Comet 40-150kVA: Uninterruptible Power Supply
Comet 40-150kVA: Uninterruptible Power Supply
c o m
KA2
                                                                UPS
                                                                Input                                                load
                                                                          KA1                           K3N
QF1
⁄ı Í
                                                           EMERGENCY
                                                           POWER OFF
fault
CO M E T
                                                                                                                 MG E
                                                                                                                 UPS SYSTEMS
                                                     Comet 40-150kVA
                                                   Uninterruptible Power Supply
                                                                                                        Comet
                                                                                                    40 - 150kVA
              Revision History
                       Comet 40-150kVA UPS Installation and User Manual 86-160310-00
86-160310-00 E00 i
                       WARNING                    Opening enclosures expose hazardous voltages. Always refer service to qualified
                                                  personnel only.
                       ATTENTION                  L'ouverture des cabinets expose des tensions dangereuses. Assurez-vous toujours que le
                                                  service ne soit fait que par des personnes qualifiees.
                       WARNING                    As standards, specifications, and designs are subject to change, please ask for confirma-
                                                  tion of the information given in this publication.
                       ATTENTION                  Comme les normes, spécifications et produits peuvent changer, veuillez demander
                                                  confirmation des informations contenues dans cette publication.
                       WARNUNG!                   Normen, Spezifizierungen und Pläne unterliegen Anderungen. Bitte verlangen Sie eine
                                                  Bestätigung über alle Informationen, die in dieser Ausgabe gemacht wurden.
                       NOTE                       This equipment has been tested and found to comply with the limits for a Class A digital
                                                  device, pursuant to part 15 of the FCC rules. These limits are designed to provide
                                                  reasonable protection against harmful interference when the equipment is operated in a
                                                  commercial environment.
                                                  This equipment generates, uses, and can radiate radio frequency energy and, if not
                                                  installed and used in accordance with the instruction manual, may cause harmful interfer-
                                                  ence to radio communications. Operation of this equipment in a residential area is likely to
                                                  cause harmful interference in which case the user will be required to correct the
                                                  interference at user's own expense.
                       WARNING                    To reduce the risk of fire or electric shock, install in a controlled indoor environment free of
                                                  conductive contaminants.
                       ATTENTION                  Pour réduire le riske d'inccendie ou d'électrocution, installer dans une enciente intérieure
                                                  contrôlée en température et humidité et sans contaminants conducteurs.
                       WARNUNG!                   Um die Gefahr von Feuer und elektrischem Schock zu reduzieren, muss das Gerät in
                                                  einem temperatur - und feuchtigkeitskontrollierten Raum, frei von leitungsfähigen
                                                  Verunreinigungen, installiert werden. Dieses Gerät ist nur für die Installation an einem
                                                  Ort mit qeingeschränkter Zugangserlaubnis vorgesehen.
                                                  Diese Ausrüstung ist nur für Anlagen in einem EINGESCHRäNKTEN ZUGRIFF STANDORT
                                                  bestimmti.
              Safety of Persons
                       ◗    The UPS has its own internal power source (the battery). Consequently, the power outlets may be
                            energized even if the UPS is disconnected from the AC power source.
                       ◗    The battery supplied with the UPS contains small amounts of toxic materials. To avoid accidents, the
                            directives listed below must be observed:
                            - Never burn the battery (risk of explosion).
                            - Do not attempt to open the battery (the electrolyte is dangerous for the eyes and skin).
                            - Comply with all applicable regulations for the disposal of the battery.
                            - Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
                              Precautions must be taken for all handling: remove watches, rings, bracelets and any other metal
                              objects, use tools with insulated handles.
                            - Do not lay tools or metal parts on top of batteries.
Product Safety
              Special Precautions
                       ◗    The UPS connection instructions and operation described in the manual must be followed in the indicated
                            order.
                       ◗    Check that the indications on the rating plate correspond to your AC powered system and to the actual
                            electrical consumption of all the equipment to be connected to the UPS.
                       ◗    Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be
                            energized for a period of 24 hours, at least once every 3 months (for a normal storage temperature less
                            than 25°C). This charges the battery, thus avoiding possible irreversible damage.
iv 86-160310-00 E00
                                                  Revision History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .i
                                                  IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . .ii
                                                  Certification Standards - Three Phase UPS . . . . . . . . . . . . . . . . . . . .iii
                                                  Safety of Persons . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
                                                  Product Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
                                                  Special Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .iii
                                                  CAUTION: Record All Serial Numbers! . . . . . . . . . . . . . . . . . . . . . .c iv
                                                  Symbol Usage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .c vi
                                                  Section Descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .c vi
             Section 2           Installation
                                 2.0              Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1
                                 2.1              Receiving . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1
                                 2.2              Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 1
                                 2.3              Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 2
                                 2.4              Prerequisite to Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 2
                                         2.4.1    Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 2
                                         2.4.2    Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 3
                                         2.4.3    Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 3
                                 2.5              Installation Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4
                                         2.5.1    Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4
                            2.6              Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4
                                    2.6.1    Main AC Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4
                                    2.6.2    Bypass AC Input (Optional) . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 4
                                    2.6.3    Remote Emergency Power Off (REPO) . . . . . . . . . . . . . . . . . . .2 — 4
                                    2.6.4    AC Output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 5
                                    2.6.5    Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2 — 5
         Section 3          Operation
                            3.0              Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1
                            3.1              Power Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 1
                                    3.1.1    Power Flow, For Normal Operation . . . . . . . . . . . . . . . . . . . . . . .3 — 1
                                    3.1.2    Power Flow, For On Battery Operation . . . . . . . . . . . . . . . . . . . .3 — 1
                                    3.1.3    Power Flow, For Bypass Operation . . . . . . . . . . . . . . . . . . . . . . .3 — 2
                            3.2              Graphical User Interface, Controls and Indicators . . . . . . . . . . . .3 — 2
                            3.3              Startup Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5
                                    3.3.1    Preliminary Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5
                                    3.3.2    Powering Up the Comet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5
                            3.4              Inverter Manual Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 5
                            3.5              Operating Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6
                                    3.5.1    Normal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6
                                    3.5.2    Operation on Battery Power . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6
                                    3.5.3    Battery Duration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6
                                             3.5.3.1 Return to AC Power . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 6
                                    3.5.4    Overload . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 7
                            3.6              Emergency Shutdown Using EPO/REPO . . . . . . . . . . . . . . . . . .3 — 8
                            3.7              Forced Transfer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 8
                            3.8              Maintenance Bypass . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 8
                                    3.8.1    From Normal Maintenance Bypass Mode . . . . . . . . . . . . . . . . . .3 — 8
                                    3.8.2    From Maintenance Bypass to Normal Mode . . . . . . . . . . . . . . . .3 — 9
                            3.9              Shutdown Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 10
                                    3.9.1    Inverter Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 10
                                    3.9.2    Powering Down . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 10
                            3.10             Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3 — 10
         Section 4          Maintenance
                            4.0              Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1
                            4.1              Battery Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1
                            4.2              Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 1
                            4.3              Replacement Parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4 — 2
              Figures
                                 figure description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
                                 1-1:     Comet 40-80kVA. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
                                 1-2:     Comet 100-150kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 1
                                 1-3:     Single Line Diagram for the Comet 40-80kVA . . . . . . . . . . . . . . . . . . . . .1 — 2
                                 1-4:     Single Line Diagram for the Comet 100-150kVA . . . . . . . . . . . . . . . . . . .1 — 2
                                 1-5:     Front View of the Comet 40-80kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 4
                                 1-6:     Rear View of the Comet 40-80kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 5
                                 1-7:     Front View of the Comet 100-150kVA . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 6
                                 1-8:     Front View of Communications Components for
                                          the Comet 100-150kVA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 7
                                 1-9:     Pinouts on the DB15 Connector . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 10
              Tables
                                 table description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .page
                                 1-1:     Comet 40-150kVA Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 8
                                 1-2:     UPS Manager Dry Contact Interface . . . . . . . . . . . . . . . . . . . . . . . . . . .1 — 10
Reorder Form
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
____________________________ ______________________________
NOTES:
86-160310-00 E00 cv
Symbol Usage
This manual uses five icon symbols with text to convey important information and tips.
