Transformer and Induction Motor
Transformer and Induction Motor
AND
ELECTRICAL APPARATUS AND
DEVICES
Hanes K. Gutierrez
BSEE – 3A
Induction Motors
1. A dc test is performed on a 460-V -connected 100-hp induction motor. If VDC = 21 V and IDC = 72 A,
what is the stator resistance R1 ? Why is this so?
SOLUTION If this motor’s armature is connected in delta, then there will be two phases in parallel with one
phase between the lines tested.
VDC R1 R1
R1
2. A 220-V three-phase six-pole 50-Hz induction motor is running at a slip of 3.5 percent. Find:
(a) The speed of the magnetic fields in revolutions per minute
(b) The speed of the rotor in revolutions per minute
(c) The slip speed of the rotor
(d) The rotor frequency in hertz
SOLUTION
(a) The speed of the magnetic fields is
120 fe 120(50 Hz)
nsync = = = 1000 r/min
P 6
(b) The speed of the rotor is
3. Answer the questions in Problem 7-2 for a 480-V three-phase four-pole 60-Hz induction motor running at
a slip of 0.025.
SOLUTION
(a) The speed of the magnetic fields is
4. A three-phase 60-Hz induction motor runs at 715 r/min at no load and at 670 r/min at full load.
(a) How many poles does this motor have?
(b) What is the slip at rated load?
(c) What is the speed at one-quarter of the rated load?
(d) What is the rotor’s electrical frequency at one-quarter of the rated load?
SOLUTION
(a) This machine has 10 poles, which produces a synchronous speed of
5. A 50-kW 440-V 50-Hz two-pole induction motor has a slip of 6 percent when operating at full-load
conditions. At full-load conditions, the friction and windage losses are 520 W, and the core losses are 500
W. Find the following values for full-load conditions:
(a) The shaft speed nm
SOLUTION
(a) The synchronous speed of this machine is
120 fe 120(50 Hz)
n = = = 3000 r/min
sync
P 2
Therefore, the shaft speed is
+
0.22 j0.43 j0.43 0.127
1− s
jX R
V j15 M 2
s
2.413
-
(a) The easiest way to find the line current (or armature current) is to get the equivalent impedance ZF
of the rotor circuit in parallel with jX M , and then calculate the current as the phase voltage divided by
the sum of the series impedances, as shown below.
IA
R1 jX 1 jXF RF
0.22 j0.43
V
jX M
The equivalent impedance of the rotor circuit in parallel with is:
1 1
=
ZF = 1 1 1 1 = 2.337 + j0.803 = 2.4719
+ +
jX M Z2 j15 2.54 + j0.43
The phase voltage is 208/ = 120 V, so line current I L is
V 1200 V
IL = I A = =
R1 + jX1 + RF + jX F 0.22 + j0.43 + 2.337 + j0.803
I L = I A = 42.3 − 25.7 A
(b) The stator copper losses are
R2
The air gap power is PAG = 3I 2 = 3I A RF
2 2
(c)
s
2 R2
(Note that 3I A2 RF is equal to 3I 2 , since the only resistance in the original rotor circuit was R2 / s ,
s
and the resistance in the Thevenin equivalent circuit is RF . The power consumed by the Thevenin
equivalent circuit must be the same as the power consumed by the original circuit.)
= 3I 2R = 3(42.3 A) (2.337 ) = 12.54 kW
R2 2
P = 3I 2
AG 2 A F
s
(d) The power converted from electrical to mechanical form is
8. For the motor in Problem 7-7, what is the slip at the pullout torque? What is the pullout torque of this
motor?
SOLUTION The slip at pullout torque is found by calculating the Thevenin equivalent of the input circuit
from the rotor back to the power supply, and then using that with the rotor circuit model.
V =
( j15 ) (1200 V) = 116.70.8 V
jX M
V =
R1 + j(X 1 + X M ) 0.22 + j(0.43 + 15 )
TH
3(116.7 V)
2
max =
(88.5 rad/s) 0.208 + (0.208 ) + (0.421 + 0.430 )
2 2
max = 100 N m
9. (a) Calculate and plot the torque-speed characteristic of the motor in Problem 7-7. (b) Calculate and plot
the output power versus speed curve of the motor in Problem 7-7.
SOLUTION
(a) A MATLAB program to calculate the torque-speed characteristic is shown below.
% M-file: prob7_9a.m
% M-file create a plot of the torque-speed curve of the
% induction motor of Problem 7-7.
(b) A MATLAB program to calculate the output-power versus speed curve is shown below.
% M-file: prob7_9b.m
% M-file create a plot of the output pwer versus speed
% curve of the induction motor of Problem 7-7.
7-10. For the motor of Problem 7-7, how much additional resistance (referred to the stator circuit) would it be
necessary to add to the rotor circuit to make the maximum torque occur at starting conditions (when the
shaft is not moving)? Plot the torque-speed characteristic of this motor with the additional resistance
inserted.
SOLUTION To get the maximum torque at starting, the smax must be 1.00. Therefore,
R2
smax =
R 2
+(X +X )2
TH TH 2
R2
1.00 =
(0.208 ) + (0.421 + 0.430 )
2 2
R2 = 0.876
Therefore, an additional 0.749 must be added to the rotor circuit. The resulting torque-speed
characteristic is:
11. If the motor in Problem 7-7 is to be operated on a 50-Hz power system, what must be done to its supply
voltage? Why? What will the equivalent circuit component values be at 50 Hz? Answer the questions in
Problem 7-7 for operation at 50 Hz with a slip of 0.05 and the proper voltage for this machine.
SOLUTION If the input frequency is decreased to 50 Hz, then the applied voltage must be decreased by 5/6
also. If this were not done, the flux in the motor would go into saturation, since
1
=
N
v dt
T
and the period T would be increased. At 50 Hz, the resistances will be unchanged, but the reactances will
be reduced to 5/6 of their previous values. The equivalent circuit of the induction motor at 50 Hz is
shown below:
IA
R1 jX 1 jX2 R2
+ j0.358 0.127
0.22 j0.358
1− s
jX R
V j12.5 M 2
s
2.413
-
(a) The easiest way to find the line current (or armature current) is to get the equivalent impedance ZF
of the rotor circuit in parallel with jX M , and then calculate the current as the phase voltage divided by
the sum of the series impedances, as shown below.
IA
R1 jX 1 jXF RF
0.22 j0.358
V
R2
The air gap power is PAG = 3I 2 = 3I A RF
2 2
(c)
s
2 R2
(Note that 3I A2 RF is equal to 3I 2 , since the only resistance in the original rotor circuit was R2 / s ,
s
and the resistance in the Thevenin equivalent circuit is RF . The power consumed by the Thevenin
equivalent circuit must be the same as the power consumed by the original circuit.)
