Instructions For Type GFR Ground Fault Protection Systems: 15321-B File
Instructions For Type GFR Ground Fault Protection Systems: 15321-B File
                                                                                                       .c
 TABLE OF CONTENTS
                                                                                     ls
 Section                                                         Page   Section                                                      Page
                                                                                  ua
 1.0        UL Listing . . . . . . . . . . . . . . . . . . . .     2     5.8         Connection Diagrams . . . . . . . . . . .         10
 2.0        General Purpose . . . . . . . . . . . . . . . .        2     5.8.1           Relay Connections. . . . . . . . . . .        10
 3. 0       Description . . . . . . . . . . . . . . . . . . .      3     5.8.2           Typical System Diagrams . . . . . .           10
 4.0       Application Considerations . . . . . . . . .            4     5.8.3           Zone Differential GFR
                                                                        an
 4.1           General . . . . . . . . . . . . . . . . . . . .     4                     Operation Principles. . . . . . . . . .       10
 4.2           Methods of Achieving System                               6.0      Ground Fault Current Sensors . . . . . . .           10
               Selectivity . . . . . . . . . . . . . . . . . .     4     6.1         General Description . . . . . . . . . . . .       10
 4.2.1             Time Current Band Settings. . . . .             4     6.2         Electrical Ratings . . . . . . . . . . . . .      10
 4.2.2             Zone Selective Interlocking . . . . .           4     6.2.1           Maximum System Voltage. . . . . .             10
                                                                 tM
 4.2.2.1              Zone Selective Interlock                           6.2.2           Withstand . . . . . . . . . . . . . . . .     11
                      Wiring . . . . . . . . . . . . . . . . .     4     6.2.3           Dielectric Withstand. . . . . . . . . .       11
 4.2.2.2              Zone Interlocking Operation                        6.2.4           Maximum Error Signal . . . . . . . .          11
                       Mode . . . . . . . . . . . . . . . . .      4     7.0      Ground Fault Test Panel. . . . . . . . . . .         14
                                                     ar
 4.3           Relay Settings. . . . . . . . . . . . . . . .       5     7.1         General Description/Purpose . . . . . .           14
 4.3.1             General . . . . . . . . . . . . . . . . . .     5     7.2         Available Types. . . . . . . . . . . . . . .      15
 4.3.1.1              Single Zone of Protection . . . .            5     7.3         Electrical Data . . . . . . . . . . . . . . .     15
 4.3.1.2              Multiple Zones of Protection -                     7.4         Operation Sequence . . . . . . . . . . . .        15
                                           lP
                                                                                                       .c
                                       ......,...
                                           ..__ __   Adjusting                                         ,_......,.._ Adjusting
                                                     Switches                                                      Switches
                                                                                             ls
                                              Turn Screw to                                                    Turn Screw to
                                                                                          ua
                                              lock Settings                                                    lock Settings
                                                                           an
 Fig. lA Ground Fault Relay-Electrical Reset With Zone
          Interlocking (Cat. No. GFR60El)
                                                                 tM
                                                                 Fig. lB Ground Fault Relay-Mechanical Reset With Zone
                                                                         Interlocking (Cat. No. GFR60Ml)
                                                           ar
 1.0 UL LISTED GROUND FAULT SENSING
      AND RELAYING EQUIPMENT
 and time delay settings, the GFR relay will initiate a trip
                                                                                             ---- Solid Core Type
 action of a disconnect device, which will open the faulted
 circuit and clear the fault.
3.0 DESCRIPTION
                                                                                              .c
 A basic type GFR ground fault protection system consists          Additional optional equipment can be added to the
 of a ground fault relay (GFR) as shown in Fig. 1, a ground     protection system to meet the requirements of the speci
 fault current sensor (GFS) as illustrated in Fig. 2 and a      fying engineer, including:
 disconnect device equipped with a shunt trip device. This
                                                                             ls
 disconnect device can be a molded case circuit breaker,        1. Ground Fault Test Panel� Fig. 4
 a power circuit breaker, a bolted pressure switch or other
                                                                2. Ground Fault Warning Indicator Relay� Fig. 5
 fusible disconnect device, suitable for application with
                                                                          ua
 UL Class I Ground Fault Sensing and Relaying equipment.        3. Ground Fault Indicating Ammeter (1)       �   Fig. 6
 A typical molded case circuit breaker with a shunt trip
 device installed is illustrated in Fig. 3 .
