PH1100206
PH1100206
(GREENFIELD)
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
CONSTRUCTION SAFETY REQUIREMENTS
1.The constructors shall follow the safety regulations and the mandatory provisions 15.It is strictly forbidden to cut off the power of a running equipment without
while constructing telecommunication project. authorization.
2.While constructing in special areas such as highways, railways, bridges, navigational 16. No connector is allowed in the middle of a power cord.
channels, and in urban areas with crowded traffic, it is necessary to set warning signs, 17.It is forbidden to install switches or fuses in the ground lead or AC neutral wire.
or send special guards if needed. 18. It is strictly forbidden to hang signal lines and power lines on the lightning
3. In high-altitude operations, constructors should ware safety belts, helmets, and soft receptor, down conductor and its support.
rubber insulated shoes. 19. It is strictly forbidden to hang the AC power cord on the communication device.
4. Temporary facilities such as living place, offices must be safe, secure, and 20. Verify the power supply capacity when using the original power outlet.
comply with fire safety regulations. Combustible material is strictly forbidden in building 21. Electric operations should use well-insulated tools and be operated by qualified
temporary facilities. Temporary facilities should be far away from electrical facilities operator. When operating in running equipment, head cabinets, and branch
and high-voltage electric wires. cabinets, do not wear metal ornaments and take effective measures to prevent
5.Living room should be built in places far away from landslides, floods and metal materials such as screws, gaskets, and metal chips from falling.
mudslides. 22. No tools or equipment shall be placed on iron frames, channels, racks, ladders.
6. When working on rivers, lakes and reservoirs, it's necessary to wear life vest and 23. When working in machine room with running equipment, the working area shall
listen to the unified command. be demarcated. The operator shall not touch the running equipment, or the fire
7. Fire and smoking are strictly prohibited while operating in optical (electric) cable protection facilities, unless it is necessary.
entry rooms, waterline houses, machine rooms, unattended stations, woodworking 24. Non-construction personnel are strictly prohibited from entering the construction
sites, warehouses, forest areas, grasslands, etc. Fire protection device for exhaust area without the consent of the on-site commander. When lifting and working on the
pipe must be installed in vehicles before entering the fire ban area. tower, it is prohibited work or stand under the tower.
8.When the cables and other materials passing through the walls or floors, the holes 25. It is strictly forbidden to operate on the tower if sick or drunk.
must be sealed with fireproof materials. 26. When working on the tower, the safety belt of the operator must be fixed to the
9. When the electrical equipment is on fire, the power must be cut off first. main structure of the tower.
10. Safety belts must comply with the national standards. It is strictly forbidden to 27. When installing the antenna feeder at high altitude, the constructor should pay
replace the seat belt with ordinary ropes, wires, etc. attention to the safety and prevent the damage of the falling objects to the people on
11.When working near power supply line, constructors must wear safety helmets, the ground.
insulated gloves, insulated shoes and use insulated tools. 28. When laying cables, do not pull hard. Do not stand on the windowsill when
12.When working near high-voltage line, the minimum distance from the laying cables on the roof. Use safety belts when you must stand on the windowsill.
high-voltage line to constructors must be guaranteed: 2.5m while the line voltage is 29. Set obvious safety warning signs at the entrance of the construction site, cranes,
below 35kV, and 4m while the line voltage is above 35kV. temporary power facilities, access passages, holes, manholes, tower bottoms,
13.When working in flammable and explosive places, explosion-proof tools must be hazardous gas and liquid storage. Safety warning signs must comply with national
used. regulations.
14.It is strictly forbidden to store flammable, explosive and other dangerous
materials in the machine room.