R2
PAG = 3I 2 = 3I A RF = 3(35.9 A) (2.310 ) = 8.93 kW
2 2 2
s
(d) The power converted from electrical to mechanical form is
Pconv = (1 − s)PAG = (1 − 0.05) (8.93 kW) = 8.48 kW
(e) The induced torque in the motor is
PAG = 8.48 kW
= 54.0 N m
ind = sync (1500 r/min) 2 rad 1 min
1r 60 s
(f) In the absence of better information, we will treat the mechanical and core losses as constant despite
the change in speed. This is not true, but we don’t have reason for a better guess. Therefore, the output
power of this motor is
POUT = Pconv − Pmech − Pcore − Pmisc = 8.48 kW − 300 W − 200 W − 0 W = 7.98 kW
The output speed is
nm = (1 − s) nsync = (1 − 0.05)(1500 r/min) = 1425 r/min
Therefore the load torque is
7.98 kW
load = OUT = (1425 r/min) 2 rad 1 min = 53.5 N m
P
m
1r 60 s
(g) The overall efficiency is
POUT POUT
= 100% = 100%
PIN 3V I A cos
7.98 kW
= 100% = 81.6%
3(100 V)(35.9 A) cos 24.7
(h) The motor speed in revolutions per minute is 1425 r/min. The motor speed in radians per second is
2 rad 1 min
m = (1425 r/min) = 149.2 rad/s
1r 60 s
12. Figure 7-16a shows a simple circuit consisting of a voltage source, a resistor, and two reactances. Find the
Thevenin equivalent voltage and impedance of this circuit at the terminals. Then derive the expressions
for the magnitude of VTH and for RTH given in Equations (7-38) and (7-42).
If X M X1 , then R12 + (X 1 + X M ) (X 1 + X M ) , so
2 2
XM
X1 + X M
TH
Z =
− R X X 1 1 M
+RX X
1 1 M 1 M
+ R X 2 + j R 2X + X 2X + X X 2
1 M 1 M 1 M
R 2 + (X + X )
TH 2
1 1 M
+ j R1 X M2 + X 1 X M + X) 1 X M
2
ZTH = RTH + jX TH = R1 X M 2 2 2
R1 + X 1 + X M )
2
( 2
(
R1 + X 1 + X M
2
2
The Thevenin resistance is RTH = R1 X M . If X M R1 , then
2
(
R1 + X 1 + X M )
2
R12 + (X 1 + X M ) (X 1 + X M ) , so
2 2
2
X
R1
X1 + X M
TH
+ X1X M 2
The Thevenin reactance is X TH = R1 X M2 + X 1 X M
2 2
.
(
R1 + X 1 + X M )
2
X1X M
TH
=X
13. Figure P7-1 shows a simple circuit consisting of a voltage source, two resistors, and two reactances in series
with each other. If the resistor RL is allowed to vary but all the other components are constant, at what
value of RL will the maximum possible power be supplied to it? Prove your answer. (Hint: Derive
an expression for load power in terms of V, RS , X S , RL and X L and take the partial derivative of that
expression with respect to RL .) Use this result to derive the expression for the pullout torque [Equation
(7-52)].
P = I L RL =
2
(RS + RL
(R + R )2 + ( X + X )2 V 2 − V 2R 2 ( R + R )
P S L S L L 2 S L
= (R + R )2 + ( X + X )2
RL
S L S L
To find the point of maximum power supplied to the load, set P / RL = 0 and solve for RL .
(R + R )2 + ( X + X )2 V 2 − V 2R 2 ( R + R ) = 0
S L S L L S L
(R + R ) + ( X + X ) = 2R ( R + R )
2 2
S L S L L S L
RS 2 + R L2 + ( X S + X L ) = 2R L2
2
R 2 +(X + X )2 = R 2
S S L L
RL = RS 2 + (X S + X L )
2
14. A 440-V 50-Hz six-pole Y-connected induction motor is rated at 75 kW. The equivalent circuit
parameters are
R1 = 0.082 R2 = 0.070 X M = 7.2
X1 = 0.19 X 2 = 0.18
PF&W = 1.3 kW Pmisc = 150 W Pcore = 1.4 kW
For a slip of 0.04, find
(a) The line current IL
(b) The stator power factor
(c) The rotor power factor
(d) The stator copper losses PSCL
+ j0.18 0.07 I2
0.082 j0.19
1− s
jX R
V j7.2 M 2
s
1.68
-
(a) The easiest way to find the line current (or armature current) is to get the equivalent impedance ZF
of the rotor circuit in parallel with jX M , and then calculate the current as the phase voltage divided by
the sum of the series impedances, as shown below.
IA
R1 jX 1 jXF RF
0.082 j0.19
V
jX M
The equivalent impedance of the rotor circuit in parallel with is:
1 1
=
ZF = 1 1 1 1 = 1.557 + j0.550 = 1.6719.2
+ +
jX M Z2 j7.2 1.75 + j0.18
0.070
smax = = 0.187
(0.0778 ) + (0.186 + 0.180 )
2 2
+
0.082 j0.228 j0.216 0.07 I2
1− s
jX R
V j8.64 2
s
M
1.68
-
The slip at pullout torque is found by calculating the Thevenin equivalent of the input circuit from the
rotor back to the power supply, and then using that with the rotor circuit model.
jX M ( R1 + jX1) =
( j8.64 )(0.082 + j0.228 ) = 0.0778 + j0.223 = 0.23670.7
Z TH = R + j X + X
( ) 0.082 + j (0.228 + 8.64 )
1 1 M
j8.64
VTH =
jXM V = (2540 V) = 247.50.5 V
R1 + j ( X1 + X M )
0.082 + j (0.228 + 8.64 )
The slip at pullout torque is
R2
smax =
RTH + (X TH + X 2 )
2 2
0.070
smax = = 0.157
(0.0778 ) 2
+ (0.223 + 0.216 )
2
sync RTH R2
+ (X TH + X 2 )
TH
3(247.5 V)
2
max =
(125.7 rad/s)0.0778 + (0.0778 ) + (0.223 + 0.216 )
max = 1396 N m
17. Plot the following quantities for the motor in Problem 7-14 as slip varies from 0% to 10%: (a) ind (b)
Pconv (c) Pout (d) Efficiency . At what slip does Pout equal the rated power of the machine?