                                                                an
                                                                tM
                                                       ar
                                              lP
                   Shunt Trip
                                ca
                                                                                                              .c
                                                                    to allow for variations in the pre-established tripping se
 4.1 General                                                        quence to allow for alternate locations of the arcing
                                                                    ground fault. A zone selective interlock coordinated sys
 Type GFR ground fault protective devices are designed to           tem provides for fast tripping of the nearest interrupting
 be used primarily on solidly grounded electrical distribu         device upstream of the arcing ground fault regardless of
                                                                                             ls
 tion systems rated up to a maximum of 600 volts, 50/60             the pre-set time delay settings. With this type of protec
 Hz, to provide for rapid clearing of arcing ground faults.         tion, the resulting systems damage level is the lowest
                                                                    possible because the interrupting devices are allowed to
                                                                                          ua
     When properly applied, these devices will satisfy the          clear the fault as quickly as they can respond.
 requirements for ground fault protection of service en
 trance equipment as outlined in Sections 2 3 0-95 and              4.2.2.I Zone Selective Interlock Wiring
 517-14 of the National Electrical code. When these de
 vices are added to downstream feeder and branch circuits           Zone interlock wiring is only applicable to type GFR re
                                                                               an
 as well as the main service disconnecting devices as sug          lays equipped with zone selective interlocking as shown in
 gested in the fine print note of 2 3 0-95 and to the down         Table I. These relays are equipped with four additional
 stream feeders as required in 517-14, additional protec           terminals which have the following function:
 tion will be provided and selective coordination of tripping
                                                                         Terminal    8 - Common (Not used on 1 25V D-C GFR's)
                                                                    tM
 operations on arcing ground faults can be achieved.
                                                                                     9 - Output signal
                                                                                    10 - Input signal, time restraint
     With selectively coordinated ground fault protection
                                                                                    11 - Input signal, no trip
 equipment     applied   on   main   service disconnects and
 downstream devices, a greater degree of continuity of
                                                             ar
                                                                         To make the relays function in a zone interlocking
 service is insured.
                                                                    mode, all relays must be of the interlocking type and ad
                                                                    ditional wiring connections are required. Typical connec
 4.2 Methods of Achieving System Selectivity
                                                                    tions for a main with multiple feeders and multiple branch
                                                    lP
 current band setting that will initiate a downstream trip         mit a single signal to upstream device. No supplementary
 ping operation and clear the faulted circuit before any            relaying is required for this function.
 upstream interrupting device tripping action can be ini
 tiated. This type of coordination necessarily requires the         4.2.2.2 Zone Interlocking Operation Mode
 longest time delay settings to be placed on the upstream
 devices. This type of coordination is fine if the faults are       Regardless of the time delay setting, any interlocking type
        .E
 always downstream.                                                 GFR relay will respond near instantaneously unless a re
                                                                    straint signal - which is indicative of a ground fault further
 4.2.2 ZONE SELECTIVE INTERLOCKING                                  downstream in the next protective zone - acts to change
                                                                    the mode of operation to the pre-set time delay. On
 In a system employing zone selective interlocking type             downstream circuits, it is frequently desired that a short
 devices, selective coordination is still achieved for down        time delay be observed before a tripping action is initiated.
w
 stream faults by the use of time-current band settings.            This can be accomplished by adding a jumper between
 With appropriate settings, downstream interrupting de             terminals 9 and 10 on the downstream relay as indicated
ww
 vices will clear the faulted circuit before any upstream           by Note 2 on Fig. 7. This jumper should not be used on
 device can operate. However, with zone selective inter            any upstream relay as it will defeat the zone interlock
 locking,   additional   intelligence   is   automatically   pro-   ing function.
                                                                                                                                          om
                                                                                                                                                                                   5
                                                                                                                                        .c
                                                                                                                                                                   TypiCal Marn
                                                                                                                  Trme Delay Input
                                                                                                                                                                        GFR
                                                                                                                     ls
         Zone 1                                                                                                                                                  TypiCal Feeder
                                                                                                                  ua
                                                                                                                                                                     GFR's
                                                                                                an
                                                                                                                                                                  TypiCal Branch
                                                                                                                                                                      GFR's
                                                                                 tM
          Zone 3
Notes:
        1. Wiring Should be Twisted Parr, Number 14 or 16 AWG With Maxrmum Distance Between Frrst and Last Zones of 250 Feet Route Separate from Power Conductors. Do Not
          Ground. On 125VDC GFR's the Wire to Terminal 8 is Not Used. Only One 125VDC Source rs Allowed.
