visual
320 | 377
Siemens CM110664en_03
2017-09-18
Desigo Open
Integration on Automation Level
19
SX API Studio, if necessary. This lets you integrate other third-party systems, protocols,
and drivers.
SX OPC The predefined SX OPC application contains an OPC DA client that can connect to
respective OPC servers of the third-party system and map their domain to the
respective BACnet objects and properties.
Engineering Engineering is carried out with the SX Configurator (a predefined Excel sheet) in
which the allocation of OPC objects and BACnet objects can be configured line by
line. You can also enable additional functions, such as alarm, scheduler, trend and
individual mapping functions.
See SX OPC SX Configurator User's Guide (CM110702) and SX Open
Engineering Guideline (CM110700).
Licensing SX Open is available for both application types in four different license models,
graded according to the number of BACnet I/O and value objects.
● Tiny for up to 200 BACnet objects
● Light for up to 2,000 BACnet objects
● Regular for up to 5,000 BACnet objects
● Full for up to 20,000 BACnet objects
The license is linked with the hardware in use (the physical MAC address). A
registry key is generated with the license. The licenses can be ordered and
downloaded via CGU Web.
All third-party software is available directly from the appropriate producer as
described in the application guide. The number of configured BACnet objects are
relevant for licensing.
Installation SX OPC operates under Microsoft Windows. The SX OPC setup file including the
function block library and the SX OPC documentation can be downloaded from the
intranet.
See SX Open data sheet (CM1N9745).
321 | 377
Siemens CM110664en_03
2017-09-18
Desigo Open
19 Integration on Automation Level
● PX Pronto
● PX Open Plattform (SDK)
Data points
PXC001.D PXC001-E.D PXA40-RS1 PXA40-RS2
PX KNX 2,000 2,000 N/A N/A
The platform for integrating LonWorks compatible third-party devices consists of:
● System controller PXC00.D and automation station PXC50.D, PXC100.D or
PXC200.D for integrating LonWorks devices via BACnet/LonTalk
● System controller PXC00-E.D and automation station PXC50-E.D, PXC100-
E.D or PXC200-E.D for integrating LonWorks devices via BACnet/IP
● PXX-L11 and PXX-L12 expansion modules for 60 and 120 LonWorks devices
PXC00..D with PXX-L11/L12 supports the firmware versions V4.1, V5.0, V5.1 and
V6.0.
PXC50..D, PXC100..D and PXC200..D with PXX-L11/L12 support the firmware
versions V5.0, V5.1 and V6.0. For information about the system limits, see chapter
System Configuration.
PX KNX PX KNX connects KNX networks with Desigo and maps the group addresses to
BACnet datapoints. PX KNX can handle the following main tasks:
● Data compression on the automation level (group functions)
● Time control
● Alarming, device monitoring
● Trend storage
● Mapping the Desigo RXB applications to BACnet for operating and monitoring
PX KNX supports the integration of:
● KNX S mode third-party devices
● RDF, RDG and RDU room thermostats
● RXB room automation stations
The PXC001.D system controller can integrate KNX via BACnet/LonTalk. The
PXC001-E.D system controller can integrate KNX via BACnet/IP. PX KNX is
preinstalled on PXC001..D controllers.
PX Modbus PX Modbus connects Modbus devices or networks supporting the Modbus protocol
to the Desigo system and maps their data points to BACnet data points. PX
Modbus is particularly suitable for integrating industrial controls or chillers and
linking them to the automation process.
The PXC001.D system controller can integrate Modbus via BACnet/LonTalk. The
PXC001-E.D system controller can integrate Modbus via BACnet/IP. The PXA40-
RS1 and PXA40-RS2 option modules support additional data points.
See PX Modbus (CA2N9772).
PX M-Bus PX M-Bus connects the M-Bus consumption meters to the Desigo system and
maps meter readings and device-related meter information to BACnet data points.
PX M-Bus handles the following main activities:
322 | 377
Siemens CM110664en_03
2017-09-18
Desigo Open
Integration on Field Level
19
323 | 377
Siemens CM110664en_03
2017-09-18
Desigo Open
19 Integration on Field Level
324 | 377
Siemens CM110664en_03
2017-09-18
Desigo Open
Integration on Room Level
19
TX Open Platform (SDK) HQ provides the TX Open Platform Software Development Kit (SDK), including
training, for experts in the regional companies. The training course provides the
necessary tools and knowledge to create new protocol applications.
325 | 377
Siemens CM110664en_03
2017-09-18
Desigo S7 Automation Stations
20 Integration on Room Level
PXM20
Operator unit
BACnet/IP
Ethernet
RS232
TOUCH
PXM10 PXC...D
Operator unit Compact
PROFIBUS DP / PROFINET/IP
326 | 377
Siemens CM110664en_03
2017-09-18
Desigo S7 Automation Stations
Product Range Overview
20
Desigo S7 Building The market performance package Desigo S7 Building Solution lets you expand a
Solution Desigo system using Simatic S7. Desigo S7 Building Solution is a complete
solution for industrial building automation and control. It expands the Desigo
system using Simatic S7 components and tools. The package uses the Desigo S7
HVAC library which is modeled on the Desigo application library.
It includes the following expansions, in addition to the communications processor
CP 343-1 BACnet:
● Desigo S7 Library
● Desigo S7 Basis Tool
Desigo S7 Library The Desigo S7 Library consists of an HVAC block library based on the proven
Desigo applications concept and functionality of the Desigo PX firmware library and
the HVAC compound library. The compound library includes preconfigured,
documented and tested applications as the basis for project-specific applications.
Desigo S7 Basis Tool The Desigo Basis Tool is an engineering tool based on the CFC Standard Tool. It
provides consistent data and efficient engineering thanks to a common data basis
for automation software and BACnet configuration. The Desigo Basis Tool is fully
integrated into the Simatic tool environment. Software changes are possible during
operation (delta download).
Desigo S7 Building The market performance package Desigo S7 Building Integration allows for
Integration seamless integration of existing Simatic S7 automation stations into the Desigo
system via BACnet communication.
In addition to using existing Simatic S7 and tools together with the CP 343-1
BACnet communication processor, the market performance package also includes
the Desigo S7 Mapping Tool.
Desigo S7 Mapping Tool The Desigo S7 Mapping Tool maps process data to BACnet objects and has
conversion functions for adapting the format.
Runtime protection
The licensing model from Siclimat is used for Desigo S7. Licensing costs depend
on the number of BACnet objects used for the building solution market
performance package. The license key must be entered on the corresponding pin
for block AS_BASIC.
