TRANE - PACU - Foundation GCC ECC
TRANE - PACU - Foundation GCC ECC
              Through the years, Trane has designed and developed the most complete line of Packaged Rooftop
              products available in the market today.
              Trane customers demanded a product that provided exceptional reliability, was easy to install, and was
              competitively priced.
              Trane listened and is proud to introduce the new Foundation™ Light Commercial rooftop unit. With
              Foundation, Trane continues to provide the highest standards in quality and reliability, comfort,
              performance, and ease of installation. light commercial products.
Copyright
              This document and the information in it are the property of Trane, and may not be used or reproduced in
              whole or in part without written permission. Trane reserves the right to revise this publication at any
              time, and to make changes to its content without obligation to notify any person of such revision or
              change.
Trademarks
              All trademarks referenced in this document are the trademarks of their respective owners.
Revision History
              •   Updated General data tables.
              •   Updated Evaporator fan performance tables.
              •   Digit K option removed.
              •   Minor edits to the document.
                Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
                      Barometric Relief . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
                      Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
                      Complete Coat™ Microchannel Condenser Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
                      Condensate Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
                      Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
                      Optional Stainless Steel Heat Exchanger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
                      Low Ambient Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
                      Unit Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
                Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
                      Cooling Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
                      Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
                      Air Delivery Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
                Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
                General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
                Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
                      Gross Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
                      Evaporator Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
                Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
                      Economizer Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
                      Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
                Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
                Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
                Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
                Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
RT-PRC060N-EN                                                                                                                                                          3
Table of Contents
                    Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
                         General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
                         Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
                         Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
                         Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
                         Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
4                                                                                                                                                  RT-PRC060N-EN
Features and Benefits
                Foundation™ has features and benefits that make it first class in the light commercial rooftop market.
                Designed with input from field contractors and technicians, its convertible airflow and ease of installation
                are outstanding.
Options(a)
                                                                             Standard
                                                                                            Factory Installed    Field Installed
Disconnect Switch X X
Economizer (Downflow) X X
Electric Heaters X X
Filters X
Hail/Vandal Guards X
LP Conversion Kit X
RT-PRC060N-EN                                                                                                                5
Features and Benefits
Large Foundation
Options(a)
                                                                                                    Standard
                                                                                                                         Factory Installed          Field Installed
Multi-Speed Oversized X
Powered Exhaust X
Remote Potentiometer X
Scroll Compressors X
Standardized Components X
Compressors
                 Foundation™ contains the best compressor technology available to achieve the highest possible
                 performance. Dual stages from manifold compressors are outstanding for humidity control and part load
                 cooling conditions.
Controls – Electromechanical
                 This 24-volt control includes the control transformer and contactor pressure lugs for power wiring.
Convertible Units
6                                                                                                                                             RT-PRC060N-EN
                                                                                                Features and Benefits
                 Foundation™ units ship in the downflow configuration. A horizontal conversion kit, consisting of two
                 downflow duct covers, is needed to convert the unit from a downflow to a horizontal airflow
                 configuration. Units come complete with horizontal duct flanges so the contractor doesn't have to field
                 fabricate them. These duct flanges are a time and cost saver. Units also have the ability to fit Trane and
                 other competitors roof curbs (Carrier). In a matter of minutes, you can go from the Trane configuration to
                 the Carrier configuration by simply changing the return air opening plate. This design allows for easy
                 field conversion and eliminates the need for costly adapter curbs.
Efficiency
                 Product efficiencies meet the requirements of ASHRAE 90.1.
Insulation
                 All panels in the evaporator section of the unit have foil-faced, glass fiber insulation. All base panels
                 have foil-faced, glass fiber insulation. All edges are either captured or sealed to ensure no insulation
                 fibers get into the airstream.
Frostat™
                 This switch monitors coil temperature to prevent evaporator icing and protect the compressor.
Heat Exchanger
                 The cabinet features a tubular heat exchanger in low, medium and high heat capacities – all available
                 for vertical and horizontal discharge directions. The heat exchanger is fabricated using aluminized steel
                 burners and corrosion-resistant, aluminized steel tubes as standard on all models. As part of the heat
                 exchanger assembly, an induced draft blower is used to pull the gas mixture through the burner tubes. A
                 direct spark ignition system, which doubles as a safety device to prove the flame, is used to ignite the
                 gas mixture.
RT-PRC060N-EN                                                                                                                7
Features and Benefits
Motors
                 All indoor fan motors are belt drive as standard.
Pressure Cutouts
                 Low and high pressure cutouts are standard on all Foundation™ models.
Phase Monitor
                 Foundation features a three-phase line monitor module that protects against phase loss, phase reversal
                 and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating
                 input voltage range of 180–600 Vac, and LED indicators for ON and FAULT. There are no field
                 adjustments and the module will automatically reset from a fault condition.
Quick-Access Panels
                 Remove three or less screws for access to the standardized internal components and wiring.
8                                                                                                          RT-PRC060N-EN
                                                                                               Features and Benefits
Standardized Components
                 Components are placed in the same location on all Foundation units. Familiarize yourself with one
                 Foundation and you are familiar with every Foundation. Due to standardized components throughout
                 the Foundation line, contractors/owners can stock fewer parts.
Variety of Options
Factory Installed Options
                 Complete Coat™ Condenser Coil
                 The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of
                 different types of heat exchangers. The coating is selected to provide excellent resistance and durability
                 to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salt air, and corrosive
                 environments.
                 Disconnect Switch
                 This accessory can be utilized as a convenient way to stock standard product without a disconnect and
                 have the ability to use the through the base/disconnect offering. The standard disconnect is non-fused,
                 3-pole, case molded switch.
                 Economizer - Downflow
                 Economizers are equipped with either dry bulb, reference, or comparative enthalpy sensing. These
                 economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly
                 installed, they offer valuable energy savings.
                 Factory-installed economizers save time and ensure proper installation.
                Note: Factory-installed economizers require some field set-up.
                 Electric Heaters
                 Electric heat modules are available within the basic unit. If ordering the through-the-base electrical
                 option with an electrical heater, the heater must be factory installed.
RT-PRC060N-EN                                                                                                                  9
Features and Benefits
                 Economizer - Horizontal
                 Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing. These
                 economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly
                 installed, they offer a valuable energy savings.
10                                                                                                            RT-PRC060N-EN
                                                                                                 Features and Benefits
                 LP Conversion Kit
                 Provided for field conversion of gas heat units from natural gas to propane.
                 Power Exhaust
                 This option is available on downflow units and provides exhaust of the return air, when using a downflow
                 economizer, to maintain proper building pressurization. This is an excellent option for relieving most
                 building overpressurization problems.
                 Remote Potentiometer
                 When installed in the economizer control circuitry, this accessory provides a method to remotely adjust
                 the minimum damper position.
                 Roof Curbs
                 Available for downflow units. Only one roof curb for the entire Foundation™ line simplifies curb
                 selection.
                 Thermostats
                 Available in programmable and non-programmable.
                 Tool-less, hail protection quality coil guards shall be field-installed for condenser coil protection. This
                 option protects the condenser coil from vandalism and/or hail damage.
Other Benefits
                 Cabinet Integrity
                 For added water integrity, Foundation has a raised 1-1/8 inch lip around the supply and return of the
                 downflow units to prevent water from blowing into the ductwork.
RT-PRC060N-EN                                                                                                                  11
Features and Benefits
                 field installed options, multiple control options, rigorously tested proven designs and superior product
                 and technical support.
                 Outstanding Flexibility
                 The Foundation unit has the ability to adapt to specific Carrier WeatherMaker™ models without costly
                 adapter curbs. This will save contractors money and make the installation an ease.
                 Rigorous Testing
                 All of Foundation’s designs were rigorously rain tested at the factory to ensure water integrity.
                 Foundation units incorporate either a one piece top or the Trane-Tite-Top (T3). Each part of the top
                 overlaps in such a way that water cannot leak into the unit. These overlapped edges are gasketed and
                 sealed to ensure superior water integrity.
                 Actual shipping tests were performed to determine packaging requirements. Units were test shipped
                 around the country to determine the best packaging. Factory shake and drop tests were used as part of
                 the package design process to help assure that the unit arrives at the job site in top condition.
                 Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and
                 rails hold up under stress. For the microchannel coils, the supplier will perform the leak check at 450
                 psig. The completely assembled refrigerant system is leak tested at a minimum of 225 psig with a
                 refrigerant and nitrogen mixture.
                 All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected
                 immediately. Every unit receives a 100% unit run test before leaving the production line to make sure it
                 lives up to rigorous Trane requirements.
                 Unmatched Support
                 Trane Sales Representatives are a Support Group that can assist you with:
                 •   Product
                 •   Special Applications
                 •   Application
                 •   Specifications
                 •   Service
                 •   Computer Programs and much more
                 •   Training
12                                                                                                                RT-PRC060N-EN
Application Considerations
                Application of this product should be within the cataloged airflow and cooling considerations.
Barometric Relief
                This product line offers an optional barometric relief damper for use in conjunction with economizer
                option. This accessory consists of gravity dampers which open with increased pressure. As building
                pressure increases, the pressure in the unit return air section also increases, opening the dampers and
                relieving the conditioned space.
                Notes:
                         •   The effectiveness of barometric relief damper during economizing operation is system
                             related.
                         •   Pressure drop of the return air system should be considered to control building
                             pressurization.
Clearance Requirements
                The recommended clearances identified with unit dimensions should be maintained to ensure adequate
                serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear
                inadequate should be reviewed with local Trane sales personnel.
Condensate Trap
                The evaporator is a draw-through configuration. A trap must be field provided prior to start-up on the
                cooling cycle.
Heating Operation
                The heat exchanger is manufactured with aluminized steel.
                To prevent condensation within the heat exchanger, do not exceed 50 percent outside air or a minimum
                mixed air temperature of 40°F.
Unit Pitch
                These units have sloped condensate drain pans. Units must be installed level. Any unit slope must be
                toward access side of the unit.
RT-PRC060N-EN                                                                                                            13
Selection Procedure
Cooling Capacity
            Note: Cooling capacity procedure is the same for cooling (E) and gas/electric (G).
            1. Calculate the building’s total and sensible cooling loads for the building at design conditions. Use
               the following calculation methods or any other standard accepted method.
                Factors used in unit selection:
                •    Total Cooling Load: 180 MBh
                •    Sensible Cooling Load: 126 MBh
                •    Airflow: 6000 cfm
                •    Electrical Characteristics: 460/60/3
                •    Summer Design Conditions: Entering Evaporator Coil: 80ºF DB/67ºF WB
                •    Outdoor Ambient: 95ºF
                •    External Static Pressure: 0.38 in. wg
                •    Rooftop – downflow configuration
                •    Efficiency: 14 SEER
                •    Accessories: Economizer, Roof Curb, Electric Heat
            2. As a starting point, a rough determination must be made of the size of the unit. The final selection
               will be made after examining the performance at the given conditions. Divide the total cooling load
               by nominal Btuh per ton (12 MBh per ton); then round up to the nearest unit size.
                180 MBh / 12 MBh = 15.0 tons
            3. Table 10, p. 26 shows that a ECC180A4 has a gross cooling capacity of 187.2 MBh and 143 MBh
               sensible capacity at 6000 cfm and 95 DB outdoor ambient with 80 DB, 67 WB air entering the
               evaporator.
                Find capacity at intermediate conditions not in the table
                When the design conditions are between two numbers that are in the capacity table, interpolation is
                required to approximate the capacity.
                Note: Extrapolation outside of the table conditions is not recommended.
            4. In order to select the correct unit which meets the building’s requirements, the fan motor heat must
               be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is
               dependent on the effort by the motor - cfm and static pressure. To determine the total unit static
               pressure you add the external static pressure to the additional static related by the added features:
             Note: Reference heating capacity section on this page for determination of heater size. No additional static add for gas/heat
                    exchanger.
                Note: The Evaporator Fan Performance Table 10, p. 26 has already accounted for the pressure
                      drop for standard filters and wet coils (see note below in Table 10, p. 26). Therefore, the
                      actual total static pressure is 0.55 - 0.05 (from ) = 0.50 wg.
                With 6000 cfm and 0.50 wg. Table 10, p. 26 shows 1.37 bhp for this unit. Note below the table is the
                formula to calculate fan motor heat.
14                                                                                                                            RT-PRC060N-EN
                                                                                               Selection Procedure
                    Now subtract the fan motor heat from the gross cooling capacity of the unit:
                    Net Total Cooling Capacity = 187.2 MBh - 4.32 = 182.88 MBh.
                    Net Sensible Cooling Capacity = 143 MBh - 4.32 = 138.68 MBh.
                5. Compare your resulting capacities to the building load. If the performance will not meet the required
                   load of the building’s total or sensible cooling load, try a selection at the next higher size unit.
Heating Capacity
                Note: Heating capacity procedures DIFFER for cooling (E) and gas/electric (G) units.