        2. Jumper may be Added Between Terminals 9 and 10 on Downstream Relays to Add Trme Delay per Dial Setting. Otherwise, Relay wrll lnrtrate Tnp Wrthout Trme Delay.
        3. Any Quantity-Up to 50-Relays may be Wired in Parallel to Provide a Srngle Upstream Restrarnt Srgnal.
                                                                     ar
        4. All Relays in a Zone Interlock System Must be of Interlocking Type.
                                                        lP
 4.3 Relay Settings                                                                               be at least one step greater than the nearest downstream
                                                                                                  device pick-up setting.
                                           ca
 4.3.1 GENERAL
                                                                                                 Minimum Time Delay©                  -    The shortest time possible
 The exact individual relay time/current settings will vary                                       should be used on the branch circuit downstream. In
 between system installations depending upon the type of                                         crease the time delay on upstream devices in increments
                              tri
 protection and level of selectivity desired. The Specifying                                      of one step or more for molded case breakers, and two
 Engineer can best make these decisions for any specific                                         steps or more for other slower operating type devices.
 installation. For general applications, settings as described
            lec
 in the following conditions may be considered.                                                  4.3.1.3 Multiple Zones of Protection With Zone
                                                                                                              Selective Interlocking
 4.3.1.1 Single Zone Level of Protection
                                                                                                 Establish time/current coordination as in 4. 3.1.2 for
 Minimum Pick-up               -   20% of disconnect rating. Increase                            multiple zones without zone interlocking. This is done
 to maximum pick-up setting (1200 Amp) where maxi                                               on the basis that most faults occur downstream and that
 .E
 mum service continuity is desired.                                                              the most downstream device should be set to clear the
                                                                                                 fault first leaving upstream devices for back-up fault
 Minimum Time Delay©                   -   10 cycles suggested.Any faster                        protection.
 time will invite nuisance trips. Increase time when more
 than minimum damage level can be tolerated.                                                          Add zone interlocking to provide fast tripping of up
w
 Minimum Pick-Up               -    The pick-up setting of the down                                  Where desired, nearly instantaneous operation of down
 stream device should still be no less than 20% of the                                           stream devices can be defeated were time delayed op
 disconnect rating. Successive upstream settings should                                          erations are adequate. See 4.2.2.2.
Table 1
                                                                                                                         .c
        GFR Relay                         120 Volt, 50/60 H z Control                         120 Volt De Control
        Types      t!>
                                          Style 1293C4 7     (!)                              Style 1293C83     <D
                                                                                                          ls
                                          Pick-up In Amperes                                  Pick-up In Amperes
                                                                                                       ua
         Electrical Reset                  Gil            G Ol                 G0 3             Gil              G Ol              G0 3
         With
         Zone Interlocking                12EI            60EI               1200EI            12EID           60EID            1200EID
                                                                                          an
        Without
        Zone Interlocking                 12E              60E                1200E            12ED            60ED              1200ED
                                                                                tM
         Zone Interlocking                12MI            60MI               1200MI           12MID            60MID            1200MID
 5.1 Available Relay Types                                                      Each type relay is provided with two switches that are
                                                                                adjustable   over the range selected. The top adjusting
 The GFR ground fault relays are available in two basic                         knob, as shown in Fig. 1, adjusts the pick-up level of the
 types, ie, with and without zone selective interlocking.                       ground fault current. The bottom adjusting knob adjusts
                                        tri
 Each type relay must be reset following a trip operation.                      the time delay range. The calibration marks provided for
 Each of the basic type relays is available with either an                      both adjustments are shown in Table 2.After the desired
 electrically held or mechanically latched output relay. The                    values have been pre-set, the adjusting knobs can be
 electrically held type must be electrically reset remotely -                   locked in position by the pointer lock screw shown in
                           lec
 reset bottom also serves as a mechanical pop-up trip indi                     nature being caused by the intermittent striking and re
 cator. A complete list of available styles is provided in                      striking of an arcing ground fault. To avoid the instanta
 Table 1.                                                                       neous resetting of the solid state timing circuitry every
                                                                                time the fault current drops to zero, Type GFR ground
                                                                                fault relays are equipped with a memory response, which
                                                                                integrates these intermittent faults with time using a seven
w
                                                                                  .c
                                                                               ls
                                                                            ua
                                                              an
                                                tM
                                             ar
                                         lP
                                   ca
                          tri
             lec
 .E
w
                                                                                                            .c
        Pick-up                                                    Eledrically held relays will satisfy most applications
       Amperes                       Dial Marking*                 where reliable control power is available following a fault
                                                                   interruption. Where control power is derived from the
      1-12              1     2        3    5        7    9   12   load side of the disconnect device and a visual trip indica
                                                                                            ls
                                                                   tion is desired, the mechanically held relay should be
     5-60               5    10       15    25    35     45   60   selected. Also, in applications where the control power is
                                                                   less than reliable and where an automatic reset could af
                                                                                         ua
      100-1200       100    200      300   500   700 900 1200      fect interlocking circuitry, the mechanically held relay
                                                                   should be selected.
