Product Catalog

Packaged Rooftop Air Conditioners


Foundation™
Cooling and Gas/Electric
15 to 25 Tons, 60 Hz

December 2022 RT-PRC060N-EN


Introduction
Packaged Rooftop Air Conditioners

Through the years, Trane has designed and developed the most complete line of Packaged Rooftop
products available in the market today.
Trane customers demanded a product that provided exceptional reliability, was easy to install, and was
competitively priced.
Trane listened and is proud to introduce the new Foundation™ Light Commercial rooftop unit. With
Foundation, Trane continues to provide the highest standards in quality and reliability, comfort,
performance, and ease of installation. light commercial products.

Copyright
This document and the information in it are the property of Trane, and may not be used or reproduced in
whole or in part without written permission. Trane reserves the right to revise this publication at any
time, and to make changes to its content without obligation to notify any person of such revision or
change.

Trademarks
All trademarks referenced in this document are the trademarks of their respective owners.

Revision History
• Updated General data tables.
• Updated Evaporator fan performance tables.
• Digit K option removed.
• Minor edits to the document.

©2022 Trane RT-PRC060N-EN


Table of Contents
Features and Benefits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Standard and Optional Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Outstanding Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Variety of Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9

Application Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Barometric Relief . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Clearance Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Complete Coat™ Microchannel Condenser Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Condensate Trap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Heating Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Optional Stainless Steel Heat Exchanger. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Low Ambient Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Unit Pitch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Cooling Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Heating Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Air Delivery Selection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Model Number Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
General Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Gross Cooling Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Evaporator Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Economizer Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
Thermostats . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Jobsite Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Weights . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

RT-PRC060N-EN 3
Table of Contents

Mechanical Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Standard Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Factory Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Factory or Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Field Installed Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

4 RT-PRC060N-EN
Features and Benefits
Foundation™ has features and benefits that make it first class in the light commercial rooftop market.
Designed with input from field contractors and technicians, its convertible airflow and ease of installation
are outstanding.

Standard and Optional Features


Large Foundation

Options(a)

Standard
Factory Installed Field Installed

1-year Limited Parts Warranty X

5-year Limited Compressor Warranty X

5-year Limited Aluminized Heat Exchanger Warranty X

10-year Limited Stainless Steel Heat Exchanger Warranty X

Barometric Relief Damper X X

Belt Drive Motors X

CO2 sensor - Demand Control Ventilation (DCV) X

Colored Connectors and Wiring X

Complete Coat Microchannel Condenser Coil X

Compressor Discharge Temperature Limit (DTL) X

Condensate Overflow Switch X X

Convertible Airflow X(b)

Crankcase Heaters X(c) X(c)

Disconnect Switch X X

Easy Access Low Voltage Connections X

Economizer (Downflow) X X

Electric Heaters X X

Filters X

Hail/Vandal Guards X

High Efficiency Filters (MERV 13) X

High Pressure Control X

High Static Motor Kit(d) X X

Insulation - 1/2-inch, 1-lb Density X

IAQ Dual Sloped and Removable Drain Pans X

Liquid Line Refrigerant Drier X

Low Ambient Cooling X

Low Leak Economizer X X

Low Pressure Control X

Low Static Drive Kit X

Low Voltage Circuit Protection X

LP Conversion Kit X

Manual Outside Air Damper X X

Motorized 2-Position Damper X X

RT-PRC060N-EN 5
Features and Benefits

Large Foundation

Options(a)

Standard
Factory Installed Field Installed

Multi-Speed Indoor Fans X

Multi-Speed Oversized X

Phase Loss/Reversal Monitor X

Powered Exhaust X

Quick Access Panels X

Remote Potentiometer X

Scroll Compressors X

Single Point Power X

Single Side Service X

Standardized Components X

Thermal Expansion Valve X

Through-the-base electrical, gas connection provisions X


(a) Refer to model number description for option availability or contact Product Support.
(b) Foundation units ship in the downflow configuration. A horizontal conversion kit, consisting of two downflow duct covers, is needed to
convert the unit from a downflow to a horizontal airflow configuration
(c) Crankcase heaters are standard on 15 to 20 ton units. Crankcase heaters are a field installed accessory on 25 ton units.
(d) Available on constant volume units only. See Accessories chapter for more information.

Outstanding Standard Features


Colored And Numbered Wiring
Save time and money tracing wires and diagnosing the unit.

Compressors
Foundation™ contains the best compressor technology available to achieve the highest possible
performance. Dual stages from manifold compressors are outstanding for humidity control and part load
cooling conditions.

Controls – Electromechanical
This 24-volt control includes the control transformer and contactor pressure lugs for power wiring.

Convertible Units

6 RT-PRC060N-EN
Features and Benefits

Foundation™ units ship in the downflow configuration. A horizontal conversion kit, consisting of two
downflow duct covers, is needed to convert the unit from a downflow to a horizontal airflow
configuration. Units come complete with horizontal duct flanges so the contractor doesn't have to field
fabricate them. These duct flanges are a time and cost saver. Units also have the ability to fit Trane and
other competitors roof curbs (Carrier). In a matter of minutes, you can go from the Trane configuration to
the Carrier configuration by simply changing the return air opening plate. This design allows for easy
field conversion and eliminates the need for costly adapter curbs.

Crankcase Heaters (15 - 20 Tons)


These band heaters provide improved compressor reliability by warming the oil to prevent migration
during off-cycles or low ambient conditions.

Discharge Line Thermostat


A bi-metal element discharge line thermostats installed as a standard feature on the discharge line of
each compressor. This standard feature provides extra protection to the compressors against high
discharge temperatures in case of loss of charge, extremely high ambient and other conditions which
could drive the discharge temperature higher.

Efficiency
Product efficiencies meet the requirements of ASHRAE 90.1.

Easy Access Low Voltage Terminal Board


Foundation™ Low Voltage Terminal Board is mounted outside the main electrical control cabinet. It is
extremely easy to locate and attach the thermostat control wiring and also test operation of all unit
functions. This is another cost and time saving installation feature.

Insulation
All panels in the evaporator section of the unit have foil-faced, glass fiber insulation. All base panels
have foil-faced, glass fiber insulation. All edges are either captured or sealed to ensure no insulation
fibers get into the airstream.

Frostat™
This switch monitors coil temperature to prevent evaporator icing and protect the compressor.

Heat Exchanger
The cabinet features a tubular heat exchanger in low, medium and high heat capacities – all available
for vertical and horizontal discharge directions. The heat exchanger is fabricated using aluminized steel
burners and corrosion-resistant, aluminized steel tubes as standard on all models. As part of the heat
exchanger assembly, an induced draft blower is used to pull the gas mixture through the burner tubes. A
direct spark ignition system, which doubles as a safety device to prove the flame, is used to ignite the
gas mixture.

Locking Safety Device with Anti-Short Cycle Timer


This device monitors compressor safety switch trips to prevent short cycling, protecting the compressor.
A manual reset is required after a fourth safety switch trip.

Low Ambient Cooling


All Foundation units have cooling capabilities down to 45°F as standard.

Low Voltage Connections


The wiring of the low voltage connections to the unit and the thermostat is as simple as R-R, G-G, Y-Y,
and W-W. This simplified system makes it easy for the installer to wire.

RT-PRC060N-EN 7
Features and Benefits

Microchannel Condenser Coil


Microchannel condensing coils are all-aluminum coils with fully-brazed construction. This design
reduces risk of leaks and provides increased coil rigidity — making them more rugged on the jobsite.
Their flat streamlined tubes with small ports and metallurgical tube-to-fin bond allow for exceptional heat
transfer. Microchannel all-aluminum construction provides several additional benefits:
• Light weight (simplifies coil handling)
• Easy to recycle
• Minimize galvanic corrosion

Motors
All indoor fan motors are belt drive as standard.

Multi-Speed Indoor Fan System


Multi-speed indoor fan system is designed for use in applications for meeting the minimum requirement
of CA Title 24. This system incorporates a multi-speed fan control to change the speed of the fan to 66%
of full airflow based off compressor stages.

Pressure Cutouts
Low and high pressure cutouts are standard on all Foundation™ models.

Phase Monitor
Foundation features a three-phase line monitor module that protects against phase loss, phase reversal
and phase unbalance. It is intended to protect compressors from reverse rotation. It has an operating
input voltage range of 180–600 Vac, and LED indicators for ON and FAULT. There are no field
adjustments and the module will automatically reset from a fault condition.

Quick-Access Panels
Remove three or less screws for access to the standardized internal components and wiring.

Quick-Adjust Fan Motor Mounting Plate


With the quick-adjust slider plate, the belt and sheaves can be quickly adjusted without moving the
mounted fan motor. This results in reduced time spent on routine maintenance.

Single Point Power


A single electrical connection powers the unit and all on-board options.

Single Side Service


Single side service is standard on all units.

8 RT-PRC060N-EN
Features and Benefits

Sloped Drain Pans


Every Foundation™ unit has a non-corrosive, sloped drain pan made of rigid PVC - standard on all units
- that is removable for easy cleaning.

Standardized Components
Components are placed in the same location on all Foundation units. Familiarize yourself with one
Foundation and you are familiar with every Foundation. Due to standardized components throughout
the Foundation line, contractors/owners can stock fewer parts.

Variety of Options
Factory Installed Options
Complete Coat™ Condenser Coil
The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of
different types of heat exchangers. The coating is selected to provide excellent resistance and durability
to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salt air, and corrosive
environments.

Stainless Steel Heat Exchanger


The optional stainless steel heat exchanger is constructed of 409 stainless steel tubes and 439
stainless steel burners. It is resistant to corrosion and oxidation and easy to clean. The high strength to
weight ratio allows for high ventilation rates with gas units and comes standard with a modulating gas
heat option. With this option, a 10-year stainless steel heat exchanger warranty is standard.

Third Side Fork Access


This option adds fork openings on the condenser end of the unit for ease of maneuvering the unit
through narrow openings.

Factory or Field Installed Options


Barometric Relief
Designed to be used on downflow units, barometric relief is an unpowered means of relieving excess
building pressure.

Condensate Overflow Switch


A condensate overflow switch is available to shut the unit down in the event that the condensate drain
becomes clogged. This option protects the unit from water overflowing from the drain pan and entering
the base of the unit.

Disconnect Switch
This accessory can be utilized as a convenient way to stock standard product without a disconnect and
have the ability to use the through the base/disconnect offering. The standard disconnect is non-fused,
3-pole, case molded switch.

Economizer - Downflow
Economizers are equipped with either dry bulb, reference, or comparative enthalpy sensing. These
economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly
installed, they offer valuable energy savings.
Factory-installed economizers save time and ensure proper installation.
Note: Factory-installed economizers require some field set-up.

Electric Heaters
Electric heat modules are available within the basic unit. If ordering the through-the-base electrical
option with an electrical heater, the heater must be factory installed.

RT-PRC060N-EN 9
Features and Benefits

Low Leak Economizer with Fault Detection and Diagnostics - Downflow


This economizer meets the damper leakage requirements for ASHRAE 90.1, IECC, and California Title
24 standards (3 cfm/ft^2 at 1.0 in. w.g. for outside air dampers and 4 cfm/ft^2 for return dampers).
Also, included as required per California Title 24:
• Fault Detection and Diagnostics system - provides detection of economizer faults. Barometric relief
must be field installed with this option.
• Occupant Controlled Smart Thermostat (OCST) Connection - user-provided thermostat allows
remote monitoring of economizer faults, and also provides the capability to receive load shedding
commands from the utility company.

Manual Outside Air Damper


A 0-25 percent manual air damper is available.

Motorized Outside Air Damper


A 0–50 percent motorized outside air dampers is available.

Reference or Comparative Enthalpy


Measures and communicates humidity while maximizing comfort control.

Through-the-Base Electrical Utility Access


An electrical service entrance shall be provided allowing access for both control and main power
connections inside the curb and through the base of the unit. This option will allow for field installation of
liquid-tight conduit and an external field installed disconnect switch.
Factory provided through the base openings simplify wiring and piping. Because these utility openings
frequently minimize the number of roof penetrations, the integrity of roofing materials is enhanced.

Through-the-Base Gas Piping (Gas Heat Units Only)


This option shall have all piping necessary including, black steel, manual gas shut-off valve, elbows, and
union. This assembly will require minor field labor to install.

Field Installed Options


CO2 Sensor - Demand Control Ventilation (DCV)
Demand-controlled ventilation (DCV) is a control strategy that responds to the actual demand (need) for
ventilation by regulating the rate at which the HVAC system brings outdoor air into the building. A CO2
sensor measures the concentration (parts per million, ppm) of CO2 in the air. As the CO2 concentration
changes, the outside air damper modulates to meet the current ventilation needs of the zone. DCV is a
passive system; direct control of the indoor fan is not possible with standard or low leak economizers.
The CO2 sensor kit is available as a field installed accessory.

Crankcase Heaters (25 Tons)


These band heaters provide improved compressor reliability by warming the oil to prevent migration
during off-cycles or low ambient conditions.

Economizer - Horizontal
Economizers are equipped with either dry bulb or reference or comparative enthalpy sensing. These
economizers provide free cooling as the outdoor temperature and/or humidity decreases. Correctly
installed, they offer a valuable energy savings.

High Altitude Kit


While recommended for units applied above 2,000 feet, domestic contractors should consult with local
authority on best practice. High altitude kits contain gas orifices that derate the gas input rate (Btuh/r) by
10%.

Low Leak Economizer with Fault Detection and Diagnostics - Horizontal


This economizer meets the damper leakage requirements for ASHRAE 90.1, IECC, and California Title
24 standards (3 cfm/ft^2 at 1.0 in. w.g. for outside air dampers and 4 cfm/ft^2 for return dampers).

10 RT-PRC060N-EN
Features and Benefits

Also, included as required per California Title 24:


• Fault Detection and Diagnostics system - provides detection of economizer faults. Barometric relief
must be field installed with this option.
• Occupant Controlled Smart Thermostat (OCST) Connection - user-provided thermostat allows
remote monitoring of economizer faults, and also provides the capability to receive load shedding
commands from the utility company.

LP Conversion Kit
Provided for field conversion of gas heat units from natural gas to propane.

Power Exhaust
This option is available on downflow units and provides exhaust of the return air, when using a downflow
economizer, to maintain proper building pressurization. This is an excellent option for relieving most
building overpressurization problems.

Remote Potentiometer
When installed in the economizer control circuitry, this accessory provides a method to remotely adjust
the minimum damper position.

Roof Curbs
Available for downflow units. Only one roof curb for the entire Foundation™ line simplifies curb
selection.

Static Drive Accessories


Available on many models, this high and low static drive accessories extend the capability of the
standard motor. Avoid expensive motors by installing this optimized sheave accessory.

Thermostats
Available in programmable and non-programmable.

Tool-less Hail Guards

Tool-less, hail protection quality coil guards shall be field-installed for condenser coil protection. This
option protects the condenser coil from vandalism and/or hail damage.

Other Benefits
Cabinet Integrity
For added water integrity, Foundation has a raised 1-1/8 inch lip around the supply and return of the
downflow units to prevent water from blowing into the ductwork.

Easy to Install, Service and Maintain


Because today’s owners are very cost-conscious when it comes to service and maintenance,
Foundation was designed with direct input from service contractors. This valuable information helped to
design a product that would get the service technician off the job quicker and save the owner money.
Foundation does this by offering outstanding standard features enhanced by a variety of factory and

RT-PRC060N-EN 11
Features and Benefits

field installed options, multiple control options, rigorously tested proven designs and superior product
and technical support.

Outstanding Flexibility
The Foundation unit has the ability to adapt to specific Carrier WeatherMaker™ models without costly
adapter curbs. This will save contractors money and make the installation an ease.

Rigorous Testing
All of Foundation’s designs were rigorously rain tested at the factory to ensure water integrity.
Foundation units incorporate either a one piece top or the Trane-Tite-Top (T3). Each part of the top
overlaps in such a way that water cannot leak into the unit. These overlapped edges are gasketed and
sealed to ensure superior water integrity.
Actual shipping tests were performed to determine packaging requirements. Units were test shipped
around the country to determine the best packaging. Factory shake and drop tests were used as part of
the package design process to help assure that the unit arrives at the job site in top condition.
Rigging tests include lifting a unit into the air and letting it drop one foot, assuring that the lifting lugs and
rails hold up under stress. For the microchannel coils, the supplier will perform the leak check at 450
psig. The completely assembled refrigerant system is leak tested at a minimum of 225 psig with a
refrigerant and nitrogen mixture.
All parts are inspected at the point of final assembly. Sub-standard parts are identified and rejected
immediately. Every unit receives a 100% unit run test before leaving the production line to make sure it
lives up to rigorous Trane requirements.

Unmatched Support
Trane Sales Representatives are a Support Group that can assist you with:
• Product
• Special Applications
• Application
• Specifications
• Service
• Computer Programs and much more
• Training

12 RT-PRC060N-EN
Application Considerations
Application of this product should be within the cataloged airflow and cooling considerations.

Barometric Relief
This product line offers an optional barometric relief damper for use in conjunction with economizer
option. This accessory consists of gravity dampers which open with increased pressure. As building
pressure increases, the pressure in the unit return air section also increases, opening the dampers and
relieving the conditioned space.
Notes:
• The effectiveness of barometric relief damper during economizing operation is system
related.
• Pressure drop of the return air system should be considered to control building
pressurization.

Clearance Requirements
The recommended clearances identified with unit dimensions should be maintained to ensure adequate
serviceability, maximum capacity and peak operating efficiency. Actual clearances which appear
inadequate should be reviewed with local Trane sales personnel.

Complete Coat™ Microchannel Condenser Coil


The cathodic epoxy type electrodisposition coating is formulated for high edge build to a number of
different types of heat exchangers. The coating is selected to provide excellent resistance and durability
to corrosive effects of alkalies, acids, alcohols, petroleum, seawater, salt air, and corrosive
environments. This coating shall be available on microchannel condenser coils.

Condensate Trap
The evaporator is a draw-through configuration. A trap must be field provided prior to start-up on the
cooling cycle.

Heating Operation
The heat exchanger is manufactured with aluminized steel.
To prevent condensation within the heat exchanger, do not exceed 50 percent outside air or a minimum
mixed air temperature of 40°F.

Optional Stainless Steel Heat Exchanger


The optional stainless steel heat exchanger is manufactured with 409 stainless steel tubes and 439
stainless steel burners. To prevent corrosion and prolong heat exchanger reliability, the minimum mixed
air temperature allowed across the heat exchanger is 40°F. Whenever high outside air or outside
applications exist, this option should be utilized.

Low Ambient Cooling


The Foundation line features low ambient cooling down to 45°F. The following options need to be
included/considered when low ambient applications are required: continuous fan operation, crankcase
heaters, or low pressure bypass timer. Contact your local Trane Representative for more assistance
with low ambient cooling applications.