                1. Calculate the building heating load.
                2. Size the system heating capacity to match the calculated building heating load. The following are
                   building heating requirements:
                    460 volt/3 phase Power Supply
                    Total heating load of 115.0 MBh
                    6000 cfm
                    The electric heat accessory capacities are listed in Table 31, p. 42. From the table, a 36 kW heater
                    will deliver 122.94 MBh at 480 volts. In order to determine capacity at 460 volts, the heater voltage
                    correction factor from Table 32, p. 43 must be used. Therefore, 122.94 MBh x 0.94 (voltage
                    correction factor) = 115.6 MBh.
                    Gas/electric: Fuel natural gas total heating load of 195 MBh. Table 30, p. 42 shows 250 MBh and
                    350 MBh input models. The output capacities of these furnaces are 203 MBh and 284 MBh
                    respectively. The low heat model with 203 MBh output best matches the building requirements.
RT-PRC060N-EN                                                                                                               15
Model Number Description
Digit 1 — Unit Type Digit 11— Minor Design Sequence Digit 17 — Condenser Coil Protection
16                                                                                                                                  RT-PRC060N-EN
General Data
Table 1. General data — 15 to 25 tons
                                                                15 Ton                 17.5 Ton                  20 Ton                                25 Ton
                                                              E/GCC180                E/GCC210                 E/GCC240                  ECC300                   GCC300
Cooling Performance(a)
Gross Cooling Capacity                                          194,000                 214,000                  252,000                 280,000                  280,000
EER (Downflow/Horizontal)                                          11                      11                       10                      10                       9.8
Nominal Airflow CFM / AHRI Rated CFM                             5400                     6650                    7000                     8000                     8000
AHRI Net Cooling Capacity                                       180,000                 206,000                  244,000                 268,000                  268,000
Integrated Energy Efficiency Ratio (IEER) (Multi
                                                                  14.2                    14.2                     13.2                    13.2                      13.2
Speed Fan)
Percent Capacity @ part load (Stage 1/Stage 2)                  53 / 100                50 / 100                 54 / 100                53 / 100                  53 / 100
System Power (kW)                                                16.36                   18.73                    24.40                   26.80                     27.35
Compressor
Number/Type                                                    2 / Scrolls             2 / Scrolls              2 / Scrolls             2 / Scrolls               2 / Scrolls
Sound
Outdoor Sound Rating (BELS)                                       9.5                      9.5                     9.5                      9.5                      9.5
Outdoor Coil
Type                                                         Microchannel            Microchannel             Microchannel            Microchannel              Microchannel
Coil Width (in.)                                                  0.71                    1.00                     1.00                    1.00                      1.00
Face Area (sq. ft.)                                              34.74                    34.74                   34.74                    34.74                    34.74
Rows/FPI                                                         1 / 23                   1 / 21                  1 / 23                   1 / 23                   1 / 23
Indoor Coil
Type                                                         Microchannel            Microchannel             Microchannel            Microchannel              Microchannel
Tube Size (in.) ID                                                 1                        1                       1                        1                        1
Face Area (sq. ft.)                                              26.00                    26.00                   26.00                    26.00                    26.00
Rows/FPI                                                          2/18                    2/18                     2/18                    4/15                      4/15
Refrigerant Control                                             TXV                     TXV                      TXV                     TXV                      TXV
                                                               1 / 1.00                1 / 1.00                 1 / 1.00                1 / 1.00                 1 / 1.00
Drain Connection Number/Size (in.)
                                                           PVC Pipe Female         PVC Pipe Female          PVC Pipe Female         PVC Pipe Female          PVC Pipe Female
Outdoor Fan
Type                                                           Propeller                Propeller               Propeller                Propeller                Propeller
Number Used/Diameter (in.)                                       2 / 28                   2 / 28                  2 / 28                   2 / 28                   2 / 28
Drive Type/No. Speeds                                          Direct / 1               Direct / 1              Direct / 1               Direct / 1               Direct / 1
cfm                                                             15,900                   15,900                  15,900                   15,900                   15,900
Number Motors/hp                                                 2 / 1.0                 2 / 1.0                  2 / 1.0                 2 / 1.0                   2 / 1.0
Motor rpm                                                        1125                     1125                    1125                     1125                     1125
Indoor Fan
Type                                                        FC Centrifugal           FC Centrifugal          FC Centrifugal           FC Centrifugal            FC Centrifugal
Number Used/Diameter (in.)                                     2 / 15x15                2 / 15x15               2 / 15x15                2 / 15x15                2 / 15x15
Drive Type/No. Speeds                                           Belt / 1                 Belt / 1                Belt / 1                 Belt / 1                 Belt / 1
Number Motors                                                      1                        1                       1                        1                        1
Motor hp (Standard/Oversized)                                   3.0 / 5.0               5.0 / 7.5                5.0 / 7.5               7.5 / 10.0               7.5 / 10.0
Motor rpm (Standard/Oversized)                                1750 / 3450             3450 / 3450              3450 / 3450             3450 / 1750               3450 / 1750
Motor Frame Size (Standard/Oversized)                         145T / 145T             145T / 184T              145T / 184T             184T / 215T               184T / 215T
Filters
Type Furnished(b)                                             Throwaway               Throwaway                Throwaway               Throwaway                 Throwaway
Number Size Recommended                                       (8) 20x25x2             (8) 20x25x2              (8) 20x25x2             (8) 20x25x2               (8) 20x25x2
Refrigerant Charge (Pounds of R-410A)(c)
Circuit 1                                                         14.6                    15.2                     16.5                    17.8                      17.8
(a)   Units are AHRI Certified to AHRI Standard 340-360 (I-P). Rating conditions are 95°F outdoor air temperature, 80°F entering dry bulb, 67°F entering wet bulb with minimum
      external static pressure as determined by rating standard.
(b)   Optional field-installed MERV 13 filters available.
(c)   Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.
RT-PRC060N-EN                                                                                                                                                                   17
General Data
18                                                                                                                                            RT-PRC060N-EN
Performance Data
Gross Cooling Capacities
Table 3. Gross cooling capacities 15 tons - E/GCC180A3,4,W
                        Ambient Temperature (°F)                         Ambient Temperature (°F)                         Ambient Temperature (°F)
                         85                                                         95                                              105
             Entering Wet Bulb Temp (°F)                                Entering Wet Bulb Temp (°F)                      Entering Wet Bulb Temp (°F)
     Ent
    DB (°    61          67           73                               61              67              73               61              67              73
CFM   F)  MBh SHC MBh SHC MBh SHC                                 MBh    SHC      MBh     SHC      MBh     SHC     MBh    SHC     MBh      SHC      MBh      SHC
          75    166.5 134.8 190.7 107.0 209.9              70.8   158.0 130.5 180.8 102.6 197.5             65.9   149.1 126.0 170.2         97.9   184.3    64.1
          80    165.7 157.3 190.1 131.6 210.6 100.2 157.3 152.8 180.4 127.1 198.3                           95.4   148.4 148.1 170.0 122.4 184.8             90.1
 4800
          85    170.6 170.6 189.7 156.5 211.5 126.2 164.0 164.0 180.0 152.1 199.6 121.0 156.8 156.8 169.7 146.2 186.2 115.6
          90    181.5 181.5 188.9 178.6 211.4 151.1 174.5 174.5 179.2 173.9 199.4 146.2 166.9 166.9 168.8 168.8 186.1 140.8
          75    170.4 143.7 194.9 112.4 213.8 75.6 161.6 136.7 184.4 107.8 200.7                            70.6   152.2 129.8 173.3 102.3 186.8             65.4
          80    169.2 167.8 194.5 139.8 213.9 104.6 160.5 160.5 184.2 135.2 201.1                           99.7   152.5 152.5 173.3 130.3 187.7             94.6
 5400
          85    178.0 178.0 193.9 164.5 214.9 132.9 170.9 170.9 183.4 161.2 202.1 127.8 163.2 163.2 172.4 156.0 187.8 122.2
          90    189.3 189.3 192.4 191.2 214.8 161.2 181.7 181.7 182.3 182.3 202.0 156.1 173.3 173.3 173.5 173.5 187.7 150.5
          75    173.5 146.8 198.1 116.8 216.9 77.1 163.8 145.7 187.5 112.1 203.2 71.9 154.0 140.7 176.1 107.1 193.2                                          68.1
          80    172.3 172.3 197.9 147.7 217.1 109.1 165.2 165.2 187.2 143.0 203.9 104.0 157.5 157.5 175.8 138.0 190.1                                        99.0
 6000
          85    184.3 184.3 196.5 175.7 217.4 139.7 176.7 176.7 185.7 170.7 203.9 134.5 168.5 168.5 174.2 165.4 190.0 129.1
          90    196.0 196.0 196.2 196.2 217.3 171.0 187.7 187.7 187.9 187.9 203.9 165.0 178.2 178.2 178.4 178.4 189.8 153.4
          75    175.2 157.9 201.2 121.6 219.5 78.4 165.6 153.0 190.1 116.7 205.2 73.1 155.5 147.9 178.2 111.6 196.4 69.8
          80    177.4 177.4 200.6 155.4 219.8 113.4 169.9 169.9 189.5 150.5 206.5 107.4 161.8 161.8 177.7 144.5 191.9 101.8
 6600
          85    189.8 189.8 198.5 185.0 219.7 146.6 181.7 181.7 187.3 179.9 206.1 141.3 172.9 172.9 175.4 174.5 191.6 135.8
          90    201.5 201.5 201.7 201.7 219.4 175.4 192.4 192.4 192.6 192.6 205.0 172.9 181.9 181.9 182.0 182.0 190.3 167.0
          75    176.8 164.9 203.5 126.2 221.5 79.7 166.9 159.9 192.0 121.2 206.7 74.3 156.5 154.8 179.8 115.9 199.0 71.3
          80    181.9 181.9 202.7 162.8 222.0 116.5 174.1 174.1 191.4 154.6 208.0 111.0 165.5 165.5 178.7 150.2 193.5 105.4
 7200
          85    194.6 194.6 199.8 194.0 222.0 153.4 186.0 186.0 188.3 188.3 207.8 148.0 176.5 176.5 176.6 176.6 192.8 142.4
          90    206.0 206.0 206.2 206.2 220.2 187.2 196.1 196.1 196.3 196.3 206.0 181.5 184.3 184.3 184.4 184.4 190.8 175.5
                        Ambient Temperature (°F)                         Ambient Temperature (°F)                         Ambient Temperature (°F)
                                 115                                               120                                              125
                      Entering Wet Bulb Temp (°F)                       Entering Wet Bulb Temp (°F)                      Entering Wet Bulb Temp (°F)
     Ent
    DB (°    61                       67              73               61              67              73               61              67              73
CFM   F)  MBh SHC                MBh     SHC      MBh     SHC     MBh    SHC      MBh     SHC      MBh     SHC     MBh    SHC     MBh      SHC      MBh      SHC
          75    139.5 118.4 158.7          92.9   169.9    58.7   134.4 114.3 152.5         89.7   161.9    55.8   129.0 110.9 146.2         86.9   153.2    52.6
          80    139.2 139.2 158.7 117.4 170.9 84.9 135.2 135.2 152.7 114.8 163.3 82.1 130.9 130.9 146.2 111.9 155.3 79.1
 4800
          85    149.0 149.0 158.3 140.8 171.3 109.8 144.7 144.7 152.2 138.0 163.8 106.9 140.0 140.0 145.6 135.0 155.7 103.8
          90    158.3 158.3 158.4 158.4 171.1 135.0 153.3 153.3 153.5 153.5 163.6 132.1 147.8 147.8 147.9 147.9 155.4 128.6
          75    141.7 128.1 161.5 97.1 171.4 59.7 136.3 125.3 155.2 94.4 170.4 59.2 130.7 122.5 148.4 91.5 153.7 53.4
          80    144.5 144.5 161.4 125.2 173.3 89.1 140.2 140.2 155.1 122.4 165.6 86.4 135.6 135.6 148.3 119.5 157.6 83.7
 5400
          85    154.6 154.6 160.4 150.5 173.3 116.6 149.8 149.8 153.9 147.5 165.3 113.6 144.6 144.6 147.0 144.4 156.6 110.3
          90    163.4 163.4 163.6 163.6 173.1 142.2 157.6 157.6 157.7 157.7 167.8 140.2 150.8 150.8 150.9 150.9 160.6 138.5
          75    143.4 135.4 163.7 101.7 180.2 63.3 137.9 132.6 157.1 98.8 163.5 57.6 132.0 129.7 150.1 95.8 154.0 54.3
          80    149.1 149.1 163.5 132.7 175.5 92.4 144.5 144.5 156.8 129.2 167.5 89.4 139.5 139.5 149.6 125.8 158.9 86.1
 6000
          85    159.1 159.1 161.7 159.7 174.6 123.3 153.9 153.9 155.0 155.0 166.2 120.1 148.0 148.0 148.1 148.1 157.2 116.8
          90    166.9 166.9 167.0 167.0 173.8 152.2 159.8 159.8 159.9 159.9 169.8 150.5 152.7 152.7 152.8 152.8 162.9 147.8
          75    144.7 142.5 165.4 106.1 173.1 61.7 138.9 138.9 158.6 103.1 164.0 58.5 133.0 133.0 151.3 100.0 168.7 59.8
          80    152.9 152.9 165.0 135.1 176.7 96.0 148.0 148.0 157.5 135.3 168.4 92.8 142.7 142.7 150.1 132.0 159.7 89.4
 6600
          85    162.7 162.7 162.8 162.8 179.9 131.3 156.9 156.9 157.0 157.0 173.1 128.7 150.2 150.2 150.3 150.3 157.6 123.1
          90    168.7 168.7 168.9 168.9 174.0 160.7 162.2 162.2 162.3 162.3 171.6 159.6 158.6 158.6 158.7 158.7 164.6 156.9
          75    145.4 145.4 166.7 110.3 185.1 66.4 140.4 140.4 159.7 107.3 178.0 63.8 135.4 135.4 152.2 104.1 154.9 56.3
          80    156.1 156.1 165.2 144.7 177.7 99.3 150.9 150.9 158.0 141.6 169.2 96.1 145.2 145.2 150.3 138.2 160.3 92.6
 7200
          85    165.4 165.4 165.5 165.5 176.4 136.3 158.9 158.9 159.0 159.0 167.3 132.0 151.4 151.4 151.5 151.5 157.5 128.5
          90    171.3 171.3 171.4 171.4 179.9 171.1 168.2 168.2 168.4 168.4 173.0 168.4 163.1 163.1 163.2 163.2 165.9 165.7
Notes:
   1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat
       formula, refer to appropriate airflow table notes.