     Time Delay
                      I©    10       15    25    35      45   60
     Cycles                                                        5.6 Relay Electrical Ratings
                                                                              an
      *All Adjustments are in discrete steps.
                                                                   5.6.1 CONTROL PO WER REQUIRED
                                                                   tM
 lay has a flat response, ie., the operating time of any given
 fault current above its pick-up setting is essentially con       5.6.2 TEST WINDING POWER REQUIRED©
 stant. There is some small variation in the lower ranges
 as indicated in Fig. 8, but very little. The pick-up and time     120 Volts, 50/60Hz., 2.5 Amps
                                                               ar
 delay tolerances, are ± 10%.
                                                                   5.6.3 OUTPUT CONTACTS
                                                                   Inrush
 5.5.1 PICK-UP RANGE                                               28 Volts, de, 3.0 Amps, Inductive Load
                                                                   125 Volts, de, 0.5 Amps, Inductive Load
 1-12 Amp - Specific circuit application where low level
                                       tri
 5-60 Amp -         Individual branch and/or motor circuits        Output Voltage, 6 Volts de
                        lec
100-1200 Amp- General purpose and service applications. 5. 6.5 MAXIMUM DIELECTRIC
 Relays without zone interlocking are best suited for single       5. 7 Mounting Arrangements©
 level applications where it is desired to only satisfy the
 minimum requirements of the National Electrical Code.             The type GFR Relay is supplied as standard in a surface
 Zone selective interlocking type relays should be selected        and semi-flush mounted enclosure with outline dimen
 for multi-level system applications where only the mini          sions as illustrated in Fig. 9. For installations requiring a
w
 mum amount of system damage can be tolerated follow              semi-flush cover mounting, panel cutout and mounting
 ing an arcing ground fault.                                       dimensions are illustrated in Fig. 10.
ww
m•m•" � m
                                                                                                                                       .c
                                                                                                         m
                                                                                                         141 Holes
                                                                                                                                      1437 _.j+-- 1437
                                                                                                                                        - -r- -
                                                                                                                  Tl � -t-�
                                                                                                                                      Top         ,
                                                                                                                                                                      2.719
                                                                                                          ls
                                                                                                                  5.06
                                                                                                                                                           ct._-- I-
�3�
"']
                                                                                                       ua
                                                                                                        Cutout
                                                                                                                       2
5.750
                                                                             I
                                                                                                                                 -$--             I            iT
                                                                                          an
                                                                             I             Fig. 10 Semi-Flush Cover Mounting Details for Type
                                                                                                       GFR Ground Fault Relay ©
.156
                                            Adjustment
                                     ca
                         tri
                                                                                 I                 I
                                                                                 I
                                                                                 I
                                                                                                   I
                                                                                                   I
                                                                         ��                        J
                          ��
                     r as -
                                    l_L ,--__      n ln l                            - -- ---- -
                                                                                                                                                                        ,
          lec
                   �                           z o e t er ock
                    � p�:re 0 11                    __     ---,-,----,---'                                        R
                   Zone Interlock              _ _     - -
                            nly
                                                                                                           � D-
                                       1                      1     1
                  c�                 �----8-�_§                                                                                                                    j
                                                                1
                                                                                                                 Trip Contacts
                                       c
                                       E
 .E
5.8 Connection Diagrams scheme, no cross interlocking with "T" auxiliary contacts
                                                                                                                 .c
                                                                          is required.
