0% found this document useful (0 votes)
45 views49 pages

Terminal Blocks: Excerpt From General Catalogue Ed.60

This document provides specifications for one-way terminal blocks, including connection capabilities for different conductor sections, rated voltages, test currents, and dimensions. Terminal blocks are available for conductor sections from 1.5 to 16 mm2 and rated voltages up to 450V. Information is given on materials, temperature ratings, and compliance with relevant standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
45 views49 pages

Terminal Blocks: Excerpt From General Catalogue Ed.60

This document provides specifications for one-way terminal blocks, including connection capabilities for different conductor sections, rated voltages, test currents, and dimensions. Terminal blocks are available for conductor sections from 1.5 to 16 mm2 and rated voltages up to 450V. Information is given on materials, temperature ratings, and compliance with relevant standards.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 49

TERMINAL BLOCKS

Excerpt from
General Catalogue Ed.60
ONE-WAY

ONE-WAY TERMINAL BLOCKS · END CONNECTORS · BARS


INSULATING HOUSING: transparent polycarbonate (PC) UL 94 V0
CONDUCTIVE BODY: brass
CAPTIVE SCREW IN: galvanized steel
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11
S1 CONDUCTOR TYPE: rigid and flexible
D1
MAX OPERATING TEMPERATURE: 85 °C
W1 L1
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004
TERMINAL BLOCKS

Code Conductor
section
Connection
capability
Connection
capability
Connection
capability
Rated voltage
(V)
Test current
(A)
Screw D1
(mm)
L1
(mm)
W1
(mm)
S1
(mm)
Ways

(mm²) Section N. rigid N. flexible
(mm²) conductors conductors
1.5 2 2
991 1.5 1 2÷3 2÷3 450 18 M3 3,1 7,5 15 14,5 10 10/500
0.75 2÷4 2÷4
2.5 2 2
992 2.5 1.5 2÷3 2÷3 450 24 M3.5 4,1 9 17,5 18,2 10 10/600
1 2÷4 2÷4
4 2 2
9924 4 2.5 2÷3 2÷3 450 32 M4 4,5 10,3 21 20 10 10/400
1.5 2÷4 2÷4
6 2 2
993 6 4 2÷3 2 450 41 M4 6 11,8 22,5 23 10 10/300
2.5 2÷4 2÷4
10 2 2
994 10 6 2÷3 2 450 57 M6 7,9 14,7 26 26 10 10/200
4 2÷4 2÷4
16 2 2
995 16 10 2÷3 2 450 76 M8 10,5 18,8 31,8 32,2 10 10/100
6 2÷4 2÷3

ONE-WAY TERMINAL BLOCKS · END CONNECTORS


INSULATING HOUSING: transparent polycarbonate (PC) UL 94 V0
CONDUCTIVE BODY: brass
CAPTIVE SCREW IN: galvanized steel
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
S1 30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11
CONDUCTOR TYPE: rigid and flexible
MAX OPERATING TEMPERATURE: 85 °C
D1
PROTECTION GRADE: IP00
W1 L1 ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Code Conductor
section
Connection
capability
Connection
capability
Connection
capability
Rated voltage
(V)
Test current
(A)
Screw D1
(mm)
L1
(mm)
W1
(mm)
S1
(mm)

(mm²) Section N. rigid N. flexible
(mm²) conductors conductors
25 2 2
9960 25 16 2÷3 2÷3 450 101 M10 12 22,5 36,3 41,9 25/25
10 2÷4 2÷4
35 2 2
9961 35 25 2÷3 2 450 125 M10 13,9 26,1 43,5 49,4 25/25
16 2÷4 2÷3

112

catalogo BM ed60 EN completo.indb 112 12/01/22 08:57


ONE-WAY

ONE-WAY TERMINAL BLOCKS · END CONNECTORS · WITH MANUAL TIGHTENING


INSULATING HOUSING: transparent polycarbonate (PC) UL 94 V0
CONDUCTIVE BODY: brass
CAPTIVE SCREW IN: galvanized steel
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11
CONDUCTOR TYPE: rigid and flexible
MAX OPERATING TEMPERATURE: 85 °C
PROTECTION GRADE: IP20
D1 ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

TERMINAL BLOCKS
W1
L1

Code Conductor
section
Connection
capability
Connection
capability
Connection
capability
Rated voltage
(V)
Test current
(A)
Screw D1
(mm)
L1
(mm)
W1
(mm)

(mm²) Section N. rigid N. flexible
(mm²) conductors conductors
4 2 2
9924Q 4 2.5 2÷3 2÷3 450 32 M4 4,5 10,3 21 20/20
1.5 2÷4 2÷4
6 2 2
993Q 6 4 2÷3 2 450 41 M4 6 11,8 22,5 20/20
2,5 2÷4 2÷4
10 2 2
994Q 10 6 2÷3 2 450 57 M6 7,9 14,7 26 20/20
4 2÷4 2÷4

ONE-WAY TERMINAL BLOCKS · END CONNECTORS · 2 INPUTS


INSULATING HOUSING: transparent polycarbonate (PC) UL 94 V0
CONDUCTIVE BODY: brass
CAPTIVE SCREW IN: galvanized steel
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
S1 30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11
CONDUCTOR TYPE: rigid and flexible
MAX OPERATING TEMPERATURE: 85 °C
PROTECTION GRADE: IP20
W1 D1

L1 ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Code Conductor
section
Connection
capability
Connection
capability
Connection
capability
Rated voltage
(V)
Test current
(A)
Screw D1
(mm)
L1
(mm)
W1
(mm)
S1
(mm)

(mm²) Section N. rigid N. flexible
(mm²) conductors conductors
16 -
9416 2 x 16 10 2 2 450 76 M5 5,5 20,5 22,6 24,5 30/30
6 2
25 -
9425 2 x 25 16 2 2 450 101 M6 7 25 26,2 25,4 20/20
10 2
35 -
9435 2 x 35 25 2 2 450 125 M8 9 32 31,2 33,4 10/10
16 2

113

catalogo BM ed60 EN completo.indb 113 12/01/22 08:57


ONE-WAY

ONE-WAY TERMINAL BLOCKS · 3 INPUTS


Unipolar terminal block with multiple inputs that can be fixed
on DIN 46277/1 and DIN 46277/3 rail
INSULATING HOUSING: transparent polycarbonate (PC) UL 94 V0
CONDUCTIVE BODY: brass
CAPTIVE SCREW IN: galvanized steel
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par. 30.2.3), EN 60695-2-10
S1
a 850 °C, EN 60695-2-11
CONDUCTOR TYPE: rigid and flexible
MAX OPERATING TEMPERATURE: 85 °C
W1
TERMINAL BLOCKS

L1 ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Code Conductor section


(mm²)
Wire protection Rated voltage
(V)
Test current
(A)
Inputs Stripping
length
Screw L1
(mm)
W1
(mm)
S1
(mm)

(mm)
996 1÷6 stainless steel 450 16 3 10 M4 22 21 24 50/50
9984 16 ÷ 35 750 125 3 18 M8 47 36,4 36 25/25

ONE-WAY TERMINAL BLOCKS · 4 INPUTS


INSULATING HOUSING: transparent polycarbonate (PC) UL 94 V0
CONDUCTIVE BODY: brass
CAPTIVE SCREW IN: galvanized steel
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par. 30.2.3), EN 60695-2-10
a 850 °C, EN 60695-2-11
26 CONDUCTOR TYPE: rigid and flexible
MAX OPERATING TEMPERATURE: 85 °C
PROTECTION GRADE: IP20
25
43 ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Code Conductor section Rated voltage


(mm²) (V)
Test current
(A)
Inputs Stripping
length
Screw

(mm)
998 6 ÷ 16 750 40 4 10 M5 25/25

114

catalogo BM ed60 EN completo.indb 114 12/01/22 08:57


ONE-WAY

ONE-WAY TERMINAL BLOCKS · 5 INPUTS


Unipolar terminal block with multiple inputs that can be fixed
on DIN 46277/1 and DIN 46277/3 rail
INSULATING HOUSING: transparent polycarbonate (PC) UL 94 V0
CONDUCTIVE BODY: brass
CAPTIVE SCREW IN: galvanized steel
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par. 30.2.3), EN 60695-2-10
24 a 850 °C, EN 60695-2-11
CONDUCTOR TYPE: rigid and flexible
21 MAX OPERATING TEMPERATURE: 85 °C
34

TERMINAL BLOCKS
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Code Conductor section


(mm²)
Wire protection Rated voltage
(V)
Test current
(A)
Inputs Stripping
length
Screw

(mm)
997 1÷6 stainless steel 450 16 5 10 M4 50/50

ONE-WAY TERMINAL BLOCKS · 6 INPUTS


INSULATING HOUSING: transparent polycarbonate (PC) UL 94 V0
CONDUCTIVE BODY: brass
SCREW IN: galvanized steel
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par. 30.2.3), EN 60695-2-10
a 850 °C, EN 60695-2-11
S1 CONDUCTOR TYPE: rigid and flexible
MAX OPERATING TEMPERATURE: 85 °C
W1 PROTECTION GRADE: IP20
L1
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Code Conductor section Rated voltage