   2. MBh = Total gross capacity
   3. SHC = Sensible heat capacity
RT-PRC060N-EN                                                                                                                                                       19
Performance Data
20                                                                                                                                                      RT-PRC060N-EN
                                                                                                                                             Performance Data
RT-PRC060N-EN                                                                                                                                                       21
Performance Data
22                                                                                                                                                      RT-PRC060N-EN
                                                                                                                                                  Performance Data
RT-PRC060N-EN                                                                                                                                                              23
Performance Data
Table 8. Evaporator fan performance - 15 ton units with gas heat (model number digit 10 = L, M, X, Y) - GCC180 -
          horizontal airflow
                                                    Available External Static Pressure (Inches of Water)
              0.10        0.20         0.30        0.40        0.50                          0.60            0.70       0.80        0.90                    1.00
  cfm      rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                        rpm bhp         rpm bhp rpm bhp rpm bhp                        rpm bhp
                 3-hp Standard Motor, Low Static Drive Accessory                                            3-hp Standard Motor and Drive
 4800      488     0.72    532    0.85     572    0.99     609    1.12    643     1.24    675     1.37    707     1.52    738    1.67     767    1.82     796    1.98
 5400      539     1.00    578    1.13     615    1.29     650    1.43    683     1.58    714     1.72    743     1.87    771    2.02     800    2.19     827    2.36
 6000      591     1.34    626    1.48     660    1.65     693    1.82    724     1.98    754     2.14    782     2.30    809    2.46     834    2.62     860    2.79
 6600      643     1.75    675    1.90     706    2.07     738    2.26    767     2.45    795     2.62    823     2.80    849    2.98     873    3.15     897    3.33
 7200      696     2.24    725    2.40     754    2.58     783    2.77    811     2.99    838     3.19    864     3.38    889    3.57     913    3.76     937    3.95
                                                     Available External Static Pressure (Inches of Water)
              1.10           1.20            1.30            1.40        1.50        1.60     1.70       1.80         1.90        2.00
  cfm      rpm bhp        rpm bhp         rpm bhp         rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
                                                          3-hp Standard Motor and High Static
              3-hp Standard Motor and Drive                                                        5-hp Oversized Motor and Drive
                                                                   Drive Accessory
 4800      823     2.13    849    2.29  874 2.44           899    2.60    923     2.76    946     2.91    969     3.07    991     3.23   1012     3.39    1033    3.55
 5400      853     2.53    879    2.70 903(a) 2.88         927    3.05    951     3.22    973     3.40    995     3.57   1017     3.75   1038     3.93    1059    4.11
 6000      886     2.98    910    3.17     934    3.36     957    3.55    980     3.74    1003    3.94   1024     4.13   1045     4.32    1066    4.52    1086    4.71
 6600      920     3.50    944    3.70     967    3.91     990    4.11    1012    4.32    1033    4.53   1054     4.74   1075     4.95     —       —       —       —
 7200      959     4.15    981    4.34    1002    4.53    1024    4.74    1045    4.96     —       —       —       —       —       —       —       —       —       —
Notes:
   1.      For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
   2.      For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
   3.      For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
   4.      Fan motor heat (MBh) = 3.15 x Fan bhp.
   5.      Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
   6.      For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
   7.      Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
           cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
           failure. Our product’s warranty will not be affected.
      8.   Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
           options.
(a)   3-hp Standard Motor and High Static Drive Accessory.
24                                                                                                                                                           RT-PRC060N-EN
                                                                                                                                                  Performance Data
Table 9. Evaporator fan performance - 15 ton units with gas heat (model number digit 10 = H, Z) - GCC180 - horizontal
          airflow
                                                    Available External Static Pressure (Inches of Water)
              0.10        0.20         0.30        0.40        0.50                          0.60            0.70        0.80         0.90                  1.00
  cfm      rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                        rpm bhp         rpm bhp rpm bhp rpm bhp                        rpm bhp
                 3-hp Standard Motor, Low Static Drive Accessory                                               3-hp Standard Motor Drive
 4800       —       —       —       —       —      —       —       —       —       —      675     1.37    707     1.52    738    1.67     767    1.82     796    1.98
 5400       —       —       —       —       —      —       650    1.43    683     1.58    714     1.72    743     1.87    771    2.02     800    2.19     827    2.36
 6000      591     1.34    626    1.48     660    1.65     693    1.82    724     1.98    754     2.14    782     2.30    809    2.46     834    2.62     860    2.79
 6600      643     1.75    675    1.90     706    2.07     738    2.26    767     2.45    795     2.62    823     2.80    849    2.98     873    3.15     897    3.33
 7200      696     2.24    725    2.40     754    2.58     783    2.77    811     2.99    838     3.19    864     3.38    889    3.57     913    3.76     937    3.95
                                                     Available External Static Pressure (Inches of Water)
              1.10           1.20            1.30            1.40         1.50        1.60                   1.70            1.80            1.90            2.00
  cfm      rpm bhp        rpm bhp         rpm bhp         rpm bhp rpm bhp rpm bhp                         rpm bhp         rpm bhp         rpm bhp         rpm bhp
                                                            3-hp Standard Motor. High Static
                 3-hp Standard Motor Drive                                                                               5-hp Oversize Motor, Drive
                                                                    Drive Accessory
 4800      823     2.13    849    2.29  874 2.44           899    2.60    923     2.76    946     2.91    969     3.07    991     3.23   1012     3.39    1033    3.55
 5400      853     2.53    879    2.70 903(a) 2.88         927    3.05    951     3.22    973     3.40    995     3.57    1017    3.75   1038     3.93    1059    4.11
 6000      886     2.98    910    3.17     934    3.36     957    3.55    980     3.74    1003    3.94   1024     4.13    1045    4.32    1066    4.52    1086    4.71
 6600      920     3.50    944    3.70     967    3.91     990    4.11    1012    4.32    1033    4.53   1054     4.74    1075    4.95     —       —       —       —
 7200      959     4.15    981    4.34    1002    4.53    1024    4.74    1045    4.96     —       —      —        —       —       —       —       —       —       —
Notes:
   1.      For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
   2.      For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
   3.      For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
   4.      Fan motor heat (MBh) = 3.15 x Fan bhp.
   5.      Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
   6.      For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
   7.      Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
           cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
           failure. Our product’s warranty will not be affected.
      8.   Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
           options.
(a)   3-hp Standard Motor and High Static Drive Accessory.
RT-PRC060N-EN                                                                                                                                                              25
Performance Data
Table 10.       Evaporator fan performance - 15 ton cooling only units (model number digit 8 = 3, 4, W) - ECC180 - downflow
                airflow
                                                    Available External Static Pressure (Inches of Water)
             0.10            0.20        0.30         0.40        0.50        0.60                          0.70            0.80        0.90         1.00
 cfm      rpm bhp         rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                        rpm bhp         rpm bhp rpm bhp rpm bhp
                                3-hp Standard Motor, Low Static Drive Accessory                                               3-hp Standard Motor Drive
4800       —       —       —       —      489     0.68    530     0.78    568    0.89     608    1.00     644    1.11     679    1.24     713    1.39     746    1.53
5400       —       —       —       —      517     0.86    558     0.99    594     1.11    628    1.23     663    1.35     697    1.48     729    1.60     760    1.75
6000       —       —      500     0.93    546     1.08    586     1.23    622    1.37     655    1.50     685    1.63     717    1.76     748    1.91     778    2.05
6600      480     0.98    530     1.17    575     1.34    614     1.50    650    1.66     683    1.81     713    1.96     741    2.10     768    2.24     798    2.40
7200      514     1.24    562     1.44    604     1.63    643     1.82    679    1.99     711    2.16     741    2.33     769    2.49     795    2.65     821    2.80
26                                                                                                                                                           RT-PRC060N-EN
                                                                                                                                                  Performance Data
Table 11. Evaporator fan performance - 15 ton cooling only units (model number digit 8 = 3, 4, W) - ECC180 -
          horizontal airflow
                                                     Available External Static Pressure (Inches of Water)
              0.10            0.20        0.30         0.40         0.50                       0.60            0.70             0.80       0.90      1.00
  cfm      rpm bhp         rpm bhp rpm bhp rpm bhp rpm bhp                                  rpm bhp         rpm bhp          rpm bhp rpm bhp rpm bhp
                           3-hp Standard Motor, Low Static Drive Accessory                                                 3-hp Standard Motor Drive
 4800       —       —      475     0.66     517    0.77     563     0.92    605     1.07    644     1.21    680     1.35    714    1.51     745    1.66     775    1.81
 5400       —       —      512     0.87     552    1.00     589     1.13    631     1.30    669     1.46    705     1.63    738    1.79     770    1.95     799    2.12
 6000      498     0.94    548     1.12     589    1.28     624     1.42    657     1.56    695     1.75    730     1.93    763    2.12     794    2.30     824    2.48
 6600      536     1.21    585     1.41     626    1.60     660     1.76    691     1.91    721     2.06    755     2.27    788    2.48     819    2.68     848    2.88
 7200      575     1.52    623     1.75     662    1.96     697     2.15    727     2.32    755     2.49    782     2.65    814    2.87     844    3.10     873    3.32
RT-PRC060N-EN                                                                                                                                                              27
Performance Data
Table 12.         Evaporator fan performance - 17.5 ton unit with gas heat - GCC210 - downflow airflow
                                                      Available External Static Pressure (Inches of Water)
              0.10         0.20         0.30         0.40        0.50                           0.60           0.70        0.80        0.90                   1.00
  cfm      rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                           rpm bhp        rpm bhp rpm bhp rpm bhp                        rpm bhp
                  5-hp Standard Motor, Low Static Drive Accessory                                                5-hp Standard Motor Drive
 5600      554     1.06    592     1.21     627    1.34     658     1.47    693     1.63     725    1.77    755     1.92    783    2.07     811    2.22     837     2.37
 6300      613     1.46    649     1.63     681    1.79     711     1.94    739     2.09     769    2.26    799     2.43    826    2.59     853    2.75     878     2.92
 7000      673     1.96    706     2.15     737    2.33     765     2.51    792     2.67     817    2.84    844     3.02    871    3.21     897    3.39     921     3.58
 7700      733     2.57    764     2.78     794    2.98     820     3.18    846     3.37     870    3.55    893     3.73    916    3.92     941    4.13     965     4.34
 8400      794     3.29    823     3.52     851    3.75     877     3.96    901     4.17     924    4.38    946     4.58    967    4.78     987    4.97 1011(a) 5.20
                                                                                           5-hp Standard Motor, High Static Drive Accessory
                                                     Available External Static Pressure (Inches of Water)
              1.10           1.20             1.30        1.40      1.50                       1.60           1.70        1.80         1.90         2.00
  cfm      rpm bhp        rpm bhp          rpm bhp rpm bhp rpm bhp                          rpm bhp        rpm bhp rpm bhp rpm bhp rpm bhp
                                          5-hp Standard Motor Drive                                        5-hp Standard Motor, High Static Drive Accessory
 5600      862     2.52    886    2.67     909    2.81     931    2.96     953     3.11     976    3.30    998     3.48    1019    3.67    1040    3.86    1061    4.05
 6300      903     3.09    926    3.26     949    3.43     971    3.60     992     3.76     1013   3.93    1033    4.10    1053    4.26    1072    4.43    1093    4.64
 7000      945     3.75    968    3.94     990    4.13    1012    4.32     1033    4.51     1053   4.70    1073    4.88    1093    5.07    1112    5.25    1130    5.44
 7700      989     4.54   1011    4.74    1033    4.94    1054    5.13     1075    5.34     1095   5.55    1114    5.76    1134    5.97    1152    6.18    1170    6.38
 8400 1033         5.43   1055    5.65    1077    5.87    1097    6.09     1118    6.31     1137   6.52    1156    6.74    1175    6.97    1194    7.20     —       —
                                                                         7.5 - hp Oversized Motor, Drive
Notes:
   1.      For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
   2.      For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
   3.      For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
   4.      Fan motor heat (MBh) = 3.15 x Fan bhp.
   5.      Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
   6.      For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
   7.      Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
           cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
           failure. Our product’s warranty will not be affected.