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
BILL OF QUANTITY
Equipment Service
Contents Description Model Quantity Unit Remark Contents Description Model Quantity Unit Remark
Wireless Master Device 700M-3Sectors-3RRH Site Wireless Wireless Installation-Macrosite-LTE Single band-3 Sectors-3 Antenna Site
Wireless Master Device 2.1G-3Sectors-2RRU Site Wireless Wireless Installation-Macrosite-LTE Dual-band-3 Sectors-3 Antenna 1 Site
Wireless Master Device 2.1G-3sectors-3RRU Site
Wireless Wireless Installation-Macrosite-LTE Dual-band-3 Sectors-6 Antenna Site
Wireless Master Device 700M&2.1G-3Sectors-2RRU 1 Site
Wireless Master Device 700M&2.1G-3Sectors-3RRU Site Wireless Wireless Installation-Macrosite-LTE Tri-band-3 Sectors-3 Antenna Site
Wireless Master Device 2.1G&2.6G-3Sectors-2RRU Site Wireless Wireless Installation-Macrosite-LTE Tri-band-3 Sectors-6 Antenna Site
Wireless Master Device 2.1G&2.6G-3Sectors-3RRU Site Wireless Wireless Installation-Macrosite-LTE Tri-band-3 Sectors-9 Antenna Site
Wireless Master Device 700M&2.1G&2.6G-3sectors-2RRU Site Installation-Macrosite-NR Synchronization construction-3 Sectors-3 Antenna
Wireless Wireless Site
Wireless Master Device 700M&2.1G&2.6G-3sectors-3RRU Site
Wireless Master Device NR-3Sectors Site Wireless Wireless Installation-Macrosite-NR Asynchronous construction-3 Sectors-3 Antenna Site
Wireless Antenna L700 4ports 13.8dBi Pcs Auxiliary Power Device Installation for outdoor cabinet 1 Cabinet
Wireless Antenna L700 4ports 15.3dBi Pcs Auxiliary Civil work Equipment pad details on ground 1.456 m3
Wireless Antenna L2.1 4ports 17.0dBi Pcs Auxiliary Civil work Tower Foundation Concrete Volume 47.5 m3
Wireless Antenna L700&L2.1 8ports 13.5dBi 3 Pcs Auxiliary Civil work Grounding cable length of grounding system 41 Meter
Wireless Antenna L2.1&L2.6 12ports Pcs Auxiliary Civil work Grounding Busbar (24 holes) 1 Pcs
Wireless Antenna L700&L2.1&L2.6 16ports 13.2dBI Pcs Auxiliary Civil work Grounding Busbar (10 holes) 1 Pcs
Auxiliary Power 2.2m Power Cabinet_LiFeO4 1 Cabinet Auxiliary Civil work Equipment room-outdoor cable tray 1 Meter
Auxiliary Power 2.2m Equipment Cabinet_LiFeO4 Cabinet Auxiliary Civil work Soil test 1 Site
Auxiliary Power 2.2m Battery Cabinet_LiFeO4 Cabinet Auxiliary Civil work Site layout and clean 1 Site
Auxiliary Power 2.2m Eltek 2Bay Rectifier Cabinet Cabinet Auxiliary Civil work Door/Gate details 1 Site
Auxiliary Power Rectifier Module(50A) 4 Pcs Auxiliary Civil work Power supply (service entrance) 1 Site
Auxiliary Power 150Ah Lithium Iron Battery 2 Pcs Auxiliary Civil work Perimeter Light 4 Pcs
Auxiliary Power 100Ah Lithium Iron Battery Banks Auxiliary Civil work Fence 1 Site
Auxiliary Monitoring Monitoring in cabinet 1 Site Auxiliary Power supply Power supply layouting-5KW Site Refer to Note 1.
Tower Monopole DGT-30-340C-2NPT 1 Site Auxiliary Power supply Power supply layouting-20KW Site Refer to Note 1.
Tower 3-Leg Tublar Tower 3GT-30-340C-2NPT Site Auxiliary Power supply Power supply layouting-25KW Site Refer to Note 1.
Tower 3-Leg Tublar Tower 3GT-36-280C-2NPT Site Auxiliary Power supply Power supply layouting-35KW+ 1 Site Refer to Note 1.
Tower 4-Leg Angle Tower JGT-30-340C-2NPT Site Auxiliary Power supply Transformer-25KVA Site Refer to Note 1.
Tower 4-Leg Angle Tower JGT-36-280C-2NPT Site Auxiliary Power supply Transformer-37.5KVA Site Refer to Note 1.
Tower 4-Leg Angle Tower JGT-42-340C-2NPT Site Auxiliary Power supply Transformer-50KVA Site Refer to Note 1.
Tower 4-Leg Tublar Tower 4GT-42-340C-2NPT Site Auxiliary Power supply Temporary power for the site installation 1 Site
Note 1. It will be adjusted based on the actual AC commercial power capacity application in the future.
Note 2. Either one of the two grounding methods can be used
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
N
TRANSFORMER50kVA
(230MAWAYFROMSITE) SITE
D SITE ID (PH1100206)
O Domsat Road., San Rafael Village, Brgy. 9-A
M Poblacion, Davao City
TEMPORARYPOWER S
A
T
R
O
A
D
AD
O
R
H
T
ID
W
M .
6
D T
O
A S
R R
S
S E
E V
A
C
C
IL
E S
T
IV
A
B VICINITY MAP
R SCALE NTS
P
Site Information
Site
0 0
12
Site Code
Site Name
Area Type
ACPDBACPDB
Urban
10
MCB
MTS
00
Location Detail
0
HH
Site Detail
Civil Work Input: Site Type MacroSite
Frequency band 700M&2.1G
Exposure category: C D ;
Quantity of sectors 3
Soil Bearing Capacity: 75 kpa; Site Sub-type Greenfield
Under Ground Water Level: -6.40 m; Site category New
Type of property Private Land
Soft Subsoil: Yes No (MEDIUM DENSE) .