SOLUTION This problem is ideally suited to solution with a MATLAB program. An appropriate program
is shown below. It follows the calculations performed for Problem 7-14, but repeats them at many values
of slip, and then plots the results. Note that it plots all the specified values versus nm , which varies from
900 to 1000 r/min, corresponding to a range of 0 to 10% slip.
% M-file: prob7_17.m
% M-file create a plot of the induced torque, power
% converted, power out, and efficiency of the induction
% motor of Problem 7-14 as a function of slip.
% Induced torque
t_ind(ii) = (3 * v_th^2 * r2 / s(ii)) / ...
(w_sync * ((r_th + r2/s(ii))^2 + (x_th + x2)^2) );
% Power converted
p_conv(ii) = t_ind(ii) * wm(ii);
% Power output
p_out(ii) = p_conv(ii) - p_mech - p_core - p_misc;
% Power input
zf = 1 / ( 1/(j*xm) + 1/(r2/s(ii)+j*x2) );
ia = v_phase / ( r1 + j*x1 + zf );
p_in(ii) = 3 * v_phase * abs(ia) * cos(atan(imag(ia)/real(ia)));
% Efficiency
eff(ii) = p_out(ii) / p_in(ii) * 100;
end
R1
VD
R1 R1
In the no-load test, the line voltage is 208 V, so the phase voltage is 120 V. Therefore,
X +X =
V
=
120 V = 5.455 @ 60 Hz
1 M
I A,nl 22.0 A
In the locked-rotor test, the line voltage is 24.6 V, so the phase voltage is 14.2 V. From the locked-rotor
test at 15 Hz,
V 14.2 V
Z LR = RLR + jX LR = = = 0.2202
I A,LR 64.5 A
−1
−1 PLR 2200 W
LR = cos = cos = 36.82
SLR 3(24.6 V)(64.5 A)
Therefore,
+ j0.317 0.071 I2
0.105 j0.211
1− s
jX R
V j5.244 2
s
M
A MATLAB program to calculate the torque-speed characteristic of this motor is shown below:
% M-file: prob7_18.m
% M-file create a plot of the torque-speed curve of the
% induction motor of Problem 7-18.
19. A 208-V four-pole 10-hp 60-Hz Y-connected three-phase induction motor develops its full-load induced
torque at 3.8 percent slip when operating at 60 Hz and 208 V. The per-phase circuit model impedances of
the motor are
R1 = 0.33 X M = 16
X1 = 0.42 X 2 = 0.42
Mechanical, core, and stray losses may be neglected in this problem.
(a) Find the value of the rotor resistance R2 .
(b) Find max , smax , and the rotor speed at maximum torque for this motor.
(c) Find the starting torque of this motor.
(d) What code letter factor should be assigned to this motor?
+ j0.42 ??? I2
0.33 j0.42
1− s
jX R
V j16 M 2
s
(a) If losses are neglected, the induced torque in a motor is equal to its load torque. At full load, the
output power of this motor is 10 hp and its slip is 3.8%, so the induced torque is
ind = load =
(10 hp)(746 W/hp) = 41.1 N m
(1732 r/min) 2 rad 60 s
1r 1 min
The induced torque is given by the equation
ind = 2
3VTH R2 / s
( R + R / s)2 + ( X + X )2
sync TH 2 TH 2
Substituting known values and solving for R2 / s yields
3(116.9 V) R22 / s
2
41.1 N m =
(188.5 rad/s) (0.313 + R / s) + (0.416 + 0.42)
2
2
7, 747 = 40, 997 R2 / s
(0.313 + R / s)2 + 0.699
2
(0.313 + R / s) + 0.699 = 5.292 R / s
2
2 2
0.098 + 0.626R / s + ( R / s) + 0.699 = 5.292 R / s
2
2 2 2
2
R2 R
− 4.666 2 + 0.797 = 0
s s
R2
= 0.178, 4.488
s
R2 = 0.0067 , 0.17
These two solutions represent two situations in which the torque-speed curve would go through this
specific torque-speed point. The two curves are plotted below. As you can see, only the 0.17 solution
is realistic, since the 0.0067 solution passes through this torque-speed point at an unstable location on
the back side of the torque-speed curve.
(b) The slip at pullout torque can be found by calculating the Thevenin equivalent of the input circuit
from the rotor back to the power supply, and then using that with the rotor circuit model. The Thevenin
equivalent of the input circuit was calculate in part (a). The slip at pullout torque is
R2
smax =
2
TH TH + X2
0.17
smax = = 0.190
(0.313 ) + (0.416 + 0.420 )
2 2
max = 90.2 N m
(c) The starting torque of this motor is the torque at slip s = 1. It is
ind = 2
3VTH R22 / s
( R + R / s) + ( X +X )2
sync TH 2 TH 2
3(116.9 V) (0.17 )
2
ind = = 38.3 N m
(188.5 rad/s)(0.313 + 0.17 ) + (0.416 + 0.420)
2 2
(d) To determine the starting code letter, we must find the locked-rotor kVA per horsepower, which is
equivalent to finding the starting kVA per horsepower. The easiest way to find the line current (or
armature current) at starting is to get the equivalent impedance Z F of the rotor circuit in parallel with
jX M at starting conditions, and then calculate the starting current as the phase voltage divided by the
sum of the series impedances, as shown below.
IA,start
R1 jX 1 jXF RF
0.33 j0.42
V
jX M
The equivalent impedance of the rotor circuit in parallel with at starting conditions (s = 1.0) is:
1 1
Z F ,start = =
1 1 1 1 = 0.161 + j0.411 = 0.44268.6
+ +
jXM Z2 j16 0.17 + j0.42
SOLUTION
(a) The equivalent circuit of this induction motor is shown below:
IA
R1 jX 1 jX2 R2
+ j0.42 0.17 I2
0.33 j0.42
1− s
jX R
V j16 M 2
s
The easiest way to find the line current (or armature current) at starting is to get the equivalent impedance
Z F of the rotor circuit in parallel with jX M at starting conditions, and then calculate the starting current
as the phase voltage divided by the sum of the series impedances, as shown below.
IA
R1 jX 1 jXF RF
0.33 j0.42
V
jX M
The equivalent impedance of the rotor circuit in parallel with at starting conditions (s = 1.0) is:
1 1
=
ZF = 1 1 1 1 = 0.161 + j0.411 = 0.44268.6
+ +
jX M Z2 j16 0.17 + j0.42
Therefore, the terminal voltage will be (75.1 V) = 130 V . Note that the terminal voltage sagged by
37.5% during motor starting, which would be unacceptable.