Unit Pitch
These units have sloped condensate drain pans. Units must be installed level. Any unit slope must be
toward access side of the unit.

RT-PRC060N-EN 13
Selection Procedure
Cooling Capacity
Note: Cooling capacity procedure is the same for cooling (E) and gas/electric (G).
1. Calculate the building’s total and sensible cooling loads for the building at design conditions. Use
the following calculation methods or any other standard accepted method.
Factors used in unit selection:
• Total Cooling Load: 180 MBh
• Sensible Cooling Load: 126 MBh
• Airflow: 6000 cfm
• Electrical Characteristics: 460/60/3
• Summer Design Conditions: Entering Evaporator Coil: 80ºF DB/67ºF WB
• Outdoor Ambient: 95ºF
• External Static Pressure: 0.38 in. wg
• Rooftop – downflow configuration
• Efficiency: 14 SEER
• Accessories: Economizer, Roof Curb, Electric Heat
2. As a starting point, a rough determination must be made of the size of the unit. The final selection
will be made after examining the performance at the given conditions. Divide the total cooling load
by nominal Btuh per ton (12 MBh per ton); then round up to the nearest unit size.
180 MBh / 12 MBh = 15.0 tons
3. Table 10, p. 26 shows that a ECC180A4 has a gross cooling capacity of 187.2 MBh and 143 MBh
sensible capacity at 6000 cfm and 95 DB outdoor ambient with 80 DB, 67 WB air entering the
evaporator.
Find capacity at intermediate conditions not in the table
When the design conditions are between two numbers that are in the capacity table, interpolation is
required to approximate the capacity.
Note: Extrapolation outside of the table conditions is not recommended.
4. In order to select the correct unit which meets the building’s requirements, the fan motor heat must
be deducted from the gross cooling capacity. The amount of heat that the fan motor generates is
dependent on the effort by the motor - cfm and static pressure. To determine the total unit static
pressure you add the external static pressure to the additional static related by the added features:

External Static Duct System 0.38 wg

Standard Filter 2 in. from Table 29, p. 41 0.05 wg

Economizer (100% Return Air) from Table 29, p. 41 0.04 wg

Electric Heater Size 36 kW fromTable 29, p. 41 0.07 wg

Total Static Pressure 0.55 wg

Note: Reference heating capacity section on this page for determination of heater size. No additional static add for gas/heat
exchanger.

Note: The Evaporator Fan Performance Table 10, p. 26 has already accounted for the pressure
drop for standard filters and wet coils (see note below in Table 10, p. 26). Therefore, the
actual total static pressure is 0.55 - 0.05 (from ) = 0.50 wg.
With 6000 cfm and 0.50 wg. Table 10, p. 26 shows 1.37 bhp for this unit. Note below the table is the
formula to calculate fan motor heat.

14 RT-PRC060N-EN
Selection Procedure

3.15 x bhp = MBh

3.15 x 1.37 = 4.32 MBh

Now subtract the fan motor heat from the gross cooling capacity of the unit:
Net Total Cooling Capacity = 187.2 MBh - 4.32 = 182.88 MBh.
Net Sensible Cooling Capacity = 143 MBh - 4.32 = 138.68 MBh.
5. Compare your resulting capacities to the building load. If the performance will not meet the required
load of the building’s total or sensible cooling load, try a selection at the next higher size unit.

Heating Capacity
Note: Heating capacity procedures DIFFER for cooling (E) and gas/electric (G) units.
1. Calculate the building heating load.
2. Size the system heating capacity to match the calculated building heating load. The following are
building heating requirements:
460 volt/3 phase Power Supply
Total heating load of 115.0 MBh
6000 cfm
The electric heat accessory capacities are listed in Table 31, p. 42. From the table, a 36 kW heater
will deliver 122.94 MBh at 480 volts. In order to determine capacity at 460 volts, the heater voltage
correction factor from Table 32, p. 43 must be used. Therefore, 122.94 MBh x 0.94 (voltage
correction factor) = 115.6 MBh.
Gas/electric: Fuel natural gas total heating load of 195 MBh. Table 30, p. 42 shows 250 MBh and
350 MBh input models. The output capacities of these furnaces are 203 MBh and 284 MBh
respectively. The low heat model with 203 MBh output best matches the building requirements.

Air Delivery Selection


Note: Air Delivery procedures is the same for cooling (E) and gas/electric (G) units.
External static pressure drop through the air distribution system has been calculated to be 0.50 inches
of water. From Table 29, p. 41 static pressure drop through the economizer is 0.04 and the 36 kW
heater is 0.07 inches of water (0.38 + 0.04 + 0.07). Enter for a ECC180A4 at 6000 cfm and 0.50 static
pressure. The standard motor with the low static drive accessory at 622 rpm will give the desired airflow
at a rated bhp of 1.37.

RT-PRC060N-EN 15
Model Number Description

Digit 1 — Unit Type Digit 11— Minor Design Sequence Digit 17 — Condenser Coil Protection

E = Packaged Cooling, Electric Heat 0 = Standard Coil


G = Packaged Gas/Electric 4 = CompleteCoat™ Condenser Coil
Digit 12,13 — Service Sequence
Digit 2 — Efficiency Digit 18 — Through The Base Provisions
00 = None
C = Generation C Note: Applicable to Digit 1, E models only
0 = No Through The Base Provisions
Digit 14 — Fresh Air Selection3, 4
Digit 3 — Airflow Configuration A = Through The Base Electric
0 = No Fresh Air Note: Applicable to Digit 1, G models only
C = Convertible
A = Manual Outside Air Damper 0-25% 0 = No Through The Base Provisions
B = Motorized Outside Air Damper 0-50% A = Through The Base Electric
Digit 4, 5, 6 — Nominal Gross Cooling
B = Through The Base Gas1
Capacity (MBh) C = Economizer, Dry Bulb 0-100% without C = Through The Base Electric/Gas
180 = 15 Tons Barometric Relief
210 = 17.5 Tons D = Economizer, Dry Bulb 0-100% with Barometric Digit 19 — Disconnect Switch
240 = 20 Tons Relief1
300 = 25 Tons 0 = No Disconnect
E = Economizer, Reference Enthalpy 0-100%
without Barometric Relief 1 = Unit Mounted Non-Fused Disconnect Switch2
Digit 7 — Major Design Sequence
F = Economizer, Reference Enthalpy 0-100% with Digit 20-24
A = Rev A Barometric Relief1
Not Used
G = Economizer, Comparative Enthalpy 0-100%
Digit 8 — Voltage Selection without Barometric Relief
H = Economizer, Comparative Enthalpy 0-100% Digit 25 — System Monitoring Controls
3 = 208-230/60/3 with Barometric Relief1
4 = 460/60/3 0 = No Monitoring Controls
J = Downflow Low Leak Economizer, Dry Bulb w/o
W = 575/60/3 A = Condensate Drain Pan Overflow Switch
Barometric Relief
Digit 9 — Unit Controls L = Downflow Low Leak Economizer, Reference Digit 26 — System Monitoring Controls
Enthalpy w/o Barometric Relief
E = Electromechanical N = Downflow Low Leak Economizer, Comparative B = Economizer Fault Detection and Diagnostics
Enthalpy w/o Barometric Relief (FDD)5
Digit 10 — Heating Capacity
Digit 15 — Supply Fan/Drive Type/Motor Model Number Notes
Note: Applicable to Digit 1 = E models only Notes:
7 = Multi-Speed Standard Motor 1. Some field set up required.
0 = No Heat 2. Must be ordered with Through the- Base
9 = Multi-Speed Oversized Motor
G = 18 kW Electric Heat Electrical option.
N = 36 kW Electric Heat Digit 16 — Access 3. All Factory Installed Options are Built-to-Order.
P = 54 kW Electric Heat Check order services for estimated
R = 72 kW Electric Heat 0 = Standard Fork Access production cycle.
4. Factory installed economizers only available in
Note: Applicable to Digit 1 = G models only F = Third Side Condenser Fork Access (15-25 Ton)
downflow configuration.
H = Gas Heat - High 5. Fault Detection and Diagnostics (FDD) is
L = Gas Heat - Low available on Low Leak Economizers only.
M = Gas Heat - Medium
X = Gas Heat - SS Ht Ex - Low
Y = Gas Heat - SS Ht Ex - Medium
Z = Gas Heat - SS Ht Ex - High

16 RT-PRC060N-EN
General Data
Table 1. General data — 15 to 25 tons
15 Ton 17.5 Ton 20 Ton 25 Ton
E/GCC180 E/GCC210 E/GCC240 ECC300 GCC300
Cooling Performance(a)
Gross Cooling Capacity 194,000 214,000 252,000 280,000 280,000
EER (Downflow/Horizontal) 11 11 10 10 9.8
Nominal Airflow CFM / AHRI Rated CFM 5400 6650 7000 8000 8000
AHRI Net Cooling Capacity 180,000 206,000 244,000 268,000 268,000
Integrated Energy Efficiency Ratio (IEER) (Multi
14.2 14.2 13.2 13.2 13.2
Speed Fan)

Percent Capacity @ part load (Stage 1/Stage 2) 53 / 100 50 / 100 54 / 100 53 / 100 53 / 100
System Power (kW) 16.36 18.73 24.40 26.80 27.35
Compressor
Number/Type 2 / Scrolls 2 / Scrolls 2 / Scrolls 2 / Scrolls 2 / Scrolls
Sound
Outdoor Sound Rating (BELS) 9.5 9.5 9.5 9.5 9.5
Outdoor Coil
Type Microchannel Microchannel Microchannel Microchannel Microchannel
Coil Width (in.) 0.71 1.00 1.00 1.00 1.00
Face Area (sq. ft.) 34.74 34.74 34.74 34.74 34.74
Rows/FPI 1 / 23 1 / 21 1 / 23 1 / 23 1 / 23
Indoor Coil
Type Microchannel Microchannel Microchannel Microchannel Microchannel
Tube Size (in.) ID 1 1 1 1 1
Face Area (sq. ft.) 26.00 26.00 26.00 26.00 26.00
Rows/FPI 2/18 2/18 2/18 4/15 4/15
Refrigerant Control TXV TXV TXV TXV TXV
1 / 1.00 1 / 1.00 1 / 1.00 1 / 1.00 1 / 1.00
Drain Connection Number/Size (in.)
PVC Pipe Female PVC Pipe Female PVC Pipe Female PVC Pipe Female PVC Pipe Female
Outdoor Fan
Type Propeller Propeller Propeller Propeller Propeller
Number Used/Diameter (in.) 2 / 28 2 / 28 2 / 28 2 / 28 2 / 28
Drive Type/No. Speeds Direct / 1 Direct / 1 Direct / 1 Direct / 1 Direct / 1
cfm 15,900 15,900 15,900 15,900 15,900
Number Motors/hp 2 / 1.0 2 / 1.0 2 / 1.0 2 / 1.0 2 / 1.0
Motor rpm 1125 1125 1125 1125 1125
Indoor Fan
Type FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal FC Centrifugal
Number Used/Diameter (in.) 2 / 15x15 2 / 15x15 2 / 15x15 2 / 15x15 2 / 15x15
Drive Type/No. Speeds Belt / 1 Belt / 1 Belt / 1 Belt / 1 Belt / 1
Number Motors 1 1 1 1 1
Motor hp (Standard/Oversized) 3.0 / 5.0 5.0 / 7.5 5.0 / 7.5 7.5 / 10.0 7.5 / 10.0
Motor rpm (Standard/Oversized) 1750 / 3450 3450 / 3450 3450 / 3450 3450 / 1750 3450 / 1750
Motor Frame Size (Standard/Oversized) 145T / 145T 145T / 184T 145T / 184T 184T / 215T 184T / 215T
Filters
Type Furnished(b) Throwaway Throwaway Throwaway Throwaway Throwaway
Number Size Recommended (8) 20x25x2 (8) 20x25x2 (8) 20x25x2 (8) 20x25x2 (8) 20x25x2
Refrigerant Charge (Pounds of R-410A)(c)
Circuit 1 14.6 15.2 16.5 17.8 17.8
(a) Units are AHRI Certified to AHRI Standard 340-360 (I-P). Rating conditions are 95°F outdoor air temperature, 80°F entering dry bulb, 67°F entering wet bulb with minimum
external static pressure as determined by rating standard.
(b) Optional field-installed MERV 13 filters available.
(c) Refrigerant charge is an approximate value. For a more precise value, see unit nameplate and service instructions.

RT-PRC060N-EN 17
General Data

Table 2. General data — heating performance – 15 to 25 tons


Heating Performance
15 Tons 17.5 Tons(a)
Heating Models Low Medium High Low Medium High (b)
Heating Input (Btu/h) 240,000 320,000 350,000 240,000 320,000 380,000 / 350,000
1st Stage (Btu) 168,000 224,000 245,000 168,000 224,000 266,000 / 245,000
Heating Output (Btu/h) 194,400 259,200 283,500 194,400 259,200 307,800 / 283,500
1st Stage (Btu) 136,080 181,440 198,450 136,080 181,440 215,460 / 198,450
Steady State Efficiency % 81 81 81 81 81 81 / 81
No. Burners 6 8 8 6 8 8/8
No. Stages 2 2 2 2 2 2/2
Gas Supply Line Pressure (in. wc)
5.5/14.0 /
Natural Gas (minimum/maximum) 5.0/14.0 5.0/14.0 4.5/14.0 5.0/14.0 5.0/14.0
4.5/14.0
11.0/14.0 /
LP (minimum/maximum) 11.0/14.0 11.0/14.0 11.0/14.0 11.0/14.0 11.0/14.0
11.0/14.0
Gas Connection Pipe Size (in.) 3/4 3/4 3/4 3/4 3/4 3/4
Heating Performance
20 to 25 Tons
Heating Models Low Medium High
Heating Input (Btu/h) 240,000 320,000 380,000
1st Stage (Btu) 168,000 224,000 266,000
Heating Output (Btu/h) 194,400 259,200 307,800
1st Stage (Btu) 136,080 181,440 215,460
Steady State Efficiency % 81 81 81
No. Burners 6 8 8
No. Stages 2 2 2
Gas Supply Line Pressure (in. wc)

Natural Gas (minimum/maximum) 5.0/14.0 5.0/14.0 5.5/14.0

LP (minimum/maximum) 11.0/14.0 11.0/14.0 11.0/14.0

Gas Connection Pipe Size (in.) 3/4 3/4 3/4


Note: Heating Performance limit settings and rating data were established and approved under
laboratory test conditions using American National Standards Institute standards (ANSI).
Ratings shown are for elevations up to 2000 feet. For elevations above 2000 feet, ratings
should be reduced at the rate of 4% for each 1000 feet above sea level.
(a) For 17.5T high heat option, input rate will de-rate from downflow to horizontal.
(b) Downflow / Horizontal

18 RT-PRC060N-EN
Performance Data
Gross Cooling Capacities
Table 3. Gross cooling capacities 15 tons - E/GCC180A3,4,W
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
85 95 105
Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
Ent
DB (° 61 67 73 61 67 73 61 67 73
CFM F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 166.5 134.8 190.7 107.0 209.9 70.8 158.0 130.5 180.8 102.6 197.5 65.9 149.1 126.0 170.2 97.9 184.3 64.1
80 165.7 157.3 190.1 131.6 210.6 100.2 157.3 152.8 180.4 127.1 198.3 95.4 148.4 148.1 170.0 122.4 184.8 90.1
4800
85 170.6 170.6 189.7 156.5 211.5 126.2 164.0 164.0 180.0 152.1 199.6 121.0 156.8 156.8 169.7 146.2 186.2 115.6
90 181.5 181.5 188.9 178.6 211.4 151.1 174.5 174.5 179.2 173.9 199.4 146.2 166.9 166.9 168.8 168.8 186.1 140.8
75 170.4 143.7 194.9 112.4 213.8 75.6 161.6 136.7 184.4 107.8 200.7 70.6 152.2 129.8 173.3 102.3 186.8 65.4
80 169.2 167.8 194.5 139.8 213.9 104.6 160.5 160.5 184.2 135.2 201.1 99.7 152.5 152.5 173.3 130.3 187.7 94.6
5400
85 178.0 178.0 193.9 164.5 214.9 132.9 170.9 170.9 183.4 161.2 202.1 127.8 163.2 163.2 172.4 156.0 187.8 122.2
90 189.3 189.3 192.4 191.2 214.8 161.2 181.7 181.7 182.3 182.3 202.0 156.1 173.3 173.3 173.5 173.5 187.7 150.5
75 173.5 146.8 198.1 116.8 216.9 77.1 163.8 145.7 187.5 112.1 203.2 71.9 154.0 140.7 176.1 107.1 193.2 68.1
80 172.3 172.3 197.9 147.7 217.1 109.1 165.2 165.2 187.2 143.0 203.9 104.0 157.5 157.5 175.8 138.0 190.1 99.0
6000
85 184.3 184.3 196.5 175.7 217.4 139.7 176.7 176.7 185.7 170.7 203.9 134.5 168.5 168.5 174.2 165.4 190.0 129.1
90 196.0 196.0 196.2 196.2 217.3 171.0 187.7 187.7 187.9 187.9 203.9 165.0 178.2 178.2 178.4 178.4 189.8 153.4
75 175.2 157.9 201.2 121.6 219.5 78.4 165.6 153.0 190.1 116.7 205.2 73.1 155.5 147.9 178.2 111.6 196.4 69.8
80 177.4 177.4 200.6 155.4 219.8 113.4 169.9 169.9 189.5 150.5 206.5 107.4 161.8 161.8 177.7 144.5 191.9 101.8
6600
85 189.8 189.8 198.5 185.0 219.7 146.6 181.7 181.7 187.3 179.9 206.1 141.3 172.9 172.9 175.4 174.5 191.6 135.8
90 201.5 201.5 201.7 201.7 219.4 175.4 192.4 192.4 192.6 192.6 205.0 172.9 181.9 181.9 182.0 182.0 190.3 167.0
75 176.8 164.9 203.5 126.2 221.5 79.7 166.9 159.9 192.0 121.2 206.7 74.3 156.5 154.8 179.8 115.9 199.0 71.3
80 181.9 181.9 202.7 162.8 222.0 116.5 174.1 174.1 191.4 154.6 208.0 111.0 165.5 165.5 178.7 150.2 193.5 105.4
7200
85 194.6 194.6 199.8 194.0 222.0 153.4 186.0 186.0 188.3 188.3 207.8 148.0 176.5 176.5 176.6 176.6 192.8 142.4
90 206.0 206.0 206.2 206.2 220.2 187.2 196.1 196.1 196.3 196.3 206.0 181.5 184.3 184.3 184.4 184.4 190.8 175.5
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
115 120 125
Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
Ent
DB (° 61 67 73 61 67 73 61 67 73
CFM F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 139.5 118.4 158.7 92.9 169.9 58.7 134.4 114.3 152.5 89.7 161.9 55.8 129.0 110.9 146.2 86.9 153.2 52.6
80 139.2 139.2 158.7 117.4 170.9 84.9 135.2 135.2 152.7 114.8 163.3 82.1 130.9 130.9 146.2 111.9 155.3 79.1
4800
85 149.0 149.0 158.3 140.8 171.3 109.8 144.7 144.7 152.2 138.0 163.8 106.9 140.0 140.0 145.6 135.0 155.7 103.8
90 158.3 158.3 158.4 158.4 171.1 135.0 153.3 153.3 153.5 153.5 163.6 132.1 147.8 147.8 147.9 147.9 155.4 128.6
75 141.7 128.1 161.5 97.1 171.4 59.7 136.3 125.3 155.2 94.4 170.4 59.2 130.7 122.5 148.4 91.5 153.7 53.4
80 144.5 144.5 161.4 125.2 173.3 89.1 140.2 140.2 155.1 122.4 165.6 86.4 135.6 135.6 148.3 119.5 157.6 83.7
5400
85 154.6 154.6 160.4 150.5 173.3 116.6 149.8 149.8 153.9 147.5 165.3 113.6 144.6 144.6 147.0 144.4 156.6 110.3
90 163.4 163.4 163.6 163.6 173.1 142.2 157.6 157.6 157.7 157.7 167.8 140.2 150.8 150.8 150.9 150.9 160.6 138.5
75 143.4 135.4 163.7 101.7 180.2 63.3 137.9 132.6 157.1 98.8 163.5 57.6 132.0 129.7 150.1 95.8 154.0 54.3
80 149.1 149.1 163.5 132.7 175.5 92.4 144.5 144.5 156.8 129.2 167.5 89.4 139.5 139.5 149.6 125.8 158.9 86.1
6000
85 159.1 159.1 161.7 159.7 174.6 123.3 153.9 153.9 155.0 155.0 166.2 120.1 148.0 148.0 148.1 148.1 157.2 116.8
90 166.9 166.9 167.0 167.0 173.8 152.2 159.8 159.8 159.9 159.9 169.8 150.5 152.7 152.7 152.8 152.8 162.9 147.8
75 144.7 142.5 165.4 106.1 173.1 61.7 138.9 138.9 158.6 103.1 164.0 58.5 133.0 133.0 151.3 100.0 168.7 59.8
80 152.9 152.9 165.0 135.1 176.7 96.0 148.0 148.0 157.5 135.3 168.4 92.8 142.7 142.7 150.1 132.0 159.7 89.4
6600
85 162.7 162.7 162.8 162.8 179.9 131.3 156.9 156.9 157.0 157.0 173.1 128.7 150.2 150.2 150.3 150.3 157.6 123.1
90 168.7 168.7 168.9 168.9 174.0 160.7 162.2 162.2 162.3 162.3 171.6 159.6 158.6 158.6 158.7 158.7 164.6 156.9
75 145.4 145.4 166.7 110.3 185.1 66.4 140.4 140.4 159.7 107.3 178.0 63.8 135.4 135.4 152.2 104.1 154.9 56.3
80 156.1 156.1 165.2 144.7 177.7 99.3 150.9 150.9 158.0 141.6 169.2 96.1 145.2 145.2 150.3 138.2 160.3 92.6
7200
85 165.4 165.4 165.5 165.5 176.4 136.3 158.9 158.9 159.0 159.0 167.3 132.0 151.4 151.4 151.5 151.5 157.5 128.5
90 171.3 171.3 171.4 171.4 179.9 171.1 168.2 168.2 168.4 168.4 173.0 168.4 163.1 163.1 163.2 163.2 165.9 165.7
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat
formula, refer to appropriate airflow table notes.
2. MBh = Total gross capacity
3. SHC = Sensible heat capacity