(mm²) (V)
Test current
(A)
Inputs Stripping
length
Screw L1
(mm)
W1
(mm)
S1
(mm)

(mm)
(2,5 ÷ 6) x 4
9981 750 40 6 11 M4 48 24 26 25/25
(6 ÷ 16) x 2
(6 ÷ 16) x 4 16
9983 750 125 6 M5, M8 77 35 35 25/25
(16 ÷ 35) x 2 18

115

catalogo BM ed60 EN completo.indb 115 12/01/22 08:57


ONE-WAY

ONE-WAY TERMINAL BLOCKS · 11 INPUTS


INSULATING HOUSING: transparent polycarbonate (PC) UL 94 V0
CONDUCTIVE BODY: brass
SCREW IN: galvanized steel
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par. 30.2.3), EN 60695-2-10
a 850 °C, EN 60695-2-11
27 CONDUCTOR TYPE: rigid and flexible
MAX OPERATING TEMPERATURE: 85 °C
24 76 PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004
TERMINAL BLOCKS

Code Conductor section Rated voltage


(mm²) (V)
Test current
(A)
Inputs Stripping
length
Screw

(mm)
(2,5 ÷ 6) x 10
9982 750 40 11 11 M4 25/25
(6 ÷ 16) x 1

ACCESSORIES FOR ONE-WAY TERMINAL BLOCKS WITH MULTIPLE INPUTS · DIN BAR BASE
Base for fixing one-way terminals with multiple inputs on DIN 46277/1
and DIN 46277/3 rail
INSULATING HOUSING: polypropylene (PP) natural color
MAX OPERATING TEMPERATURE: 85 °C
ASSEMBLY: The terminal blocks can be mounted on the rail by means
of a slight pressure and can be released by inserting a screwdriver into
the head opening.

Code Terminal block type Bases per terminal


block

99601 996-997 1 50/50
99811 998-9981 1 50/50
99821 9982 2 50/50
99831 9983 2 50/50
99841 9984 1 50/50

116

catalogo BM ed60 EN completo.indb 116 12/01/22 08:57


ONE-WAY

ONE-WAY TERMINAL BLOCKS · QUICK-CONNECT


One-way push-wire terminal block for rigid conductors
INSULATING HOUSING: polyamide (PA 6.6)
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
CONDUCTOR TYPE: rigid
MAX OPERATING TEMPERATURE: 85 °C
9.5
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-2: 2004
20
L1

TERMINAL BLOCKS
Code Conductor section Rated voltage
(mm²) (V)
Inputs Stripping
length
L1
(mm)

(mm)
803 0,75 ÷ 2,5 450 3 10 ÷ 13 14 100/100
805 0,75 ÷ 2,5 450 5 10 ÷ 13 22 100/100

117

catalogo BM ed60 EN completo.indb 117 12/01/22 08:57


ONE-WAY

INDIRECT CLAMPING TERMINAL BLOCK · TWIN BLOCK


One-way terminal block with multiple inputs and indirect clamping for electrical cables,
useful for channel or flying shunts or junctions.
INSULATING HOUSING: transparent polycarbonate (PC) UL 94 V0
L1 CONDUCTIVE BODY: nickel-plated die-cast brass
SAFETY CLIP IN: black polyamide (PA 6.6)
SCREW IN: galvanized steel

S1
MAX OPERATING TEMPERATURE: 85 °C
W1 CLAMPING TYPE: indirect
TEST VOLTAGE: 2500 V
TERMINAL BLOCKS

PROTECTION GRADE: IP20


ACCORDING TO STD.: EN 60947-7-1, EN 60998-1: 2004, EN 60998-2-1: 2004, EN 60999

Code Conductor section


(mm²)
Connectable flexible conductors
Primary
Connectable flexible conductors
Derivative
Rated voltage
(V)
L1
(mm)
W1
(mm)
S1
(mm)

(mm²) (mm²)
25 25
25 16
25 10
95261 10-25 450 64 27 43 1/10
16 16
16 10
10 10
50 50
50 35
50 25
95262 25-50 450 71 34 49 1/10
35 35
35 25
25 25
95 95
95 70
95 50
95263 50-95 450 77 41 61 1/10
70 70
70 50
50 50
120 120
120 95
120 70
95264 70-120 450 90 50 72 1/5
95 95
95 70
70 70

ASSEMBLY INSTRUCTIONS 3
Remove the black clips, open the blue shell, 2
make electrical connections, close the
shell and insert the safety clips
3

1 3

2
3

CONNECTION TYPES

118

catalogo BM ed60 EN completo.indb 118 12/01/22 08:57


CONNECTORS

POLARIZED PLUG TERMINALS · 2-WAY CONNECTORS · M902 SERIES


BROWN PLUG AND SOCKET: polyamide (PA 6.6) and
25% fiberglass
WHITE PLUG AND SOCKET: polyamide (PA 6.6)
WHITE AND BLACK SHELL AND CABLE CLAMP:
L1
polyamide (PA 6.6)
S1
CONDUCTIVE BODY IN: nickel-plated brass
CAPTIVE SCREW IN: galvanized steel
L1
W1 TEST CURRENT: 16 A
INSULATION SELF-EXTINGUISHING: EN 60335-1:

TERMINAL BLOCKS
2002 +A2:2006 (par. 30.2.3), EN 60695-2-11
RATED IMPULSE VOLTAGE: 4 kV
CONDUCTOR TYPE: rigid and flexible
L1 OPERATING CYCLES: 5000
RATED VOLTAGE: 400 V
S1
POLLUTION DEGREE: 2
L1
W1 PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 61984: 2009

Code Description Section


(mm²)
Operating temperature Terminal Block
Material
Terminal Block
Color
Shells
Material
Shells
Color
Shells W1
Cable clamp (mm)
L1
(mm)
S1
(mm)

B9021 Male plug 2,5 from -10 °C to 105 °C max PA 6.6 White - 19 32 20 100/100
B9022 Female receptacle 2,5 from -10 °C to 105 °C max PA 6.6 White - 19 32 20 100/100
Male plug with from -10 °C to 105
B9023 2,5 PA 6.6 White PA 6.6 White 5,7 - 7 19 60 21 50/50
shell °C max
Female receptacle from -10 °C to 105
B9024 with shell 2,5 PA 6.6 White PA 6.6 White 5,7 - 7 19 60 21 50/50
°C max
Male plug from -10 °C to 150 PA 6.6 +
M9021 2,5 Brown - 19 32 20 100/100
high temperature °C max fiberglass
Female receptacle from -10 °C to 150 PA 6.6 +
M9022 2,5 Brown - 19 32 20 100/100
high temperature °C max fiberglass
Male plug high
from -10 °C to 105 PA 6.6 +
M9023 temperature with 2,5 Brown PA 6.6 Black 5,7 - 7 19 60 21 50/50
°C max fiberglass
shell
Female receptacle
from -10 °C to 105 PA 6.6 +
M9024 high temperature 2,5 Brown PA 6.6 Black 5,7 - 7 19 60 21 50/50
with shell °C max fiberglass

119

catalogo BM ed60 EN completo.indb 119 12/01/22 08:57


CONNECTORS

POLARIZED PLUG TERMINALS · 3-WAY CONNECTORS · M903 SERIES


BROWN PLUG AND SOCKET: polyamide (PA 6.6) and
25% fiberglass
WHITE PLUG AND SOCKET: polyamide (PA 6.6)
WHITE AND BLACK SHELL AND CABLE CLAMP:
polyamide (PA 6.6)
L1
S1
CONDUCTIVE BODY IN: nickel-plated brass
CAPTIVE SCREW IN: galvanized steel
L1
W1 TEST CURRENT: 16 A
INSULATION SELF-EXTINGUISHING: EN 60335-1:
TERMINAL BLOCKS

2002 +A2:2006 (par. 30.2.3), EN 60695-2-11


RATED IMPULSE VOLTAGE: 4 kV
CONDUCTOR TYPE: rigid and flexible

L1
OPERATING CYCLES: 5000
RATED VOLTAGE: 400 V
S1
POLLUTION DEGREE: 2
L1
W1 PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 61984: 2009

Code Description Section


(mm²)
Operating temperature Terminal Block
Material
Terminal Block
Color
Shells
Material
Shells
Color
Shells W1
Cable clamp (mm)
L1
(mm)
S1
(mm)

B9031 Male plug 2,5 from -10 °C to 105 °C max PA 6.6 White - 29 32 20 50/50
B9032 Female receptacle 2,5 from -10 °C to 105 °C max PA 6.6 White - 29 32 20 50/50
Male plug with from -10 °C to 105
B9033 2,5 PA 6.6 White PA 6.6 White 4,5 - 10,5 32 57 23 50/50
shell °C max
Female receptacle from -10 °C to 105
B9034 2,5 PA 6.6 White PA 6.6 White 4,5 - 10,5 32 57 23 50/50
with shell °C max
Male plug from -10 °C to 150 PA 6.6 +
M9031 2,5 Brown - 29 32 20 50/50
high temperature °C max fiberglass
Female receptacle from -10 °C to 150 PA 6.6 +
M9032 2,5 Brown - 29 32 20 50/50
high temperature °C max fiberglass
Male plug
from -10 °C to 105 PA 6.6 +
M9033 high temperature 2,5 Brown PA 6.6 Black 4,5 - 10,5 32 57 23 50/50
°C max fiberglass
with shell
Female receptacle
from -10 °C to 105 PA 6.6 +
M9034 high temperature 2,5 Brown PA 6.6 Black 4,5 - 10,5 32 57 23 50/50
with shell °C max fiberglass