(c) If an ideal 1.2:1 step-down autotransformer is connected between the transmission line and the
motor, the motor’s impedances will be referred across the transformer by the square of the turns ratio a =
1.2. The referred impedances are
R1 = a2R1 = 1.44 (0.33 ) = 0.475
X1 = a2 X1 = 1.44 (0.42 ) = 0.605
RF = a2RF = 1.44 (0.161 ) = 0.232
X F = a2 X F = 1.44 (0.411 ) = 0.592
Therefore, the starting current referred to the primary side of the transformer will be
V ,bus
IL = IA = + jX + R + jX + R + jX
Rline line 1 1 F F
1200 V
IL = IA =
0.50 + j0.35 + 0.475 + j0.605 + 0.232 + j0.592
IL = IA = 61.2 − 52 A
The voltage at the motor end of the transmission line would be the same as the referred voltage at the
terminals of the motor
V = IA (R1 + jX1 + RF + jX F )
V = (61.2 − 52 A)(0.475 + j0.605 + 0.232 + j0.592 )
V = 85.07.4 V
Therefore, the line voltage at t he motor end of the transmission line will be (85 V) = 147.3 V . Note
that this voltage sagged by 29.2% during motor starting, which is less than the 37.5% sag with case of
across-the-line starting. Since the sag is still large, it might be possible to use a bigger autotransformer
turns ratio on the starter.
21. In this chapter, we learned that a step-down autotransformer could be used to reduce the starting current
drawn by an induction motor. While this technique works, an autotransformer is relatively expensive. A
much less expensive way to reduce the starting current is to use a device called Y- starter. If an
induction motor is normally -connected, it is possible to reduce its phase voltage V (and hence its
starting current) by simply re-connecting the stator windings in Y during starting, and then restoring the
connections to when the motor comes up to speed. Answer the following questions about this type of
starter.
(a) How would the phase voltage at starting compare with the phase voltage under normal running
conditions?
(b) How would the starting current of the Y-connected motor compare to the starting current if the motor
remained in a -connection during starting?
SOLUTION
(a) The phase voltage at starting would be 1 / = 57.7% of the phase voltage under normal running
conditions.
(b) Since the phase voltage decreases to 1 / = 57.7% of the normal voltage, the starting phase
current will also decrease to 57.7% of the normal starting current. However, since the line current for the
original delta connection was times the phase current, while the line current for the Y starter
connection is equal to its phase current, the line current is reduced by a factor of 3 in a Y- starter.
22. A 460-V 50-hp six-pole -connected 60-Hz three-phase induction motor has a full-load slip of 4 percent, an
efficiency of 91 percent, and a power factor of 0.87 lagging. At start-up, the motor develops 1.75 times
the full-load torque but draws 7 times the rated current at the rated voltage. This motor is to be started
with an autotransformer reduced voltage starter.
(a) What should the output voltage of the starter circuit be to reduce the starting torque until it equals the
rated torque of the motor?
(b) What will the motor starting current and the current drawn from the supply be at this voltage?
SOLUTION
(a) The starting torque of an induction motor is proportional to the square of VTH ,
2 2
V VT
= 2
start2
=
TH2
start1 VTH1 VT 1
2 2
V V
= T2
start2
= TH2
start1 VTH1 VT 1
If a torque of 1.75 rated is produced by a voltage of 460 V, then a torque of 1.00 rated would be
produced by a voltage of
1.00
2
V
1.75
rated
= T2
rated 460 V
VT 2 =
(460 V)2
= 348 V
1.75
(b) The motor starting current is directly proportional to the starting voltage, so
348 V
I L2 = I = (0.756)IL1 = (0.756) (7I rated ) = 5.296 I rated
L1
460 V
The input power to this motor is
PIN =
POUT
=
(50 hp) (746 W/hp) = 40.99 kW
0.91
The rated current is equal to
Irated =
PIN
=
(40.99 kW) = 59.1 A
3 VT PF 3 (460 V)(0.87)
Therefore, the motor starting current is
I L2 = 5.843 I rated = (5.296) (59.1 A) = 313 A
The turns ratio of the autotransformer that produces this starting voltage is
NSE + NC = 460 V = 1.32
NC 348 V
so the current drawn from the supply will be
Istart = 313 A = 237 A
Iline =
1.32 1.32
23. A wound-rotor induction motor is operating at rated voltage and frequency with its slip rings shorted and
with a load of about 25 percent of the rated value for the machine. If the rotor resistance of this machine
is doubled by inserting external resistors into the rotor circuit, explain what happens to the following:
(a) Slip s
(b) Motor speed nm
(g) PRCL
SOLUTION
(a) The slip s will increase.
(b) The motor speed nm will decrease.
(g) The rotor copper losses (including the external resistor) will increase.
(h) The overall efficiency will decrease.
24. Answer the following questions about a 460-V -connected two-pole 100-hp 60-Hz starting code letter F
induction motor:
(a) What is the maximum current starting current that this machine’s controller must be designed to
handle?
(b) If the controller is designed to switch the stator windings from a connection to a Y connection
during starting, what is the maximum starting current that the controller must be designed to handle?
(c) If a 1.25:1 step-down autotransformer starter is used during starting, what is the maximum starting
current that will be drawn from the line?
SOLUTION
(a) The maximum starting kVA of this motor is
(b) The frequency of the rotor before plugging is fr = sfe = (0.038)(60 Hz) = 2.28 Hz
(c) The induced torque before plugging is 41.1 Nm in the direction of motion (see Problem 7-19).
(d) After switching stator leads, the synchronous speed becomes –1800 r/min, while the mechanical
speed initially remains 1732 r/min. Therefore, the slip becomes
nsync − nm − 1800 − 1732
s= = = 1.962
nsync − 1800
(e) The frequency of the rotor after plugging is fr = sfe = (1.962)(60 Hz) = 117.72 Hz
(f) The induced torque immediately after switching the stator leads is
Transformer
1. The high-voltage coil of a transformer is wound with 700 turns of wire, and the low-
voltage coil is wound with 292 turns. When used as a step-up transformer (the low-
voltage coil is used as the primary), the load current is 10.5 A. Find the load component
of the primary current.
A. 43.5 A B. 4.38 A C. 25.18 A D. 2.518 A
Solution:
𝑁𝑝 𝐼𝑠
=
𝑁𝑠 𝐼𝑝
𝐼 = 𝐼𝑠𝑁𝑠
=
(700)(10.5)
𝑝 𝑁𝑝 292
• 𝑰𝒑 = 𝟐𝟓. 𝟏𝟕 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
• 𝑵𝒔 = 𝟏𝟐𝟎 𝒕𝒖𝒓𝒏𝒔
• ∅𝒎 = 𝟒. 𝟓𝟎 𝒎𝑾𝒃
9. A single-phase transformer has a no-load power input of 250 Watts, when supplied at 250
V, 50 Hz has a p.f of 0.25. What is the magnetizing component of the no-load current?