RT-PRC060N-EN 19
Performance Data

Table 4. Gross cooling capacities 17.5 tons - E/GCC210A3,4,W


Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
85 95 105
Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
Ent
DB (° 61 67 73 61 67 73 61 67 73
CFM F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 192.3 156.3 219.9 124.4 243.4 83.6 183.0 151.6 208.7 119.4 229.2 81.9 173.1 146.6 196.7 114.1 213.5 75.9
80 190.3 180.4 219.2 152.4 243.6 117.0 181.1 175.4 208.1 147.3 229.6 111.5 171.3 170.1 196.1 142.0 214.1 105.5
5600
85 194.5 194.5 217.7 180.4 243.8 146.3 187.4 187.4 206.9 175.4 230.1 140.4 179.6 179.6 195.1 166.8 215.0 134.3
90 206.5 206.5 215.8 204.0 243.3 174.3 198.9 198.9 204.9 198.6 229.7 168.8 190.5 190.5 193.1 192.9 214.7 162.9
75 196.8 166.2 225.0 130.6 247.4 89.1 187.0 159.9 213.1 125.3 232.4 83.4 176.6 151.5 200.4 120.0 216.9 77.5
80 193.9 191.6 224.0 161.5 247.9 122.1 184.2 184.2 212.3 156.3 233.2 116.4 174.9 174.9 199.7 150.8 217.2 110.4
6300
85 202.6 202.6 222.3 188.1 248.3 154.0 194.9 194.9 210.4 184.7 233.7 148.2 186.4 186.4 197.8 178.8 217.6 142.0
90 215.1 215.1 219.4 217.4 247.6 185.7 206.8 206.8 207.9 207.9 233.2 180.1 197.4 197.4 197.6 197.6 217.4 173.9
75 200.2 170.2 229.0 136.5 250.8 90.6 189.4 167.9 216.7 130.5 235.6 84.9 178.4 162.3 203.5 124.7 219.6 79.0
80 196.5 196.5 227.8 170.3 251.5 127.0 188.8 188.8 215.6 165.0 236.1 121.3 180.5 180.5 202.5 159.3 220.0 115.3
7000
85 209.6 209.6 225.0 200.7 251.7 161.8 201.3 201.3 212.8 194.9 236.5 155.9 192.2 192.2 199.6 188.8 219.8 149.5
90 222.4 222.4 222.6 222.6 250.9 196.9 213.4 213.4 213.6 213.6 236.0 191.1 203.1 203.1 203.3 203.3 219.5 177.8
75 202.0 181.2 232.5 141.3 253.9 92.2 191.3 175.7 219.8 135.8 238.4 86.5 180.0 169.9 206.0 129.9 221.7 80.5
80 202.2 202.2 230.8 178.8 254.5 131.8 194.1 194.1 218.2 173.4 238.9 126.0 185.2 185.2 204.6 167.2 222.4 119.0
7700
85 215.6 215.6 226.9 210.5 254.4 169.4 206.9 206.9 214.3 204.6 238.6 163.4 197.1 197.1 200.7 198.5 221.8 157.0
90 228.7 228.7 228.9 228.9 253.6 203.5 219.0 219.0 219.1 219.1 237.5 198.5 207.7 207.7 207.9 207.9 219.8 191.2
75 203.5 188.6 235.5 146.5 256.8 93.9 192.5 183.0 222.2 140.8 240.7 88.0 180.9 177.2 207.9 134.8 223.5 81.9
80 207.2 207.2 233.2 187.1 257.3 135.9 198.7 198.7 220.2 178.4 241.2 129.6 189.3 189.3 205.5 172.8 224.5 123.3
8400
85 221.0 221.0 228.2 220.0 256.6 176.9 211.6 211.6 215.2 214.1 240.4 170.8 201.2 201.2 201.3 201.3 223.4 164.4
90 234.2 234.2 234.3 234.3 254.5 214.1 223.6 223.6 223.8 223.8 238.0 207.4 211.4 211.4 211.5 211.5 220.1 200.2
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
115 120 125
Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
Ent
DB (° 61 67 73 61 67 73 61 67 73
CFM F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 162.4 140.1 183.4 108.3 197.4 69.8 156.6 134.9 176.1 105.3 188.4 66.6 150.5 130.4 168.3 102.0 178.7 63.0
80 160.7 160.7 183.0 136.2 197.8 99.4 156.0 156.0 175.8 133.1 189.1 96.2 151.1 151.1 168.0 129.7 179.7 92.8
5600
85 170.8 170.8 181.9 162.0 198.0 127.7 165.9 165.9 174.6 158.6 189.4 124.4 160.4 160.4 166.8 155.0 180.0 120.9
90 180.7 180.7 180.9 180.9 197.7 156.3 175.0 175.0 175.2 175.2 189.0 153.0 168.5 168.5 168.6 168.6 179.7 149.2
75 164.8 148.4 186.5 113.4 199.8 71.3 158.7 145.2 178.9 110.1 190.4 67.9 152.2 141.9 170.7 106.6 180.2 64.3
80 166.3 166.3 185.9 144.8 200.6 104.3 161.4 161.4 178.3 141.6 191.6 101.1 156.1 156.1 170.1 138.1 182.0 97.2
6300
85 176.8 176.8 183.9 172.3 200.6 135.5 171.3 171.3 176.3 168.8 191.6 132.1 165.2 165.2 168.0 165.0 181.7 128.5
90 186.4 186.4 186.6 186.6 200.0 165.0 179.9 179.9 180.0 180.0 191.1 156.9 172.3 172.3 172.4 172.4 180.8 157.7
75 166.6 156.2 189.0 118.5 201.7 72.7 160.3 153.0 181.0 115.1 191.9 69.2 153.5 149.6 172.5 111.5 181.4 65.6
80 171.1 171.1 188.1 153.2 203.0 108.5 165.9 165.9 180.2 148.7 193.9 104.8 160.2 160.2 171.8 143.5 183.9 101.1
7000
85 181.7 181.7 185.2 182.1 202.6 143.1 175.7 175.7 177.2 177.2 193.2 139.6 168.8 168.8 168.9 168.9 183.0 135.9
90 190.8 190.8 190.9 190.9 201.1 174.8 183.4 183.4 183.5 183.5 191.6 171.0 175.5 175.5 175.6 175.6 181.3 167.0
75 167.8 163.8 190.9 123.4 203.3 74.0 161.3 160.5 182.6 120.0 202.0 73.4 154.3 154.3 173.8 116.3 182.5 66.8
80 175.2 175.2 189.8 155.5 204.9 112.5 169.7 169.7 181.0 155.3 195.3 108.9 163.5 163.5 172.1 151.3 185.0 105.1
7700
85 185.7 185.7 185.8 185.8 204.2 150.5 179.1 179.1 179.2 179.2 194.5 147.0 171.6 171.6 171.7 171.7 184.1 143.2
90 194.0 194.0 194.1 194.1 201.7 184.0 186.4 186.4 186.5 186.5 191.9 180.2 178.4 178.4 178.5 178.5 181.3 176.1
75 168.5 168.5 192.3 128.2 204.6 75.3 162.1 162.1 183.9 124.7 204.3 75.0 156.4 156.4 174.8 121.0 183.5 68.2
80 178.8 178.8 190.0 165.8 206.4 116.5 172.8 172.8 181.4 162.1 196.5 112.9 166.2 166.2 172.3 158.0 185.9 109.0
8400
85 188.9 188.9 189.0 189.0 205.4 157.9 181.8 181.8 181.8 181.8 195.6 153.3 173.6 173.6 173.7 173.7 184.9 144.8
90 196.8 196.8 196.9 196.9 201.9 193.0 189.3 189.3 189.4 189.4 191.9 189.1 180.6 180.6 180.6 180.6 181.2 181.2
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat
formula, refer to appropriate airflow table notes.
2. MBh = Total gross capacity
3. SHC = Sensible heat capacity

20 RT-PRC060N-EN
Performance Data

Table 5. Gross cooling capacities 20 tons - E/GCC240A3,4,W


Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
85 95 105
Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
Ent
DB (° 61 67 73 61 67 73 61 67 73
CFM F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 231.8 181.2 262.2 145.9 288.6 100.1 220.1 175.0 248.1 139.4 270.5 93.6 207.4 168.4 232.6 132.4 251.6 90.5
80 229.5 203.7 261.5 176.3 288.7 137.2 217.6 201.1 247.8 169.7 270.9 130.0 204.9 193.9 232.4 162.6 251.5 122.3
6400
85 226.8 226.8 260.1 206.3 288.8 168.9 218.1 218.1 246.3 199.8 271.3 161.8 208.5 208.5 231.2 192.8 251.9 154.0
90 239.8 239.8 257.7 232.5 288.6 199.1 230.7 230.7 244.0 225.3 271.2 191.8 220.3 220.3 228.9 217.6 251.7 183.9
75 237.4 191.6 268.5 152.6 293.6 107.1 224.9 185.2 253.4 145.7 274.7 99.6 211.4 178.3 236.7 138.4 255.4 92.1
80 233.6 219.4 267.9 186.0 294.0 142.6 221.3 212.4 252.8 179.0 275.0 135.0 207.9 205.0 236.3 171.5 255.7 127.5
7200
85 236.0 236.0 265.6 219.2 294.3 177.2 226.6 226.6 250.9 212.4 275.7 169.3 216.1 216.1 234.8 200.6 255.6 161.2
90 249.6 249.6 262.0 246.2 293.6 210.9 239.5 239.5 247.4 238.8 275.1 203.4 228.0 228.0 231.3 231.3 254.7 195.2
75 241.7 201.6 273.5 158.9 297.8 108.8 228.6 194.9 257.4 151.7 279.0 101.4 214.4 184.0 239.9 144.1 258.4 93.5
80 236.7 230.2 272.5 195.1 298.2 147.7 223.7 223.1 256.6 187.9 278.8 140.1 209.8 209.8 239.2 180.0 258.9 132.5
8000
85 243.9 243.9 269.8 227.9 298.7 185.1 233.8 233.8 253.7 220.9 279.0 177.1 222.4 222.4 236.4 212.4 258.9 169.1
90 258.0 258.0 264.8 259.3 297.6 222.4 247.0 247.0 249.4 249.4 278.2 214.6 234.3 234.3 234.5 234.5 257.3 206.4
75 245.0 207.9 277.4 164.6 302.2 110.6 231.9 197.4 260.7 156.3 282.3 102.9 215.6 193.0 242.6 148.2 266.8 96.9
80 238.7 238.7 276.1 203.9 301.8 152.8 226.2 226.2 259.5 196.4 282.3 145.3 214.9 214.9 241.5 188.4 261.4 137.4
8800
85 250.9 250.9 271.8 238.8 302.1 192.9 240.1 240.1 255.4 230.7 281.7 184.8 227.7 227.7 237.4 222.0 261.2 176.6
90 265.3 265.3 266.5 266.5 300.7 233.7 253.4 253.4 253.5 253.5 280.6 225.7 239.5 239.5 239.6 239.6 260.1 209.1
75 246.5 216.3 280.9 169.3 305.7 112.3 232.1 208.5 263.7 161.5 285.0 104.4 216.6 200.2 244.8 153.1 270.4 98.7
80 242.1 242.1 278.9 212.4 305.1 157.8 231.4 231.4 261.8 204.7 285.0 149.4 219.5 219.5 243.2 196.5 263.6 140.5
9600
85 257.1 257.1 273.4 248.4 304.7 200.5 245.5 245.5 256.4 240.1 284.1 192.4 232.2 232.2 237.9 231.3 262.9 184.1
90 271.6 271.6 271.8 271.8 303.7 242.6 258.8 258.8 258.9 258.9 281.6 232.4 243.7 243.7 243.8 243.8 259.6 223.0
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
115 120 125
Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
Ent
DB (° 61 67 73 61 67 73 61 67 73
CFM F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 193.5 161.3 215.2 124.7 231.1 82.6 186.0 157.5 205.6 120.5 227.3 81.0 178.0 153.5 195.3 116.1 218.5 77.6
80 191.2 186.3 215.2 154.7 231.6 114.5 183.7 182.3 205.6 150.4 220.5 110.3 175.7 175.7 195.4 145.9 208.5 105.8
6400
85 197.6 197.6 214.3 184.0 232.0 145.1 191.4 191.4 205.0 176.8 221.1 140.8 184.5 184.5 194.5 173.7 209.3 136.1
90 208.2 208.2 211.9 209.2 231.5 175.7 201.2 201.2 202.6 202.6 220.7 171.4 193.0 193.0 193.2 193.2 214.8 169.0
75 196.8 169.7 218.3 130.4 241.0 86.4 188.8 163.4 208.3 126.0 221.7 79.4 180.7 156.3 197.6 120.5 208.7 74.6
80 193.4 193.4 218.0 163.3 234.5 119.4 186.5 186.5 207.9 158.8 222.9 115.1 179.8 179.8 197.1 154.1 220.9 114.2
7200
85 204.0 204.0 216.3 193.4 234.9 152.9 197.1 197.1 206.2 188.6 229.2 150.5 189.3 189.3 195.3 183.4 210.8 143.5
90 214.4 214.4 214.5 214.5 234.1 187.0 206.3 206.3 206.4 206.4 227.4 184.2 197.0 197.0 197.1 197.1 218.3 180.1
75 198.3 177.0 220.7 134.6 245.4 88.3 189.8 172.5 210.2 130.0 236.2 84.7 180.8 167.7 199.0 125.1 209.7 75.6
80 197.9 197.9 220.1 171.6 242.7 126.3 191.2 191.2 209.6 167.0 233.3 122.7 183.8 183.8 198.3 162.2 223.3 119.0
8000
85 209.2 209.2 217.3 203.2 236.9 160.4 201.5 201.5 206.8 198.2 232.6 158.5 192.9 192.9 195.4 192.9 223.0 154.8
90 219.1 219.1 219.2 219.2 236.1 192.5 210.0 210.0 210.1 210.1 229.4 192.0 200.8 200.8 200.9 200.9 219.7 188.3
75 199.3 184.3 222.6 139.4 249.0 90.1 190.6 179.7 211.7 134.6 239.5 86.4 181.2 174.9 200.0 129.5 210.4 76.6
80 202.2 202.2 221.6 179.7 244.8 130.2 195.0 195.0 210.8 173.7 226.7 122.7 187.0 187.0 199.0 165.9 213.6 117.6
8800
85 213.4 213.4 217.6 212.6 238.3 171.4 205.0 205.0 206.8 206.1 235.1 166.3 195.5 195.5 195.6 195.6 225.3 162.4
90 222.7 222.7 222.8 222.8 236.1 204.3 213.6 213.6 213.7 213.7 230.7 201.9 203.9 203.9 204.0 204.0 221.0 197.8
75 199.8 191.4 223.9 143.9 251.9 91.8 190.8 186.7 212.6 139.0 242.1 88.0 181.1 181.1 200.7 133.9 211.1 77.6
80 205.9 205.9 222.7 182.1 247.0 133.8 198.2 198.2 210.6 179.6 227.7 126.4 189.5 189.5 198.5 174.0 227.4 125.8
9600
85 216.7 216.7 217.5 217.5 246.5 177.5 207.7 207.7 207.7 207.7 237.0 173.8 197.6 197.6 197.7 197.7 226.9 169.8
90 225.8 225.8 225.8 225.8 241.1 215.1 216.7 216.7 216.8 216.8 231.6 211.1 211.4 211.4 211.6 211.6 221.7 207.0
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat
formula, refer to appropriate airflow table notes.
2. MBh = Total gross capacity
3. SHC = Sensible heat capacity