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
LIGHTNING
ARRESTER
N
32°
OB LIGHT
NOTE:
LESSOR AGREED TO USE THE OUTSIDE LEASED AREA (12000 x 12000)
LEASED AREA FOR EXCAVATION
PROPOSED
L700 & L2.1ANTENNA 1000 10000 1000
(RRH & RRU AT THE BACK OF ANTENNA)
500
500
PROPOSED
24 HOLES BUSBAR
PROPOSED
DGT-30-340C-2NPT
7600
2500
2500
3700
FOUNDATION LINE
2500
2500
DGT-30-340C-2NPT
10000
10000
2600
7600
2500
2500
PROPOSED TEST
PIT (OPTION 2)
PROPOSED
PROPOSED DGT-30-340C-2NPT
MTS TOWER
PROPOSED
3700
MCB 4 - Ø26/32mm HDPE PIPE
PROPOSED PROPOSED GPS LOCATION
2500
2500
PULL BOX
PROPOSED
PROPOSED PROPOSED POWER 5 m 1*Ø110 PVC PIPE
50mmØIMC SUPPLY CABINET AT THE 5 m FOC
CEF ROUTE EQUIPMENT PAD
PROPOSED
50mmØFLEXIBLE PROPOSED 24 HOLES BUSBAR
METAL/PVC
DISTANCE SHALL NOT
1500
1500
1500
CONDUIT
LESS THAN 700mm
PROPOSED ACPDB LOCATION
PROPOSED SURGE PROTECTOR DEVICE
SERVICE ENTRANCE AT THE BACK RESERVED 3 Ø110 STEEL
PROPOSED PROPOSED HANDHOLE
PIPE, w/ 3mm THICKNESS
TEST PIT (OPTION 1) 600*600*850
PROPOSED
5 m 1*Ø110 PVC PIPE THE LENGTH OF THE MATERIAL CAN
5 m FOC BE ADJUSTED ACCORDING TO THE
ACTUAL SCENE
PROPOSED 2200 2200 2175 3425
5 m 4*Ø26 / 32 HDPE PIPE THE LENGTH OF THE MATERIAL CAN
BE ADJUSTED ACCORDING TO THE
5 m FOC ACTUAL SCENE HH
PROPOSED
AM
KWHR METER
P
PROPOSED
GATE WAY
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
N
32°
TO AVIATION LIGHT
PERIMETER LIGHT
2*3.5mm²AC cable(BLACK/RED) with 20mm Ø PVC
PROPOSED
TEST PIT (OPTION 1)
PROPOSED
350 900 350 DGT-30-340C-2NPT
Equipment Pad
GPS Location
PROPOSED TEST
PIT (OPTION 2)
1140
2*60mm²AC cable(BLACK/RED)
2.5 m
Waterproof Switch for
4-Perimeter Lights
@1.5m HIGH from FGL POWER SUPPLY
CABINET MTS
MCB
2 SECTION "Y"
SCALE: NTS
Proposed Equipment list
1 ELECTRICAL LAYOUT NOTES :
SCALE: NTS NO. Item Dimension(mm)(W*D*H) QTY Comments
1. ALL EMBEDDED PIPES @450mm DEPTH.
LEGEND: 1 Self Supporting Tower 30000(H) 1 2. FOR WIRING & CONDUIT DETAILS REFER TO "SINGLE LINE DIAGRAM".
2 PERIMETER LIGHT 4 3. PVC PIPE FOR THE PERIMETER LIGHTS EMBEDDED IN THE COLUMN FROM
GROUND TO THE PERIMETER LIGHT.