120

catalogo BM ed60 EN completo.indb 120 12/01/22 08:57


CONNECTORS

POLARIZED PLUG TERMINALS · 5-WAY CONNECTORS · M905 SERIES


BROWN PLUG AND SOCKET: polyamide (PA 6.6) and
25% fiberglass
WHITE PLUG AND SOCKET: polyamide (PA 6.6)
WHITE AND BLACK SHELL AND CABLE CLAMP:
S1 polyamide (PA 6.6)
L1 CONDUCTIVE BODY IN: nickel-plated brass

W1
CAPTIVE SCREW IN: galvanized steel
L1
TEST CURRENT: 16 A
INSULATION SELF-EXTINGUISHING: EN 60335-1:

TERMINAL BLOCKS
2002 +A2:2006 (par. 30.2.3), EN 60695-2-11
RATED IMPULSE VOLTAGE: 4 kV
CONDUCTOR TYPE: rigid and flexible
OPERATING CYCLES: 5000
L1
RATED VOLTAGE: 400 V
S1
POLLUTION DEGREE: 2
L1
W1 PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 61984: 2009

Code Description Section


(mm²)
Operating temperature Terminal Block
Material
Terminal Block
Color
Shells
Material
Shells
Color
Shells W1
Cable clamp (mm)
L1
(mm)
S1
(mm)

B9051 Male plug 2,5 from -10 °C to 105 °C max PA 6.6 White - 48,5 32 20 50/50
B9052 Female receptacle 2,5 from -10 °C to 105 °C max PA 6.6 White - 48,5 32 20 50/50
Male plug with from -10 °C to 105 1x(9-14)-
B9053 2,5 PA 6.6 White PA 6.6 White 48,5 76,5 26 50/50
shell °C max 2x(9-10,5)
Female receptacle from -10 °C to 105 1x(9-14)-
B9054 2,5 PA 6.6 White PA 6.6 White 48,5 76,5 26 50/50
with shell °C max 2x(9-10,5)
Male plug high from -10 °C to 150 PA 6.6 +
M9051 2,5 Brown - 48,5 32 20 50/50
temperature °C max fiberglass
Female receptacle from -10 °C to 150 PA 6.6 +
M9052 2,5 Brown - 48,5 32 20 50/50
high temperature °C max fiberglass
Male plug high
from -10 °C to 105 PA 6.6 + 1x(9-14)-
M9053 temperature with 2,5 Brown PA 6.6 Black 48,5 76,5 26 50/50
°C max fiberglass 2x(9-10,5)
shell
Female receptacle
from -10 °C to 105 PA 6.6 + 1x(9-14)-
M9054 high temperature 2,5 Brown PA 6.6 Black 48,5 76,5 26 50/50
with shell °C max fiberglass 2x(9-10,5)

121

catalogo BM ed60 EN completo.indb 121 12/01/22 08:57


CONNECTORS

ACCESSORIES FOR M903 SERIES · 3-WAY SHUNT BLOCK


CONDUCTIVE BODY IN: nickel-plated brass
SHUNT: 3 female sockets + 1 male plug
41.5
INSULATING HOUSING IN: polycarbonate (PC), black
INSULATION SELF-EXTINGUISHING: UL 94 V0

33.5
TERMINAL BLOCKS

39

Code Operating temperature



M9039 90 °C max 10/10

M9039 ASSEMBLY INSTRUCTIONS

122

catalogo BM ed60 EN completo.indb 122 12/01/22 08:57


CONNECTORS

AUTOMATIC CRIMPING CONNECTORS· TERMINALS · M620 SERIES · REEL


TEST CURRENT: 15 A
L1 TERMINAL MATERIAL: tinned brass
L4 L3
RATED VOLTAGE: 300 AC/DC V
L2
MAX CONTACT RESISTANCE: 10 (20 after environmental testing) mΩ
D1

L1
L3 L4

L2

TERMINAL BLOCKS
D1

Code Type Section


(mm²)
Section
(AWG)
Ø insulant
(mm)
Operating temperature Tools L1
(mm)
L2
(mm)
L3
(mm)
L4
(mm)
D1
(mm)

02230 male 0.5÷2.0 (20-14) 1.9 - 3.4 from -25 °C to 105 °C max 53P000 +53M2C2 20,5 12,8 3,2 2,8 2 4000/4000
02240 female 0.5÷2.0 (20-14) 1.9 - 3.4 from -25 °C to 105 °C max 53P000 +53M2C2 20,5 12,8 3,2 2,8 1,9 4000/4000

ACCESSORIES FOR AUTOMATIC CRIMPING CONNECTORS · EXTRACTION TOOL

Code Description

1107 Tool for extracting terminals from housing 1/1

PANEL ASSEMBLY INSTRUCTIONS


L2
L2

W2 W1
W2 W1

W3
L3
L1
L1

SHAPE I SHAPE II

Template for code # ways Shape Panel hole size tolerance ± 0.13 mm
L1 L2 L3 W1 W2 W3

01042 2 I 18,8 3,7 11 7,8 -


01043 3 I 25 3,7 11 7,8 -
01044 4 II 18,8 13,8 4 14,1 9,4 1,6
01046 6 II 25 20 4 14,1 9,4 1,6
01049 9 II 25 20 4 20,3 9,4 1,6
Applicable on boards 0.8 - 2 mm thick

123

catalogo BM ed60 EN completo.indb 123 12/01/22 08:57


CONNECTORS

ACCESSORIES FOR CRIMPING CONNECTORS · M620 SERIES · MALE HOUSING


INSULATING HOUSING IN: polyamide (PA 6.6) natural color
DIELECTRIC STRENGTH: 1500 AC-1 minute V
INSULATION SELF-EXTINGUISHING: UL 94 V2
TERMINAL BLOCKS

Code Type Operating temperature Shells


Material
Shells
Color
Ways Rated voltage
(V)
Current
(A)

01031 male from -25 °C to 105 °C max PA 6.6 Natural 1 300 15 500/500
01032 male from -25 °C to 105 °C max PA 6.6 Natural 2 300 15 500/500
01033 male from -25 °C to 105 °C max PA 6.6 Natural 3 300 14 500/500
01033R male from -25 °C to 105 °C max PA 6.6 Red 3 300 14 500/500
01034 male from -25 °C to 105 °C max PA 6.6 Natural 4 300 13 500/500
01036 male from -25 °C to 105 °C max PA 6.6 Natural 6 300 12 300/300
01039 male from -25 °C to 105 °C max PA 6.6 Natural 9 300 9 200/200

ACCESSORIES FOR CRIMPING CONNECTORS · M620 SERIES · FEMALE HOUSING


INSULATING HOUSING IN: polyamide (PA 6.6) natural color
DIELECTRIC STRENGTH: 1500 AC-1 minute V
INSULATION SELF-EXTINGUISHING: UL 94 V2

Code Type Operating temperature Shells


Material
Shells
Color
Ways Rated voltage
(V)
Current
(A)

01041 female from -25 °C to 105 °C max PA 6.6 Natural 1 300 15 500/500
01042 female from -25 °C to 105 °C max PA 6.6 Natural 2 300 15 500/500
01043 female from -25 °C to 105 °C max PA 6.6 Natural 3 300 14 500/500
01043R female from -25 °C to 105 °C max PA 6.6 Red 3 300 14 500/500
01044 female from -25 °C to 105 °C max PA 6.6 Natural 4 300 13 300/300
01046 female from -25 °C to 105 °C max PA 6.6 Natural 6 300 12 300/300
01049 female from -25 °C to 105 °C max PA 6.6 Natural 9 300 9 200/200

124

catalogo BM ed60 EN completo.indb 124 12/01/22 08:57


CONNECTORS

RJ PHONE PLUGS
CABLE TYPE: phone cables
CONDUCTOR SECTION: (26-24) AWG
L1 INSULATING HOUSING: transparent polycarbonate (PC) UL 94 V2
PIN MATERIAL: phosphor bronze with 50 micro inch gilding

S1

TERMINAL BLOCKS
W1

Code Description Positions -


Contacts
Tools W1
(mm)
L1
(mm)
S1
(mm)

01064 RJ22 4P - 4C 549 6,5 12,5 7,5 100/100
01065 RJ11/RJ14 6P - 4C 549 6,5 12,5 9,5 100/100
01066 RJ12 6P - 6C 549 6,5 12,5 9,5 100/100