                            WARNING             Information provided to protect the user and service personnel against safety
                                                hazards and/or possible equipment damage.
                            CAUTION             Information provided to protect the user and service personnel against possible
                                                equipment damage.
                            ELECTRICAL          Information provided to protect the user and service personnel against possible
                                                electrical hazard and equipment damage.
         Section Descriptions
                  1    System Description and Specifications
                  Provides a general description of the Comet 40-150kVA Uninterruptible Power Systems major components,
                  available options, and system specifications.
2 Installation
                  Installation of the Comet 40-150kVA UPS, which include receiving, handling, and storage procedures;
                  prerequisites to installation; installation procedures; and startup procedures.
3 Operation
                  Important information on the Comet 40-150kVA systems’ operation procedure sequences; for normal, on
                  battery, and bypass operation, with descriptions of the control and display indicators.
                            NOTE                For details on the Graphical User Interface (GUI) display, please refer to
                                                manual 86-160316-00.
4 Maintenance
                  Preventive maintenance and battery safety instructions for Comet 40-150kVA UPS, and information about
                  replacement parts, and customer service.
                            NOTE                This manual provides technical information required for operation and
                                                maintenance of the Comet 40-150kVA Uninterruptible Power System (UPS).
                                                Please read this manual before operating the Comet 40-150kVA equipment.
                                                Please retain this manual for future reference.
1.0 Scope
                       Provides a general description of the Comet 40-150kVA Uninterruptible Power Systems major components,
                       available options, and system specifications.
                       The Comet family consists of compact, high-efficiency Uninterruptible Power Systems which are available in power
                       ratings from 40-150kVA, and are optimized for compatibility with nonlinear computer-type loads. Computer-aided
                       UPS diagnostics and modular construction assure that any required service can be identified and completed rapidly.
                       Remote system monitoring, remote annunciation of UPS performance signals and communication capabilities allow
                       total control of the UPS by its user. See Figures 1-1 and 1-2.
                       The Comet UPS and its auxiliary equipment are designed for installation in a room where humidity and temperature
                       can be controlled. The recommended and maximum environmental parameters are listed in the Specifications
                       section of this document.
                                  UPS
                                  Input                                                load
                                            KA1                           K3N                                                                  KA2
                                                                                                                                     UPS
                                                  QF1                                                                                Input                                                load
                                                                                                                                               KA1                           K3N
QF1
⁄ı Í
⁄ı Í
                             EMERGENCY
                             POWER OFF
                                                                                                                                EMERGENCY
                                                                                                                                POWER OFF
fault
fault
                                                                                CO M E T
                                                                                                                                                                                   CO M E T
                                                                                   MG E
                                                                                   UPS SYSTEMS
                                                                                                                                                                                      MG E
                                                                                                                                                                                      UPS SYSTEMS
                  Figure 1-3, and 1-4 show single-line diagrams of a typical UPS system installation. During normal operation,
                  utility power (Main Input) is supplied to the UPS Rectifier where it is converted to DC voltage. The Inverter
                  converts the DC voltage from the Rectifier to three-phase regulated AC voltage, which supplies the critical load.
                  During power failure conditions, the Inverter is supplied by the stored energy in the batteries, and the load is
                  powered continuously with no disruption.
UPS CABINET
                                                                         STATIC SWITCH
                          BYPASS                      KA2
                         AC INPUT                                                                            SR1
                       (OPTIONAL)
                                                      KA1                                              K3N           TO
                             MAIN
                                                                                                                     CRITICAL
                         AC INPUT
                                                             INPUT                            OUTPUT                 LOAD
                                                             FUSES   RECTIFIER    INVERTER    FUSES
                                                                     BATTERY
                                                                     CABINET      QF1
BATTERY
UPS CABINET
                                                                         STATIC SWITCH
                         BYPASS                       KA2
                        AC INPUT                                                                             SR1
                                                       KA1                                             K3N            TO
                            MAIN
                                                                                                                      CRITICAL
                        AC INPUT
                                                             INPUT                            OUTPUT                  LOAD
                                                             FUSES   RECTIFIER     INVERTER   FUSES
                                                                      BATTERY
                                                                      CABINET     QF1
BATTERY
The following is a description of the cabinets and major components. Refer to Figures 1-5 to 1-8.
                       UPS Cabinet                         Converts the input AC power to direct current and charges the battery. DC power
                                                           is converted back to clean AC power by the inverter for the critical load. Section
                                                           3 describes the operation in detail.
                       Auxiliary Cabinet                   Performs the voltage conversion for the input AC and/or bypass AC using step-
                                                           up and/or step-down transformers.
                       Battery Cabinet                     The battery cabinet stores energy for use by the Inverter. The stored energy is
                                                           utilized in the event that the AC input power from the utility source fails, or falls
                                                           outside of acceptable tolerances. The internal Battery Charger maintains the
                                                           charge of the battery system. The DC output voltage of the charger is tempera-
                                                           ture regulated to ensure an optimal charge voltage. If a customer supplied battery
                                                           system is to be used, an external battery charger may be necessary.
                                                           The standard battery system is housed in a separate enclosure. For systems where
                                                           additional back-up time is required, up to two (2) additional battery cabinets are
                                                           available.
                       Rectifier                           Converts the AC input voltage from the utility source into a DC voltage, supplying
                                                           the Inverter.
                       Inverter                            Converts the DC voltage supplied from either the Rectifier or the battery system into
                                                           a three-phase AC voltage. An AC output filter is used to achieve a computer-grade
                                                           sinewave output voltage waveform, with a total harmonic distortion of less than 2%
                                                           under linear-load conditions.
                       Static Switch                       Transfers the load between the Inverter output and the bypass AC source without
                                                           interrupting the supply of power to the load, allowing the load to continue
                                                           operation in the event of a UPS fault. The Static Switch circuit assures that
                                                           voltage from the UPS output cannot be fed back to the utility input lines.
