DSEGenset

DSE8610 ENVIRONMENTAL TESTING STANDARDS

ELECTRO MAGNETIC COMPATIBILITY


AUTO START LOAD SHARE MODULE BS EN 61000-6-2
EMC Generic Immunity Standard for the
Industrial Environment
BS EN 61000-6-4
EMC Generic Emission Standard for the
Industrial Environment
FEATURES ELECTRICAL SAFETY
BS EN 60950
Safety of Information Technology Equipment,
including Electrical Business Equipment

TEMPERATURE
BS EN 60068
Ab/Ae Cold Test -30oC
The DSE8610 is an easy to use The event log will record 250 events KEY LOAD SHARE FEATURES: BS EN 60068-2-2
multi-generator loadshare system, to facilitate easy maintenance. An • Peak lopping Bb/Be Dry Heat +70oC
designed to synchronise up to 32 extensive number of fixed and • Sequential set start VIBRATION
generators including electronic and flexible monitoring, metering and • Manual voltage/frequency BS EN 60068-2-6
non-electronic engines. protection features are included adjustment Ten sweeps in each of three major axes
5Hz to 8Hz @ +/-7.5mm, 8Hz to 500Hz @ 2gn
as well as comprehensive • R.O.C.O.F. and vector shift
The DSE8610 monitors the communication and system • Generator load demand HUMIDITY
generator and indicates operational expansion options. • Automatic hours run balancing BS EN 60068-2-30
Db Damp Heat Cyclic 20/55oC @ 95% RH
status and fault conditions, • Mains (Utility) de-coupling 48 Hours
automatically starting or stopping Using the DSE PC Configuration • Mains (Utility) de-coupling BS EN 60068-2-78
the engine on load demand or fault Suite Software allows easy test mode Cab Damp Heat Static 40oC @ 93% RH
48 Hours
condition. alteration of the operational • Dead bus sensing
sequences, timers and alarms. With • Bus failure detection SHOCK
System alarms are annunciated on all communication ports capable of • Direct governor and AVR control BS EN 60068-2-27
Three shocks in each of three major axes
the LCD screen (multiple language being active at the same time, the • Volts and frequency matching 15gn in 11mS
options available), illuminated LED DSE8610 is ideal for a wide variety • kW and kV Ar load sharing
DEGREES OF PROTECTION
and audible sounder. of demanding load share PROVIDED BY ENCLOSURES
applications. BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.

COMPREHENSIVE FEATURE LIST TO SUIT A WIDE VARIETY


OF LOAD SHARE APPLICATIONS
DSE2131 MODEM MODBUS PC
DSE2133
DSE2152
DSE2130 11 6 4
DSE2157
DSE2548 232 485

DSENET ®
RS232 AND USB USB CONFIGURABLE DC OUTPUTS ANALOGUE EMERGENCY DC POWER
EXPANSION RS485 PORT HOST INPUTS SENDERS STOP SUPPLY 8-35V

ETHERNET +

DEUTZ
DSE8610 MSC
ISUZU
PERKINS
CATERPILLAR
MTU
7 8610 8610 8660 VOLVO
OTHER
CUMMINS
SCANIA

BUS VOLT FREE GENERATOR SENSING FUEL & CRANK CHARGE ELECTRONIC MAGNETIC
SENSING OUTPUTS OUTPUTS ALTERNATOR ENGINES PICK-UP
FLEXIBLE WITH CAN

CURRENT VOLTS D+
+ W/L

1ph 2 1ph 1ph


2ph 2ph 2ph
3ph 3ph 3ph
N N N

ISSUE 3
®

DSEGenset

DSE8610 SPECIFICATION

DC SUPPLY
AUTO START LOAD SHARE MODULE CONTINUOUS VOLTAGE RATING
8 V to 35 V continuous

CRANKING DROPOUTS
Able to survive 0 V for 50 mS, providing
supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
FEATURES without the need for internal batteries