RJ 45 LAN PLUGS
CABLE TYPE: 5e category (TIA/EIA-568-B)
CONDUCTOR SECTION: (26-24) AWG
INSULATING HOUSING: transparent polycarbonate (PC) UL 94 V2
L1
PIN MATERIAL: phosphor bronze with 50 micro inch gilding
S1

W1

Code Description Positions -


Contacts
Tools W1
(mm)
L1
(mm)
S1
(mm)

01068 RJ45 8P - 8C 549, 53P5YA 8 21 11,5 100/100
01069 fully shielded RJ45 8P - 8C 549, 53P5YA 8,2 21,2 117 100/100

ACCESSORIES FOR RJ 45 · PLUG BOOTS


MATERIAL: polycarbonate (PC) UL 94 V0

16

28
14

Code Shells
Color

01060B Blue 100/100
01060N Black 100/100
01060R Red 100/100
01060V Green 100/100

125

catalogo BM ed60 EN completo.indb 125 12/01/22 08:57


CONNECTORS

RJ PLUG + PLUG BOOTS + 549 CRIMPING TOOL


TERMINAL BLOCKS

Code Description

RJ plugs for phone and data networks, plug boots and crimping tool
00410
in plastic case

Component Description Pcs / code

549 Crimping tool for RJ connectors 1


01065 RJ phone plugs 100
01068 RJ45 lan plugs 400
01060B Plug boots for RJ45, blu 50
00405 Plastic case 1

126

catalogo BM ed60 EN completo.indb 126 12/01/22 08:57


MULTIWAY TERMINAL BLOCKS

TERMINAL BLOCKS
POLYPROPYLENE TERMINAL BLOCKS STEATITE TERMINAL BLOCKS

300 °C MAX

85 °C MAX
for higher temperatures

• Nylon standard • Nylon “GF”


with fiberglass for the highest
• Nylon “CS” temperatures
with wire protection
• Nylon “GF/CS”
with fiberglass for the highest
temperatures
with wire protection
100 °C ÷125 °C MAX

110 °C ÷150 °C MAX

NYLON TERMINAL BLOCKS

Number of poles More insulating Customizable


1 to 12 base types marking

8.5

FLAT FAST CLAMP RAISED WITH GROUND CONNECTION

127

catalogo BM ed60 EN completo.indb 127 12/01/22 08:57


ACCESSORIES · WAY MARKING
TERMINAL BLOCKS

Ways marking is printed on the insulation of the screws of the terminal blocks. Markings are printed in black on natural colour
terminal blocks, in white on brown terminal blocks. For markings that are not available in the following tables, contact BM.

ACCORDING TO SDT: symbol complies to IEC 60417-5017 (Earth); symbol complies to 60417-5019 (Protective
Earth)

FOR M092 SERIES FOR M093, M093H, N920 SERIES


Drawing # ways Way marking Drawing # ways Way marking
1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12

4376 L 4192 1
1
4377 N 4118 L N
2
4200 2 L N 4350 _
4257 L N 4365 N L
4162 L N 4364 L N
3
4316 N L 4143 L N
4153 N L 4193 L N
4349 6 1 2 3 4 5 6 4117 L N
4157 10 L N N L N L + - 4161 N L
3
4363 12 A B C D E F G H I L M N 4088 N L
4078 _ _
FOR M094 SERIES 4178 N
4223 _ _
Drawing # ways Way marking 4370 L L N
1 2 3 4 5 6 7 8 9 10 11 12 4371 N L L
4091 2 N L 4372 L N L1
4090 N L 4198 1 2 N
4368 G R S 4367 L N + -
4148 N L 4150 4 N 1 2
4154 3 L N 4089 L N _
4288 N L 4187 _ L N
4182 L N 4317 C P A
4119 F _ N 4366 L N + -
4245 N P F 4310 L N X
4327 1 2 N 4177 N L _ _
4 5
4112 L N _ 4247 _ _ _ _
4329 L _ N 4352 N L 1+ 2+
4309 L N _ 4307 L N L
4308 L N L N 4306 N 1 2 3 4
5
4292 N L _ _ 4289 6 L N C M A
4304 1 2 3 N 4369 6 5 4 3 L2 N1
4464 N 1 2 3 4 4186 L N 1 2 3
7
4331 6 2 1 _ _ N 4373 7 6 5 4 3 L2 N1
4305 1 2 3 4 5 4263 L N 1 2 3 4 5 6
4314 P N P N P N P N 4353 8 1 2 3 4 5 6 7 8
12 4374 8 7 6 5 4 3 L2 N1
4152 P N L P N L P N L
4185 L N 1 2 3 4 5
9
4375 9 8 7 6 5 4 3 L2 N1
FOR M095 SERIES 4278
4328 12 P N P N P N P N
Drawing # ways Way marking 4175 P N L P N L P N L
1 2 3 4 5 6 7 8 9 10 11 12

4315 2 N L
4311 1 2
3
4313 L N
4312 6 1 2 3 4 5
4330 P N P N P N P N
12
4176 P N L P N L P N L

128

catalogo BM ed60 EN completo.indb 128 12/01/22 08:57


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · POLYPROPYLENE · 12 WAYS · 920 SERIES


INSULATING HOUSING: polypropylene (PP) natural color
CONDUCTIVE BODY: brass
W2
CAPTIVE SCREW IN: galvanized steel
L2 D2 INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11
CONDUCTOR TYPE: rigid and flexible
S1 MAX OPERATING TEMPERATURE: 85 °C
S2
TEST VOLTAGE: 2500 V (9200, 9201, 9202, 9203), 3000 V (9204)
L3 L4

D1 L1
W1
PROTECTION GRADE: IP20

TERMINAL BLOCKS
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004, EN 60335-
1: 2002 + A2: 2006 (Par. 30.2.3), IEC/EN 60695-2-11

Code Section
(mm²)
Rated
voltage
Test
current
Stripping
length
Screw Torque
(Nm)
L1
(mm)
L2 L3 L4 W1 W2 S1 S2 D1 D2
(mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm) (mm)

(V) (A) (mm)
9200 2,5 400 24 5 M3 0,25 93,7 8 5,6 5,6 16 6 14,7 9 3 2,2 50/700
9201 4 400 32 7 M3 0,25 116,5 10 6 6 20,5 10 17,2 9,5 3,1 3,1 50/500
9202 6 400 41 7,5 M3.5 0,4 139,5 12 7,5 7,5 23,5 10 20,1 11,8 4,2 3,6 50/300
9203 16 450 76 8,5 M4 0,7 175,5 15 10,5 10,5 25,3 11 22,5 13 6 4,1 25/200
9204 25 500 101 11,5 M5 0,8 228 19,5 14 14 35,2 15 33,5 19 7,2 4,1 10/80

129

catalogo BM ed60 EN completo.indb 129 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · N9201 SERIES


Standard version of the N9201 series
INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
W2
CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M3)
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
CONDUCTOR TYPE: rigid and flexible
S1
S2
L3 L4
MAX OPERATING TEMPERATURE: 125 °C
W1
D1 L1 MAX SHORT-TIME TEMPERATURE: 160 °C
TERMINAL BLOCKS

TEST VOLTAGE: 2500 V


STRIPPING LENGTH: 7 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

4 - 400 32 125 0,25

- 18-14 600 15(**) 115 0,5


** 25 A rated for Factory Wiring Only

Code Ways L1
(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

N9201/1 1 6 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201/2 2 16 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201/3 3 26 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201/4 4 36 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201/5 5 46 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201/6 6 56 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1 Contact BM
N9201/7 7 66 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201/8 8 76 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201/9 9 86 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201/10 10 96 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201/11 11 106 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201 12 116,5 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1 50/500

file n° E 70156

130

catalogo BM ed60 EN completo.indb 130 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · N9201 SERIES WITH WIRE PROTECTION
Wire protection version of the N9201 series
INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
W2
CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M3)
WIRE PROTECTION: stainless steel
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
S1
S2
L3 L4
CONDUCTOR TYPE: rigid and flexible
W1
D1 L1 MAX OPERATING TEMPERATURE: 125 °C

TERMINAL BLOCKS
MAX SHORT-TIME TEMPERATURE: 160 °C
TEST VOLTAGE: 2500 V
STRIPPING LENGTH: 7 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

2,5 - 400 24 125 0,25

- 18-14 600 15 (**) 115 0,5


** 25 A rated for Factory Wiring Only

Code Ways L1
(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

N9201CS1 1 6 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201CS2 2 16 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201CS3 3 26 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201CS4 4 36 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201CS5 5 46 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201CS6 6 56 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1 Contact BM
N9201CS7 7 66 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201CS8 8 76 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201CS9 9 86 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201CS10 10 96 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201CS11 11 106 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1
N9201CS 12 116,5 10 5,8 4,2 20,2 10 17,2 9,8 3,1 3,1 50/500

file n° E 70156

131

catalogo BM ed60 EN completo.indb 131 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · N9202 SERIES


Standard version of the N9202 series
INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
W2
CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M3,5)
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
CONDUCTOR TYPE: rigid and flexible
S1
S2
L3 L4
MAX OPERATING TEMPERATURE: 125 °C
W1
D1 L1 MAX SHORT-TIME TEMPERATURE: 160 °C
TERMINAL BLOCKS