 5. 8.1 RELAY CONNECTIONS
                                                                          5.8.3.6 This scheme may be expanded to additional alter
 A simple block diagram is provided in Fig. 11 to illus                  nate sources as long as interrupting devices are available
 trate the internal functional circuits of the type GFR                   to isolate any potential ground fault on each side of the
 Relay. Complete external connections are a function of                   fault.
                                                                                                 ls
 the associated devices used with the relay along with the
 complexity of the system in which the components are
                                                                          6.0 GROUND FAULT CURRENT SENSORS
                                                                                              ua
 applied. The terminals on the GFR relay are suitable for
                                                                              (See Table 5, Page 21)
 #16 through #14 AWG copper conductors. A maximum
 of two per terminal are permitted.
                                                                          6.1 General Description
                                                                                     an
                                                                          As indicated in Table 5 (Page 21), Ground Fault Current
 Basic, typical radial distribution system diagrams are pro              Sensors (GFS) are available in a variety of physical sizes
 vided in this leaflet for guidance; refer to Figs. llA, l iB,            and current ratings to match the application requirements
 ll C, l iD and l iE.                                                     of the distribution system. Sensors should be selected to
                                                                          tM
                                                                          match the ampere rating of the specified GFR Relay. The
      Two multiple source distribution systems are illus                 physical size should be selected to properly encompass the
 trated in Figs. 11F and l lH. Fig. l l F illustrates a dual              required conductor configuration with space allowed for
 source distribution system with center point grounding                   minimum clearances as shown in the applicable outline
 as allowed in the National Electrical Code under Article                 mounting figure. Outline references are given in Table 5.
                                                                   ar
 250-23a, Exception No. 4 Fig. 11H illustrates a multiple
 source, multiple ground distribution system with zone dif                  Sensors are available with solid cores having round con
 ferential ground fault sensing methods employed.                         ductor openings and in split core designs with various size
                                                           lP
                        G:�
                                                    ca
                              ��
                                                                             Ground Fault Current Sensors are special rated current
 5.8.3.1 In general,           will operate only for ground
                                                                          transformers and must be applied only with type GFR
 faults within Zone 1 and              for Zone 2. This includes          Relays shown in Table 1 . Sensors cannot be used with any
                                                                          other equipment.
 ground faults for feeders located in these respective zones.
                                 tri
                                       G:�
                                                                             Sensors are insulated with cast apoxy and can be
 5.8.3.2 With " M l " and "T" closed and " M2" open and
                                                                          mounted directly to enclosure surfaces. Ideally, they
                   �
                    lec
 with a ground fault in Zone 2,                     will not operate to   should be installed so that all conductors passing through
                    R                                                     the sensor opening are physically centered in the window
 trip "M 1" but,        will to trip   "   T   ".
                                                     ��
 5.8.3.3 Conversely, with "M2" and "T" closed and " M1"
                                                                          possible error signals. Rectangular configurations are pro
                          G��
 open and with a ground fault in Zone 1,                   will not op   vided with compensating windings to reduce potential
          .E
                                                                          error signals.
 erate to trip "M2" but         will to trip "T".