RT-PRC060N-EN 21
Performance Data

Table 6. Gross cooling capacities 25 tons - E/GCC300A3,4,W


Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
85 95 105
Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
Ent
DB (° 61 67 73 61 67 73 61 67 73
CFM F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 253.7 194.1 287.3 158.0 318.8 112.4 241.0 187.4 272.6 151.0 300.3 104.1 227.3 180.2 256.6 143.6 279.5 101.0
80 249.6 222.6 286.4 189.8 318.9 149.8 237.3 212.0 271.8 182.4 300.5 142.1 223.1 206.3 256.1 174.9 279.8 133.8
7000
85 244.7 244.7 285.0 220.3 318.6 182.3 232.6 232.6 270.3 213.3 300.4 174.8 222.9 222.9 254.3 205.7 280.2 166.5
90 255.4 255.4 281.4 247.3 318.4 213.8 246.1 246.1 267.1 235.2 300.5 206.1 235.9 235.9 250.6 231.4 280.2 197.6
75 260.7 206.2 296.0 166.0 326.3 113.0 247.1 199.1 280.0 158.6 305.9 111.2 232.4 191.5 262.5 150.7 283.0 102.2
80 254.5 234.5 295.4 201.1 326.4 156.2 241.1 226.8 279.7 193.6 306.2 148.0 226.7 218.6 262.2 185.5 283.8 139.2
8000
85 252.6 252.6 292.0 235.2 326.2 192.8 243.0 243.0 276.2 227.8 306.4 183.9 232.4 232.4 259.1 219.9 284.5 175.0
90 267.3 267.3 286.2 262.9 325.7 227.5 257.2 257.2 270.6 254.8 305.8 219.3 245.9 245.9 253.8 246.1 284.0 210.4
75 265.9 217.5 302.8 173.3 331.7 121.4 251.4 210.1 285.6 165.6 309.7 112.7 236.0 202.2 266.9 157.3 285.4 103.2
80 257.8 246.5 302.0 211.8 332.0 162.1 243.7 238.5 284.6 203.7 310.4 153.5 228.4 228.4 265.9 195.2 286.5 144.4
9000
85 262.2 262.2 297.0 249.2 332.0 201.6 251.8 251.8 280.3 238.3 310.9 192.9 240.3 240.3 261.1 229.1 287.4 183.4
90 277.6 277.6 289.3 277.3 330.5 240.5 266.6 266.6 272.9 269.0 309.6 232.0 254.2 254.2 255.2 255.2 286.6 222.8
75 269.6 228.1 308.1 180.2 335.9 123.0 254.5 218.1 289.7 171.3 312.4 113.9 237.0 208.7 270.4 162.6 288.4 104.7
80 259.6 257.7 306.3 221.6 336.4 167.8 244.6 244.6 288.1 213.3 313.6 158.9 232.6 232.6 268.5 204.6 288.9 149.5
10000
85 270.6 270.6 299.0 258.1 336.8 210.6 259.5 259.5 281.3 249.1 314.1 201.4 247.1 247.1 262.2 239.6 289.3 191.6
90 286.5 286.5 290.7 290.7 334.1 253.1 274.6 274.6 274.8 274.8 312.3 244.4 261.1 261.1 261.2 261.2 288.5 233.4
75 271.5 233.3 312.5 185.9 339.0 124.5 254.7 225.8 293.7 177.3 314.8 115.2 237.8 216.5 273.3 168.2 290.5 106.0
80 261.5 261.5 309.5 231.1 339.9 173.2 250.3 250.3 290.6 222.6 316.3 164.2 238.1 238.1 270.4 213.7 291.0 154.7
11000
85 277.9 277.9 300.4 268.6 339.8 219.1 266.1 266.1 282.0 259.4 316.2 209.7 252.9 252.9 262.3 249.8 290.7 199.7
90 294.3 294.3 294.5 294.5 336.8 265.4 281.5 281.5 281.6 281.6 314.3 250.4 266.8 266.8 267.0 267.0 288.2 242.1
Ambient Temperature (°F) Ambient Temperature (°F) Ambient Temperature (°F)
115 120 125
Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F) Entering Wet Bulb Temp (°F)
Ent
DB (° 61 67 73 61 67 73 61 67 73
CFM F) MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC MBh SHC
75 212.4 172.5 238.7 135.5 255.6 91.5 204.4 168.4 228.8 131.1 242.8 86.6 195.9 164.2 218.1 126.5 230.1 81.7
80 208.5 197.9 238.6 166.7 256.3 124.5 200.6 193.5 228.9 162.3 243.4 119.5 192.3 188.9 218.1 157.5 230.7 114.7
7000
85 212.1 212.1 236.7 197.6 257.3 157.0 206.1 206.1 227.1 193.2 244.6 151.6 199.5 199.5 216.7 187.7 231.1 146.3
90 224.3 224.3 233.3 222.4 257.3 188.3 217.8 217.8 223.8 217.7 244.5 183.2 210.5 210.5 213.6 212.6 230.9 177.8
75 216.6 183.5 243.1 142.2 258.5 92.7 208.0 179.3 232.5 137.5 245.6 87.8 199.0 172.6 221.0 132.7 237.2 84.6
80 211.1 210.0 242.7 176.7 258.8 129.6 202.8 202.8 232.1 171.9 246.3 124.9 194.8 194.8 220.7 166.9 232.8 119.9
8000
85 220.5 220.5 240.4 208.0 259.7 165.1 213.8 213.8 229.2 203.1 246.5 159.8 206.5 206.5 218.0 197.6 233.4 154.7
90 233.0 233.0 235.3 235.3 259.6 200.7 225.5 225.5 225.6 225.6 246.2 195.5 217.1 217.1 217.2 217.2 232.4 190.2
75 219.3 189.2 246.3 147.5 260.8 93.9 209.3 186.2 235.1 142.6 247.1 88.8 199.7 181.0 223.1 137.3 242.1 86.7
80 214.1 214.1 245.4 186.1 261.9 134.0 207.5 207.5 234.2 181.2 248.5 130.1 200.3 200.3 222.3 176.0 234.5 124.6
9000
85 227.4 227.4 241.0 219.1 261.5 173.3 220.0 220.0 230.1 213.8 248.6 168.2 211.9 211.9 218.4 208.2 234.5 162.8
90 239.8 239.8 239.9 239.9 261.1 212.9 231.4 231.4 231.5 231.5 247.4 202.1 221.8 221.8 221.9 221.9 233.3 198.0
75 219.4 199.1 248.9 153.0 262.4 95.0 210.0 194.1 237.1 147.8 248.1 89.8 200.0 188.8 224.5 142.4 246.0 88.7
80 219.7 219.7 247.2 195.2 263.7 140.0 212.6 212.6 235.6 190.2 250.2 133.9 204.8 204.8 223.3 184.0 235.7 128.3
10000
85 233.0 233.0 241.4 229.5 263.7 180.6 225.0 225.0 230.1 224.1 249.8 176.4 216.0 216.0 218.1 218.1 235.2 170.9
90 245.2 245.2 245.3 245.3 261.1 220.6 235.8 235.8 235.9 235.9 246.8 214.5 225.0 225.0 225.0 225.0 232.7 208.6
75 219.6 206.8 250.8 158.2 263.5 96.1 209.9 201.6 238.4 152.9 260.5 94.7 199.7 196.3 225.2 147.2 249.0 90.4
80 224.4 224.4 248.4 202.4 265.3 143.5 216.8 216.8 236.0 194.6 251.3 138.0 208.4 208.4 222.6 190.0 243.9 135.0
11000
85 237.7 237.7 241.0 239.6 264.5 189.7 229.0 229.0 229.5 229.5 250.5 184.4 219.2 219.2 219.3 219.3 235.6 178.8
90 249.4 249.4 249.5 249.5 260.6 230.3 239.0 239.0 239.0 239.0 246.2 224.3 226.9 226.9 226.9 226.9 232.0 218.4
Notes:
1. All capacities shown are gross and have not considered indoor fan heat. To obtain NET cooling capacity subtract indoor fan heat. For indoor fan heat formula,
refer to appropriate airflow table notes.
2. MBh = Total gross capacity
3. SHC = Sensible heat capacity

22 RT-PRC060N-EN
Performance Data

Evaporator Fan Performance


Table 7. Evaporator fan performance - 15 ton units with gas heat - GCC180 - downflow airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor, Low Static Drive Accessory 3-hp Standard Motor and Drive
4800 483 0.69 525 0.81 562 0.92 602 1.05 638 1.17 671 1.3 703 1.43 732 1.56 760 1.68 787 1.81
5400 532 0.94 572 1.08 607 1.21 640 1.34 675 1.49 707 1.63 738 1.76 767 1.91 794 2.05 820 2.20
6000 581 1.26 619 1.41 653 1.56 683 1.71 713 1.85 744 2.01 774 2.17 802 2.32 829 2.48 855 2.64
6600 632 1.63 667 1.81 699 1.98 728 2.14 756 2.30 782 2.45 812 2.63 839 2.80 865 2.98 890 3.14
7200 683 2.08 716 2.28 747 2.46 774 2.64 801 2.82 826 2.99 850 3.16 877 3.35 902 3.54 927 3.73
Available External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor and High Static Drive
3-hp Standard Motor and Drive 5-hp Oversized Motor and Drive
Accessory
4800 812 1.93 838 2.09 864 2.25 889 2.41 912 2.57 936 2.74 958 2.90 980 3.07 1001 3.24 1022 3.41
5400 845 2.34 870 2.48 893 2.62 915 2.76 939 2.94 962 3.12 984 3.30 1006 3.48 1027 3.67 1047 3.85
6000 880 2.80 903(a) 2.96 926 3.12 949 3.28 970 3.43 991 3.59 1011 3.75 1032 3.93 1053 4.13 1074 4.33
6600 915 3.31 938 3.49 961 3.67 983 3.85 1004 4.02 1025 4.20 1045 4.37 1064 4.55 1083 4.72 1102 4.89
7200 951 3.92 974 4.10 996 4.29 1017 4.48 1038 4.68 1059 4.87 — — — — — — — —
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) 3-hp Standard Motor and High Static Drive Accessory.

RT-PRC060N-EN 23
Performance Data

Table 8. Evaporator fan performance - 15 ton units with gas heat (model number digit 10 = L, M, X, Y) - GCC180 -
horizontal airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor, Low Static Drive Accessory 3-hp Standard Motor and Drive
4800 488 0.72 532 0.85 572 0.99 609 1.12 643 1.24 675 1.37 707 1.52 738 1.67 767 1.82 796 1.98
5400 539 1.00 578 1.13 615 1.29 650 1.43 683 1.58 714 1.72 743 1.87 771 2.02 800 2.19 827 2.36
6000 591 1.34 626 1.48 660 1.65 693 1.82 724 1.98 754 2.14 782 2.30 809 2.46 834 2.62 860 2.79
6600 643 1.75 675 1.90 706 2.07 738 2.26 767 2.45 795 2.62 823 2.80 849 2.98 873 3.15 897 3.33
7200 696 2.24 725 2.40 754 2.58 783 2.77 811 2.99 838 3.19 864 3.38 889 3.57 913 3.76 937 3.95
Available External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor and High Static
3-hp Standard Motor and Drive 5-hp Oversized Motor and Drive
Drive Accessory
4800 823 2.13 849 2.29 874 2.44 899 2.60 923 2.76 946 2.91 969 3.07 991 3.23 1012 3.39 1033 3.55
5400 853 2.53 879 2.70 903(a) 2.88 927 3.05 951 3.22 973 3.40 995 3.57 1017 3.75 1038 3.93 1059 4.11
6000 886 2.98 910 3.17 934 3.36 957 3.55 980 3.74 1003 3.94 1024 4.13 1045 4.32 1066 4.52 1086 4.71
6600 920 3.50 944 3.70 967 3.91 990 4.11 1012 4.32 1033 4.53 1054 4.74 1075 4.95 — — — —
7200 959 4.15 981 4.34 1002 4.53 1024 4.74 1045 4.96 — — — — — — — — — —
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) 3-hp Standard Motor and High Static Drive Accessory.

24 RT-PRC060N-EN
Performance Data

Table 9. Evaporator fan performance - 15 ton units with gas heat (model number digit 10 = H, Z) - GCC180 - horizontal
airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor, Low Static Drive Accessory 3-hp Standard Motor Drive
4800 — — — — — — — — — — 675 1.37 707 1.52 738 1.67 767 1.82 796 1.98
5400 — — — — — — 650 1.43 683 1.58 714 1.72 743 1.87 771 2.02 800 2.19 827 2.36
6000 591 1.34 626 1.48 660 1.65 693 1.82 724 1.98 754 2.14 782 2.30 809 2.46 834 2.62 860 2.79
6600 643 1.75 675 1.90 706 2.07 738 2.26 767 2.45 795 2.62 823 2.80 849 2.98 873 3.15 897 3.33
7200 696 2.24 725 2.40 754 2.58 783 2.77 811 2.99 838 3.19 864 3.38 889 3.57 913 3.76 937 3.95
Available External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor. High Static
3-hp Standard Motor Drive 5-hp Oversize Motor, Drive
Drive Accessory
4800 823 2.13 849 2.29 874 2.44 899 2.60 923 2.76 946 2.91 969 3.07 991 3.23 1012 3.39 1033 3.55
5400 853 2.53 879 2.70 903(a) 2.88 927 3.05 951 3.22 973 3.40 995 3.57 1017 3.75 1038 3.93 1059 4.11
6000 886 2.98 910 3.17 934 3.36 957 3.55 980 3.74 1003 3.94 1024 4.13 1045 4.32 1066 4.52 1086 4.71
6600 920 3.50 944 3.70 967 3.91 990 4.11 1012 4.32 1033 4.53 1054 4.74 1075 4.95 — — — —
7200 959 4.15 981 4.34 1002 4.53 1024 4.74 1045 4.96 — — — — — — — — — —
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) 3-hp Standard Motor and High Static Drive Accessory.

RT-PRC060N-EN 25
Performance Data

Table 10. Evaporator fan performance - 15 ton cooling only units (model number digit 8 = 3, 4, W) - ECC180 - downflow
airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor, Low Static Drive Accessory 3-hp Standard Motor Drive
4800 — — — — 489 0.68 530 0.78 568 0.89 608 1.00 644 1.11 679 1.24 713 1.39 746 1.53
5400 — — — — 517 0.86 558 0.99 594 1.11 628 1.23 663 1.35 697 1.48 729 1.60 760 1.75
6000 — — 500 0.93 546 1.08 586 1.23 622 1.37 655 1.50 685 1.63 717 1.76 748 1.91 778 2.05
6600 480 0.98 530 1.17 575 1.34 614 1.50 650 1.66 683 1.81 713 1.96 741 2.10 768 2.24 798 2.40
7200 514 1.24 562 1.44 604 1.63 643 1.82 679 1.99 711 2.16 741 2.33 769 2.49 795 2.65 821 2.80

Available External Static Pressure (Inches of Water)


1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor Drive 3-hp Standard Motor, High Static Drive Accessory
4800 777 1.68 806 1.82 832 1.97 858 2.12 882 2.26 906 2.41 928 2.56 951 2.72 972 2.87 994 3.02
5400 791 1.91 820 2.07 849 2.24 876 2.40 902 2.57 926 2.73 949 2.89 971 3.06 993 3.23 1014 3.39
6000 806 2.18 835 2.34 863 2.52 890 2.70 916 2.88 942 3.06 966 3.24 990 3.43 1013 3.61 1034 3.79
6600 826 2.55 853 2.71 879 2.86 905 3.01 931 3.20 956 3.40 981 3.60 1004 3.80 1028 4.00 1050 4.20
7200 846 2.96 873 3.13 899 3.30 924 3.47 948 3.63 972 3.79 995 3.98 1019 4.19 1042 4.41 1065 4.62
5-hp Oversize Motor, Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories
and options.

26 RT-PRC060N-EN
Performance Data

Table 11. Evaporator fan performance - 15 ton cooling only units (model number digit 8 = 3, 4, W) - ECC180 -
horizontal airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor, Low Static Drive Accessory 3-hp Standard Motor Drive
4800 — — 475 0.66 517 0.77 563 0.92 605 1.07 644 1.21 680 1.35 714 1.51 745 1.66 775 1.81
5400 — — 512 0.87 552 1.00 589 1.13 631 1.30 669 1.46 705 1.63 738 1.79 770 1.95 799 2.12
6000 498 0.94 548 1.12 589 1.28 624 1.42 657 1.56 695 1.75 730 1.93 763 2.12 794 2.30 824 2.48
6600 536 1.21 585 1.41 626 1.60 660 1.76 691 1.91 721 2.06 755 2.27 788 2.48 819 2.68 848 2.88
7200 575 1.52 623 1.75 662 1.96 697 2.15 727 2.32 755 2.49 782 2.65 814 2.87 844 3.10 873 3.32

Available External Static Pressure (Inches of Water)


1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
3-hp Standard Motor Drive 3-hp Standard Motor, High Static Drive Accessory 5-hp Oversize Motor, Drive
4800 804 1.96 831 2.12 858 2.27 883 2.42 907 2.58 931 2.74 953 2.92 975 3.09 996 3.27 1017 3.45
5400 828 2.29 855 2.47 881 2.64 906 2.81 931 2.98 954 3.15 977 3.33 1000 3.5 1021 3.67 1042 3.86
6000 852 2.66 879(a) 2.85 905 3.04 930 3.23 954 3.42 978 3.61 1001 3.8 1023 3.99 1044 4.18 1066 4.37
6600 877 3.08 904 3.28 930 3.47 954 3.68 979 3.89 1002 4.1 1025 4.31 1047 4.52 1068 4.73 1089 4.94
7200 901 3.54 928 3.76 954 3.98 979 4.19 1003 4.41 1026 4.63 1049 4.86 — — — — — —
5-hp Oversize Motor, Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) 3-hp Standard Motor and High Static Drive Accessory.

