Contator 110v 150a

This document provides technical specifications for a 3RT1064-6AF36 power contactor. It lists detailed ratings and parameters including voltage, current, power, temperature ranges, and more. The contactor has a rated current of 225A at 400V AC-3 and is designed for industrial applications requiring high current switching.

Uploaded by

Murky Nightblue
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
9 views8 pages

Contator 110v 150a

This document provides technical specifications for a 3RT1064-6AF36 power contactor. It lists detailed ratings and parameters including voltage, current, power, temperature ranges, and more. The contactor has a rated current of 225A at 400V AC-3 and is designed for industrial applications requiring high current switching.

Uploaded by

Murky Nightblue
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

Data sheet 3RT1064-6AF36

power contactor, AC-3e/AC-3 225 A, 110 kW / 400 V AC (50-60 Hz) / DC


Uc: 110-127 V 3-pole, auxiliary contacts 2 NO + 2 NC drive: conventional
main circuit: busbar control and auxiliary circuit: screw terminal

product brand name SIRIUS


product designation Power contactor
product type designation 3RT1
General technical data
size of contactor S10
product extension
● function module for communication No
● auxiliary switch Yes
power loss [W] for rated value of the current
● at AC in hot operating state 51 W
● at AC in hot operating state per pole 17 W
● without load current share typical 7.4 W
insulation voltage
● of main circuit with degree of pollution 3 rated value 1 000 V
● of auxiliary circuit with degree of pollution 3 rated 500 V
value
surge voltage resistance
● of main circuit rated value 8 kV
● of auxiliary circuit rated value 6 kV
maximum permissible voltage for safe isolation between 690 V
coil and main contacts according to EN 60947-1
shock resistance at rectangular impulse
● at AC 8,5g / 5 ms, 4,2g / 10 ms
● at DC 8,5g / 5 ms, 4,2g / 10 ms
shock resistance with sine pulse
● at AC 13,4g / 5 ms, 6,5g / 10 ms
● at DC 13,4g / 5 ms, 6,5g / 10 ms
mechanical service life (operating cycles)
● of contactor typical 10 000 000
● of the contactor with added electronically optimized 5 000 000
auxiliary switch block typical
● of the contactor with added auxiliary switch block 10 000 000
typical
reference code according to IEC 81346-2 Q
Substance Prohibitance (Date) 05/01/2012
Ambient conditions
installation altitude at height above sea level maximum 2 000 m
ambient temperature
● during operation -25 ... +60 °C
● during storage -55 ... +80 °C
relative humidity minimum 10 %
relative humidity at 55 °C according to IEC 60068-2-30 95 %
maximum

3RT10646AF36 Subject to change without notice


2/20/2023
Page 1/8 © Copyright Siemens
Main circuit
number of poles for main current circuit 3
number of NO contacts for main contacts 3
operating voltage
● at AC-3 rated value maximum 1 000 V
● at AC-3e rated value maximum 1 000 V
operational current
● at AC-1 at 400 V at ambient temperature 40 °C 275 A
rated value
● at AC-1
— up to 690 V at ambient temperature 40 °C 275 A
rated value
— up to 690 V at ambient temperature 60 °C 250 A
rated value
— up to 1000 V at ambient temperature 40 °C 100 A
rated value
— up to 1000 V at ambient temperature 60 °C 100 A
rated value
● at AC-3
— at 400 V rated value 225 A
— at 500 V rated value 225 A
— at 690 V rated value 225 A
— at 1000 V rated value 68 A
● at AC-3e
— at 400 V rated value 225 A
— at 500 V rated value 225 A
— at 1000 V rated value 68 A
● at AC-4 at 400 V rated value 195 A
● at AC-5a up to 690 V rated value 242 A
● at AC-5b up to 400 V rated value 186 A
● at AC-6a
— up to 230 V for current peak value n=20 rated 225 A
value
— up to 400 V for current peak value n=20 rated 225 A
value
— up to 500 V for current peak value n=20 rated 225 A
value
— up to 690 V for current peak value n=20 rated 225 A
value
— up to 1000 V for current peak value n=20 rated 68 A
value
● at AC-6a
— up to 230 V for current peak value n=30 rated 172 A
value
— up to 400 V for current peak value n=30 rated 172 A
value
— up to 500 V for current peak value n=30 rated 172 A
value
— up to 690 V for current peak value n=30 rated 172 A
value
— up to 1000 V for current peak value n=30 rated 68 A
value
minimum cross-section in main circuit at maximum AC-1 150 mm²
rated value
operational current for approx. 200000 operating
cycles at AC-4
● at 400 V rated value 96 A
● at 690 V rated value 85 A
operational current
● at 1 current path at DC-1
— at 24 V rated value 200 A
— at 60 V rated value 200 A
— at 110 V rated value 18 A
— at 220 V rated value 3.4 A
— at 440 V rated value 0.8 A
— at 600 V rated value 0.5 A
● with 2 current paths in series at DC-1