A. 4.00 A B. 3.87 A C. 1.00 A D. none of these
Solution:
𝑃 250
𝑆= =
𝑝.𝑓 0.25
• 𝑆 = 1, 000 𝑉𝐴
𝑝𝑓 = 𝑐𝑜𝑠−1 0.25
• 𝑝𝑓 = 75.52°
𝑆 = 𝑉𝐼
1,000∠75.52
𝐼= = 4∠75.52° 𝐴𝑚𝑝𝑒𝑟𝑒𝑠
250
• 𝐼 = 1 + 𝑗 3.873 𝐴𝑚𝑝𝑒𝑟𝑒𝑠
• 𝑰𝒎 = 𝟑. 𝟖𝟕𝟑 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
REE – September 2011
10. A 4, 400 V, 60 Hz transformer has a core loss of 840 Watts, of which one-third is eddy
current loss. What is the core loss when the x’former is connected to a 4, 600 V, 50 Hz
source?
A. 977 Watts B. 907 Watts C. 927 Watts D. 944 Watts
Solution:
𝑃𝑐𝑜𝑟𝑒 = 𝑃 𝑒𝑑𝑑𝑦
1
3
1
𝑃𝑒1 = 3 (840)
• 𝑃𝑒1 = 280 𝑊𝑎𝑡𝑡𝑠
𝑃𝑐𝑜𝑟𝑒 = 𝑃ℎ + 𝑃𝑒
𝑃ℎ1 = 840 − 280
• 𝑃ℎ1 = 560 𝑊𝑎𝑡𝑡𝑠
𝑃𝑒2 𝑘 (𝐸 )2
= 2 2 2
𝑃𝑒1 𝑘1(𝐸1)
𝑃 = 280 4,6002
𝑒2 ( 2)
4,440
• 𝑃𝑒2 = 306.033 𝑊𝑎𝑡𝑡𝑠
𝐸 1.6
𝑘2( 2 0.6)
𝑃 ℎ2 𝑓2
= 𝐸1
1.6
𝑃ℎ1 𝑘1( 0.6)
𝑓1
4,6001.6
( 500.6 )
𝑃ℎ2 = 560 [ 4,4001.6
]
( )
600.6
• 𝑃ℎ2 = 670.788 𝑊𝑎𝑡𝑡𝑠
𝑃𝑐𝑜𝑟𝑒2 = 𝑃ℎ2 + 𝑃𝑒2 = 670.788 + 306.033
• 𝑷𝒄𝒐𝒓𝒆𝟐 = 𝟗𝟕𝟔. 𝟖𝟐𝟏 𝑾𝒂𝒕𝒕𝒔
2 =( )
𝑃𝑐𝑢−𝐹𝐿 𝑆 𝑟𝑎𝑡𝑒𝑑
𝑃
𝑆=
𝑝.𝑓
1,500 𝐾𝑊𝑙𝑜𝑎𝑑/0.71 2
=( )
1,180 100
𝐾𝑊𝑙𝑜𝑎𝑑 2 1,500
( ) = 1002 ( )
0.71 1,180
1,500
𝐾𝑊𝑙𝑜𝑎𝑑 = √(0.71)2(100)2 ( )
1,180
13. Given a 10-kVA transformer with full-load losses amounting to 70 Watts in the iron and
140 Watts in the copper. Calculate the efficiency at half-load unity power factor.
A. 98.62% B. 97.97% C. 97.28% D. 97.94%
Solution:
𝑃𝐶𝑢𝐻𝐿 𝑆𝐻𝐿 2
=( )
𝑆𝐹𝐿
𝑃𝐶𝑢𝐹𝐿
140(52)
𝑃𝐶𝑢 𝐻𝐿
=
102
• 𝑃𝐶𝑢 𝐻𝐿 = 35 𝑊𝑎𝑡𝑡𝑠
𝑃𝑜𝐻𝐿 5,000
ɳ 𝐻𝐿 = × 100% = × 100%
𝑃𝑜𝐻𝐿+𝑃𝑐𝑜𝑟𝑒+𝑃𝐶𝑢𝐻𝐿 5,000+35
• ɳ 𝑯𝑳 = 𝟗𝟕. 𝟗𝟒%
17. Calculate the all-day efficiency of a 100-kVA transformer operating under the following
conditions: 6 hours on a load of 50 kW at 0.73 power factor; 3 hours on a load of 90 kW
at 0.82 power factor; 15 hours with no load on secondary. The iron loss is 1, 000 Watts
and the full-load copper loss is 1, 060 Watts.
A. 96.31% B. 94.87% C. 95.33% D. 95.29%
Solution:
𝑃𝑜𝑢𝑡 = (50, 000)(6) + (90, 000)(3) + (0)(15)
• 𝑃𝑜𝑢𝑡 = 570 𝑘𝑊ℎ𝑟
𝑃𝑐𝑜𝑟𝑒 = (1, 000)(24)
• 𝑃𝑐𝑜𝑟𝑒 = 24 𝑘𝑊ℎ𝑟
𝑘𝑉𝐴 2
𝑃𝐶𝑢1 1
=( )
𝑃𝐶𝑢𝐹𝐿 𝑘𝑉𝐴𝐹𝐿
50/0.73 2
𝑃𝐶𝑢1 = 1, 060 ( )
100
• 𝑃𝐶𝑢1 = 497.279 𝑊𝑎𝑡𝑡𝑠
90/0.82 2
𝑃 = 1, 060 ( )
𝐶𝑢2 100
• 𝑃𝐶𝑢2 = 1, 276.919 𝑊𝑎𝑡𝑡𝑠
• 𝑃𝐶𝑢3 = 0 𝑊𝑎𝑡𝑡𝑠
𝑃𝐶𝑢𝑡𝑜𝑡𝑎𝑙 = 𝑃𝐶𝑢1(6) + 𝑃𝐶𝑢2(3) + 𝑃𝐶𝑢3(15)
𝑃𝐶𝑢𝑡𝑜𝑡𝑎𝑙 = (487.279)(6) + (1, 276.919)(3) + (0)(15)
• 𝑃𝐶𝑢𝑡𝑜𝑡𝑎𝑙 = 6.814 𝑘𝑊ℎ𝑟
𝑃𝑜𝑢𝑡 570
ɳ = × 100% = × 100%
𝑎𝑙𝑙 𝑑𝑎𝑦 𝑃𝑜𝑢𝑡+𝑃𝑐𝑜𝑟𝑒+𝑃𝐶𝑢 570+24+6.814
• ɳ𝒂𝒍𝒍 𝒅𝒂𝒚 = 𝟗𝟒. 𝟖𝟕%
REE – September 2005
18. A 50-kVA, single-phase transformer has 96% efficiency when it operates at full-load
unity power factor for 8 hours per day. What is the all-day efficiency of the transformer if
the copper loss is 60% of full-load losses?