The license key is part of the project data in the mapping tool for the market
performance package.
327 | 377
Siemens CM110664en_03
2017-09-18
Desigo S7 Automation Stations
20 Product Range Overview
Simatic ET 200 S
In conjunction with Simatic S7, digital and analog inputs and outputs can be linked
to the central control system via the PROFINET or PROFIBUS DP field bus system.
The peripheral devices can perform central control sub-functions independently.
Sections of the plant can be tested and commissioned in advance. In the event of
an error, stand-alone elements can continue to operate autonomously.
Ordering
All Simatic components are ordered via the standard horizontal path at Siemens for
the relevant region.
The CP341-1 BACnet is ordered directly by SBT at the Distribution Center
Nuremburg.
The touch panel TP177B is ordered via the configuration center at SBT Zug.
Desigo S7 tools and library are downloaded via the SBT Standard Download
Server.
328 | 377
Siemens CM110664en_03
2017-09-18
Desigo S7 Automation Stations
System Limits
20
Item Limits
Configured alarm recipient (number of entries on the NC recipient list) 30
COV subscriptions as server (If > 400 decrease of updating performance) approx. 400
Number of BACnet I/O objects including typical HVAC application* for building solution:
Trend Log – limited only by available RAM in the CPU Depends on RAM*
Key:
* A calculation table is available for a more precise calculation.
329 | 377
Siemens CM110664en_03
2017-09-18
Desigo S7 Automation Stations
20 Alarm Management
Desigo S7 Desigo PX
Principle The Notification Class (NOTIFCL) is local and applies Notification Class is a server function that applies
per automation station only. globally for the entire site.
Number of Notification One NOTIFCL required per automation station in the 48 NOTIFCL blocks per automation station in the
Class objects Global chart. Global chart.
All entries are made in this block.
Number of alarm classes 32 alarm classes (only 6 are used in the library). 16 alarm classes (only 6 are used in the library).
330 | 377
Siemens CM110664en_03
2017-09-18
Desigo S7 Automation Stations
Control Concept
20
Desigo S7 Desigo PX
Number of objects One CMN_ALM per BACnet hierarchy A CMN_ALM block per plant
Alarms can be acknowledged via the TP177B, which is wired on the CMN_ALM -
Acknowledge a BACnet hierarchy level.
Alarmable blocks not interconnect on the CMN_ALM may only be operated via a
BACnet client.
Desigo S7 Desigo PX
Principle Interconnected with CMN_ALM (optional functionality) Integrated in CMN_ALM
Number of objects One block per BACnet hierarchy A CMN_ALM block per plant
Number of filters Four filters per block – multiple blocks may be used Five filters
Desigo S7 Desigo PX
Function Light control Compound solution using the same functional scope
Flash speed depends on the alarm input
Control strategy
The control strategy for Desigo S7 is similar to the control strategy for PX.
The strategy comprises the following function blocks:
● PID_CTR: As individual controlled or wired (FmHigher/ToLower). It can be
used as a sequence controller. The block is mapped on a standard BACnet
loop object. This expands the interface for Desigo S7.
● CAS_CTR: A cascade controller like in PX.
● SEQLINK: The block binds multiple PID_CTR blocks to a sequence controller.
The block offers benefits primarily during engineering (PX).
331 | 377
Siemens CM110664en_03
2017-09-18
Desigo S7 Automation Stations
20 Desigo S7 Block Library
I/O blocks
Emergency operation Manual operation can be recorded directly on the I/O Module using Desigo. For
(local override) Desigo S7, local manual override is logged on the module level via its own
feedback signal. The blocks BO, AO and MO have the pin [Ovrr] for this purpose.
In contrast to Desigo, the value of manual operation is not issued on PrVal.
332 | 377
Siemens CM110664en_03
2017-09-18
Desigo S7 Automation Stations
Operating States
20
Peer-to-peer blocks
Blocks AO_PTP, BO_PTP and MO_PTP (FB327) write a value to the BACnet
object (command via BACnet). The block is used to write a process value via
BACnet to another automation station (commanding).
Device object
Each automation station contains a device object, which in turn contains the device
and system information for that automation station. The device object is a standard
BACnet object, representing the entire Desigo S7 automation station and, among
other, includes a list of all processed BACnet objects.
BACnet – IP RUN BACnet/IP allows Ethernet communication including BACnet/IP and S7 communication.
BACnet communication can also be interrupted in RUN mode. Reasons:
- No BACnet configured (S7 – hardware configuration)
- Reconfiguration is running
- Fatal error BACnet – CP
BACnet – IP STOP BACnet/IP allows PG functions via Ethernet, for example, restart or diagnostics.
The STOP state is achieved due to:
- Fatal error BACnet - CP
- User operation
333 | 377
Siemens CM110664en_03
2017-09-18
Desigo S7 Automation Stations
20 Error Sources and Monitoring Functions
Error Effect
1) Fatal error in S7-CPU, for example, memory command S7 goes to STOP.
code. All binary outputs are reset.
2) Potentially dangerous process state in S7-CPU, for The application is no longer processed.
example, faulty I/O periphery. An alarm is sent via BACnet.
BACnet communication is stopped.
S7 must be restarted locally or via remote following troubleshooting.
5) Non-critical error BACnet-CP, for example, buffer An alarm is sent via BACnet.
overloaded.
334 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
Error Sources and Monitoring Functions
21
21 System Configuration
System overview
Terms
Desigo system Covers all the devices on the MLN (Management Level Network), ALN (Automation
Level Network) and FLN (Field Level Network).
335 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
21 Error Sources and Monitoring Functions
One Desigo system may comprise several BACnet internetworks. These are
connected into a system with Desigo CC. In this case, Desigo CC appears as a
BACnet device in several BACnet internetworks.
BACnet internetwork A BACnet internetwork consists of one or several BACnet networks. Individual
BACnet networks are connected to BACnet routers.
Each BACnet device can communicate with another BACnet device in the
internetwork. A BACnet device in one internetwork cannot communicate with a
device in another internetwork.
A Desigo management station can be used to integrate the operation of several
BACnet internetworks and other systems (see Desigo system).
When defining the system configuration, FLN integrations (LonWorks, KNX) are
also added to the BACnet internetwork. In this way, the Desigo system can be
seen as a combination of several BACnet internetworks. Technically, the individual
FLN devices are not BACnet devices. They do not communicate via the BACnet
protocol.
BACnet PTP internetwork BACnet PTP communication uses modem (telephony) or null-modem (RS232)
connections. Owing to the slow rate of data transfer via these connections, the
limits are lower for a BACnet PTP internetwork. Modem-based PTP connections
are considered obsolete and are therefore no longer used. The BACnet PTP
communication connects BACnet networks via BACnet half routers.