3RT10646AF36 Subject to change without notice


2/20/2023
Page 2/8 © Copyright Siemens
— at 24 V rated value 200 A
— at 60 V rated value 200 A
— at 110 V rated value 200 A
— at 220 V rated value 20 A
— at 440 V rated value 3.2 A
— at 600 V rated value 1.6 A
● with 3 current paths in series at DC-1
— at 24 V rated value 200 A
— at 60 V rated value 200 A
— at 110 V rated value 200 A
— at 220 V rated value 200 A
— at 440 V rated value 11 A
— at 600 V rated value 4A
● at 1 current path at DC-3 at DC-5
— at 24 V rated value 200 A
— at 60 V rated value 7.5 A
— at 220 V rated value 0.6 A
— at 440 V rated value 0.17 A
— at 600 V rated value 0.12 A
● with 2 current paths in series at DC-3 at DC-5
— at 24 V rated value 200 A
— at 60 V rated value 200 A
— at 110 V rated value 200 A
— at 220 V rated value 2.5 A
— at 440 V rated value 0.65 A
— at 600 V rated value 0.37 A
● with 3 current paths in series at DC-3 at DC-5
— at 24 V rated value 200 A
— at 60 V rated value 200 A
— at 110 V rated value 200 A
— at 220 V rated value 200 A
— at 440 V rated value 1.4 A
— at 600 V rated value 0.75 A
operating power
● at AC-3
— at 230 V rated value 55 kW
— at 400 V rated value 110 kW
— at 500 V rated value 160 kW
— at 690 V rated value 200 kW
— at 1000 V rated value 90 kW
● at AC-3e
— at 230 V rated value 55 kW
— at 400 V rated value 110 kW
— at 500 V rated value 160 kW
— at 1000 V rated value 90 kW
operating power for approx. 200000 operating cycles
at AC-4
● at 400 V rated value 54 kW
● at 690 V rated value 82 kW
operating apparent power at AC-6a
● up to 230 V for current peak value n=20 rated value 90 000 kVA
● up to 400 V for current peak value n=20 rated value 150 000 VA
● up to 500 V for current peak value n=20 rated value 190 000 VA
● up to 690 V for current peak value n=20 rated value 260 000 VA
● up to 1000 V for current peak value n=20 rated 110 000 VA
value
operating apparent power at AC-6a
● up to 230 V for current peak value n=30 rated value 60 000 VA
● up to 400 V for current peak value n=30 rated value 110 000 VA
● up to 500 V for current peak value n=30 rated value 140 000 VA
● up to 690 V for current peak value n=30 rated value 200 000 VA
● up to 1000 V for current peak value n=30 rated 110 000 VA
value
short-time withstand current in cold operating state
up to 40 °C

