P R I N T - C O N T E N T S
7SJ602 V3.6
Created by:
Date of creation:13.05.24 10:49:28
Last modified:13.05.24 10:49:37
Comment:
Settings Settings group A
LSC
Folder / Folder
7SJ602 V3.6
7SJ6025***201FA0 V03.6x
Settings Settings group A
1100 POWER SYSTEM DATA
1101 Rated Frequency Line Freq of 50 Hz
1105 Rated primary current 300 A
1106 Secondary rated current 5A
1110 Neutral CT ratio over Phase CT ratio 1.000
1116 Threshold circuit breaker closed 0.10 I/In
1118 Nominal current of motor in relation to Tr.C. 1.0
1121 Reset thermal image on startup YES
1134 Minimum trip command duration 0.15 s
1135 Maximum close command duration 1.00 s
1136 Intervalltime for average measurements 15 MIN
1137 Cycle for automatic drag indicator reset 1 D
1138 Start of automatic drag indicator reset 1 D
1139 Minute of day for autom. drag indicator reset 1 min
1300 PHASE OVERCURRENT PROTECTION
1301 50HS/50/51 - Non-dir phase inst/time O/C prot. ON
1303 Pick-up value of the high-set inst. stage I>>> +* I/In
1305 50HS - Phase high-set inst. O/C pickup +* I/In
1307 50HS - Phase high-set inst. O/C time delay 0.03 s
1308 50 - Phase instantaneous O/C pickup 7.2 I/In
1310 50 - Phase instantaneous O/C time delay 0.02 s
1311 Measurement repetition NO
1312 51 - Phase time O/C characteristic Extremely Inverse
1313 51 - Inv. time overcurrent time dial 2.00 s
1316 51 - Phase time O/C pickup 0.8 I/In
1318 51 - Phase time O/C freq. response Without Harmonics
1319 Manual close mode 50HS IOC w/o Delay
1320 Drop-out for phase Instantaneous
1400 GROUND OVERCURRENT PROTECTION
1401 50NHS/50N/51N- Non-dir gnd inst/time O/C prot. ON
1402 50NHS - Ground high-set inst. O/C pickup +* I/In
1404 50NHS - Ground high-set inst. O/C time delay 0.10 s
1405 50N - Ground instantaneous O/C pickup 0.90 I/In
1407 50N - Ground instantaneous O/C time delay 0.02 s
1408 Measurement repetition for ground NO
1409 51N - Ground time O/C characteristic Normal Inverse
1410 51N - Ground TOC time dial 0.10 s
1413 51N - Ground time O/C pickup 0.05 I/In
1415 51N - Ground time O/C freq. response Without Harmonics
1416 Manual close mode 50NHS IOC w/o Delay
1418 Drop-out for earth current Instantaneous
2900 MEASURED VALUE SUPERVISION
2901 Summation threshold for current monitoring 0.10 I/In
2902 Factor for current summation monitoring 0.10
3800 TIME DELAY BETW ALARM RECOGNITION AND LOG
3801 Time delay for first user defined alarm 0.01 s
3802 Time delay for second user defined alarm 0.01 s
3803 Time delay for third user defined alarm 0.01 s
3804 Time delay for fourth user defined alarm 0.01 s
3900 TRIP CIRCUIT SUPERVISION
3901 Trip circuit supervision ON