                                                                                                                                        .c
 6.2.1 Maximum System Voltage
                                                                                                 Service Source
 6.2.2 WITHSTAND
                                                                                                            ls
                         200KA                           0.05                                                                                                        Feeder   )
                            50KA                         0.3
                                                                                                         ua
                         <!l 4KA                         Continuous
                                                                                             an
 Windings to Mounting Holes - 3 KV
 Windings to Inner Core Surface - 3KV                                                           Notes:
                                                                                                    • Zero Sequence
                                                                                                GFP Sensing Method
 Mounting Surface to Inner Core Surface - 3KV
 12A Solid
 60A Solid
            BOLTED PHASE THROUGH FAULT
                                 1.0 A@ 144A
                                 5.0 A@ 720A
                                                                                    tM              • GFP on Mam Only
                                                                                   Neutral
                                 tri
                                                                 Feeder   )
               lec
      Grounding Electrode
      Conductor
 .E
                                                                                               Notes:
      Notes:
                                                                                                   • Mam-Ground Return
                                                                                               GFP Sensing Method
          •Mimmum per NEC 230-95                                                                  •Two level for Improved ServiCe ContmUity as Suggested by NEC 230-95(b)
      Type of Protection                                                                       Type of Protection
          •Not Perm1tted Downstream of ServiCe D1sconnect per NEC 250-23(a)                        •Not Permitted Downstream of ServiCe D1sconnect per NEC 250-23(a)
      *Additional Grounding                                                                    *Additional Grounding
ww
 Fig. llA Simple Radial System With GFR on Main                                              Fig. IIC Simple Radial System With GFR on Main and
                 Only-Ground Return Sensing                                                               Feeders-Ground Return Sensing on Main
                                                                                                                                                                               om
 12
                                                                                                                                                                             .c
                                                                                                                                                                           ain on_
                                                                                                                                                                                 e
                                                                                                                                                                       �- - - z
                                                                                                                                                            1"' �: ���� : �_
                                                                                                                                                          T---'-•
                                                                                                                                                                                         �
                                                            GFS
                                                                                                                                                           e-1
                                                                                                                                                          ..=,
                                                                                        Neutral
                                                                                                                                                             I
                                                                                                                                                                                              �
                                                                                                                                                                                              "
                                                                                                                                                                                              0
                                                                                                                Service Source                                                                N
                                                                                                                                                                                              "
   Service Source
                                                                                                                                                 ls
                                                                                                                                                                                              �
                                                                                                                                              ua
                                                                                                               Note: See Figure 7 lor
                                                                                                               Interlock Wiring Details.
                                                                                                                            an
                                                                                                               Notes:
                                                                                                                    •Mam-Ground Return.
                                                                                                               GFP Sensing Methods
                                                                                                                    • Feeders-Zero Sequence
      Notes:
          •Time/Current Coordmat1on BetweenMam and Downstream Feeders                                               •Time/Current Coordmation BetweenMain and Downstream Feeders.
      Ground Fault Selectivity                                                                                 Ground Fault Selectivity
          • FeederTrips BeforeMain for Downstream Faults.                                                           • FeederTnps BeforeMam lor Fault in Feeder Zone
                                                                                                                    •MamTnps Without Pre-set Time Delay lor Fault 1nMain Zone
          •Not Permitted Downstream of Service Disconnect perNEC 250-23ia)
      * Additional Grounding
          •Must Not be on Downstream S1de of Ground Fault Sensor.                                                   •Not Permitted Downstream of Service DISconnect perNEC 250-23ia).
                                                                                                               *Additional Grounding
                                                                                            ar
 Fig. liD Simple Radial System With GFR on Main and                                                        Fig. liE Simple Radial System With GFR on Main and
                                                                              lP
                                    Service Source
                                                                                                                                                                 N umber 2
                                                              ca
                                                                                                                                                            Service Source
                                    Number 1
                                       ,-Tnp--                                                                                                           -----,
                                                                                                                                                             Tnp
                                                  tri
                                                                                                                                                                                     �
                                                                                                                                                                        I
                                                                                                                                                                        I
                                                                                                                                                                        L----            M2
                                                                                                                                                                    Neutral Disconnect
                                 lec
T1e
                      ----�.---+--� ------
                    '-
               .E
      Notes:
      GFP Sensing Method
                         Return With Polar1t1es Arran:::�d to Avo1d Neutral Unbalance                                      •T1me/Current Coardmatlon Between Mam. T1e and Feeders
                                                                                                                        Ground Fault Selectivity
      Type of Pr otection
         • Feeders-Zero Sequence
•Zone Select1ve lnterlock1ng May be Added for MmmlUm Arcmg Fault Damage
 Fig. llF Dual Source System Using Center Point Grounding (NEC 250-23a-Exception No. 4)
                                                                                                                                                                                      om
                                                                                                                                                                                                                                     13
                                                                                                                                                                                    .c
               GFR                                                                                                                                               GFR
                                                                                                                                                                  -
               iiii1                                                                                                                                             M2
       8 I 9 110 111
       I               I
                       I
                                          cp�                                                                                                             8 I 9 110 111
                                                                                                                                                          I
                                                                                                                                                                       I
                                                                      �1                                       1
                                           v
��
                                                                                                                                                 ls
                                                                                              GFR-                              n0
                                                                                                                  M2
                                      r------<
                                                                      a     -                  Tie             -,a               1-----,
                                      I
                                                                                           8j9 L10j11
                                                                                                                                              ua
                                               -
                                                                                                               ��
                               CDI                                                                                                    CD:
                               �#          Tie.�                                                                             Tie__    Tie   +-
                                cs          b ;r
                                                                           n
                                                                                             ll
                                                                                                                                                                                               Notes:
                                                                                                                             an
                                                                                                                                                                                                    Bus 1 or 2.