3RT10646AF36 Subject to change without notice


2/20/2023
Page 3/8 © Copyright Siemens
● limited to 1 s switching at zero current maximum 4 000 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 5 s switching at zero current maximum 2 807 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 10 s switching at zero current maximum 2 082 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 30 s switching at zero current maximum 1 397 A; Use minimum cross-section acc. to AC-1 rated value
● limited to 60 s switching at zero current maximum 1 144 A; Use minimum cross-section acc. to AC-1 rated value
no-load switching frequency
● at AC 2 000 1/h
● at DC 2 000 1/h
operating frequency
● at AC-1 maximum 750 1/h
● at AC-2 maximum 250 1/h
● at AC-3 maximum 500 1/h
● at AC-3e maximum 500 1/h
● at AC-4 maximum 130 1/h
Control circuit/ Control
type of voltage of the control supply voltage AC/DC
control supply voltage at AC
● at 50 Hz rated value 110 ... 127 V
● at 60 Hz rated value 110 ... 127 V
control supply voltage at DC
● rated value 110 ... 127 V
operating range factor control supply voltage rated
value of magnet coil at DC
● initial value 0.8
● full-scale value 1.1
operating range factor control supply voltage rated
value of magnet coil at AC
● at 50 Hz 0.8 ... 1.1
● at 60 Hz 0.8 ... 1.1
design of the surge suppressor with varistor
apparent pick-up power of magnet coil at AC
● at 50 Hz 590 VA
● at 60 Hz 590 VA
inductive power factor with closing power of the coil
● at 50 Hz 0.9
● at 60 Hz 0.9
apparent holding power of magnet coil at AC
● at 50 Hz 6.7 VA
● at 60 Hz 6.7 VA
inductive power factor with the holding power of the
coil
● at 50 Hz 0.9
● at 60 Hz 0.9
closing power of magnet coil at DC 650 W
holding power of magnet coil at DC 7.4 W
closing delay
● at AC 30 ... 95 ms
● at DC 30 ... 95 ms
opening delay
● at AC 40 ... 80 ms
● at DC 40 ... 80 ms
arcing time 10 ... 15 ms
control version of the switch operating mechanism Standard A1 - A2
Auxiliary circuit
number of NC contacts for auxiliary contacts 2
instantaneous contact
number of NO contacts for auxiliary contacts 2
instantaneous contact
operational current at AC-12 maximum 10 A
operational current at AC-15
● at 230 V rated value 6A
● at 400 V rated value 3A
● at 500 V rated value 2A
● at 690 V rated value 1A

3RT10646AF36 Subject to change without notice


2/20/2023
Page 4/8 © Copyright Siemens
operational current at DC-12
● at 24 V rated value 10 A
● at 48 V rated value 6A
● at 60 V rated value 6A
● at 110 V rated value 3A
● at 125 V rated value 2A
● at 220 V rated value 1A
● at 600 V rated value 0.15 A
operational current at DC-13
● at 24 V rated value 10 A
● at 48 V rated value 2A
● at 60 V rated value 2A
● at 110 V rated value 1A
● at 125 V rated value 0.9 A
● at 220 V rated value 0.3 A
● at 600 V rated value 0.1 A
contact reliability of auxiliary contacts 1 faulty switching per 100 million (17 V, 1 mA)
UL/CSA ratings
full-load current (FLA) for 3-phase AC motor
● at 480 V rated value 180 A
● at 600 V rated value 192 A
yielded mechanical performance [hp]
● for 3-phase AC motor
— at 200/208 V rated value 60 hp
— at 220/230 V rated value 75 hp
— at 460/480 V rated value 150 hp
— at 575/600 V rated value 200 hp
contact rating of auxiliary contacts according to UL A600 / Q600
Short-circuit protection
design of the fuse link
● for short-circuit protection of the main circuit
— with type of coordination 1 required gG: 500 A (690 V, 100 kA)
— with type of assignment 2 required gG: 400 A (690 V, 100 kA), aM: 315 A (690 V, 50 kA), BS88: 400 A (415
V, 50 kA)
● for short-circuit protection of the auxiliary switch gG: 10 A (500 V, 1 kA)
required
Installation/ mounting/ dimensions
mounting position with vertical mounting surface +/-90° rotatable, with vertical mounting
surface +/- 22.5° tiltable to the front and back
fastening method screw fixing
● side-by-side mounting Yes
height 210 mm
width 145 mm
depth 202 mm
required spacing
● with side-by-side mounting
— forwards 20 mm
— upwards 10 mm
— downwards 10 mm
— at the side 0 mm
● for grounded parts
— forwards 20 mm
— upwards 10 mm
— at the side 10 mm
— downwards 10 mm
● for live parts
— forwards 20 mm
— upwards 10 mm
— downwards 10 mm
— at the side 10 mm
Connections/ Terminals
type of electrical connection
● for main current circuit Connection bar