DC CABLE 3 MCB 1
4 MTS 1
AC CABLE 5 ACPDB 1
6 Power Supply Cabinet 900*900*2285 1
FIBER
GLENN L. BRIONES
_____________________________________
PROFESSIONAL ELECTRICAL ENGINEER
PRC NO.: 0004812 PTR NO.: 4075993
TIN: 921-277-492 DATE ISSUED: 1/4/2023
2023MAR28
PLACE ISSUED: MALAYBALAY CITY, BUKIDNON
LIGHTNING
ARRESTER
PROPOSED
L700M&L2.1ANTENNA
OB LIGHT (L700 RRH & L2100 RRU AT A01
THE BACK OF ANTENNA)
A03
N
PROPOSED 32° S01:0°
L700M&L2.1ANTENNA
(L700 RRH & L2100 RRU AT
29.1 m THE BACK OF ANTENNA)
PROPOSED
L700 & L2.1ANTENNA
(RRH & RRU AT THE BACK OF ANTENNA)
S03:240°
PROPOSED L700M&L2.1ANTENNA
(L700 RRH AT THE BACK OF ANTENNA)
26 m
A02
S02:120°
Platform 1 Layout
PROPOSED
24 HOLES BUSBAR
OB Light power supply Cable:
ZRVV22 3x1.5mm2, (Blue/Black/Yellow & Green)
Note:
The metal outer sheath of the cable installed
horizontally should be connected to the lightning
protection flat bar or the ground wire every 5m ~ 10m;
The metal outer sheath of the cable (vertical) running Proposed Antenna Information
up and down should be grounded at least once near
both the upper and lower ends. Sector ID NO. Antenna Group Azimuth(°) ANT Height(m) Dimension(H*W*D) M-tilt(°) E-tilt(°) Ant mounted on Type
S01 A01 L700&L2.1 8ports 13.5dBi 0 29.1 1590×499×199 3 2 Platform 1 APXVBBLL15B_43-C-I20
S02 A02 L700&L2.1 8ports 13.5dBi 120 29.1 1590×499×199 3 3 Platform 1 APXVBBLL15B_43-C-I20
AHPC:
2*6mm² RRU DC POWER CABLE(BLUE/BLACK)
S03 A03 L700&L2.1 8ports 13.5dBi 240 29.1 1590×499×199 3 3 Platform 1 APXVBBLL15B_43-C-I20
ARGA: A04 GPS ANT 2.5
2*10mm² RRU DC POWER CABLE(BLUE/BLACK)
1 CPRI 50 5
2 Jumper 3 / 10 16 / 8
RONIE A. SOLIJON
______________________________________
PROFESSIONAL ELECTRONICS ENGINEER
PRC NO.: 0000364 PTR NO.: 5573564
TIN: 176-146-755 DATE ISSUED: 1/3/2023
2023MAR28
PLACE ISSUED: CAGAYAN DE ORO CITY
N
32°
PROPOSED
POWER SUPPLY CABINET
PROPOSED GPS
LOCATION
PROPOSED 1600
PROPOSED
EQUIPMENT PAD
PROPOSED
CABLE TRAY
1140
PROPOSED
24 HOLES
BUSBAR
2040
900
560
460
SURGE
PROTECTOR
DEVICE
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
10000
NOTES :
3. CHB / MASONRY :
1800
825 650 1500 650 1475 650 600 450 3200
10000
NOTE:
ALL PERIMETER
LIGHTS SHOULD
BE ON TOP OF
750
FGL +0.30
300
NGL ±0.00
2 TYPICAL ELEVATION
550
- SCALE : 1:20M
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
WELDED BARBED WIRE WELDED BARBED WIRE
(SEE NOTE #2) STAY 5-Ø10 ROUND BAR STAY 5-Ø10 ROUND BAR
(SEE NOTE #2)
94
94
BARBED WIRE HOLDER BARBED WIRE HOLDER PROPOSED COLUMN
75 350 75
142
142
142
142
31 31
10 10
75
750
26
26
750
100
142
142
30
30
100 88 142
100 88 142
30
30
200
350
500
25 THK CEMENT MORTAR
COPING 12mmØ BARS
200
200
BOTHWAYS
100
100
200
2000
OUTSIDE
75
INSIDE
LONG REBAR LONG REBAR
100 100 75 75
NGL ±0.000
2 BARBED WIRE HOLDER +0.300 10mmØ HORIZONTAL
SCALE NTS
BARS@ 600mm O.C.
CONTINUOUS WALL
300
FOOTING
38mmØ PVC 10mmØ VERTICAL
12mmØ BARS WEEP HOLES BARS @ 400mm O.C.
550
50mm THK.
LEAN CONCRETE
12mmØ 150mm THK CHB WITH
TIE BARS @ 200 O.C. MORTAR (150mm CHB)
50 500 50 -0.150
50
3-12mmØ CONT.
BARS
150
FENCE POST DETAIL
75
1 -0.300
SCALE NTS
500
75 250 75
75 350 75
400
PROPOSED COLUMN
200
CONTINUOUS WALL FOOTING DETAIL
75
50 100 50 5
100
4-12mmØ WITH 10mmØ LATERAL SCALE NTS
TIES @ 200mm O.C.
50
200
100
200
350
500
BILL OF MATERIAL(GRAVEL )
50
12mmØ BARS
BOTHWAYS
3 COLUMN SECTION A
200
NOTES :