BACnet network A quantity of BACnet devices connected within an IP or LonTalk or MS/TP network
with specific (that means, the devices are in the same BACnet Broadcast Domain)
limits. In the case of the LonTalk or MS/TP network, the limit is physical. In the
case of an IP network, the network can be physically the same, but the limit is
determined by different UDP ports.
Local communication between two BACnet devices in a BACnet network is not
visible in another BACnet network.
IP segment Sub-area of an IP network. IP segments are connected by IP routers.
In order to ensure that BACnet communications (Broadcasts) can always take
place across IP routers, BBMDs (BACnet Broadcast Management Devices) are
required. PXG3.L/M and PXC…-E.D over IP can be configured as BBMDs.
Individual BACnet devices in an IP segment can register with a BBMD as foreign
devices.
LonWorks segment (ALN) Sub-area of a BACnet/LonTalk network. LonWorks segments are connected by
LonWorks routers. In most cases it is not necessary to divide a BACnet/LonTalk
network into several LonWorks segments (ALN).
It is not possible to use a LonWorks router because of the restricted length of the
data packets. An L-Switch can be used as a router on the ALN.
LonWorks segment (FLN) Sub-area of a LonWorks network. LonWorks segments are connected by
LonWorks routers.
An L-Switch or a LonWorks router can be used as a router on the FLN.
LonWorks trunk (FLN) Comprises all the devices connected on the FLN side of the PXC00.D/-E.D + PXX-
L1…. Consists of one or several LonWorks segments (FLN).
A LonWorks trunk (FLN) is the equivalent of a LonWorks network (FLN).
PX KNX integration Comprises the integration of KNX devices that are connected on the FLN side of
the PXC001.D/-E.D.
PX site A Desigo PX automation system site.
The PX BACnet devices which control the plant in a PX site are interconnected via
the global objects and the primary copy procedure.
A PX site is independent of the limits affecting the BACnet network. A site can
extend over several BACnet networks. One BACnet network may include several
sites. All the associated limits must be maintained simultaneously.
336 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
Technical Limits and Limit Values
21
337 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
21 Networks
21.2 Networks
The following table shows the maximum number of elements, permitted in a
network area.
The columns show the network area. The rows show the maximum number of
elements permitted in the network area. For example, network area: BACnet
internetwork; number of elements: BACnet/LonTalk network. Maximum number of
BACnet/LonTalk networks per internetwork = 100.
Number of elements / Per Desigo BACnet BACnet BACnet/ BACnet BACnet/ LonWorks PX KNX PX site
network area system inter- PTP inter- IP MS/TP LonTalk trunk inte-
network network network network network (FLN) gration
Desigo topology
BACnet internetwork 200 n/a n/a n/a n/a n/a n/a n/a
BACnet PTP internetwork 118 n/a n/a n/a n/a n/a n/a n/a
BACnet/IP network n/a 10 [50*] [1]19 n/a n/a n/a n/a [total 20]
BACnet MS/TP network n/a [50] n/a 8 n/a n/a n/a n/a
PXG3.M/L (BACnet router) n/a [100] [30] [100] 1 1 n/a n/a n/a
IP segment n/a 10 [50*] 6 [50*] 6 10 [50*] 6 n/a n/a n/a n/a n/a
LonWorks segment (ALN) n/a [100] [30] n/a n/a 1 n/a n/a n/a
PX plant [4,000] [2,000] [60] n/a n/a n/a n/a n/a 100
LonWorks trunk (FLN) [200] [100] [30] n/a n/a n/a n/a [50]
LonWorks segment (FLN) n/a n/a n/a n/a n/a n/a [5] n/a [250]
PX KNX integration [200] [100] [30] n/a n/a n/a n/a [50]
Desigo devices
PX… without DXR2/PXC315 [2,000] [1,000]9 [30] [200]8 n/a 30 n/a n/a 50/10017
PXC3.E (Desigo Room (10,000)16 [1,500] n/a 25023 n/a n/a n/a n/a n/a15
Automation) (2,500) [500]24
DXR214 (Desigo Room (10,000)16 [1,500] n/a 25023 6421 n/a n/a n/a n/a15
Automation) (2,500) [500]24
PXM20-E n/a (50)9 [20] [50] n/a n/a n/a n/a total 1510
PXA40-W1/W2 (integrated n/a (15)9 [15] [15] n/a [15] n/a n/a total 1510
web server)
Desigo Xworks Plus (XWP) n/a [10] [10] [10] n/a [5] n/a n/a total 1510
(commissioning)12
Total LonWorks nodes [40,000] [20,000] [6,000] n/a n/a n/a 3002 n/a [10,000]
RXB [8,000] [2,000] [1,200] n/a n/a n/a n/a 454 [2,000]
Physical data points [100,000] [100,000] [3,000] [20,000] n/a n/a n/a n/a [6,000]
Total BACnet objects [500,000] [100,000] [30,000] [100,000] [3,000] [30,000] n/a n/a [50,000]
Trendlog object [30,000] [2,500] [200] [2,500] [540] [600] n/a n/a [1,000]
338 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
Networks
21
Key:
n/a Not applicable.
– No restrictions.
2 Not the same as the number of integrated devices ( PXC00.D/-E.D + PXX-L…).
3 LonWorks routers must not be used at the automation level.
4 Limit applies only if this device type is used exclusively.
6 For higher performance use a PXG3 instead of a PXC-E.D for the BBMD function.
7a Limit for PXC00.D/-E.D + PXX-L11.
7b Limit for PXC00.D/-E.D + PXX-L12.
8 Limit for PX devices without Desigo Room Automation (due to PX web support of a PX site). Do
not exceed the number of PXC devices per site.
9 The limit on the number of PX automation stations per internetwork can only be maintained if no
PX clients (PXM20, PXM20-E, PXA40-W1/W2) are used. PX clients limit the permissible number
of PX per internetwork. The values can be obtained by reference to the relevant automation
station columns. The restricted view option does not affect the system configuration of PX clients.
10 The number of temporary alarm receivers in a PX is a technical limit. The recommended limit is
lower. This takes account of the fact that additional devices may be connected for service
purposes.
11 The number of temporary alarm receivers in a PX is a technical limit. The recommended limit is
lower. This takes account of the fact that additional alarm receivers (third-party) may have entries
in this list.
12 Parallel engineering (commissioning ) is possible subject to the following restrictions:
- Node setup: Only one XWP per LonTalk/IP segment.