                       Battery System                      Stores energy for use by the Inverter. The stored energy is utilized in the event
                                                           that the AC input power from the utility source fails, or falls outside of acceptable
                                                           tolerances. The internal Battery Charger maintains the charge of the battery
                                                           system. The DC output voltage of the charger is temperature regulated to ensure
                                                           an optimal charge voltage. If a customer supplied battery system is to be used,
                                                           an external battery charger may be necessary.
8 Inverter Assembly
9 Feedback PCA
11 Interconnect PCA
17 Battery Connections
                                                                                       19
                                                                                            (TB2) Output Terminal Block
                                                                                       23   Neutral Busbar
                                         01
                                 TOP ENTRY
                            CONDUIT LANDING
                                       TOP ENTRY
                                        CHANNEL
                                      T1 INPUT
                                 TRANSFORMER
                                    (OPTIONAL)
                                    T2 OUTPUT
                                 TRANSFORMER
                                    (OPTIONAL)
7 Rectifier
8 Static Switch
9 Inverter Assembly
10 Chopper Assembly
11 Interconnect PCA
12 Ground Busbar
14 Charger PCA
16 DC Cap Modules
Figure 1-8: Front View of Communications Components for the Comet 100-150kVA.
                       COMMUNICATION
                                PCAs
1.3 Specifications
                  The Comet 40-150kVA UPS systems are rated for various input and output voltages (see Table 1-1). When
                  different input and/or output voltages are specified, optional transformers provide step up/down functions as
                  required.
                                                                                INPUT
                                     INPUT       OUTPUT OUTPUT               CURRENT            TOTAL         NET        HEAT
                                    VOLTAGE      VOLTAGE CURRENT              (on UPS/          WIDTH      WEIGHT        LOSS
                                      (VAC)       (VAC)  (Amperes)           on bypass)        (in/mm)      (lb/kg)     (Btu/hr)
                                                                              (Amperes)
                  40kVA/32 kW          208          208           111          102/111        32.75/832   1760/800      13500
                                       220          220           105          96/105         32.75/832   1760/800      13500
                                       480          208           111          43/111         32.75/832   1360/617      12135
                                       480          480            48           43/48         32.75/832    880/400       8220
                                       600          208           111          35/111        60.00/1524   2820/1279     13500
                  50kVA/40 kW          208          208           139         127/139         32.75/832   1760/800      16873
                                       220          220           131         120/131         32.75/832   1760/800      16873
                                       480          208           139          54/139         32.75/832   1360/617      15169
                                       480          480            60           54/60         32.75/832    880/400      10276
                                       600          208           139          44/139        60.00/1524   2820/1279     16873
                  65kVA/52 kW          208          208           180         162/180         32.75/832   2115/960      17552
                                       220          220           170         153/170         32.75/832   2115/960      17552
                                       480          208           180          70/180         32.75/832   1590/721      15433
                                       480          480            78           70/78         32.75/832    970/440       11328
                                       600          208           180          57/180        60.00/1524   2910/1320     17552
                  80kVA/64 kW          208          208           222         200/222         32.75/832   2115/960      21603
                                       220          220           210         190/210         32.75/832   2115/960      21603
                                       480          208           222          86/222         32.75/832   1590/721      21603
                                       480          480            96           86/96         32.75/832    970/440      13992
                                       600          208           222          70/222        60.00/1524   2910/1320     21603
                  100kVA/80 kW         208          208           278         256/278        69.50/1765   3400/1543     28300
                                       220          220           263         242/263        69.50/1765   3400/1543     28300
                                       480          208           278         109/278        42.75/1086   2450/1112     22278
                                       480          480           120         109/120        42.75/1086   1460/662      15420
                                       600          600            96           89/96        96.00/2438   3700/1678     28300
                                       600          208           278          91/278        69.50/1765   3400/1543     28300
                  125kVA/100 kW        208          208           347         316/347        69.50/1765   3400/1543     38247
                                       220          220           328         298/328        69.50/1765   3400/1543     38247
                                       480          208           347         134/347        42.75/1086   2450/1112     30662
                                       480          480           150         134/150        42.75/1086   1460/662      20804
                                       600          600           120         109/120        96.00/2438   3700/1678     38247
                                       600          208           347         109/347        69.50/1765   3400/1543     38247
                  150kVA/120 kW        208          208           417         378/417        69.50/1765   3400/1543     50759
                                       220          220           394         375/394        69.50/1765   3400/1543     50759
                                       480          208           417         160/417        42.75/1086   2450/1112     41560
                                       480          480           180         160/180        42.75/1086   1460/662      26351
                                       600          600           145         131/145        69.50/1765   3700/1678     50759
                                       600          208           417         131/417        96.00/2438   3400/1543     50759
                       NOTES:
                       1. Total width, weight, and heat loss are for system line-up excluding battery cabinets.
                       2. Data does not include battery data; refer to the installation drawings supplied with your equipment.
                       Consult the installation drawings provided with your equipment.
                                 Total harmonic
                                 distortion (THD)                <2% (linear load)
<3% (for 100% non-linear load with a crest factor of less than 3.0)
1.3.3 DC Ratings
Altitude <3000 ft. (1000m), up to 6000 ft. (<2000 m) @ 28° C (82°F) maximum
                  The UPS Manager connector enables communication with the most common computer systems (AS/400,
                  NOVELL, etc.), or with the optional "UPS Manager UM1" software.
                                                           DB15 -pin
                                                           connector
                           PIJO PC board                        5
                                                NO              8    Operation on Inverter
                                                NC
                                                                     Operation on
                                                NO
                           Breaking             NC              6    Bypass
                           capacity of
                           contacts is:                         10
                                                                                                    8 7 6 5 4 3 2 1
                           P = 3va              NO              9    Operation on Battery
                           V = 30VDC max.       NC              11
                                                                                                    15 14 13 12 11 10 9
                           I = 100mA max.
                                                                13
                                                               14
                                                                     UPS Remote Inverter Shutdown
                                                                     (3 to 15 VDC voltage signal)
                                                                4
GROUND 1
                  Please note that once the UPS remote inverter shutdown signal is applied, the Inverter stops and the
                  load transfers to bypass after a predetermined time (typically 2 minutes).
                       Options are available for the Comet 40-150kVA UPS’s. Most options must be specified at the time of the original
                       order for factory installation. Some options can be field installed; contact your MGE Sales Representative for
                       further information.
                       Auxiliary Cabinet                   The auxiliary cabinet may provide one or both of the following options: an input
                                                           bypass step up/down transformer, and an output distribution panel. An output
                                                           distribution panel provides connection points for distribution of AC power to
                                                           computers and other equipment. Also available are external maintenance bypass
                                                           cabinets.
                       Extended Battery Cabinets Up to two Extended Battery Cabinets are available to provide extra back-up time
                                                 during power outage.
                       Isolated Redundant System This option is used to connect the static switch and maintenance bypass to a
                                                 reserve UPS source for redundancy
                       UPS without Standard                This option allows for the connection of a customer-supplied battery system to
                       Battery Subsystem                   the UPS.
                       (External Batteries)
                       Communication Options               Communication options may be used simultaneously on the Comet, thus
                                                           enabling communication with a wide number of computers and control devices.