      8.   Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
           options.
(a)   7.5-hp Oversize Motor and Drive.
28                                                                                                                                                           RT-PRC060N-EN
                                                                                                                                                  Performance Data
Table 13.         Evaporator fan performance - 17.5 ton unit with gas heat - GCC210 - horizontal airflow
                                                     Available External Static Pressure (Inches of Water)
              0.10        0.20        0.30          0.40                       0.50            0.60             0.70       0.80      0.90                     1.00
  cfm      rpm bhp rpm bhp rpm bhp rpm bhp                                  rpm bhp         rpm bhp          rpm bhp rpm bhp rpm bhp                       rpm bhp
           5-hp Standard Motor, Low Static Drive Accessory                                                 5-hp Standard Motor Drive
 5600      561     1.12    599     1.26     635    1.43     670     1.58    702     1.73    732     1.88    761     2.03    788    2.18     816    2.36     843    2.53
 6300      622     1.56    656     1.71     689    1.88     721     2.07    751     2.24    780     2.41    808     2.58    834    2.74     859    2.91     884    3.08
 7000      684     2.10    714     2.26     745    2.44     774     2.64    803     2.85    830     3.04    857     3.22    882    3.41     906    3.60  930 3.79
 7700      747     2.76    775     2.93     802    3.12     829     3.32    856     3.55    882     3.78    907     3.99    931    4.19     955    4.40 977 (a) 4.61
 8400      810     3.54    836     3.74     860    3.93     886     4.15    910     4.37    935     4.63    959     4.87    982    5.10    1004    5.33    1026    5.55
                                                                                                                                7.5 - hp Oversized Motor, Drive
                                                     Available External Static Pressure (Inches of Water)
              1.10           1.20        1.30        1.40                     1.50            1.60        1.70         1.80          1.90       2.00
  cfm      rpm bhp        rpm bhp rpm bhp rpm bhp                          rpm bhp         rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
                               5-hp Standard Motor Drive                                         5-hp Standard Motor, High Static Drive Accessory
 5600      869     2.71    894    2.89     919    3.07     942    3.25     965     3.43    988     3.61    1010    3.79    1031    3.98    1052    4.16    1073    4.35
 6300      909     3.28    933    3.48     956    3.68     979    3.88     1001    4.08    1023    4.28    1045    4.48    1066    4.69    1086    4.89    1106    5.09
 7000      952     3.97    974    4.16     996    4.37    1019    4.59     1041    4.81    1062    5.03    1082    5.25    1102    5.48    1122    5.70    1142    5.93
 7700      999     4.81   1021    5.02    1041    5.23    1061    5.43     1081    5.64    1102    5.88    1122    6.12    1142    6.37    1161    6.61    1180    6.85
 8400 1047         5.78   1068    6.01    1088    6.23    1108    6.45     1127    6.68    1146    6.90    1164    7.13    1182    7.35      —      —       —       —
                                                                         7.5 - hp Oversized Motor, Drive
Notes:
   1.      For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
   2.      For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
   3.      For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
   4.      Fan motor heat (MBh) = 3.15 x Fan bhp.
   5.      Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
   6.      For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
   7.      Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
           cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
           failure. Our product’s warranty will not be affected.
      8.   Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
           options.
(a)   5-hp Oversize Motor and Drive.
RT-PRC060N-EN                                                                                                                                                              29
Performance Data
Table 14.       Evaporator fan performance - 17.5 ton cooling only units (model number digit 8 = 3, 4, W) - ECC210 -
                downflow airflow
                                                   Available External Static Pressure (Inches of Water)
             0.10           0.20        0.30         0.40        0.50        0.60                           0.70           0.80        0.90         1.00
 cfm      rpm bhp        rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                         rpm bhp        rpm bhp rpm bhp rpm bhp
                               5-hp Standard Motor, Low Static Drive Accessory                                               5-hp Standard Motor Drive
5600       —       —       —       —       —      —       572    1.08    608     1.21    641     1.33    675     1.46    709    1.59     740    1.72     771    1.85
6300       —       —       —       —      566    1.23     606    1.38    642     1.53    674     1.68    705     1.81    733    1.95     764    2.10     794    2.25
7000       —       —      559    1.38     601    1.56     640    1.74    676     1.91    708     2.07    738     2.24    766    2.39     792    2.54     818    2.69
7700      551     1.52    597    1.74     638    1.95     675    2.15    710     2.35    742     2.53    771     2.71    799    2.89     825    3.07     850    3.24
8400      593     1.93    636    2.17     675    2.41     711    2.63    744     2.85    776     3.06    805     3.26    833    3.46     859    3.65     883    3.85
30                                                                                                                                                          RT-PRC060N-EN
                                                                                                                                                  Performance Data
Table 15.        Evaporator fan performance - 17.5 ton cooling only units (model number digit 8 = 3, 4, W) - ECC210 -
                 horizontal airflow
                                                    Available External Static Pressure (Inches of Water)
              0.10           0.20        0.30        0.40         0.50    0.60                               0.70             0.80       0.90      1.00
  cfm      rpm bhp        rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                         rpm bhp          rpm bhp rpm bhp rpm bhp
                          5-hp Standard Motor, Low Static Drive Accessory                                                5-hp Standard Motor Drive
 5600       —       —      529    0.97     569    1.11     605    1.24    645     1.41    683     1.58    719     1.75    752    1.92     783    2.09     813    2.27
 6300       —       —      573    1.29     613    1.46     647    1.61    679     1.75    714     1.94    749     2.14    782    2.33     813    2.52     842    2.72
 7000      571     1.45    617    1.67     657    1.87     691    2.05    721     2.21    749     2.37    780     2.57    813    2.79     843    3.01     872    3.22
 7700      617     1.87    663    2.13     701    2.35     735    2.57    764     2.76    792     2.94    818     3.11    844    3.30     874    3.55     903    3.79
 8400      664     2.37    709    2.67     745    2.92     778    3.16    809     3.39    835     3.59    860     3.79    884    3.98     907    4.17     934    4.42
RT-PRC060N-EN                                                                                                                                                              31
Performance Data
Table 16.         Evaporator fan performance - 20 ton unit with gas heat - GCC240 - downflow airflow
                                                    Available External Static Pressure (Inches of Water)
              0.10           0.20        0.30         0.40        0.50        0.60                              0.70             0.80        0.90         1.00
  cfm      rpm bhp        rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                            rpm bhp          rpm bhp rpm bhp rpm bhp
                                5-hp Standard Motor, Low Static Drive Accessory                                                    5-hp Standard Motor Drive
 6400      621     1.53    657    1.70     689    1.86     719    2.02    746      2.17     776     2.34     805     2.51     833     2.67     859     2.84     884     3.00
 7200      690     2.12    723    2.32     753    2.51     781    2.69    807      2.86     832     3.03     857     3.21     884     3.40     909     3.60     934     3.78
 8000      759     2.86    790    3.08     818    3.29     844    3.50    869      3.70     893     3.89     915     4.08     937     4.27     961     4.48     985     4.70
 8800      829     3.76    857    4.00     884    4.24     909    4.47    932      4.69     955     4.91     976     5.12     997     5.33     1017    5.54     1037    5.75
 9600      899     4.83 925(a) 5.10 950(a) 5.36 974(a) 5.61               997 5.86 1018 6.10 1039 6.34                        1059    6.58     1078    6.81     1097    7.03
                                                                            7.5-hp Oversized Motor and Drive
                                                     Available External Static Pressure (Inches of Water)
              1.10           1.20            1.30             1.40             1.50             1.60             1.70             1.80         1.90        2.00
  cfm      rpm bhp        rpm bhp         rpm bhp          rpm bhp          rpm bhp          rpm bhp          rpm bhp          rpm bhp rpm bhp rpm bhp
                                                                                                                                 5-hp Standard Motor, High Static
                                                 5-hp Standard Motor Drive
                                                                                                                                         Drive Accessory
 6400      909     3.18    932    3.35     955    3.52     977     3.70     998      3.87    1019     4.03    1039     4.20    1059     4.37    1078     4.54    1097     4.73
                                                                                             1065
 7200      957     3.97    980    4.15    1002    4.34    1024     4.54    1045      4.74     (b)     4.93    1085     5.12    1104     5.32    1123     5.51    1142     5.70
 8000 1008         4.91   1030    5.12    1052    5.32    1073     5.53     1093     5.73    1113     5.95    1132     6.17    1151     6.38    1170     6.60    1188     6.82
 8800 1059         5.99   1081    6.23    1102    6.46     1123    6.69     1143     6.92    1162     7.15    1181     7.37    1199     7.59     —        —       —        —
 9600      1115    7.26   1133    7.49      —      —        —       —      —      —     —     —       —                 —       —        —       —        —       —        —
                                                                     7.5-hp Oversized Motor and Drive
Notes:
   1.      For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
   2.      For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
   3.      For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
   4.      Fan motor heat (MBh) = 3.15 x Fan bhp.
   5.      Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
   6.      For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
   7.      Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
           cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
           failure. Our product’s warranty will not be affected.
      8.   Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
           options.
(a)   Field supplied BK160 x 1.4375" fan sheave, 1VP50 x 1.125" motor sheave, and BX57 belt.
(b)   5-hp Standard Motor and High Static Drive Accessory.
32                                                                                                                                                                 RT-PRC060N-EN
                                                                                                                                                       Performance Data
Table 17.        Evaporator fan performance - 20 ton unit with gas heat (model number digit 10 = L, M, X, Y) - GCC240 -
                 horizontal airflow
                                                 Available External Static Pressure (Inches of Water Gauge)
              0.1             0.2        0.3          0.4          0.5    0.6                                   0.7              0.8        0.9       1
  cfm      rpm bhp        rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                            rpm bhp          rpm bhp rpm bhp rpm bhp
                          5-hp Standard Motor, Low Static Drive Accessory                                                   5-hp Standard Motor Drive
 6400      631     1.63    664    1.78     697    1.95     729    2.14     759     2.32     787     2.49     815     2.66     841     2.83     866     3.00     890     3.18
 7200      702     2.28    732    2.44     761    2.62     790    2.83     818     3.04     845     3.24     871     3.43     896     3.62     920     3.82     943     4.01
 8000      774     3.08    801    3.26     827    3.45     853    3.66     879     3.89     905     4.13     929     4.35     953     4.57     976     4.78     998     5.00
 8800  846 4.05 871 4.26 894 4.45 919 4.68 942 4.90 966 5.17 989                                                     5.43     1012    5.68     1034    5.92     1055    6.15
 9600 918(a) 5.22 941(a) 5.44 963(a) 5.66 985(a) 5.88 1007 6.13 1029 6.38 1051                                       6.67     1072    6.95     1093    7.24     1114    7.50
                                                     7.5 - hp Oversized Motor, Drive
                                                 Available External Static Pressure (Inches of Water Gauge)
              1.1            1.2             1.3              1.4              1.5              1.6              1.7               1.8          1.9         2
  cfm      rpm bhp        rpm bhp         rpm bhp          rpm bhp          rpm bhp          rpm bhp          rpm bhp          rpm bhp rpm bhp rpm bhp
                                                                                                                                 5-hp Standard Motor, High Static
                                                  5-hp Standard Motor Drive
                                                                                                                                         Drive Accessory
 6400      914     3.36    939    3.57     962    3.77     985     3.97     1007     4.18    1029     4.38    1050     4.59    1071     4.79    1091     5.00    1111     5.21
 7200      966     4.20    987    4.39    1008    4.59    1030     4.81     1052     5.04    1073     5.26    1093     5.49    1113     5.72    1133     5.95    1152     6.18
 8000 1020         5.21   1041    5.42    1061    5.64    1081     5.85     1101     6.07    1120     6.28    1139     6.52    1159     6.78    1178     7.03    1197     7.28
 8800 1076         6.39   1096    6.63    1116    6.87     1135    7.10     1154     7.33     —        —       —        —       —        —       —        —       —        —
 9600       —       —       —       —       —      —        —       —          —     —      —      —     —              —       —        —       —        —       —        —
                                                                         7.5 - hp Oversized Motor, Drive
Notes:
   1.      For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
   2.      For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
   3.      For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
   4.      Fan motor heat (MBh) = 3.15 x Fan bhp.
   5.      Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
   6.      For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
   7.      Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
           cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
           failure. Our product’s warranty will not be affected.
      8.   Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
           options.
(a)   Field supplied BK160 x 1.4375" fan sheave, 1VP50 x 1.125" motor sheave, and BX57 belt.