TEST VOLTAGE: 2500 V


STRIPPING LENGTH: 7 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

6 10 400 41 125 0,4

Code Ways L1
(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

N9202/1 1 7,5 12 7,4 4,5 23 10 20,1 11,9 4,2 3,6
N9202/2 2 19,5 12 7,4 4,5 23 10 20,1 11,9 4,2 3,6
N9202/3 3 31,5 12 7,4 4,5 23 10 20,1 11,9 4,2 3,6
N9202/4 4 43,5 12 7,4 4,5 23 10 20,1 11,9 4,2 3,6
N9202/5 5 55,5 12 7,4 4,5 23 10 20,1 11,9 4,2 3,6
N9202/6 6 67 12 7,4 4,5 23 10 20,1 11,9 4,2 3,6 Contact BM
N9202/7 7 79 12 7,4 4,5 23 10 20,1 11,9 4,2 3,6
N9202/8 8 91 12 7,4 4,5 23 10 20,1 11,9 4,2 3,6
N9202/9 9 103 12 7,4 4,5 23 10 20,1 11,9 4,2 3,6
N9202/10 10 115 12 7,4 4,5 23 10 20,1 11,9 4,2 3,6
N9202/11 11 127 12 7,4 4,5 23 10 20,1 11,9 4,2 3,6
N9202 12 139,5 12 7,4 4,5 23 10 20,1 11,9 4,2 3,6 10/50

132

catalogo BM ed60 EN completo.indb 132 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M092 SERIES


Standard version of the M092 series
INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
W2 CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M3)
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C

S1
CONDUCTOR TYPE: rigid and flexible
S2
L3 L4
TEST VOLTAGE: 2500 V
W1
D1 L1 STRIPPING LENGTH: 5 mm

TERMINAL BLOCKS
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

2,5 - 250/380 24 125 0,25

- 20-16 600 10 (*) 105 0,5


* 15 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

92/1 1 Natural 5,6 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92/2 2 Natural 13,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92/3 3 Natural 21,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92/4 4 Natural 30 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92/5 5 Natural 37,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92/6 6 Natural 45,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6 Contact BM
92/7 7 Natural 54 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92/8 8 Natural 61,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92/9 9 Natural 69,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92/10 10 Natural 77,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92/11 11 Natural 85,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
M092 12 Natural 93,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6 50/700

file n° E 70156

133

catalogo BM ed60 EN completo.indb 133 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M092 SERIES WITH WIRE PROTECTION
Wire protection version of the M092 series
INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
W2 CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M3)
WIRE PROTECTION: stainless steel

S1
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
S2
L3 L4
CONDUCTOR TYPE: rigid and flexible
W1
D1 L1 TEST VOLTAGE: 2500 V
TERMINAL BLOCKS

STRIPPING LENGTH: 5 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

2,5 - 250/380 24 125 0,25

- 20-16 600 10 (*) 105 0,5


* 15 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

92CS1 1 Natural 5,6 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92CS2 2 Natural 13,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92CS3 3 Natural 21,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92CS4 4 Natural 30 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92CS5 5 Natural 37,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92CS6 6 Natural 45,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6 Contact BM
92CS7 7 Natural 54 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92CS8 8 Natural 61,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92CS9 9 Natural 69,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92CS10 10 Natural 77,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92CS11 11 Natural 85,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
M92CS 12 Natural 93,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6 50/700

file n° E 70156

134

catalogo BM ed60 EN completo.indb 134 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M093 SERIES


Standard version of the M093 series
INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
W2 CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M3)
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C

S1
CONDUCTOR TYPE: rigid and flexible
S2
L3 L4
TEST VOLTAGE: 2500 V
W1
D1 L1 STRIPPING LENGTH: 7 mm

TERMINAL BLOCKS
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

4 - 400 32 125 0,25

- 18-12 600 20 (*) 105 0,5


* 30 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

93/1 1 Natural 6,7 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93/2 2 Natural 16,7 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93/3 3 Natural 26,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93/4 4 Natural 36,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93/5 5 Natural 46,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93/6 6 Natural 56,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3 Contact BM
93/7 7 Natural 67 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93/8 8 Natural 77 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93/9 9 Natural 87 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93/10 10 Natural 97 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93/11 11 Natural 107 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
M093 12 Natural 117 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3 50/700

file n° E 70156

135

catalogo BM ed60 EN completo.indb 135 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M093 SERIES WITH WIRE PROTECTION
Wire protection version of the M093 series
INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
W2 CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M3)
WIRE PROTECTION: stainless steel

S1
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
S2
L3 L4
CONDUCTOR TYPE: rigid and flexible
W1
D1 L1 TEST VOLTAGE: 2500 V
TERMINAL BLOCKS

STRIPPING LENGTH: 7 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

2,5 - 400 24 125 0,25

- 18-12 600 20 (*) 105 0,5


* 30 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

93CS1 1 Natural 6,7 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93CS2 2 Natural 16,7 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93CS3 3 Natural 26,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93CS4 4 Natural 36,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93CS5 5 Natural 46,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93CS6 6 Natural 56,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3 Contact BM
93CS7 7 Natural 67 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93CS8 8 Natural 77 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93CS9 9 Natural 87 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93CS10 10 Natural 97 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93CS11 11 Natural 107 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
M93CS 12 Natural 117 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3 50/700

file n° E 70156

136

catalogo BM ed60 EN completo.indb 136 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M093H SERIES


Standard version of the M093H series
INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
W2 CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M3)
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
S1
S2 L3 L4
CONDUCTOR TYPE: rigid and flexible
W1 D1 L1 MAX SHORT-TIME TEMPERATURE: 200 °C
L5 TEST VOLTAGE: 2500 V

TERMINAL BLOCKS
STRIPPING LENGTH: 7 mm
PROTECTION GRADE: IP20
CLEARANCE: 8.5 mm to withstand 8000V rated impulse voltage (EN 60335-
1, par.29)
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

4 - 400 32 125 0,25

- 18-12 600 20 (*) 105 0,5


* 30 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
L5
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

M93H1 1 Natural 6,7 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M93H2 2 Natural 16,7 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M93H3 3 Natural 26,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M93H4 4 Natural 36,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M93H5 5 Natural 46,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M93H6 6 Natural 56,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3 Contact BM
M93H7 7 Natural 67 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M93H8 8 Natural 77 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M93H9 9 Natural 87 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M93H10 10 Natural 97 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M93H11 11 Natural 107 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M093H 12 Natural 117 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3 50/500

file n° E 70156

137

catalogo BM ed60 EN completo.indb 137 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M093H SERIES WITH WIRE PROTECTION
Wire protection version of the M093H series
INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
W2 CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M3)
WIRE PROTECTION: stainless steel
S1
S2 L3 L4
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
W1 D1 L1 CONDUCTOR TYPE: rigid and flexible
L5 TEST VOLTAGE: 2500 V
TERMINAL BLOCKS

STRIPPING LENGTH: 7 mm
PROTECTION GRADE: IP20
CLEARANCE: 8.5 mm to withstand 8000V rated impulse voltage (EN 60335-
1, par.29)
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

2,5 - 400 24 125 0,25

- 18-12 600 20 (*) 105 0,5


* 30 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
L5
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

93HCS1 1 Natural 67 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HCS2 2 Natural 16,7 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HCS3 3 Natural 26,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HCS4 4 Natural 36,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HCS5 5 Natural 46,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HCS6 6 Natural 56,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3 Contact BM
93HCS7 7 Natural 67 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HCS8 8 Natural 77 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HCS9 9 Natural 87 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HCS10 10 Natural 97 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HCS11 11 Natural 107 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M93HCS 12 Natural 117 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3 50/50

file n° E 70156

138

catalogo BM ed60 EN completo.indb 138 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M094 SERIES


Standard version of the M094 series
INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
W2 CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M3,5)
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C

S1
CONDUCTOR TYPE: rigid and flexible
S2
L3 L4
TEST VOLTAGE: 2500 V
W1
D1 L1 STRIPPING LENGTH: 7.5 mm

TERMINAL BLOCKS
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

6 - 400 41 125 0,7

- 18-10 600 30 (*) 105 0,9


* 40 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

M94/1 1 Natural 7,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
M94/2 2 Natural 19,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
M94/3 3 Natural 31,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
M94/4 4 Natural 43,6 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
M94/5 5 Natural 55,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
M94/6 6 Natural 68 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1 Contact BM
M94/7 7 Natural 80 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
M94/8 8 Natural 92 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
M94/9 9 Natural 104 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
M94/10 10 Natural 116 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
M94/11 11 Natural 128 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
M094 12 Natural 140 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1 50/300

file n° E 70156

139

catalogo BM ed60 EN completo.indb 139 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M094 SERIES WITH WIRE PROTECTION
Wire protection version of the M094 series
INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
W2 CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M3,5)
WIRE PROTECTION: stainless steel

S1
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
S2
L3 L4
CONDUCTOR TYPE: rigid and flexible
W1
D1 L1 TEST VOLTAGE: 2500 V
TERMINAL BLOCKS