                       Monitor Plus                        Mini terminal for control and display of system parameters. This option can be in-
                                                           stalled locally or remotely.
Contact 5 This option offers communication of five different signals via dry relay contacts:
                                                           ◗   Load on UPS
                                                           ◗   Load on Bypass
                                                           ◗   Operation on Battery
                                                           ◗   Low Battery Shutdown Warning
                                                           ◗   Summary Alarm (major or minor faults)
U-Talk This option manages an RS232 serial interface using an ASCII protocol.
                       Solution-Pac                        ◗   Automatic file shutdown during power outage or severe brownout for stand-
                                                               alone systems.
                                                           ◗   Automatic file shutdown for network servers plus additional monitoring and
                                                               network communication functions.
1 — 13 86-160310-00 E00
2.0 Scope
                       Installation of the Comet 40-150kVA UPS, which include receiving, handling, and storage procedures; prerequisites
                       to installation; installation procedures; and startup procedures.
                                 CAUTION            Scheduling of the MGE Field Service Engineers typically should be done 7 to 10
                                                    days before they are required on-site. If the startup of the product is critical to
                                                    maintaining your schedule, please call the MGE toll free telephone number at
                                                    1-800-438-7373 for assistance.
2.1 Receiving
                       Before accepting the shipment from the freight carrier, inspect the exterior surfaces of shipping container(s),
                       packaging, and equipment for damage that may have occurred during transit. If the shipping containers or
                       equipment show evidence of damage, note the damage on the receiving document (bill of lading) prior to
                       signing for receipt of equipment. Verify that the equipment nameplate corresponds with the equipment ordered.
                       Damage claims should be filed directly with the carrier. Replacements for damaged components can be ordered
                       by calling 1-800-438-7373.
2.2 Handling
                       Any equipment shipped on a shipping pallet is intended for handling by a pallet jack or a fork lift truck. Move
                       the equipment to its intended location while still mounted on its pallet, and remove the equipment from the pallet
                       when it is near its final location. See Figure 2-1.
                       The Comet UPS and optional auxiliary cabinets have heavy-duty casters to allow the equipment to be moved
                       into position easily once they have been unloaded from the shipping truck. Once the UPS is in its final position,
                       the leveling jacks on all four-bottom corners should be lowered to secure the cabinet in place. Refer to the
                       installation drawings that were shipped with the cabinets.
                       Battery cabinet weighing less than 3000 lbs. are equipped with casters for ease of handling on site. For
                       shipment, these cabinets are mounted on pallets to prevent movement on ramps and other inclined surfaces.
                       A forklift (4000 lbs capacity or greater) is required to remove the battery cabinet from its pallet. The 42" battery
                       cabinets should be lifted from the side only. For battery cabinets weighing more than 3000 lbs., no casters are
                       provided, and therefore must be moved by forklift only.
                  If the equipment is to be stored for more than three months before installation, it should be unpacked and
                  connected to an AC input source to allow the batteries to be recharged. Refer to the installation instructions that
                  follow, and the installation drawings.
2.3 Storage
                  If the equipment is to be stored prior to installation, it should be stored in a cool, dry, well-ventilated location
                  that is protected against rain, splashing water, chemical agents, etc. The equipment should be covered with a
                  tarpaulin or plastic wrapper to protect it against dust, dirt, paint, or other foreign materials.
                            IMPORTANT           Batteries should be stored no longer than three (3) months at approximately 25°C
                                                (77° F) prior to recharging. Too high or too low a temperature will damage batteries.
                                                Exceeding the recommended ambient storage temperature will reduce back-up time
                                                and may adversely affect life.
                  This section provides more information for a successful and efficient installation of the Comet 40-150kVA.
                  Installation of equipment must be handled by skilled technicians and electrician's familiar with the requirements
                  of high energy electrical equipment. The installation must comply with the requirements of the National
                  Electrical Code (NEC, ANSI/NFPA 70, latest issue) and with local codes and requirements as applicable. We
                  strongly recommend contracting MGE Customer Support Services for startup. Do not allow unqualified
                  personnel to handle or operate the equipment.
2.4.1 Environmental
                  The Comet 40-150kVA UPS is intended for use in an environment where control of temperature and humidity is
                  provided. The maximum operating and recommended environmental parameters are provided in the Specifications
                  section of this document.
                  The Comet UPS generates heat and exhausts air through the top portion of its enclosure. Heat loss data is
                  provided in Table 1-1.
2.4.2 Mechanical
                       The Comet UPS can be mounted on a raised computer room floor, or flush-mounted on a concrete floor. All
                       floors must be level. On a raised floor, conduits can be run below the floor, with cut-outs made in the floor tiles
                       as shown on the installation drawings.
                       Allow at least three feet of clearance in front of the UPS for normal operation (access to the UPS controls). The
                       Comet requires at least 36 inches top clearance for ventilation.
2.4.3 Electrical
                       Electrical service for the Comet UPS should be supplied on its own dedicated branch circuit. Main input cables and
                       upstream protective devices must be provided and sized per the National Electrical Code (NEC, ANSI/NFPA 70,
                       latest issue), and as appropriate for your load and distribution requirements. Cable sizing data is provided on the
                       installation drawings supplied with the equipment. The Comet 480/480V UPS is not a separately-derived source.
                       The Comet 208/208V UPS is a separately derived source. The neutral must be grounded on a separately derived
                       source (like the Comet 208/208V UPS).
                                 CAUTION            The customer supplied upstream protective device shall open in one cycle
                                                    when 10 times the output rated current is applied or in the event of an output
                                                    short circuit when the unit is working on “Static Switch.”
                  Installation of UPS equipment must be handled by skilled technicians and electrician's familiar with the special
                  requirements of high-energy electrical equipment. We strongly recommend contracting MGE Customer Support
                  Services for start-up of the installed Comet UPS system. Do not allow unqualified personnel to handle or
                  operate the Comet UPS.
Refer to the installation drawings for proper placement and connections of auxiliary cabinets.
2.5.1 Placement
                  Move the Comet UPS, battery cabinets (if any), and auxiliary cabinets (if any), to their final location (see Figure
                  2-2). For cabinets installed adjacent to each other, alignment is critical to properly install the mechanical and
                  cable interconnections. Allow at least 36 inches clearance above all cabinets for maintenance and cooling.
36" recommended
2.6 Connections
                  Electrical connections and cabinet interconnection will vary depending upon the configuration of your Comet
                  UPS system. Refer to Figures 2-3 & 2-4 and to the installation drawings supplied with your equipment.
                            CAUTION             Before making any electrical connections, verify that all battery disconnect
                                                circuit breaker (QF1) are in the “off” position. Customer-supplied upstream
                                                protective devices and distribution circuits should be OFF.
                  The connections to be made are the three phases, and ground cables from the utility AC power source to the
                  UPS. The main AC input cables are terminated at the "Main Input" Terminal Block (TB1) for 40-80kVA and the
                  input busbars for 100-150kVA. Complete wiring instructions for your installation are provided on the installation
                  drawings supplied with the equipment.