A. 92% B. 90% C. 89.5% D. 93%
Solution:
50
0.96 =
50+𝑃𝑙𝑜𝑠𝑠𝑒𝑠𝐹𝐿
50
𝑃𝑙𝑜𝑠𝑠𝑒𝑠 𝐹𝐿 = 0.96 − 50
• 𝑃𝑙𝑜𝑠𝑠𝑒𝑠𝐹𝐿 = 2.083 𝑘𝑊
𝑃𝐶𝑢𝐹𝐿 = (0.6)(2, 083)
• 𝑃𝐶𝑢𝐹𝐿 = 1, 249.8 𝑊
𝑃𝑐𝑜𝑟𝑒 = 𝑃𝑙𝑜𝑠𝑠 + 𝑃𝐶𝑢𝐹𝐿 = 2, 083 − 1, 249.8
• 𝑃𝑐𝑜𝑟𝑒 = 833.2 𝑊𝑎𝑡𝑡𝑠
𝑃𝑜𝑢𝑡𝑡𝑜𝑡𝑎𝑙 = (50 𝑘𝑉𝐴)(1.0)(8)
• 𝑃𝑜𝑢𝑡𝑡𝑜𝑡𝑎𝑙 = 400𝑘𝑊ℎ𝑟
𝑃𝑐𝑜𝑟𝑒 𝑡𝑜𝑡𝑎𝑙 = (833.2)(24)
• 𝑃𝑜𝑢𝑡𝑡𝑜𝑡𝑎𝑙 = 19.997 𝑘𝑊ℎ𝑟
𝑃𝐶𝑢𝑡𝑜𝑡𝑎𝑙 = (1, 249.8)(8)
• 𝑃𝐶𝑢𝑡𝑜𝑡𝑎𝑙 = 9.998 𝑘𝑊ℎ𝑟
400
ɳ𝑎𝑙𝑙 =
400+19.997+9.998
× 100%
𝑑𝑎𝑦
• ɳ𝒂𝒍𝒍 𝒅𝒂𝒚 = 𝟗𝟑. 𝟎𝟐%
20. A 500 kVA, single-phase, 13, 200/2, 400 Volts transformer has 4% reactance and 1%
resistance. The leakage reactance and resistance of the high voltage (primary) winding
are 6.34 Ω and 1.83 Ω, respectively. The core loss under rated condition is 1, 800 Watts.
Calculate the leakage reactance and resistance of the low voltage (secondary) winding.
A. 7.56 Ω and 1.66 Ω B. 13.69 Ω and 3.42 Ω
C. 0.25 Ω and 0.055 Ω D. 13.9 Ω and 3.48 Ω
Solution:
(𝑉𝑏)2 (13,200)2
𝑍𝑏 = =
𝑆𝑏 500,000
• 𝑍𝑏 = 348.48 𝑜ℎ𝑚𝑠
𝑅𝑒𝑝 = 𝑅𝑝𝑢𝑍𝑏𝑎𝑠𝑒 = (0.01)(348.48)
• 𝑅𝑒𝑝 = 3.4848 𝑜ℎ𝑚𝑠
𝑋𝑒𝑝 = 𝑋𝑝𝑢𝑍𝑏𝑎𝑠𝑒 = (0.04)(348.48)
• 𝑋𝑒𝑝 = 13.9392 𝑜ℎ𝑚𝑠
𝑟𝑒𝑓𝑒𝑟𝑟𝑒𝑑 𝑡𝑜 𝑝𝑟𝑖𝑚𝑎𝑟𝑦
𝑅𝑒 𝑝 = 𝑟𝑝 + 𝑎2𝑟𝑠
13,200
𝑎=
2,400
• 𝑎 = 5.5
𝑅𝑒𝑝−𝑟𝑝 3.4848−1.83
𝑟𝑠 = =
𝑎2 5.52
• 𝒓𝒔 = 𝟎. 𝟎𝟓𝟓
𝑋𝑒𝑝 = 𝑋𝑝 + 𝑎2𝑋𝑠
𝑋𝑒𝑝−𝑋𝑝 13.9392−6.34
𝑋𝑠 = =
𝑎2 5.52
• 𝑿𝒔 = 𝟎. 𝟐𝟓𝟏 𝒐𝒉𝒎𝒔
21. In Problem No.20, calculate the %V.R and efficiency of the transformer at full-load,
0.85 p.f. lagging and 2, 400 Volts.
A. 4% and 97.8% B. 6% and 95.4% C. 5% and 96.8% D. 3% and 98.4%
Solution:
𝑟𝑝 1.83
=
𝑎2 5.52
• 𝑟𝑝 = 0.0605 𝑜ℎ𝑚𝑠
𝑎2
𝑋𝑝 6.34
𝑎2
=
5.52
• 𝑋𝑝 = 0.21 𝑜ℎ𝑚𝑠
𝑎2
𝜃 = 𝑐𝑜𝑠−1(0.85)
• 𝜃 = 31.79°
500,000 ∠−31.79°
𝐼𝑇 = 2,400
• 𝐼𝑟𝑇 = 208.33𝑋∠ − 31.79°
𝑍 = ( 𝑝 + 𝑟 ) + 𝑗 ( 𝑝 + 𝑋 ) = (0.0605 + 0.055) + 𝑗(0.21 + 0.25)
𝑒𝑠 𝑎2 𝑠 𝑎2 𝑠
• ɳ𝑭𝑳 = 𝟗𝟕. 𝟓𝟔 %
REE – September 2002
24. A 20 kV/7.87 kV autotransformer has 200 A current in the common winding. What is the
secondary line current?
A. 143.52 B. 200 C. 56.48 D. 329
Solution:
𝐼𝑐
=𝑎−1
𝐼𝑝
20,000
𝑎=
7,870
• 𝑎 = 2.54
200
= 2.54 − 1
𝐼𝑝
• 𝐼𝑝 = 129.76 𝐴𝑚𝑝𝑒𝑟𝑒𝑠
𝐼𝑠 = 𝐼𝑝 + 𝐼𝑐 = 129.76 + 200
• 𝑰𝒔 = 𝟑𝟐𝟗. 𝟕𝟔 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
25. An autotransformer is adjusted for an output voltage of 85.3 Volts when operated from a
117 Volts line. The variable power load draws 3.63 kW at unity power factor at this
setting. Determine the transformed power and the connected power from the source to the
load.