                                                                                                                                                                 F2
       8 I 9 110 111                                                                                                             ��                       8 I 9llOJ11
                                                                                                  -:ra
                                                                                                                                                                                               @ Add Cell Switch Contacts When
       I II                                      <T         v
                                                                                                                                                     _jl                                            Tie is Drawout Construction.
                                                                                                                                                                                               0 Steering D iodes
                                                                                                                                                                                                    (Similar to 1N457)
                                                                            II"'""I
                                                                                                               tM
                                                                            lo...l                              l..oll
                                                                                                                 �
 Fig. l lG Special Zone Interlocking Wiring that may be used with Dual Source System using Center Point Grounding
                       (See Figure llF)©
                                                                                             ar
                                                        Service Source                                                                                           Service Source
                                                        Number 1                                                                                                           Number 2
                               lj�                                                                                                                                                         1Jj-<
                                                                            lP
                                                ;clarityMarks
                                           /
                                                                                                                                                                  (fh
                                                        ca
                           GF�
                                     >-tft-'
                                                                                                                                                                                                    � ��� �
                  "
                                                                                                                                                                                                -
                                      .,r-c�I�                                                                                                       L
                           M1A
lGFR Tnp
     I                                                  r       ZSI
                                                                                      I                         w
                                                                                                                  l                                  Note@            M2
                                                                                                                                                                       ZSI         I
                                                                                                                                                                                     -r---t - /M2
                                                                  ---zSITrip
                                          tri
     ZoneM1                                                                                                                                                      _                                                         ZoneM
                                                                                                          Gi's�,NoteG)r-Gi's
                                                                                                                                                                                   j
                                                                                                                                                                                         ZSI
                                                        L_                                        -                                          -       �P
                           *__)o,
                                                                                                                                     MlB
                  f
                                                                                          ____                                                        _____                    _
Phase
                                                                                                 rr                                         iT
                                                                                                         M2s      �:;.-
           Note
                           --                                                                    �--�-
                                                                       Neutral
                                                                                                                                             -1-
                                                                                                                         T
                           -
           CD -                                                                                  ,__,                                       '--"--
                                                                                                                                                                               m
 .E
                                                                                                                                                              ��!:
           J
      Fee r Zone
                                                                                                                                                              load 2       I
     Notes:
       •Mams/Feeders-Zero Sequence.                                         • Zone Differential for Fault Area IsolatiOn.                                                          (j) Zone Interlock Wiring Should beTwisted
     GFP Sensing Method                                                   Ground Fault Selectivity
                                                                            •T1me/Cunent Coordmat1on BetweenMain and Downstream Feeders W1thm Zone.                                     Pa1r. Refer to
w
       •Two level for Improved Service ContinUity                           • Feeder Tnps BeforeMain/Tie for Fault in Feeder Zone.                                                 CD Control Power for GFRM1, GFRM2 andT
     Type of Protection                                                                                                                                                                                  4.2.2.1.
       • Zone Select1ve Interlocking forMinimum                             •MainTrips Without Pre-setTime Delay for Fault 1nMain Zone                                                 Should be Supplied From Common Source.