- Download and online operation: only one XWP for each automation station.
14 In pressurized rooms with or without fume hood, all automation stations of a room must be
connected to a switch in a starlike manner to ensure high availability.
15 Desigo Room Automation automation stations do not belong to a PX site (no primary copy
function).
16 For the system configurations of the Desigo CC management platform, see Desigo CC System
Description (A6V10415500).
17 50: If Lon PX exists in the PX site. 100: If no Lon PX exist in the PX site (only IP PX).
18 These limits in the Desigo system refer in particular to Desigo Insight. The limits may be
significantly lower due to the PTP connection(s) outside the Desigo system and their technical
limitations. Examples of such limitations outside the Desigo system can include available
bandwidth for the PTP link or available modem speeds.
19 This limit can be exceeded if all BACnet devices are located within the same IP subnetwork, or if
no communication between the various BACnet/IP networks is required.
20 These limits apply only to IP-based DXR2 devices.
21 These limits apply to MS/TP-based DXR2 devices.
23 Multiple IP segments per BACnet internetwork.
24 One IP segment per BACnet internetwork.
For more information about networks, see Application Guide for IP Networks in
Building Automation Systems (CM110668).
339 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
21 Networks
Number of external BACnet references 500 Maximum number of external BACnet references that support a
Desigo Room Automation system function PX. The Desigo Room
Automation system function PX requires external references for the
life check and for scheduler functions. Examples of objects with
external references:
- EventEnrollment: 1reference
- Schedule: 1-5 references
Event Enrollment per Desigo Room 1 Number of Event Enrollment objects required on the Desigo Room
Automation automation station Automation system functions PX for the life check per Desigo Room
Automation automation station.
Sample number of Desigo Room Automation 250 Desigo Room Automation system function PX with maximum
automation stations per Desigo Room scheduler functions.
Automation system function group The limit designates the maximum number of Desigo Room
Automation automation stations in the Desigo Room Automation
system function group. In this example, it is assumed that the
following scheduler objects are available on the Desigo Room
Automation system function PX:
- Maximum number of scheduler objects
- Per scheduler object, maximum number of external references
Sample number of Desigo Room Automation 500 Desigo Room Automation system function PX without scheduler
automation stations per Desigo Room functions.
Automation system function group The limit designates the maximum number of Desigo Room
Automation automation stations on the Desigo Room Automation
system function group. In this example, it is assumed that no
scheduler objects are available on the Desigo Room Automation
system function PX.
Table 117: Desigo Room Automation automation stations with own alarming (Desigo V6.x)
340 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
Devices
21
21.3 Devices
Number of function block 1,900* 1,900* 1,900* 2,900* 1,900* 2,900* 2,900*
instances (application
size)
Physical data points n/a 52* 200* 15 (350)15 n/a n/a n/a
I/O module (TX-I/O, PTM)
Total number of data n/a 400* 600* 15 (1,000) 15 n/a n/a n/a
points (TX-/I/O, PTM and
TX Open)
TX Open per island bus n/a 516 516 516 n/a n/a n/a
P bus BIM TXB1.PBUS12 n/a n/a n/a n/a n/a n/a n/a
Dynamic event enrollment 50* 50* 50* 50* 50* 50* 50*
objects20
Dynamic notification class 50* 50* 50* 50* 50* 50* 50*
objects20
Dynamic trend log 100* 100* 100* 100* 100* 100* 100*
objects20
Dynamic trend log 20* 20* 20* 20* 20* 20* 20*
multiple objects 20
341 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
21 Devices
Key:
n/a Not applicable
1 PXM20, PX-Web and XWP are temporary alarm receivers.
2 Desigo CC is a configured alarm receiver.
The number of entries in the notification class is limited to 20. The total number of different
configured alarm receivers across all notification classes is limited to 30.
3 Max. number of SubscribeCOV requests which can be accepted.
Example: 400 1 client and 400 values 2 clients and 200 values.
4 Max. number of BACnet client references, values read from or written to (commanded) your own
automation station or a remote automation station.
BACnet client references are used in Input, Output, Scheduler, Trendlog and Group objects (all
NameRef_Type inputs with AddrKind = B). The configured alarm receivers of the Notification
Class objects do NOT require any BACnet client references.
The available number of BACnet client references shall address not more than 50 different
remote automation stations. If this value is exceeded the number of BACnet broadcast messages
on the network will increase.
5 Every active Trendlog object needs a BACnet reference.
Trends need 12 bytes per entry (irrespective of data type). Max. 64 KB can be allocated to the
log buffer (approx. 5,000 entries) for each Trendlog object. These log buffers are assigned in D-
MAP RAM. If the log buffer size is changed and there is insufficient D-MAP RAM available, the
Reliability property of the Trendlog object is set to Memory limit reached.
6 Max. number of physical data points (TX-I/O module) for PXC64-U is 200.
Max. number of physical data points (TX-I/O module) for PXC128-U is more then 200, however
the reaction times are in accordance with following table and the system limits to consider.
The number of physical data points influences the reaction time of the application. If minimum
reaction times are specified, the number of physical data points may have to be reduced.
The following relationship between reaction times and the number of physical data points can be
assumed:
- up to 150 physical data points = Reaction times < 1s
- up to 250 physical data points = Reaction times 1-2s
8 The address of the PPS-2 devices QAX84.1 and RXZ90.1 is always 1 (no address selection).
9 PX KNX = PXC001.D / PXC001-E.D and loaded PX KNX firmware.
10 PX Open = PXC001.D / PXC001-E.D with option module PXA40-RS1/RS2 and loaded PX Open
firmware.
14 Maximum 30 calendar entries.
15 Max. number of physical data points for PXC100.D/-E.D is 200.
Max. number of physical data points for PXC200.D/-E.D is more then 200, however the reaction
times are in accordance with following table and the system limits to consider.
The number of physical data points influences the reaction time of the application. If minimum
reaction times are specified, the number of physical data points may have to be reduced.
The following relationship between reaction times and the number of physical data points can be
assumed:
- up to 150 physical data points = Reaction times < 1s
- up to 250 physical data points = Reaction times 1…2 s
- up to 350 physical data points = Reaction times 2…3 s
16 Max. 5 TX Open per PXC50/100/200…D.
342 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
Devices
21
D-MAP RAM If the whole D-MAP RAM is taken up with trendlog objects, a delta (differential)
download will no longer be possible.
The overall size of the free and used D-MAP RAM can be viewed with XWP,
Desigo CC or PXM20. The information concerned is stored in the device object
under the memory statistics property [MemStc].