SCALE NTS
1. PROVIDE DRAIN HOLES ON THE FRAMES.
75
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
412
3000
20
31 83 70 197 63
25 1465 1465 25
10 25 25 25
80
30 26
93
142
30
R20
142
40
750
40
900
142
142
109
205
ELEV. +2.300
88
250
250
R60
60
96
5 6
--
15
15
--
975
700
2700
63 20
412
83 70 197 63
800
4
2 --
975
3 --
--
400
300
FGL +0.300
2 BARREL BOLT DETAIL 25 25 25
NOTE:
FOOT BOLT SHOULD BE 35
INSTALLED INSIDE 1 METAL GATE DETAILS 12
FENCE/GATE. -- SCALE: 1:30
10 15
70
0
10
10 15
R1
10
15
12.5
25
15
35
25
60
35
40
6
25
70
25
12.6
7 DETAIL B
10
-- SCALE: 1:5
12.5 22.5 10 10
25
35 40
20
7
252
252
--
135
135
160
160
75
75
175
175
50
50
FGL ±0.30
50
50
150
45
25
4 HINGE DETAIL
3 FOOT BOLT DETAIL 100
25
-- SCALE: 1:5
-- SCALE: 1:10
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
300
00
30
15
00
4 RAMP DETAILS
SCALE 1:50
BILL OF MATERIAL(RAMP )
NOTES :
1.CONCRETE STRENCGTH:CLASS "A",21MPa(3000psi) @28 DAYS.
REINFORCING BARS: DIA.≥16,fy=414MPa
DIA.≤12,fy=275MPa
2.THE CONCRETE RAMP IS LAID ON THE COMPACTED SOIL WHICH
MUST BE NO LESS THAN 93% OF MAX DENSITY.
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
20mmØ TIMBLE EYEBOLT
MESSENGER WIRE TO
300 ELECTRICAL POLE
SPOOL INSULATOR
(IF REQUIRED PROVIDE 10mmØ BARS
400
DRIP LOOP) 6-16mmØ BARS WITH 450
650
10mmØ TIES @ 150mm O.C.
100 100 100 100
100
10mmØ BARS(SEE
SECTION 'B' DETAIL)
50
100
300
VARIES (AS PER POWER PROVIDER REQUIREMENT)
100
300
200
MALLEABLE CLAMP
1.0m SPACING
50
A CONDULET WITH 4 SECTION 'B'
REMOVABLE COVER SCALE NTS
SCALE NTS
KWHR METER
WITH CAGE & PADLOCK
1200
75 1050 75 450
REMOVABLE COVER
75
100
FGL +0.300 (MIN.)
300
NGL ±0.000
300
IMC CONDUIT
1200
1050
75
1 ELEVATION NOTES :
SCALE NTS
1.CONCRETE STRENCGTH:CLASS "A",21MPa(3000psi) @28 DAYS.
LEAN CONCRETE STRENGTH: 7MPa;
REINFORCING BARS: DIA.≥16 ,fy=414MPa
DIA.≤12 ,fy=275MPa
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
650
850
30 10mmØ BARS RING
50mmØ HDPE
A
ONE CLAMP PER METER
200 200
MCB MTS
CONDULET WITH
REMOVABLE COVER CLAMP
IMC CLAMP
1200
METAL/PVC CONDUIT 50mmØ HDPE
1200
CABLE LADDER IMC CLAMP
50mmØ IMC
FGL +0.300
50mmØ IMC
450
IMC
COUPLING
FGL +0.300
450 TO EQUIPMENT
50mmØ PVC&
50mmØ HDPE
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
SEE HANDLE
DETAIL
500
50 50
SEE HINGES
50mmØ PVC DETAIL 50 L 50mm x 6mm THK
PIPE SLEEVE
10
300
500
4-10mmØ NUTS 10mmØ DOWEL
38mm² BCW WITH WASHERS
50 50
10mmØ HANDLE
500mm x 200mm x 6mm THK
FLAT BAR (STOPPER PLATE)
5 HINGE DETAIL
3 TEST PIT / PULL-BOX COVER DETAIL NTS
SCALE NTS
SCALE
100
100
800
800
50mmØ PVC
50mm x 200mm x 6mm THK
950
950
PIPE SLEEVE
800
800
10 50
38mm² BCW END-BELL
150
200
50
50
38mm² BCW
COMPACTED COMPACTED
GRAVEL BEDDING GRAVEL BEDDING HANDLE DETAIL
SCALE NTS
5
8"Ø
x 3m
GROUNDING ROD
350 350
GLENN L. BRIONES
_____________________________________
PROFESSIONAL ELECTRICAL ENGINEER
PRC NO.: 0004812 PTR NO.: 4075993
TIN: 921-277-492 DATE ISSUED: 1/4/2023
2023MAR28
PLACE ISSUED: MALAYBALAY CITY, BUKIDNON
460
400 460
30 200 200 30
L60x60x6
4
420
400
420
400
350
3
400
340
24
24
L60x60x6
150
86
86
1000
1000
780
700
780
1500
1500
L60x60x6
L60x60x6
650
610
610
500
500
120
4 FRONT VIEW
SCALE 1:20M
3 SIDE VIEW
SCALE 1:20M