3RT10646AF36 Subject to change without notice


2/20/2023
Page 5/8 © Copyright Siemens
● for auxiliary and control circuit screw-type terminals
● at contactor for auxiliary contacts Screw-type terminals
● of magnet coil Screw-type terminals
width of connection bar 25 mm
thickness of connection bar 6 mm
diameter of holes 11 mm
number of holes 1
connectable conductor cross-section for main
contacts
● stranded 70 ... 240 mm²
connectable conductor cross-section for auxiliary
contacts
● solid or stranded 0.5 ... 4 mm²
● finely stranded with core end processing 0.5 ... 2.5 mm²
type of connectable conductor cross-sections
● for auxiliary contacts
— solid 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²), max. 2x (0.75 ... 4 mm²)
— solid or stranded 2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²), max. 2x (0,75 ... 4 mm²)
— finely stranded with core end processing 2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
● at AWG cables for auxiliary contacts 2x (20 ... 16), 2x (18 ... 14), 1x 12
AWG number as coded connectable conductor cross
section
● for auxiliary contacts 18 ... 14
Safety related data
product function
● mirror contact according to IEC 60947-4-1 Yes
● positively driven operation according to IEC 60947- No
5-1
B10 value with high demand rate according to SN 31920 1 000 000
T1 value for proof test interval or service life according to 20 a
IEC 61508
protection class IP on the front according to IEC IP00; IP20 with box terminal/cover
60529
touch protection on the front according to IEC 60529 finger-safe, for vertical contact from the front with box terminal/cover
suitability for use
● safety-related switching OFF Yes
Certificates/ approvals
General Product Approval

Confirmation KC

Functional
EMC Safety/Safety of Declaration of Conformity Test Certificates
Machinery

Type Examination Type Test Certific- Special Test Certific-


Certificate ates/Test Report ate

Test Certificates Marine / Shipping

Miscellaneous

other Railway

3RT10646AF36 Subject to change without notice


2/20/2023
Page 6/8 © Copyright Siemens
Miscellaneous Confirmation Miscellaneous Confirmation Vibration and Shock Special Test Certific-
ate

Environment

Environmental Con-
firmations

Further information
Information on the packaging
https://support.industry.siemens.com/cs/ww/en/view/109813875
Information- and Downloadcenter (Catalogs, Brochures,…)
https://www.siemens.com/ic10
Industry Mall (Online ordering system)
https://mall.industry.siemens.com/mall/en/en/Catalog/product?mlfb=3RT1064-6AF36
Cax online generator
http://support.automation.siemens.com/WW/CAXorder/default.aspx?lang=en&mlfb=3RT1064-6AF36
Service&Support (Manuals, Certificates, Characteristics, FAQs,...)
https://support.industry.siemens.com/cs/ww/en/ps/3RT1064-6AF36
Image database (product images, 2D dimension drawings, 3D models, device circuit diagrams, EPLAN macros, ...)
http://www.automation.siemens.com/bilddb/cax_de.aspx?mlfb=3RT1064-6AF36&lang=en
Characteristic: Tripping characteristics, I²t, Let-through current
https://support.industry.siemens.com/cs/ww/en/ps/3RT1064-6AF36/char
Further characteristics (e.g. electrical endurance, switching frequency)
http://www.automation.siemens.com/bilddb/index.aspx?view=Search&mlfb=3RT1064-6AF36&objecttype=14&gridview=view1

3RT10646AF36 Subject to change without notice


2/20/2023
Page 7/8 © Copyright Siemens
1/L1

3/L2

5/L3
A1

13

21

31

43
-Q

U
A2

2/T1

4/T2

6/T3

14

22

32

44
last modified: 2/10/2023

3RT10646AF36 Subject to change without notice


2/20/2023
Page 8/8 © Copyright Siemens