Access rights Access rights are managed via USPRF. You can define a maximum of 10 user
management groups and 20 users. 10 user groups and 6 users are already predefined as a
template (global chart).
Item Limit
LonWorks devices:
PXX-L11 60* (for example: 5 Group Members are defined, that means 5 x 12 = 60 COV resources are needed)
PXX-L12 120*
Max. number of integrated LonWorks devices covers RXC..., QAX50/QAX51 and third-party
LonWorks devices.
Group members Cross-disciplinary groups can have more than 5 destinations. The number of cross-disciplinary groups
depends on the COV client resources (max. 250). A different number of COVs is required, depending
on the group type. These must be multiplied by the number of destinations.
Calculation basis:
343 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
21 Devices
Reaction times depending on number of Without LonWorks devices Up to 5 LonWorks devices 5 to 20 LonWorks devices
physical data points
Max. 150 data points < 1s 1-2s 3-4s
SCL data points [250*] Max. number of data points per PX SCL.
M-bus data points [250*] Max. number of data points per PX M-bus.
SCL data points [800*] Max. number of data points per PX SCL.
M-bus data points [800*] Max. number of data points per PX M-bus.
344 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
Devices
21
SCL data points [1,000*] Max. number of data points per PX SCL.
M-bus data points [2,000*] Max. number of data points per PX M-bus.
RXB 45 Max. number of RXB devices per KNX (approx. 50 KNX data points
per RXB, depending on the application).
RXL 45 Max. Number of RXL devices per KNX (approx. 50 KNX data points
per RXL, depending on the application).
TXM1.8RB 8 I/O blinds modules max. 8 Used TX-I/Os are counted (1 data point per
relay).
345 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
21 Devices
TXM1.8D 8 I/O digital input modules max. 8 Used TX-I/Os are counted.
TXM1.16D 16 I/O digital input modules max. 16 Used TX-I/Os are counted.
346 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
Devices
21
AQR253… Flush-mounted room sensor with: 1-3 Fixed count, 1 data point per measured value
AQR257… Front module (optional potential-free, passive NTC sensors
are not counted)
Base module
347 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
21 Devices
ASN Physical TX-I/O data points used Total I/O data points (TX-I/O, DALI, KNX PL-Link)
PXC3.E16A n/a 64
PXC3.E72 72 140
PXC3.E72A 72 140
Templates with standard background pictures 2 6 Maximum number of different templates which are using the default
background pictures.
Customized background pictures 2 1.5 MB Maximum total size of all customized background pictures (the PNG
file format is used as a reference).
Key:
1 Restriction: When using standard web clients (web browser on PCs, smart phones, tablets, etc.),
the screen display and operation (touch or mouse) are neither modified nor tested for the
available browsers.
2 Valid values when using 8 room applications at the boundary of maximum system limits.
348 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
Devices
21
ASN Max. number of onboard IO- and KNX PL-Link data points Description
DXR2.x09T 30 1 DI, 2 UI, 4 Triac, 1 AO, 1 Relay
Templates with standard background pictures 2 2 Maximum number of different templates which are using the default
background pictures.
Customized background pictures 2 1.5 MB Maximum total size of all customized background pictures (the PNG
file format is used as a reference).
Key:
1 Restriction: When using standard web clients (web browser on PCs, smart phones, tablets, etc.),
the screen display and operation (touch or mouse) are neither modified nor tested for the
available browsers.
2 Valid values when using 8 room applications at the boundary of maximum system limits.
Alarm administration Only the alarms from the site where the user is logged on are
displayed (PXM20 self-registers as temporary alarm recipient for all
devices of a site).
BACnet objects in alarm per site 50* Maximum number of BACnet objects per site.
The administration of the number of BACnet objects in alarm per site
is limited. Others cannot be displayed or operated in Alarm Viewer
when there are more BACnet objects in alarm.
Alarm History 50* Maximum number of entries in the Alarm History. The oldest entries
are deleted when this limit is exceeded.
349 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
21 Devices
Alarm administration Only the alarms from the site where the user is logged on are
displayed. (PXM20-E self-registers as temporary alarm recipient for all
devices of a site).
BACnet objects in alarm per site [250*] Maximum number of BACnet objects per site.
The administration of the number of BACnet objects in alarm per site
is limited. Others cannot be displayed or operated in Alarm Viewer
when there are more BACnet objects in alarm.
Alarm administration Management of the alarms of the PXC to which the PXM10 is
connected.
BACnet objects in alarm per PXC 25* Max. number of BACnet objects in alarm per PXC.
The management of the number of BACnet objects in alarm per PXC
is limited. Others cannot be displayed or operated in Alarm Viewer
when there are more BACnet objects in alarm.
350 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
Devices
21
Alarm administration Alarm Viewer only handles the alarms from the local device.
SMS/Email messages 50* Maximum number of SMS/email messages that can be sent.
There is a limit to the number of messages sent by SMS/email. If
more than this number of BACnet objects are in alarm in the BACnet
internetwork, no SMS/email objects will be sent for these.
Web graphic pages [100] Number of web graphics: Limited at present by the available memory
for the sum of all files of max. 7 MB.
Objects per web graphics page 60 Number of objects per web graphic.
Alarm administration Management of all alarms in the BACnet internetwork (from all sites)
(PXA40-W1/W2 registers as a temporary alarm recipient with all
devices in the BACnet internetwork).
In Alarm Viewer, only the alarms from the site where the user is
logged on are displayed.
However, alarms from all sites can be forwarded via SMS and/or
email.
BACnet objects in alarm per internetwork 1,000* Maximum number of BACnet objects in the alarm per BACnet
internetwork.
Administration of the number of BACnet objects in alarm per BACnet
internetwork is limited. Others are not handled when there are more
BACnet object in alarm.
BACnet objects in alarm per site 200* Maximum number of BACnet objects per site.
The administration of the number of BACnet objects in alarm per site
is limited. Others cannot be displayed or operated in Alarm Viewer
when there are more BACnet objects in alarm.
351 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
21 Devices
Web graphic pages (VV2 only) [100] Number of web graphics: Limited at present by the available memory
for the sum of all files of max. 7 MB.
Objects per web graphics page (VV2 only) 60 Number of objects per web graphic
Configuration data size 7 MB* Limited by the available memory for all configuration data
(Configurationdata.tar).
BACnet objects, total number 2,000* Max. number of BACnet objects engineered on PXG3.W100.
Permanently displayed BACnet objects 300 Total number of permanently displayed BACnet objects which are
updated by PXG3.W100.
Customized Views 25* Max. number of customized views (memory limit of PXG3.W100).