STRIPPING LENGTH: 7.5 mm


PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

4 - 400 23 125 0,9

- 18-10 600 30 (*) 105 0,9


* 40 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

94CS1 1 Natural 7,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94CS2 2 Natural 19,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94CS3 3 Natural 31,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94CS4 4 Natural 43,6 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94CS5 5 Natural 55,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94CS6 6 Natural 68 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1 Contact BM
94CS7 7 Natural 80 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94CS8 8 Natural 92 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94CS9 9 Natural 104 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94CS10 10 Natural 116 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94CS11 11 Natural 128 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
M94CS 12 Natural 140 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1 50/50

file n° E 70156

140

catalogo BM ed60 EN completo.indb 140 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M095 SERIES


Standard version of the M095 series
INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
W2
CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M4)
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
CONDUCTOR TYPE: rigid and flexible
S1
S2
L3 L4
TEST VOLTAGE: 2500 V
W1
D1 L1 STRIPPING LENGTH: 9 mm

TERMINAL BLOCKS
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

10 - 400 57 125 0,7

- 18-8 600 50 105 1,2

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

95/1 1 Natural 9,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95/2 2 Natural 24,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95/3 3 Natural 39 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95/4 4 Natural 54,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95/5 5 Natural 69,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95/6 6 Natural 84 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2 Contact BM
95/7 7 Natural 99 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95/8 8 Natural 114,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95/9 9 Natural 129,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95/10 10 Natural 145 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95/11 11 Natural 160,2 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
M095 12 Natural 174 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2 10/200

file n° E 70156

141

catalogo BM ed60 EN completo.indb 141 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M095 SERIES WITH WIRE PROTECTION

INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2


W2
CONDUCTIVE BODY: nickel-plated brass
L2 D2 CAPTIVE SCREW IN: galvanized steel (M4)
WIRE PROTECTION: stainless steel
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
S1
S2
L3 L4
CONDUCTOR TYPE: rigid and flexible
W1
D1 L1 TEST VOLTAGE: 2500 V
TERMINAL BLOCKS

STRIPPING LENGTH: 9 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

6 - 400 41 125 0,7

- 18-8 600 50 105 1,2

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

95CS1 1 Natural 9,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95CS2 2 Natural 24,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95CS3 3 Natural 39 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95CS4 4 Natural 54,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95CS5 5 Natural 69,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95CS6 6 Natural 84 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2 Contact BM
95CS7 7 Natural 99 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95CS8 8 Natural 114,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95CS9 9 Natural 129,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95CS10 10 Natural 145 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95CS11 11 Natural 160,2 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
M95CS 12 Natural 174 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2 10/10

file n° E 70156

142

catalogo BM ed60 EN completo.indb 142 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · 3-WAY · FOR DIRECT GROUNDING


INSULATING HOUSING: polyamide (PA 6.6) natural color
CONDUCTIVE BODY: nickel-plated brass
D2
L2 W2 CAPTIVE SCREW IN: galvanized steel (M3)
S1 Ø4.2 Ø3.5 ±0.1 Ø4.2 MARKING: L  N on the ways

S2
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
= = CONDUCTOR TYPE: rigid and flexible

L3 MAX OPERATING TEMPERATURE: 100 °C


D1 30 MAX SHORT-TIME TEMPERATURE: 160 °C
L1

TERMINAL BLOCKS
W1
TEST VOLTAGE: 2500 V
STRIPPING LENGTH: 11 mm
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004
ASSEMBLY: Grounding screw hole for metal sheets with
thickness up to 1 mm: Ø 3,5 ± 0,1. Drilling template as shown
in the figure.
GROUNDING SCREW: M4x10

Code Section
(mm²)
Ways Rated
voltage
Test
current
Torque
(Nm)
L1
(mm)
L2
(mm)
L3
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

(V) (A)
M096 2,5 3 400 24 0,25 36 10 24 27 20,5 17,5 10 3,1 4,2 1000/1000

MULTIWAY TERMINAL BLOCKS · NYLON · 3-WAY · FOR FIXING ON SHEET


+0.1 INSULATING HOUSING: polyamide (PA 6.6) white color
26
-0 CONDUCTIVE BODY: nickel-plated brass
L2 W2 = = CAPTIVE SCREW IN: galvanized steel (M3)
S1
GROUNDING FORK FOR M4 SCREW (T VERSION): brass
S2
MARKING: L  N on the ways
21.5 INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
+0.1
4.2 CONDUCTOR TYPE: rigid and flexible
-0
L1 MAX OPERATING TEMPERATURE: 110 °C
W1
MAX SHORT-TIME TEMPERATURE: 160 °C
M4 TEST VOLTAGE: 2500 V
STRIPPING LENGTH: 7 mm
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004
ASSEMBLY: Drilling template as shown in the figure. Fasten on
metal sheets with 0,6 ÷ 1 mm thickness by pressing the pins.

Code Description Section


(mm²)
Rated
voltage
Test
current
Torque
(Nm)
L1
(mm)
L2
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)

(V) (A)
963 2,5 450 24 0,25 27 10 24,5 10 18,5 10,5 1000/1000
with stainless
963CS steel wire 2,5 450 24 0,25 27 10 24,5 10 18,5 10,5 1000/1000
protection

143

catalogo BM ed60 EN completo.indb 143 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 5 WAYS · WITH FUSE HOLDER · M097 SERIES
Standard version of the M097 series
INSULATING HOUSING: polyamide (PA 6.6) white color
CONDUCTIVE BODY: nickel-plated brass
CAPTIVE SCREW IN: galvanized steel (M3)
FUSE: 5x20 fuse compliant to IEC 127 (not included)
INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C
L4 CONDUCTOR TYPE: rigid and flexible
MAX OPERATING TEMPERATURE: 100 °C
L3
TERMINAL BLOCKS

MAX SHORT-TIME TEMPERATURE: 160 °C


TEST VOLTAGE: 2500 V
STRIPPING LENGTH: 7 mm
ACCORDING TO STD.: EN 60257, EN 60998-1: 2004, EN 60998-
2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

2,5 - 450 24 100 0,25

Code Ways L1
(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)

971 1 12,85 10 20 10 21 10 22,7 100/100


972 2 22,05 10 20 10 21 10 22,7 100/100
973 3 32,05 10 20 10 21 10 22,7 100/100
974 4 42,05 10 20 10 21 10 22,7 100/100
975 5 52,05 10 20 10 21 10 22,7 100/100

144

catalogo BM ed60 EN completo.indb 144 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 5 WAYS · WITH FUSE HOLDER · M097 SERIES WITH WIRE
PROTECTION
Wire protection version of the M097 series
INSULATING HOUSING: polyamide (PA 6.6) white color
CONDUCTIVE BODY: nickel-plated brass
L2
CAPTIVE SCREW IN: galvanized steel (M3)
WIRE PROTECTION: stainless steel
S1 FUSE: 5x20 fuse compliant to IEC 127 (not included)
W2 L4 INSULATION SELF-EXTINGUISHING: EN 60695-2-10 a 850 °C

TERMINAL BLOCKS
CONDUCTOR TYPE: rigid and flexible
W1 L1 L3
MAX OPERATING TEMPERATURE: 100 °C
MAX SHORT-TIME TEMPERATURE: 160 °C
TEST VOLTAGE: 2500 V
STRIPPING LENGTH: 7 mm
ACCORDING TO STD.: EN 60257, EN 60998-1: 2004, EN 60998-
2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

2,5 - 450 24 100 0,25

Code Ways L1
(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)

971CS 1 12,85 10 20 10 21 10 22,7 100/100


972CS 2 22,05 10 20 10 21 10 22,7 100/100
973CS 3 32,05 10 20 10 21 10 22,7 100/100
974CS 4 42,05 10 20 10 21 10 22,7 100/100
975CS 5 52,05 10 20 10 21 10 22,7 100/100

ACCESSORIES FOR 963/963CS AND M092, M093, M094 SERIES · FORK TERMINAL FOR GROUNDING

24.5
8

Code Description

963T Fork terminal for grounding 100/1000

145

catalogo BM ed60 EN completo.indb 145 12/01/22 08:58


MULTIWAYS

ACCESSORIES FOR M093 SERIES · PROTECTION COVERS · FROM 3 TO 5 WAYS


INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
MAX OPERATING TEMPERATURE: 110 °C
ASSEMBLY: Snap onto M093 series terminal block or fasten with M3 screw
through the through hole on the cover and terminal block.