RT-PRC060N-EN                                                                                                                                                                    33
Performance Data
Table 18.        Evaporator fan performance - 20 ton unit with gas heat (model number digit 10 = H, Z) - GCC240 - horizontal
                 airflow
                                                 Available External Static Pressure (Inches of Water Gauge)
              0.1             0.2        0.3          0.4          0.5    0.6                                   0.7              0.8        0.9       1
  cfm      rpm bhp        rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                            rpm bhp          rpm bhp rpm bhp rpm bhp
                          5-hp Standard Motor, Low Static Drive Accessory                                                   5-hp Standard Motor Drive
 6400       —       —       —       —       —      —       —       —       —       —        787     2.49     815     2.66     841     2.83     866     3.00     890     3.18
 7200       —       —       —       —      761    2.62     790    2.83     818     3.04     845     3.24     871     3.43     896     3.62     920     3.82     943     4.01
 8000      774     3.08    801    3.26     827    3.45     853    3.66     879     3.89     905     4.13     929     4.35     953     4.57     976     4.78     998     5.00
 8800  846 4.05 871 4.26 894 4.45 919 4.68 942 4.90 966 5.17 989                                                     5.43     1012    5.68     1034    5.92     1055    6.15
 9600 918(a) 5.22 941(a) 5.44 963(a) 5.66 985(a) 5.88 1007 6.13 1029 6.38 1051                                       6.67     1072    6.95     1093    7.24     1114    7.50
                                                     7.5 - hp Oversized Motor, Drive
                                                 Available External Static Pressure (Inches of Water Gauge)
              1.1            1.2             1.3              1.4              1.5              1.6              1.7               1.8          1.9         2
  cfm      rpm bhp        rpm bhp         rpm bhp          rpm bhp          rpm bhp          rpm bhp          rpm bhp          rpm bhp rpm bhp rpm bhp
                                                                                                                                 5-hp Standard Motor, High Static
                                                  5-hp Standard Motor Drive
                                                                                                                                         Drive Accessory
 6400      914     3.36    939    3.57     962    3.77     985     3.97     1007     4.18    1029     4.38    1050     4.59    1071     4.79    1091     5.00    1111     5.21
 7200      966     4.20    987    4.39    1008    4.59    1030     4.81     1052     5.04    1073     5.26    1093     5.49    1113     5.72    1133     5.95    1152     6.18
 8000 1020         5.21   1041    5.42    1061    5.64    1081     5.85     1101     6.07    1120     6.28    1139     6.52    1159     6.78    1178     7.03    1197     7.28
 8800 1076         6.39   1096    6.63    1116    6.87     1135    7.10     1154     7.33     —        —       —        —       —        —       —        —       —        —
 9600       —       —       —       —       —      —        —       —          —     —      —      —     —              —       —        —       —        —       —        —
                                                                         7.5 - hp Oversized Motor, Drive
Notes:
   1.      For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
   2.      For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
   3.      For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
   4.      Fan motor heat (MBh) = 3.15 x Fan bhp.
   5.      Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
   6.      For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
   7.      Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
           cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
           failure. Our product’s warranty will not be affected.
      8.   Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
           options.
(a)   Field supplied BK160 x 1.4375" fan sheave, 1VP50 x 1.125" motor sheave, and BX57 belt.
34                                                                                                                                                                 RT-PRC060N-EN
                                                                                                                                                   Performance Data
Table 19.        Evaporator fan performance - 20 ton cooling only units (model number digit 8 = 3, 4, W) - ECC240 - downflow
                 airflow
                                                     Available External Static Pressure (Inches of Water)
              0.10            0.20        0.30         0.40        0.50        0.60                          0.70            0.80        0.90         1.00
  cfm      rpm bhp         rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                        rpm bhp         rpm bhp rpm bhp rpm bhp
                                 5-hp Standard Motor, Low Static Drive Accessory                                               5-hp Standard Motor Drive
 6400       —       —       —       —      571     1.28    611     1.43    647    1.58     679    1.73     709    1.87     738    2.01     767    2.16     797    2.31
 7200       —       —      570     1.48    612     1.67    650     1.85    685    2.03     718    2.20     747    2.37     775    2.53     801    2.69     827    2.84
 8000      569     1.69    614     1.92    653     2.14    690     2.35    724    2.55     756    2.75     786    2.94     813    3.13     839    3.31     864    3.49
 8800      617     2.19    658     2.45    697     2.70    731     2.93    764    3.16     795    3.39     825    3.60     852    3.81     878    4.02  902 4.23
                                                                                                                                                       942(a)
 9600      665     2.79    704     3.07    740     3.35    774     3.61    805    3.86     835    4.12     864    4.36     891    4.60     917    4.83   (b)  5.06
RT-PRC060N-EN                                                                                                                                                             35
Performance Data
Table 20.        Evaporator fan performance - 20 ton cooling only units (model number digit 8 = 3, 4, W) - ECC240 -
                 horizontal airflow
                                                     Available External Static Pressure (Inches of Water)
              0.10        0.20         0.30        0.40        0.50                           0.60             0.70        0.80        0.90                       1.00
  cfm      rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                         rpm bhp          rpm bhp rpm bhp rpm bhp                            rpm bhp
                 5-hp Standard Motor, Low Static Drive Accessory                                                 5-hp Standard Motor Drive
 6400       —       —      579    1.34     620    1.51     653    1.67    685     1.81     719     1.99     754     2.19     786     2.39     817     2.59     847    2.78
 7200      584     1.56    630    1.79     669    2.00     703    2.19    733     2.36     761     2.53     789     2.70     821     2.93     852     3.16     881    3.38
 8000      637     2.07    683    2.35     719    2.59     753    2.81    783     3.02     810     3.21     836     3.39     860     3.57     888     3.80     916    4.05
 8800      691     2.69    736    3.01     771    3.28     803    3.53    834     3.78     860     4.00  885 4.21 909 4.42 931 4.62              953                  4.82
 9600      746     3.42    787    3.78     823    4.09     854    4.38    883     4.65     911     4.92 935(a) 5.16 958(a) 5.40 980(a) 5.62 1001                      5.84
                                                                                                                  7.5-hp Oversized Motor and Drive
                                                     Available External Static Pressure (Inches of Water)
              1.10            1.20       1.30       1.40                       1.50            1.60       1.70          1.80         1.90                         2.00
  cfm      rpm bhp         rpm bhp rpm bhp rpm bhp                          rpm bhp         rpm bhp rpm bhp rpm bhp rpm bhp                                    rpm bhp
                          5-hp Standard Motor Drive                                        5-hp Standard Motor, High Static Drive Accessory
 6400      875     2.98    902    3.17     928    3.37     952     3.58     977     3.78    1000     3.98    1023     4.19    1045     4.39    1066     4.60   1087   4.80
 7200      909     3.60    935    3.82     961    4.04     986     4.26    1010     4.47    1033     4.70    1056     4.93    1078     5.16    1099     5.39   1120   5.62
 8000      944     4.30    970    4.55     995    4.80    1020     5.04    1044     5.29    1067     5.53    1089     5.77    1111     6.01    1133     6.25   1153   6.51
 8800      979     5.08   1005    5.36    1030    5.64    1055     5.92    1078     6.19    1101     6.46    1123     6.73    1145     7.00    1166     7.26    —      —
 9600 1022         6.06   1042    6.28    1066    6.57    1090     6.88 1113 7.18 1136 7.48            —               —       —        —       —        —      —      —
                                                                      7.5-hp Oversized Motor and Drive
Notes:
   1.      For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
   2.      For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
   3.      For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
   4.      Fan motor heat (MBh) = 3.15 x Fan bhp.
   5.      Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
   6.      For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
   7.      Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
           cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
           failure. Our product’s warranty will not be affected.
      8.   Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
           options.
(a)   Field supplied BK160 x 1.4375" fan sheave, 1VP50 x 1.125" motor sheave, and BX57 belt.
36                                                                                                                                                              RT-PRC060N-EN
                                                                                                                                                  Performance Data
Table 21.         Evaporator fan performance - 25 ton unit with gas heat - GCC300 - downflow airflow
                                                     Available External Static Pressure (Inches of Water)
              0.10            0.20            0.30            0.40            0.50           0.60            0.70        0.80         0.90        1.00
  cfm      rpm bhp         rpm bhp         rpm bhp         rpm bhp         rpm bhp        rpm bhp         rpm bhp rpm bhp rpm bhp rpm bhp
                                                                                                              7.5-hp Standard Motor, Low Static Drive
                             7.5-hp Standard Motor, Field Supplied Drive(a)
                                                                                                                            Accessory
  7000      —       —      706     2.15    737     2.33    765     2.51    792     2.67    817    2.84     844    3.02    871     3.21    897     3.39    921     3.58
  7500      716    2.38    748     2.59    777     2.78    804     2.97    830     3.16    854    3.34     878    3.51    903     3.71    928     3.91    953     4.11
  8000      759    2.86    790     3.08    818     3.29    844     3.50    869     3.70    893    3.89     915    4.08    937     4.27    961     4.48    985     4.70
  8500      803    3.40    832     3.64    859     3.86    885     4.08    909     4.30    931    4.51     953    4.71    974     4.91    995     5.11   1017     5.34
  9000      846    4.01    874     4.26    900     4.50    925     4.74    948     4.97    971    5.19     992    5.41    1012    5.63    1032    5.84   1052     6.05
  9500      890    4.68    917     4.95    942     5.21    966     5.46    989     5.70   1010    5.94    1031    6.18    1051    6.41    1070    6.64   1089     6.86
 10000      934    5.43    960     5.71    984     5.99   1007     6.25   1029     6.51   1050    6.77    1070    7.02    1090    7.27    1109    7.51    1127    7.75
                                                                                          1091
 10500      978    6.25    1003    6.55    1026    6.84   1049     7.12   1070     7.40     (b)   7.67    1110    7.94    1129    8.20    1148    8.46    1166    8.71
                                           1069           1090
 11000 1022        7.16    1046    7.47     (b)    7.78     (b)    8.08    1111    8.37   1131    8.66    1151    8.94    1169    9.21    1187    9.49   1204     9.76
                                                                                      10-hp Oversized Motor and Drive
                                                     Available External Static Pressure (Inches of Water)
              1.10            1.20            1.30            1.40            1.50           1.60       1.70       1.80       1.90                           2.00
  cfm      rpm bhp         rpm bhp         rpm bhp         rpm bhp         rpm bhp        rpm bhp rpm bhp rpm bhp rpm bhp                                 rpm bhp
                                                                                                  7.5-hp Standard Motor Drive
  7000      945    3.75    968     3.94    990     4.13   1012     4.32   1033     4.51   1053    4.70    1073    4.88    1093    5.07    1112    5.25    1130    5.44
  7500      976    4.31    999     4.50    1021    4.69   1042     4.89   1063     5.09   1083    5.30    1103    5.50    1122    5.70    1141    5.90    1159    6.10
  8000     1008    4.91    1030    5.12    1052    5.32   1073     5.53   1093     5.73   1113    5.95    1132    6.17    1151    6.38    1170    6.60    1188    6.82
  8500     1040    5.57    1062    5.79    1083    6.02    1104    6.24   1124     6.46   1143    6.67    1162    6.89    1181    7.12    1200    7.35   1218     7.58
  9000     1072    6.28    1094    6.53    1115    6.77    1135    7.01   1155     7.24   1174    7.48    1193    7.71    1212    7.94    1230    8.16   1248     8.41
  9500     1107    7.08    1127    7.32    1147    7.58    1167    7.84   1187     8.09   1206    8.34    1225    8.59    1243    8.84    1261    9.08   1278     9.32
 10000 1145        7.99    1163    8.22    1180    8.46   1200     8.73   1219     9.00   1238    9.27    1256    9.54    1274    9.80     —       —       —       —
 10500 1183        8.96    1200    9.21    1217    9.46   1233     9.70   1252     9.98     —       —      —       —       —       —       —       —       —       —
 11000 1222        10.0     —       —       —       —       —       —     —     —     —      —      —              —       —       —       —       —       —       —
                                                                     10-hp Oversized Motor and Drive
Notes:
   1.      For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
   2.      For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
   3.      For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
   4.      Fan motor heat (MBh) = 3.15 x Fan bhp.
   5.      Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
   6.      For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
   7.      Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
           cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
           failure. Our product’s warranty will not be affected.
      8.   Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
           options.
(a)   Field supplied BK160 x 1.4375" fan sheave, 1VP44 x 1.125" motor sheave, and BX60 belt.
(b)   Field supplied BK120 x 1.4375" fan sheave, 1VP75 x 1.375" motor sheave, and BX55 belt.