Customized views
Item Limit Description
BACnet objects 100* Max. number of BACnet objects per customized view.
Graphics pages
Item Limit Description
BACnet objects 60* Max. number of BACnet objects per graphics page.
352 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
Devices
21
Web clients, max. system design 3* Max. number of registered users per PXG3.W100, where the limit of
permanently displayed BACnet objects of all clients may not be
exceeded at maximum system design1.
Key:
1 An example of a maximum system design:
- 20 customized views
- 5 graphics pages per customized view
- 20 BACnet objects per graphics page. System limit: 2000 BACnet objects total and 100 BACnet
objects per customized view.
- 3 Web clients with the above design. System limit: 300 permanently displayed BACnet objects.
- 10 trends per customized view
- 10 schedulers per customized view. System limit: The configuration data size < 7MB applies to
all of the above.
FDT (Foreign Device Table) [50*] Maximum number of foreign devices which can register with the
BACnet router.
Desigo CC in a remote IP segment counts as a foreign device.
Ethernet bit rate 10/100 Mbit/s The router supports 10/100 Mbps.
353 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
21 Devices
BACnet/LonTalk [100 - 120] pkt/s The BACnet router integrates one (1) BACnet/LonTalk network. The
@78 KB/s router operates transparently. The same restrictions apply to global
Max. [~4,5] KB/s broadcast telegrams as for MS/TP.
BACnet/IPv4 [~2500] pkt/s The BACnet router can route between two BACnet/IP networks. The
Max. [~500] KB/s BACnet/IP networks have different UDP ports.
BACnet/IPv6 1 The BACnet router integrates one (1) BACnet/IPv6 network. The
router works transparent, but when connection ports for BACnet/IPv4
and BACnet/IPv6 are used simultaneously, make sure that no
unintentional ethernet loops are created on the IT side.
21.3.19 SX OPC
Item Limit Description
SX OPC applications 1 SX OPC application per PC. The performance depends on the PC
hardware.
OPC server [10] Max. number; OPC data access 2.x or 3.0 specification.
Alarm-generating objects [2,000] Alarm-generating objects (of total 20,000 BACnet objects).
Key:
1 Max. number of BACnet client connections (COF or polling), that is, values read from or written to
(commanded) the own automation station or a remote automation station.
BACnet client connections are used in Input, Output, Scheduler, Trendlog and Group objects (all
NameRef_Type inputs with AddrKind = B). The configured alarm receivers of the Notification
Class objects do NOT require any BACnet client references.
The available number of BACnet client references does not address more than 50 different
remote automation stations.
21.3.20 Desigo CC
For the system configurations of the Desigo CC management platform, see Desigo
CC System Description (A6V10415500).
354 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
Devices
21
Number of XWP per BACnet internetwork 10 Parallel engineering is possible under the following limitations:
(parallel engineering) Node setup: Only one XWP per LonWorks/IP segment.
Download and online operation: Only one XWP per automation
station.
Number of I/O function block instance per 200 The number of I/O function block instances are limited per plan
plan (compound). Mapping of function blocks on BACnet sets the limit. The
limit is lower for other function blocks mapped to BACnet.
Problems with a high When the maximum number of data points for a PXC..U is reached (350), it may no
number of data points per longer be possible to load the program into the PX automation stations due to the
automation station number of data blocks generated during compilation.
In this case, carry out the following steps on the PX automation station:
1. Reload parameters.
2. Run Reorganize in the PX Design Manager.
3. Go to Tools > Settings > Compilation download and select the Compress
check box.
4. Recompile the data.
5. Perform a full download.
355 | 377
Siemens CM110664en_03
2017-09-18
System Configuration
21 Applications
21.4 Applications
Cycle time [ms] 500 Minimum cycle time required to ensure the functioning of the PDL
application.
To guarantee the cycle time, use a PX modular automation station
(PXC 100/200…D, PXC12/22/36…D).
Do not use the the automation station with the PDL application to
control any other plant.
The PDL application must be confined to one automation station only.
Limit control is binary only (enabled/disabled). Step control (Stage1,
Stage2, Stage3) or modulating control (0…100%) is not possible.
Commissioning and operation are only possible with XWP.
There is no provision for backward compatibility with future PDL
applications.
356 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
Glossary
22
22 Compatibility
For information on the system compatibility of the Desigo CC management
platform, see Desigo CC System Description (A6V10415500).
For information on the system compatibility of the Desigo Insight management
station V6.0 SP2, see Desigo Building Automation System 6.0 SP, Technical
Principles (CM110664 / 2016-09-20).
For information on the compatibility of Desigo S7 with other Desigo system
components, see chapter Desigo S7 Automation Stations.
22.1 Glossary
Abbreviations
The following abbreviations are used in this document:
Abbreviation Description
ABT Automation Building Tool (XWP program component for engineering Desigo Room Automation)
AS Automation Station
Desigo PX Compact and modular automation stations and system controllers (PXC…D)
ETS Engineering Tool Software (KNX commissioning tool for RXB and KNX third-party devices)
FEP Front End Processor (the computer serving as the interface between the automation level and
Desigo CC)
FW Firmware
HW Hardware
IE Internet Explorer
LED LibSet Extension of Desigo (assigned LibSet numbering system displaying functional extensions
of Libsets)
LibSets Library Set. Standard application libraries. Each LibSet delivery is assigned to a Desigo system
version.
LMU (DCC) Licence Management Utility (activates and manages licences and contains the installed licences
for Desigo CC)
LMU (XWP) Library Maintenance Utility (library maintenance tool for XWP)
OS Operating System
Operator units Operator units Desigo Touch and Web (PXM40/50 with PXG3.W100), PXM20(-E), PXM10, PX
Web, and Desigo CC
357 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
22 Desigo Version Compatibility Definition
Abbreviation Description
SP Service Pack
SSA Service & Setup Assistant (commissioning tool for Desigo Room Automation)
SW Software
TRA Total Room Automation (from Desigo V6.0 Desigo Room Automation is also used)
Terms
The following terms are used in this document:
Term Description
Project data Desigo engineering and project data required to create runtime systems, but that are no longer
needed for operation (offline data).
Runtime system Firmware (loaded) installed on the hardware of the customer plant or software with compiled
project data including libraries (online data).
New New Desigo customer project with no Desigo runtime system and project data.
Extension Existing plant or installation (existing Desigo runtime system with project data) that is being
expanded or extended (for example, additional buildings).
Migration Replacement of existing plant or installation (existing Desigo / Visonik / Unigyr / Integral runtime
system with project data) by new technology with a change of software and/or hardware.