19.5

32.5
TERMINAL BLOCKS

L1

Code Terminal block ways Color L1


(mm)

933 2-3 Natural 30 1000/1000
935 4-5 Natural 50 500/500

ACCESSORIES FOR M093 AND M094 SERIES · TERMINAL-BLOCK BASES · 3 WAYS


Polyamide holder with cable clamp and cover for M093 and M094 3 series
terminal blocks.
The holder can be supplied without cover.
25 INSULATING HOUSING: polyamide (PA 6.6) natural color UL 94 V2
MAX OPERATING TEMPERATURE: 100 °C
ASSEMBLY: Drilling template as shown in the figure

50.5
31.5

5.2

14.5 ±0.1

Code Description Terminal block ways



M0983 Holder for M093 series 3 1000/1000
M0984 Holder for M094 series 3 1000/1000
M098C protection cover 500/500

146

catalogo BM ed60 EN completo.indb 146 12/01/22 08:58


MULTIWAYS

ACCESSORIES FOR M093 AND M094 SERIES · TERMINAL-BLOCK BASES · 24 WAYS


Accessory for properly routing input and output cables, to increase the insulation between
terminal blocks and board, and to protect against accidental exit of conductors from the
terminal block.
Pre-cut for easy sizing based on the number of terminal block poles.

INSULATING HOUSING: polyamide (PA 6.6) white color UL 94 V2


MAX OPERATING TEMPERATURE: 125 °C

3.5 240

49

TERMINAL BLOCKS
Code Terminal block ways

M099 1-24 50/200

147

catalogo BM ed60 EN completo.indb 147 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M092 SERIES WITH FIBERGLASS
High temperature version of the M092 series
INSULATING HOUSING: polyamide (PA 6.6) brown color and 25%
W2 fiberglass UL 94 V0
CONDUCTIVE BODY: nickel-plated brass
L2 D2
CAPTIVE SCREW IN: galvanized steel (M3)
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
S1 30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11
S2
L3 L4 CONDUCTOR TYPE: rigid and flexible
D1
W1 L1
MAX SHORT-TIME TEMPERATURE: 200 °C
TERMINAL BLOCKS

TEST VOLTAGE: 2500 V


STRIPPING LENGTH: 5 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

2,5 - 250 24 140 0,25

- 20-16 600 10 (*) 110 0,5


* 15 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

92GF1 1 Brown 5,6 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92GF2 2 Brown 13,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92GF3 3 Brown 21,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92GF4 4 Brown 30 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92GF5 5 Brown 37,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92GF6 6 Brown 45,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6 Contact BM
92GF7 7 Brown 54 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92GF8 8 Brown 61,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92GF9 9 Brown 69,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92GF10 10 Brown 77,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92GF11 11 Brown 85,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
M92GF 12 Brown 93,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6 50/50

file n° E 70156

148

catalogo BM ed60 EN completo.indb 148 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M092 SERIES WITH FIBERGLASS AND WIRE
PROTECTION
High temperature version with wire protection of the M092 series
INSULATING HOUSING: polyamide (PA 6.6) brown color and 25%
W2 fiberglass UL 94 V0
CONDUCTIVE BODY: nickel-plated brass
L2 D2
CAPTIVE SCREW IN: galvanized steel (M3)
WIRE PROTECTION: stainless steel
S1
S2
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
L3 L4 30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11

TERMINAL BLOCKS
D1
W1 L1
CONDUCTOR TYPE: rigid and flexible
MAX SHORT-TIME TEMPERATURE: 200 °C
TEST VOLTAGE: 2500 V
STRIPPING LENGTH: 5 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

2,5 - 250 24 140 0,25

- 20-16 600 10 (*) 110 0,5


* 15 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

92FS1 1 Brown 5,6 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92FS2 2 Brown 13,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92FS3 3 Brown 21,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92FS4 4 Brown 30 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92FS5 5 Brown 37,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92FS6 6 Brown 45,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6 Contact BM
92FS7 7 Brown 54 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92FS8 8 Brown 61,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92FS9 9 Brown 69,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92FS10 10 Brown 77,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92FS11 11 Brown 85,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6
92GFCS 12 Brown 93,5 ± 1 8 5,5 2,5 15,2 6 15,3 8,7 3 2,6 50/700

file n° E 70156

149

catalogo BM ed60 EN completo.indb 149 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M093 SERIES WITH FIBERGLASS
High temperature version of the M093 series
INSULATING HOUSING: polyamide (PA 6.6) brown color and 25%
W2 fiberglass UL 94 V0
CONDUCTIVE BODY: nickel-plated brass
L2 D2
CAPTIVE SCREW IN: galvanized steel (M3)
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
S1 30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11
S2
L3 L4 CONDUCTOR TYPE: rigid and flexible
D1
W1 L1
MAX SHORT-TIME TEMPERATURE: 200 °C
TERMINAL BLOCKS

TEST VOLTAGE: 2500 V


STRIPPING LENGTH: 7 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

4 - 400 32 150 0,25

- 18-12 600 20 (*) 110 0,5


* 30 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

93GF1 1 Brown 6,7 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93GF2 2 Brown 16,7 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93GF3 3 Brown 26,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93GF4 4 Brown 36,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93GF5 5 Brown 46,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93GF6 6 Brown 56,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3 Contact BM
93GF7 7 Brown 67 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93GF8 8 Brown 77 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93GF9 9 Brown 87 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93GF10 10 Brown 97 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93GF11 11 Brown 107 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
M93GF 12 Brown 117 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3 50/50

file n° E 70156

150

catalogo BM ed60 EN completo.indb 150 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M093 SERIES WITH FIBERGLASS AND WIRE
PROTECTION
High temperature version with wire protection of the M093 series
INSULATING HOUSING: polyamide (PA 6.6) brown color and 25%
W2 fiberglass UL 94 V0
CONDUCTIVE BODY: nickel-plated brass
L2 D2
CAPTIVE SCREW IN: galvanized steel (M3)
WIRE PROTECTION: stainless steel
S1
S2
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
L3 L4 30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11

TERMINAL BLOCKS
D1
W1 L1
CONDUCTOR TYPE: rigid and flexible
MAX SHORT-TIME TEMPERATURE: 200 °C
TEST VOLTAGE: 2500 V
STRIPPING LENGTH: 7 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

2.5 - 400 24 150 0,25

- 18-12 600 20 (*) 110 0,5


* 30 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

93FS1 1 Brown 6,7 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93FS2 2 Brown 16,7 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93FS3 3 Brown 26,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93FS4 4 Brown 36,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93FS5 5 Brown 46,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93FS6 6 Brown 56,6 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3 Contact BM
93FS7 7 Brown 67 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93FS8 8 Brown 77 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93FS9 9 Brown 87 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93FS10 10 Brown 97 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93FS11 11 Brown 107 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3
93GFCS 12 Brown 117 ± 1 10 6,7 3,3 20,5 10 17,5 10 3,3 3,3 50/50

file n° E 70156

151

catalogo BM ed60 EN completo.indb 151 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M093H SERIES WITH FIBERGLASS
High temperature version of the M093H series
INSULATING HOUSING: polyamide (PA 6.6) brown color and 25%
fiberglass UL 94 V0
W2
CONDUCTIVE BODY: nickel-plated brass
L2 D2
CAPTIVE SCREW IN: galvanized steel (M3)
S1 INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
S2 L3 L4 30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11
W1 D1 L1
CONDUCTOR TYPE: rigid and flexible
L5
MAX SHORT-TIME TEMPERATURE: 200 °C
TERMINAL BLOCKS

TEST VOLTAGE: 2500 V


STRIPPING LENGTH: 7 mm
PROTECTION GRADE: IP20
CLEARANCE: 8.5 mm to withstand 8000V rated impulse voltage (EN 60335-
1, par.29)
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

2,5 - 400 32 150 0,25

- 18-12 600 20 (*) 110 0,5


* 30 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
L5
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

93HGF1 1 Brown 6,7 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HGF2 2 Brown 16,7 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HGF3 3 Brown 26,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HGF4 4 Brown 36,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HGF5 5 Brown 46,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HGF6 6 Brown 56,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3 Contact BM
93HGF7 7 Brown 67 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HGF8 8 Brown 77 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HGF9 9 Brown 87 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HGF10 10 Brown 97 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HGF11 11 Brown 107 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M93HGF 12 Brown 117 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3 50/50

file n° E 70156

152

catalogo BM ed60 EN completo.indb 152 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M093H SERIES WITH FIBERGLASS AND WIRE
PROTECTION
High temperature version with wire protection of the M093H series
INSULATING HOUSING: polyamide (PA 6.6) brown color and 25%
fiberglass UL 94 V0
W2
CONDUCTIVE BODY: nickel-plated brass
L2 D2
CAPTIVE SCREW IN: galvanized steel (M3)
S1 WIRE PROTECTION: stainless steel
S2
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
L3 L4

D1 L1
W1
30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11

TERMINAL BLOCKS
L5
CONDUCTOR TYPE: rigid and flexible
MAX SHORT-TIME TEMPERATURE: 200 °C
TEST VOLTAGE: 2500 V
STRIPPING LENGTH: 7 mm
PROTECTION GRADE: IP20
CLEARANCE: 8.5 mm to withstand 8000V rated impulse voltage (EN 60335-
1, par.29)
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

2,5 - 400 24 150 0,25

- 18-12 600 20 (*) 110 0,5


* 30 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
L5
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