RT-PRC060N-EN                                                                                                                                                              37
Performance Data
Table 22.          Evaporator fan performance - 25 ton unit with gas heat - GCC300 - horizontal airflow
                                                     Available External Static Pressure (Inches of Water)
              0.10         0.20       0.30         0.40           0.50                       0.60        0.70         0.80        0.90        1.00
  cfm      rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                        rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
                   7.5-hp Standard Motor, Field Supplied Drive(a)                              7.5-hp Standard Motor, Low Static Drive Accessory
  7000      —       —      714     2.26    745     2.44    774     2.64    803     2.85    830    3.04     857    3.22    882     3.41    906     3.60    930     3.79
  7500      729     2.56   757     2.73    786     2.92    813     3.12    841     3.34    867    3.55     892    3.76    917     3.96    941     4.16    964     4.36
  8000      774     3.08   801     3.26    827     3.45    853     3.66    879     3.89    905    4.13     929    4.35    953     4.57    976     4.78    998     5.00
  8500      819     3.67   844     3.86    869     4.05    894     4.28    918     4.50    943    4.76     967    5.01    990     5.24    1012    5.47   1033     5.70
  9000      864     4.33   888     4.54    912     4.74    935     4.96    958     5.19    982    5.45    1005    5.72    1027    5.98    1048    6.23   1069     6.47
  9500      909     5.06   932     5.29    955     5.50    977     5.72    999     5.97   1021    6.21    1043    6.50    1065    6.79    1086    7.06    1106    7.32
 10000      954     5.88   977     6.12    998     6.34   1019     6.56   1040     6.82   1061    7.08    1082    7.35    1103    7.66    1123    7.96    1143    8.24
                                                                          1082
 10500 1000         6.78   1021    7.03    1042    7.27   1062     7.50     (b)    7.76   1102    8.03    1122    8.30    1142    8.60    1162    8.92    1181    9.23
           1045            1066            1086
 11000       (b)    7.77    (b)    8.03     (b)    8.28    1105    8.53   1124     8.78   1144    9.07    1162    9.35    1181    9.63    1200    9.96   1219     10.3
                                                                        10 - hp Oversized Motor, Drive
                                                     Available External Static Pressure (Inches of Water)
              1.10            1.20            1.30            1.40            1.50       1.60       1.70       1.80                          1.90            2.00
  cfm      rpm bhp         rpm bhp         rpm bhp         rpm bhp         rpm bhp rpm bhp rpm bhp rpm bhp                                rpm bhp         rpm bhp
                                                                                   7.5-hp Standard Motor Drive
  7000      952     3.97   974     4.16    996     4.37   1019     4.59   1041     4.81   1062    5.03    1082    5.25    1102    5.48    1122    5.70    1142    5.93
  7500      986     4.56   1007    4.76    1028    4.96   1048     5.16   1069     5.39   1090    5.63    1110    5.86    1130    6.10    1150    6.34    1169    6.58
  8000     1020     5.21   1041    5.42    1061    5.64   1081     5.85   1101     6.07   1120    6.28    1139    6.52    1159    6.78    1178    7.03    1197    7.28
  8500     1054     5.93   1075    6.16    1095    6.38    1115    6.61   1134     6.84   1152    7.07    1171    7.29    1188    7.52    1207    7.77   1225     8.04
  9000     1090     6.71   1110    6.96    1130    7.20    1149    7.44   1167     7.68   1186    7.92    1204    8.16    1221    8.40    1239    8.64   1255     8.88
  9500     1126     7.57   1145    7.83    1165    8.09    1183    8.34   1202     8.60   1220    8.85    1237    9.10    1255    9.35    1272    9.61   1288     9.87
 10000 1163         8.52   1182    8.78    1200    9.05   1218     9.32   1237     9.59   1254    9.86     —       —       —       —       —       —       —       —
 10500 1200         9.53   1219    9.82     —       —       —       —       —       —       —       —      —       —       —       —       —       —       —       —
 11000      —       —       —       —       —       —       —       —       —     —      —      —      —           —       —       —       —       —       —       —
                                                                        10 - hp Oversized Motor, Drive
Notes:
   1.      For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
   2.      For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
   3.      For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
   4.      Fan motor heat (MBh) = 3.15 x Fan bhp.
   5.      Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
   6.      For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
   7.      Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
           cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
           failure. Our product’s warranty will not be affected.
      8.   Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
           options.
(a)   Field supplied BK160 x 1.4375" fan sheave, 1VP44 x 1.125" motor sheave, and Bx60 belt.
(b)   Field supplied BK120 x 1.4375" fan sheave, 1VP75 x 1.375" motor sheave, and BX55 belt.
38                                                                                                                                                           RT-PRC060N-EN
                                                                                                                                                  Performance Data
Table 23.         Evaporator fan performance - 25 ton cooling only unit - ECC300 (model number digit 8 = 3, 4, W) - downflow
                  airflow
                                                     Available External Static Pressure (Inches of Water)
              0.10            0.20            0.30            0.40            0.50            0.60           0.70        0.80         0.90        1.00
  cfm      rpm bhp         rpm bhp         rpm bhp         rpm bhp         rpm bhp         rpm bhp        rpm bhp rpm bhp rpm bhp rpm bhp
                                                                                                              7.5-hp Standard Motor, Low Static Drive
                             7.5-hp Standard Motor, Field Supplied Drive(a)
                                                                                                                            Accessory
  7000      —       —       —       —      601     1.56    640     1.74    676     1.91     708    2.07    738    2.24     766    2.39    792     2.54    818     2.69
  7500      —       —      586     1.63    627     1.83    665     2.03    700     2.22     732    2.39    762    2.57     789    2.74    816     2.91    841     3.07
  8000      —       —      614     1.92    653     2.14    690     2.35    724     2.55     756    2.75    786    2.94     813    3.13    839     3.31    864     3.49
  8500      599    1.99    642     2.24    680     2.48    716     2.70    749     2.92     781    3.14    810    3.34     838    3.54    863     3.74    888     3.94
  9000      629    2.33    670     2.60    707     2.85    742     3.09    775     3.33     805    3.56    834    3.79     862    4.00    888     4.21    912     4.43
  9500      659    2.71    698     2.99    735     3.26    769     3.52    800     3.77     830    4.02    859    4.26     886    4.50    912     4.73    937     4.95
 10000      689    3.13    727     3.42    763     3.72    796     3.99    826     4.25     856    4.52    884    4.78     911    5.03    936     5.28    961     5.52
 10500      720    3.59    756     3.90    791     4.21    823     4.50    853     4.78     881    5.06    909    5.34     935    5.61    961     5.87    985     6.13
 11000      750    4.10    786     4.42    819     4.75    850     5.06    880     5.36     908    5.65    934 5.94 960 6.23 985                  6.51   1009     6.79
                                                                                                          7.5-hp Standard Motor Drive
                                                     Available External Static Pressure (Inches of Water)
              1.10            1.20            1.30            1.40            1.50            1.60           1.70        1.80         1.90         2.00
  cfm      rpm bhp         rpm bhp         rpm bhp         rpm bhp         rpm bhp         rpm bhp        rpm bhp rpm bhp rpm bhp rpm bhp
                                                                                                              7.5-hp Standard Motor, High Static Drive
                                        7.5-hp Standard Motor Drive
                                                                                                                            Accessory
  7000      846    2.86    873     3.03    899     3.19    924     3.35    948     3.51     973    3.70    997    3.91     1021   4.12    1044    4.33   1067     4.55
  7500      865    3.23    890     3.41    916     3.59    941     3.77    965     3.94     988    4.11   1011    4.28     1034   4.47    1057    4.69   1079     4.92
  8000      888    3.67     911    3.84    933     4.01    958     4.20    982     4.39    1005    4.58   1028    4.77     1050   4.95    1071    5.14   1092     5.31
  8500      911    4.13    934     4.32    956     4.50    977     4.69    999     4.87    1022    5.08   1045    5.28     1067   5.48    1088    5.68    1109    5.88
  9000      935    4.63    958     4.84    979     5.04   1001     5.23   1021     5.43    1041    5.62   1062    5.83     1084   6.04    1105    6.26    1126    6.47
  9500      960    5.17    982     5.39    1003    5.61   1024     5.82   1044     6.03    1064    6.24   1083    6.44     1102   6.64    1122    6.86    1143    7.09
 10000      984    5.75    1006    5.99    1027    6.22   1048     6.45   1068     6.68    1087    6.90   1106    7.12     1125   7.34    1143    7.55    1161    7.76
 10500 1008        6.38    1031    6.63    1052    6.88   1072     7.12   1092     7.36    1111    7.60   1130    7.84     1148   8.07    1166    8.30    1184    8.53
                                           1076           1096
 11000 1032        7.06    1055    7.32     (b)    7.58     (b)    7.84   1116     8.10    1135    8.35   1154    8.60     1172   8.85    1190    9.10   1207     9.34
                                                                                          10 - hp Oversized Motor, Drive
Notes:
   1.      For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
   2.      For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
   3.      For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
   4.      Fan motor heat (MBh) = 3.15 x Fan bhp.
   5.      Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
   6.      For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
   7.      Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
           cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
           failure. Our product’s warranty will not be affected.
      8.   Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
           options.
(a)   Field supplied BK160 x 1.4375" fan sheave, 1VP44 x 1.125" motor sheave, and Bx60 belt.
(b)   Field supplied BK120 x 1.4375" fan sheave, 1VP75 x 1.375" motor sheave, and BX55 belt.
RT-PRC060N-EN                                                                                                                                                              39
Performance Data
Table 24.           Evaporator fan performance - 25 ton cooling only unit (model number digit 8 = 3, 4, W) - ECC300 - horizontal
                    airflow
                                                      Available External Static Pressure (Inches of Water)
                0.10        0.20         0.30        0.40                      0.50        0.60         0.70        0.80        0.90                           1.00
      cfm   rpm bhp rpm bhp rpm bhp rpm bhp                                 rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp                                         rpm bhp
              7.5-hp Standard Motor, Field Supplied Drive(a)                     7.5-hp Standard Motor, Low Static Drive Accessory
  7000       —        —      617    1.67     657    1.87    691     2.05    721     2.21    749     2.37    780     2.57    813     2.79    843     3.01    872     3.22
  7500       604     1.74    650    1.99     688    2.21    722     2.41    752     2.59    780     2.77    806     2.94    835     3.15    865     3.39    894     3.62
  8000       637     2.07    683    2.35     719    2.59    753     2.81    783     3.02    810     3.21    836     3.39    860     3.57    888     3.80    916     4.05
  8500       671     2.44    716    2.75     751    3.01    784     3.25    815     3.48    841     3.69    866     3.89    890     4.09    913     4.28    939     4.51
  9000       705     2.86    748    3.19     784    3.47    816     3.73    846     3.99    873     4.22    897     4.44    921     4.65    943     4.86    965     5.06
  9500       739     3.32    781    3.68     816    3.98    847     4.27    877     4.54    905     4.80    929     5.04    952     5.27    974     5.49    995     5.71
 10000       773     3.83    814    4.21     849    4.55    880     4.85    908     5.14    935     5.42    961     5.69    983     5.94    1005    6.17  1026 6.41
 10500       807     4.39    847    4.79     882    5.17    912     5.49    940     5.79    966     6.09    992     6.39    1015    6.66    1036    6.92 1057(b) 7.17
                                                                                                                                            1068
 11000       842     5.01    880    5.43     915    5.83    945     6.18    972     6.51    998     6.83    1022    7.14    1046    7.44     (c)    7.72 1088(c) 7.98
                                                                   7.5-hp Standard Motor Drive
                                                      Available External Static Pressure (Inches of Water)
                1.10            1.20            1.30            1.40            1.50            1.60            1.70        1.80         1.90         2.00
      cfm    rpm bhp         rpm bhp         rpm bhp         rpm bhp         rpm bhp         rpm bhp         rpm bhp rpm bhp rpm bhp rpm bhp
                                                                                                                 7.5-hp Standard Motor, High Static Drive
                                           7.5-hp Standard Motor Drive
                                                                                                                               Accessory
  7000       900      3.44    927    3.65     953    3.86    978     4.07   1002     4.29   1025     4.51   1047     4.74   1069     4.96   1091     5.18   1112    5.41
  7500       922      3.86    948    4.09     974    4.32    999     4.54   1023     4.77   1046     4.99   1068     5.23   1090     5.46    1111    5.70   1132    5.94
  8000       944      4.30    970    4.55     995    4.80    1020    5.04   1044     5.29   1067     5.53   1089     5.77    1111    6.01   1133     6.25   1153    6.51
  8500       966      4.78    992    5.05    1017    5.31    1042    5.58   1065     5.84   1088     6.10    1110    6.36   1132     6.62   1153     6.87   1174    7.13
  9000       988      5.29   1014    5.58    1039    5.87    1063    6.15   1087     6.43    1110    6.71   1132     6.98   1153     7.26   1175     7.53   1195    7.81
  9500       1016     5.92   1037    6.15    1062    6.45    1086    6.75    1109    7.05   1131     7.35   1154     7.64   1175     7.94   1196     8.23   1216    8.52
 10000       1046     6.64   1066    6.87    1085    7.09    1108    7.40    1131    7.71   1154     8.03   1175     8.34   1197     8.66   1218     8.97   1238    9.28
 10500 1077(b) 7.41          1096    7.66    1115    7.89    1133    8.13    1154    8.42   1176     8.75   1198     9.08   1219     9.41   1239     9.74    —       —
 11000       1107     8.25   1126    8.51    1145    8.76    1163    9.01 1181 9.26 1198 9.51 1220                   9.87     —      —        —      —       —       —
                                                                         10 - hp Oversized Motor, Drive
Notes:
   1.       For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
   2.       For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
   3.       For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
   4.       Fan motor heat (MBh) = 3.15 x Fan bhp.
   5.       Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
   6.       For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
   7.       Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
            cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
            failure. Our product’s warranty will not be affected.