                  The connections to be made are the three phases, and ground cables from the bypass AC input power source
                  to the UPS. The bypass AC input cables are terminated at the "Bypass Input" Terminal Block (TB3) for 40-80kVA
                  and the bypass busbars for 100-150kVA. This option provides a separate AC input source for bypass operation.
                  The control connections are available for "Remote Emergency Power Off" (REPO) through a customer-supplied
                  normally closed pushbutton. With REPO connected, the jumper on the "REPO" terminal blocks must be removed.
2.6.4 AC Output
                       The connections to be made are the three phases, and ground cables from the load source to the UPS. The
                       output cables are terminated at the Output Terminal Block (TB2) for 40-80kVA, and the output busbars for 100-
                       150kVA.
                       Load cables must be run separately from all other cables (power supply or computer-system interconnection
                       cables). They should not pass near interference-emitting equipment or sensitive loads.
2.6.5 Battery
                       The connections to be made are the positive, negative, and ground cables from the battery cabinet to the UPS.
                       These are terminated at the appropriate connections in the UPS cabinet (see Figures 2-3 and 2-4). Additionally,
                       control wires and temperature sensors in the battery cabinet must be terminated. Refer to the battery cabinet
                       installation drawings for more details.
OUTPUT
                                                                              C4
                                                                        B4
                                                                  A4
                                                         OPT
                                                                                    C5
                                                                             B5
                                       BYPASS
                                                                       A5
                                                                                     +       -
                                                                               C3
                                                                            B3
                                                                   A3
INPUT BATT.
3.0 Scope
                       Important information on the Comet 40-150kVA systems’ operation procedure sequences; for normal, on battery,
                       and bypass operation, with descriptions of the control and display indicators.
                       During normal operation the AC input source supplies the Rectifier, which converts the incoming AC power to
                       DC. The rectifier in turn supplies the Inverter, which converts DC power to AC to supply the attached load (see
                       Figure 3-1).
                          BYPASS
                           INPUT
                        (OPTIONAL)
RECTIFIER INVERTER
                             MAIN
                                                                                              TO LOAD
                            INPUT
BATTERY
                       When AC input power fails, the UPS goes to on-battery operation. DC power is supplied from the UPS battery
                       system to the inverter, which converts battery power (DC) to AC power to supply the attached load (see Figure
                       3-2).
                            BYPASS
                             INPUT
                          (OPTIONAL)
RECTIFIER INVERTER
                             MAIN
                                                                                              TO LOAD
                            INPUT
BATTERY
                  Should there be an internal fault in the UPS, the load will automatically be transferred to the "Static Switch".
                  (If bypass AC input is within tolerance). The load is supplied without interruption while the UPS is bypassed (see
                  Figure 3-3).
                        BYPASS
                         INPUT
                      (OPTIONAL)
RECTIFIER INVERTER
                          MAIN
                                                                                       TO LOAD
                         INPUT
BATTERY
                  The Graphical User Interface (GUI) display, controls and indicators are located on the front panel in the upper
                  left-hand corner of the Comet UPS, and consist of the following: (See Figure 3-4 for arrangement.)
◗ An alert buzzer.
◗ Four (4) LED's which indicate the overall operating status of the UPS.
◗ Danger of a break in the supply of power to the load (load not protected)
                  When the buzzer is activated it will provide an audible warning to the operator by sounding a pulsed “beep”
                  when any of the following conditions occur:
◗ The load is supplied directly by AC input power via the "Static Switch".
                  It beeps softly and slowly for minor faults and during Inverter operation on battery power. When the low battery
                  shutdown warning level has been reached, the sound volume and the frequency of the beeps increase.
                  In the event of an Inverter shutdown, a continuous alarm is emitted. A buzzer reset key is provided on the front
                  panel. Detection of a new fault will reactivate the buzzer.
                                                                                         1
                                                               Setup    Load             Load Protected
                                                               Alarms   Battery
                                                                                    0%         % KVA            Load
                                                               Inputs    Main
KA2
                                                                UPS
                                                                Input                                                  load
                                                                          KA1                             K3N
QF1
                                                                                3         5               7              8
                                                                                    ⁄ı         Í
                                                     2
                                                           EMERGENCY
                                                           POWER OFF
                                                                                    4          6
                                                                                          9                                   11
                                                                                                           fault
10
                                 NOTE               For details on the Graphical User Interface (GUI) display, please refer to
                                                    manual 86-160316-00.
                  Graphical User                    This display provides specific information concerning normal UPS operation as
                  Interface Display                 well as faults.
                  Emergency Power Off               This red Emergency Power Off (EPO) pushbutton is used to stop the unit during
                                                    an emergency situation only. All power is removed from the load.
Load not protected LED This red LED turns on when any of these conditions occur:
                                                    ◗      Direct supply of power to the load by AC input power via the "Static Switch"
                                                           because of Inverter shutdown (voluntary or following an overload or an
                                                           internal fault).
                                                    ◗      Battery power is not available. Battery circuit breaker is in the "OFF" position
                                                           or battery not connected.
                  Fault LED                         This yellow LED indicates an operating fault or an environmental fault. However,
                                                    the load continues to be supplied by the Inverter.
                                                    ◗      It flashes to indicate that the low battery shutdown warning level has been
                                                           reached.
                                                    ◗      If the LED flashes when the system is not on battery power, battery
                                                           conditions should be checked.
                  Load protected LED                This green LED indicates that the Comet is operating normally. The load is
                                                    protected and supplied via the Inverter output. Bypass Switch SR1 must be in the
                                                    "NORMAL" position.
                  Fault Reset                       This key clears the faults stored in memory. Clearing of alarms in memory is
                                                    accepted only after the alarm conditions themselves have been corrected.
                  Security Key                      This key enables forced operation. The security key must be held down while the
                                                    desired function is executed. Refer to the Forced Transfer section.
                  Buzzer Reset                      This key allows the user to silence the buzzer after a particular alarm. However,
                                                    the buzzer will sound if another alarm occurs.
◗ Verify that the battery circuit breaker(s) are in the "OFF" position.
◗ Verify that the Manual Bypass Switch SR1 is set to the “NORMAL” position.
◗ Verify that the fan switch (SR2) is set to the “ON” position.
◗ Check that the ventilation system is not blocked (air entry through the bottom front and exhaust through the top).
◗ Check that there is a minimum of 36 inches clearance at the front and top for ventilation.
◗ Check that the Comet no longer rests on its 4 wheels (lifting levelers in place).
◗ Check that the load-circuit breaker(s) (where applicable) are in the "OFF" position.
                                 CAUTION               As soon as AC input power is supplied to the Comet (customer supplied up-
                                                       stream circuit breaker is in the “ON” position), the load is initially supplied
                                                       via the “Static Switch.” The Graphical User Interface (GUI) display will begin
                                                       to startup.
◗ Apply AC input power to the unit by closing the upstream circuit breaker.
◗ The inverter automatically starts up, except if the system is in “manual startup” mode (optional).