93HFS1 1 Brown 6,7 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HFS2 2 Brown 16,7 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HFS3 3 Brown 26,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HFS4 4 Brown 36,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HFS5 5 Brown 46,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HFS6 6 Brown 56,6 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3 Contact BM
93HFS7 7 Brown 67 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HFS8 8 Brown 77 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HFS9 9 Brown 87 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HFS10 10 Brown 97 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
93HFS11 11 Brown 107 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3
M93HGFCS 12 Brown 117 ± 1 10 6,7 3,4 8,5 20,5 10 20 12,5 3,3 3,3 50/50

file n° E 70156

153

catalogo BM ed60 EN completo.indb 153 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M094 SERIES WITH FIBERGLASS
High temperature version of the M094 series
INSULATING HOUSING: polyamide (PA 6.6) brown color and 25%
W2 fiberglass UL 94 V0
CONDUCTIVE BODY: nickel-plated brass
L2 D2
CAPTIVE SCREW IN: galvanized steel (M3,5)
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
S1 30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11
S2
L3 L4 CONDUCTOR TYPE: rigid and flexible
D1
W1 L1
MAX SHORT-TIME TEMPERATURE: 200 °C
TERMINAL BLOCKS

TEST VOLTAGE: 2500 V


STRIPPING LENGTH: 7.5 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

6 - 400 41 140 0,7

- 18-10 600 30 (*) 110 0,9


* 40 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

94GF1 1 Brown 7,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94GF2 2 Brown 19,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94GF3 3 Brown 31,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94GF4 4 Brown 43,6 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94GF5 5 Brown 55,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94GF6 6 Brown 68 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1 Contact BM
94GF7 7 Brown 80 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94GF8 8 Brown 92 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94GF9 9 Brown 104 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94GF10 10 Brown 116 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94GF11 11 Brown 128 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
M94GF 12 Brown 140 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1 50/50

file n° E 70156

154

catalogo BM ed60 EN completo.indb 154 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M094 SERIES WITH FIBERGLASS AND WIRE
PROTECTION
High temperature version with wire protection of the M094 series
INSULATING HOUSING: polyamide (PA 6.6) brown color and 25%
W2 fiberglass UL 94 V0
CONDUCTIVE BODY: nickel-plated brass
L2 D2
CAPTIVE SCREW IN: galvanized steel (M3,5)
WIRE PROTECTION: stainless steel
S1
S2
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
L3 L4 30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11

TERMINAL BLOCKS
D1
W1 L1
CONDUCTOR TYPE: rigid and flexible
MAX SHORT-TIME TEMPERATURE: 200 °C
TEST VOLTAGE: 2500 V
STRIPPING LENGTH: 7.5 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

4 - 400 23 140 0,7

- 18-10 600 30 (*) 110 0,9


* 40 A rated for Factory Wiring Only

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

94FS1 1 Brown 7,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94FS2 2 Brown 19,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94FS3 3 Brown 31,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94FS4 4 Brown 43,6 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94FS5 5 Brown 55,5 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94FS6 6 Brown 68 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1 Contact BM
94FS7 7 Brown 80 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94FS8 8 Brown 92 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94FS9 9 Brown 104 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94FS11 11 Brown 128 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94FS10 10 Brown 116 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1
94GFCS 12 Brown 140 ± 1 12 7,3 4,7 23 10 20,7 12,2 4,2 3,1 50/300

file n° E 70156

155

catalogo BM ed60 EN completo.indb 155 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M095 SERIES WITH FIBERGLASS
High temperature version of the M095 series
INSULATING HOUSING: polyamide (PA 6.6) brown color and 25%
W2 fiberglass UL 94 V0
CONDUCTIVE BODY: nickel-plated brass
L2 D2
CAPTIVE SCREW IN: galvanized steel (M4)
INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
S1 30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11
S2
L3 L4 CONDUCTOR TYPE: rigid and flexible
W1
D1 L1 MAX SHORT-TIME TEMPERATURE: 200 °C
TERMINAL BLOCKS

TEST VOLTAGE: 2500 V


STRIPPING LENGTH: 9 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

10 - 400 57 140 0,7

- 18-8 600 50 110 1,2

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

95GF1 1 Brown 9,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95GF2 2 Brown 24,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95GF3 3 Brown 39 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95GF4 4 Brown 54,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95GF5 5 Brown 69,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95GF6 6 Brown 84 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2 Contact BM
95GF7 7 Brown 99 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95GF8 8 Brown 114,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95GF9 9 Brown 129,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95GF10 10 Brown 145 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95GF11 11 Brown 160,2 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
M95GF 12 Brown 174 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2 10/10

file n° E 70156

156

catalogo BM ed60 EN completo.indb 156 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · NYLON · FROM 1 TO 12 WAYS · M095 SERIES WITH FIBERGLASS AND WIRE
PROTECTION
High temperature version with wire protection of the M095 series
INSULATING HOUSING: polyamide (PA 6.6) brown color and 25%
W2 fiberglass UL 94 V0
CONDUCTIVE BODY: nickel-plated brass
L2 D2
CAPTIVE SCREW IN: galvanized steel (M4)
WIRE PROTECTION: stainless steel
S1 INSULATION SELF-EXTINGUISHING: EN 60335-1: 2002+A2:2006 (par.
S2
30.2.3), EN 60695-2-10 a 850 °C, EN 60695-2-11

TERMINAL BLOCKS
L3 L4

W1
D1 L1 CONDUCTOR TYPE: rigid and flexible
MAX SHORT-TIME TEMPERATURE: 200 °C
TEST VOLTAGE: 2500 V
STRIPPING LENGTH: 9 mm
PROTECTION GRADE: IP20
ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Section Section Rated voltage Test current Max operating Torque


(mm²) (AWG) (V) (A) temperature (Nm)
(°C)

6 - 400 41 140 0,7

- 18-8 600 50 110 1,2

Code Ways Color L1


(mm)
L2
(mm)
L3
(mm)
L4
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
S2
(mm)
D1
(mm)
D2
(mm)

95FS1 1 Brown 9,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95FS2 2 Brown 24,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95FS3 3 Brown 39 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95FS4 4 Brown 54,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95FS5 5 Brown 69,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95FS6 6 Brown 84 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2 Contact BM
95FS7 7 Brown 99 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95FS8 8 Brown 114,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95FS9 9 Brown 129,5 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95FS10 10 Brown 145 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95FS11 11 Brown 160,2 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2
95GFCS 12 Brown 174 ± 1 15 9,4 5,6 25,3 11 25,7 15,7 5 4,2 10/200

file n° E 70156

157

catalogo BM ed60 EN completo.indb 157 12/01/22 08:58


MULTIWAYS

ACCESSORIES FOR M093 SERIES · PROTECTION COVERS WITH FIBERGLASS · FROM 3 TO 5 WAYS
INSULATING HOUSING: polyamide (PA 6.6) brown color and 25% fiberglass UL 94 V0
MAX OPERATING TEMPERATURE: 150 °C
ASSEMBLY: Snap onto M093 series terminal block or fasten with M3 screw
through the through hole on the cover and terminal block.

19.5

32.5
TERMINAL BLOCKS

L1

Code Terminal block ways Color L1


(mm)

933GF 2-3 Brown 30 1000/1000
935GF 4-5 Brown 50 500/500

158

catalogo BM ed60 EN completo.indb 158 12/01/22 08:58


MULTIWAYS

MULTIWAY TERMINAL BLOCKS · STEATITE


Terminal blocks for high temperature applications
INSULATING HOUSING: steatite
L4 W2
L3 CONDUCTIVE BODY: brass
D2 CONDUCTOR TYPE: rigid and flexible
L2 L5
MOUNTING HOLE: through hole (no threaded)
L1
MAX OPERATING TEMPERATURE (METALLIC PARTS): 300 °C
L1
S1
MAX OPERATING TEMPERATURE (INSULATING HOUSING): 1000 °C
L1 PROTECTION GRADE: IP00

TERMINAL BLOCKS
W1
D1 ACCORDING TO STD.: EN 60998-1: 2004, EN 60998-2-1: 2004

Code Section
(mm²)
Ways Test current
(A)
Screw Torque
(Nm)
L1
(mm)
L2
(mm)
L3
(mm)
L4
(mm)
L5
(mm)
W1
(mm)
W2
(mm)
S1
(mm)
D1
(mm)
D2
(mm)

9516 1 32 M3 0,25 10 25 10 18,5 3,1 117/117


9517 4 2 32 M3 0,25 22 11,5 25 10 18,5 3,1 4,1 54/54
9518 3 32 M3 0,25 34 11,5 11,5 11,5 25 10 18,5 3,1 4,1 36/36
9519 1 41 M3.5 0,4 11 26 10 20,5 4,2 117/117
9520 6 2 41 M3.5 0,4 24 12,5 26 10 20,5 4,2 4,1 54/54
9521 3 41 M3.5 0,4 37 11,5 11,5 11,5 26 10 20,5 4,2 4,1 36/36
9522 1 76 M4 0,7 15 32,5 13 23 6 54/54
9523 16 2 76 M4 0,7 30 14,5 32,5 13 23 6 4,1 27/27
9524 3 76 M4 0,7 45 11,5 11,5 11,5 32,5 13 23 6 4,1 18/18

159