Upgrade Functional improvement to existing plant or installation (existing Desigo runtime system with
project data) by deploying developments for a new Desigo system version.
Update Existing plant or installation (existing Desigo runtime system with project data) is updated within
the same version (for example, to eliminate errors with a service pack).
Project data conversion Online Desigo project data from earlier Desigo versions > V2.3x are migrated to the current
ABT/XWP V6.1 version when opened in ABT/XWP V6.1.
During conversion, the existing database structure and/or associated tool landscape is migrated to
the latest version. A conversion always impacts all project data of a tool project.
The project data and libraries remain unchanged. The runtime system (online project data) does
not change, that is, the original version status remains as is.
358 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
Desigo V6.1 System Compatibility Basics
22
359 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
22 Desigo V6.1 System Compatibility Basics
Desigo V6.1 does not support BACnet protocol revision functions higher than
V1.13. Usually, BACnet devices of a specific BACnet protocol revision fully support
earlier revision functions (downward compatibility). However, since this is not true
in all cases, we recommend that you verify the compatibility in each case.
For an overview of the BACnet functions supported in Desigo, see BACnet
Protocol Implementation Conformance Statement (PICS) (CM110665).
UTF-8 and ANSI 3.4 BACnet protocol revision 1.10 introduced UTF-8 instead of ANSI 3.4.
If ANSI 3.4 / UTF-8 is used for BACnet communications, and if devices featuring
BACnet protocol revision < 1.10 (prior to Desigo V5.0) communicate with devices
of BACnet protocol revision ≥ 1.10 (from Desigo V5.0):
● Received BACnet character strings of type ANSI 3.4 are handled properly, as
only ANSI X3.4 code points (0..127) are sent that have coding identical to UTF-
8.
● Sent BACnet character strings of type UTF-8 are added properly to data
storage by Desigo devices < V5.0, provided the code points are in the range
0..127.
● If the code points are in range 128..255, UTF-8 coding (multibyte) is interpreted
as ISO-Latin-1 (1 byte) and taken over into data storage. As a result, the data
storage does not match the received string ("René" becomes "René").
To read back this type of string, Desigo devices < V5.0 use ANSI conversion
and only code points in the range 0..127 are sent ("René" becomes "RenA.").
● If the code points are in the range 128..255, UTF-8 coding (multibyte) is
rejected either by third-party devices with BACnet protocol revision < 1.10 (not
ANSI X3.4), or not interpreted along a defined rule.
● Desigo V5.0 supports UTF-8 coding for code points in the range 0..255.
● The following applies from Desigo V5.1:
– Desigo PX / Desigo Room Automation fully supports UTF-8 coding.
Create and delete BACnet As of Desigo V5.1 a function is available for PXC automation stations to create and
objects delete dynamic BACnet objects. If you use this function with an older version, an
error message will appear.
The function can be used on Desigo PXC automation stations. Desigo Room
Automation room automation stations PXC3 are not supported.
Third-party devices can be processed using the same functionality as long as they
support creating and deleting BACnet objects. PXM20 operating units do not
display dynamic objects.
Backup and restore With the BACnet backup and restore function you can upload saved program data
BACnet devices (application program) from a BACnet device to Desigo CC and restore it to the
same or a new BACnet device.
The backup and restore function can only be run if the third-party BACnet devices
support it.
Compatibility Desigo For information on the system compatibility of the Desigo Insight management
Insight station V6.0 SP2, see Desigo Building Automation System 6.0 SP, Technical
Principles (CM110664 / 2016-09-20).
Compatibility Desigo CC For information on the system compatibility of the Desigo CC management
platform, see Desigo CC System Description (A6V10415500).
360 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
Desigo V6.1 System Compatibility Basics
22
Key:
1 From Desigo V5.1 SP
2 Only basic tests (engineering, commissioning, reporting, driver compatibility)
Unlisted Microsoft server operating systems/editions are not supported. They can,
however, be used for stand-alone SQL servers and file hosts.
361 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
22 Desigo V6.1 System Compatibility Basics
Key:
1 These web browsers are supported in addition to the PXM touchpanels.
3 Lighting an blinds functions are not supported together with PXC3 room automation stations.
4 Support of of HTML5-capable browsers with native SVG format.
6 Tested and released browsers. Differences in display and operation compared to the
recommended browser (Firefox) are possible.
7 Minimallly tested browsers. No support from Siemens BT.
Desigo CC For notes on Desigo CC web client running in a browser shell, see Desigo CC
System Description (A6V10415500).
362 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
Desigo V6.1 System Compatibility Basics
22
363 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
22 When to Upgrade to Desigo V6.1
364 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
When to Upgrade to Desigo V6.1
22
365 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
22 When to Upgrade to Desigo V6.1
Restrictions When engineering a tool project, all tool installations must have the same version
as the project.
366 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
When to Upgrade to Desigo V6.1
22
PXC00(-E).D Desigo PX
PXC001(-E).D Desigo PX
PXC100(-E).D Desigo PX
PXC200(-E). D Desigo PX
TXI1.OPEN Desigo PX
TXI2.OPEN Desigo PX
TXI2-S.OPEN Desigo PX
PXC12(-E).D Desigo PX
PXC22(-E).D Desigo PX
PXC36(-E).D Desigo PX
PXC22/36-1 Desigo PX
PXC-NRUF Desigo PX
367 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
22 When to Upgrade to Desigo V6.1
PXM20(-E) Desigo PX
TXB1.P-BUS Desigo PX
PXX-L11/12 Desigo PX
PXX-PBUS Desigo PX
Table 156: Compatibility of TX-I/O modules with PXC..D and PXC3 automation stations
Key:
1 Directly switched lighting applications (by the user) are not supported by the PXC..D automation
stations. For this reason, the configured button function of the digital input modules is not
available together with the PXC…D automation stations.
Restrictions A firmware update or upgrade from TX-I/O modules is not possible (except for
TXI1.OPEN, TXI2.OPEN, and TXI2-S.OPEN).
22.4.3 TX Open
Restrictions The TXI1.OPEN, TXI2.OPEN, and TXI2-S.OPEN TX Open modules can only be
used together with the PXC50/100/200(-E).D and PXC22.1/PXC36.1(-E).D
automation stations.
368 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
Upgrade to Desigo V6.1
22
22.4.4 Desigo RX
Nides.RX PXR-xx PXX-Lxx
Description Phased out Q1/2010 Phased out Q4/2011 Released with Desigo V4
22.4.5 Libraries
Converting or upgrading existing Desigo V2.x/V5.0 V4.x libraries is required:
● To be able to use XWP/ABT V5.1.