RT-PRC060N-EN 27
Performance Data

Table 12. Evaporator fan performance - 17.5 ton unit with gas heat - GCC210 - downflow airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, Low Static Drive Accessory 5-hp Standard Motor Drive
5600 554 1.06 592 1.21 627 1.34 658 1.47 693 1.63 725 1.77 755 1.92 783 2.07 811 2.22 837 2.37
6300 613 1.46 649 1.63 681 1.79 711 1.94 739 2.09 769 2.26 799 2.43 826 2.59 853 2.75 878 2.92
7000 673 1.96 706 2.15 737 2.33 765 2.51 792 2.67 817 2.84 844 3.02 871 3.21 897 3.39 921 3.58
7700 733 2.57 764 2.78 794 2.98 820 3.18 846 3.37 870 3.55 893 3.73 916 3.92 941 4.13 965 4.34
8400 794 3.29 823 3.52 851 3.75 877 3.96 901 4.17 924 4.38 946 4.58 967 4.78 987 4.97 1011(a) 5.20
5-hp Standard Motor, High Static Drive Accessory
Available External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor Drive 5-hp Standard Motor, High Static Drive Accessory
5600 862 2.52 886 2.67 909 2.81 931 2.96 953 3.11 976 3.30 998 3.48 1019 3.67 1040 3.86 1061 4.05
6300 903 3.09 926 3.26 949 3.43 971 3.60 992 3.76 1013 3.93 1033 4.10 1053 4.26 1072 4.43 1093 4.64
7000 945 3.75 968 3.94 990 4.13 1012 4.32 1033 4.51 1053 4.70 1073 4.88 1093 5.07 1112 5.25 1130 5.44
7700 989 4.54 1011 4.74 1033 4.94 1054 5.13 1075 5.34 1095 5.55 1114 5.76 1134 5.97 1152 6.18 1170 6.38
8400 1033 5.43 1055 5.65 1077 5.87 1097 6.09 1118 6.31 1137 6.52 1156 6.74 1175 6.97 1194 7.20 — —
7.5 - hp Oversized Motor, Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) 7.5-hp Oversize Motor and Drive.

28 RT-PRC060N-EN
Performance Data

Table 13. Evaporator fan performance - 17.5 ton unit with gas heat - GCC210 - horizontal airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, Low Static Drive Accessory 5-hp Standard Motor Drive
5600 561 1.12 599 1.26 635 1.43 670 1.58 702 1.73 732 1.88 761 2.03 788 2.18 816 2.36 843 2.53
6300 622 1.56 656 1.71 689 1.88 721 2.07 751 2.24 780 2.41 808 2.58 834 2.74 859 2.91 884 3.08
7000 684 2.10 714 2.26 745 2.44 774 2.64 803 2.85 830 3.04 857 3.22 882 3.41 906 3.60 930 3.79
7700 747 2.76 775 2.93 802 3.12 829 3.32 856 3.55 882 3.78 907 3.99 931 4.19 955 4.40 977 (a) 4.61
8400 810 3.54 836 3.74 860 3.93 886 4.15 910 4.37 935 4.63 959 4.87 982 5.10 1004 5.33 1026 5.55
7.5 - hp Oversized Motor, Drive
Available External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor Drive 5-hp Standard Motor, High Static Drive Accessory
5600 869 2.71 894 2.89 919 3.07 942 3.25 965 3.43 988 3.61 1010 3.79 1031 3.98 1052 4.16 1073 4.35
6300 909 3.28 933 3.48 956 3.68 979 3.88 1001 4.08 1023 4.28 1045 4.48 1066 4.69 1086 4.89 1106 5.09
7000 952 3.97 974 4.16 996 4.37 1019 4.59 1041 4.81 1062 5.03 1082 5.25 1102 5.48 1122 5.70 1142 5.93
7700 999 4.81 1021 5.02 1041 5.23 1061 5.43 1081 5.64 1102 5.88 1122 6.12 1142 6.37 1161 6.61 1180 6.85
8400 1047 5.78 1068 6.01 1088 6.23 1108 6.45 1127 6.68 1146 6.90 1164 7.13 1182 7.35 — — — —
7.5 - hp Oversized Motor, Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) 5-hp Oversize Motor and Drive.

RT-PRC060N-EN 29
Performance Data

Table 14. Evaporator fan performance - 17.5 ton cooling only units (model number digit 8 = 3, 4, W) - ECC210 -
downflow airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, Low Static Drive Accessory 5-hp Standard Motor Drive
5600 — — — — — — 572 1.08 608 1.21 641 1.33 675 1.46 709 1.59 740 1.72 771 1.85
6300 — — — — 566 1.23 606 1.38 642 1.53 674 1.68 705 1.81 733 1.95 764 2.10 794 2.25
7000 — — 559 1.38 601 1.56 640 1.74 676 1.91 708 2.07 738 2.24 766 2.39 792 2.54 818 2.69
7700 551 1.52 597 1.74 638 1.95 675 2.15 710 2.35 742 2.53 771 2.71 799 2.89 825 3.07 850 3.24
8400 593 1.93 636 2.17 675 2.41 711 2.63 744 2.85 776 3.06 805 3.26 833 3.46 859 3.65 883 3.85

Available External Static Pressure (Inches of Water)


1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, High Static Drive
5-hp Standard Motor Drive
Accessory
5600 801 2.02 831 2.19 859 2.36 886 2.53 912 2.70 938 2.88 961 3.05 983 3.22 1004 3.39 1025 3.56
6300 822 2.40 849 2.54 877 2.71 904 2.89 930 3.08 955 3.28 980 3.47 1004 3.66 1027 3.85 1049 4.05
7000 846 2.86 873 3.03 899 3.19 924 3.35 948 3.51 973 3.70 997 3.91 1021 4.12 1044 4.33 1067 4.55
7700 874 3.40 897 3.57 923 3.75 948 3.94 972 4.12 995 4.30 1018 4.47 1040 4.65 1062 4.84 1084 5.07
8400 907 4.04 929 4.22 951 4.40 973 4.58 995 4.78 1019 4.98 1041 5.18 1063 5.38 1085 5.57 1105 5.76
7.5 - hp Oversized Motor & Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.

30 RT-PRC060N-EN
Performance Data

Table 15. Evaporator fan performance - 17.5 ton cooling only units (model number digit 8 = 3, 4, W) - ECC210 -
horizontal airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, Low Static Drive Accessory 5-hp Standard Motor Drive
5600 — — 529 0.97 569 1.11 605 1.24 645 1.41 683 1.58 719 1.75 752 1.92 783 2.09 813 2.27
6300 — — 573 1.29 613 1.46 647 1.61 679 1.75 714 1.94 749 2.14 782 2.33 813 2.52 842 2.72
7000 571 1.45 617 1.67 657 1.87 691 2.05 721 2.21 749 2.37 780 2.57 813 2.79 843 3.01 872 3.22
7700 617 1.87 663 2.13 701 2.35 735 2.57 764 2.76 792 2.94 818 3.11 844 3.30 874 3.55 903 3.79
8400 664 2.37 709 2.67 745 2.92 778 3.16 809 3.39 835 3.59 860 3.79 884 3.98 907 4.17 934 4.42

Available External Static Pressure (Inches of Water)


1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor Drive 5-hp Standard Motor, High Static Drive Accessory
5600 841 2.45 868 2.62 894 2.80 919 2.98 944 3.16 967 3.34 990 3.52 1012 3.70 1034 3.88 1055 4.06
6300 871 2.90 898 3.10 923 3.30 948 3.50 972 3.70 996 3.90 1018 4.10 1041 4.30 1062 4.50 1083 4.71
7000 900 3.44 927 3.65 953 3.86 978 4.07 1002 4.29 1025 4.51 1047 4.74 1069 4.96 1091 5.18 1112 5.41
7700 930 4.03 957 4.27 982 4.50 1007 4.74 1031 4.97 1054 5.20 1077 5.43 1099 5.67 1120 5.92 1141 6.16
8400 961 4.68 987(a) 4.95 1013 5.21 1037 5.47 1061 5.73 1084 5.98 1106 6.24 1128 6.49 1149 6.75 — —
7.5 - hp Oversized Motor & Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) 5-hp Standard Motor and High Static Drive Accessory.

RT-PRC060N-EN 31
Performance Data

Table 16. Evaporator fan performance - 20 ton unit with gas heat - GCC240 - downflow airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, Low Static Drive Accessory 5-hp Standard Motor Drive
6400 621 1.53 657 1.70 689 1.86 719 2.02 746 2.17 776 2.34 805 2.51 833 2.67 859 2.84 884 3.00
7200 690 2.12 723 2.32 753 2.51 781 2.69 807 2.86 832 3.03 857 3.21 884 3.40 909 3.60 934 3.78
8000 759 2.86 790 3.08 818 3.29 844 3.50 869 3.70 893 3.89 915 4.08 937 4.27 961 4.48 985 4.70
8800 829 3.76 857 4.00 884 4.24 909 4.47 932 4.69 955 4.91 976 5.12 997 5.33 1017 5.54 1037 5.75
9600 899 4.83 925(a) 5.10 950(a) 5.36 974(a) 5.61 997 5.86 1018 6.10 1039 6.34 1059 6.58 1078 6.81 1097 7.03
7.5-hp Oversized Motor and Drive
Available External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, High Static
5-hp Standard Motor Drive
Drive Accessory
6400 909 3.18 932 3.35 955 3.52 977 3.70 998 3.87 1019 4.03 1039 4.20 1059 4.37 1078 4.54 1097 4.73
1065
7200 957 3.97 980 4.15 1002 4.34 1024 4.54 1045 4.74 (b) 4.93 1085 5.12 1104 5.32 1123 5.51 1142 5.70
8000 1008 4.91 1030 5.12 1052 5.32 1073 5.53 1093 5.73 1113 5.95 1132 6.17 1151 6.38 1170 6.60 1188 6.82
8800 1059 5.99 1081 6.23 1102 6.46 1123 6.69 1143 6.92 1162 7.15 1181 7.37 1199 7.59 — — — —
9600 1115 7.26 1133 7.49 — — — — — — — — — — — — — — — —
7.5-hp Oversized Motor and Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) Field supplied BK160 x 1.4375" fan sheave, 1VP50 x 1.125" motor sheave, and BX57 belt.
(b) 5-hp Standard Motor and High Static Drive Accessory.

32 RT-PRC060N-EN
Performance Data

Table 17. Evaporator fan performance - 20 ton unit with gas heat (model number digit 10 = L, M, X, Y) - GCC240 -
horizontal airflow
Available External Static Pressure (Inches of Water Gauge)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, Low Static Drive Accessory 5-hp Standard Motor Drive
6400 631 1.63 664 1.78 697 1.95 729 2.14 759 2.32 787 2.49 815 2.66 841 2.83 866 3.00 890 3.18
7200 702 2.28 732 2.44 761 2.62 790 2.83 818 3.04 845 3.24 871 3.43 896 3.62 920 3.82 943 4.01
8000 774 3.08 801 3.26 827 3.45 853 3.66 879 3.89 905 4.13 929 4.35 953 4.57 976 4.78 998 5.00
8800 846 4.05 871 4.26 894 4.45 919 4.68 942 4.90 966 5.17 989 5.43 1012 5.68 1034 5.92 1055 6.15
9600 918(a) 5.22 941(a) 5.44 963(a) 5.66 985(a) 5.88 1007 6.13 1029 6.38 1051 6.67 1072 6.95 1093 7.24 1114 7.50
7.5 - hp Oversized Motor, Drive
Available External Static Pressure (Inches of Water Gauge)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, High Static
5-hp Standard Motor Drive
Drive Accessory
6400 914 3.36 939 3.57 962 3.77 985 3.97 1007 4.18 1029 4.38 1050 4.59 1071 4.79 1091 5.00 1111 5.21
7200 966 4.20 987 4.39 1008 4.59 1030 4.81 1052 5.04 1073 5.26 1093 5.49 1113 5.72 1133 5.95 1152 6.18
8000 1020 5.21 1041 5.42 1061 5.64 1081 5.85 1101 6.07 1120 6.28 1139 6.52 1159 6.78 1178 7.03 1197 7.28
8800 1076 6.39 1096 6.63 1116 6.87 1135 7.10 1154 7.33 — — — — — — — — — —
9600 — — — — — — — — — — — — — — — — — — — —
7.5 - hp Oversized Motor, Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) Field supplied BK160 x 1.4375" fan sheave, 1VP50 x 1.125" motor sheave, and BX57 belt.

RT-PRC060N-EN 33
Performance Data

Table 18. Evaporator fan performance - 20 ton unit with gas heat (model number digit 10 = H, Z) - GCC240 - horizontal
airflow
Available External Static Pressure (Inches of Water Gauge)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, Low Static Drive Accessory 5-hp Standard Motor Drive
6400 — — — — — — — — — — 787 2.49 815 2.66 841 2.83 866 3.00 890 3.18
7200 — — — — 761 2.62 790 2.83 818 3.04 845 3.24 871 3.43 896 3.62 920 3.82 943 4.01
8000 774 3.08 801 3.26 827 3.45 853 3.66 879 3.89 905 4.13 929 4.35 953 4.57 976 4.78 998 5.00
8800 846 4.05 871 4.26 894 4.45 919 4.68 942 4.90 966 5.17 989 5.43 1012 5.68 1034 5.92 1055 6.15
9600 918(a) 5.22 941(a) 5.44 963(a) 5.66 985(a) 5.88 1007 6.13 1029 6.38 1051 6.67 1072 6.95 1093 7.24 1114 7.50
7.5 - hp Oversized Motor, Drive
Available External Static Pressure (Inches of Water Gauge)
1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, High Static
5-hp Standard Motor Drive
Drive Accessory
6400 914 3.36 939 3.57 962 3.77 985 3.97 1007 4.18 1029 4.38 1050 4.59 1071 4.79 1091 5.00 1111 5.21
7200 966 4.20 987 4.39 1008 4.59 1030 4.81 1052 5.04 1073 5.26 1093 5.49 1113 5.72 1133 5.95 1152 6.18
8000 1020 5.21 1041 5.42 1061 5.64 1081 5.85 1101 6.07 1120 6.28 1139 6.52 1159 6.78 1178 7.03 1197 7.28
8800 1076 6.39 1096 6.63 1116 6.87 1135 7.10 1154 7.33 — — — — — — — — — —
9600 — — — — — — — — — — — — — — — — — — — —
7.5 - hp Oversized Motor, Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) Field supplied BK160 x 1.4375" fan sheave, 1VP50 x 1.125" motor sheave, and BX57 belt.

34 RT-PRC060N-EN
Performance Data

Table 19. Evaporator fan performance - 20 ton cooling only units (model number digit 8 = 3, 4, W) - ECC240 - downflow
airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, Low Static Drive Accessory 5-hp Standard Motor Drive
6400 — — — — 571 1.28 611 1.43 647 1.58 679 1.73 709 1.87 738 2.01 767 2.16 797 2.31
7200 — — 570 1.48 612 1.67 650 1.85 685 2.03 718 2.20 747 2.37 775 2.53 801 2.69 827 2.84
8000 569 1.69 614 1.92 653 2.14 690 2.35 724 2.55 756 2.75 786 2.94 813 3.13 839 3.31 864 3.49
8800 617 2.19 658 2.45 697 2.70 731 2.93 764 3.16 795 3.39 825 3.60 852 3.81 878 4.02 902 4.23
942(a)
9600 665 2.79 704 3.07 740 3.35 774 3.61 805 3.86 835 4.12 864 4.36 891 4.60 917 4.83 (b) 5.06

Available External Static Pressure (Inches of Water)


1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor Drive 5-hp Standard Motor, High Static Drive Accessory
6400 826 2.46 853 2.61 879 2.76 906 2.95 932 3.14 958 3.33 982 3.53 1006 3.72 1029 3.92 1052 4.12
7200 853 3.00 880 3.18 906 3.35 931 3.52 955 3.68 978 3.84 1002 4.04 1026 4.26 1049 4.48 1072 4.69
8000 888 3.67 911 3.84 933 4.01 958 4.20 982 4.39 1005 4.58 1028 4.77 1050 4.95 1071 5.14 1092 5.31
8800 926 4.43 948 4.63 970 4.82 991 5.01 1012 5.20 1032 5.39 1055 5.61 1077 5.82 1098 6.03 1119 6.23
9600 964(b) 5.29 987(b) 5.51 1008 5.73 1029 5.95 1049 6.16 1069 6.37 1088 6.57 1106 6.78 1125 6.99 1146 7.22
7.5-hp Oversized Motor and Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories
and options.
(a) 7.5-hp Oversized Motor and Drive
(b) Field supplied BK160 x 1.4375" fan sheave, 1VP50 x 1.125" motor sheave, and BX57 belt.

RT-PRC060N-EN 35
Performance Data

Table 20. Evaporator fan performance - 20 ton cooling only units (model number digit 8 = 3, 4, W) - ECC240 -
horizontal airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor, Low Static Drive Accessory 5-hp Standard Motor Drive
6400 — — 579 1.34 620 1.51 653 1.67 685 1.81 719 1.99 754 2.19 786 2.39 817 2.59 847 2.78
7200 584 1.56 630 1.79 669 2.00 703 2.19 733 2.36 761 2.53 789 2.70 821 2.93 852 3.16 881 3.38
8000 637 2.07 683 2.35 719 2.59 753 2.81 783 3.02 810 3.21 836 3.39 860 3.57 888 3.80 916 4.05
8800 691 2.69 736 3.01 771 3.28 803 3.53 834 3.78 860 4.00 885 4.21 909 4.42 931 4.62 953 4.82
9600 746 3.42 787 3.78 823 4.09 854 4.38 883 4.65 911 4.92 935(a) 5.16 958(a) 5.40 980(a) 5.62 1001 5.84
7.5-hp Oversized Motor and Drive
Available External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
5-hp Standard Motor Drive 5-hp Standard Motor, High Static Drive Accessory
6400 875 2.98 902 3.17 928 3.37 952 3.58 977 3.78 1000 3.98 1023 4.19 1045 4.39 1066 4.60 1087 4.80
7200 909 3.60 935 3.82 961 4.04 986 4.26 1010 4.47 1033 4.70 1056 4.93 1078 5.16 1099 5.39 1120 5.62
8000 944 4.30 970 4.55 995 4.80 1020 5.04 1044 5.29 1067 5.53 1089 5.77 1111 6.01 1133 6.25 1153 6.51
8800 979 5.08 1005 5.36 1030 5.64 1055 5.92 1078 6.19 1101 6.46 1123 6.73 1145 7.00 1166 7.26 — —
9600 1022 6.06 1042 6.28 1066 6.57 1090 6.88 1113 7.18 1136 7.48 — — — — — — — —
7.5-hp Oversized Motor and Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) Field supplied BK160 x 1.4375" fan sheave, 1VP50 x 1.125" motor sheave, and BX57 belt.