                       ◗    If the transfer conditions (AC input power within tolerances) are correct, the Inverter comes on line and supplies
                            the load. The green "Load Protected" LED goes on.
                       Typically, the Inverter is configured for automatic startup mode. For manual startup mode configuration, contact
                       MGE Customer Support Services.
◗ The Inverter starts and if the transfer conditions are correct, the load is transferred to the Inverter.
◗ The green "Load Protected" LED is on. The GUI display indicates the operating status of the UPS.
                  ◗    The power drawn by the load is supplied by AC input power via the Rectifier and Inverter modules. The Battery
                       Charger float charges or recharges the battery.
                  When AC input power fails or is out of tolerance, the Rectifier shuts down and the battery supplies the power
                  required by the Inverter to supply the load. The battery discharges.
◗ The green "Load Protected" LED is on. The GUI display indicates the operating status of the UPS.
                  The user is warned of operation on battery power by the buzzer and by the yellow "Battery Status" LED. This
                  information is also available via the standard UPS MANAGER DB15 connector.
During an AC input power failure, the duration of Inverter operation on battery power depends on:
                  The real backup time, which depends on the actual load, may be greater if the Inverter operates at less than
                  full rated load. It is possible, during operation on battery power, to increase the battery backup time by reducing
                  the power drawn by the load (shedding of non-priority load).
                  A low battery shutdown warning signal is available via the standard UPS MANAGER DB15 connector for remote
                  indications. It warns the user of upcoming battery shutdown at a user-determined level of remaining power.
                  On the UPS itself, the buzzer beeps louder and more rapidly, and the yellow "Battery Status" LED flashes
                  rapidly.
                  The end of battery power occurs when the battery reaches shutdown level. At this point, the Inverter shuts down
                  and the UPS goes into "Stand-By" mode. Load is no longer supported. If the input AC power does not return to
                  within tolerance within approximately 2 hours, the unit will shutdown.
                  Once input AC power returns, the batteries begin their charging cycle. It takes approximately 10 hours of online
                  operation to restore 10 minutes of backup time.
When the AC input power failure ends or power returns to within tolerances:
◗ If the end of battery backup power was not reached, the Comet returns to normal operating mode.
                  ◗    If the end of battery backup power was reached and unit is in "Standby" mode, the Rectifier and the Inverter
                       automatically start up (the inverter must be manually started if the system is in manual startup mode).
◗ If the end of "Stand-By" mode was reached, follow the Startup procedure.
3.5.4 Overload
                       When an Inverter temporary overload occurs, the load is transferred to the "Static Switch". Return to normal
                       mode of operation is automatic, following elimination of the overload.
                       The Inverter can handle a continuous overload for a given duration depending on the size of the output current
                       overload (see Figure 3-5) or the output power overload (see Figure 3-6).
                       The operating status of the UPS is provided by the GUI display. If the overload continues during operation via
                       the "Static Switch", the supply of power to the load is interrupted after a specified time.
                       When the Comet shuts down because of a continuous overload, the "Fault Reset" key must be pressed prior to
                       return to normal operation and after elimination of the overload.
10 mn
                                    1 mn
                                    10 s
1s
                                                                                               rated load
                                                                                                current
                                   0.15 s
                                            1.05 1.1       1.3    1.5        1.7        1.9    3     I (A)
                                    1 mn
                                     10 s
1s
                                                                                               rated load
                                                                                                 power
                                    0.3 s
                                                 1.1       1.3    1.5        1.7         1.9   2      P (kw)
                            CAUTION             Pressing the “Emergency Power Off” (EPO) or “Remote Emergency Power Off”
                                                (REPO) pushbutton disconnects the attached load. The EPO is to be used during
                                                emergency situations only, where a hazard to personnel or equipment exists, such
                                                as during a fire. DO NOT USE THE EPO TO TURN THE UPS ON OR OFF.
Follow the procedures listed in this section for turning the Inverter on and off.
                  During an emergency situation, such as a fire in the computer or electrical room, the UPS and all downstream
                  devices can be instantly shut down by pressing the EPO pushbutton on the front panel of the UPS cabinet, or
                  by pressing the "Remote Emergency Power Off" (REPO) optional pushbutton.
The EPO or REPO pushbuttons should not be used for normal shutdown of the equipment.
                  If the EPO pushbutton has been pressed, it must be reset by pressing it again and by pressing the "Fault Reset"
                  key on the front panel to allow the UPS to restart.
                            CAUTION             Using the forced transfer functions will cause the load to experience a power
                                                interruption for a minimum of 500 milliseconds. Be certain that the load can
                                                tolerate this interruption.
                  Forced transfer is required if bypass input is out of tolerance. The load can be transferred from the Inverter
                  output to the bypass input source, or back, with a power interruption of 500 milliseconds.
                  On the front panel, press the "Security" key and hold it while pressing the gray "Inverter OFF" pushbutton for 3
                  seconds.
                  On the front panel, press the "Security" key and hold it while pressing the green "Inverter ON" pushbutton for 3
                  seconds.
This procedure assumes that the UPS is operating normally, with the attached load supplied via the Inverter.
                  1.   Stop the Inverter by pressing the gray "Inverter OFF" pushbutton on the UPS front panel for approximately three
                       (3) seconds. The audible alarm will sound; silence the alarm by pressing the "Buzzer Reset" pushbutton. If the
                       transfer conditions are not satisfied (bypass out of tolerance or other reason), a forced transfer will be required.
                       Refer to the "Forced Transfers" section for more information.
                            NOTE                The battery circuit breaker QF1 will automatically trip open if left in the “ON”
                                                position when the UPS is placed in the Maintenance Bypass mode.
3. Turn the manual bypass switch to the "TRANSFER" position, then to the "BYPASS" position.
                                 NOTE               The cooling fans will remain operational when the UPS is placed on
                                                    Maintenance Bypass mode to prevent the optional input/output transformers
                                                    inside the UPS from overheating. If it is necessary to de-energize the fans,
                                                    move the fan control switch (SR2) to the “OFF” position.
                                 CAUTION            In this mode of operation, the UPS is ready for maintenance, but voltage is
                                                    still present on terminal blocks and various internal components.
                                 WARNING            Failure to follow the proper Startup sequence will result in load loss. After
                                                    SR1 is set to “TRANSFER,” it takes the UPS five (5) to six (6) \seconds to test
                                                    the input power before turning on the “Static Switch”. During this time, the
                                                    load is still supplied by the Maintenance Bypass line, and moving SR1 to
                                                    “NORMAL” will result in interruption of power to the load.
                       1.   Move the fan control switch (SR2) to the “ON” position if the cooling fans were de-energized during
                            maintenance.
                       4.   Turn the Inverter off by pressing the gray "Inverter OFF" pushbutton on the front panel for approximately
                            3 seconds if your Comet has been programmed to automatically restart.
CAUTION ALWAYS turn the Inverter off before rotating the Manual Bypass Switch (SR1).
                       7.   Turn the Inverter on by pressing the green “Inverter ON" pushbutton on the front panel. If the transfer
                            conditions are not satisfied (bypass out of tolerance or other reason), a forced transfer will be required.