A. 980 Watts and 2, 650 Watts B. 1, 343 Watts and 2, 287 Watts
C. 1, 815 Watts and 1, 815 Watts D. 1, 210 Watts and 2, 420 Watts
Solution:
117
𝑎=
85.3
• 𝑎 = 1.37
1 1
𝑃 = 𝑃 (1 − ) = (3, 630) (1 − )
𝑡𝑟𝑎𝑛𝑠 𝑖𝑛 𝑎 1.37
• 𝑷𝒕𝒓𝒂𝒏𝒔 = 𝟗𝟖𝟎. 𝟑𝟔 𝑾𝒂𝒕𝒕𝒔
𝑃 3,630
𝑃𝑐𝑜𝑛 = 𝑖𝑛 =
𝑎 1.37
• 𝑷𝒄𝒐𝒏 = 𝟐, 𝟔𝟒𝟗. 𝟔𝟒 𝑾𝒂𝒕𝒕𝒔
31. In problem No. 30, determine the p.f of each transformer secondary.
A. 0.820 lagging and 0.820 lagging B. 0.996 lagging and 0.424 leading
C. 0.996 lagging and 0.424 lagging D. 0.410 lagging and 0.410 lagging
Solution:
𝜃 = 𝑐𝑜𝑠−1(0.82)
• 𝜃 = 34.92°
𝑝. 𝑓1 = 𝑐𝑜 𝑠(30 + 𝜃) = 𝑐𝑜 𝑠(30 + 34.92)
• 𝒑. 𝒇𝟏 = 𝟎. 𝟒𝟐𝟒 𝒍𝒂𝒈𝒈𝒊𝒏𝒈
𝑝. 𝑓2 = 𝑐𝑜 𝑠(30 − 𝜃) = 𝑐𝑜 𝑠(30 − 34.92)
• 𝒑. 𝒇𝟐 = 𝟎. 𝟗𝟗𝟔 𝒍𝒂𝒈𝒈𝒊𝒏𝒈
34. A polarity test is performed upon a 1, 150/115 V transformer. If the input voltage is 116,
calculate the voltmeter reading if the polarity is subtractive.
A. 127.6 V B. 106 V C. 126 V D. 104.4 V
Solution:
𝑠𝑢𝑏𝑡𝑟𝑎𝑐𝑡𝑖𝑣𝑒
1,150
𝑎=
115
• 𝑎 = 10
116
𝑉𝑟𝑒𝑎𝑑𝑖𝑛𝑔 = 116 −
10
• 𝑽𝒓𝒆𝒂𝒅𝒊𝒏𝒈 = 𝟏𝟎𝟒. 𝟒 𝑽𝒐𝒍𝒕𝒔
35. A 20:1 potential transformer is used with a 150-V voltmeter. If the instrument
deflection is 118 Volts, calculate the line voltage.
A. 3, 000 V B. 2, 850 V C. 2, 360 V D. 2, 242 V
Solution:
𝑉𝐿
𝑎= 𝑉𝑟𝑒𝑎𝑑𝑖𝑛𝑔
20 𝑉𝐿
=
1 118
• 𝑽𝑳 = 𝟐, 𝟑𝟔𝟎 𝑽𝒐𝒍𝒕𝒔
REE –September 2010
36. A three-phase wye-delta connected, 50 MVA, 345/34.5 kV transformer is protected by
differential protection. The current transformer on the high side for differential protection
is 150:5. What is the current on the secondary side of CT’s?
A. 3.83 A B. 2.53 A C. 4.50 A D. 4.83 A
Solution:
𝑆 50,000,000
𝐼∅𝑝 = = 345,000
3𝑉∅𝑝 3( )
√3
• 𝐼∅𝑝 = 83.67 𝐴𝑚𝑝𝑒𝑟𝑒𝑠
𝑠𝑖𝑛𝑐𝑒 𝑤𝑦𝑒 − 𝑐𝑜𝑛𝑛𝑒𝑐𝑡𝑖𝑜𝑛
𝐼∅𝑝 = 𝐼𝐿 𝑝
• 𝐼𝐶𝑇 𝑝 = 𝐼𝐶𝑇 𝑝 = 83.67 𝐴𝑚𝑝𝑒𝑟𝑒𝑠
𝐿 ∅
𝐼𝑝 𝑁𝑝
𝑎= =
𝐼𝑠 𝑁𝑠
150 83.67
=
5 𝐼𝐶𝑇𝑠
∅
(83.67)(5)
𝐼𝐶𝑇 𝑠 =
∅ 150
• 𝐼𝐶𝑇 𝑠 = 2.789 𝐴𝑚𝑝𝑒𝑟𝑒𝑠
∅
𝐼𝐶𝑇𝑠𝑒𝑐 = √3 (2.789)
• 𝑰𝑪𝑻𝒔𝒆𝒄 = 𝟒. 𝟖𝟑𝟏 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
• 𝒁𝒓𝒆𝒍𝒂𝒚 = 𝟏. 𝟐 𝒐𝒉𝒎𝒔
38. Two transformers 1 and 2 are connected in parallel supplying a common load of 120 kVA.
Transformer 1 is rated 50 kVA, 7, 620/240-V single-phase and has an equivalent
impedance of 8.5 Ω while transformer 2 is rated 75 kVA, 7, 620/240-V single-phase and
has an equivalent impedance of 5.1 Ω. The two transformers operate with the same power
factors. What is the kVA load of each transformer?
A. 48 & 72 B. 45 & 75 C. 42 & 78 D. 40 & 80
Solution:
𝑍𝑒1 𝑆2
=
𝑍𝑒2 𝑆1
8.5 𝑆2
=
5.1 𝑆1
• 𝑆2 = 1.67𝑆1 → 𝑒𝑞′𝑛 1
• 𝑆𝐿 = 𝑆1 + 𝑆2 → 𝑒𝑞′𝑛 2
𝑆𝑢𝑏𝑠𝑡𝑖𝑡𝑢𝑡𝑒 𝑒𝑞’𝑛 1 𝑖𝑛 2
120 = 𝑆1 + 1.67𝑆1
• 𝑺𝟏 = 𝟒𝟒. 𝟗𝟒 𝒌𝑽𝑨
𝑆2 = 1.67(44.94)
• 𝑺𝟐 = 𝟕𝟓. 𝟎𝟓 𝒌𝑽𝑨
39. Two single-phase transformers are connected in parallel at no-load. One has a turns ratio
of 5, 000/440 and rating of 200 kVA, the other has a ratio of 5, 000/480 and rating of 350
kVA the leakage reactance of each is 3.5%. The no-load circulating current is .