36 RT-PRC060N-EN
Performance Data

Table 21. Evaporator fan performance - 25 ton unit with gas heat - GCC300 - downflow airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor, Low Static Drive
7.5-hp Standard Motor, Field Supplied Drive(a)
Accessory
7000 — — 706 2.15 737 2.33 765 2.51 792 2.67 817 2.84 844 3.02 871 3.21 897 3.39 921 3.58
7500 716 2.38 748 2.59 777 2.78 804 2.97 830 3.16 854 3.34 878 3.51 903 3.71 928 3.91 953 4.11
8000 759 2.86 790 3.08 818 3.29 844 3.50 869 3.70 893 3.89 915 4.08 937 4.27 961 4.48 985 4.70
8500 803 3.40 832 3.64 859 3.86 885 4.08 909 4.30 931 4.51 953 4.71 974 4.91 995 5.11 1017 5.34
9000 846 4.01 874 4.26 900 4.50 925 4.74 948 4.97 971 5.19 992 5.41 1012 5.63 1032 5.84 1052 6.05
9500 890 4.68 917 4.95 942 5.21 966 5.46 989 5.70 1010 5.94 1031 6.18 1051 6.41 1070 6.64 1089 6.86
10000 934 5.43 960 5.71 984 5.99 1007 6.25 1029 6.51 1050 6.77 1070 7.02 1090 7.27 1109 7.51 1127 7.75
1091
10500 978 6.25 1003 6.55 1026 6.84 1049 7.12 1070 7.40 (b) 7.67 1110 7.94 1129 8.20 1148 8.46 1166 8.71
1069 1090
11000 1022 7.16 1046 7.47 (b) 7.78 (b) 8.08 1111 8.37 1131 8.66 1151 8.94 1169 9.21 1187 9.49 1204 9.76
10-hp Oversized Motor and Drive
Available External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor Drive
7000 945 3.75 968 3.94 990 4.13 1012 4.32 1033 4.51 1053 4.70 1073 4.88 1093 5.07 1112 5.25 1130 5.44
7500 976 4.31 999 4.50 1021 4.69 1042 4.89 1063 5.09 1083 5.30 1103 5.50 1122 5.70 1141 5.90 1159 6.10
8000 1008 4.91 1030 5.12 1052 5.32 1073 5.53 1093 5.73 1113 5.95 1132 6.17 1151 6.38 1170 6.60 1188 6.82
8500 1040 5.57 1062 5.79 1083 6.02 1104 6.24 1124 6.46 1143 6.67 1162 6.89 1181 7.12 1200 7.35 1218 7.58
9000 1072 6.28 1094 6.53 1115 6.77 1135 7.01 1155 7.24 1174 7.48 1193 7.71 1212 7.94 1230 8.16 1248 8.41
9500 1107 7.08 1127 7.32 1147 7.58 1167 7.84 1187 8.09 1206 8.34 1225 8.59 1243 8.84 1261 9.08 1278 9.32
10000 1145 7.99 1163 8.22 1180 8.46 1200 8.73 1219 9.00 1238 9.27 1256 9.54 1274 9.80 — — — —
10500 1183 8.96 1200 9.21 1217 9.46 1233 9.70 1252 9.98 — — — — — — — — — —
11000 1222 10.0 — — — — — — — — — — — — — — — — — —
10-hp Oversized Motor and Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) Field supplied BK160 x 1.4375" fan sheave, 1VP44 x 1.125" motor sheave, and BX60 belt.
(b) Field supplied BK120 x 1.4375" fan sheave, 1VP75 x 1.375" motor sheave, and BX55 belt.

RT-PRC060N-EN 37
Performance Data

Table 22. Evaporator fan performance - 25 ton unit with gas heat - GCC300 - horizontal airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor, Field Supplied Drive(a) 7.5-hp Standard Motor, Low Static Drive Accessory
7000 — — 714 2.26 745 2.44 774 2.64 803 2.85 830 3.04 857 3.22 882 3.41 906 3.60 930 3.79
7500 729 2.56 757 2.73 786 2.92 813 3.12 841 3.34 867 3.55 892 3.76 917 3.96 941 4.16 964 4.36
8000 774 3.08 801 3.26 827 3.45 853 3.66 879 3.89 905 4.13 929 4.35 953 4.57 976 4.78 998 5.00
8500 819 3.67 844 3.86 869 4.05 894 4.28 918 4.50 943 4.76 967 5.01 990 5.24 1012 5.47 1033 5.70
9000 864 4.33 888 4.54 912 4.74 935 4.96 958 5.19 982 5.45 1005 5.72 1027 5.98 1048 6.23 1069 6.47
9500 909 5.06 932 5.29 955 5.50 977 5.72 999 5.97 1021 6.21 1043 6.50 1065 6.79 1086 7.06 1106 7.32
10000 954 5.88 977 6.12 998 6.34 1019 6.56 1040 6.82 1061 7.08 1082 7.35 1103 7.66 1123 7.96 1143 8.24
1082
10500 1000 6.78 1021 7.03 1042 7.27 1062 7.50 (b) 7.76 1102 8.03 1122 8.30 1142 8.60 1162 8.92 1181 9.23
1045 1066 1086
11000 (b) 7.77 (b) 8.03 (b) 8.28 1105 8.53 1124 8.78 1144 9.07 1162 9.35 1181 9.63 1200 9.96 1219 10.3
10 - hp Oversized Motor, Drive
Available External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor Drive
7000 952 3.97 974 4.16 996 4.37 1019 4.59 1041 4.81 1062 5.03 1082 5.25 1102 5.48 1122 5.70 1142 5.93
7500 986 4.56 1007 4.76 1028 4.96 1048 5.16 1069 5.39 1090 5.63 1110 5.86 1130 6.10 1150 6.34 1169 6.58
8000 1020 5.21 1041 5.42 1061 5.64 1081 5.85 1101 6.07 1120 6.28 1139 6.52 1159 6.78 1178 7.03 1197 7.28
8500 1054 5.93 1075 6.16 1095 6.38 1115 6.61 1134 6.84 1152 7.07 1171 7.29 1188 7.52 1207 7.77 1225 8.04
9000 1090 6.71 1110 6.96 1130 7.20 1149 7.44 1167 7.68 1186 7.92 1204 8.16 1221 8.40 1239 8.64 1255 8.88
9500 1126 7.57 1145 7.83 1165 8.09 1183 8.34 1202 8.60 1220 8.85 1237 9.10 1255 9.35 1272 9.61 1288 9.87
10000 1163 8.52 1182 8.78 1200 9.05 1218 9.32 1237 9.59 1254 9.86 — — — — — — — —
10500 1200 9.53 1219 9.82 — — — — — — — — — — — — — — — —
11000 — — — — — — — — — — — — — — — — — — — —
10 - hp Oversized Motor, Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) Field supplied BK160 x 1.4375" fan sheave, 1VP44 x 1.125" motor sheave, and Bx60 belt.
(b) Field supplied BK120 x 1.4375" fan sheave, 1VP75 x 1.375" motor sheave, and BX55 belt.

38 RT-PRC060N-EN
Performance Data

Table 23. Evaporator fan performance - 25 ton cooling only unit - ECC300 (model number digit 8 = 3, 4, W) - downflow
airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor, Low Static Drive
7.5-hp Standard Motor, Field Supplied Drive(a)
Accessory
7000 — — — — 601 1.56 640 1.74 676 1.91 708 2.07 738 2.24 766 2.39 792 2.54 818 2.69
7500 — — 586 1.63 627 1.83 665 2.03 700 2.22 732 2.39 762 2.57 789 2.74 816 2.91 841 3.07
8000 — — 614 1.92 653 2.14 690 2.35 724 2.55 756 2.75 786 2.94 813 3.13 839 3.31 864 3.49
8500 599 1.99 642 2.24 680 2.48 716 2.70 749 2.92 781 3.14 810 3.34 838 3.54 863 3.74 888 3.94
9000 629 2.33 670 2.60 707 2.85 742 3.09 775 3.33 805 3.56 834 3.79 862 4.00 888 4.21 912 4.43
9500 659 2.71 698 2.99 735 3.26 769 3.52 800 3.77 830 4.02 859 4.26 886 4.50 912 4.73 937 4.95
10000 689 3.13 727 3.42 763 3.72 796 3.99 826 4.25 856 4.52 884 4.78 911 5.03 936 5.28 961 5.52
10500 720 3.59 756 3.90 791 4.21 823 4.50 853 4.78 881 5.06 909 5.34 935 5.61 961 5.87 985 6.13
11000 750 4.10 786 4.42 819 4.75 850 5.06 880 5.36 908 5.65 934 5.94 960 6.23 985 6.51 1009 6.79
7.5-hp Standard Motor Drive
Available External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor, High Static Drive
7.5-hp Standard Motor Drive
Accessory
7000 846 2.86 873 3.03 899 3.19 924 3.35 948 3.51 973 3.70 997 3.91 1021 4.12 1044 4.33 1067 4.55
7500 865 3.23 890 3.41 916 3.59 941 3.77 965 3.94 988 4.11 1011 4.28 1034 4.47 1057 4.69 1079 4.92
8000 888 3.67 911 3.84 933 4.01 958 4.20 982 4.39 1005 4.58 1028 4.77 1050 4.95 1071 5.14 1092 5.31
8500 911 4.13 934 4.32 956 4.50 977 4.69 999 4.87 1022 5.08 1045 5.28 1067 5.48 1088 5.68 1109 5.88
9000 935 4.63 958 4.84 979 5.04 1001 5.23 1021 5.43 1041 5.62 1062 5.83 1084 6.04 1105 6.26 1126 6.47
9500 960 5.17 982 5.39 1003 5.61 1024 5.82 1044 6.03 1064 6.24 1083 6.44 1102 6.64 1122 6.86 1143 7.09
10000 984 5.75 1006 5.99 1027 6.22 1048 6.45 1068 6.68 1087 6.90 1106 7.12 1125 7.34 1143 7.55 1161 7.76
10500 1008 6.38 1031 6.63 1052 6.88 1072 7.12 1092 7.36 1111 7.60 1130 7.84 1148 8.07 1166 8.30 1184 8.53
1076 1096
11000 1032 7.06 1055 7.32 (b) 7.58 (b) 7.84 1116 8.10 1135 8.35 1154 8.60 1172 8.85 1190 9.10 1207 9.34
10 - hp Oversized Motor, Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) Field supplied BK160 x 1.4375" fan sheave, 1VP44 x 1.125" motor sheave, and Bx60 belt.
(b) Field supplied BK120 x 1.4375" fan sheave, 1VP75 x 1.375" motor sheave, and BX55 belt.

RT-PRC060N-EN 39
Performance Data

Table 24. Evaporator fan performance - 25 ton cooling only unit (model number digit 8 = 3, 4, W) - ECC300 - horizontal
airflow
Available External Static Pressure (Inches of Water)
0.10 0.20 0.30 0.40 0.50 0.60 0.70 0.80 0.90 1.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor, Field Supplied Drive(a) 7.5-hp Standard Motor, Low Static Drive Accessory
7000 — — 617 1.67 657 1.87 691 2.05 721 2.21 749 2.37 780 2.57 813 2.79 843 3.01 872 3.22
7500 604 1.74 650 1.99 688 2.21 722 2.41 752 2.59 780 2.77 806 2.94 835 3.15 865 3.39 894 3.62
8000 637 2.07 683 2.35 719 2.59 753 2.81 783 3.02 810 3.21 836 3.39 860 3.57 888 3.80 916 4.05
8500 671 2.44 716 2.75 751 3.01 784 3.25 815 3.48 841 3.69 866 3.89 890 4.09 913 4.28 939 4.51
9000 705 2.86 748 3.19 784 3.47 816 3.73 846 3.99 873 4.22 897 4.44 921 4.65 943 4.86 965 5.06
9500 739 3.32 781 3.68 816 3.98 847 4.27 877 4.54 905 4.80 929 5.04 952 5.27 974 5.49 995 5.71
10000 773 3.83 814 4.21 849 4.55 880 4.85 908 5.14 935 5.42 961 5.69 983 5.94 1005 6.17 1026 6.41
10500 807 4.39 847 4.79 882 5.17 912 5.49 940 5.79 966 6.09 992 6.39 1015 6.66 1036 6.92 1057(b) 7.17
1068
11000 842 5.01 880 5.43 915 5.83 945 6.18 972 6.51 998 6.83 1022 7.14 1046 7.44 (c) 7.72 1088(c) 7.98
7.5-hp Standard Motor Drive
Available External Static Pressure (Inches of Water)
1.10 1.20 1.30 1.40 1.50 1.60 1.70 1.80 1.90 2.00
cfm rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp rpm bhp
7.5-hp Standard Motor, High Static Drive
7.5-hp Standard Motor Drive
Accessory
7000 900 3.44 927 3.65 953 3.86 978 4.07 1002 4.29 1025 4.51 1047 4.74 1069 4.96 1091 5.18 1112 5.41
7500 922 3.86 948 4.09 974 4.32 999 4.54 1023 4.77 1046 4.99 1068 5.23 1090 5.46 1111 5.70 1132 5.94
8000 944 4.30 970 4.55 995 4.80 1020 5.04 1044 5.29 1067 5.53 1089 5.77 1111 6.01 1133 6.25 1153 6.51
8500 966 4.78 992 5.05 1017 5.31 1042 5.58 1065 5.84 1088 6.10 1110 6.36 1132 6.62 1153 6.87 1174 7.13
9000 988 5.29 1014 5.58 1039 5.87 1063 6.15 1087 6.43 1110 6.71 1132 6.98 1153 7.26 1175 7.53 1195 7.81
9500 1016 5.92 1037 6.15 1062 6.45 1086 6.75 1109 7.05 1131 7.35 1154 7.64 1175 7.94 1196 8.23 1216 8.52
10000 1046 6.64 1066 6.87 1085 7.09 1108 7.40 1131 7.71 1154 8.03 1175 8.34 1197 8.66 1218 8.97 1238 9.28
10500 1077(b) 7.41 1096 7.66 1115 7.89 1133 8.13 1154 8.42 1176 8.75 1198 9.08 1219 9.41 1239 9.74 — —
11000 1107 8.25 1126 8.51 1145 8.76 1163 9.01 1181 9.26 1198 9.51 1220 9.87 — — — — — —
10 - hp Oversized Motor, Drive
Notes:
1. For Standard Evaporator Fan Speed (rpm), see table Standard motor and drive/fan speed.
2. For High Evaporator Fan Speed (rpm), see table Standard motor and high static drive accessory sheave / fan speed.
3. For Oversized Evaporator Fan Speed (rpm), see table Oversized motor and drive/fan speed.
4. Fan motor heat (MBh) = 3.15 x Fan bhp.
5. Data includes pressure drop due to standard filters and wet coils. No accessories or options are included in pressure drop data.
6. For all non-standard sheave combinations, refer to accessory installer’s guides ACC-SVN163*-EN and ACC-SVN169*-EN.
7. Factory supplied motors, in commercial equipment, are definite purpose motors, specifically designed and tested to operate reliably and continuously at all
cataloged conditions. Using the full horsepower range of our fan motors as shown in our tabular data will not result in nuisance tripping or premature motor
failure. Our product’s warranty will not be affected.
8. Available External Static Pressure is the static pressure between the return duct and the supply duct plus the static pressure drop caused by accessories and
options.
(a) Field supplied BK160 x 1.4375" fan sheave, 1VP44 x 1.125" motor sheave, and Bx60 belt.
(b) 7.5-hp Standard Motor and High Static Drive Accessory.
(c) Field supplied BK120 x 1.4375" fan sheave, 1VP75 x 1.375" motor sheave, and BX55 belt.

40 RT-PRC060N-EN
Performance Data

Table 25. Standard motor and drive/fan speed (rpm)


6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Unit Model Number Closed
Open Open Open Open Open Open
15 E/G*C180A3,4,W 653 669 746 793 839 886 N/A
17.5 E/G*C210A3,4,W 721 772 824 875 927 978 N/A
G*C240A3,4,W 824 875 927 978 1030 1081 N/A
20
E*C240A3,4,W 721 772 824 875 927 978 N/A
G*C300A3,4,W 995 1048 1100 1153 1205 1257 N/A
25
E*C300A3,4,W 886 912 957 1003 1048 1094 N/A
Note: Factory set at 3 turns open.

Table 26. Standard motor and low static drive accessory sheave/fan speed (rpm)
6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Unit Model Number Closed
Open Open Open Open Open Open
15 E/G*C180A3,4,W 488 523 558 592 627 662 N/A
17.5 E/G*C210A3,4,W 560 596 632 668 703 739 N/A
G*C240A3,4,W 627 672 717 762 806 851 N/A
20
E*C240A3,4,W 538 574 609 645 681 717 N/A
G*C300A3,4,W 838 891 943 995 1048 1100 N/A
25
E*C300A3,4,W 729 775 821 866 912 957 N/A

Table 27. Standard motor and high static drive accessory sheave/fan speed (rpm)
6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Unit Model Number Closed
Open Open Open Open Open Open
15 E/G*C180A3,4,W 886 932 979 1026 1072 1119 N/A
17.5 E/G*C210A3,4,W 978 1030 1081 1133 1184 1236 N/A
20 E/G*C240A3,4,W 863 918 974 1029 1085 1141 N/A
25 E*C300A3,4,W 995 1048 1100 1153 1205 1257 N/A

Table 28. Oversized motor and drive/fan speed (rpm)


6 Turns 5 Turns 4 Turns 3 Turns 2 Turns 1 Turn
Tons Unit Model Number Closed
Open Open Open Open Open Open
15 E/G*C180A3,4,W 847 908 968 1029 1089 1150 N/A
17.5 E/G*C210A3,4,W 995 1048 1100 1153 1205 1257 N/A
20 E/G*C240A3,4,W 995 1048 1100 1153 1205 1257 N/A
25 E/G*C300A3,4,W 1108 1151 1194 1237 1280 1323 N/A

Table 29. Static pressure drop through accessories (inches water column)
Low Leak
Standard
Economizer with
2 in. 2-in. Economizer with Electric Heater Accessory (kW)(b)
Unit Model OA/RA Dampers
Tons cfm Standard MERV 13 OA/RA Dampers(a) (a)
Number
Filters Filters
100% 100% 100%
100% RA 18 36 54 72
OA OA RA
4800 0.03 0.10 0.15 0.04 0.19 0.22 0.01 0.01 — —
E/G*C180A
6000 0.05 0.14 0.20 0.04 0.31 0.34 0.02 0.02 — —
(Downflow)
7200 0.07 0.17 0.27 0.04 0.45 0.48 0.03 0.03 — —
15
4800 0.03 0.1 0.15 0.04 0.19 0.22 0.01 0.01 — —
E/G*C180A
6000 0.05 0.14 0.2 0.04 0.31 0.34 0.02 0.02 — —
(Horizontal)
7200 0.07 0.17 0.27 0.04 0.45 0.48 0.04 0.04 — —
5600 0.05 0.12 0.18 0.04 0.27 0.29 — 0.03 0.04 0.04
E/G*C210A
7000 0.07 0.16 0.26 0.04 0.42 0.46 — 0.05 0.05 0.06
(Downflow)
8400 0.10 0.20 0.35 0.06 0.61 0.66 — 0.06 0.07 0.09
17.5
5600 0.05 0.12 0.18 0.04 0.27 0.29 — 0.03 0.04 0.04
E/G*C210A
7000 0.07 0.16 0.26 0.04 0.42 0.46 — 0.05 0.06 0.07
(Horizontal)
8400 0.10 0.20 0.35 0.06 0.61 0.66 — 0.07 0.09 0.11

RT-PRC060N-EN 41
Performance Data

Table 29. Static pressure drop through accessories (inches water column) (continued)
Low Leak
Standard
Economizer with
2 in. 2-in. Economizer with Electric Heater Accessory (kW)(b)
Unit Model OA/RA Dampers
Tons cfm Standard MERV 13 OA/RA Dampers(a) (a)
Number
Filters Filters
100% 100% 100%
100% RA 18 36 54 72
OA OA RA
6400 0.07 0.15 0.22 0.04 0.35 0.38 — 0.04 0.05 0.05
E/G*C240A
8000 0.10 0.19 0.32 0.05 0.55 0.60 — 0.05 0.07 0.08
(Downflow)
9600 0.17 0.24 0.44 0.07 0.81 0.86 — 0.06 0.08 0.11
20
6400 0.07 0.15 0.22 0.04 0.35 0.38 — 0.04 0.05 0.06
E/G*C240A
8000 0.10 0.19 0.32 0.05 0.55 0.60 — 0.07 0.08 0.10
(Horizontal)
9600 0.17 0.24 0.44 0.07 0.81 0.86 — 0.09 0.11 0.14
7000 0.07 0.16 0.26 0.04 0.42 0.46 — 0.05 0.05 0.06
E/G*C300A
9000 0.10 0.22 0.40 0.07 0.71 0.75 — 0.06 0.08 0.10
(Downflow)
11000 0.17 0.28 0.57 0.10 1.07 1.12 — 0.07 0.10 0.12
25
7000 0.07 0.16 0.26 0.04 0.42 0.46 — 0.05 0.06 0.07
E/G*C300A
9000 0.10 0.22 0.40 0.07 0.71 0.75 — 0.08 0.10 0.12
(Horizontal)
11000 0.17 0.28 0.57 0.10 1.07 1.12 — 0.13 0.18 0.23
(a) OA = Outside Air and RA = Return Air.
(b) Nominal kW ratings at 240, 480, 600 volts.