MAXIMUM OPERATING CURRENT


460 mA at 12 V, 245 mA at 24 V

MAXIMUM STANDBY CURRENT


375 mA at 12 V, 200 mA at 24 V

CHARGE FAIL/EXCITATION RANGE


0 V to 35 V

OUTPUTS
OUTPUT A (FUEL)
15 A DC at supply voltage

OUTPUT B (CRANK)
15 A DC at supply voltage

OUTPUTS C & D
8 A AC at 250 V AC (Volt free)

AUXILIARY OUTPUTS E,F,G


2 A DC at supply voltage

GENERATOR & BUS


VOLTAGE RANGE
15 V to 333 V AC (L-N)

FREQUENCY RANGE
3.5 Hz to 75 Hz

MAGNETIC PICK-UP
VOLTAGE RANGE
+/- 0.5 V to 70 V

FREQUENCY RANGE
10,000 Hz (max)
KEY FEATURES • Fixed and flexible LED indicators • Worldwide language support BUILT-IN GOVERNOR CONTROL
• Comprehensive loadshare • Event log (250) • Configuration Suite PC software MINIMUM LOAD IMPEDANCE
1000Ω
capabilities • Engine protection • Direct USB connection to PC Fully isolated
• Configurable inputs (11) • Fault condition notification to • Ethernet monitoring
• Configurable outputs (8) a designated PC • USB host GAIN VOLTAGE
0 V to 10 V DC
• Voltage measurement • Protected front panel • Data logging & trending Fully isolated
• Built-in governor and AVR programming
OFFSET VOLTAGE
control • PC configuration EXPANSION DEVICES +/- 10 V DC
• kW overload alarms • Fully configrable • DSE2131 Ratiometric Input Fully isolated
• Comprehensive electrical • SMS alert messaging Expansion Module
BUILT-IN AVR CONTROL
protection • Compatible with DSE8700 Series • DSE2133 RTD/Thermocouple MINIMUM LOAD IMPEDANCE
• Magnetic pick-up Input Expansion Module 1000Ω
• Electronic engine capability KEY BENEFITS • DSE2152 Analogue Output Fully isolated

• RS232 & RS485 remote • RS232 & RS485 can be used Expansion Module GAIN VOLTAGE
communications at the same time • DSE2548 LED Expansion 0 V to 10 V DC
Fully isolated
• Modbus RTU • DSENet connection for Module
• PLC functionality system expansion • DSE2130 Input Expansion OFFSET VOLTAGE
• Multi event exercise timer • PLC functionality Module +/- 10 V DC
Fully isolated
• Back-lit LCD 4-line text display • Auto voltage sensing • DSE2157 Output Expansion
• Multiple display languages • Five step dummy load support Module DIMENSIONS
OVERALL
• Automatic start/Manual start • Five step load shedding support • DSE124 CAN/MSC Extender 240 mm x 172 mm x 57 mm
• Audible alarm • High number of inputs and 9.4” x 6.8” x 2.2”
• Reduced file transfer time outputs
PANEL CUTOUT
220 mm x 160 mm
8.7” x 6.3”
RELATED MATERIALS
TITLE PART NO’S MAXIMUM PANEL THICKNESS
8 mm
DSE8610 Installation Instructions 053-069 0.3”
DSE8610 Operator Manual 057-115
DSE8600 PC Configuration Suite Manual 057-119 STORAGE TEMPERATURE RANGE
DSE8660 Date Sheet 055-086 -40 oC to +85 oC

DEEP SEA ELECTRONICS PLC UK DEEP SEA ELECTRONICS INC USA


Highfield House, Hunmanby Industrial Estate, Hunmanby YO14 0PH 3230 Williams Avenue, Rockford, IL 61101-2668 USA
TELEPHONE +44 (0) 1723 890099 FACSIMILE +44 (0) 1723 893303 TELEPHONE +1 (815) 316 8706 FACSIMILE +1 (815) 316 8708
EMAIL sales@deepseaplc.com WEBSITE www.deepseaplc.com EMAIL sales@deepseausa.com WEBSITE www.deepseausa.com

Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649 055-083/12/11 (3)
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457