                            Refer to the "Forced Transfers" section for more information.
                       Now the UPS is in normal operating mode. The green "Load Protected" LED is illuminated on the front panel,
                       and the operating status of the UPS is provided by the GUI display.
◗ Press and hold the gray "Inverter OFF" pushbutton for 3 seconds.
                  It is recommended not to power down the Comet for long periods because the battery should remained charged.
                  However, to carry out a power down, proceed as follows:
3.10 Alarms
                  Any state other than normal operation (green “Load Protected” LED on) is considered a fault by the diagnostics
                  system.
                  Before undertaking any servicing or other action, note the status of the different LED's and the GUI messages
                  displayed on the panel.
If an alarm is present and the load still functions, it is supplied via the "Static Switch", i.e. it is not protected.
                                                              UPS shutdown;
                                                              load supplied via maintenance bypass
                               light off,
                        beep
                        beep
                               buzzer on,
light on,
light flashing
4.0 Scope
                       Preventive maintenance and battery safety instructions for Comet 40-150kVA UPS, and information about
                       replacement parts, and customer service.
                       A. Servicing of batteries should be performed or supervised by personnel knowledgeable with batteries and
                          the required precautions. Keep unauthorized personnel away from batteries.
B. When replacing batteries, use the same model and manufacturer of batteries.
C. CAUTION — Do not dispose of battery or batteries in a fire. The battery may explode.
                       D. CAUTION — Do not open or mutilate the battery or batteries. Released electrolyte is harmful to the skin
                          and eyes. It may be toxic.
                       E. CAUTION — A battery can present a risk of electrical shock and high short-circuit current. The following
                          precautions should be observed when working with batteries:
                       6.   Determine if ground faults exists. If so, remove the source of ground. Contact with any part of a grounded
                            battery can result in electrical shock. The likelihood of such shock will be reduced if such grounds are
                            removed during installation and maintenance.
                       The following preventive maintenance routines should be considered the minimum requirements; your
                       installation and site may require additional preventive maintenance to assure optimal performance from your
                       installed Comet UPS and associated equipment. These routines should be performed twice a year (more often
                       if required). We strongly recommend contracting MGE Customer Support Services for preventive and remedial
                       maintenance at 1-800-438-7373.
                       The technician or electrician performing preventive maintenance on the UPS must be familiar with the
                       indicators, controls, and operation of the UPS.
                       a.   Isolate and de-energize all Comet UPS equipment for all maintenance operations. Lock and tag all upstream
                            circuit breaker(s) during maintenance.
                       b.   Ensure that all equipment is clean and free of dust, dirt, and debris. The exterior of the UPS enclosure may
                            be cleaned with a mild solution of soap and water, lightly applied with a lint-free cloth.
c. Clean/replace the air intake filters, exhaust plates, and the enclosure interior with a vacuum cleaner.
e. Test the main operating sequences as applicable to your installation (see Section 3).
                  Three levels of replacement parts are available for the Comet. The three levels are designated A, B, and C. The
                  level that you should keep on hand for your installation will vary depending on the type of maintenance planned
                  on site, and the configuration of your UPS system.
                  Having the replacement parts on hand will prevent any unacceptable delays (because of time involved obtaining
                  spares) during critical periods, such as system startup. Any items used during start-up will be replaced by MGE
                  at no charge. Contact MGE Customer Care Center at 1-800-438-7373 for specific recommendations.
Level Description
                  A    This level of replacement parts consists of consumable items, specifically power and control fuses.
                       It is recommended to have these items on hand during installation of the UPS systems, including initial startup.
                  B    This level of replacement parts is recommended when the user can tolerate short-duration UPS down-time
                       to obtain replacement parts in the event of a major UPS failure. This level of replacement parts consists of
                       consumable items, specifically power and control fuses, fans, and the most critical circuit board assemblies.
                  C    This level of replacement parts is recommended when the user can tolerate only a minimum of down-time in
                       the event of a major UPS failure. This level of replacement parts consists of consumable items, specifically
                       power and control fuses, fans, and a significant set of circuit board assemblies.
                   MGE UPS SYSTEMS, INC. (“MGE”) warrants three phase products it manufactures to be free from defects in
                   materials and workmanship for a period of three hundred sixty five (365) days counting from the date of purchase by
                   or for the first end user (“Purchaser”), or, if applicable, the date of MGE’s completion of initial startup of the subject
                   product, provided however said warranty shall not exceed eighteen (18) months from the date of delivery of the
                   subject product to Purchaser (the “Warranty Period”). MGE’s liability hereunder is limited to replacing or repairing at
                   MGE’s factory or on the job site, at MGE’s option, any part or parts that are defective and reported to MGE during
                   the Warranty Period. MGE shall have the sole right to determine if the parts are to be repaired at the job site or
                   whether they are to be returned to the factory for repair or replacement. All items returned to MGE for repair or
                   replacement must be sent freight prepaid to its factory. Purchaser must obtain MGE’s Return Goods Authorization
                   (“RGA”) prior to returning items. The conditions stated herein must be met for MGE’s warranty to be valid. MGE will
                   not be liable for any damage done by unauthorized repair work, unauthorized replacement parts, from any misappli-
                   cation of the subject product, for damage due to accident, abuse, or act of God (such as earthquake, flood, inclement
                   weather, rain or fire), or relating to Purchaser’s failure to follow proper environmental conditions for the product.
                   In no event shall MGE be liable for loss, damage, or expense directly or indirectly arising from the use of or any
                   defects in the subject product, or from any other cause, except as expressly stated in this warranty. EXCEPT AS
                   EXPRESSLY STATED IN THIS WARRANTY, MGE UPS SYSTEMS, INC. MAKES NO WARRANTIES, EXPRESS OR
                   IMPLIED, INCLUDING ANY WARRANTY AS TO MERCHANTABILITY OR FITNESS FOR A PARTICULAR
                   PURPOSE OR USE OR NON-INFRINGEMENT. MGE is not liable for and Purchaser waives any right of action it
                   has or may have against MGE for any consequential or special damages arising out of any breach of warranty, and
                   for any damages Purchaser may claim for damage to any property or injury or death to any person arising out of its
                   purchase or the use, operation or maintenance of the subject product. The warranty stated herein includes parts and
                   labor; however, MGE will not be liable for any labor subcontracted or performed by Purchaser for preparation of the
                   warranted item for return to MGE’s factory or for preparation work for field repair or replacement, and MGE will not
                   be responsible to pay any invoice therefore.
                   This warranty shall be exclusive of any and all other warranties express or implied and may be modified only by a
                   writing signed by an authorized officer of MGE UPS SYSTEMS, INC. This warranty shall extend to the Purchaser
                   but to no one else. Accessories supplied by MGE, but manufactured by others, carry any warranty the manufactur-
                   ers have made to MGE, and which can be passed on to Purchaser.
                   MGE UPS SYSTEMS, INC. makes no warranty with respect to whether the products sold hereunder infringe any
                   patent, U.S. or foreign, and Purchaser represents that any specially ordered products do not infringe any patent.