● To allow the use of an additional application scope for Desigo V5.1.
● When an automation station, a system controller or room automation station is
used with Desigo V5.1 firmware in the runtime system.
● To make changes to old PX programs engineered with libraries V4.1 (or earlier)
with Desigo Xworks Plus (XWP).
LibSet Desigo LibSets have been converted and/or upgraded to Desigo LibSet V6.1 and
have been provided on the Desigo LibSet installation CD.
Restrictions All Desigo software and LibSets must be on the same PC and have the same
system version.
RC and local libraries Converting and/or upgrading is necessary for RC and local libraries at the
automation level. To do this, use the Library Maintenance Utility (LMU).
For details, see chapter Upgrade PX (CAS) Libraries.
Restrictions Mixing different versions of PX libraries on devices (PX...) is not allowed within the
same application. This applies to CAS libraries, RC libraries, and local libraries.
369 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
22 Upgrade to Desigo V6.1
370 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
Upgrade to Desigo V6.1
22
TRA_01_V6.0SP_HQ_ABT1.2 Desigo TRA library. Compatible with the Desigo V6.0 library.
Restrictions Restricted readback of minor Command and Device objects properties which were
changed in the runtime system after the last read back with ABT V5.1 or ABT V6.1.
Affects upgrades of PXC3 room automation stations from Desigo 5.1 to V6.1 with
XWP/ABT V6.1 without readback done previously.
Des Description
Des Description
QMX7 QMX7 is provided from Desigo V5.1 SP. This requires the following versions:
● ABT V5.1 SP
● Application library V5.1 SP
● PXC3 FW V5.1 SP
Restrictions Projects under older versions, such as V5.0, must be upgraded to ≥V5.1 SP
(System Version Set).
Branch Office Server Procedure for upgrading XWP and BOS from the previous version to the latest
(BOS) version:
1. Check in previous version of XWP using the presious version of BOS.
2. Install new BOS version.
3. Continue with new XWP version only.
You do not need to upgrade all tool project data of all automation stations, system
controllers or room automation stations to V6.1.
In a Desigo runtime system, existing PX automation stations, system controllers or
room automation stations may remain unchanged on Desigo ≤ V5.x even after a
conversion to the V6.1 tool environment.
371 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
22 Upgrade to Desigo V6.1
Restrictions When engineering a tool project, all tool installations must have the same version
as the project.
All Desigo software and LibSets must be on the same PC and have the same
version.
372 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
Siemens WEoF Clients
22
Permanent Open User V6.1 Desigo Xworks Plus (XWP) including PX firmware library
(FW), Automation Building Tool (ABT) and additional tools
Minimum user level required Standard User Standard User Standard User
Described in Requirements
CM110776 Automation Level Engineering Manual
Migration of Unigyr:
Described in Requirements
CM110496 Unigyr tools V7.61 with Unigyr automation level V7.64
Migration of Integral:
373 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
22 Hardware Requirements of Desigo Software Products
Described in Requirements
CM110499 NCRS from V3.1 (only automation level)
For replacing Integral RS modules (NRUA, NRUB, NRUC, and NRUD) with PXC
AS and PXC-NRUD modules, Desigo supports the use of PXC-NRUD modules
with PXC100/200(-E).D (from Desigo ≥ V4.1) and PXC50(-E).D (from V5.0).
Migration of Visonik:
Described in Requirements
CM110497 DCS from V22.16 Patch 195 or V24.16 Patch 195 (server with automation level)
Desigo Xworks Plus V6.1 Compatible with > 1.6 GHz (> 3 6 GB RAM (> 50 GB HDD* with Monitor: 1366x768
(including ABT/SSA Intel and AMD GHz) 16 GB RAM) good performance Recommended for
and other additional technology (HDD at very fast ABT 1680x1050
tools) or ABT Site access times)
(stand-alone) DVD
(SSD drive)
(USB port for SSA-
DNT as alternative to
ethernet connection)
Multiple core
processors, for
example, for VMware
Branch Office Server V6.1 Compatible with > 1.6 GHz (2.5 4 GB RAM (8 HDD size PCI slot or PC card
(BOS) Intel and AMD GHz) GB RAM) depending on (Typ II) or USB2
technology project data
volume
RXT10.3 / RXT10.5 - Compatible with > 1.6 GHz 4 GB RAM HDD size
Intel and AMD depending on
technology project data
volume
Key:
* Desigo Xworks Plus (XWP) requires ca. 1.4 GB memory. Automation Building Tool (ABT)
requires ca. 1-2 GB memory. Uncompressed project data requires an additional 0.5 MB memory
per data point (reference value). The performance depends on available memory.
The indicated values apply to a host installation. For stable and reliable operation
of VMware, CPU and RAM requirements are higher.
Values in (…) are recommended, especially if Automation Building Tool (ABT) is
installed on a 64-bit operating system, to allow for larger projects (up to 12 PXC3
374 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
VVS Desigo V6.1
22
with 8 rooms each per ABT project). For details, see chapter Compatibility with
Operating Systems.
16 GB RAM are recommended if two Automation Building Tool (ABT) satellite
projects are opened at the same time, and if in ABT two PXC3 are to be online at
the same time.
Configure SSDs for a long life. See Microsoft documentation (Windows 7 & SSD).
ABT projects require ca. 2.5 times more memory per PXC3 room automation
station compared to PXC automation stations.
Parallel port or USB port for license dongle.
For online functions you need:
● LonWorks interface card or LonWorks dongle
● Ethernet interface
● Connection cable for automation stations
● USB port for P-bus BIM connection
The following software is required:
● Operating system: See chapter Compatibility with Operating Systems
● Microsoft Office: See chapter Compatibility with Microsoft Office
● Acrobat Reader 6.0 or higher (optional installation with tool installation)
● WinZIP
● .NET Framework >= V3.5 (version 3.5 is available on the tool DVD)
TXB1.P-BUS V1.1.34 -
375 | 377
Siemens CM110664en_03
2017-09-18
Compatibility
22 VVS Desigo V6.1
The versions listed correspond to the latest state upon delivery release of Desigo
V6.1. As part of continuous product improvements, more current firmware versions
(with higher numbers) may be delivered.
For the current state, see the current release notes of the product.
376 | 377
Siemens CM110664en_03
2017-09-18
Issued by © Siemens Switzerland Ltd, 2015
Siemens Switzerland Ltd Technical specifications and availability subject to change without notice.
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
+41 58 724 2424
www.siemens.com/buildingtechnologies