A. 207 A B. 702 A C. 720 A D. 270 A
Solution:
2
𝑋 = (𝑉 𝑏𝑎𝑠𝑒1)
=
(440)2
𝑏𝑎𝑠𝑒1 𝑆𝑏𝑎𝑠𝑒1 200,000
• 𝑋𝑏𝑎𝑠𝑒1 = 0.968 Ω
(𝑉 )2 (480)2
𝑏𝑎𝑠𝑒2
𝑋𝑏𝑎𝑠𝑒2 = =
𝑆𝑏𝑎𝑠𝑒2 350,000
• 𝑋𝑏𝑎𝑠𝑒2 = 0.658 Ω
𝑋𝑒−𝑠1 = 𝑋𝑒𝑋𝑏𝑎𝑠𝑒1 = (0.035)(0.968)
• 𝑿𝒆−𝒔𝟏 = 𝟎. 𝟎𝟑𝟑𝟗 Ω
𝑋𝑒−𝑠2 = 𝑋𝑒𝑋𝑏𝑎𝑠𝑒2 = (0.035)(0.658)
• 𝑿𝒆−𝒔𝟐 = 𝟎. 𝟎𝟐𝟑 Ω
REE – October 1997
40. A power transformer rated 50, 000 kVA, 34.5/13.8 kV is connected Y-grounded primary
and delta on the secondary. Determine the full load phase current at the secondary side.
A. 2, 092 A B. 1, 725 A C. 1, 449 A D. 1, 208 A
Solution:
𝑆 = √3 𝑉𝐿𝐼𝐿
50,000,000
𝐼𝐿 𝑝 = (34,500)(√3)
• 𝐼𝐿 𝑝 = 836.74 𝐴𝑚𝑝𝑒𝑟𝑒𝑠
𝐼𝐿𝑝 = 𝐼∅𝑝
𝑉𝑝 𝐼𝑠
=
𝑉𝑠 𝐼𝑝
(34,500)(836.74)
𝐼∅𝑠 = 13,800 (√3)
• 𝑰𝒔∅ = 𝟏, 𝟐𝟎𝟕. 𝟕𝟑 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
𝑎𝑛𝑜𝑡ℎ𝑒𝑟 𝑠𝑜𝑙𝑢𝑡𝑖𝑜𝑛:
50,000,000
𝐼𝐿𝑠 = (√3) (13,800)
• 𝐼𝐿𝑠 = 2, 091.849 𝐴𝑚𝑝𝑒𝑟𝑒𝑠
𝐼 =
𝐼𝐿 𝑠
=
2,091.849
∅𝑠 √3 √3
• 𝑰∅𝒔 = 𝟏, 𝟐𝟎𝟕. 𝟕𝟑 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
46. Three 5:1 transformers are connected in delta-wye to step up the voltage at the beginning
of a 13, 200-Volt three-phase transmission line. Calculate the line voltage on the high
side of the transformers.
A. 114, 300 V B. 66, 000 V C. 132, 000 V D. 198, 000 V
Solution:
5 𝑉∅2 𝑉∅2
= =
1 𝑉∅1 13,200 𝑉
𝑉∅2 = 𝑎𝑉𝑝
𝑉∅2 = (5)(13, 200)
• 𝑉∅2 = 66, 000 𝑉𝑜𝑙𝑡𝑠
𝑉𝐿 = √3 𝑉∅2 = √3 (66, 000)
• 𝑽𝑳 = 𝟏𝟏𝟒, 𝟑𝟏𝟓. 𝟑𝟓𝟑 𝑽𝒐𝒍𝒕𝒔
47. A 150 kVA, 2, 400/480-V, three-phase transformer with an equivalent impedance of 4%is
connected to an infinite bus and without load. If a three-phase fault occurs at the
secondary terminals, the fault current in amperes is .
A. 4, 512 A B. 3, 908 A C. 7, 815 A D. 1, 504 A
Solution:
3 ∅ 𝑓𝑎𝑢𝑙𝑡 𝑜𝑛 𝑡ℎ𝑒 𝑠𝑒𝑐𝑜𝑛𝑑𝑎𝑟𝑦 𝑡𝑒𝑟𝑚𝑖𝑛𝑎𝑙𝑠
𝑆𝐵
𝐼𝐹 3∅ =
√3 𝑉𝐵𝑋𝑝𝑢
150,000
𝐼𝐹 3∅ = √3 (480)(0.04)
• 𝑰𝑭𝟑∅ = 𝟒, 𝟓𝟏𝟎. 𝟓𝟒𝟗 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
48. Transformer 1 is in parallel with Transformer 2
Transformer 1 Transformer 2
150 kVA, single-phase 300 kVA, single-phase
6, 600/240 V 6, 600/240 V
𝑍𝑒−𝑠1 = 0.02425∠62.9° Ω 𝑍𝑒−𝑠2 = 0.01067∠62.9° Ω
Determine the maximum kVA load the bank can carry without overloading any of the two transformers,
assuming that the two transformers operate at the same power factors.
A. 450 kVA B. 432 kVA C. 420 kVA D. 412 kVA
Solution:
𝑆1 + 𝑆2 = 𝑆𝑙𝑜𝑎𝑑
𝐶𝑎𝑠𝑒 𝐼:
𝑇1 @ 150 𝑘𝑉𝐴
𝑍𝑒−𝑠1 𝑆2
=
𝑍𝑒−𝑠2 𝑆1
𝑍𝑒−𝑠1 0.02425∠62.9°
= 0.01067∠62.9°
𝑍𝑒−𝑠2
• 𝑍𝑒−𝑠1 = 2.273
𝑍𝑒−𝑠2
𝑆2
2.273 =
𝑆1
𝑆2 = 2.273 (150, 000)
• 𝑆2 = 340.95 𝑘𝑉𝐴
• ∴ 𝑜𝑣𝑒𝑟𝑙𝑜𝑎𝑑 𝑎𝑡 𝑇2
𝐶𝑎𝑠𝑒 𝐼𝐼:
𝑇2 @ 300 𝑘𝑉𝐴
300,000
𝑆1 = 2.273
• 𝑆1 = 131.984 𝑘𝑉𝐴
𝑆𝑙𝑜𝑎𝑑 = 𝑆1 + 𝑆2 = (131.984) + (300)
• 𝑺𝒍𝒐𝒂𝒅 = 𝟒𝟑𝟏. 𝟗𝟖𝟏 𝒌𝑽𝑨