         Arcing Fault Damage
                                                                            • Not Permitted Downstream of Service Disconnect per NEC 250-23(a)                                     @ Refer to 5.8.3.6
                                                                       * Additional Grounding
ww
Fig. l lH Multiple Source, Multiple Grounded System Using Zone Differential Sensing
                                                                                                                                 .c
                                         f---6
                                             --- .500-------..1                                            Plus Panel   {
                                         t-----6.000-------.j                                .250          Thickness
                                          1+-----4.688----..1
1 2 3 4 5 6 7 8 9
                                 1.375
                                                 t2Hb0000000
                                                                                                                      ls
                                                 000000000
1.375
                                                                                                                   ua
                                                                                                    an
                                                                                              .170 Diameter (4)
                                                                                              Mounting Holes
                                                                                         tM
                                                                                     ar
                                                                     lP
 Fig. 12 Outline of Catalog No. GFRTPD and GFRTP Ground Fault Test Panels©
                                                     ca
                .1s
                       Panel Cutout
                             I             "
                                                     .170 Diameter (4)   �               7.0 GROUND FAULT TEST PANEL (See Fig. 4)
        -.-.L-.EJ
             •A-:r-
           �r�
                                 ---
        5.000
                                                                                         rent from a location remote from the disconnect using a
                4.63                                                                     separate power source. Provisions are available to conduct
                                                                                         a test in either of two operational modes: By opening the
                                                                                         disconnect or by not opening the disconnect.
           .E
                       f------:��0------jf
                                                                             I
                                                                                         method to conduct ground fault tests on a repeat basis.
                                                                                         Tests can be conducted by qualified maintenance person
                                                                                         nel during routine maintenance schedules.
w
                                                                                                            .c
     The test panel is available only as a semi-flush, cover                    1. Turn selector switch to "TEST" - Hold one second
     mounted assembly under Cat. No. GFRTP or GFRTPD                               Red and Amber lamps turn "ON"
     (for de control) as illustrated in Fig. 4. It is provided
     with a selector switch for initiating the desired test                     2. Turn selector switch to "RESET" - Hold six seconds
                                                                                            ls
     sequence, a red lamp to signify a ground fault trip opera                    Red and Amber lamps turn "OFF"
     tion, an amber lighteD to indicate the availability of test
     power to the test panel, and an instruction nameplate.                     3. Release selector switch - spring return to "Normal"
                                                                                         ua
     Outline dimensions are shown in Fig. 12 with panel cut
     out and drilling plan details in Fig. 13.                                  7.4.5 TEST WITH SERVICE INTERRUPTION©
                                                                                an
     Test Winding                                                               2. Turn selector switch to "TEST" - Hold one second
     Requires a 120 Volt, 50/60 Hz. control power source                           Breaker/Interrupter "OPENS"
     (300 VA) for operation.                                                       Red and Amber lamps turn "ON"
     Ac Control Circuit
     Requires a 120 Volt, 50/60 Hz., 0.125 Amp source; use
     same source as Test Winding, above.                             tM         3. Turn selector switch to "RESET" - Hold six seconds
                                                                                   Red and Amber lamps turn "OFF"
     Test Power Lamp "OFF"                                                      Fig. 14A illustrates the external connections required for
     Ground Fault Lamp "OFF"                                                    a complete GFP system using 1 20 volt a-c, 50/60Hz.
     Selector Switch in "NOR MAL" position                                      control power, including: Type GFR Relay, a ground
                                                                                fault sensor (GFS) and a test panel. A tabulation is also
                         tri
     7.4.2 IF GRO UND FAULT OCC URS©                                            shown to illustrate the various contact positions of the
                                                                                selector switch and red lamp (switch). Fig. 14B illustrates
     1. Breaker/Interrupter "OPENS"                                             the external connections required for 1 25 volt d-e control
   lec
     7.4.3 ACTION REQUIRED                                                         Proper operation of the GFP system requires the use of
     1. Locate and clear ground fault condition                                 twisted wire connections on certain terminations. Details
     2. Turn selector to "RESET" - hold six seconds                             are provided on the various connection diagrams including
 .E
3. Release selector switch - spring return to "Normal" Fig. 7. Refer also to 4.2.2.1.
     <D Note:   The   amber   light   turns   "on"   only   during   a   test
       sequence.
                                                                            om
                                                                          .c
28
                                                     ls
                                           () 8         ,.
() . D . o ..
                                                  ua
                                                        ,
                                                ;'lft
                                                  )-t-1
                                                Jf�J.4..
                                              an
                                                        �CI.i       A.,
                                           tM
                                         ar
                                        lP
                              ca
                        tri
        lec
      .E
 w
ww
               -
     Westinghouse
     rom"�'"-     Elecfrlc
                        . Corporation