       8.   Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
            options.
(a)    Field supplied BK160 x 1.4375" fan sheave, 1VP44 x 1.125" motor sheave, and Bx60 belt.
(b)    7.5-hp Standard Motor and High Static Drive Accessory.
(c)    Field supplied BK120 x 1.4375" fan sheave, 1VP75 x 1.375" motor sheave, and BX55 belt.
40                                                                                                                                                            RT-PRC060N-EN
                                                                                                                             Performance Data
Table 26.     Standard motor and low static drive accessory sheave/fan speed (rpm)
                                       6 Turns    5 Turns   4 Turns   3 Turns   2 Turns      1 Turn
  Tons      Unit Model Number                                                                                  Closed
                                        Open       Open      Open      Open      Open        Open
    15         E/G*C180A3,4,W            488       523       558       592        627            662            N/A
   17.5        E/G*C210A3,4,W            560       596       632       668        703            739            N/A
                G*C240A3,4,W             627       672       717       762        806            851            N/A
    20
                E*C240A3,4,W             538       574       609       645        681            717            N/A
                G*C300A3,4,W             838       891       943       995        1048           1100           N/A
    25
                E*C300A3,4,W             729       775       821       866        912            957            N/A
Table 27.     Standard motor and high static drive accessory sheave/fan speed (rpm)
                                       6 Turns    5 Turns   4 Turns   3 Turns   2 Turns      1 Turn
  Tons      Unit Model Number                                                                                  Closed
                                        Open       Open      Open      Open      Open        Open
    15         E/G*C180A3,4,W            886       932       979       1026       1072           1119           N/A
   17.5        E/G*C210A3,4,W            978       1030      1081      1133       1184           1236           N/A
    20         E/G*C240A3,4,W            863       918       974       1029       1085           1141           N/A
    25          E*C300A3,4,W             995       1048      1100      1153       1205           1257           N/A
Table 29.     Static pressure drop through accessories (inches water column)
                                                                              Low Leak
                                                              Standard
                                                                           Economizer with
                                         2 in.      2-in.  Economizer with                               Electric Heater Accessory (kW)(b)
           Unit Model                                                      OA/RA Dampers
 Tons                        cfm       Standard   MERV 13 OA/RA Dampers(a)       (a)
            Number
                                        Filters    Filters
                                                           100%             100%     100%
                                                                  100% RA                               18            36      54       72
                                                            OA               OA       RA
                             4800        0.03       0.10     0.15     0.04      0.19      0.22          0.01          0.01    —         —
           E/G*C180A
                             6000        0.05       0.14     0.20     0.04      0.31      0.34          0.02          0.02    —         —
           (Downflow)
                             7200        0.07       0.17     0.27     0.04      0.45      0.48          0.03          0.03    —         —
  15
                             4800        0.03       0.1      0.15     0.04      0.19      0.22          0.01          0.01    —         —
           E/G*C180A
                             6000        0.05       0.14      0.2     0.04      0.31      0.34          0.02          0.02    —         —
           (Horizontal)
                             7200        0.07       0.17     0.27     0.04      0.45      0.48          0.04          0.04    —         —
                             5600        0.05       0.12     0.18     0.04      0.27      0.29           —            0.03   0.04      0.04
           E/G*C210A
                             7000        0.07       0.16     0.26     0.04      0.42      0.46           —            0.05   0.05      0.06
           (Downflow)
                             8400        0.10       0.20     0.35     0.06      0.61      0.66           —            0.06   0.07      0.09
 17.5
                             5600        0.05       0.12     0.18     0.04      0.27      0.29           —            0.03   0.04      0.04
           E/G*C210A
                             7000        0.07       0.16     0.26     0.04      0.42      0.46           —            0.05   0.06      0.07
           (Horizontal)
                             8400        0.10       0.20     0.35     0.06      0.61      0.66           —            0.07   0.09      0.11
RT-PRC060N-EN                                                                                                                                 41
Performance Data
Table 29.           Static pressure drop through accessories (inches water column) (continued)
                                                                                       Low Leak
                                                                       Standard
                                                                                    Economizer with
                                              2 in.          2-in.  Economizer with                                            Electric Heater Accessory (kW)(b)
                 Unit Model                                                         OA/RA Dampers
      Tons                         cfm      Standard       MERV 13 OA/RA Dampers(a)       (a)
                  Number
                                             Filters        Filters
                                                                    100%             100%     100%
                                                                           100% RA                                             18         36             54          72
                                                                     OA               OA       RA
                                  6400         0.07           0.15           0.22        0.04        0.35       0.38           —          0.04           0.05        0.05
                 E/G*C240A
                                  8000         0.10           0.19           0.32        0.05        0.55       0.60           —          0.05           0.07        0.08
                 (Downflow)
                                  9600         0.17           0.24           0.44        0.07        0.81       0.86           —          0.06           0.08        0.11
       20
                                  6400         0.07           0.15           0.22        0.04        0.35       0.38           —          0.04           0.05        0.06
                 E/G*C240A
                                  8000         0.10           0.19           0.32        0.05        0.55       0.60           —          0.07           0.08        0.10
                 (Horizontal)
                                  9600         0.17           0.24           0.44        0.07        0.81       0.86           —          0.09           0.11        0.14
                                  7000         0.07           0.16           0.26        0.04        0.42       0.46           —          0.05           0.05        0.06
                 E/G*C300A
                                  9000         0.10           0.22           0.40        0.07        0.71       0.75           —          0.06           0.08        0.10
                 (Downflow)
                                  11000        0.17           0.28           0.57        0.10        1.07       1.12           —          0.07           0.10        0.12
       25
                                  7000         0.07           0.16           0.26        0.04        0.42       0.46           —          0.05           0.06        0.07
                 E/G*C300A
                                  9000         0.10           0.22           0.40        0.07        0.71       0.75           —          0.08           0.10        0.12
                 (Horizontal)
                                  11000        0.17           0.28           0.57        0.10        1.07       1.12           —          0.13           0.18        0.23
(a)    OA = Outside Air and RA = Return Air.
(b)    Nominal kW ratings at 240, 480, 600 volts.
42                                                                                                                                                              RT-PRC060N-EN
                                                                                                                                                 Performance Data
Table 32.       Electric heater voltage correction factors (applicable to auxiliary heat capacity)
                Nominal Voltage                                     Distribution Voltage                                       Capacity Multiplier
                                                                               208                                                        0.75
                        240                                                    230                                                        0.92
                                                                               240                                                        1.00
                                                                               380                                                        0.63
                                                                               440                                                        0.84
                        480
                                                                               460                                                        0.94
                                                                               480                                                        1.00
                                                                               540                                                        0.81
                        600                                                    575                                                        0.92
                                                                               600                                                        1.00
RT-PRC060N-EN                                                                                                                                                  43
Controls
Economizer Controls
                      The standard equipment offering is a fixed dry bulb changeover control. In addition, there are two
                      optional controls, Reference Enthalpy Control and Comparative Enthalpy Control.
Remote Potentiometer
                      Minimum position setting of economizer can be remotely adjusted with this accessory.
Thermostats
        Model #            Type          Stages          Display Type           Features
TCONT302AS42DA Programmable 4H/2C Touchscreen Common preferred, not required 2/ 2 AA battery power
TCONT402AN32DA Non-Programmable 3H/2C Backlit Display and Keys Outdoor Temperature Sensor included
BAYSTAT814 Touchscreen 3H/2C Touchscreen Remote access via Pivot Mobile App
BAYSTAT300 Programmable 3H/2C Backlit Display and Keys BACnet MS-TP enabled
44                                                                                                                       RT-PRC060N-EN
Electrical Data
Table 34.        Unit wiring with cooling (no electric heat) or gas heat
                                                                         Standard Indoor Fan Motor                            Oversized Indoor Fan Motor
                    Unit Model           Unit Operating                                    Maximum Fuse Size                                   Maximum Fuse Size
      TONS                                                        Minimum Circuit                                        Minimum Circuit
                     Number              Voltage Range                                     or Maximum Circuit                                  or Maximum Circuit
                                                                    Ampacity(a)                                             Ampacity
                                                                                                Breaker                                             Breaker
                   E/GCC180A3                 208-230                     79                           100                     85                     110
       15          E/GCC180A4                   460                       36                            45                     39                      50
                   E/GCC180AW                   575                       30                           35                      32                     40
                   E/GCC210A3                 208-230                     92                           110                     99                     125
      17.5         E/GCC210A4                   460                       40                           50                      44                     50
                   E/GCC210AW                   575                       33                           40                      36                      45
                   E/GCC240A3                 208-230                     101                          125                     109                    125
       20          E/GCC240A4                   460                       50                           60                      53                      60
                   E/GCC240AW                   575                       39                            50                      42                     50
                   E/GCC300A3                 208-230                     133                          175                     140                    175
       25          E/GCC300A4                   460                        58                           70                      61                     70
                   E/GCC300AW                   575                        46                           60                      48                     60
(a)   For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.
Table 35.        Unit wiring with electric heat (single point connection)
                                                                                                    Standard Indoor Motor              Oversized Indoor Motor
                    Unit Model         Heater Model         Heater kW           Control                      Max Fuse Size                        Max Fuse Size
      Tons
                     Number              Number              Rating             Stages         MCA           or Max Circuit           MCA         or Max Circuit
                                                                                                                Breaker                             Breaker(a)
                                                                        208/230 Volts Three Phase
                                       BAYHTFB318A            13.5/18            1             79                  100                 85              110
       15           ECC180A3           BAYHTFC336A             27/36             2         108/122               110/125             115/130         125/150
                                       BAYHTFC354A            40.5/54            2         155/144                 175               162/151           175
                                       BAYHTFC336A             27/36             2          115/130              125/150             125/139         125/150
      17.5          ECC210A3           BAYHTFC354A            40.5/54            2         162/151                 175               172/161           175
                                       BAYHTFC372A             54/72             2         172/195               200/225             181/204         200/225
                                       BAYHTFD336A             27/36             2          115/130              125/150             125/139         125/150
       20           ECC240A3           BAYHTFD354A            40.5/54            2         162/151                 175               172/161           175
                                       BAYHTFD372A             54/72             2         172/195               200/225             181/204         200/225
                                       BAYHTFD336A             27/36             2         133/139                 175               140/147           175
       25           ECC300A3           BAYHTFD354A            40.5/54            2         172/161                 175               180/169         200/175
                                       BAYHTFD372A             54/72             2         181/204               200/225             189/212         200/225
                                                                          460 Volts Three Phase
                                       BAYHTFB418A               18              1            36                    45                39                50
       15           ECC180A4           BAYHTFC436A               36              2            61                    70                64                70
                                       BAYHTFC454A               54              2            72                    90                75                90
                                       BAYHTFC436A               36              2            64                    70                68                70
      17.5          ECC210A4           BAYHTFC454A               54              2            75                    90                79                90
                                       BAYHTFC472A               72              2            97                   110                101              110
                                       BAYHTFD436A               36              2            64                    70                68                70
       20           ECC240F4           BAYHTFD454A               54              2            75                    90                79                90
                                       BAYHTFD472A               72              2            97                   110                101              110
                                       BAYHTFD436A               36              2            68                    70                72                80
       25           ECC300A4           BAYHTFD454A               54              2            79                    90                83                90
                                       BAYHTFD472A               72              2            101                  110                105              110
                                                                          575 Volts Three Phase
                                       BAYHTFBW18A               18              1            30                   35                  32              40
       15           ECC180AW           BAYHTFCW36A               36              2            49                   50                  51              60
                                       BAYHTFCW54A               54              2            57                   70                  60              70
                                       BAYHTFCW36A               36              2            51                   60                  55              60
      17.5          ECC210AW           BAYHTFCW54A               54              2            60                   70                  64              70
                                       BAYHTFCW72A               72              2            77                   90                  81              90
                                       BAYHTFDW36A               36              2            51                   60                  55              60
       20           ECC240AW           BAYHTFDW54A               54              2            60                   70                  64              70
                                       BAYHTFDW72A               72              2            77                   90                  81              90
                                       BAYHTFDW36A               36              2            55                   60                  58              60
       25           ECC300AW           BAYHTFDW54A               54              2            64                   70                  66              70
                                       BAYHTFDW72A               72              2            81                   90                  84              90
(a)   Values do not include power exhaust accessory.
RT-PRC060N-EN                                                                                                                                                      45
Electrical Data
46                                                                                                                                                                     RT-PRC060N-EN
Jobsite Connections
                Table 40.    Typical number of wires
Thermostats
A N/A
                                                                     DISCONNECT
                                                                       SWITCH
                                                                     (BY OTHERS)
                                                               A
                          THERMOSTAT
                                                                                             ROOFTOP
                                                                                               UNIT
                Notes:
                         •   For specific wiring information, see the installation instructions.
                         •   All wiring except power wire is low voltage.