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
PROPOSED POWER
SUPPLY CABINET
800
500
150 500 150
PROPOSED BUSBAR Ø10mm TIES
75 SPACED AT 250mm O.C
75
PROPOSED
500
EQUIPMENT PLATFORM
4 - 16Ømm
CLOSED TIES
900
4 - Ø10mm TIES
TEMPERATURE BARS
75
1 SECTION 1
SCALE: NTS:
Ø10mm TIES
SPACED AT 250mm O.C
INSIDE OUTSIDE
NOTE:
500
THE PVC PIPE NEEDS TO BE ENCAPSULATED WITH CONCRETE COVERING
150
100mm THICK 3000PSI CONCRETE. FGL +0.300 (MIN.) ALL AROUND TO CONCEAL
700mm (min)
200 100
BOLTS & STIFFENERS
1 (SMOOTH FINISH)
300
550
400
100
NGL ±0.000
TOP OF ROADWAY
110 300
00
700
BOX CONCRETE R6
900
ENCASEMENT
Ø110 PVC PIPE
50
200
NOTE :
300 200 300
100mm THICK CONCRETE
IF THE HAND HOLE IS ON MAIN ROAD OR PAVEMENT, KEEP THE TOP ENCASEMENT 4 - Ø 26/32mm
HPDE PIPE 100mm THICK CONCRETE 75mm THICK
OF HAND HOLE COVER AT THE SAME SURFACE OF ROAD OR
ENCASEMENT LEAN CONCRETE
PAVEMENT. 2
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
NOTE :
800
600
550
RISING SLOT
100
TOP OF ROADWAY
800
4MMTHHK
125
HANDHOLE TOP COVER
100
25
TOP OF ROADWAY
DITO
800
550
800
4-HPDE CONDUIT
110 300
195 195
Ø26/32mm
700
2020
900
25
125
50
800
Ø110mm PVC PIPE
200
HANDHOLE COVER
IRON SUMP FRAME
300 200 300
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
C.V.AMIT J.REYES J.REYES
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
C.V.AMIT J.REYES J.REYES
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
CABLE TRAY
ACPDB
POWER
WORKING PLATFORM CABINET
ACPDB
FGL FGL
3Ø75 IMC
EXPOSED PIPE
WORKING PLATFORM
FGL FGL
3Ø75 PVC
EMBEDDED PIPE
_____________________________________
STRUCTURAL ENGINEER
2023MAR28
LLVD MCB
2x16A/1P
8x32A/1P
2x125A/1P
BLVD MCB
Battery MCB 6x16A/1P
4x125A/1P 3x25A/1P
5x32A/1P
Monitor 2x16A/1P
RECTIFIER
MODULE
DCDU-1U 50A (4)
FMS GSFU-1U
A2-3U DCDU ON ON ON ON ON ON ON ON
4x40A
I I I I I I I I
0 0 0 0 0 0 0 0
OFF OFF OFF OFF OFF OFF OFF OFF
SPARE-1U 4x30A 40A 40A 40A 40A 30A 30A 30A 30A
RESERVED-IDU-2U
SPARE-1U
BBU-3U
ODF-3U
RONIE A. SOLIJON
______________________________________
PROFESSIONAL ELECTRONICS ENGINEER
PRC NO.: 0000364 PTR NO.: 5573564
TIN: 176-146-755 DATE ISSUED: 1/3/2023
2023MAR28
PLACE ISSUED: CAGAYAN DE ORO CITY
C.V.AMIT J.REYES J.REYES
RONIE A. SOLIJON
______________________________________
PROFESSIONAL ELECTRONICS ENGINEER
PRC NO.: 0000364 PTR NO.: 5573564
TIN: 176-146-755 DATE ISSUED: 1/3/2023
2023MAR28
PLACE ISSUED: CAGAYAN DE ORO CITY
C.V.AMIT J.REYES J.REYES
RONIE A. SOLIJON
______________________________________
PROFESSIONAL ELECTRONICS ENGINEER
PRC NO.: 0000364 PTR NO.: 5573564
TIN: 176-146-755 DATE ISSUED: 1/3/2023
2023MAR28
PLACE ISSUED: CAGAYAN DE ORO CITY
C.V.AMIT J.REYES J.REYES
RONIE A. SOLIJON
______________________________________
PROFESSIONAL ELECTRONICS ENGINEER
PRC NO.: 0000364 PTR NO.: 5573564
TIN: 176-146-755 DATE ISSUED: 1/3/2023
2023MAR28
PLACE ISSUED: CAGAYAN DE ORO CITY
GENERAL NOTES:
160 AMP /Single Phase 1. ALL ELECTRICAL INSTALLATION WORKS HEREIN SHALL BE DONE IN ACCORDANCE WITH DITO
SPECIFICATIONS, THE LATEST EDITION OF THE PHILIPPINE ELECTRICAL CODE, THE RULES AND
SERVICE ENTRANCE PEDESTAL 2 - 60mm² THW (BLACK/RED) + REGULATION OF THE LOCAL MUNICIPALITY AND POWER UTILITY COMPANY.