Table 30. Gas fired heating capacities

Heating Input Heating Output Air Temp Rise


Tons Unit Model Number
(MBh)(a) (MBh)(a) (°F)
G*C180A(3,4,W)E(L or X) 240/168 194/136 15-45
15 G*C180A(3,4,W)E(M or Y) 320/224 259/181 20-50
G*C180A(3,4,W)E(H or Z) 350/245 284/198 25-55
G*C210A(3,4,W)E(L or X) 240/168 194/136 15-45
G*C210A(3,4,W)E(M or Y) 320/224 259/181 20-50
17.5(b)
G*C210A(3,4,W)E(H or Z)- Downflow 380/266 308/215 20-50
G*C210A(3,4,W)E(H or Z)- Horizontal 350/245 284/198 25-55
G*C240A(3,4,W)E(L or X) 240/168 194/136 15-45
20 G*C240A(3,4,W)E(M or Y) 320/224 259/181 20-50
G*C240A(3,4,W)E(H or Z) 380/266 308/215 20-50
G*C300A(3,4,W)E(L or X) 240/168 194/136 15-45
25 G*C300A(3,4,W)E(M or Y) 320/224 259/181 20-50
G*C300A(3,4,W)E(H or Z) 380/266 308/215 20-50
(a) For two stage heaters (input or output), second stage is total heating capacity. Second stage/first stage.
(b) For 17.5T high heat option, input rate will de-rate from downflow to horizontal.

Table 31. Auxiliary electric heat capacity


Total(a) Stage1 Stage 2
Tons Unit Model Number kW MBh No. of Stages kW MBh kW MBh
Input(b) Output Input Output Input Output
18 61.5 1 18 61.5 — —
15 E*C180A3,4,W 36 122.9 2 18 61.5 18 61.5
54 184.4 2 36 122.9 18 61.5
E*C210A3,4,W 36 122.9 2 18 61.5 18 61.5
17.5 - 25 E*C240A3,4,W 54 184.4 2 36 122.9 18 61.5
E*C300A3,4,W 72 245.9 2 36 122.9 36 122.9
(a) Heaters are rated at 240V, 480V, and 600V. For other than rated voltage, CAP = (voltage/rated voltage) x rated cap.
(b) For all input/output categories, does not include fan power or heat.

42 RT-PRC060N-EN
Performance Data

Table 32. Electric heater voltage correction factors (applicable to auxiliary heat capacity)
Nominal Voltage Distribution Voltage Capacity Multiplier
208 0.75
240 230 0.92
240 1.00
380 0.63
440 0.84
480
460 0.94
480 1.00
540 0.81
600 575 0.92
600 1.00

Table 33. Air temperature rise across electric heaters (°F)


15 Tons 17.5 Tons 20 Tons 25 Tons
kW Stages 6000 cfm 7000 cfm 8000 cfm 9000 cfm
E*C180A E*C210A E*C240A E*C300A
18 1 9.5 — — —
36 2 19.0 16.3 14.2 12.6
54 2 28.5 24.4 21.3 19
72 2 — 32.5 28.5 25.3
Notes:
1. For minimum design airflow, see airflow performance table for each unit.
2. To calculate temp rise at different airflow, use the following formula: Temp. rise across Electric Heater = kW x 3414/1.08 x cfm.

RT-PRC060N-EN 43
Controls
Economizer Controls
The standard equipment offering is a fixed dry bulb changeover control. In addition, there are two
optional controls, Reference Enthalpy Control and Comparative Enthalpy Control.

Reference Enthalpy Control


Replaces the dry bulb control with a wet bulb changeover controller which has a fully adjustable
setpoint. Enthalpy control offers a higher level of comfort control, along with energy savings potential,
than the standard dry bulb control. This is due to the additional wet bulb sensing capability.

Comparative Enthalpy Control


Comparative Enthalpy replaces the standard dry bulb control with two sensors that compare total heat
content of the indoor air and outdoor air to determine the most efficient air source. This control option
offers the highest level of comfort control, plus energy efficiency, available.

Remote Potentiometer
Minimum position setting of economizer can be remotely adjusted with this accessory.

Thermostats
Model # Type Stages Display Type Features

TCONT302AS42DA Programmable 4H/2C Touchscreen Common preferred, not required 2/ 2 AA battery power

TCONT402AN32DA Non-Programmable 3H/2C Backlit Display and Keys Outdoor Temperature Sensor included

BAYSTAT814 Touchscreen 3H/2C Touchscreen Remote access via Pivot Mobile App

BAYSTAT300 Programmable 3H/2C Backlit Display and Keys BACnet MS-TP enabled

44 RT-PRC060N-EN
Electrical Data
Table 34. Unit wiring with cooling (no electric heat) or gas heat
Standard Indoor Fan Motor Oversized Indoor Fan Motor
Unit Model Unit Operating Maximum Fuse Size Maximum Fuse Size
TONS Minimum Circuit Minimum Circuit
Number Voltage Range or Maximum Circuit or Maximum Circuit
Ampacity(a) Ampacity
Breaker Breaker
E/GCC180A3 208-230 79 100 85 110
15 E/GCC180A4 460 36 45 39 50
E/GCC180AW 575 30 35 32 40
E/GCC210A3 208-230 92 110 99 125
17.5 E/GCC210A4 460 40 50 44 50
E/GCC210AW 575 33 40 36 45
E/GCC240A3 208-230 101 125 109 125
20 E/GCC240A4 460 50 60 53 60
E/GCC240AW 575 39 50 42 50
E/GCC300A3 208-230 133 175 140 175
25 E/GCC300A4 460 58 70 61 70
E/GCC300AW 575 46 60 48 60
(a) For Standard and Oversized Indoor Fan Motor, values do not include power exhaust accessory.

Table 35. Unit wiring with electric heat (single point connection)
Standard Indoor Motor Oversized Indoor Motor
Unit Model Heater Model Heater kW Control Max Fuse Size Max Fuse Size
Tons
Number Number Rating Stages MCA or Max Circuit MCA or Max Circuit
Breaker Breaker(a)
208/230 Volts Three Phase
BAYHTFB318A 13.5/18 1 79 100 85 110
15 ECC180A3 BAYHTFC336A 27/36 2 108/122 110/125 115/130 125/150
BAYHTFC354A 40.5/54 2 155/144 175 162/151 175
BAYHTFC336A 27/36 2 115/130 125/150 125/139 125/150
17.5 ECC210A3 BAYHTFC354A 40.5/54 2 162/151 175 172/161 175
BAYHTFC372A 54/72 2 172/195 200/225 181/204 200/225
BAYHTFD336A 27/36 2 115/130 125/150 125/139 125/150
20 ECC240A3 BAYHTFD354A 40.5/54 2 162/151 175 172/161 175
BAYHTFD372A 54/72 2 172/195 200/225 181/204 200/225
BAYHTFD336A 27/36 2 133/139 175 140/147 175
25 ECC300A3 BAYHTFD354A 40.5/54 2 172/161 175 180/169 200/175
BAYHTFD372A 54/72 2 181/204 200/225 189/212 200/225
460 Volts Three Phase
BAYHTFB418A 18 1 36 45 39 50
15 ECC180A4 BAYHTFC436A 36 2 61 70 64 70
BAYHTFC454A 54 2 72 90 75 90
BAYHTFC436A 36 2 64 70 68 70
17.5 ECC210A4 BAYHTFC454A 54 2 75 90 79 90
BAYHTFC472A 72 2 97 110 101 110
BAYHTFD436A 36 2 64 70 68 70
20 ECC240F4 BAYHTFD454A 54 2 75 90 79 90
BAYHTFD472A 72 2 97 110 101 110
BAYHTFD436A 36 2 68 70 72 80
25 ECC300A4 BAYHTFD454A 54 2 79 90 83 90
BAYHTFD472A 72 2 101 110 105 110
575 Volts Three Phase
BAYHTFBW18A 18 1 30 35 32 40
15 ECC180AW BAYHTFCW36A 36 2 49 50 51 60
BAYHTFCW54A 54 2 57 70 60 70
BAYHTFCW36A 36 2 51 60 55 60
17.5 ECC210AW BAYHTFCW54A 54 2 60 70 64 70
BAYHTFCW72A 72 2 77 90 81 90
BAYHTFDW36A 36 2 51 60 55 60
20 ECC240AW BAYHTFDW54A 54 2 60 70 64 70
BAYHTFDW72A 72 2 77 90 81 90
BAYHTFDW36A 36 2 55 60 58 60
25 ECC300AW BAYHTFDW54A 54 2 64 70 66 70
BAYHTFDW72A 72 2 81 90 84 90
(a) Values do not include power exhaust accessory.

RT-PRC060N-EN 45
Electrical Data

Table 36. Electrical characteristics—compressor motor and condenser motor


Compressor Motors Condenser Fan Motors
Tons Unit Model No. Amps(a) Amps
No. Volts Phase rpm No. Phase hp
RLA LRA FLA LRA
E/GCC180A3 2 280–230 3 3500 26.9/24.9 208/180 2 3 1 4.8 20.0
15 E/GCC180A4 2 460 3 3500 12.1/10.8 98/75 2 3 1 2.5 10.1
E/GCC180AW 2 575 3 3500 10.1/8.8 75/60 2 3 1 1.9 8.0
E/GCC210A3 2 280–230 3 3500 28.9/28.9 208/208 2 3 1 4.8 20.0
17.5 E/GCC210A4 2 460 3 3500 12.1/12.1 98/98 2 3 1 2.5 10.1
E/GCC210AW 2 575 3 3500 10.1/10.1 75/75 2 3 1 1.9 8.0
E/GCC240A3 2 280–230 3 3500 35.7/29.6 240/240 2 3 1 4.8 20.0
20 E/GCC240A4 2 460 3 3500 16.8/15.5 140/130 2 3 1 2.5 10.1
E/GCC240AW 2 575 3 3500 13.6/11.8 107.6/93.7 2 3 1 1.9 8.0
E/GCC300A3 2 280–230 3 3500 50.5/35.7 245/240 2 3 1 4.8 20.0
25 E/GCC300A4 2 460 3 3500 19.5/16.8 125/140 2 3 1 2.5 10.1
E/GCC300AW 2 575 3 3500 15.5/13.6 100/107.6 2 3 1 1.9 8.0
(a) For Compressor Motors and Condenser Fan Motors: Amp draw for each motor; multiply value by number of motors to determine total amps.

Table 37. Electrical characteristics—evaporator fan motor


Standard Evaporator Fan Motor Oversized Evaporator Fan Motor

Tons Unit Model Number Amps Amps


No. Volts Phase hp No. Volts Phase hp
FLA LRA FLA LRA

E/GCC180A3 1 208–230 3 3 10.6 83.0 1 208–230 3 5 16.7 110.0

15 E/GCC180A4 1 460 3 3 4.8 35.5 1 460 3 5 7.6 56.0

E/GCC180AW 1 575 3 3 3.9 31.0 1 575 3 5 6.1 44.0

E/GCC210A3 1 208–230 3 5 16.7 110.0 1 208–230 3 7.5 24.2 150.0

17.5 E/GCC210A4 1 460 3 5 7.6 56.0 1 460 3 7.5 11.0 75.0

E/GCC210AW 1 575 3 5 6.1 44.0 1 575 3 7.5 9.0 60.0

E/GCC240A3 1 208–230 3 5 16.7 110.0 1 208–230 3 7.5 24.2 150.0

20 E/GCC240A4 1 460 3 5 7.6 56.0 1 460 3 7.5 11.0 75.0

E/GCC240AW 1 575 3 5 6.1 44.0 1 575 3 7.5 9.0 60.0

E/GCC300A3 1 208–230 3 7.5 24.2 150.0 1 208–230 3 10 30.8 227.2

25 E/GCC300A4 1 460 3 7.5 11.0 75.0 1 460 3 10 14.0 113.6

E/GBC300AW 1 575 3 7.5 9.0 60.0 1 575 3 10 11.0 90.8

Table 38. Electrical characteristics—combustion blower motor (gas heat units)


Heating Amps
Unit Model Number Heat hp rpm(a) Volts Phase
Stages FLA LRA
GCC180A,210A,240A,300A Low 2 1/15 3350/2800 208–230 1 0.36 0.72

GCC180A,210A,240A,300A Med/High 2 1/6 3300/2300 208–230 1 0.95 1.41

(a) High/Low Speed.

Table 39. Electrical characteristics—power exhaust


Amps
Tons Volts Phase Hp rpm
FLA LRA
280-230 1 3/4 1040 6.6 13.5
15-25 460 1 3/4 1040 3.2 8.4
575 1 3/4 1040 2.1 5.2

46 RT-PRC060N-EN
Jobsite Connections
Table 40. Typical number of wires

Thermostats

A N/A

B 3 Power Wires + 1 Ground Wire (three phase)

DISCONNECT
SWITCH
(BY OTHERS)

A
THERMOSTAT
ROOFTOP
UNIT

Notes:
• For specific wiring information, see the installation instructions.
• All wiring except power wire is low voltage.
• All customer supplied wiring to be copper and must conform to applicable electrical codes
and local electric codes. Wiring shown dotted is to be furnished and installed by the
customer.

RT-PRC060N-EN 47
Dimensional Data
Figure 1. Cooling with optional electrical heat — overview (gas/electric)

CONDENSATE DRAIN
REFRIGERANT GAUGE
CONNECTION
ACCESS

GAS CONNECTION(G*C UNIT ONLY) CUSTOMER POWER


CONDUIT CONNECTION(ALTERNATE)
GAS CONNECTION
(G*C UNIT-TBU GAS ONLY)
DISCONNECT
SWITCH ACCESS

Figure 2. Cooling with optional electrical heat — front and side views (gas/electric)

58 5/8”
58 5/8” 59 5/16”
39 13/16”

22 7/16”

4 1/2”
50 7/8”

82 1/4” 7 15/16”
(G*C UNITS ONLY)
13”
123 1/8”

NOTES:
1.THROUGH THE BASE GAS AND ELECTRICAL IS NOT STANDARD ON ALL UNITS.
2.VERIFY WEIGHT, CONNECTION, AND ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION.

48 RT-PRC060N-EN
Dimensional Data

Figure 3. Cooling with optional electrical heat units— plain view (gas/electric)
SUPPLY
RETURN

19-7/32"

72-3/32"
65-1/32"
73-17/32"
68-19/32"

14-21/32"
6-23/32" 7-23/32" 7-3/8"

14-3/8" 14-3/8"
THROUGH THE BASE ELECTRICAL
6-29/32" 36-3/32"

61-13/32"

74-3/16" 7-9/32"
(THRU-THE-BASE GAS-G*C UNITS ONLY)
122-29/32"

NOTES:
1.THROUGH THE BASE GAS AND ELECTRICAL PROVISIONS ARE STANDARD ON ALL UNITS.
2.VERIFY WEIGHT, CONNECTIONS, AND ALL OTHER DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSULATION.

Figure 4. Cooling with optional electrical heat units — back view (horizontal configuration) (gas/electric)
RETURN
SUPPLY

46 11/16”
25 11/16”

6”
5 1/2” 6”
26 15/16” 20 3/16”

82 1/16”

RT-PRC060N-EN 49
Dimensional Data

Figure 5. Cooling with optional electrical heat — roof curb (gas/electric)

116 7/8”
1”
2969 MM
25 MM
1 13/16”
46 MM 1”
1 1/2” (38 MM) PERIMETER 25 MM
22 1/4”
CURB FLANGE
565 MM 23 1/4”
1”
591 MM
25 MM
28 9/16”
7 7/6” 725 MM
189 MM

69 1/2”
1765 MM

14 1/16”
357 MM
2”
51 MM

7 1/2” 81”
191 MM 2057 MM
117 3/16”
2977 MM

Figure 6. Cooling with optional electrical heat — downflow duct connections—field fabricated (gas/electric)
1”
25 MM

19 5/16”
491 MM

73 7/16” 1”
1865 MM 25 MM

26 5/16”
668 MM
1”
66 1/2” 25 MM
1689 MM

1”
25.4 MM
CURB FLANGE
LONG SIDES
1 1/2”
38 MM
CURB FLANGE
SHORT SIDES
N
TUR
7 7/16” RE
189 MM

14 1/16”
357 MM
LY
PP
SU

NOTES:
• DUCT FLANGES MOUNT 7-7/16” DOWN INSIDE THE CURB ON THE 1-1½” CURB FLANGES.
• ROOFCURB IS INTENDED FOR DOWNFLOW USE ONLY.