                   Purchaser agrees to indemnify and hold MGE UPS SYSTEMS, INC. harmless from any liability by virtue of any
                   patent claims where Purchaser has ordered a product conforming to Purchaser’s specifications, or conforming to
                   Purchaser’s specific design.
                   Purchaser has not relied and shall not rely on any oral representation regarding any products sold hereunder and
                   any oral representation shall not bind MGE UPS SYSTEMS, INC. and shall not be part of any warranty.
                   There are no warranties which extend beyond the description on the face hereof. In no event shall MGE UPS
                   SYSTEMS, INC. be responsible for consequential damages or for any other damages except as expressly stated
                   herein.
                   The information in this manual is the property of MGE UPS SYSTEMS, INC., and represents a proprietary article in
                   which MGE UPS SYSTEMS, INC. retains any and all intellectual property rights, including exclusive rights of use
                   and/or manufacture and/or sale. Possession of this information does not convey any permission to reproduce,
                   print, manufacture or have made the article or articles shown herein. Such permission may be granted only by
                   specific written authorization signed by an authorized officer of MGE UPS SYSTEMS, INC.
                   IBM, PC-AT, ES/9000, and AS/400 are trademarks of International Business Machines Corporation. MGE and
                   MGE UPS SYSTEMS are trademarks of MGE UPS SYSTEMS, INC. Other trademarks that may be used herein
                   are owned by their respective companies and are referred to in an editorial fashion only.
                   For Three Phase Warranty outside of the United States, Canada and Mexico, refer to Three Phase International
                   Warranty.
                   Thank you for choosing MGE UPS SYSTEMS, INC. for your power protection, distribution, and quality
                   requirements. We are pleased to have you join our increasing family of users.
                   In order to maximize the value you receive from this product, and to ensure that you are kept informed of
                   product or software updates, we recommend that you take a few minutes to register your new purchase.
                   You may register online at the URL noted below. Should you not have Internet access, you may mail or fax
                   this form back (attn: Warranty Registration) as indicated at the bottom of the page.
                   Register your product at: http://www.mgeups.com/email/warranty/menu.htm
                   Please be prepared with the following information to register and validate your product’s warranty, keep
                   informed on software and product updates, and register your extension "Warranty+" if purchased with the
                   product.
                   User Information
                   Last name               ________________________________________
                   First name              ________________________________________
                   Company name            ________________________________________
                   Address                 ________________________________________
                   Zip code                ________________________________________
                   City                    ________________________________________
                   State/Province          ________________________________________
                   Country                 ________________________________________
                   Tel                      ________________________________________
                   Fax                     ________________________________________
                   Email                   ________________________________________
                   Product Information
                   Model                   ________________________________________
                   Serial Number           ________________________________________
                   Date of purchase        ________________________________________
                                       MGE UPS SYSTEMS, INC., 1660 Scenic Avenue, Costa Mesa, CA 92626, USA
                                         Tel: 714-557-1636                              Fax: 714-557-9788
                     ?       Technical questions? If you encounter a problem while following the instructions in this manual, or have
                   questions about the operation, repair, or servicing of your equipment, please direct calls to MGE UPS SYSTEMS,
                   INC. Customer Care Center or visit our web site www.mgeups.com for complete service information.
                   To insure that your questions are correctly answered, please obtain the serial number of the unit and include
                   them in any discussions or correspondence.
Who To Contact
                   Customer FAQ
                   or International calls:                 1-714-557-1636
                   Commitment: MGE UPS SYSTEMS, INC. is committed to providing easy to access factory trained experts that
                   will provide responses to any questions that you might have.
                  Scheduling of the MGE Field Service Engineers typically should be done 7 to 10 days before they are required
                  on-site. If the startup of the product is critical to maintaining your schedule, please call the MGE toll free
                  telephone number at 1-800-438-7373 for assistance.
                   Should you require factory service for your equipment, contact MGE Customer Care Center and obtain a Return
                   Goods Authorization (RGA) prior to shipping your unit. Never ship equipment to MGE without first obtaining an RGA
                   number.
                   Date:              ______________________________________________________
                   RGA Number:       ______________________________________________________
                   Contact Name: ______________________________________________________
/ And/or.
°C Degree Celsius.
°F Degree Fahrenheit.
Ø Phase angle.
® Trade Mark.
2nd Second.
                        BTU or Btu                   British thermal unit. Defined as the amount of heat required to raise the tempera-
                                                     ture of one pound of water by 1°F.
                        BYPASS                       See “Static Transfer switch”.
Carrier The company or individual responsible for delivering goods from one location to another.
C Common.
CB Circuit breaker.
                        cm                           Centimeter.
                        CSA                          Canadian Standards Association.
                        dB                           Decibels.
                        DC                           Direct current.
                        Conduit                      A flexible or rigid tube enclosing electrical conductors.
Current rating The maximum current that a conductor or equipment can carry reliably without damage.
Digital Meter The LCD display on the front panel of inverter system.
Earth ground A ground circuit that has contact with the earth.
                  ECO Mode                      Operating mode by which the load is supplied directly by the AC source if it is within the
                                                tolerances defined by the user. This mode reduces the consumption of electrical power.
Frequency slew rate The change in frequency per unit of time. Given in term of Hz per second (Hz/sec.).
I Current.
Input branch circuit The input circuit from the building power panel to the equipment.
Inverter An electrical circuit that generates an AC voltage source from a DC voltage source.
L Line.
mA Milliampere.
MAX. Maximum.
                  MCM                           Thousand circular mil; standard wire sizes for multiple stranded conductors over 4/0 AWG in
                                                diameter. M is from Roman numerical system indicating 1000.
N Neutral.
NC Normally closed.
NO Normally open.
                            PF                             Power factor.
                            PN                             Part number.
On-line mode Inverter output power is the primary energy source to load.
                            Off-line mode                  Inverter output is off, and the load connected at the inverter output receives power
                                                           from utility line via a static transfer switch or maintenance bypass relay.
                            Static Transfer                An solid state switching mechanism electronically controlled to pass AC power
                                                           directly from the utility to an output load.
                            Test connector                 DB-9 type connector on the LCD panel allowing MGE UPS SYSTEMS Customer
                                                           Support Service technician to access programmable and diagnostic features of the
                                                           system.
                            ve                             Battery voltage.
                            Via                            By way of.
                   Use this form to report any errors, omissions, or other problems you have experienced, or to order additional
                   hardcopies of this document. A free copy of this document may be downloaded from the proprietary MGE Rep Web
                   site. Please contact your MGE UPS SYSTEMS, INC. Representative for assistance.
NAME ____________________________________________________________________________________
COMPANY _________________________________________________________________________________
Comet 40-150kVA
86-160310-00 E00
                                                                                  Contact MGE
                                                                                  United States
                                                                                  MGE UPS SYSTEMS
                                                                                  1660 Scenic Ave.
                                                                                  Costa Mesa, CA 92626
                                                                                  Canada
                                                                                  MGE UPS SYSTEMS
                                                                                  #9, 2789 Thamesgate Drive
                                                                                  Mississauga, ON L4T 4E8