1 - 30mm² THW GROUND (GREEN) 2. WIRING METHOD:
IN 50mmØ IMC OR 50mm PVC PIPE A. INTERMEDIATE METAL CONDUIT (IMC) FOR SERVICE ENTRANCE AND ALL EXPOSED PORTIONS.
B. UNDERGROUND CONDUITS SHALL BE PVC, ENCASED IN CONCRETE .
C. GROUNDING WIRES SHALL BE INSULATED.
MECB
TO ELECTRIC UTILITY CO. IN NEMA 3R ENCLOSURE 3. ALL NON-CURRENT CARRYING ELECTRICAL EQUIPMENT PARTS SHALL BE PROPERLY GROUNDED.
SERVICE DROP 160 AT, 2P, 25 kAIC MCCB 4. MINIMUM WIRE SIZE INSTALLED SHALL BE 3.5 mm² TYPE THHN/THW, UNLESS OTHERWISE INDICATED.
230VAC, 1 PHASE SYSTEM, 60Hz 230V, 60 Hz (ACPDB) 5. ALL WIRES SHALL BE A BRAND
SPD AC DISTRIBUTION PANEL 6. WIRING DEVICES SHALL BE A BRAND.
100 kA IP 55 Enclosure 7. ALL CIRCUIT BREAKERS SHALL BE BOLT ON TYPE IN IP 55 ENCLOSURE
FOR OUTDOOR LOCATIONS, USING DITO TYPE APPROVED ENCLOSURE.
160 AT, 2P
8. MAIN CIRCUIT BREAKERS SHALL BE INDUSTRIAL TYPE, 25 kAIC, WHILE BRANCH CIRCUIT BREAKERS
2 - 60mm² THW (BLACK/RED) + SHALL BE COMMERCIAL TYPE, 10 kAIC
125AT, 2P 20AT, 2P
1 - 30mm² THW GROUND (GREEN
RECTIFIER 1 1 2 SPACE 9. INSULATION TEST SHALL BE DONE BEFORE THE SITE IS ENERGIZED AND WITNESSED .
IN 50mmØ IMC OR 50mm PVC PIPE RESISTANCE SHALL BE GREATER THAN FIFTY(50) MEGA OHMS.
20AT, 2P 20AT, 2P
10. ALL EQUIPMENT AND MATERIALS SHALL BE BRAND NEW AND SUITED TO THE REQUIRED USE.
M Perimeter Light 3 4 C.OUTLETS
20AT, 2P 20AT, 2P 11. PULL BOXES OR JUNCTION BOXES SHALL BE PROVIDED, EVEN IF NOT
SPARE 5 6 SPARE INDICATED IN THE PLANS.
GENSET PROVISION
20AT, 2P 12. ALL ELECTRICAL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF A DULY
2 - 60mm² THW (BLACK/RED) + TO GROUNDING LOOP
SPARE 7 8 SPACE LICENSED AND REGISTERED ELECTRICAL ENGINEER.
1 - 30mm² THW GROUND (GREEN) NOTE:
IN 50mmØ IMC OR 50mm PVC PIPE MTS
1. THE POWER CORD OF THE SITE AVIATION OBSTRUCTION LIGHT SHOULD BE INSTALLED WITH
IN NEMA 3R OR 4X ENCLOSURE SPACE 9 10 SPACE
2- 160 AT, 2P, 25 kAIC MCCB A POWER CABLE WITH A METAL SHEATH OR LAID THROUGH A STEEL TUBE.
230V, 60 Hz THE METAL OUTER SHEATH OF THE CABLE (OR STEEL PIPE) SHOULD BE GROUNDED AT
BOTH ENDS AND INTO THE EQUIPMENT ROOM.
BOTH ENDS OF THE OUTDOOR CABLE LADDER SHOULD BE GROUNDED, AND THE GROUND
CONNECTED TO 10 HOLES GROUNDING CONNECTION
BUSBAR INSTALLED @ THE FIRST PLATFORM
OF THE TOWER or BASEPAD OF ELECTRICAL WIRE SHOULD BE A MULTI-STRAND COPPER WIRE WITH A CROSS-SECTIONAL AREA OF NOT
EQUIPMENT, REFER TO RISER DIAGRAM
LESS THAN 10MM2.
SINGLE LINE DIAGRAM 2. IF THE AVIATION OBSTRUCTION LIGHT IS DUAL TYPE (AC) TAPPING POINT SHALL BE AT THE ACPDB CIRCUIT NO.5.