50 RT-PRC060N-EN
Dimensional Data

Figure 7. Cooling with optional electric heat — downflow unit clearance (gas/electric)
CLEARANCE 36”
914 MM

UNIT OUTLINE
CLEARANCE 68”
1727 MM

CLEARANCE FORM
TOP OF UNIT 72” MM (1829 MM)

ROOF 76 1/2”
OPENING 1943 MM

CLEARANCE 48”
1219 MM
81”
2057 MM

CLEARANCE 60”
1524 MM

Figure 8. Cooling with optional electric heat — barometric relief and economizer (gas/electric)
ECONOMIZER OR
FAN BAROMETRIC MOTORIZED DAMPER HOOD
RELIFE

BAROMETRIC
RELIFE

58
9 3/8”(5 3/8”
FOR LOW LEAK)

13 5/8”

20 3/16” 18 5/16”
(20 5/8” FOR LOW LEAK) 68 3/8”
7 3/4”
5 15/16”

123 1/8” 86 15/16”

BACK VIEW OF UNIT ECONOMIZER LEFT VIEW OF UNIT

NOTES:
1. VERIFY WEIGHT, CONNECTION AND ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION.
2.BAROMETRIC RELIEF IS FOR USE WITH A DOWNFLOW ECONOMIZER ONLY.

RT-PRC060N-EN 51
Dimensional Data

Figure 9. Cooling with optional electric heat — manual damper (gas/electric)


FAN MANUAL DAMPER
HOOD

26 7/8”

24 7/8” 12 13/16”

123 1/8” 18 1/4” 86 15/16”

BACK VIEW OF UNIT LEFT VIEW OF UNIT

NOTE:
VERIFY WEIGHT, CONNECTION, AND ALL DIMENSIONS WITH INSTALLER DOCUMENTS BEFORE INSTALLATION.

52 RT-PRC060N-EN
Weights
Table 41. Maximum unit and corner weights (lb) and center of gravity dimensions (in.) cooling with optional electric
heat units only

Unit Model Weights (lb)(a) , (b) Corner Weights(c) Center of Gravity (in.)
Tons
No. Shipping Net A B C D Length Width
15 ECC180A 2175 1850 638 477 367 367 56 35

17.5 ECC210A 2180 1855 637 479 369 369 56 35

20 ECC240A 2185 1860 632 484 372 372 55 37

25 ECC300A 2221 1896 644 492 379 379 55 36


(a) Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
(b) Weights do not include additional factory or field installed options/accessories.
(c) Corner weights are given for information only. 15–25 ton models must be supported continuously by a curb or equivalent frame support.

Table 42. Maximum unit and corner weights (lb) and center of gravity dimensions (in.) gas/electric heat units only

Unit Model Weights (lb)(a) , (b) Corner Weights(c) Center of Gravity (in.)
Tons
No.
Shipping Net A B C D Length Width
15 GCC180A 2339 2013 649 508 398 459 55 37

17.5 GCC210A 2353 2028 653 511 399 464 55 37

20 GCC240A 2350 2025 643 512 403 466 55 37

25 GCC300A 2386 2061 671 524 393 472 55 36


(a) Weights are approximate. Horizontal and downflow unit and corner weights may vary slightly.
(b) Weights do not include additional factory or field installed options/accessories.
(c) Corner weights are given for information only. 15 to 25 ton models must be supported continuously by a curb or equivalent frame support.

Figure 10. Corner weights


CENTER OF GRAVITY
LENGTH

A B

CENTER OF
GRAVITY
WIDTH

D C
CENTER OF GRAVITY

Note: To calculate additional weight for accessories, see Accessory net weights table.

RT-PRC060N-EN 53
Weights

Table 43. Accessory net weight (lb)


Accessories E/GCC180 E/GCC210 E/GCC240 E/GCC300
Standard Economizer(a) , (b) 91 91 91 91

Low Leak Economizer - Downflow 105 105 105 105

Low Leak Economizer - Horizontal 115 115 115 115


Manual Outside Air Damper 15 15 15 15
Motorized outside Air Damper(c) 82 82 82 82

Power Exhaust 110 110 110 110

Barometric relief 40 40 40 40

Roof Curb 235 235 235 235

Oversized Motor

5 HP 2 – – –

7.5 HP – 20 20 –

10 HP – – – 60

Hail Guard 43 43 43 43
Through the Base Electrical 22 22 22 22

Disconnect 5 5 5 5
High Static Drive Kit(d) 2 2 2 2

Low Static Drive Kit 2 2 2 2

LP Gas Conversion 2 2 2 2
Electric Heaters(e) , (f)

18 kW (230 / 460 and 575 V) 36 / 29 – – –


36 kW (230 / 460 and 575 V) 41 / 35 41 / 35 41 / 35 41 / 35
54 kW (230 / 460 and 575 V) 48 / 40 48 / 40 48 / 40 48 / 40
72 kW (230 / 460 and 575 V) – 51 / 42 51 / 42 51 / 42
(a) Net weight should be added to unit weight when ordering factory-installed accessories.
(b) Weights for factory installed options and field installed accessories not listed are less than 5 lb.
(c) Downflow only.
(d) Not available on all models (see Fan Performance tables for specific models).
(e) For 600 V heaters net weights are same as 480 V heaters.
(f) To estimate shipping weight add 5 lb to net weight.

54 RT-PRC060N-EN
Mechanical Specifications
General
• Packaged rooftop units cooling, heating capacities, and efficiencies are AHRI Certified within scope
of AHRI Standard 340-360 (I-P) and ANSIZ21.47 and 10 CFR Part 431 pertaining to Commercial
Warm Air Furnaces
• Packaged rooftop units are dedicated downflow or horizontal airflow
• Operating range between 125°F and 40°F in cooling standard from the factory
• Factory assembled, internally wired, fully charged with R-410A, and 100 percent run tested to check
cooling operation, fan and blower rotation, and control sequence before leaving the factory
• Colored and numbered wring internal to the unit for simplified identification
• Units ETL listed and labeled, classified in accordance UL 1995/C 22.2, 236-15 5th Edition

Standard Features
Casing
• Zinc coated, heavy gauge, galvanized steel
• Weather-resistant baked enamel finish on phosphatized exterior surfaces
• Meets ASTM B117, 672 hour salt spray test
• Removable single side maintenance access panels
• Lifting handles in maintenance access panels (can be removed and reinstalled by removing no more
than three fasteners while providing a water and air tight seal)
• Exposed vertical panels and top covers in the indoor air section shall be insulated with a 1/2-inch, 1-
pound density foil-faced, fire-resistant, permanent, odorless, glass fiber material
• Base of unit shall be insulated with 1/2-inch, 1-pound density, foil-faced, glass fiber material
• Base pan shall have no penetrations within the perimeter of the curb other than the raised 1 1/8–inch
high downflow supply/return openings to provide an added water integrity precaution, if the
condensate drain backs up
• Downflow unit’s base pan shall have no penetrations within the perimeter of the curb other than the
raised 1 1/8–inch high supply/return openings to provide an added water integrity precaution, if the
condensate drain backs up
• Base of unit shall have provisions for forklift and crane lifting

Compressors
• All units have direct-drive, hermetic, scroll type compressors with centrifugal type oil pumps
• Suction gas-cooled motor with voltage utilization range of plus or minus 10 percent of unit
nameplate voltage
• Internal overloads standard with scroll compressors
• All models have phase monitors and Low and High Pressure Controls as standard

Controls
• Units factory-wired with necessary controls and contactor pressure lugs or terminal block for power
wiring
• External location available for mounting a fused disconnect device

Crankcase Heaters
• Offered as standard on 15 and 20 Ton
• Offered as field installed option on 25 Ton
• Band heaters provide improved compressor reliability by warming the oil to prevent migration during
off-cycles or low ambient conditions.

RT-PRC060N-EN 55
Mechanical Specifications

Discharge Line Thermostat


• A bi-metal element discharge line thermostat is installed as a standard option on the discharge line
of each system
• Provides extra protection to the compressors against high discharge temperatures in case of loss of
charge, extremely high ambient and other conditions which could drive the discharge temperature
higher
• Wired in series with high pressure control
• When discharge temperature rises above the protection limit, the bi-metal disc in the thermostat
switches to the off position, opening the 24 Vac circuit
• When temperature on the discharge line cools down, the bi-metal disc closes the contactor circuit,
providing power to the compressor

Evaporator and Condenser Coils


• Microchannel coils burst tested by manufacturer
• Microchannel condenser coils standard on all units
• Coils leak tested to ensure the pressure integrity
• Evaporator coil and condenser coil leak tested to 225 psig and pressure tested to 450 psig
• Sloped condensate drain pans are standard

Filters
Two inch standard filters shall be factory supplied on all units.

Gas Heat Section


• Progressive tubular heat exchanger, stainless steel burners and corrosion resistant steel
• Induced draft combustion blower shall be used to pull the combustion products through the firing
tubes
• Heater shall use a direct spark ignition (DSI) system
• On initial call for heat, the combustion blower shall purge the heat exchanger for 20 seconds before
ignition
• After three unsuccessful ignition attempts, entire heating system shall be locked out until manually
reset at the thermostat/zone sensor
• Units shall be suitable for use with natural gas or propane (field-installed kit)
• Units shall comply with the California requirement for low NOx emissions (gas heat only)

Indoor Fan
• Belt driven, FC centrifugal fans with adjustable motor sheaves
• Motors thermally protected
• Oversized motors available for high static application
• Indoor fan motors meet the U.S. Energy Policy Act of 1992 (EPACT)

Locking Safety Device


• Pressure switch monitoring allows for lockout in a situation where the switch is opened
• By monitoring the Y input as well as the pressure switches, advanced decision making can be made
to identify situations where faults/errors occur

Outdoor Fans
• Outdoor fan shall be direct-drive, statically and dynamically balanced, draw-through in the vertical
discharge position
• Fan motor(s) shall be permanently lubricated and shall have built-in thermal overload protection

Phase Monitor
• 3-phase line monitor module

56 RT-PRC060N-EN
Mechanical Specifications

• Protects against phase loss, phase imbalance and phase reversal indication
• Intended to protect compressors from reverse rotation
• Operating input voltage range of 180–600 Vac
• LED indicators for ON and FAULT
• No field adjustments
• Module will automatically reset from a fault condition

Refrigerant Circuits
• Each refrigerant circuit shall have a fixed orifice, service pressure ports, and refrigerant line filter
driers factory installed as standard
• An area shall be provided for replacement suction line driers

Refrigerant Pressure Control


All units include High and Low Pressure Cutouts as standard.

Unit Top
The top cover shall be double hemmed and gasket sealed to prevent water leakage.

Factory Installed Options


Complete Coat™ Microchannel Condenser Coil
• Cathodic epoxy type electro-disposition coating formulated for high edge build to a number of
different types of heat exchangers
• Coating provides excellent resistance and durability to corrosive effects of alkalies, acids, alcohols,
petroleum, seawater, salt air and corrosive environments
• Option is available on the microchannel type condenser coil

Multi-Speed Indoor Fan System


• Designed for use in applications for meeting the minimum requirement of CA Title 24
• Incorporates a multi-speed fan control to change the speed of the fan to 67% of full airflow based off
of compressor stages

Stainless Steel Heat Exchanger


• Gas heat exchanger shall be of tubular heat exchanger design
• Constructed from a minimum 409 grade stainless steel tubes and 439 stainless steel burners
• Shall have a 10-year warranty as standard (Gas/Electric only)

Third Side Fork Access


This option shall provide fork openings on condenser end of unit for ease of maneuvering unit through
narrow openings.

Factory or Field Installed Options


Barometric Relief
• Designed to be used on downflow units
• Barometric relief is an unpowered means of relieving excess building pressure

Condensate Overflow Switch


This option shall shut the unit down in the event that a clogged condensate drain line prevents proper
condensate removal from the unit.

RT-PRC060N-EN 57
Mechanical Specifications

Economizer (Standard) — Downflow


• Assembly includes fully modulating 0–100% motor and dampers, barometric relief, minimum
position setting, preset linkage, wiring harness with plug, fixed dry bulb and spring return actuator
• Barometric relief damper shall provide a pressure operated damper that shall be gravity closing and
shall prohibit entrance of outside air during the equipment “off” cycle

Electric Heaters
• Electric heat modules shall be available for installation within the basic unit
• Elements shall be constructed of heavy-duty nickel chromium elements internally delta connected
for 240 volt, wye connected for 480 and 600 volt
• Each heater package shall have temperature high limiting devices that are equipped with an auto-
resetting and a single operation switch operating as line break limits
• Single operation switch shall act as a backup limit control if the auto resetting switch fail to operate
appropriately
• All heaters shall be individually fused from the factory, where required, and shall meet all NEC and
CEC requirements when properly installed
• Power assemblies shall provide single-point connection
• Electric heat modules shall be UL listed or CSA certified
• If ordering the Through the Base Electrical option with an Electric Heater, the heater must be factory
installed.

Low Leak Economizer with Fault Detection & Diagnostics - Downflow


• Economizer meets the damper leakage requirements for ASHRAE 90.1, IECC, and California Title
24 standards (3 cfm/ft^2 at 1.0 in. w.g. for outside air dampers and 4 cfm/ft^2 for return dampers).
• Controller shall have the capability to provide the value of each sensor used in controlling the
economizer operation
• System status is also indicted for the following conditions:
– Free cooling available
– Economizer enabled
– Compressor enabled
– Heating Enabled
– Mixed air low limit cycle active
• Fault Detection and Diagnostic system detects the following faults:
– Air temperature sensor failure/fault
– Not economizing when conditions indicate system should be economizing
– Economizing when conditions indicate system should not be economizing
– Dampers are not modulating
– Excessive amounts of outside air are being introduced though the economizer
• Fault Detection and Diagnostic system is certified by the California Energy Commission as meeting
requirements of California Title 24 120.2(i)1 through 120.2(i)8 in accordance with Section 100(h)

Manual Outside Air Damper


The rain hood and screen shall provide up to 25% outside air.

Motorized Outside Air Damper


• Manually set outdoor air dampers shall provide up to 50% outside air
• Outdoor air dampers shall open to set position when indoor fan starts
• Damper shall close to the full closed position when indoor fan shuts down

58 RT-PRC060N-EN
Mechanical Specifications

Oversized Motors
Oversized motors shall be available for high static applications.
Note: 10 hp oversized motor is factory installed only.

Reference or Comparative Enthalpy


• Used to measure and communicate outdoor humidity
• Unit receives and uses this information to provide improved comfort cooling while using the
economizer
• Comparative Enthalpy measures and communicates humidity for both outdoor and return air
conditions, and return air temperature – unit receives and uses this information to maximize use of
economizer cooling, and to provide maximum occupant comfort control
• Reference or Comparative Enthalpy option shall be available when a factory or field installed
Downflow Economizer is ordered
• Option is available on all models

Through the Base Electrical with Disconnect Switch


• Three-pole, molded case, disconnect switch with provisions for through the base electrical
connections are available
• Installed in the unit in a water tight enclosure with access through a swinging door
• Factory wiring shall be provided from the switch to the unit high voltage terminal block
• Switch shall be UL/CSA agency recognized
Note: The disconnect switch will be sized per NEC and UL guidelines but will not be used in place of unit
overcurrent protection.

Through the Base Gas Piping


• Unit shall include a standard through the base gas provision
• Option shall have all piping necessary including, black steel, manual gas shut-off valve, elbows, and
union
• Manual shutoff valve shall include a 1/8” NPT pressure tap
• Assembly will require minor field labor to install (Gas/Electric Only)

Through the Base Utilities Access


• Electrical service entrance shall be provided allowing electrical access for both control and main
power connections inside the curb and through the base of the unit
• Option shall allow for field installation of liquid-tight conduit and an external field installed disconnect
switch

Field Installed Options


Crankcase Heaters
• Offered as standard on 15 and 20 Ton
• Offered as field installed option on 25 Ton
• Band heaters provide improved compressor reliability by warming the oil to prevent migration during
off-cycles or low ambient conditions.

Demand Control Ventilation with CO2 Sensor


• CO2 sensor shall have the ability to monitor the concentration (parts per million, ppm) of CO2
(Carbon Dioxide) in the air
• As the CO2 concentration changes, the outside air damper modulates to meet the current ventilation
needs of the zone

RT-PRC060N-EN 59
Mechanical Specifications

Economizer – Horizontal
The horizontal economizer shall contain the same features as the downflow economizer with the
exception of barometric relief.

Filters
Two inch standard filters shall be factory supplied on all units.

Hail Guards
Tool-less, hail protection quality coil guards are available for condenser coil protection.

Low and High Static Drive


The high static drive option shall allow the standard motor on all units to operate at various external
static pressure conditions.

Low Leak Economizer with Fault Detection & Diagnostics - Downflow


• Economizer meets the damper leakage requirements for ASHRAE 90.1, IECC, and California Title
24 standards (3 cfm/ft^2 at 1.0 in. w.g. for outside air dampers and 4 cfm/ft^2 for return dampers).
• Controller shall have the capability to provide the value of each sensor used in controlling the
economizer operation
• System status is also indicted for the following conditions:
– Free cooling available
– Economizer enabled
– Compressor enabled
– Heating Enabled
– Mixed air low limit cycle active
• Fault Detection and Diagnostic system detects the following faults:
– Air temperature sensor failure/fault
– Not economizing when conditions indicate system should be economizing
– Economizing when conditions indicate system should not be economizing
– Dampers are not modulating
– Excessive amounts of outside air are being introduced though the economizer
• Fault Detection and Diagnostic system is certified by the California Energy Commission as meeting
requirements of California Title 24 120.2(i)1 through 120.2(i)8 in accordance with Section 100(h)

Powered Exhaust
The powered exhaust shall provide exhaust of return air, when using an economizer, to maintain better
building pressurization.

Remote Potentiometer
The minimum position setting of the economizer shall be adjusted with this accessory.

Roof Curb – Downflow


• Roof curb shall be designed to mate with the downflow unit and provide support and a water tight
installation when installed properly
• Design shall allow field-fabricated rectangular supply/return ductwork to be connected directly to the
curb
• Curb shall be shipped knocked down for field assembly and shall include wood nailer strips

60 RT-PRC060N-EN
Notes

RT-PRC060N-EN 61
Notes

62 RT-PRC060N-EN
Notes

RT-PRC060N-EN 63
The AHRI Certified mark indicates Trane U.S. Inc. participation in the AHRI Certification program. For verification of individual certified products, go to
ahridirectory.org.

Trane - by Trane Technologies (NYSE: TT), a global innovator - creates comfortable, energy efficient indoor
environments for commercial and residential applications. For more information, please visit trane. com or
tranetechnologies.com.

Trane has a policy of continuous product and product data improvements and reserves the right to change design and specifications without notice. We
are committed to using environmentally conscious print practices.

RT-PRC060N-EN 03 Dec 2022


Supersedes RT-PRC060M-EN (June 2020) ©2022 Trane