                         •   All customer supplied wiring to be copper and must conform to applicable electrical codes
                             and local electric codes. Wiring shown dotted is to be furnished and installed by the
                             customer.
RT-PRC060N-EN                                                                                                            47
Dimensional Data
Figure 1. Cooling with optional electrical heat — overview (gas/electric)
             CONDENSATE DRAIN
                                                                                    REFRIGERANT GAUGE
             CONNECTION
                                                                                     ACCESS
Figure 2. Cooling with optional electrical heat — front and side views (gas/electric)
                                                                       58 5/8”
                                                 58 5/8”   59 5/16”
                                                                                 39 13/16”
22 7/16”
                                                                                        4 1/2”
       50 7/8”
             82 1/4”                                                                  7 15/16”
             (G*C UNITS ONLY)
                                                                                             13”
                     123 1/8”
 NOTES:
 1.THROUGH THE BASE GAS AND ELECTRICAL IS NOT STANDARD ON ALL UNITS.
 2.VERIFY WEIGHT, CONNECTION, AND ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION.
48                                                                                                      RT-PRC060N-EN
                                                                                                              Dimensional Data
Figure 3. Cooling with optional electrical heat units— plain view (gas/electric)
                                        SUPPLY
                  RETURN
19-7/32"
                                                                                                               72-3/32"
                                                                                                    65-1/32"
73-17/32"
            68-19/32"
                                                                                                               14-21/32"
            6-23/32"                                                  7-23/32"                       7-3/8"
                            14-3/8"              14-3/8"
                                                                                                         THROUGH THE BASE ELECTRICAL
            6-29/32"                  36-3/32"
61-13/32"
                                           74-3/16"                                                  7-9/32"
                                (THRU-THE-BASE GAS-G*C UNITS ONLY)
                                                                 122-29/32"
                  NOTES:
                  1.THROUGH THE BASE GAS AND ELECTRICAL PROVISIONS ARE STANDARD ON ALL UNITS.
                  2.VERIFY WEIGHT, CONNECTIONS, AND ALL OTHER DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSULATION.
Figure 4. Cooling with optional electrical heat units — back view (horizontal configuration) (gas/electric)
                                                                        RETURN
                                                 SUPPLY
                                                    46 11/16”
                        25 11/16”
                                                                        6”
                                                                              5 1/2” 6”
                        26 15/16”                     20 3/16”
82 1/16”
RT-PRC060N-EN                                                                                                                    49
Dimensional Data
                                                                                                                 116 7/8”
                                                                                  1”
                                                                                                                 2969 MM
                                                                                  25 MM
                                                        1 13/16”
                                                        46 MM                                            1”
     1 1/2” (38 MM) PERIMETER                                                                            25 MM
                                                                      22 1/4”
             CURB FLANGE
                                                                      565 MM              23 1/4”
                                                                                                                                     1”
                                                                                          591 MM
                                                                                                                                     25 MM
                                                                                                            28 9/16”
          7 7/6”                                                                                            725 MM
          189 MM
                                                                        69 1/2”
                                                                        1765 MM
14 1/16”
357 MM
                    2”
                    51 MM
                                                                        7 1/2”                                                      81”
                                                                        191 MM                                                      2057 MM
                                                      117 3/16”
                                                      2977 MM
Figure 6. Cooling with optional electrical heat — downflow duct connections—field fabricated (gas/electric)
                                                      1”
                                                      25 MM
                                                                  19 5/16”
                                                                  491 MM
                                73 7/16”                                              1”
                                1865 MM                                               25 MM
                                                                                              26 5/16”
                                                                                              668 MM
                                                                                                                            1”
                                                              66 1/2”                                                       25 MM
                                                              1689 MM
                                                                                                    1”
                                                                                                    25.4 MM
                                                                                                    CURB FLANGE
                                                                                                    LONG SIDES
                                                                                                                      1 1/2”
                                                                                                                      38 MM
                                                                                                                  CURB FLANGE
                                                                                                                  SHORT SIDES
                                                  N
                                              TUR
7 7/16”                                    RE
189 MM
      14 1/16”
      357 MM
                                                                                 LY
                                                                             PP
                                                                         SU
NOTES:
• DUCT FLANGES MOUNT 7-7/16” DOWN INSIDE THE CURB ON THE 1-1½” CURB FLANGES.
• ROOFCURB IS INTENDED FOR DOWNFLOW USE ONLY.
50                                                                                                                                            RT-PRC060N-EN
                                                                                                         Dimensional Data
Figure 7. Cooling with optional electric heat — downflow unit clearance (gas/electric)
                                                             CLEARANCE 36”
                                                             914 MM
                                                                             UNIT OUTLINE
CLEARANCE 68”
1727 MM
                              CLEARANCE FORM
                         TOP OF UNIT 72” MM (1829 MM)
                                        ROOF                    76 1/2”
                                        OPENING                 1943 MM
                                                                                     CLEARANCE 48”
                                                                                     1219 MM
                       81”
                       2057 MM
                CLEARANCE 60”
                1524 MM
Figure 8. Cooling with optional electric heat — barometric relief and economizer (gas/electric)
                                                                                 ECONOMIZER OR
                FAN                                     BAROMETRIC            MOTORIZED DAMPER HOOD
                                                        RELIFE
                                                                                       BAROMETRIC
                                                                                       RELIFE
                                                                        58
                                                          9 3/8”(5 3/8”
                                                          FOR LOW LEAK)
13 5/8”
                            20 3/16”                           18 5/16”
                                                               (20 5/8” FOR LOW LEAK)                       68 3/8”
                                                                                                7 3/4”
                                   5 15/16”
NOTES:
1. VERIFY WEIGHT, CONNECTION AND ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION.
2.BAROMETRIC RELIEF IS FOR USE WITH A DOWNFLOW ECONOMIZER ONLY.
RT-PRC060N-EN                                                                                                                51
Dimensional Data
26 7/8”
24 7/8” 12 13/16”
NOTE:
VERIFY WEIGHT, CONNECTION, AND ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION.
52                                                                                                             RT-PRC060N-EN
Weights
Table 41.         Maximum unit and corner weights (lb) and center of gravity dimensions (in.) cooling with optional electric
                  heat units only
                 Unit Model         Weights (lb)(a) , (b)               Corner Weights(c)                    Center of Gravity (in.)
      Tons
                    No.           Shipping            Net          A          B          C        D         Length             Width
        15        ECC180A            2175             1850       638        477        367       367           56                35
Table 42. Maximum unit and corner weights (lb) and center of gravity dimensions (in.) gas/electric heat units only
               Unit Model         Weights (lb)(a) , (b)                Corner Weights(c)                   Center of Gravity (in.)
      Tons
                  No.
                                 Shipping          Net         A          B          C          D          Length           Width
       15       GCC180A             2339          2013         649       508        398        459            55               37
A B
                                   CENTER OF
                                    GRAVITY
                                     WIDTH
                                                 D                                                                                                C
                                        CENTER OF GRAVITY
Note: To calculate additional weight for accessories, see Accessory net weights table.
RT-PRC060N-EN                                                                                                                                         53
Weights
Barometric relief 40 40 40 40
Oversized Motor
5 HP 2 – – –
7.5 HP – 20 20 –
10 HP – – – 60
Hail Guard                                              43                43                43                 43
Through the Base Electrical                             22                22                22                 22
Disconnect                                              5                 5                 5                  5
High Static Drive Kit(d)                                2                 2                  2                 2
LP Gas Conversion                                       2                 2                  2                 2
Electric Heaters(e) , (f)
54                                                                                                                     RT-PRC060N-EN
Mechanical Specifications
General
                •   Packaged rooftop units cooling, heating capacities, and efficiencies are AHRI Certified within scope
                    of AHRI Standard 340-360 (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial
                    Warm Air Furnaces
                •   Packaged rooftop units are dedicated downflow or horizontal airflow
                •   Operating range between 125°F and 40°F in cooling standard from the factory
                •   Factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check
                    cooling operation, fan and blower rotation, and control sequence before leaving the factory
                •   Colored and numbered wring internal to the unit for simplified identification
                •   Units ETL listed and labeled, classified in accordance UL 1995/C 22.2, 236-15 5th Edition
Standard Features
Casing
                •   Zinc coated, heavy gauge, galvanized steel
                •   Weather-resistant baked enamel finish on phosphatized exterior surfaces
                •   Meets ASTM B117, 672 hour salt spray test
                •   Removable single side maintenance access panels
                •   Lifting handles in maintenance access panels (can be removed and reinstalled by removing no more
                    than three fasteners while providing a water and air tight seal)
                •   Exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2-inch, 1-
                    pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material
                •   Base of unit shall be insulated with 1/2-inch, 1-pound density, foil-faced, glass fiber material
                •   Base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8–inch
                    high downflow supply/return openings to provide an added water integrity precaution, if the
                    condensate drain backs up
                •   Downflow unit’s base pan shall have no penetrations within the perimeter of the curb other than the
                    raised 1 1/8–inch high supply/return openings to provide an added water integrity precaution, if the
                    condensate drain backs up
                •   Base of unit shall have provisions for forklift and crane lifting
Compressors
                •   All units have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps
                •   Suction gas-cooled motor with voltage utilization range of plus or minus 10 percent of unit
                    nameplate voltage
                •   Internal overloads standard with scroll compressors
                •   All models have phase monitors and Low and High Pressure Controls as standard
Controls
                •   Units factory-wired with necessary controls and contactor pressure lugs or terminal block for power
                    wiring
                •   External location available for mounting a fused disconnect device
Crankcase Heaters
                •   Offered as standard on 15 and 20 Ton
                •   Offered as field installed option on 25 Ton
                •   Band heaters provide improved compressor reliability by warming the oil to prevent migration during
                    off-cycles or low ambient conditions.
RT-PRC060N-EN                                                                                                           55
Mechanical Specifications
Filters
                 Two inch standard filters shall be factory supplied on all units.
Indoor Fan
                 •   Belt driven, FC centrifugal fans with adjustable motor sheaves
                 •   Motors thermally protected
                 •   Oversized motors available for high static application
                 •   Indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT)
Outdoor Fans
                 •   Outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical
                     discharge position
                 •   Fan motor(s) shall be permanently lubricated and shall have built-in thermal overload protection
Phase Monitor
                 •   3-phase line monitor module
56                                                                                                         RT-PRC060N-EN
                                                                                            Mechanical Specifications
                 •   Protects against phase loss, phase imbalance and phase reversal indication
                 •   Intended to protect compressors from reverse rotation
                 •   Operating input voltage range of 180–600 Vac
                 •   LED indicators for ON and FAULT
                 •   No field adjustments
                 •   Module will automatically reset from a fault condition
Refrigerant Circuits
                 •   Each refrigerant circuit shall have a fixed orifice, service pressure ports, and refrigerant line filter
                     driers factory installed as standard
                 •   An area shall be provided for replacement suction line driers
Unit Top
                 The top cover shall be double hemmed and gasket sealed to prevent water leakage.
RT-PRC060N-EN                                                                                                                   57
Mechanical Specifications
Electric Heaters
                   •   Electric heat modules shall be available for installation within the basic unit
                   •   Elements shall be constructed of heavy-duty nickel chromium elements internally delta connected
                       for 240 volt, wye connected for 480 and 600 volt
                   •   Each heater package shall have temperature high limiting devices that are equipped with an auto-
                       resetting and a single operation switch operating as line break limits
                   •   Single operation switch shall act as a backup limit control if the auto resetting switch fail to operate
                       appropriately
                   •   All heaters shall be individually fused from the factory, where required, and shall meet all NEC and
                       CEC requirements when properly installed
                   •   Power assemblies shall provide single-point connection
                   •   Electric heat modules shall be UL listed or CSA certified
                   •   If ordering the Through the Base Electrical option with an Electric Heater, the heater must be factory
                       installed.
58                                                                                                              RT-PRC060N-EN
                                                                                           Mechanical Specifications
Oversized Motors
                Oversized motors shall be available for high static applications.
                Note: 10 hp oversized motor is factory installed only.
RT-PRC060N-EN                                                                                                                 59
Mechanical Specifications
Economizer – Horizontal
                 The horizontal economizer shall contain the same features as the downflow economizer with the
                 exception of barometric relief.
Filters
                 Two inch standard filters shall be factory supplied on all units.
Hail Guards
                 Tool-less, hail protection quality coil guards are available for condenser coil protection.
Powered Exhaust
                 The powered exhaust shall provide exhaust of return air, when using an economizer, to maintain better
                 building pressurization.
Remote Potentiometer
                 The minimum position setting of the economizer shall be adjusted with this accessory.
60                                                                                                             RT-PRC060N-EN
                Notes
RT-PRC060N-EN      61
Notes
62      RT-PRC060N-EN
                Notes
RT-PRC060N-EN      63
The AHRI Certified mark indicates Trane U.S. Inc. participation in the AHRI Certification program. For verification of individual certified products, go to
ahridirectory.org.
Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient indoor
environments for commercial and residential applications. For more information, please visit trane. com or
tranetechnologies.com.
Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We
are committed to using environmentally conscious print practices.