3. IF THE AVIATION OBSTRUCTION LIGHT IS SINGLE TYPE (DC) TAPPING POINT SHALL BE AT THE RECTIFIER CABINET.
NTS SCALE
Perimeter Light
LEGEND
3 230 400 1.74 20 2P 2 - 3.5mm², THHN 1 - 3.5mm², THHN 15.4mm Ø IMC Pipe(1/2"), or 20mm Ø PVC
Feeder:
4 C. OUTLETS 230 600 2.61 20 2P 2 - 3.5mm², THHN 1 - 3.5mm², THHN 15.4mm Ø IMC Pipe(1/2"), or 20mm Ø PVC 2-60mm² THW (Black/Red)+ 1-30 mm² THW GROUND (GREEN)
IN 50 mmØ IMC or 50mm Ø PVC M KILOWATT HOUR METER
5 SPARE 230 600 2.61 20 2P 2 - 3.5mm², THHN 1 - 3.5mm², THHN 15.4mm Ø IMC Pipe(1/2"), or 20mm Ø PVC
MECB MAIN ENCLOSED CIRCUIT BREAKER
SPARE 230 2P
6 600 2.61 20 2 - 3.5mm², THHN 1 - 3.5mm², THHN 15.4mm Ø IMC Pipe(1/2"), or 20mm Ø PVC
Protection: MTS MANUAL TRANSFER SWITCH
7 SPARE - - - - - - - - 160 AT, 1-Phase MECB 2P, 230 V, 25 kAIC (EZD), ACPDB AC PANEL DISTRIBUTION BOARD
in NEMA 3R or 4x Enclosure.
8 SPACE - - - - - - - -
SPACE - - - - - - - - SPD
9
10 SPACE - - - - - - - - GROUND
GLENN L. BRIONES
_____________________________________
PROFESSIONAL ELECTRICAL ENGINEER
PRC NO.: 0004812 PTR NO.: 4075993
TIN: 921-277-492 DATE ISSUED: 1/4/2023
2023MAR28
PLACE ISSUED: MALAYBALAY CITY, BUKIDNON
10000
1000
THE TRANSFORMER. Please refer
3 WAY to the SINGLE LINE DIAGRAM
EXOTHERMIC FOR EXACT kVA RATING OF
CONN TRANSFORMER.
4000
1-24 HOLES GROUNDING
3 WAY BUSBAR FOR ELECTRICAL
EXOTHERMIC EQUIPMENT PAD
CONN
SEE TEST
PIT DETAILS (ST-07)
10000
10000
8000
8000
4000
4000
200 200
LEGEND:
3 WAY
EXOTHERMIC
38mm² BARE COPPER WIRE
CONN
3 WAY 4 WAY
3 WAY 40mmx4mm HDG FLAT BAR
EXOTHERMIC EXOTHERMIC
EXOTHERMIC
CONN
CONN CONN 30mm² INSULATED COPPER CABLE (GREEN)
FOR GROUNDING ELECTRODE CONDUCTOR
700
3 WAY COMPACTED
EXOTHERMIC REFER TO NOTE 1 FILL
1000
1000
CONN CONVERSION BAR COPPER TO HDG
3 WAY
16mmØ or 58"Ø x 2.5m or 3m
EXOTHERMIC COPPER CLAD STEEL
CONN Using Exothermic Weld or Cad Weld
CRIMP TYPE TERMINAL LUG To Bond the grounding cable and
Grounding Rod
(FOR BARE AND INSULATED
80
200
COPPER CABLE, CU/AL)
3-WAY EXOTHERMIC CONNECTION with BCW
& Grounding Rod
38mm² BARE COPPER WIRE
2750 3-WAY EXOTHERMIC CONNECTION with BCW
& FLATBAR
3000mm or 2500mm
4000 4000
1000 8000 1000 3-WAY EXOTHERMIC CONNECTION with BCW
10000
4-WAY EXOTHERMIC CONNECTION
1 EARTHING & LIGHTING LAYOUT
SCALE : NTS
16mmØ or 58"Ø x2.5m or 3m
SEE TEST PIT DETAILS COPPER CLAD STEEL
ST-07
2 DETAIL A
SCALE : NTS
GLENN L. BRIONES
_____________________________________
PROFESSIONAL ELECTRICAL ENGINEER
PRC NO.: 0004812 PTR NO.: 4075993
TIN: 921-277-492 DATE ISSUED: 1/4/2023
2023MAR28
PLACE ISSUED: MALAYBALAY CITY, BUKIDNON
C.V.AMIT J.REYES J.REYES
GLENN L. BRIONES
_____________________________________
PROFESSIONAL ELECTRICAL ENGINEER
PRC NO.: 0004812 PTR NO.: 4075993
TIN: 921-277-492 DATE ISSUED: 1/4/2023
2023MAR28
PLACE ISSUED: MALAYBALAY CITY, BUKIDNON